Vous êtes sur la page 1sur 3

50/3POCKETMODEL/xxxx/0406/EN

RIGID POCKET FILTERS


3 Pocket Model

Typical applications Separators


Hot melt gluing
Rigid pocket filters with mini-pleated extended filtering
surface are used for fine dust filtration in regular Sealant
ventilation systems. The main advantages of such Cold moulded polyurethane
construction are a low pressure loss and a long life
time of the filter. Frame
With a flange of 25 mm filters may be installed into Plastic
standard mounting frames.

Operating temperature

Advantages 80°C

• Strong plastic frame and rigid construction guarantee Relative humidity


high stability during utilization Max. 90 %
• Ease of maintenance
• Long service life Specifications
• Filters are completely incinerable • Filters available in classes F6-F8

Quality and environment


Technical characteristics
The operations of Halton Clean Air Oy are certified

Media with the ISO 9001:2000 Quality and ISO 14001

Glass fibre paper Environmental standards.

RIGID POCKET FILTERS - 3 Pocket Model



50/3POCKETMODEL/xxxx/0406/EN
EFFICIENCY

FILTER CLASS Average efficiency, Em % 0,4 µm


CEN - EN 779
F6 60 < Em < 80
F7 80 < Em < 90
F8 90 < Em < 95

25
DIMENSIONS

W
D
25

Pressure drop as a function of the air flow rate (clean device)

NR CODE Dimensions Flow rate Filtering Initial pressure Volume Weight


W

W x L x D mm m 3/h surface m 2 drop Pa m3 kg


1 CLP - RP - P - 402 - 593 - 292 - 3 - F6 - GF - P 402 x 593 x 292 2600 9,0 135 0,084 3,50
2 CLP - RP - P - 288 - 593 - 292 - 3 - F6 - GF - P 288 x 593 x 292 1750 6,5 135 0,060 2,60
3 CLP - RP - P - 491
L - 593 - 292 - 3 - F6 - GF - P 491 x 593 x 292 3200 11,5 135 0,102 4,00
4 CLP - RP - P - 593 - 593 - 292 - 3 - F6 - GF - P 593 x 593 x 292 4000 14,0 135 0,123 5,00
Recommended final pressure drop < 600 Pa
Maximum final pressure drop < 1000 Pa

2 1 3 4
160

140
Pressure drop (Pa)

120

100

80

60

40

20

0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000
Air flow rate (m 3/s)

RIGID POCKET FILTERS - 3 Pocket Model



50/3POCKETMODEL/xxxx/0406/EN
NR CODE Dimensions Flow rate Filtering Initial pressure Volume Weight
W x L x D mm m 3/h surface m 2 drop Pa m3 kg
1 CLP - RP - P - 402 - 593 - 292 - 3 - F7 - GF - P 402 x 593 x 292 2600 9,0 140 0,084 3,50
2 CLP - RP - P - 288 - 593 - 292 - 3 - F7 - GF - P 288 x 593 x 292 1750 6,5 140 0,060 2,60
3 CLP - RP - P - 491 - 593 - 292 - 3 - F7 - GF - P 491 x 593 x 292 3200 11,5 140 0,102 4,00
4 CLP - RP - P - 593 - 593 - 292 - 3 - F7 - GF - P 593 x 593 x 292 4000 14,0 140 0,123 5,00
Recommended final pressure drop < 600 Pa
Maximum final pressure drop < 1000 Pa

2 1 3 4
180
SE30
SE30 SE29 SE31 SE32
160
Pressure drop (Pa)

140
120

100
80
60
40

20

0
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000
Air flow rate (m 3/s)

NR CODE Dimensions Flow rate Filtering Initial pressure Volume Weight


W x L x D mm m 3/h surface m 2 drop Pa m3 kg
1 CLP - RP - P - 402 - 593 - 292 - 3 - F8 - GF - P 402 x 593 x 292 2600 9,0 160 0,084 3,50
2 CLP - RP - P - 288 - 593 - 292 - 3 - F8 - GF - P 288 x 593 x 292 1750 6,5 160 0,060 2,60
3 CLP - RP - P - 491 - 593 - 292 - 3 - F8 - GF - P 491 x 593 x 292 3200 11,5 160 0,102 4,00
4 CLP - RP - P - 593 - 593 - 292 - 3 - F8 - GF - P 593 x 593 x 292 4000 14,0 160 0,123 5,00
Recommended final pressure drop < 600 Pa
Maximum final pressure drop < 1000 Pa

2 1 3 4
200
180
160
Pressure drop (Pa)

140
120
100
80
60
40
20
0
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000
Air flow rate (m 3/s)

RIGID POCKET FILTERS - 3 Pocket Model




Vous aimerez peut-être aussi