Vous êtes sur la page 1sur 11

BILL OF QUANTITIES(Non betaluctum)

BILL OF QUANTITIES - SCHEDULE A


SUPPLY
Sr. No.

Description

Unit

Qty.

SCREW CHILLER
Supply /Installation/ Testing / Commissioning of Screw type Water Cooled Chilling unit complete with
accessories and Star Delta starter preferably with graphic display. Water temperature out/in of 7/12
deg C duly installed and commissioned including initial charge of refrigerant and oil. The Chiller shall
be preferably with multiple compressors and PLC based controls.
220 TR water cooled screw chiller skid mounted type. Motor control centre and all necessary switch
gear should also be skid mounted. Chiller should be suitable for R134a gas. The chiller should have
BMS compatibility. Capacity 220 TR

No.

No.

Nos

Nos

Nos

CHILLED and CONDENSER WATER PIPING & VALVES


Butterfly valve
Butterfly valve shall be of short wafer flangeless type with cast iron body and PN-10 rating
125 mm
100 mm

Nos
Nos

10
10

NRV
Check valves up to 65 mm size shall be of gunmetal construction with screwed female ends.
Check Valves of sizes 65 mm and above shall be of C.I. constructions with flanged ends and
gunmetal seat rings and PN-10 as per tender specifications
125 mm
100 mm

Nos
Nos

3
3

Y Strainer
Strainers shall have 0.6 mm bronze screen having 3 mm 0 perforations to provide minimum net
free area of 4 times the cross sections area of the pipeline in which it is installed and PN-10 as per
tender specifications
125 mm
100 mm

Nos
Nos

3
3

Refrigerant
: R134
Condensor inlet
: 32 Deg C
Condensor outlet
: 36 Deg C
WBT
: 26 deg C
Capacity : 220 TR at operating condition
2

COOLING TOWER

Supplying, installing, testing and commissioning of FRP cooling tower Single / Multicell for following
water flow with FRP water basin, PVC fillings with integral louvers and drift eliminators complete with
hot water basin either fitted with spray nozzles or having self rotating sprinkles, statically and
dynamically balanced axial flow type fan-direct driven or driven through reduction gear box with high
efficiency TEFC induction motor as per EFF1 standards, Motor suitable for VFD application, suction
screen, make up-quick fill arrangement, overflow and drain connections with necessary valves and
suitable inspection ladder, access arrangement for cooling tower interior, anti-vibration mountings
etc. complete as per specifications and as required.

3
4

Induced draft FRP cooling tower complete with all accessories , fittings , fan , fan motor etc suitable
for following capacity
Capacity
: 220 TR
Water Flow
: 880 USGPM
Water inlet temperature
: 36.2 C
Water outlet temperture
: 32.2 C
Motor H.P
: 5 H.P
PUMPS
CHILLED WATER PUMPS
Supply, Installation, testing & commissioning of
Backpullout type pumps suitable for 660 USGPM working against a head of 40 Mtrs. Pump should
have common base frame, coupling, suitable motor. Pump should be operated on 2900 RPM (1
working + 1 stand by)

CONDENSOR WATER PUMPS


Supply, Installation, testing & commissioning of
Backpullout type pumps suitable for 880 USGPM working against a head of 25 Mtrs. Pump should
have common base frame, coupling, suitable motor. Pump should be operated on 2900 RPM

6.1

7
7.1
a
7.1.1
7.1.2
7.2
a
7.2.1
7.2.2
7.3
a
7.3.1
7.3.2

ELECTRICAL WORKS
Design, supply, installation, testing & commissioning of Cubicle type floor mounted panel board
comprising main incoming with MCCB & outgoing feeder with MCB upto 63A & MCCB above 63A,
Digital ammeter & voltmeter, with selector switches to be provided for ON-OFF-Trip indicating lamp
along with Star-Delta/ DOL starter, etc. for 2 chiller pump, 2 condensor pumps & 2 cooling towers.

Rate

Amount

ED Amount
@12.36% will be
provided as per
gate pass

B=A*0.1236

B=A*0.1236

INSTALLATION
2% CST

C=(A+B)*0.02

C=(A+B)*0.02

Rate

Amount

12.36 % ST

F=E*0.1236

F=E*0.1236

Total

A+B+C+D+E+F

A+B+C+D+E+F

BILL OF QUANTITIES(Non betaluctum)


BILL OF QUANTITIES - SCHEDULE A
SUPPLY
Sr. No.

Description

Unit

Qty.

Rate

Amount

A
7.4

7.4.1
7.4.2
7.4.2
8
8.1
a
8.1.1
8.1.2
8.1.3
8.2
a
8.2.1
8.2.2
8.2.3
8.2.4
8.3
a
8.3.1
8.3.2
8.3.3
8.3.4
8.4
a
8.4.1
8.4.2
9
9.1

9.2

10.1

Balancing valve
Balancing valve shall be constructed of dezincification resistant brass or bronze alloy. 2" to 12"
valves will be constructed of iron with ANSI Class 125/150 flanged or grooved ends. All valves
shall be globe style for precise regulation and control and rated 175 psi for Iron and 240psi for
Bronze at 250F. Each valve shall have two metering/test ports with internal check valve and
protective caps. All valves must be equipped with visual position readout and memory stop for
repeatable regulation and control.
150 mm
125 mm
100 mm

32
9
9

Globe valves
Gun metal valves up to 65 mm shall conform to IS 778. Cast iron valves with Bronze / Gun Metal
spindles, seats etc. from 65 mm to 300 mm sizes shall conform to IS 780 Class 2 and from sizes
350 mm ad above shall conform to IS 2906. Globe valves shall have brass plated indicators. The
valve shall have rising spindles only, and PN-10
40 mm
32 mm
25 mm
20 mm

Nos
Nos
Nos
Nos

20
21
4
11

Nos
Nos
Nos
Nos

5
5
16
6

NRV
NRV shall conform to IS 5312. Check valves up to 65 mm size shall be of gunmetal construction
with screwed female ends. Check Valves of sizes 65 mm and above shall be of C.I. constructions
with flanged ends and gunmetal seat rings and PN-10 rating
100 mm
Nos
80 mm
Nos

3
3

3 Way Mixing Valve - Modulating Type


Installation, testing and commissioning of three way modulating type valves along with actuators,
proportionating humidity controller with humidity display complete with necessary linkage, valve and
counter flanges. Nipples, fittings to be considered for sizes less than 50mm dia.
50 mm
25 mm
20 mm
15 mm

CHILLED & COOLING WATER-SCALE & CORROSION CONTROL


Supply installation testing and commissioning of Baccomber descaler cum magnetic generator to
control scaling, corrosion, algae and bacteria of cooling water system
Line Size : 150 mm
Supply installation testing and commissioning of Baccomber descaler cum magnetic generator to
control scaling, corrosion, algae and bacteria of chilled water system
Line Size : 125 mm

No.

No.

No.

Unpressurised Closed Expansion Tank with Membrane without insulation valve & fittings, 1000
ltr. PN 10
Closed Expansion Tank with Membrane, without insulation, valves & fittings, 100litres, PN10

Safety Valve 10Bar (1No. Reqiured per Closed Expansion Tank)


Pressure Maintaining Station complete with double pump, (2CMH, 45mWC), IP55 Control Panel
with soft Starter, Pressure Transmitter, Interconnecting piping & wiring.
1000 Ltr. M.S. Closed Cell Pressurization Expansion all accessories as above.

10.1.1

3
3
3

HOT WATER VALVES


Gate valves
Gun metal valves up to 65 mm shall conform to IS 778. Cast iron valves with Bronze / Gun Metal
spindles, seats etc. from 65 mm to 300 mm sizes shall conform to IS 780 Class 2 and from sizes
350 mm ad above shall conform to IS 2906. The valve shall have rising spindles only, and PN-10
rating
32 mm
Nos
25 mm
Nos
20 mm
Nos

Nos
Nos
Nos

ED Amount
@12.36% will be
provided as per
gate pass
B=A*0.1236

INSTALLATION
2% CST

C=(A+B)*0.02

Rate

Amount

12.36 % ST

F=E*0.1236

Total

A+B+C+D+E+F

BILL OF QUANTITIES(Non betaluctum)


BILL OF QUANTITIES - SCHEDULE A
SUPPLY
Sr. No.

Description

10.2

Expansion Tank
Supplying, installation, testing and commissioning of M.S. expansion tank made of 3mm thick mild
steel sheet complete with 25 mm thick expanded polystyrene (TF quality) insulation covered with
vapour barrier, 0.5mm x 20G GI wire mesh netting and finished with 0.5mm thick GI cladding duly
plastered and complete with vent and drain connections with float valve, quick fill and control
valves, foundation etc. as required.
1000 Ltr. M.S. Expansion tank

Unit

Qty.

Rate

Amount

No

RO

10.3.1

The Packaged Plant Room System should provide instantaneous temperature controlled hot water
using steam as the heating medium.
Description of the system:
1. Plate heat exchanger for efficient heating complete with demountable plates for easy cleaning.
2. Safety Valve to protect the heat exchanger.
3. Pressure Reducing Valve to maintain correct pressure on to heat exchanger.
4. 2-port control valve with correct valve characteristics for the application.
5. independent high limit control to provide overheat protection.
6. receiver to allow collection of condensate.
7. Pump Trap combination to remove condensate under all load conditions.
8. Controller for accurately maintaining desired water temperature.
Capacity = 450 KW

Nos

11
11.1
a
11.1.1
11.1.2
11.1.3
11.1.4
11.1.5
11.1.6

CHILLED WATER PIPING & VALVES


Butterfly valves
Butterfly valves shall be of short wafer flangeless type with cast iron body and PN-10
125 mm
100 mm
65 mm
50 mm
40 mm
25 mm

Nos
Nos
Nos
Nos
Nos
Nos

2
7
10
10
10
20

Pressure gauges as per specification for mounting on chilled water pipe (Range: 0 - 10kg/cm2)

Nos

20

Temperature gauges
Provision of tappings with brass thermowells and nitrile rubber insulation for mounting temperature
gauges on chilled water line.
Temperature gauges as per specification for mounting on CHW pipe. (Range 0 - 25C)

Nos

20

Nos
Nos
Nos
Nos
Nos
Nos
Nos

3
2
2
2
12
5
3

10.2.1
10.3
a

11.2
11.2.1
11.2.2
11.3
11.3.1
11.3.2
11.4
a
11.4.1
11.4.2
11.4.3
11.4.4
11.4.5
11.4.6
11.4.7
12
a
b

Instantaneous Hot Water Generation System (Forbes Marshall / Equivalent make)

Pressure gauges
Provision of tappings for pressure gauges with cock and U pipe with nitrile rubber insulation tubing
brass with cr plating on Chilled water pipe

3 Way Mixing Valve - Modulating Type


Installation, testing and commissioning of three way modulating valves along with actuators,
proportionating Thermostat with temperature display, & valve, linkage and counter flanges.
Nipples, fittings to be considered for sizes less than 65 mm dia.
65 mm
50 mm
40 mm
32 mm
25 mm
20 mm
15 mm
DOUBLE SKIN AIR HANDLING UNITS
Double skin air handling units fabricated from outer skin with 0.63 mm thick precoated G.I sheet &
plain 0.63 mm thick inner G.I sheet with 40 mm thick injected puf insulation with Aluminum
extruded frame work having Thermal break profile with internal coving complete with the following
sections working in conjuction with condensing units/chillers
Mixing Chamber

Filter Section complete with pre-filters designed to remove particles down to 10 Microns with an
efficiency of 90% on ASHRAE STD. 52-56 and 90% on BS 2831 Test Dust No. 2 (Junior Filter) in
CRCA construction duly powder coated. The filter shall have 3 stage of Non Woven synthetic
polymedia sandwitched between 2 layers of HDPE mesh duly epoxy sealed at the ends.

MICROVEE FILTERS designed to remove particles down to 5 Microns in CRCA construction with
an efficiency of 99.9% on ASHRAE STD. 52-76 and 90% on BS 2831 Test Dust No. 2 (Junior
Filter) in CRCA construction duly powder coated. The filter shall have 3 stage of Non Woven
synthetic polymedia sandwitched between 2 layers of HDPE mesh duly epoxy sealed at the ends.

HEPA FILTERS (High efficiency particulate air) designed to remove particles down to 0.3 Microns
from air streams with an efficiency of 50%. The filter matrix comprises specially treated glass fiber
media with machine pleated aluminium separators. It is housed in an aluminium frame provided
with angle turned flanges closed cell gaskets. Each HEPA filter is subjected to test confirming to
international standard especially US MIL STD 282 and IES Recommended Practice IES - RP
CC 001 - 86.

Cooling Coil Section with suitable rows deep cooling coil made of copper tubes and aluminium fins.

ED Amount
@12.36% will be
provided as per
gate pass
B=A*0.1236

INSTALLATION
2% CST

C=(A+B)*0.02

Rate

Amount

12.36 % ST

F=E*0.1236

Total

A+B+C+D+E+F

BILL OF QUANTITIES(Non betaluctum)


BILL OF QUANTITIES - SCHEDULE A
SUPPLY
Sr. No.

Description

Unit

Qty.

Rate

Amount

A
g
h
i
j

Hot Water Coil Section with suitable rows deep heating coil made of copper tubes and aluminium
fins.
Fan section complete with backward curved multi-louvered direct driven plug type fan suitable for
various CFM working against a static pressure 110 mm w.g.
Crompton/Equivalent make TEFC squirrel cage induction motor suitable for operation on AC 3
Phase, 415 volts, 50 c/s. supply
Magnahelic Gauges with Gauge Box across Microvee & HEPA filter Range : 0-50 mm of W.G./0100 mm of WG

ED Amount
@12.36% will be
provided as per
gate pass
B=A*0.1236

INSTALLATION
2% CST

C=(A+B)*0.02

Rate

Amount

12.36 % ST

F=E*0.1236

Total

A+B+C+D+E+F

BILL OF QUANTITIES(Non betaluctum)


BILL OF QUANTITIES - SCHEDULE A
SUPPLY
Sr. No.

Description

Unit

Qty.

No.
No.
No.
No.
No.
No.
No.
No.
No.
No.
No.
No.
No.
No.
No.
No.
No.
No.
No.
No.
No.
No.
No.
No.
No.
No.
No.

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

No.
No.
No.
No.

1
1
1
1

No.
No.
No.
No.

1
1
1
1

Sq.ft

200

Rate

Amount

A
12.1.1
12.1.2
12.1.3
12.1.4
12.1.5
12.1.6
12.1.7
12.1.8
12.1.9
12.1.10
12.1.11
12.1.12
12.1.13
12.1.14
12.1.15
12.1.16
12.1.17
12.1.18
12.1.19
12.1.20
12.1.21
12.1.22
12.1.23
12.1.24
12.1.25
12.1.26
12.1.27
13.1
a

c
d
e
f
g
13.1.1
13.1.2
13.1.3
13.1.4
13.2
a
b
c
d

13.2.1
13.2.2
13.2.3
13.2.4
14

14.1

AHU 60 /3335 CFM / 110 MM S.P / 7.5H.P / 4 P/4 ROWS DX/2 ROWS HW
AHU 59 /1418 CFM / 110 MM S.P / 5H.P / 4 P/4 ROWS DX/2 ROWS HW
AHU 58 /1495 CFM / 110 MM S.P / 5H.P / 4 P/4 ROWS DX/2 ROWS HW
AHU 57 /17950 CFM / 110 MM S.P / 20H.P / 4 P/4 ROWS DX/2 ROWS HW
AHU 56 /1465 CFM / 110 MM S.P / 5H.P / 4 P/4 ROWS DX/2 ROWS HW
AHU 55 /2767 CFM / 110 MM S.P / 5H.P / 4 P/4 ROWS DX/2 ROWS HW
AHU 54 /16500 CFM / 110 MM S.P / 20H.P / 4 P/4 ROWS DX/2 ROWS HW
AHU 53 /2791 CFM / 110 MM S.P / 5H.P / 4 P/8 ROWS DX/2 ROWS HW
AHU 52 /2450 CFM / 110 MM S.P / 5H.P / 4 P/8 ROWS DX/2 ROWS HW
AHU 51 /2710 CFM / 110 MM S.P / 5H.P / 4 P/8 ROWS DX/2 ROWS HW
AHU 50 /2270 CFM / 110 MM S.P / 5 H.P / 4 P/4 ROWS DX/2 ROWS HW
AHU 49 /4800 CFM / 110 MM S.P / 7.5H.P / 4 P/8 ROWS DX/2 ROWS HW
AHU 48 /2390 CFM / 50 MM S.P / 5H.P / 4 P/4 ROWS DX/2 ROWS HW
AHU 47 /4300 CFM / 110 MM S.P / 7.5H.P / 4 P/8 ROWS DX/2 ROWS HW
AHU 46 /6300 CFM / 110 MM S.P / 10H.P / 4 P/4 ROWS DX/2 ROWS HW
AHU 45 /3000 CFM / 110 MM S.P / 7.5 H.P / 4 P/8 ROWS DX/2 ROWS HW
AHU 44 /11000 CFM / 110 MM S.P / 15 H.P / 4 P/8 ROWS DX/2 ROWS HW
AHU 43 /2086 CFM / 110 MM S.P / 5H.P / 4 P/4 ROWS DX/2 ROWS HW
AHU 42 /2140 CFM / 110 MM S.P / 5H.P / 4 P/4 ROWS DX/2 ROWS HW
AHU 41 /2090 CFM / 110 MM S.P / 5H.P / 4 P/4 ROWS DX/2 ROWS HW
AHU 40 /2060 CFM / 110 MM S.P / 5H.P / 4 P/4 ROWS DX/2 ROWS HW
AHU 39 /2020 CFM / 110 MM S.P / 5H.P / 4 P/4 ROWS DX/2 ROWS HW
AHU 38 /700 CFM / 110 MM S.P / 2 H.P / 2 P/4 ROWS DX/2 ROWS HW
AHU 37 /700 CFM / 110 MM S.P / 2 H.P / 2 P/4 ROWS DX/2 ROWS HW
AHU 36 /550 CFM / 110 MM S.P / 2 H.P / 2 P/4 ROWS DX/2 ROWS HW
AHU 35 /16260 CFM / 110 MM S.P / 20H.P / 4 P/4 ROWS DX/2 ROWS HW
AHU 34 /8020 CFM / 110 MM S.P / 10H.P / 4 P/4 ROWS DX/2 ROWS HW
SINGLE SKIN SUPPLY AIR WASHER UNITS
Sheet metal sectionalised cabinet type air washer units in Single skin construction fabricated from
1.6 mm Thick G.I sheet complete with following section
Filter Section complete with pre-filters designed to remove particles down to 10 Microns with an
efficiency of 90% on ASHRAE STD. 52-56 and 90% on BS 2831 Test Dust No. 2 (Junior Filter) in
CRCA construction duly powder coated. The filter shall have 3 stage of Non Woven synthetic
polymedia sandwitched between 2 layers of HDPE mesh duly epoxy sealed at the ends.
Filter section for mounting 5 micron filters without filters
Fan section complete with Forward curved multi-louvered centrifugal type fan suitable for various
CFM working against a static pressure 50 mm w.g.
Crompton/Equivalent make TEFC squirrel cage induction motor suitable for operation on AC 3
Phase, 415 volts, 50 c/s. supply
Humidifier section complete with Cell Deck pads, eliminators & FRP lined water tank.
Air washer circulating pumps complete with air washer G.I class B piping , isolating valves , NRV ,
Y strainers ,pressure gauges & temperature gauges
FDV- 1 / 4425 CFM / 50 MM S.P / 5 H.P / 4 P
FDV- 2 / 5860 CFM / 50 MM S.P /7.5 H.P / 2 P
FDV- 3 / 3640 CFM / 50 MM S.P / 5 H.P / 4 P
FDV - 4 / 10000 CFM / 50 MM S.P. / 7.5 H.P / 4 P
SINGLE SKIN EXHAUST VENTILATION UNITS
Single skin exhaust air ventilation unit fabricated from 1.6 mm thick G.I sheet complete with
following sections for supplying fresh air
Mixing chamber
Fan section complete with Forward curved multi-louvered centrifugal type fan suitable for various
CFM working against a static pressure 50 mm w.g.
Crompton/Equivalent make TEFC squirrel cage induction motor suitable for operation on AC 3
Phase, 415 volts, 50 c/s. supply
Filter Section complete with pre-filters designed to remove particles down to 10 Microns with an
efficiency of 90% on ASHRAE STD. 52-56 and 90% on BS 2831 Test Dust No. 2 (Junior Filter) in
CRCA construction duly powder coated. The filter shall have 3 stage of Non Woven synthetic
polymedia sandwitched between 2 layers of HDPE mesh duly epoxy sealed at the ends.
FDV- 1 /4425 CFM / 25 MM S.P / 3.0H.P / 4 P
FDV- 2 /5860 CFM / 25 MM S.P /5.0 H.P / 4 P
FDV- 3 /3640 CFM / 25 MM S.P / 3 H.P / 4 P
FDV - 4 / 9200 CFM / 25 MM S.P. / 5 H.P / 4 P
Anti Corrosive Coating for Chemical treatment of Cooling Coils for protection against
corrosion
The cooling coils of 4/6 rows deep are to be coated with Blygold for corrosion resistance to
enhance the life of the unit. Blygold PoluAl is a metallic impregnated polyurethane coating
specifically designed for applications of Al finned-Cu coils. It is a thin (25 micron), flexible, UV
&impact resistant coating that exhibits excellent adherence to Al surfaces & provides superior
protection to Cu/Al coils. The area given is the face area of the coil.

ED Amount
@12.36% will be
provided as per
gate pass
B=A*0.1236

INSTALLATION
2% CST

C=(A+B)*0.02

Rate

Amount

12.36 % ST

F=E*0.1236

Total

A+B+C+D+E+F

BILL OF QUANTITIES(Non betaluctum)


BILL OF QUANTITIES - SCHEDULE A
SUPPLY
Sr. No.

Description

Unit

Qty.

Rate

Amount

A
15
a

Weather protection on Insulation


Supply air ducts will be coated with one coat of Starbond30/36 chemical, then it will be wrapped
with glass cloth (FG - MII) on the surface. After wrapping it will be again coated with 2 coats of
Starbond 30/36 chemical.

Sq.ft

7500

sq.ft

155

16

GSS opposed blade type Volume control dampers

17

VAV BOXES WITH FLOW SENSOR AND CONTROLLER


Thermally powered Therma-Fuser VAV Diffuser model TF-HC including a complete VAV terminal
and thermostat/actuator self-contained in a nominal 600 x 600mm SQUARE diffuser. The VAV
diffusers shall vary the supply air volume to provide both VAV heating and VAV cooling using two
room sensing thermostats and one changeover thermostat. The damper shall be of perimeter
Blade type. The diffuser will be suitable for ceiling mounting. The diffuser will be fitted with Remote Nos
Adjuster type DA to provide temperature adjustment through the Digital Wall Adjuster. Neck Size
150mm to 300mm dia. Air flow-130cfm to 650cfm
i) Master Diffusers
ii) Secondary Diffusers

17.1

17.2

18

Digital Wall Adjuster type ADJ-D for remote adjustment of temperature. This can be located
anywhere in the room and provides adjustment from 21 deg.C to 24 deg.C. It will be powered by
24 V AC supply. The unit will also provide an analog 0-2 V DC signal for input and
output to a BMS system for temperature setting. Note: Each Digital Wall Adjuster can be
connected with one Master and up to four Secondary diffusers.

10

Nos

10

Fire Damper (Motorised with actuator)

18.1

Supply, Installation, Testing and Commissioning of galvanized sheet fire control damper with limit
switch. The damper shall be CBRI approved for fire rating of 90 minutes & only for the main
supply/return air ducts. Fire Dampers shall also have provision for Motorised type Operation

Sq ft

150

18.2
18.3

Motorized Actuator for above fire damper


Fusible link for above fire damper

Nos.
Nos

68
RO

19.1

Supply air diffuser in extruded aluminum construction with volume control dampers
Nos.
Nos.

116
100

300X300
450X450

Nos.
Nos.

116
100

Factory fabricated Return Air Riser in G.I. construction with body in 16 G & the front cover in 18
G compatible with return air riser grilles with front operated volume control dampers.The front
cover should be easily detachable .
300X150X3000
500X150X3000

Nos.
Nos.

20
85

19.1.1
19.1.2
19.2
19.2.1
19.2.2

20.1
20.1.1
20.1.2
20.2

20.2.1

21
a
21.1
21.2
21
21.1
21.1.1
21.1.2
21.1.3
21.1.4
21.1.5

300X300
450X450
Return air diffuser in extruded aluminum construction with volume control dampers

Return Air Riser Grill


Return Air Riser Grill complete with volume control dampers & pre-filters designed to remove
particles down to 10 Microns with an efficiency of 90% on ASHRAE STD. 52-56 and 90% on BS
2831 Test Dust No. 2 (Junior Filter) in CRCA construction duly powder coated. The filter shall have Sq ft
3 stage of Non Woven synthetic polymedia sandwitched between 2 layers of HDPE mesh duly
epoxy sealed at the ends.

165

FILTERS
FLANGE TYPE MICROVEE FILTERS designed to remove particles down to 5 Microns in CRCA
powder coated construction with an efficiency of 99.9% on ASHRAE STD. 52-76 and 90% on BS
2831 Test Dust No. 2 (Junior Filter) in AL.construction. The filter shall have 3 stage NWP
sandwitched betwen two layers of HDPE.
610 X 610 X 300 mm
610 X 610 X 150 mm

Nos.
Nos.

51
11

ELECTRICAL WORKS
Power Control Centre (PCC), cubicle type floor mounted panel board comprising main incoming
with MCCB & outgoing feeder with MCB upto 63A & MCCB above 63A, Digital ammeter, Digital
voltmeter with selector switches in incomer feeder.
PANEL 1 : AHU34,AHU35,AHU-36,AHU-37,AHU-38,AHU-39,AHU-40
PANEL 2 : AHU-41,AHU-42,AHU-43,AHU-44,AHU-45,AHU-46,AHU-47
PANEL 3 : AHU-48,AHU-49,AHU-50,AHU-51,AHU-52,AHU-53,AHU-54
PANEL 4 : AHU-55,AHU-56,AHU-57,AHU-58,AHU-59,AHU-60.
PANEL 5 : SFDV-1,SFDV-2,SFDV-3,SFDV-4,EFDV-1,EFDV-2,EFDV-3,EFDV-4

No.
No.
No.
No.
No.

1
1
1
1
1

ED Amount
@12.36% will be
provided as per
gate pass
B=A*0.1236

INSTALLATION
2% CST

C=(A+B)*0.02

Rate

Amount

12.36 % ST

F=E*0.1236

Total

A+B+C+D+E+F

BILL OF QUANTITIES(Non betaluctum)


BILL OF QUANTITIES - SCHEDULE A
SUPPLY
Sr. No.

Description

Unit

Qty.

Rate

Amount

A
22

22.1
23

PID CONTROLLER PANEL


PID controller Panel along with Temperature / Humidity Controller as follows:
Independent Display for Temp. & % RH
Measuring Range: -50 to 1500C
Input:' Dry Bulb / Wet Bulb' or temperature & 1 Humidity Sensor (RH transmitter)
Control Type: Modulating type
Power Requried: 120 to 240 V
Make: Dwyer, Honywell or Equivalent
PID PANEL for AHU 34 to 60

Nos

27

MAGNAHELIC GAUGES

23.1

Magna-Helic gauge for measuring differential pressure for 5 micron filter section of AHU's of
range 0-50mm and 0-100mm respectively, complete with SS mounting and Box

Nos.

RO

23.2

Magna-helic gauge of 0-10 mm of WG for rooms with fixing box made out of CRCA epoxy powder
Nos.
coated provided with SS 304 cover plates.

20

24.1

Water Flow switches for measuring flow of water across condensor

Nos.

Danfoss / ABB or quivalent make Variable Frequency Drives with a programmable control
PLC. This will be required for plug type fan
20 HP
15 HP
10 HP
7.5 HP
5 HP
2 HP

Nos
Nos
Nos
Nos
Nos
Nos

3
1
2
4
14
3

Nos
Nos
Nos
Nos
Nos
Nos

3
1
2
4
14
3

Nos

27

Nos

10

Nos
Nos
Nos

49
80
80

27.1

Each AHU to be provided with airflow switch / differential switch across fan in case of failure of
fans for any reason it should give alarm and indication. This control can be integrated as mentioned Nos
above & signal from the airflow switch to be integrated with hooter alarm system for the item B.

27

27.2

Electronic Differential Pressure Magnehelic gauges to check differential pressure across


microvee filters and HEPA filters with indicator and alarm. The unit should be mounting on top of
the AHU complete with hooter and push buttom. The hooter to give alarm when differential
pressure goes beyond set point. The entire arrangement along with control wiring to be housed in
the independant control box.

27

25.1
25.1.1
25.1.2
25.1.3
25.1.4
25.1.5
25.1.6
25.2
a
25.2.1
25.2.2
25.2.3
25.2.4
25.2.5
25.2.6
25.3
a

25.4

26

26.1
26.2
26.3
27

VFD Panel
Electrical panel for individual AHU having VFD along with Bypass starter and change over switch.
20 HP
15 HP
10 HP
7.5 HP
5 HP
2 HP
Velocity sensor
Sontay/Kele make Multi point air velocity flow sensor/probe complete with Differential Pressure
Transmitter of Dwyer / Greystone make
Anergy instruments make battery operated wall mounting type Temperature / RH data logger
with display in the room
Plenum box suitable for fixing SS perforated sheet fabricated out of 18 G CRCA Sheet duly
powder coated having in built gear type G.I. opposed blade VCD suitable for operation from below
the ceilling with SS 304 perforated sheet
Perforation Size as under:
300 X 300 - (300 CFM)
450 X 450 - (700 CFM)
600 X 600 - (1250 CFM)
Each AHU should have 1 set complete of the following equipments

Nos

ED Amount
@12.36% will be
provided as per
gate pass
B=A*0.1236

INSTALLATION
2% CST

C=(A+B)*0.02

Rate

Amount

12.36 % ST

F=E*0.1236

Total

A+B+C+D+E+F

BILL OF QUANTITIES(Non betaluctum)


BILL OF QUANTITIES - SCHEDULE A
SUPPLY
Sr. No.

Description

Unit

Qty.

Rate

Amount

A
28.2
a
b

FRESH AIR Air Handling Unit


Single skin fresh air plenum fabricated from 1.6 mm thick G.I. Sheet complete with Mixing
chamber, Pre filter Section with 10 Microns Pre-filters. Capacity=27150 CFM
Mixing Chamber

Filter Section complete with pre-filters designed to remove particles down to 10 Microns with an
efficiency of 90% on ASHRAE STD. 52-56 and 90% on BS 2831 Test Dust No. 2 (Junior Filter) in
CRCA construction duly powder coated. The filter shall have 3 stage of Non Woven synthetic
polymedia sandwitched between 2 layers of HDPE mesh duly epoxy sealed at the ends.

Fan section complete with backward curved multi-louvered direct driven plug type fan suitable for
various CFM working against a static pressure 25 mm w.g.

Crompton/Equivalent make TEFC squirrel cage induction motor suitable for operation on AC 3
Phase, 415 volts, 50 c/s. supply

TOTAL
Note: CST : CENTRAL SALES TAX
ST : SERVICE TAX
ED : EXCISE DUTY

Nos

ED Amount
@12.36% will be
provided as per
gate pass
B=A*0.1236

INSTALLATION
2% CST

C=(A+B)*0.02

Rate

Amount

12.36 % ST

F=E*0.1236

Total

A+B+C+D+E+F

BILL OF QUANTITIES - Schedule B (Non beta lactum)


Supply
ED Amount
Sr.
No.

Description

Unit

Qty.

1
1.1
1.2
1.3
1.4

POWER WIRING WITH SHEATHED ARMOURED ALUMINIUM CABLES


3.0 cx 4 sq.mm AL
3.0 cx 6 sq.mm AL
3.5 cx 10 sq.mm AL
3.5 cx 300 sq.mm AL

rft
rft
rft
rft

60
60
120
200

2
2.1
2.2

CONTROL WIRING WITH SHEATHED ARMOURED COPPER CABLES


3.0 c x 1.5 sq mm Cu
2.0 c x 1.5 sq mm Cu

rft
rft

60
60

EARTHING
Providing & fixing in position the following bare GI tape/ wire including providing all fixing
accessories & effecting proper connections.
Earthing 8 G G.I
25 X 3 MM G.I STRIPS

rft
rft

30
100

CABLE TRAYS
Supply and fixing pregalvanized factory fabricated GI perforated type cable tray with radial
bends, supports of following sizes as per specifications
300 mm wide cable tray with G.I.support
450 mm wide cable tray with G.I.support
100 mm wide cable tray with G.I.support

rft
rft
rft

100
100
100

Condenser water piping


Condenser water piping of G.I.class B pipe inter-connecting cooling tower,
pumpsets complete with fittings like valves,elbow,tees,reducers,etc
200 mm
150 mm
125 mm
100 mm

rft
rft
rft
rft

200
200
55
500

HOT WATER PIPPING


Hot water piping of M.S class 'C' pipe inter-connecting chiller,pumpsets and
airhandling units complete with fittings like valves, elbow, tees, reducers
,etc insulated with 2"/50mm thick mineral wool finished with 26G aluminum sheet
150 mm
125 mm
100 mm
80 mm
65 mm
50 mm
40 mm
32 mm
25 mm

rft
rft
rft
rft
rft
rft
rft
rft
rft

200
200
60
100
100
152
100
80
20

CHILLED WATER PIPPING


Chill water piping of M.S class 'C' pipe inter-connecting chiller,pumpsets and
airhandling units complete with fittings like valves,elbow,tees,reducers
,etc insulated with 2"/50mm thick mineral wool finished with 26G aluminum sheet
200 mm
150 mm
125 mm
100 mm

rft
rft
rft
rft

250
250
697
72

3
a
3.1
3.2
4
a
4.1
4.2
4.3

5
5.1
5.1.1
5.1.2
5.1.3
5.1.4
5.2

5.2.1
5.2.2
5.2.3
5.2.4
5.2.5
5.2.6
5.2.7
5.2.8
5.2.9
5.3

5.3.1
5.3.2
5.3.3
5.3.4

Rate

@12.36% will be
provided as per
Amount
gate pass

Installation
2% CST

12.36% S.T
Rate

Amount

Total

5.3.5
5.3.6
5.3.7
5.3.8
5.3.9
5.3.10
6
21.1
a
6.1.1
6.1.2
6.1.3
6.1.4

80 mm
65 mm
50 mm
40 mm
32 mm
25 mm
AIR DISTRIBUTION SYSTEM
DUCTING
Sheet metal work comprising of G.S.S. ducting with RTV sealant, sizes & quantities
are as under:
24 G ( 0.63 mm Thick )
22 G ( 0.80 mm Thick )
20 G ( 1.0 mm Thick )
18 G ( 1.2 mm Thick )

THERMAL INSULATION
19mm thick Thermal insulation with non fibrous CFC free, closed cell, chemically
6.2.1 closed linked Polyethylene foamed TROCELLEN insulation with factory backed
Aluminium foil.
13mm thick Thermal insulation with non fibrous CFC free, closed cell, chemically
6.2.2 closed linked Polyethylene foamed TROCELLEN insulation with factory backed
Aluminium foil.
9mm thick Thermal insulation with non fibrous CFC free, closed cell, chemically
6.2.3 closed linked Polyethylene foamed TROCELLEN insulation with factory backed
Aluminium foil.

rft
rft
rft
rft
rft
rft

178
132
152
72
132
250

sq.ft
sq.ft
sq.ft
sq.ft

20000
16000
12500
2500

sq.ft

15000

sq.ft

10000

sq.ft

25000

rft
rft
rft
rft
rft
rft
rft
rft
rft

400
600
620
25
75
100
100
480
300

6.2

7.1
7.1.1
7.1.2
7.1.3
7.1.4
7.1.5
7.1.6
7.1.7
7.1.8
7.1.9

Power wiring with sheathed armoured aluminium cables


3.5c x 70 sq.mm AL
3.5c x 50 sq.mm AL
3.5c x 4 sq.mm AL
3.5c x 6 sq.mm AL
3.5c x 10 sq.mm AL
4c x 10 sq.mm AL
4c x 6 sq.mm AL
3c x 4 sq.mm AL
3c x 6 sq.mm AL

7.2
7.2.1
7.2.2
7.2.3

Control wiring with sheathed armoured copper cables


3c x 1.5 sq.mm Cu
4c x 1.5 sq.mm Cu
6c x 1.5 sq.mm Cu

EARTHING
Providing & fixing in position the following bare GI tape/ wire including providing all
fixing accessories & effecting proper connections.
7.3.1 Earthing 8 G G.I
7.3.2 25 X 3 MM G.I STRIPS

rft
rft
rft

3000
2500
1250

rft
rft

250
350

rft
rft
rft
rft
rft
rft

600
450
300
250
500
500

7.3
a

7.4
a
7.4.1
7.4.2
7.4.3
7.4.4
7.4.5
7.4.6

Cable trays
Supply and fixing pregalvanized factory fabricated GI perforated type cable tray with
radial bends, supports of following sizes as per specifications
600 mm wide cable tray with G.I.support
450 mm wide cable tray with G.I.support
300 mm wide cable tray with G.I.support
200 mm wide cable tray with G.I.support
150 mm wide cable tray with G.I.support
100 mm wide cable tray with G.I.support

Drain piping
Drain piping of G.I. Class `B pipe insulated with 2/50mm thick expanded polystyrene
finished with 26 G aluminum sheet.
8.1 50 mm
rft
8.2 40 mm
rft
8.3 25 mm
rft
9.1 DUCT CLEANING PLENUMS
Single skin factory fabricated plenum box fabricated out of 18 G GSS sheet to
provided at strategic location with the ducting having openable door. The door should
9.1.1 be double skin type with PUF duly injected. The door should have locks and
Nos
necessary gasketing to make leak proof. (2 in supply & 2 in return for each individual
system)
kg
9.3 MS Structural work
a

10

108

1000

SUPPLY AND INSTALLATION OF FALSE CEILING

Standard Ceiling Partition are a composite construction of two skins of PPGI/PPGI


with 38+2 kg/m3 density, 50mm thick injected PUF. Panel has lamination on both
10.1 sides of 0.5 mm thick CRCA sheet having powder coating of 25 to 40 microns on
both the sides. Panel joints slip on tongue/groove with width of panel as 1180 mm
complete with all the accessories like support, corner angles, etc.
11
11.1
11.2
11.3
11.4

250
250
250

Flushing & PVC Covings


PVC coving with base of size 2" x 2"
PVC 2 way corner
50 mm wide flushing for cutouts
Cutouts to be provided in the False ceiling for lights, boxes, etc.

TOTAL

sq.ft

6000

rft
Nos
rft
rft

5000
200
2000
2000

Vous aimerez peut-être aussi