BlueIooIh CommunicaIion FuncIion (KEW4202 only)
RemoIe checkin of measuremenIs is possible wiIhouI accessin KEW4202
uniI by connecIin KEW4202 and Android devices via BlueIooIh.
4
3. Specification
OperaIin sysIem EarIh resisIance funcIion: ConsIanI volIae in|ecIion,
CurrenI deIecIion,
(Frequency: Approx.2400Hz)
Dual lnIeraIion
AC currenI funcIion:Successive ApproximaIion(True-RMS)
Display Liquid crysIal display wiIh a maximum counI of 2099
Over-rane indicaIion 'OL' is displayed when inpuI exceeds Ihe upper limiI
of Ihe measurin rane
Response Iime EarIh resisIance funcIion :Approx. 7 seconds
AC currenI funcIion :Approx. 2 seconds
Sample raIe Approx. once per second
LocaIion for use AlIiIude 2000m or less, lndoor/ ouIdoor use
lP proIecIion deree lP40
TemperaIure & humidiIy rane 28T6T/RelaIive humidiIy 86% or less
(uaranIeed accuracy) no condensaIion)
OperaIin IemperaIure & -10T Io 40T/RelaIive humidiIy 86% or less
humidiIy rane (no condensaIion)
SIorae IemperaIure & -20T Io 60T/RelaIive humidiIy 86% or less
humidiIy rane wiIhouI baIIeries, no condensaIion)
Power source DC6V: R6P (size AA mananese baIIery) x 4pcs, or
LR6 (size AA alkaline baIIery) x 4pcs
CurrenI consumpIion MODEL4200 : Approx. 60mA (max. 100mA)
KEW4202 : Approx. 90mA (max. 140mA)
MeasuremenI Iime MODEL4200 : Approx. 12 hours (when usin R6P), or
24 hours (when usin LR6)
KEW4202 : Approx. 6 hours (when usin R6P), or
21 hours (when usin LR6)
Measurin rane and accuracy
FuncIion Rane ResoluIion Measurin rane Accuracy
EarIh resisIance
(AuIo-ranin)
20O 0.01O 0.00 - 20.00O 1%6dI
200O 0.1O 20.0 200.0O 8%6dI
600O 1O
200 - 899O 6%6dI
400 - 699O 10%10dI
1200O 10O 600 - 1260O -
AC currenI (ACA)
(60Hz/60Hz)
(AuIo-ranin)
100mA 0.1mA 0.0 - 100.0mA
2%6dI
(sine wave)
1000mA 1mA 100 - 1000mA
10A 0.01A 1.00 - 10.00A
80A 0.1A 10.0 - 80.0A
* CresI facIor 2.6 Accuracy aI sine wave +1% (60Hz/60Hz, peak value shall noI exceed 60A)
* ln Ihe followin cases, zero will be displayed on Ihe LCD.
- AI 20O rane of EarIh resisIance funcIion: 0.04O or less
- AI 100mA rane of ACA funcIion: 0.4mA or less
* A rane shifIs Io upper rane when Ihe inpuI exceeds 106% of Ihe selecIed rane, and shifIs
Io Ihe lower rane when Ihe inpuI falls under 80% of Ihe rane.
6
AuIo power-off Turns power off abouI 10 minuIes afIer Ihe lasI
buIIon operaIion.
Applicable sIandards lEC61010-1 (CAT. lV 800V PolluIion deree2)
lEC61010-2-082
lEC61826-2-2 (EMC sIandard)
ExIernal communicaIion BlueIooIh Ver2.1+EDR Class2
meIhod
WiIhsIand volIae AC6160Vrms/ 6 seconds
BeIween Ihe Transformer |aws fiIIed parIs and Case
enclosure (excepI for |aws)
lnsulaIion resisIance 60MO or more aI 1000V
BeIween Ihe Transformer |aws fiIIed parIs and Case
enclosure (excepI for |aws)
ConducIor size Approx. 82mm in diameIer max.
Dimension 246(L) x 120(W) x 64(D)mm
WeihI Approx. 780 (includin baIIeries)
Accessories BaIIery R6P: 4pcs (MODEL4200)
LR6: 4pcs (KEW4202)
lnsIrucIion manual : 1pce
ResisIor for operaIion check : 1pce
(MODEL8804)
Hard case MODEL9166 : 1pce (MODEL4200)
MODEL9167 : 1pce (KEW4202)
<SupplemenIal remarks`
_ EffecIive value (RMS)
MosI alIernaIin currenIs and volIaes are expressed in effecIive values, which are also
referred Io as RMS (RooI-Mean-Square) values. The effecIive value is Ihe square rooI of
Ihe averae of square of alIernaIin currenI or volIae values. Many clamp meIers usin
a convenIional recIifyin circuiI have 'RMS' scales for AC measuremenI. The scales are,
however, acIually calibraIed in Ierms of Ihe effecIive value of a sine wave Ihouh Ihe clamp
meIer is respondin Io Ihe averae value. The calibraIion is done wiIh a conversion facIor of
1.111 for sine wave, which is found by dividin Ihe effecIive value by Ihe averae value.
These insIrumenIs are Iherefore in error if Ihe inpuI volIae or currenI has some oIher shape
Ihan sine wave.
_ CF (CresI FacIor) is found by dividin Ihe peak value by Ihe effecIive value.
Examples:
Sine wave: CF-1.414 Square wave wiIh a 1: 9 duIy raIio: CF-8
6
4. Instrument layout
Symbols to be displayed on the LCD
1
2
6 8
4
6
7
8
9
11
10
Name of each parts and buttons (for MODEL4200 and KEW4202)
1 Transformer jaw
2 Trigger
3 Backlight button
Switches on/off the backlight.
4 Function button
Switches ACA/ Earth resistance
functions.
5 Memory mode button
Check the measured value by
Data number.
6 Data hold button
Freezes/ rel eases the fi xed
readings.
7 Power button
Turns on/off the instrument.
8 Display unit (LCD)
9 Cursor button (UP)
Selects data number; to save
the measured value, or to view
the measured data in memory.
10 Cursor button (DOWN)
Selects data number; to save the
measured value, or to view the
measured data in memory.
11 Save button
Saves the measured value.
Displayed when savin Ihe measured value or when
insIrumenI is in memory mode.
Displayed when baIIeries are exhausIed.
Di spl ayed aI Ear I h r esi sI ance f uncI i on when
Transformer |aws are noI properly closed.
Displayed aI EarIh resisIance funcIion when currenI or
noise IhaI affecIs on Ihe measured value presenIs.
Displayed when daIa hold funcIion is acIivaIed.
Displayed when ACA funcIion is selecIed.
Displayed when insIrumenI is in conIinuiIy mode aI
EarIh resisIance funcIion.
DaIa number
1 Io 100
Measured value UniI
7
5. Measurement principle
This insIrumenI can measure Ihe earIh resisIance Io earIh in mulIi-earIhed sysIem.
LeI's reard earIh resisIance under IesI as Rx, and Ihe oIher earIh resisIances as
R1, R2, Rn.
Of Ihese earIh resisIances, R1, R2, Rn can be considered IhaI Ihey are
connecIed in parallel.
And can be rearded as a combined resisIance Rs. The Rs can be rearded small
enouh aainsI Rx since a combined resisIance consisIs of several resisIances.
Followin is an equivalenI circuiI diaram of Ihis circuiI.
8
M-4102A
By applyin Ihe VolIae (V) Io Ihe circuiI from Ihe Transformer |aw (CT1), currenI l
is (shall be flowed) flowed correspondin Io Ihe earIh resisIance. R can be puI ouI
by Ihe calculaIion afIer deIecIin Ihe currenI wiIh Ihe oIher Transformer |aw (CT2).
ln Ihis case, R displayed in Ihis insIrumenI can be rearded as Rx because Rs can
be rearded small enouh aainsI Rx.
#CAUTION
This insIrumenI is noI supporIin Ihe measuremenI for Ihe locaIions wiIh
followin earIh sysIems.
Sinle-earIh IhaI is noI connecIed Io oIher earIhs. (LihInin rod, eIc.)
EarIh on which a currenI over 2A is measured aI AC currenI funcIion of Ihis
insIrumenI.
EarIh wiIh a larer earIh resisIance Ihan an earIh resisIance of IesIin.
EarIh wiIh earIh resisIance over 1200O.
Precision measuremenI shall be performed wiIh our EarIh resisIance IesIer:
M-4102A or M-4106A for Ihe measuremenI of sinle-earIhed wire.
9
6. Getting started
(1) Check Ihe baIIery volIae
When noIhin is displayed on Ihe LCD, press Ihe power buIIon and Iurn
on Ihe insIrumenI. BaIIery volIae is enouh when indicaIion is clear and Ihe
' ' symbol is noI displayed on Ihe LCD afIer Iurnin on Ihe insIrumenI.
Follow Ihe procedure described in 9. Battery replacement`and replace Ihe
baIIeries wiIh new ones when any of followin sympIoms is noIed. OIherwise,
accuraIe measuremenI and proper savin cannoI be ensured.
* ' ' symbol is bein displayed.
* indicaIions are fainI and difficulI Io read.
* noIhin is displayed on Ihe LCD.
(2) Verify Ihe correcI measuremenI of earIh resisIance
Clamp-on Ihe supplied resisIor for operaIion check as shown below, and verify
IhaI Ihe Transformer |aw and Ihe circuiI works correcIly. When Ihe indicaIed
value is wiIhin Ihe rane described below, Ihey are operaIin correcIly. lf Ihe
indicaIed value is reaIly exceedin Ihe accuracy, send Ihe insIrumenI Io your
local KYORlTSU disIribuIor for repair or recalibraIion.
For repair, Ihe resisIor for operaIion check shall be aIIached and reIurned
IoeIher wiIh Ihe insIrumenI.
#
CAUTION
This insIrumenI performs self-calibraIion for abouI 8 seconds when iI is Iurned
on. (' ' is displayed on Ihe LCD.) Do noI clamp onIo any conducIor or
open Ihe |aws in Ihis period. OIherwise, inaccuraIe measuremenI may occur.
ResisIor for operaIion check
1 O
10 O
Allowable rane
0.98 1.07
9.76 10.26
10
7. Measuring method
#
DANGER
Never make measuremenI on a circuiI in which Ihe elecIrical poIenIial
exceeds AC800V.
Transformer |aws are made of meIal and Iheir Iips are noI compleIely
insulaIed. Be especially careful abouI Ihe possible shorIin where Ihe
equipmenI under IesI has exposed meIal parIs.
Never make measuremenI wiIh Ihe BaIIery cover removed.
Do noI measure a currenI over 80A. Transformer |aws may heaI Io cause
a fire or deformaIion of moldin parIs, which will derade insulaIion. When
clampin Ihe conducIors on which over 80A flowin and ' ' is displayed
on Ihe LCD, sIop measuremenI immediaIely and Iake off Ihe insIrumenI
from Ihe conducIor under IesI.
#
CAUTION
Take sufficienI care noI Io apply shock, vibraIion or excessive force Io Ihe
|aw Iips.
OIherwise, precisely ad|usIed Transformer |aws will be damaed.
This insIrumenI performs self-calibraIion for abouI 8 seconds when
iI is Iurned on. ('
' is displayed on Ihe LCD.) Do noI clamp onIo
any conducIor or open Ihe |aws in Ihis period. OIherwise, inaccuraIe
measuremenI may occur.
When forein subsIances are sIuck in Ihe |aw Iips or Ihey are noI properly
enaed, Ihe Transformer |aws do noI fully close. ln such a case, do noI
release Ihe |aw Irier abrupIly or aIIempI Io close Ihe Transformer |aws by
applyin exIernal force. Make sure IhaI Ihe |aws close by Ihemselves afIer
removin Ihe forein subsIance or makin Ihem free Io move.
The size of a conducIor can be IesIed is 80mm in diameIer. AccuraIe
measuremenI cannoI be made on a conducIor larer Ihan Ihis, because Ihe
Transformer |aws cannoI fully close.
Never aIIempI Io apply excessive force Io close Ihe |aws.
When measurin lare currenI, Ihe Transformer |aws may buzz. This has no
effecI on Ihe insIrumenI's performance or safeIy.
SensiIive Transformer |aws are used for Ihis insIrumenI. Because of Ihe
characIerisIics of Transformer |aws, which can be opened and closed,
iI is impossible Io eliminaIe Ihe inIerference of exIernal maneIic field
compleIely. lf Ihere are someIhin, which eneraIin lare maneIic field, aI
a nearby siIe, currenI value can be displayed (0`may noI be displayed)
before clampin on Ihe conducIor. For such a case, please use Ihe
insIrumenI aI a locaIion far from Ihe Ihin, which eneraIin maneIic field.
Followin are Ihe Iypical Ihins eneraIin maneIic field.
* ConducIor fed lare currenI
* MoIor
* EquipmenI which has maneI
* lnIeraIin waIImeIer
11
7-1 Normal measurement of current
* Press Ihe FuncIion buIIon and selecI Ihe ACA funcIion.
* Confirm Ihe displayed uniI is ' mA ', and Ihe ' MEM ' is noI displayed aI Ihe
upper lefI on Ihe LCD.
* Press Ihe Irier Io open Ihe Transformer |aws, and close Ihem over one
conducIor only.
* Measured currenI value is displayed on Ihe LCD.
(EarIh leakae currenI IhaI flows Ihrouh an earIhed wire can be measured by
Ihis meIhod.)
7-2 Measurement of balance leakage current
* Press Ihe FuncIion buIIon and selecI Ihe ACA funcIion.
* Confirm Ihe displayed uniI is ' mA ', and Ihe ' MEM ' is noI displayed aI Ihe
upper lefI on Ihe LCD.
* Clamp onIo all conducIors excepI for Ihe earIhed wire.
* Measured currenI value is displayed on Ihe LCD.