This document contains calculations for voltage drop and cable sizing for multiple underground cable runs connecting electrical panels to lighting poles. It determines the required cable sizes and verifies that voltage drops and cable ampacities are within acceptable limits. Cable runs of 16mm and 35mm cables are analyzed, with corrections applied for burial depth, temperature, grouping, and soil conditions. Voltage drops are found to be under 5% in all cases.
This document contains calculations for voltage drop and cable sizing for multiple underground cable runs connecting electrical panels to lighting poles. It determines the required cable sizes and verifies that voltage drops and cable ampacities are within acceptable limits. Cable runs of 16mm and 35mm cables are analyzed, with corrections applied for burial depth, temperature, grouping, and soil conditions. Voltage drops are found to be under 5% in all cases.
This document contains calculations for voltage drop and cable sizing for multiple underground cable runs connecting electrical panels to lighting poles. It determines the required cable sizes and verifies that voltage drops and cable ampacities are within acceptable limits. Cable runs of 16mm and 35mm cables are analyzed, with corrections applied for burial depth, temperature, grouping, and soil conditions. Voltage drops are found to be under 5% in all cases.
Calculation Sheet EXPAND SHAIBAH ABQAIQ P/L CAPACITY-1000MBC PMT AND CAT PROPOSED ACCOMODATION KM. 431 Cable Sizing & VDC TO AREA LIGHTING ( 7 LIGHTING POLES) Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DLF ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 16 mm! Ampacity = 98 Amperes 1 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 98 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 16 mm! Cable Selected : 1 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 69 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 1 Z = ( 1.47 x 0.85 ) + ( 0.1060 x sinarccos( 0.85 )) = ohms / KM Ze = (1.305 x 210) / (1 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. CABLE PC-0001 ELEC. PANELBOARD PMT GUARDHOUSE (DP-02B) 3.50 0.98 0.78 69.03 0.85 210 688.80 1.4700 0.1060 1.3050 0.2740 Calculation Sheet 4.36 11.02 0.97 0.95 220 9.19 5.00 1.98 215.64 1.982 Cable Sizing & VDC Calculation Sheet TO AREA LIGHTING ( 9 LIGHTING POLES) Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DLF ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 35 mm! Ampacity = 158 Amperes 1 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 158 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 35 mm! Cable Selected : 1 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 111 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 1 Z = ( 0.6690 x 0.85 ) + ( 0.0980 x sinarccos( 0.85 )) = ohms / KM Ze = (0.6203 x 325) / (1 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 20.99 CABLE PC-0002 ELEC. PANELBOARD PMT GUARDHOUSE (DP-02B) 8.00 220 0.78 3.332 0.6203 11.29 0.85 325 1066.00 0.6690 25.19 0.97 0.95 0.98 0.2016 7.33 5.00 3.33 212.67 0.0980 Cable Sizing & VDC Calculation Sheet TO AREA LIGHTING ( 7 LIGHTING POLES) Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DLF ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 16 mm! Ampacity = 98 Amperes 1 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 98 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 16 mm! Cable Selected : 1 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 69 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 1 Z = ( 0.1.4700 x 0.85 ) + ( 0.1060 x sinarccos( 0.85 )) = ohms / KM Ze = (1.3050 x 200) / (1 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. CABLE PC-0003A ELEC. PANELBOARD PMT GUARDHOUSE (DP-02B) 0.97 220 9.19 1.887 215.85 11.02 0.98 0.78 69.03 1.3050 0.2610 4.15 5.00 1.89 0.85 200 656.00 1.4700 0.1060 0.95 3.50 Cable Sizing & VDC Calculation Sheet TO AREA LIGHTING ( 6 LIGHTING POLES) Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DLF ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 16 mm! Ampacity = 98 Amperes 1 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 98 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 16 mm! Cable Selected : 1 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 69 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 1 Z = ( 1.4700 x 0.85 ) + ( 0.1060 x sinarccos( 0.85 )) = ohms / KM Ze = (1.3050 x 220) / (1 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. CABLE PC-0003B ELEC. PANELBOARD PMT GUARDHOUSE (DP-02B) 3.00 220 7.87 9.45 0.97 0.95 0.98 0.78 69.03 0.85 220 721.60 1.4700 0.1060 1.3050 0.2871 3.91 5.00 1.78 216.09 1.778 Cable Sizing & VDC Calculation Sheet TO AREA LIGHTING ( 6 LIGHTING POLES) Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 16 mm! Ampacity = 98 Amperes 1 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 98 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 16 mm! Cable Selected : 1 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 69 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 1 Z = ( 1.4700 x 0.85 ) + ( 0.1060 x sinarccos( 0.85 )) = ohms / KM Ze = (1.305 x 151) / (1 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 1.425 495.28 1.4700 0.1060 1.3050 151 0.1971 3.13 5.00 1.43 216.87 0.97 0.85 3.50 220 9.19 11.02 ELECTRICAL PANELBOARD CAT GUARDHOUSE 0.98 0.78 69.03 CABLE PC-0004 0.95 Cable Sizing & VDC Calculation Sheet TO AREA LIGHTING ( 5 LIGHTING POLES) Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 16 mm! Ampacity = 98 Amperes 1 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 98 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 16 mm! Cable Selected : 1 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 69 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 1 Z = ( 1.4700 x 0.85 ) + ( 0.1060 x sinarccos( 0.85 )) = ohms / KM Ze = (1.305 x 250) / (1 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 220 6.56 7.87 0.97 0.95 CABLE PC-0005 ELECTRICAL PANELBOARD CAT GUARDHOUSE 2.50 5.00 1.69 216.29 1.685 1.4700 0.1060 3.71 1.3050 0.3262 0.98 0.78 69.03 0.85 250 820.21 Cable Sizing & VDC Calculation Sheet TO AREA LIGHTING ( 6 LIGHTING POLES) Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 16 mm! Ampacity = 98 Amperes 1 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 98 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 16 mm! Cable Selected : 1 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 69 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 1 Z = ( 1.4700 x 0.85 ) + ( 0.1060 x sinarccos( 0.85 )) = ohms / KM Ze = (1.3050 x 250) / (1 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 0.95 5.00 1.69 216.29 1.685 1.4700 0.1060 1.3050 0.3263 3.71 CABLE PC-0006 ELECTRICAL PANELBOARD CAT GUARDHOUSE 3.00 0.98 0.78 69.03 0.85 250 820.21 220 7.87 9.45 0.97 Cable Sizing & VDC Calculation Sheet TO JOCKEY PUMP MOTOR Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 16 mm! Ampacity = 98 Amperes 1 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 98 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 16 mm! Cable Selected : 1 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 69 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 1 Z = ( 1.47 x 0.85 ) + ( 0.1068 x sinarccos( 0.85 )) = ohms / KM Ze = (1.3058 x 50) / (1 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 2.23 215.10 2.226 0.1068 1.3058 0.0653 4.90 5.00 0.85 50 164.00 1.4700 51.96 0.97 0.95 0.98 0.78 16.50 220 43.30 69.03 CABLE PC-0007 MAIN ELECTRICAL PANELBOARD (MDP-3) Cable Sizing & VDC Calculation Sheet TO MAIN BUSBAR PANEL (MBP-01) Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 250 mm! Ampacity = 1808 Amperes 4 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 1808 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 250 mm! Cable Selected : 4 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 1274 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 4 Z = ( 0.0967 x 0.85 ) + ( 0.0900 x sinarccos( 0.85 )) = ohms / KM Ze = (0.1296 x 10) / (4 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 0.18 219.60 0.181 0.0900 0.1296 0.0003 0.40 5.00 1273.55 0.85 10 32.80 0.0967 850.30 0.97 0.95 0.98 0.78 270.00 220 708.59 CABLE PC-0008 GENERATOR (G-1) (RUNNING) Cable Sizing & VDC Calculation Sheet TO MAIN BUSBAR PANEL (MBP-01) Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 250 mm! Ampacity = 1808 Amperes 4 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 1808 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 250 mm! Cable Selected : 4 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 1274 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 4 Z = ( 0.0967 x 0.85 ) + ( 0.0900 x sinarccos( 0.85 )) = ohms / KM Ze = (0.1296 x 10) / (4 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 270.00 220 708.59 850.30 0.97 0.95 0.98 0.78 1273.55 CABLE PC-0009 GENERATOR (G-2) (STAND-BY) 0.85 10 32.80 0.0967 0.0900 0.1296 0.0003 0.40 5.00 0.18 219.60 0.181 Cable Sizing & VDC Calculation Sheet TO MAIN DISTRIBUTION PANEL (MDP-1) Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 250 mm! Ampacity = 1808 Amperes 4 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 1808 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 250 mm! Cable Selected : 4 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 1274 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 4 Z = ( 0.0967 x 0.85 ) + ( 0.0900 x sinarccos( 0.85 )) = ohms / KM Ze = (0.1296 x 10) / (4 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. CABLE PC-0010 MAIN BUSBAR PANEL (MBP-01) 270.00 220 708.59 850.30 0.97 0.95 0.98 0.78 1273.55 0.85 10 32.80 0.0967 0.0900 0.1296 0.0003 0.40 5.00 0.18 219.60 0.181 Cable Sizing & VDC Calculation Sheet TO PANELBOARD INSIDE THE SAPMT BLDG. (PB-1) Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 70 mm! Ampacity = 229 Amperes 1 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 229 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 70 mm! Cable Selected : 1 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 161 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 1 Z = ( 0.3430 x 0.85 ) + ( 0.0950 x sinarccos( 0.85 )) = ohms / KM Ze = (0.1345 x 171 / (1 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 0.78 1.20 217.36 1.200 0.0950 0.1307 0.0224 2.64 5.00 26.00 220 68.23 CABLE PC-0011A MAIN DISTRIBUTION PANEL (MDP-1) 161.31 0.85 171 560.88 0.3430 81.88 0.97 0.95 0.98 Cable Sizing & VDC Calculation Sheet TO BUSBAR OUTSIDE THE SAPMT BLDG. (BP-01) Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 250 mm! Ampacity = 632 Amperes 2 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 632 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 250 mm! Cable Selected : 2 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 445 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 2 Z = ( 0.1908 x 0.85 ) + ( 0.0910 x sinarccos( 0.85 )) = ohms / KM Ze = (0.2101 x 171) / (2 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 445.18 0.85 171 560.88 0.1908 0.0910 0.2101 0.0180 5.67 5.00 2.58 214.33 2.579 CABLE PC-0011B MAIN DISTRIBUTION PANEL (MDP-1) 69.51 220 182.42 218.91 0.97 0.95 0.98 0.78 Cable Sizing & VDC Calculation Sheet TO PANELBOARD INSIDE THE SAPMT BLDG. (PB-3) Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 70 mm! Ampacity = 229 Amperes 1 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 229 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 70 mm! Cable Selected : 1 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 161 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 1 Z = ( 0.3430 x 0.85 ) + ( 0.0950 x sinarccos( 0.85 )) = ohms / KM Ze = 0.1307 x 180) / (1 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 5.00 1.08 217.63 1.079 161.31 0.85 180 590.55 0.3430 0.0950 0.1307 0.0235 2.37 CABLE PC-0011C MAIN DISTRIBUTION PANEL (MDP-1) 22.20 220 58.26 69.91 0.97 0.95 0.98 0.78 Cable Sizing & VDC Calculation Sheet TO BUSBAR OUTSIDE THE SAPMT BLDG. (BP-02) Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 95 mm! Ampacity = 548 Amperes 2 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 548 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 95 mm! Cable Selected : 2 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 386 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 2 Z = ( 0.2480 x 0.85 ) + ( 0.0930 x sinarccos( 0.85 )) = ohms / KM Ze = (0.2597x 180) / (2 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 182.66 0.97 0.95 0.98 0.78 386.01 0.85 180 590.55 0.2480 0.0930 0.2597 0.0234 6.16 5.00 2.80 213.84 2.800 CABLE PC-0011D MAIN DISTRIBUTION PANEL (MDP-1) 58.00 220 152.22 Cable Sizing & VDC Calculation Sheet TO PANELBOARD OUTSIDE (DP-01A) THE SAPMT VIP ACCOM. Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 185 mm! Ampacity = 774 Amperes 2 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 774 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 185 mm! Cable Selected : 2 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 545 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 2 Z = ( 0.1290 x 0.85 ) + ( 0.0910 x sinarccos( 0.85 )) = ohms / KM Ze = (0.1576 x 152) / (2 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 2.67 214.12 2.672 0.0910 0.1576 0.0120 5.88 5.00 545.20 0.85 152 498.56 0.1290 340.12 0.97 0.95 0.98 0.78 108.00 220 283.44 CABLE PC-0012 MAIN DISTRIBUTION PANEL (MDP-1) Cable Sizing & VDC Calculation Sheet TO PANELBOARD INSIDE THE SAPMT MOSQUE Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 16 mm! Ampacity = 98 Amperes 1 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 98 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 16 mm! Cable Selected : 1 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 69 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 1 Z = ( 1.4700 x 0.85 ) + ( 0.10607 x sinarccos( 0.85 )) = ohms / KM Ze = (1.3050 x 174) / (1 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 3.05 213.30 3.049 0.1060 1.3050 0.2770 6.71 5.00 69.03 0.85 174 570.72 1.4700 20.47 0.97 0.95 0.98 0.78 6.50 220 17.06 CABLE PC-0013 MAIN DISTRIBUTION PANEL (MDP-1) Cable Sizing & VDC Calculation Sheet TO MAIN DISTRIBUTION PANEL (MDP-2) Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 250 mm! Ampacity = 1808 Amperes 4 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 1808 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 250 mm! Cable Selected : 4 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 1274 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 4 Z = ( 0.0967 x 0.85 ) + ( 0.0900 x sinarccos( 0.85 )) = ohms / KM Ze = (0.1296 x 10) / (4 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 0.18 219.60 0.181 0.85 10 32.80 0.0967 0.0900 0.1296 0.0003 0.40 5.00 270.00 220 708.59 850.30 0.97 0.95 0.98 0.78 1273.55 CABLE PC-0016 MAIN BUSBAR PANEL (MBP-01) Cable Sizing & VDC Calculation Sheet TO PANELBOARD OUTSIDE (DP-02A) SAPMT SENIOR ACCOM Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 185 mm! Ampacity = 774 Amperes 2 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 774 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 185 mm! Cable Selected : 2 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 545 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 2 Z = ( 0.1290 x 0.85 ) + ( 0.0910 x sinarccos( 0.85 )) = ohms / KM Ze = (0.1576 x 80) / (2 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 130.00 220 341.17 545.20 0.85 80 262.40 0.1290 409.41 0.97 0.95 0.98 0.78 CABLE PC-0017 ELECTRICAL PANELBOARD ( MDP-2) 1.69 216.28 1.693 0.0910 0.1576 0.0063 3.72 5.00 Cable Sizing & VDC Calculation Sheet TO PANELBOARD INSIDE THE SAPMT RECREATION BLDG. Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 120 mm! Ampacity = 310 Amperes 1 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 310 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 120 mm! Cable Selected : 1 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 218 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 1 Z = ( 0.1970 x 0.85 ) + ( 0.0910 x sinarccos( 0.85 )) = ohms / KM Ze = (0.2153 x 116) / (1 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 215.46 2.064 0.0910 0.2153 0.0249 4.54 5.00 116 380.48 0.1970 125.97 0.97 0.95 0.98 0.78 2.06 40.00 220 104.98 CABLE PC-0018A ELECTRICAL PANELBOARD ( MDP-2) 218.36 0.85 Cable Sizing & VDC Calculation Sheet TO PANELBOARD INSIDE THE SAPMT RECREATION BLDG. Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 70 mm! Ampacity = 229 Amperes 1 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 229 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 70 mm! Cable Selected : 1 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 161 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 1 Z = ( 0.3430 x 0.85 ) + ( 0.0950 x sinarccos( 0.85 )) = ohms / KM Ze = (0.1307 x 116) / (1 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 0.0950 0.1307 0.0152 2.26 5.00 1.03 217.74 1.028 CABLE PC-0018B ELECTRICAL PANELBOARD ( MDP-2) 32.80 220 86.08 103.30 0.97 0.95 0.98 0.78 161.31 0.85 116 380.48 0.3430 Cable Sizing & VDC Calculation Sheet TO BUSBAR OUTSIDE THE SAPMT CAFETERIA (BP-03) Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 185 mm! Ampacity = 387 Amperes 1 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 387 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 185 mm! Cable Selected : 1 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 273 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 1 Z = ( 0.1290 x 0.85 ) + ( 0.0910 x sinarccos( 0.85 )) = ohms / KM Ze = (0.1575 x 99) / (1 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 223.60 0.97 0.95 0.98 0.78 71.00 220 186.33 2.29 214.97 2.288 0.0910 0.1575 0.0156 5.04 5.00 272.60 0.85 99 324.72 0.1290 CABLE PC-0019A ELECTRICAL PANELBOARD ( MDP-2) Cable Sizing & VDC Calculation Sheet TO PANELBOARD INSIDE THE SAPMT CAFETERIA Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 95 mm! Ampacity = 274 Amperes 1 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 274 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 95 mm! Cable Selected : 1 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 193 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 1 Z = ( 0.2480 x 0.85 ) + ( 0.0930 x sinarccos( 0.85 )) = ohms / KM Ze = (0.2597 x 99) / (1 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. CABLE PC-0019B ELECTRICAL PANELBOARD (M DP-2) 42.00 220 110.23 132.27 0.97 0.95 0.98 0.78 193.00 0.85 99 324.72 0.2480 0.0930 0.2597 0.0257 4.91 5.00 2.23 215.09 2.231 Cable Sizing & VDC Calculation Sheet TO DP INSIDE THE SAPMT GUARDHOUSE BLDG (DP-02B) Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 125 mm! Ampacity = 316 Amperes 1 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 316 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 125 mm! Cable Selected : 1 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 223 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 1 Z = ( 0.1908 x 0.85 ) + ( 0.0910 x sinarccos( 0.85 )) = ohms / KM Ze = (0.2101 x 236) / (1 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 3.07 213.24 3.073 0.0910 0.2101 0.0496 6.76 5.00 222.59 0.85 236 774.08 0.1908 94.48 0.97 0.95 0.98 0.78 30.00 220 78.73 CABLE PC-0020 ELECTRICAL PANELBOARD ( MDP-2) Cable Sizing & VDC Calculation Sheet TO PANELBOARD INSIDE THE SAPMT CLINIC Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 16 mm! Ampacity = 98 Amperes 1 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 98 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 16 mm! Cable Selected : 1 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 69 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 1 Z = ( 1.4700 x 0.85 ) + ( 0.1060 x sinarccos( 0.85 )) = ohms / KM Ze = (1.305 x 60) / (1 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 1.46 216.80 1.456 0.1060 1.3050 0.0783 3.20 5.00 69.03 0.85 60 196.80 1.4700 28.34 0.97 0.95 0.98 0.78 9.00 220 23.62 CABLE PC-0021 PANELBOARD INSIDE SAMPT GUARDHOUSE (DP-02B) Cable Sizing & VDC Calculation Sheet TO AREA LIGHTING ( 8 LIGHTING POLES) Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 35 mm! Ampacity = 158 Amperes 1 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 158 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 35 mm! Cable Selected : 1 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 111 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 1 Z = ( 0.6690 x 0.85 ) + ( 0.0980 x sinarccos( 0.85 )) = ohms / KM Ze = (0.6203 x 365) / (1 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 0.0980 0.6203 0.2264 8.23 5.00 111.29 0.85 365 895.44 0.6690 3.74 211.77 3.741 PANELBOARD INSIDE PMT GUARDHOUSE (DP-02B) 25.19 0.97 0.95 0.98 0.78 8.00 220 20.99 CABLE PC-0024 Cable Sizing & VDC Calculation Sheet TO VIP ROOMS (8 BARRACKS) Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 25 mm! Ampacity = 128 Amperes 1 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 128 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 25 mm! Cable Selected : 1 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 90 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 1 Z = ( 0.9270 x 0.85 ) + ( 0.1030 x sinarccos( 0.85 )) = ohms / KM Ze = (0.8422 x 60) / (1 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 1.36 217.02 1.357 0.1030 0.8422 0.0505 2.99 5.00 CABLE PC-0025 ELEC. PANELBOARD DP-01A 13.00 220 34.12 90.16 0.85 60 196.80 0.9270 40.94 0.97 0.95 0.98 0.78 Cable Sizing & VDC Calculation Sheet TO SENIOR ROOMS (8 BARRACKS) Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 25 mm! Ampacity = 128 Amperes 1 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 128 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 25 mm! Cable Selected : 1 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 90 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 1 Z = ( 0.9270 x 0.85 ) + ( 0.1030 x sinarccos( 0.85 )) = ohms / KM Ze = (0.8422 x 55) / (5 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 1.53 216.63 1.530 0.1030 0.8422 0.0463 3.37 5.00 90.16 0.85 55 180.40 0.9270 50.39 0.97 0.95 0.98 0.78 41.99 CABLE PC-0026 ELEC. PANELBOARD (DP-02A) 16.00 220 Cable Sizing & VDC Calculation Sheet TO PANELBOARD INSIDE PMT OFFICE (PB-2) Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 150 mm! Ampacity = 346 Amperes 1 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 346 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 150 mm! Cable Selected : 1 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 244 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 1 Z = ( 0.1600 x 0.85 ) + ( 0.0910 x sinarccos( 0.85 )) = ohms / KM Ze = (0.1839 x 50) / (1 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 1.32 217.09 1.321 0.0910 0.1839 0.0092 2.91 5.00 243.72 0.85 50 164.00 0.1600 218.91 0.97 0.95 0.98 0.78 69.51 220 182.42 CABLE PC-0027 BUSBAR PANEL OUTSIDE PMT OFFICE (BP-01) Cable Sizing & VDC Calculation Sheet TO PANELBOARD INSIDE PMT OFFICE (PB-4) Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 120 mm! Ampacity = 310 Amperes 1 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 310 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 120 mm! Cable Selected : 1 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 218 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 1 Z = ( 0.1970 x 0.85 ) + ( 0.0910 x sinarccos( 0.85 )) = ohms / KM Ze = (0.2154 x 30) / (1 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 0.77 218.30 0.774 0.0910 0.2154 0.0064 1.70 5.00 218.36 0.85 30 98.40 0.1970 182.66 0.97 0.95 0.98 0.78 58.00 220 152.22 CABLE PC-0028 BUSBAR PANEL OUTSIDE PMT OFFICE (BP-02) Cable Sizing & VDC Calculation Sheet TO PANELBOARD INSIDE PMT MESS (PB-1) Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 150 mm! Ampacity = 346 Amperes 1 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 346 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 150 mm! Cable Selected : 1 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 244 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 1 Z = ( 0.1600 x 0.85 ) + ( 0.0910 x sinarccos( 0.85 )) = ohms / KM Ze = (0.1839 x 30) / (1 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 0.97 0.95 0.98 0.78 243.72 0.85 30 98.40 0.1600 0.0910 0.1839 0.0055 1.78 5.00 0.81 218.22 0.809 CABLE PC-0029 BUSBAR PANEL OUTSIDE PMT MESS (BP-03) 71.00 220 186.33 223.60 Cable Sizing & VDC Calculation Sheet TO Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 150% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 150 mm! Ampacity = 692 Amperes 2 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 692 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 150 mm! Cable Selected : 2 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 487 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 2 Z = ( 0.16 x 0.85 ) + ( 0.0957 x sinarccos( 0.85 )) = ohms / KM Ze = (0.1864 x 50) / (2 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 459.26 0.97 0.95 0.98 0.78 FIRE WATER PUMP 70.00 220 183.70 CABLE PC-0031 ELECTRICAL PANELBOARD ( MDP-3) 0.67 218.52 0.674 0.0957 0.1864 0.0047 1.48 5.00 487.44 0.85 50 164.00 0.1600 Cable Sizing & VDC Calculation Sheet TO ELECTRICAL PANELBOARD ( MDP-3) Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 95 mm! Ampacity = 822 Amperes 3 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 822 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 95 mm! Cable Selected : 3 -SET, 4 /C - XLPE/SWA/PVC Derated Ampacity : 579 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 3 Z = ( 0.2480 x 0.85 ) + ( 0.0930 x sinarccos( 0.85 )) = ohms / KM Ze = ( .25980 x 10) / (3 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 220 CABLE PC-0034 MAIN BUSBAR PANEL (MBP-01) 80.00 0.85 0.0009 0.31 5.00 0.14 219.69 0.143 209.95 251.94 0.2598 0.97 0.95 0.98 0.78 579.01 10 32.80 0.2480 0.0930 Cable Sizing & VDC Calculation Sheet TO ELEC. PANELBOARD INSIDE CAT GUARDHOUSE Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 70 mm! Ampacity = 229 Amperes 1 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 229 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 70 mm! Cable Selected : 1 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 161 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 1 Z = ( 0.343 x 0.85 ) + ( 0.0988 x sinarccos( 0.85 )) = ohms / KM Ze = (0.3436 x 181) / (1 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 214.35 2.570 CABLE PC-0035 ELECTRICAL PANELBOARD ( MDP-3) 20.00 220 52.49 62.98 0.97 0.95 0.98 0.78 161.31 0.85 181 593.68 0.3430 0.0988 0.3436 0.0622 5.65 5.00 2.57 Cable Sizing & VDC Calculation Sheet TO ELEC. PANELBOARD OUTSIDE CAT OFFICE (DP-03A) Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 35 mm! Ampacity = 316 Amperes 2 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 316 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 35 mm! Cable Selected : 2 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 223 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 2 Z = ( 0.6690 x 0.85 ) + ( 0.0980 x sinarccos( 0.85 )) = ohms / KM Ze = (0.6203 x 150) / (2 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. CABLE PC-0036 ELECTRICAL PANELBOARD ( MDP-3) 50.00 220 131.22 157.46 0.97 0.95 0.98 0.78 222.59 0.85 150 557.74 0.6690 0.0980 0.6203 0.0465 10.57 5.00 4.80 209.43 4.806 Cable Sizing & VDC Calculation Sheet TO WATER PUMP Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 4 mm! Ampacity = 46 Amperes 1 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 46 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 4 mm! Cable Selected : 1 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 32.4 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 1 Z = ( 5.88 x 0.85 ) + ( 0.1237 x sinarccos( 0.85 )) = ohms / KM Ze = (5.0632 x 50) / (1 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 2.288 CABLE PC-0038 ELECTRICAL PANELBOARD ( MDP-3) 4.38 220 11.48 13.78 0.97 0.95 0.98 0.78 32.40 0.85 50 164.00 5.8800 0.1237 5.0632 0.2532 5.03 5.00 2.29 214.97 Cable Sizing & VDC Calculation Sheet TO DIESEL TANK LIGHTING Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 4 mm! Ampacity = 46 Amperes 1 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 46 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 4 mm! Cable Selected : 1 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 32.4 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 1 Z = ( 5.88 x 0.85 ) + ( 0.1237 x sinarccos( 0.85 )) = ohms / KM Ze = (5.0632 x 50) / (1 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 0.97 0.95 0.98 0.78 32.40 0.85 50 164.00 5.8800 0.1237 5.0632 0.2532 2.30 5.00 1.05 217.70 1.046 CABLE PC-0039 ELECTRICAL PANELBOARD ( MDP-3) 2.00 220 5.25 6.30 Cable Sizing & VDC Calculation Sheet TO SEWAGE EJECTION PUMP Total Load kVA = kVA Line Voltage (nominal) = volts phase = ! Maximum Load Current (Ia) = (Load kVA x 1000) / ( 1.732 x V ) = amps CABLE SIZING : (SAES-P-104, 12.1) Assumption Load Current (I DL ) = Ia x 120% = amps
AMPACITY DERATING : Select a Cable Size for the requirement = 35 mm! Ampacity = 158 Amperes 1 Set/s of Cable 4 Core/s Cable Min. capacity of new cable (Id) = CAB. Ampacity x ( Correction Factor ) where : Correction Factor for Thermal resist. of soil @ 1.2 o C-m/W = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.3) Correction Factor for ground temperature @ 40 o C = (Saudi cable cat. for direct laid in ground) (SAES-P-104, 12.2) Correction Factor for depth of burial @ 0.60 in ground = (Saudi cable cat. for direct laid in ground) (Cable Grouping Factor) Correction Factor for grouping @ 0.15mtr. Flat formation = (Saudi cable cat. for direct laid in ground) Id = 158 x (0.97 x 0.95 x 0.98 x 0.78) = Amps CABLE SIZE CONCLUSION : Cable Size : 35 mm! Cable Selected : 1 -SET, 4 /C - XLPE/SWA/PVC Cable Ampacity : 111 amps therefore, cable derated ampacity is ok. VOLTAGE DROP : Z = (R x pf) + X x sin[arccos(pf)] (NEC Chapter 9, Table 9, Note 2) Ze = (Z x L) / (n x 1000) where : Z = Impedance pf = Power Factor = L = Cable Length = meters or feet R = Resistance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = Reactance = ohms-neutral/KM (Saudi cable catalogue AC at 90C) X = X L , since X C is negligible below 600V (NEC Table 9, 75C (167C)) n = no. of set/s of multi-core cables or ( for single core, n=1 ) = 1 Z = ( 0.669 x 0.85 ) + ( 0.1041 x sinarccos( 0.85 )) = ohms / KM Ze = (0.6235 x 50) / (1 x 1000) = ohms Voltage Drop (VD) = (Ia x Ze) x m = volts ( m = 1.732 for 3-Phase & m = 2 for Single Phase) %VD Required (SAES-P-100) = % %VD = VD/VL x 100% = % Voltage Reading at Junction = volts TOTAL % VOLTAGE DROP = % Therefore, voltage drop ok. 2.126 0.0312 4.68 5.00 2.13 215.32 164.00 0.6690 0.1041 0.6235 CABLE PC-0040 ELECTRICAL PANELBOARD ( MDP-3) 33.00 220 50 111.29 0.85 86.60 103.92 0.97 0.95 0.98 0.78