HOSPITAL/CLEANROOM DIFFUSERS
Contents
Page No.
Stainless
Stainless
Stainless
Stainless
Stainless
Stainless
Steel
Steel
Steel
Steel
Steel
Steel
3
-
Radial
Radial
Radial
Radial
Radial
Radial
Pattern
Pattern
Pattern
Pattern
Pattern
Pattern
90
180
90 - HEPA or ULPA Filter
180 - HEPA or ULPA Filter
90 - Flush Face
180 - Flush Face
8
8
15
15
26
26
34
39
46
46
53
- Stainless Steel - 1/4 Turn Fasteners - 3/4" (19) Spacing - Fixed Blades
- Stainless Steel - 1/4 Turn Fasteners - 1/2" (13) Spacing - Fixed Blades
73
79
87
88
92
93
94
94
96
97
98
99
101
102
102
104
105
105
106
107
108
108
109
110
111
Back
Home
Contents
Dimensions
Data
Spec
HOSPITAL/CLEANROOM DIFFUSERS
Model 92RPD-SS
MODEL 92RPDF-SS
RADIAL PATTERN DIFFUSERS WITH FILTERS
Model 92RPDF-SS Radial Pattern Diffusers with filters
are similar to the standard model above, however, they
incorporate an extended plenum and a unique frame
designed to accommodate a Gel Seal HEPA or ULPA
filter. The filters can be easily removed and replaced from
the face of the unit. These high quality filters incorporate
a separatorless 2" (51) deep media, integral test port and
an anodized aluminum gel seal frame.
Model 92RPDF-SS
MODEL 92FRP-SS
FLUSH FACE RADIAL PATTERN DIFFUSERS
Model 92FRP-SS Flush Face Radial Pattern Diffusers
provide an air pattern very similar to the standard model
but incorporate a unique 'Flush Face' appearance.
Specially designed internal baffles and a pressure plate
produce an excellent radial air pattern that allows large
volumes of air to be supplied at low velocities. The
unobtrusive flush face design provides the smooth
appearance required for architectural excellence.
Model 92FRP-SS
Back
Home
Contents
Dimensions
Data
Spec
HOSPITAL/CLEANROOM DIFFUSERS
MODEL 92LFD-SS
LAMINAR FLOW DIFFUSERS
Model 92LFD-SS Laminar Flow Diffusers utilize the wellproven and time-tested concept of vertical air mass
' laminar flow ' technology. They produce a non-aspirating,
low velocity, uniformly distributed downward moving
' piston' of conditioned air. They may be used individually,
or as in the case of hospital operating rooms, several
units may be banked together to sufficiently cover the
area and produce one combined laminar mass. Installed
in an operating room above the operating table, the clean
conditioned air flows over and blankets the operating
table, greatly enhancing the ventilation rate.
The advantages of ' laminar flow ' technology provide
similar benefits in other ' cleanroom ' applications such as
research laboratories, animal laboratories, food
processing plants, pharmaceutical laboratories and
protective environment rooms.
Model 92LFD-SS
MODEL 92LFDF-SS
LAMINAR FLOW DIFFUSERS WITH FILTERS
Model 92LFDF-SS Laminar Flow Diffusers with filters are
similar to the standard model above, however, they
incorporate an extended plenum and a unique frame
designed to accommodate a Gel Seal HEPA or ULPA
filter. The filters can be easily removed and replaced from
the face of the unit. These high quality filters incorporate
a separatorless 2" (51) deep media, integral test port and
an anodized aluminum gel seal frame.
Model 92LFDF-SS
Back
Home
Contents
Dimensions
Data
Spec
HOSPITAL/CLEANROOM DIFFUSERS
MODEL 92LS-SS
STERI-SYSTEM LINEAR SLOT DIFFUSERS
Model 92LS-SS Steri-System Linear Slot Diffusers are
specially designed to provide an air curtain for operating
rooms. The unique slot design creates a continuous
curtain of air, angled outwards 5 15 degrees, that
encloses the operating area and minimizes the possibility
of contaminated air entering the surgical area. The single
slot design creates a uniform low velocity curtain that
minimizes entrainment of contaminated air into the
curtain air stream. It also creates a wider velocity profile
with less turbulence and hence less induction over similar
two slot designs. The face design incorporates
longitudinal deflectors that horizontally deflect a small
amount of air lengthwise. This effectively joins the airflow
through sections and corners with a truly continuous air
curtain, resulting in enhanced isolation of the surgical
area.
Model 92LS-SS
MODEL 92STSYS
STERI-SYSTEM HOSPITAL OPERATING ROOM AIR
DISTRIBUTION SYSTEMS
Model 92STSYS is a complete operating room ventilation
system, specially designed to reduce airborne
contaminants. Model 92LS-SS Linear Slot Diffusers,
located around the perimeter, create a continuous low
velocity curtain of air angled outwards 5 15 degrees. The
curtain encloses the operating area and minimizes the
possibility of contaminated air entering the surgical area.
Model 92LFD-SS Laminar Flow Diffusers, installed above
the operating table, produce a low velocity non-aspirating,
vertical air pattern. This low velocity 'clean' conditioned air
flows over the operating table and greatly increases the
ventilation rate within the surgical area. The Steri-System
is available in fourteen standard module sizes with a wide
variety of custom variations that allow it to be tailored to suit
almost any application or configuration.
Model 92STSYS
Back
Home
Contents
Dimensions
Data
Spec
HOSPITAL/CLEANROOM DIFFUSERS
Back
Home
Contents
Dimensions
Model 35SST
Data
Spec
HOSPITAL/CLEANROOM DIFFUSERS
MODEL 35SVM
"PRESSURIZATION" FAN POWERED TERMINAL UNITS
The Nailor Model 35SVM "Pressurization" Fan Powered
Terminal Units are designed specifically for critical
environment applications. Nailors EPIC TM/ECM fan motor
technology utilizes an ultra-high efficiency 'brushless dc'
motor to provide a pressure independent constant
volume assembly. This means that the airflow through the
unit will not change due to pressure changes in the
system as the filter loads or as the pressure in the
exhaust or supply ducts change. Options include electric
or hot water reheat, and various 'IAQ' linings including a
solid metal liner.
Refer to the Nailor VAV Terminal Units catalog for more
information.
Model 35SVM
Model 1221
ACCESS DOORS
The Nailor range of Duct Access Doors has been
designed to allow easy and convenient access to
dampers, coils and other equipment that require
inspection, testing and maintenance. The 0800 Series flat
oval access doors were developed to provide a premium
quality, ultra-low leakage door with optimum ergonomics
in mind. The unique oval shape, available in a variety of
sizes, allows for different degrees of access, enabling the
most appropriate unit to be utilized depending on duct
size and entry requirements. The 0800 Series features
rugged die-formed frames and double skin, insulated
door panels with an integral continuous bulb seal, as well
as progressive camlocks for tight, secure closure. Also
available are Nailors 0895 Series for round duct, 0900-2
Series universal access doors for drywall applications
and 0900-1 Series fire-rated access doors.
Refer to the Nailor Air Control Products catalog for a
complete selection of access door products.
Back
Home
Contents
Dimensions
Access Doors
Data
Spec
HOSPITAL/CLEANROOM DIFFUSERS
RADIAL PATTERN
DIFFUSERS
UNIQUE DESIGN
HIGH CAPACITY
HINGED FACE
STAINLESS STEEL
Models:
92RPD-2SS
180 Pattern
92RPD-1SS
90 Pattern
Model 92RPD-2SS
The Model 92RPD Series Radial Pattern Diffusers have been designed to provide low aspiration and high ventilation
rates especially for cleanroom applications such as research laboratories, bio-technology facilities, animal labs, food
processing, semi-conductor manufacturing, hospital rooms and computer rooms. The unique design of solid baffles in an
intrusive perforated face can handle large volumes of air with low initial face velocities.
The 92RPD-2SS model introduces air in a semi-cylindrical 180 degree radial flow pattern, flushing a room with large
volumes of clean conditioned air, minimizing entrainment and hence mixing with contaminated air, while still allowing low
room air velocities. The 92RPD-1SS model introduces air in a 90 degree radial flow pattern for perimeter applications.
FEATURES:
Unique curved face design is pleasing
to the eye. No unsightly sharp angles.
Engineered design and performance
are the result of extensive laboratory
testing.
Standard 92RPD-2SS model has a
true 180 radial air pattern.
Model 92RPD-1SS has a 90 radial
pattern for perimeter applications.
The face of the diffuser is attached
to the plenum with two stainless steel
hinges. The opposite side is secured
with 1/4 turn fasteners.
The diffuser face simply hinges
down for easy access to the interior
for cleaning and sanitation.
Back
Home
Contents
Dimensions
Data
Spec
OPTIONS:
316 Stainless Steel construction.
AW Appliance White finish.
This product is also available in
aluminum construction for less
demanding applications. Refer to the
Nailor Air Distribution Products
catalog.
HOSPITAL/CLEANROOM DIFFUSERS
CM = CEILING MODULE
CM - 1/4" (6)
NOMINAL ROUND DUCT DIA. D
NECK SIZE = D - 1/8" (3)
2 1/2
(64)
2 1/2"
(64)
PERFORATED FACE
6"
(152)
6"
(152)
HINGE
6"
(152)
HINGE
6"
(152)
PERFORATED FACE
BAFFLES
Imperial Modules
Imperial Units
S.I. Units
(inches)
(mm)
D
CM
D
CM
8
48 x 12
203
1219 x 305
8
24 x 24
203
610 x 610
12
48 x 24
305
1219 x 610
Home
Metric Modules
S.I. Units
(mm)
D
CM
203
1200 x 300
203
600 x 600
305
1200 x 600
HINGED
FACE WITH
1/4 TURN
FASTENERS
HINGED
FACE WITH
1/4 TURN
FASTENERS
Back
BAFFLES
Contents
Dimensions
CEILING MODULE
CM - 1/4" (6)
Data
Spec
HOSPITAL/CLEANROOM DIFFUSERS
92RPD-2SS - 08 - 24 x 24 - L - #3 - 316
MODEL
OPTIONS
- 180 Pattern
92RPD-2SS
- None (default)
- 90 Pattern
92RPD-1SS
316
FINISH
08 (203)
- #3 Satin Polished
12 (305)
- Appliance White
AW
- Special
SP
FRAME TYPE
#3
- Lay-in T-Bar
- 24 x 24 (610 x 610)
- Surface Mount
- 48 x 24 (1219 x 610)
Metric Modules (mm)
(Model 92RPD-1SS only)
- 1200 x 300
- 600 x 600
- 1200 x 600
SUGGESTED SPECIFICATION:
Furnish and install Nailor Model 92RPD-SS Radial Pattern Ceiling Diffusers of the size and type shown on the plans
and air distribution schedules. The diffusers shall be constructed entirely from 304 stainless steel (316 optional),
minimum 24 ga.. The perforated face of the diffuser shall have 13% free area with 3/32" (2.4) dia. holes on 1/4" (6)
staggered centers. The face shall have rounded corners and integral distribution baffles to provide a low velocity, nonaspirating radial air pattern. The face shall have 1/4 turn fasteners on one side and hinges on the other to allow for
access to the interior for cleaning. Integral earthquake hanger tabs shall be included with all units.
All exposed surfaces shall have a #3 satin polished finish.
The manufacturer shall provide published performance data for the diffuser, which shall be tested in accordance with
ANSI/ASHRAE Standard 70 1991.
Back
Home
Contents
Dimensions
Data
Spec
10
HOSPITAL/CLEANROOM DIFFUSERS
T Vertical Throw @
100
75
50
FPM
FPM
FPM
Airflow
CFM
Pt
Ps
NC
300
.101
.055
21
1.0
1.5
2.0
2.5
3.0
4.0
400
.179
.097
30
1.5
2.0
2.5
3.0
4.0
5.0
500
.280
.152
38
2.0
2.5
3.0
3.5
4.5
5.5
48" x 24" or 1200 mm x 600 mm Module Size 12" (305 mm) dia. Inlet T - 10F (5.5C)
T Horizontal Throw @
100
75
50
FPM
FPM
FPM
T Vertical Throw @
100
75
50
FPM
FPM
FPM
Airflow
CFM
Pt
Ps
NC
600
.072
.036
22
1.0
1.5
2.0
1.5
2.0
2.5
800
.129
.064
32
1.5
2.0
2.5
2.0
2.5
3.5
1000
.201
.100
41
2.0
2.5
3.5
2.5
3.0
4.5
CFM
FPM
Pt
Ps
T
NC
Performance Notes:
1. The radial flow pattern of the
92RPD-2SS is unlike conventional air
distribution devices. The data
presented above describes isovels by
average terminal velocity in both
horizontal and vertical directions.
2. T is the temperature difference
between supply and room air. Testing
is based on 10F (5.5C) cooling.
Back
Home
Contents
Dimensions
Data
Spec
11
HOSPITAL/CLEANROOM DIFFUSERS
T Vertical Throw @
0.51
0.38
0.25
M/S
M/S
M/S
Airflow
L/S
Pt
Ps
NC
142
25
14
21
0.3
0.5
0.6
0.8
0.9
1.2
189
44
24
30
0.5
0.6
0.8
0.9
1.2
1.5
236
70
38
38
0.6
0.8
0.9
1.1
1.4
1.7
1219 mm x 610 mm or 1200 mm x 600 mm Module Size 12" (305 mm) dia. Inlet T - 10F (5.5C)
T Horizontal Throw @
0.51
0.38
0.25
M/S
M/S
M/S
T Vertical Throw @
0.51
0.38
0.25
M/S
M/S
M/S
Airflow
L/S
Pt
Ps
NC
283
18
22
0.3
0.5
0.6
0.5
0.6
0.8
378
32
16
32
0.5
0.6
0.8
0.6
0.8
1.1
472
50
25
41
0.6
0.8
1.1
0.8
0.9
1.4
L/S
M/S
Pt
Ps
T
NC
Performance Notes:
1. The radial flow pattern of the
92RPD-2SS is unlike conventional air
distribution devices. The data
presented above describes isovels by
average terminal velocity in both
horizontal and vertical directions.
2. T is the temperature difference
between supply and room air. Testing
is based on 10F (5.5C) cooling.
Back
Home
Contents
Dimensions
Data
Spec
12
HOSPITAL/CLEANROOM DIFFUSERS
T Vertical Throw @
100
75
50
FPM
FPM
FPM
Airflow
CFM
Pt
Ps
NC
300
.114
.068
21
2.0
2.5
3.5
3.5
4.0
5.0
400
.203
.121
29
2.5
3.5
4.0
4.0
4.5
6.0
500
.317
.189
36
3.0
3.5
4.5
4.5
5.0
7.0
48" x 24" or 1200 mm x 600 mm Module Size 12" (305 mm) dia. Inlet T - 10F (5.5C)
T Horizontal Throw @
100
75
50
FPM
FPM
FPM
T Vertical Throw @
100
75
50
FPM
FPM
FPM
Airflow
CFM
Pt
Ps
NC
600
.082
.046
21
1.5
2.5
3.5
3.0
4.0
6.0
800
.146
.081
30
2.0
3.0
4.0
3.5
5.0
7.5
1000
.228
.127
38
2.5
3.0
4.5
4.5
6.0
8.5
48" x 12" or 1200 mm x 300 mm Module Size 8" (203 mm) dia. Inlet T - 10F (5.5C)
T Horizontal Throw @
100
75
50
FPM
FPM
FPM
T Vertical Throw @
100
75
50
FPM
FPM
FPM
Airflow
CFM
Pt
Ps
NC
300
.125
.079
22
1.5
2.0
3.0
1.0
1.5
2.0
400
.221
.139
30
2.0
2.5
3.5
2.0
2.5
3.5
500
.346
.218
37
2.5
3.5
4.5
2.5
3.0
4.0
CFM
FPM
Pt
Ps
T
NC
Performance Notes:
1. The radial flow pattern of the
92RPD-1SS is unlike conventional air
distribution devices. The data
presented above describes isovels by
average terminal velocity in both
horizontal and vertical directions.
Back
Home
Contents
Dimensions
Data
Spec
13
HOSPITAL/CLEANROOM DIFFUSERS
T Vertical Throw @
0.51
0.38
0.25
M/S
M/S
M/S
Airflow
L/S
Pt
Ps
NC
142
28
17
21
0.6
0.8
1.1
1.1
1.2
1.5
189
50
30
29
0.8
1.1
1.2
1.2
1.4
1.8
236
79
47
36
0.9
1.1
1.4
1.4
1.5
2.1
1219 mm x 610 mm or 1200 mm x 600 mm Module Size 12" (305 mm) dia. Inlet T - 10F (5.5C)
T Horizontal Throw @
0.51
0.38
0.25
M/S
M/S
M/S
T Vertical Throw @
0.51
0.38
0.25
M/S
M/S
M/S
Airflow
L/S
Pt
Ps
NC
283
20
11
21
0.5
0.8
1.1
0.9
1.2
1.8
378
36
20
30
0.6
0.9
1.2
1.1
1.5
2.3
472
57
32
38
0.8
0.9
1.4
1.4
1.8
2.6
1219 mm x 305 mm or 1200 mm x 300 mm Module Size 8" (203 mm) dia. Inlet T - 10F (5.5C)
T Horizontal Throw @
0.51
0.38
0.25
M/S
M/S
M/S
T Vertical Throw @
0.51
0.38
0.25
M/S
M/S
M/S
Airflow
L/S
Pt
Ps
NC
142
31
20
22
0.5
0.6
0.9
0.3
0.5
0.6
189
55
35
30
0.6
0.8
1.1
0.6
0.8
1.1
236
86
54
37
0.8
1.1
1.4
0.8
0.9
1.2
L/S
M/S
Pt
Ps
T
NC
Performance Notes:
1. The radial flow pattern of the
92RPD-1SS is unlike conventional air
distribution devices. The data
presented above describes isovels by
average terminal velocity in both
horizontal and vertical directions.
Back
Home
Contents
Dimensions
Data
Spec
14
HOSPITAL/CLEANROOM DIFFUSERS
RADIAL PATTERN
DIFFUSERS WITH FILTERS
UNIQUE DESIGN
HEPA OR ULPA FILTERS
HINGED FACE
STAINLESS STEEL
Models:
92RPDF-2SS
180 Pattern
92RPDF-1SS
90 Pattern
Model 92RPDF-2SS
The Model 92RPDF Series Radial Pattern Diffusers with Filters have been designed to provide low aspiration and high
ventilation rates especially for cleanroom applications such as research laboratories, bio-technology facilities, animal labs,
semi-conductor manufacturing, food processing, hospital rooms and computer rooms. The unique design of solid baffles in
an intrusive perforated face can handle large volumes of air with low initial face velocities. They are designed with an
integral 'knife-edge' frame to accommodate a Gel Seal HEPA or ULPA filter. The filters can be easily removed and replaced
from the face of the unit. These high quality filters incorporate a separatorless 2" (51) deep media, integral test port and an
anodized aluminum gel seal frame.
The 92RPDF-2SS model introduces air in a semi-cylindrical 180 degree radial flow pattern, flushing a room with large
volumes of clean conditioned air, minimizing entrainment and hence mixing with contaminated air, while still allowing low
room air velocities. The 92RPDF-1SS model introduces air in a 90 degree radial flow pattern for perimeter applications.
FEATURES:
Unique curved face design is pleasing
to the eye. No unsightly sharp angles.
Engineered design and performance
are the result of extensive laboratory
testing.
Standard 92RPDF-2SS model has a
true 180 radial air pattern.
Model 92RPDF-1SS has a 90 radial
pattern for perimeter applications.
The face of the diffuser is attached
to the plenum with two stainless steel
hinges. The opposite side is secured
with 1/4 turn fasteners.
The diffuser face simply hinges
down for easy access to the interior
for cleaning and sanitation.
Type 304 stainless steel perforated
face has 3/32" (2.4) dia. holes on 60
Back
Home
Contents
Dimensions
Data
Spec
15
HOSPITAL/CLEANROOM DIFFUSERS
Model Series 92RPDF-SS Radial Pattern Diffusers With Filters Dimensional Data
CM = CEILING MODULE
CM - 1/4" (6)
NOMINAL ROUND DUCT DIA. D
NECK SIZE = D - 1/8" (3)
CM = CEILING MODULE
CM - 1/4" (6)
NOMINAL ROUND DUCT DIA. D
NECK SIZE = D - 1/8" (3)
2 1/2"
(64)
2 1/2"
(64)
HEPA OR ULPA
FILTER
HEPA OR ULPA
FILTER
PERFORATED FACE
9"
(229)
9"
(229)
HINGE
6"
(152)
HINGE
6"
(152)
BAFFLES
PERFORATED FACE
Imperial Modules
Imperial Units
S.I. Units
(inches)
(mm)
D
CM
D
CM
8
48 x 12
203
1219 x 305
8
24 x 24
203
610 x 610
12
48 x 24
305
1219 x 610
CM - 1/4" (6)
CEILING OPENING
= CM 2 1/4" (57)
CEILING MODULE
CM - 1/4" (6)
GEL SEAL
GEL SEAL
Home
Metric Modules
S.I. Units
(mm)
D
CM
203
1200 x 300
203
600 x 600
305
1200 x 600
HINGED
FACE WITH
1/4 TURN
FASTENERS
HINGED
FACE WITH
1/4 TURN
FASTENERS
Back
BAFFLES
Contents
Dimensions
Data
Spec
16
HOSPITAL/CLEANROOM DIFFUSERS
92RPDF-2SS - 08 - 24 x 24 - L - #3 - 316
MODEL
OPTIONS
- 180 Pattern
92RPDF-2SS
- None (default)
- 90 Pattern
92RPDF-1SS
316
- HEPA Filter
(99.99% on 0.3 m)
HE
- ULPA Filter
(99.9995% on 0.12 m)
UL
FINISH
- #3 Satin Polished
#3
- Appliance White
AW
- Special
SP
FRAME TYPE
- Lay-in T-Bar
- Surface Mount
- 1200 x 600
SUGGESTED SPECIFICATION:
Furnish and install Nailor Model 92RPDF-SS Radial Pattern Ceiling Diffusers of the size and type shown on the
plans and air distribution schedules. The diffusers shall be constructed entirely from 304 stainless steel (316 optional),
minimum 24 ga.. The perforated face of the diffuser shall have 13% free area with 3/32" (2.4) dia. holes on 60 degree
1/4" (6) staggered centers. The face shall have rounded corners and integral distribution baffles to provide a low
velocity, non-aspirating radial air pattern. The face shall have 1/4 turn fasteners on one side and hinges on the other
to allow for access to the interior for cleaning. Integral earthquake hanger tabs shall be included with all units.
The diffuser plenum shall incorporate an integral filter frame to accommodate a Gel Seal filter. Filters shall be securely
held in place by at least four mounting brackets allowing filter removal from the face of the diffuser without disturbing
installed ductwork or the diffuser mounting surface. Filters shall incorporate a removable test port, to measure filter
pressure drop, perform leakage (scan) tests and to adjust the optional dampers without removing the filter. The filters
efficiency shall be HEPA: 99.99% minimum removal efficiency on 0.30 micrometer particle size (ULPA: 99.9995%
minimum removal efficiency on 0.12 micrometer particle size optional). Filters shall incorporate an anodized extruded
aluminum frame and a 2" (51) deep separatorless filter pack. All filters shall be UL 900 Class I Listed and Factory
Mutual Approved. All filters shall be individually scan tested per Section 6.2 of IEST-RP-CC034.1. Filters are to be
packaged independently from the diffuser for final installation of the filter in the field (by others).
All exposed surfaces shall have a #3 satin polished finish.
The manufacturer shall provide published performance data for the diffuser, which shall be tested in accordance with
ANSI/ASHRAE Standard 70 1991.
Back
Home
Contents
Dimensions
Data
Spec
17
HOSPITAL/CLEANROOM DIFFUSERS
Pt
Ps
100
.14
150
.32
200 *
.57
250
.89
295 ** 1.24
NC
.14
.31
.55
.86
1.19
16
19
22
T Horizontal
Throw @
100
75
50
FPM FPM FPM
0.5
0.5
1.0
0.5
1.0
1.0
0.5
1.0
1.5
1.0
1.5
2.0
1.0
1.5
2.0
T Vertical
Throw @
100
75
50
FPM FPM FPM
0.5
1.0
1.5
1.0
1.0
2.0
1.5
2.0
3.0
2.0
2.5
3.5
2.5
3.0
4.0
48" x 24" or 1200 mm x 600 mm Module Size 12" (305 mm) dia. Inlet T 10F (5.5C)
Airflow
CFM
Pt
Ps
300
.22
400
.40
500 *
.62
600
.90
715 ** 1.27
CFM
FPM
Pt
Ps
T
NC
.22
.38
.60
.86
1.22
NC
19
23
28
T Horizontal
Throw @
100
75
50
FPM FPM FPM
0.5
0.5
1.0
0.5
1.0
1.5
1.0
1.0
1.5
1.0
1.5
2.0
1.5
2.0
2.5
T Vertical
Throw @
100
75
50
FPM FPM FPM
0.5
1.0
1.5
0.5
1.0
2.0
1.0
1.5
2.0
1.5
2.0
2.5
2.0
2.5
3.0
Performance Notes:
1. The radial flow pattern of the
92RPDF-2SS is unlike conventional
air distribution devices. The data
presented above describes isovels by
average terminal velocity in both
horizontal and vertical directions.
2. T is the temperature difference
between supply and room air. Testing
is based on 10F (5.5C) cooling.
3. Performance data is for diffusers with
clean filters. Filters may be operated up
to a final resistance of 2" w.g. (500 Pa).
Back
Home
Contents
Dimensions
Data
Spec
18
HOSPITAL/CLEANROOM DIFFUSERS
Pt
Ps
NC
47
35
71
80
94 * 142
118
221
139 ** 308
35
77
137
214
296
16
19
22
T Horizontal
Throw @
0.51 0.38 0.25
M/S M/S M/S
0.2
0.2
0.3
0.2
0.3
0.3
0.2
0.3
0.5
0.3
0.5
0.6
0.3
0.5
0.6
T Vertical
Throw @
0.51 0.38 0.25
M/S M/S M/S
0.2
0.3
0.5
0.3
0.3
0.6
0.5
0.6
0.9
0.6
0.8
1.1
0.8
0.9
1.2
1219 mm x 610 mm or 1200 mm x 600 mm Module Size 12" (305 mm) dia. Inlet T 10F (5.5C)
Airflow
L/S
Pt
Ps
NC
142
55
189
99
236 * 154
283
224
337 ** 316
55
94
149
214
303
19
23
28
L/S
M/S
Pt
Ps
T
NC
T Horizontal
Throw @
0.51 0.38 0.25
M/S M/S M/S
0.2
0.2
0.3
0.2
0.3
0.5
0.3
0.3
0.5
0.3
0.5
0.6
0.5
0.6
0.8
T Vertical
Throw @
0.51 0.38 0.25
M/S M/S M/S
0.2
0.3
0.5
0.2
0.3
0.6
0.3
0.5
0.6
0.5
0.6
0.8
0.6
0.8
0.9
Performance Notes:
1. The radial flow pattern of the
92RPDF-2SS is unlike conventional
air distribution devices. The data
presented above describes isovels by
average terminal velocity in both
horizontal and vertical directions.
2. T is the temperature difference
between supply and room air. Testing
is based on 10F (5.5C) cooling.
3. Performance data is for diffusers with
clean filters. Filters may be operated up
to a final resistance of 2" w.g. (500 Pa).
Back
Home
Contents
Dimensions
Data
Spec
19
HOSPITAL/CLEANROOM DIFFUSERS
Pt
Ps
100
.14
150
.32
200 *
.57
250
.89
295 ** 1.24
NC
.14
.31
.55
.86
1.19
16
19
22
T Horizontal
Throw @
100
75
50
FPM FPM FPM
0.5
1.0
1.5
1.0
1.5
2.0
1.5
2.0
2.5
2.0
2.5
3.0
2.0
2.5
3.5
T Vertical
Throw @
100
75
50
FPM FPM FPM
1.0
1.5
2.5
2.0
2.5
3.5
2.5
3.5
4.0
3.0
3.5
4.5
3.5
4.0
5.0
48" x 24" or 1200 mm x 600 mm Module Size 12" (305 mm) dia. Inlet T 10F (5.5C)
Airflow
CFM
Pt
Ps
300
.23
400
.40
500 *
.63
600
.91
715 ** 1.29
NC
.22
.39
.60
.87
1.23
19
23
28
T Horizontal
Throw @
100
75
50
FPM FPM FPM
0.5
1.0
1.5
1.0
1.5
2.0
1.0
2.0
3.0
1.5
2.5
3.5
2.0
3.0
4.0
T Vertical
Throw @
100
75
50
FPM FPM FPM
1.5
2.0
2.5
2.0
3.0
4.0
2.5
3.5
5.0
3.0
4.0
6.0
3.5
4.5
6.5
48" x 12" or 1200 mm x 300 mm Module Size 8" (203 mm) dia. Inlet T 10F (5.5C)
Airflow
CFM
Pt
Ps
100
.14
150
.33
200 *
.58
250
.90
290 ** 1.22
CFM
FPM
Pt
Ps
T
NC
.14
.31
.56
.87
1.17
NC
17
20
23
T Horizontal
Throw @
100
75
50
FPM FPM FPM
0.5
0.5
1.0
0.5
1.0
1.5
1.0
1.5
2.0
1.0
1.5
2.5
1.5
2.0
3.0
Performance Notes:
1. The radial flow pattern of the
92RPDF-1SS is unlike conventional
air distribution devices. The data
presented above describes isovels by
average terminal velocity in both
horizontal and vertical directions.
Back
Home
Contents
T Vertical
Throw @
100
75
50
FPM FPM FPM
0.5
0.5
1.0
0.5
1.0
1.5
0.5
1.0
1.5
1.0
1.5
2.0
1.0
1.5
2.0
Dimensions
Data
Spec
20
HOSPITAL/CLEANROOM DIFFUSERS
Pt
Ps
NC
47
35
71
80
94 * 142
118
221
139 ** 308
35
77
137
214
296
16
19
22
T Horizontal
Throw @
0.51 0.38 0.25
M/S M/S M/S
0.2
0.3
0.5
0.3
0.5
0.6
0.5
0.6
0.8
0.6
0.8
0.9
0.6
0.8
1.1
T Vertical
Throw @
0.51 0.38 0.25
M/S M/S M/S
0.3
0.5
0.8
0.6
0.8
1.1
0.8
1.1
1.2
0.9
1.1
1.4
1.1
1.2
1.5
1219 mm x 610 mm or 1200 mm x 600 mm Module Size 12" (305 mm) dia. Inlet T 10F (5.5C)
Airflow
L/S
Pt
Ps
NC
142
57
189
99
236 * 157
283
226
337 ** 321
55
97
149
216
306
19
23
28
T Horizontal
Throw @
0.51 0.38 0.25
M/S M/S M/S
0.2
0.3
0.5
0.3
0.5
0.6
0.3
0.6
0.9
0.5
0.8
1.1
0.6
0.9
1.2
T Vertical
Throw @
0.51 0.38 0.25
M/S M/S M/S
0.5
0.6
0.8
0.6
0.9
1.2
0.8
1.1
1.5
0.9
1.2
1.8
1.1
1.4
2.0
1219 mm x 305 mm or 1200 x 300 mm Module Size 8" (203 mm) dia. Inlet T 10F (5.5C)
Airflow
L/S
Pt
Ps
NC
47
35
71
82
94 * 144
118
224
137 ** 303
35
77
139
216
291
17
20
23
L/S
M/S
Pt
Ps
T
NC
T Horizontal
Throw @
0.51 0.38 0.25
M/S M/S M/S
0.2
0.2
0.3
0.2
0.3
0.5
0.3
0.5
0.6
0.3
0.5
0.8
0.5
0.6
0.9
Performance Notes:
1. The radial flow pattern of the
92RPDF-1SS is unlike conventional
air distribution devices. The data
presented above describes isovels by
average terminal velocity in both
horizontal and vertical directions.
Back
Home
Contents
T Vertical
Throw @
0.51 0.38 0.25
M/S M/S M/S
0.2
0.2
0.3
0.2
0.3
0.5
0.2
0.3
0.5
0.3
0.5
0.6
0.3
0.5
0.6
Dimensions
Data
Spec
21
HOSPITAL/CLEANROOM DIFFUSERS
Pt
Ps
100
.17
150
.38
200 *
.68
250
1.06
295 ** 1.47
NC
.16
.37
.66
1.02
1.43
16
19
22
T Horizontal
Throw @
100
75
50
FPM FPM FPM
0.5
0.5
1.0
0.5
1.0
1.0
0.5
1.0
1.5
1.0
1.5
2.0
1.0
1.5
2.0
T Vertical
Throw @
100
75
50
FPM FPM FPM
0.5
1.0
1.5
1.0
1.0
2.0
1.5
2.0
3.0
2.0
2.5
3.5
2.5
3.0
4.0
48" x 24" or 1200 mm x 600 mm Module Size 12" (305 mm) dia. Inlet T 10F (5.5C)
Airflow
CFM
Pt
Ps
300
.27
400
.48
500 *
.74
600
1.07
715 ** 1.52
CFM
FPM
Pt
Ps
T
NC
.26
.46
.72
1.03
1.47
NC
19
23
28
T Horizontal
Throw @
100
75
50
FPM FPM FPM
0.5
0.5
1.0
0.5
1.0
1.5
1.0
1.0
1.5
1.0
1.5
2.0
1.5
2.0
2.5
T Vertical
Throw @
100
75
50
FPM FPM FPM
0.5
1.0
1.5
0.5
1.0
2.0
1.0
1.5
2.0
1.5
2.0
2.5
2.0
2.5
3.0
Performance Notes:
1. The radial flow pattern of the
92RPDF-2SS is unlike conventional
air distribution devices. The data
presented above describes isovels by
average terminal velocity in both
horizontal and vertical directions.
2. T is the temperature difference
between supply and room air. Testing
is based on 10F (5.5C) cooling.
3. Performance data is for diffusers with
clean filters. Filters may be operated up
to a final resistance of 2" w.g. (500 Pa).
Back
Home
Contents
Dimensions
Data
Spec
22
HOSPITAL/CLEANROOM DIFFUSERS
Pt
Ps
NC
47
42
71
94
94 * 169
118
264
139 ** 365
40
92
164
254
355
16
19
22
T Horizontal
Throw @
0.51 0.38 0.25
M/S M/S M/S
0.2
0.2
0.3
0.2
0.3
0.3
0.2
0.3
0.5
0.3
0.5
0.6
0.3
0.5
0.6
T Vertical
Throw @
0.51 0.38 0.25
M/S M/S M/S
0.2
0.3
0.5
0.3
0.3
0.6
0.5
0.6
0.9
0.6
0.8
1.1
0.8
0.9
1.2
1219 mm x 610 mm or 1200 mm x 600 mm Module Size 12" (305 mm) dia. Inlet T 10F (5.5C)
Airflow
L/S
142
189
236 *
283
337 **
L/S
M/S
Pt
Ps
T
NC
Pt
Ps
NC
67
119
184
266
378
65
114
179
256
365
19
23
28
T Horizontal
Throw @
0.51 0.38 0.25
M/S M/S M/S
0.2
0.2
0.3
0.2
0.3
0.5
0.3
0.3
0.5
0.3
0.5
0.6
0.5
0.6
0.8
T Vertical
Throw @
0.51 0.38 0.25
M/S M/S M/S
0.2
0.3
0.5
0.2
0.3
0.6
0.3
0.5
0.6
0.5
0.6
0.8
0.6
0.8
0.9
Performance Notes:
1. The radial flow pattern of the
92RPDF-2SS is unlike conventional
air distribution devices. The data
presented above describes isovels by
average terminal velocity in both
horizontal and vertical directions.
2. T is the temperature difference
between supply and room air. Testing
is based on 10F (5.5C) cooling.
3. Performance data is for diffusers with
clean filters. Filters may be operated up
to a final resistance of 2" w.g. (500 Pa).
Back
Home
Contents
Dimensions
Data
Spec
23
HOSPITAL/CLEANROOM DIFFUSERS
Pt
100
.17
150
.38
200 *
.68
250
1.07
295 ** 1.49
Ps
NC
.17
.37
.66
1.03
1.44
16
19
22
T Horizontal
Throw @
100
75
50
FPM FPM FPM
0.5
1.0
1.5
1.0
1.5
2.0
1.5
2.0
2.5
2.0
2.5
3.0
2.0
2.5
3.5
T Vertical
Throw @
100
75
50
FPM FPM FPM
1.0
1.5
2.5
2.0
2.5
3.5
2.5
3.5
4.0
3.0
3.5
4.5
3.5
4.0
5.0
48" x 24" or 1200 mm x 600 mm Module Size 12" (305 mm) dia. Inlet T 10F (5.5C)
Airflow
CFM
Pt
300
.27
400
.48
500 *
.75
600
1.08
715 ** 1.53
Ps
NC
.26
.46
.72
1.04
1.48
19
23
28
T Horizontal
Throw @
100
75
50
FPM FPM FPM
0.5
1.0
1.5
1.0
1.5
2.0
1.0
2.0
3.0
1.5
2.5
3.5
2.0
3.0
4.0
T Vertical
Throw @
100
75
50
FPM FPM FPM
1.5
2.0
2.5
2.0
3.0
4.0
2.5
3.5
5.0
3.0
4.0
6.0
3.5
4.5
6.5
48" x 12" or 1200 mm x 300 mm Module Size 8" (203 mm) dia. Inlet T 10F (5.5C)
Airflow
CFM
Pt
100
.17
150
.39
200 *
.69
250
1.08
290 ** 1.45
CFM
FPM
Pt
Ps
T
NC
Ps
NC
.17
.38
.67
1.04
1.40
17
20
23
T Horizontal
Throw @
100
75
50
FPM FPM FPM
0.5
0.5
1.0
0.5
1.0
1.5
1.0
1.5
2.0
1.0
1.5
2.5
1.5
2.0
3.0
Performance Notes:
1. The radial flow pattern of the
92RPDF-1SS is unlike conventional
air distribution devices. The data
presented above describes isovels by
average terminal velocity in both
horizontal and vertical directions.
Back
Home
Contents
T Vertical
Throw @
100
75
50
FPM FPM FPM
0.5
0.5
1.0
0.5
1.0
1.5
0.5
1.0
1.5
1.0
1.5
2.0
1.0
1.5
2.0
Dimensions
Data
Spec
24
HOSPITAL/CLEANROOM DIFFUSERS
Pt
Ps
47
42
71
94
94 * 169
118
266
139 ** 370
42
92
164
256
358
NC
16
19
22
T Horizontal
Throw @
0.51 0.38 0.25
M/S M/S M/S
0.2
0.3
0.5
0.3
0.5
0.6
0.5
0.6
0.8
0.6
0.8
0.9
0.6
0.8
1.1
T Vertical
Throw @
0.51 0.38 0.25
M/S M/S M/S
0.3
0.5
0.8
0.6
0.8
1.1
0.8
1.1
1.2
0.9
1.1
1.4
1.1
1.2
1.5
1219 mm x 610 mm or 1200 mm x 600 mm Module Size 12" (305 mm) dia. Inlet T 10F (5.5C)
Airflow
L/S
142
189
236 *
283
337 **
Pt
Ps
67
119
186
268
380
65
114
179
259
368
NC
19
23
28
T Horizontal
Throw @
0.51 0.38 0.25
M/S M/S M/S
0.2
0.3
0.5
0.3
0.5
0.6
0.3
0.6
0.9
0.5
0.8
1.1
0.6
0.9
1.2
T Vertical
Throw @
0.51 0.38 0.25
M/S M/S M/S
0.5
0.6
0.8
0.6
0.9
1.2
0.8
1.1
1.5
0.9
1.2
1.8
1.1
1.4
2.0
1219 mm x 305 mm or 1200 mm x 300 mm Module Size 8" (203 mm) dia. Inlet T 10F (5.5C)
Airflow
L/S
Pt
Ps
47
42
71
97
94 * 172
118
268
137 ** 360
42
94
167
259
348
L/S
M/S
Pt
Ps
T
NC
NC
17
20
23
T Horizontal
Throw @
0.51 0.38 0.25
M/S M/S M/S
0.2
0.2
0.3
0.2
0.3
0.5
0.3
0.5
0.6
0.3
0.5
0.8
0.5
0.6
0.9
Performance Notes:
1. The radial flow pattern of the
92RPDF-1SS is unlike conventional
air distribution devices. The data
presented above describes isovels by
average terminal velocity in both
horizontal and vertical directions.
Back
Home
Contents
T Vertical
Throw @
0.51 0.38 0.25
M/S M/S M/S
0.2
0.2
0.3
0.2
0.3
0.5
0.2
0.3
0.5
0.3
0.5
0.6
0.3
0.5
0.6
Dimensions
Data
Spec
25
HOSPITAL/CLEANROOM DIFFUSERS
RADIAL PATTERN
DIFFUSERS
Models:
92FRP-2SS
180 Pattern
92FRP-1SS
90 Pattern
Model 92FRP-2SS
The Model 92FRP-SS Flush Face Radial Pattern Diffusers have been designed to provide low aspiration at high
ventilation rates especially for cleanroom applications such as research laboratories, bio-technology facilities, animal labs,
food processing, semi-conductor manufacturing, hospital rooms and computer rooms. Specially designed internal baffles
and pressure plate produce an excellent radial air pattern that allows large volumes of air to be supplied at low velocities.
The unobtrusive flush face design provides the smooth appearance required for architectural excellence.
The 92FRP-2SS model introduces air in a semi-cylindrical 180 degree radial flow pattern, flushing a room with large
volumes of clean conditioned air, minimizing entrainment and hence mixing with contaminated air, while still allowing low
room air velocities. The 92FRP-1SS model introduces air in a 90 degree radial flow pattern for perimeter applications.
FEATURES:
Unique, architecturally appealing
flush face design.
Face plate is removable for
cleaning and is secured by 1/4 turn
fasteners.
Safety cables are included as
standard and prevent accidental
dropping of removable face.
Perforated face has 3/16" (5) dia.
holes on 1/4" (6) staggered centers
(51% free area).
Back
Home
Contents
Dimensions
Data
Spec
OPTIONS:
316 Stainless Steel construction.
AW Appliance White finish.
This product is also available in
steel and aluminum for less
demanding applications. Contact
your local Nailor representative for
more information.
26
HOSPITAL/CLEANROOM DIFFUSERS
W - 1/4" (6)
L - 1/4" (6)
L - 2 3/4" (70)
D - 1/8" (3)
STANDARD
SAFETY
CABLE
PERFORATED
FACE
6" (152)
2 1/2" (64)
36 x 24
48 x 24
60 x 24
900 x 600 1200 x 600 1500 x 600
6, 7,
7, 8,
10,
8, 10
10, 12
12
152, 178, 178, 203,
254,
203, 254 254, 305
305
CEILING OPENING
= CM 2 1/4" (57)
CM - 1/4" (6)
Back
Home
Contents
Dimensions
Data
Spec
27
HOSPITAL/CLEANROOM DIFFUSERS
W - 1/4" (6)
L - 1/4" (6)
L - 2 3/4" (70)
D - 1/8" (3)
STANDARD
SAFETY
CABLE
PERFORATED
FACE
6" (152)
2 1/2" (64)
36 x 24
48 x 24
60 x 24
900 x 600 1200 x 600 1500 x 600
6, 7,
7, 8,
10,
8, 10
10, 12
12
152, 178, 178, 203,
254,
203, 254 254, 305
305
CEILING OPENING
= CM 2 1/4" (57)
CM - 1/4" (6)
Back
Home
Contents
Dimensions
Data
Spec
28
HOSPITAL/CLEANROOM DIFFUSERS
92FRP-2SS - 08 - 24 x 24 - L - #3 - 316
MODEL
OPTIONS
- 180 Pattern
92FRP-2SS
- None (default)
- 90 Pattern
92FRP-1SS
316
FINISH
06 (152)
- #3 Satin Polished
07 (178)
- Appliance White
AW
08 (203)
- Special
SP
10 (254)
FRAME TYPE
12 (305)
- Lay-in T-Bar
- Surface Mount
#3
SUGGESTED SPECIFICATION:
Furnish and install Nailor Model 92FRP-SS Flush Face Radial Pattern Ceiling Diffusers of the size and type shown
on the plans and air distribution schedules. The diffusers shall be constructed entirely from 304 stainless steel (316
optional), minimum 24 ga.. The perforated face of the diffuser shall have 51% free area with 3/16" (5) dia. holes on
1/4" (6) staggered centers. Integral distribution baffles and pressure plate shall be attached to the face to provide a
low velocity, non-aspirating radial air pattern. The face shall be attached with 1/4 turn fasteners to allow for complete
removal and access to the interior for cleaning. All diffusers are to include safety cables to prevent accidental dropping
of the removable face. Integral earthquake hanger tabs shall be included with all units.
All exposed surfaces shall have a #3 satin polished finish.
The manufacturer shall provide published performance data for the diffuser, which shall be tested in accordance with
ANSI/ASHRAE Standard 70 1991.
Back
Home
Contents
Dimensions
Data
Spec
29
HOSPITAL/CLEANROOM DIFFUSERS
Pt
Ps
NC
200
300
400
500
600
.058
.131
.233
.365
.525
.037
.082
.146
.228
.329
20
29
36
43
50
100
FPM
1
2
3
4
4
75
FPM
2
3
5
6
7
24" x 24" or 600 mm x 600 mm Module Size 10" (254 mm) dia. Inlet
T Spread
Airflow
CFM
Pt
Ps
NC
200
300
400
500
600
.026
.058
.104
.162
.233
.017
.039
.068
.107
.154
20
20
24
29
38
100
FPM
1
1
2
3
4
75
FPM
1
2
3
5
6
48" x 24" or 1200 mm x 600 mm Module Size 10" (254 mm) dia. Inlet
T Spread
Airflow
CFM
Pt
Ps
NC
400
500
600
700
800
900
.099
.155
.223
.304
.397
.502
.064
.100
.144
.196
.256
.324
20
24
30
38
45
51
100
FPM
3
4
5
5
6
6
75
FPM
4
5
6
7
8
9
48" x 24" or 1200 mm x 600 mm Module Size 12" (305 mm) dia. Inlet
T Spread
Airflow
CFM
Pt
Ps
NC
500
600
700
800
900
1000
.083
.119
.163
.212
.269
.332
.057
.082
.111
.145
.183
.226
20
24
29
34
40
46
CFM
FPM
Pt
Ps
T
NC
100
FPM
2
2
3
3
4
4
Back
Home
Contents
75
FPM
3
3
4
5
6
8
Performance Notes:
1. The radial flow pattern of the
92FRP-2SS is unlike conventional air
distribution devices. The data
presented above describes isovels by
average terminal velocity in both
horizontal and vertical directions.
Dimensions
Data
Spec
30
HOSPITAL/CLEANROOM DIFFUSERS
Pt
Ps
NC
94
142
189
236
283
14
33
58
91
131
9
20
36
57
82
20
29
36
43
50
0.51
M/S
0.3
0.6
0.9
1.2
1.2
0.38
M/S
0.6
0.9
1.5
1.8
2.1
T Vertical Throw @
3C T
0.25 0.51 0.38 0.25
M/S M/S M/S M/S
1.2
0.3
0.3
0.3
1.8
0.3
0.6
0.6
2.1
0.3
0.9
1.2
2.4
0.6
0.9
1.8
2.7
0.9
1.2
2.1
610 mm x 610 mm or 600 mm x 600 mm Module Size 10" (254 mm) dia. Inlet
T Spread
Airflow
L/S
Pt
Ps
NC
94
142
189
236
283
6
14
26
40
58
4
10
17
27
38
20
20
24
29
38
0.51
M/S
0.3
0.3
0.6
0.9
1.2
0.38
M/S
0.3
0.6
0.9
1.5
1.8
T Vertical Throw @
3C T
0.25 0.51 0.38 0.25
M/S M/S M/S M/S
0.6
0.3
0.3
0.3
1.2
0.3
0.6
0.6
1.8
0.3
0.9
1.5
2.4
0.6
1.2
1.8
2.7
0.9
1.5
2.4
1219 mm x 610 mm or 1200 mm x 600 mm Module Size 10" (254 mm) dia. Inlet
T Spread
Airflow
L/S
Pt
Ps
NC
189
236
283
330
378
425
25
39
55
76
99
125
16
25
36
49
64
81
20
24
30
38
45
51
0.51
M/S
0.9
1.2
1.5
1.5
1.8
1.8
0.38
M/S
1.2
1.5
1.8
2.1
2.4
2.7
T Vertical Throw @
3C T
0.25 0.51 0.38 0.25
M/S M/S M/S M/S
2.1
0.3
0.3
0.6
2.4
0.3
0.6
0.9
2.7
0.3
0.6
1.2
2.7
0.6
0.6
1.5
3.0
0.6
0.9
1.5
3.4
0.6
1.2
1.8
1219 mm x 610 mm or 1200 mm x 600 mm Module Size 12" (305 mm) dia. Inlet
T Spread
Airflow
L/S
Pt
Ps
NC
236
283
330
378
425
472
21
30
41
53
67
83
14
20
28
36
45
56
20
24
29
34
40
46
L/S
M/S
Pt
Ps
T
NC
0.51
M/S
0.6
0.6
0.9
0.9
1.2
1.2
0.38
M/S
0.9
0.9
1.2
1.5
1.8
2.4
Back
Home
Contents
T Vertical Throw @
3C T
0.25 0.51 0.38 0.25
M/S M/S M/S M/S
1.2
0.3
0.6
0.9
1.8
0.3
0.6
1.2
2.4
0.3
0.6
1.5
2.7
0.6
0.9
1.5
3.0
0.6
1.2
1.8
3.4
0.9
1.5
2.1
Performance Notes:
1. The radial flow pattern of the
92FRP-2SS is unlike conventional air
distribution devices. The data
presented above describes isovels by
average terminal velocity in both
horizontal and vertical directions.
Dimensions
Data
Spec
31
HOSPITAL/CLEANROOM DIFFUSERS
Pt
Ps
NC
200
300
400
500
600
.054
.121
.215
.336
.484
.032
.072
.128
.200
.288
20
26
35
41
45
100
FPM
1
1
2
3
4
75
FPM
2
3
3
4
5
24" x 24" or 600 mm x 600 mm Module Size 10" (254 mm) dia. Inlet
T Spread
Airflow
CFM
Pt
Ps
NC
200
300
400
500
600
.025
.056
.099
.155
.223
.016
.036
.064
.100
.144
20
20
28
33
36
100
FPM
1
2
3
4
4
75
FPM
2
3
4
5
6
48" x 24" or 1200 mm x 600 mm Module Size 10" (254 mm) dia. Inlet
T Spread
Airflow
CFM
Pt
Ps
NC
400
500
600
700
800
900
.096
.150
.216
.294
.383
.485
.061
.095
.136
.186
.242
.307
24
28
33
37
41
46
100
FPM
1
1
2
2
3
3
75
FPM
2
2
2
3
4
4
48" x 24" or 1200 mm x 600 mm Module Size 12" (305 mm) dia. Inlet
T Spread
Airflow
CFM
Pt
Ps
NC
500
600
700
800
900
1000
.079
.114
.155
.202
.256
.316
.053
.076
.103
.135
.171
.211
20
23
27
31
37
44
CFM
FPM
Pt
Ps
T
NC
100
FPM
1
2
3
3
3
4
Back
Home
Contents
75
FPM
2
3
3
4
4
5
Performance Notes:
1. The radial flow pattern of the
92FRP-1SS is unlike conventional air
distribution devices. The data
presented above describes isovels by
average terminal velocity in both
horizontal and vertical directions.
Dimensions
Data
Spec
32
HOSPITAL/CLEANROOM DIFFUSERS
Pt
Ps
NC
94
142
189
236
283
13
30
53
84
120
8
18
32
50
72
20
26
35
41
45
0.51
M/S
0.3
0.3
0.6
0.9
1.2
0.38
M/S
0.6
0.9
0.9
1.2
1.5
T Vertical Throw @
3C T
0.25 0.51 0.38 0.25
M/S M/S M/S M/S
0.9
0.3
0.3
0.6
1.2
0.3
0.6
0.9
1.2
0.6
0.9
1.5
1.5
0.6
1.2
1.8
1.8
0.9
1.2
2.1
610 mm x 610 mm or 600 mm x 600 mm Module Size 10" (254 mm) dia. Inlet
T Spread
Airflow
L/S
Pt
Ps
NC
94
142
189
236
283
6
14
25
39
55
4
9
16
25
36
20
20
28
33
36
0.51
M/S
0.3
0.6
0.9
1.2
1.2
0.38
M/S
0.6
0.9
1.2
1.5
1.8
T Vertical Throw @
3C T
0.25 0.51 0.38 0.25
M/S M/S M/S M/S
1.2
0.3
0.3
0.6
1.5
0.3
0.6
0.9
1.8
0.6
0.9
1.5
2.1
0.6
1.2
2.1
2.4
1.2
1.8
2.4
1219 mm x 610 mm or 1200 mm x 600 mm Module Size 10" (254 mm) dia. Inlet
T Spread
Airflow
L/S
Pt
Ps
NC
189
236
283
330
378
425
24
37
54
73
95
121
15
24
34
46
60
76
24
28
33
37
41
46
0.51
M/S
0.3
0.3
0.6
0.6
0.9
0.9
0.38
M/S
0.6
0.6
0.6
0.9
1.2
1.2
T Vertical Throw @
3C T
0.25 0.51 0.38 0.25
M/S M/S M/S M/S
0.9
0.6
1.2
1.8
0.9
0.9
1.2
1.8
1.2
0.9
1.5
2.1
1.2
1.2
1.5
2.1
1.5
1.2
1.8
2.4
1.8
1.5
1.8
2.4
1219 mm x 610 mm or 1200 mm x 600 mm Module Size 12" (305 mm) dia. Inlet
T Spread
Airflow
L/S
Pt
Ps
NC
236
283
330
378
425
472
20
28
39
50
64
79
13
19
26
34
43
52
20
23
27
31
37
44
L/S
M/S
Pt
Ps
T
NC
0.51
M/S
0.3
0.6
0.9
0.9
0.9
1.2
0.38
M/S
0.6
0.9
0.9
1.2
1.2
1.5
Back
Home
Contents
T Vertical Throw @
3C T
0.25 0.51 0.38 0.25
M/S M/S M/S M/S
0.9
0.9
1.2
2.1
1.2
1.2
1.5
2.1
1.5
1.2
1.8
2.4
1.5
1.5
2.1
2.4
1.8
1.8
2.1
2.7
2.1
2.1
2.4
2.7
Performance Notes:
1. The radial flow pattern of the
92FRP-1SS is unlike conventional air
distribution devices. The data
presented above describes isovels by
average terminal velocity in both
horizontal and vertical directions.
Dimensions
Data
Spec
33
HOSPITAL/CLEANROOM DIFFUSERS
LAMINAR FLOW
CEILING DIFFUSERS
PROVEN TECHNOLOGY
REMOVABLE PERFORATED
FACE
INTEGRAL VOLUME DAMPER
UNIDIRECTIONAL AIRFLOW
Models:
92LFD-SS
Stainless Steel
Model 92LFD-SS
The Nailor 92LFD-SS Series Laminar Flow Diffusers utilize the well-proven and time-tested concept of vertical air mass
'laminar flow' technology. The 92LFD-SS Series produce a non-aspirating, low velocity, uniformly distributed downward
moving 'piston' of conditioned air.
They may be used individually, or as in the case of hospital operating rooms, several units may be banked together to sufficiently
cover the area and produce one large combined laminar mass. Installed in an operating room above the operating table,
the clean conditioned air flows over and blankets the operating table, helping to protect and effectively isolate the patient
from contaminated air. The only significant amount of room air entrainment occurs at the outer boundary of the laminar flow
mass, outside the confines of the operating table. The patient is therefore bathed in 'clean air' and effectively isolated from
secondary room air and any airborne contaminants.
The advantages of Laminar Flow technology provide similar benefits in other 'cleanroom' applications such as research
laboratories, bio-technology facilities, animal laboratories, food processing plants, semi-conductor manufacturing,
pharmaceutical laboratories and protective environment rooms.
The ability of the 92LFD-SS to maintain a sterile environment directly below is enhanced by the use of low level exhaust
grilles located around the room periphery which remove the contaminated air before it can react with the boundary layer of
the laminar flow mass.
A more recent application has been their use in computer rooms, where localized heavy cooling loads present a problem.
The 92LFD-SS, when installed overhead, cools the load source directly, without creating objectionable high velocities in
the occupied zone.
FEATURES:
Face plate is removable for cleaning
and is secured by 1/4 turn fasteners.
Safety cables are included as
standard and prevent accidental
dropping of the removable face.
Perforated face has 3/32" (2.4) dia.
holes on 60 degree 1/4" (6) staggered
centers (13% free area).
Integral pressure plate ensures true
laminar airflow.
Round inlets for simple duct
connection.
Back
Home
Contents
Dimensions
Data
Spec
OPTIONS:
316 Stainless Steel construction.
AW Appliance White finish.
This product is also available in
steel and aluminum for less
demanding applications. Refer to
the Nailor Air Distribution Products
Catalog.
Higher capacity versions of this
product are also available. Contact
your local Nailor representative for
more information.
34
HOSPITAL/CLEANROOM DIFFUSERS
W - 1/4" (6)
REMOVABLE
PLUG FOR
SCREWDRIVER
ACCESS
L - 1/4" (6)
L - 2 3/4" (70)
D - 1/8" (3)
STANDARD
SAFETY
CABLE
2 1/2" (64)
6" (152)
PERFORATED
PRESSURE
PLATE
Model 92LFD-SS
Ceiling Module Sizes L x W & Nominal Round Duct Sizes D
L
x
W
72 x 12
1800 x 300
6, 7,
8
152, 178,
203
24 x 24
36 x 24
48 x 24
600 x 600 900 x 600 1200 x 600
6, 7,
6, 7, 8
7, 8,
8
10, 12
10, 12
152, 178, 152, 178, 203 178, 203,
203
254, 305
254, 305
Back
Home
60 x 24
72 x 24
1500 x 600 1800 x 600
10,
10,
12
12
254,
254,
305
305
Contents
Dimensions
CEILING MODULE
CM - 1/4" (6)
Data
Spec
35
HOSPITAL/CLEANROOM DIFFUSERS
92LFD-SS - 08 - 48 x 24 - L - #3 - 316
MODEL
OPTIONS
92LFD-SS
- None (default)
INLET SIZE
316
FINISH
- Appliance White
AW
SP
#3
- 48 x 12
(1219 x 305)
- Special
- 60 x 12
(1524 x 305)
FRAME TYPE
- 72 x 12
(1829 x 305)
- Lay-in T-Bar
- 24 x 24
(610 x 610)
- Surface Mount
- 36 x 24
(914 x 610)
- 48 x 24
(1219 x 610)
- 60 x 24
(1524 x 610)
- 72 x 24
(1829 x 610)
SUGGESTED SPECIFICATION:
Furnish and install Nailor Model 92LFD-SS Laminar Flow Ceiling Diffusers of the size and type shown on the plans
and air distribution schedules. The diffusers shall be constructed entirely from 304 stainless steel (316 optional),
minimum 24 ga.. The perforated face of the diffuser shall have 13% free area with 3/32" (2.4) dia. holes on 1/4" (6)
staggered centers. The face shall incorporate a second pressure plate as an integral assembly to ensure true laminar
airflow. The face shall be attached with 1/4 turn fasteners to allow for complete removal and access to the interior for
cleaning. All diffusers are to include safety cables to prevent accidental dropping of the removable face. A disk type
damper, adjustable from the face of the diffuser, shall be provided with all units. Integral earthquake hanger tabs shall
be included with all units.
All exposed surfaces shall have a #3 satin polished finish.
The manufacturer shall provide published performance data for the diffuser, which shall be tested in accordance with
ANSI/ASHRAE Standard 70 1991.
Back
Home
Contents
Dimensions
Data
Spec
36
HOSPITAL/CLEANROOM DIFFUSERS
48" x 12"
or
1200 mm x 300 mm
60" x 12"
or
1500 mm x 300 mm
72" x 12"
or
1800 mm x 300 mm
Module Size
24" x 24"
or
600 mm x 600 mm
36" x 24"
or
900 mm x 600 mm
48" x 24"
or
1200 mm x 600 mm
Airflow, CFM
Total Pressure
NC
Throw
Total Pressure
NC
Throw
Total Pressure
NC
Throw
100
.030
.5-1-2
.028
.5-1-2
.026
.5-1-2
120
.043
17
.5-1-3
.040
16
1-1-3
.037
16
1-1-3
140
.058
19
1-1.5-4
.055
18
1-1.5-4
.050
18
1-1.5-4
160
.076
22
1.5-2-4
.072
21
1-2-4
.066
21
1-2-4
180
.096
25
1.5-2.5-5
.091
24
1-2.5-4.5
.083
23
1-2.5-4.5
200
.119
27
2-3.5-5
.112
25
2-3.5-5
.103
26
2-3.5-5
220
.144
29
2.5-4-6
.136
28
2-4-5.5
.125
27
2-4.5-5
240
.172
31
3-4.5-7
.161
30
3-4-6.5
.148
30
3-4-6.5
260
.201
34
3-4.5-7.5
.189
33
3-5-7
.174
32
3-4.5-7
280
.233
35
4-5.5-8
.220
34
4-5-8
.202
33
4-5-8
300
.268
37
4.5-6-9
.252
36
4-6-8.5
.232
35
4-6-8.5
Airflow, CFM
Total Pressure
NC
Throw
Total Pressure
NC
Throw
Total Pressure
NC
Throw
100
.030
.5-1-2
.026
0-1-1.5
.023
0-.5-1.5
120
.043
17
.5-1-3
.037
15
0-1-2
.034
.5-1-2
140
.058
19
1-1.5-4
.050
18
0-1-3
.046
17
.5-1-2.5
160
.076
22
1.5-2-4
.066
21
1-2-3.5
.060
20
1-1.5-3
180
.096
25
1.5-2.5-5
.083
24
1-2-4.5
.075
23
1-2-4
200
.119
27
2-3.5-6
.103
26
2-3-5
.093
25
1-2-5
220
.144
29
2.5-4-6
.125
28
2-3-5.5
.113
27
1.5-2.5-5
240
.172
31
3-4.5-7
.148
30
2-3.5-6
.134
30
2-3-6
260
.201
34
3-4.5-7.5
.174
33
2.5-4.5-7
.158
32
2-4-6.5
280
.233
35
4-5.5-8
.202
34
3-5-8
.183
33
2-4.5-7
300
.268
37
4.5-6-9
.232
36
3-5-8
.210
35
3-5-7
160
.022
1-1-3
.021
1-1-3
.021
1-1-3
180
.028
15
1-2-4
.027
1-2-4
.027
1-1-4
200
.035
18
1-2-5
.033
17
1-2-5
.033
17
1-2-4.5
220
240
.042
.050
19
22
1.5-2.5-5
2-3-6
.040
.048
19
22
1.5-2.5-5
2-3-6
.036
.043
19
22
1-2-5
1.5-2.5-6
260
.059
25
2-4-6.5
.056
24
2-4-6.5
.050
24
2-3-6
280
.069
27
2-4.5-7
.065
27
2-4.5-7
.058
27
2-4-7
300
.079
29
3-5-7
.074
29
3-5-7
.066
29
2.5-4-7
320
.090
31
3-5-8
.084
31
3-5-8
.076
31
3-4.5-7.5
340
.113
33
4-6-8.5
.107
33
4-6-8.5
.096
32
3.5-5-8
360
.140
35
5-7-9
.132
35
5-7-9
.118
34
4.5-6-9
230
.036
15
1-2-6
.031
15
1-2-6
.028
14
1-2-5
260
.046
18
1.5-3-6.5
.040
18
2-3-6
.036
17
1.5-2.5-6
290
.057
21
2-4-7
.049
21
2-4-7
.045
20
2-4-6.5
375
.096
28
4.5-6-8.5
.083
28
4.5-6-8.5
.075
27
4-5.5-8
400
.109
30
5-7-9.5
.094
30
5-6.5-9
.085
29
5-6-8.5
48" x 24"
or
1200 mm x 600 mm
60" x 24"
or
1500 mm x 600 mm
72" x 24"
or
1800 mm x 600 mm
Airflow, CFM
Total Pressure
NC
Throw
Total Pressure
NC
Throw
Total Pressure
NC
Throw
48" x 24"
or
1200 mm x 600 mm
60" x 24"
or
1500 mm x 600 mm
72" x 24"
or
1800 mm x 600 mm
CFM
FFM
TP
T
NC
Airflow, CFM
Total Pressure
NC
Throw
Total Pressure
NC
Throw
Total Pressure
NC
Throw
Back
Home
315
.068
22
3-5-8
.058
22
3-5-8
.053
21
3-4.5-7
345
.081
25
4-5.5-8
.070
25
4-5.5-7.5
.063
24
4-5-7
Performance Notes:
1. Throws are the average vertical
distance in feet to terminal velocities of
100, 75 and 50 fpm. Based upon a
cooling T of 10F. 9 ft. ceiling.
Contents
Dimensions
Data
430
460
490
520
.126
.144
.163
.184
32
35
38
42
5.5-7.5-10 6-8-11 6.5-8.5-11.5 7-9-12
.108
.124
.141
.159
32
35
38
42
5.5-7.5-9.5 6-8-10.5
6-8.5-11 6.5-8.5-11.5
.099
.113
.128
.144
31
34
37
41
5-7-9
5.5-7.5-10 6-8-10.5
6-8-11
Spec
37
HOSPITAL/CLEANROOM DIFFUSERS
1219 mm x 305 mm
or
1200 mm x 300 mm
1524 mm x 305 mm
or
1500 mm x 300 mm
1829 mm x 305 mm
or
1800 mm x 300 mm
Module Size
610 mm x 610 mm
or
600 mm x 600 mm
914 mm x 610 mm
or
900 mm x 600 mm
1219 mm x 610 mm
or
1200 mm x 600 mm
Airflow, L/S
Total Pressure
NC
Throw
Total Pressure
NC
Throw
Total Pressure
NC
Throw
47
57
66
76
85
94
104
113
123
132
142
7
11
14
19
24
30
36
43
50
58
67
17
19
22
25
27
29
31
34
35
37
0.2-0.3-0.6 0.2-0.3-0.9 0.3-0.5-1.2 0.5-0.6-1.2 0.5-0.8-1.5 0.6-1.1-1.5 0.8-1.2-1.8 0.9-1.4-2.1 0.9-1.4-2.3 1.2-1.7-2.4 1.4-1.8-2.7
7
10
14
18
23
28
34
40
47
55
63
16
18
21
24
25
28
30
33
34
36
0.2-0.3-0.6 0.3-0.3-0.9 0.3-0.5-1.2 0.3-0.6-1.2 0.3-0.8-1.4 0.6-1.1-1.5 0.6-1.2-1.7 0.9-1.2-2.0 0.9-1.5-2.1 1.2-1.5-2.4 1.2-1.8-2.6
6
9
12
16
21
26
31
37
43
50
58
16
18
21
23
26
27
30
32
33
35
0.2-0.3-0.6 0.3-0.3-0.9 0.3-0.5-1.2 0.3-0.6-1.2 0.3-0.8-1.4 0.6-1.1-1.5 0.6-1.4-1.5 0.9-1.2-2.0 0.9-1.4-2.1 1.2-1.5-2.4 1.2-1.8-2.6
Airflow, L/S
Total Pressure
NC
Throw
Total Pressure
NC
Throw
Total Pressure
NC
Throw
47
57
66
76
85
94
104
113
123
132
142
7
11
14
19
24
30
36
43
50
58
67
17
19
22
25
27
29
31
34
35
37
0.2-0.3-0.6 0.2-0.3-0.9 0.3-0.5-1.2 0.5-0.6-1.2 0.5-0.8-1.5 0.6-1.1-1.8 0.8-1.2-1.8 0.9-1.4-2.1 0.9-1.4-2.3 1.2-1.7-2.4 1.4-1.8-2.7
6
9
12
16
21
26
31
37
43
50
58
15
18
21
24
26
28
30
33
34
36
0-0.3-0.5 0-0.3-0.6 0-0.3-0.9 0.3-0.6-1.1 0.3-0.6-1.4 0.6-0.9-1.5 0.6-0.9-1.70.6-1.1-1.8 0.8-1.4-2.1 0.9-1.5-2.4 0.9-1.5-2.4
6
8
11
15
19
23
28
33
39
45
52
17
20
23
25
27
30
32
33
35
0-0.2-0.5 0.2-0.3-0.6 0.2-0.3-0.8 0.3-0.5-0.9 0.3-0.6-1.2 0.3-0.6-1.5 0.5-0.8-1.5 0.6-0.9-1.8 0.6-1.2-2.0 0.6-1.4-2.1 0.9-1.5-2.1
1219 mm x 610 mm
or
1200 mm x 600 mm
1524 mm x 610 mm
or
1500 mm x 600 mm
1829 mm x 610 mm
or
1800 mm x 600 mm
Airflow, L/S
Total Pressure
NC
Throw
Total Pressure
NC
Throw
Total Pressure
NC
Throw
76
85
94
104
113
123
132
142
151
160
170
5
7
9
10
12
15
17
20
22
28
35
15
18
19
22
25
27
29
31
33
35
0.3-0.3-0.9 0.3-0.6-1.2 0.3-0.6-1.5 0.5-0.8-1.5 0.6-0.9-1.8 0.6-1.2-2.0 0.6-1.4-2.1 0.9-1.5-2.1 0.9-1.5-2.4 1.2-1.8-2.6 1.5-2.1-2.7
5
7
8
10
12
14
16
18
21
27
33
17
19
22
24
27
29
31
33
35
0.3-0.3-0.9 0.3-0.6-1.2 0.3-0.6-1.5 0.5-0.8-1.5 0.6-0.9-1.8 0.6-1.2-2.0 0.6-1.4-2.10.9-1.5-2.1 0.9-1.5-2.4 1.2-1.8-2.6 1.5-2.1-2.7
5
7
8
9
11
12
14
16
19
24
29
17
19
22
24
27
29
31
32
34
0.3-0.3-0.9 0.3-0.3-1.2 0.3-0.6-1.4 0.3-0.6-1.5 0.5-0.8-1.8 0.6-0.9-1.8 0.6-1.2-2.10.8-1.2-2.1 0.9-1.4-2.3 1.1-1.5-2.4 1.4-1.8-2.7
1219 mm x 610 mm
or
1200 mm x 600 mm
1524 mm x 610 mm
or
1500 mm x 600 mm
1829 mm x 610 mm
or
1800 mm x 600 mm
L/S
M/S
TP
T
NC
Airflow, L/S
Total Pressure
NC
Throw
Total Pressure
NC
Throw
Total Pressure
NC
Throw
109
123
137
149
163
177
189
203
217
231
245
9
11
14
17
20
24
27
31
36
41
46
15
18
21
22
25
28
30
32
35
38
42
0.3-0.6-1.8 0.5-0.9-2.0 0.6-1.2-2.1 0.9-1.5-2.4 1.2-1.7-2.4 1.4-1.8-2.6 1.5-2.1-2.9 1.7-2.3-3.0 1.8-2.4-3.4 2.0-2.6-3.5 2.1-2.7-3.7
8
10
12
14
17
21
23
27
31
35
40
15
18
21
22
25
28
30
32
35
38
42
0.3-0.6-1.8 0.6-0.9-1.8 0.6-1.2-2.1 0.9-1.5-2.4 1.2-1.7-2.3 1.4-1.8-2.6 1.5-2.0-2.7 1.7-2.3-2.9 1.8-2.4-3.2 1.8-2.6-3.4 2.0-2.6-3.5
7
9
11
13
16
19
21
25
28
32
36
14
17
20
21
24
27
29
31
34
37
41
0.3-0.6-1.5 0.5-0.8-1.8 0.6-1.2-2.0 0.9-1.4-2.1 1.2-1.5-2.1 1.2-1.7-2.4 1.5-1.8-2.6 1.5-2.1-2.7 1.7-2.3-3.0 1.8-2.4-3.2 1.8-2.4-3.4
Back
Home
Contents
Performance Notes:
1. Throws are the average vertical
distance in feet to terminal velocities of
0.51, 0.38 and 0.25 m/s. Based upon a
cooling T of 5.5C. 2.7 m ceiling.
Dimensions
Data
Spec
38
HOSPITAL/CLEANROOM DIFFUSERS
LAMINAR FLOW
CEILING DIFFUSERS
PROVEN TECHNOLOGY
HEPA OR ULPA FILTERS
REMOVABLE PERFORATED
FACE
INTEGRAL VOLUME DAMPER
UNIDIRECTIONAL AIRFLOW
Models:
92LFDF-SS Stainless Steel
With Filter
Model 92LFDF-SS
The Nailor 92LFDF-SS Series Laminar Flow Diffusers with Filters utilize the well-proven and time-tested concept of
vertical air mass 'laminar flow' technology. The 92LFD-SS Series produce a non-aspirating, low velocity, uniformly
distributed downward moving 'piston' of conditioned air. They are designed with an integral 'knife-edge' frame to
accommodate a Gel Seal HEPA or ULPA filter. The filters can be easily removed and replaced from the face of the unit.
These high quality filters incorporate a separatorless 2" (51) deep media, integral test port and an anodized aluminum gel
seal frame.
They may be used individually, or as in the case of hospital operating rooms, several units may be banked together to
sufficiently cover the area and produce one large combined laminar mass. Installed in an operating room above the
operating table, the clean conditioned air flows over and blankets the operating table, helping to protect and effectively
isolate the patient from contaminated air. The only significant amount of room air entrainment occurs at the outer boundary
of the laminar flow mass, outside the confines of the operating table. The patient is therefore bathed in 'clean air' and
effectively isolated from secondary room air and any airborne contaminants.
The advantages of Laminar Flow technology provide similar benefits in other 'cleanroom' applications such as research
laboratories, bio-technology facilities, animal laboratories, food processing plants, semi-conductor manufacturing,
pharmaceutical laboratories and protective environment rooms.
The ability of the 92LFDF-SS to maintain a sterile environment directly below is enhanced by the use of low level exhaust
grilles located around the room periphery which remove the contaminated air before it can react with the boundary layer of
the laminar flow mass.
FEATURES:
Face plate is removable for cleaning
and is secured by 1/4 turn fasteners.
Safety cables are included as standard
and prevent accidental dropping of
the removable face.
Perforated face has 3/32" (2.4) dia.
holes on 60 degree 1/4" (6) staggered
centers (13% free area).
Round inlets for simple duct
connection.
Integral earthquake hanger tabs are
standard.
Standard unit designed for both
Lay-in T-Bar ceiling systems and
surface mount applications.
Back
Home
Contents
Integral
'knife-edge'
frame
accommodates Gel Seal HEPA or
ULPA filters.
Clear anodized extruded aluminum
filter frame with a removable test port
for damper adjustment, filter pressure
drop measurement or to perform
leakage (scan) tests.
Filters are packaged independently
from the diffuser for final installation in
the field (by others).
Integral damper with screwdriver slot
adjustment is easily accessed.
Material: Type 304 Stainless Steel
construction.
Finish: #3 Satin Polished finish is
standard. Other finishes are available.
Dimensions
Data
Spec
OPTIONS:
316 Stainless Steel construction.
HE HEPA Filter
(99.99% on 0.3 m).
UL ULPA Filter
(99.9995% on 0.12 m).
AW Appliance White finish.
39
HOSPITAL/CLEANROOM DIFFUSERS
W - 1/4" (6)
REMOVABLE
PLUG FOR
SCREWDRIVER
ACCESS
L - 1/4" (6)
L - 2 3/4" (70)
D - 1/8" (3)
STANDARD
SAFETY
CABLE
2 1/2" (64)
9" (229)
HEPA OR ULPA
FILTER
Model 92LFDF-SS
Ceiling Module Sizes L x W & Nominal Round Duct Sizes D
LxW
36 x 24
48 x 24
60 x 24
900 x 600 1200 x 600 1500 x 600
6, 7,
7, 8,
10,
8, 10
10, 12
12
152, 178, 178, 203,
254,
203, 254 254, 305
305
CEILING MODULE
CM - 1/4" (6)
GEL SEAL
Back
Home
Contents
Dimensions
GEL SEAL
Data
Spec
40
HOSPITAL/CLEANROOM DIFFUSERS
92LFDF-SS - 08 - 48 x 24 - L - #3 - 316
MODEL
OPTIONS
92LFDF-SS
- None (default)
INLET SIZE
316
- HEPA Filter
(99.99% on 0.3 m)
HE
- ULPA Filter
(99.9995% on 0.12 m)
UL
(1219 x 305)
- 60 x 12
(1524 x 305)
- 24 x 24
(610 x 610)
- 36 x 24
(914 x 610)
- 48 x 24
(1219 x 610)
- 60 x 24
(1524 x 610)
FINISH
- #3 Satin Polished
#3
- Appliance White
AW
- Special
SP
FRAME TYPE
- Lay-in T-Bar
- Surface Mount
- 1500 x 300
- 600 x 600
- 900 x 600
- 1200 x 600
- 1500 x 600
SUGGESTED SPECIFICATION:
Furnish and install Nailor Model 92LFDF-SS Laminar Flow Ceiling Diffusers of the size and type shown on the
plans and air distribution schedules. The diffusers shall be constructed entirely from 304 stainless steel (316 optional),
minimum 24 ga.. The perforated face of the diffuser shall have 13% free area with 3/32" (2.4) dia. holes on 1/4" (6)
staggered centers. The face shall be attached with 1/4 turn fasteners to allow for complete removal and access to the
interior for cleaning. All diffusers are to include safety cables to prevent accidental dropping of the removable face. A
disk type balancing damper shall be provided with all units. Integral earthquake hanger tabs shall be included with all
units.
The diffuser plenum shall incorporate an integral filter frame to accommodate a Gel Seal filter. Filters shall be securely
held in place by at least four mounting brackets allowing filter removal from the face of the diffuser without disturbing
installed ductwork or the diffuser mounting surface. Filters shall incorporate a removable test port, to measure filter
pressure drop, perform leakage (scan) tests and to adjust the balancing damper without removing the filter. The filters
efficiency shall be HEPA: 99.99% minimum removal efficiency on 0.30 micrometer particle size (ULPA: 99.9995%
minimum removal efficiency on 0.12 micrometer particle size optional). Filters shall incorporate an anodized extruded
aluminum frame and a 2" (51) deep separatorless filter pack. All filters shall be UL 900 Class I Listed and Factory
Mutual Approved. All filters shall be individually scan tested per Section 6.2 of IEST-RP-CC034.1. Filters are to be
packaged independently from the diffuser for final installation of the filter in the field (by others).
All exposed surfaces shall have a #3 satin polished finish.
The manufacturer shall provide published performance data for the diffuser, which shall be tested in accordance with
ANSI/ASHRAE Standard 70 1991.
Back
Home
Contents
Dimensions
Data
Spec
41
HOSPITAL/CLEANROOM DIFFUSERS
Airflow, CFM
Total Pressure
48" x 12"
Static Pressure
or
NC
1200 mm x 300 mm
Throw
Total Pressure
60" x 12"
Static Pressure
or
NC
1500 mm x 300 mm
Throw
Module Size
Airflow, CFM
Total Pressure
24" x 24"
Static Pressure
or
NC
600 mm x 600 mm
Throw
Total Pressure
36" x 24"
Static Pressure
or
NC
900 mm x 600 mm
Throw
Total Pressure
48" x 24"
Static Pressure
or
NC
1200 mm x 600 mm
Throw
100
0.17
0.16
.5-1-2
0.11
0.11
.5-1-2
120
0.24
0.24
17
.5-1-3
0.16
0.15
16
1-1-3
140
0.33
0.32
19
1-1.5-4
0.22
0.21
18
1-1.5-4
160
0.43
0.42
22
1.5-2-4
0.28
0.27
21
1-2-4
180
0.55
0.53
25
1.5-2.5-5
0.36
0.34
24
1-2.5-4.5
200
0.68
0.66
27
2-3.5-5
0.44
0.42
25
2-3.5-5
220
0.82
0.79
29
2.5-4-6
0.54
0.51
28
2-4-5.5
240
0.98
0.94
31
3-4.5-7
0.64
0.61
30
3-4-6.5
260
1.14
1.11
34
3-4.5-7.5
0.75
0.71
33
3-5-7
280
1.33
1.28
35
4-5.5-8
0.87
0.83
34
4-5-8
290
1.42
1.38
37
4.5-6-9
0.93
0.89
36
4-6-8.5
100
0.17
0.16
.5-1-2
0.07
0.07
0-1-1.5
0.05
0.04
0-.5-1.5
120
0.24
0.23
17
.5-1-3
0.10
0.10
15
0-1-2
0.07
0.06
.5-1-2
140
0.32
0.31
19
1-1.5-4
0.14
0.13
18
0-1-3
0.09
0.08
17
.5-1-2.5
160
0.42
0.41
22
1.5-2-4
0.18
0.17
21
1-2-3.5
0.12
0.10
20
1-1.5-3
180
0.54
0.52
25
1.5-2.5-5
0.23
0.21
24
1-2-4.5
0.15
0.13
23
1-2-4
200
0.66
0.64
27
2-3.5-6
0.29
0.26
26
2-3-5
0.18
0.16
25
1-2-5
220
0.80
0.77
29
2.5-4-6
0.35
0.32
28
2-3-5.5
0.22
0.20
27
1.5-2.5-5
240
0.95
0.92
31
3-4.5-7
0.41
0.38
30
2-3.5-6
0.27
0.24
30
2-3-6
260
1.12
1.08
34
3-4.5-7.5
0.48
0.45
33
2.5-4.5-7
0.31
0.28
32
2-4-6.5
280
1.30
1.25
35
4-5.5-8
0.56
0.52
34
3-5-8
0.36
0.32
33
2-4.5-7
295
1.44
1.39
37
4.5-6-9
0.62
0.58
36
3-5-8
0.40
0.36
35
3-5-7
160
0.14
0.14
15
1-2-3.5
0.08
0.08
1-1-3
0.06
0.05
1-1-3
180
0.18
0.17
18
1-2-4.5
0.10
0.10
15
1-2-4
0.07
0.06
1-2-4
200
0.22
0.21
20
2-3-5
0.13
0.12
18
1-2-5
0.09
0.08
17
1-2-5
220
0.27
0.26
21
2-3-5.5
0.15
0.14
19
1.5-2.5-5
0.11
0.10
19
1.5-2.5-5
240
0.32
0.30
23
2-3.5-6
0.18
0.17
22
2-3-6
0.13
0.11
22
2-3-6
260
0.37
0.36
26
2.5-4-7
0.21
0.20
25
2-4-6.5
0.15
0.13
24
2-4-6.5
280
0.43
0.41
28
3-5-8
0.25
0.23
27
2-4.5-7
0.17
0.15
27
2-4.5-7
300
0.50
0.48
30
3-5-8
0.28
0.27
29
3-5-7
0.20
0.18
29
3-5-7
320
0.56
0.54
32
4-5.5-8.5
0.32
0.30
31
3-5-8
0.22
0.20
31
3-5-8
340
0.64
0.61
34
4-6-9
0.37
0.34
33
4-6-8.5
0.25
0.23
33
4-6-8.5
360
0.71
0.69
36
5-7-9.5
0.41
0.38
35
5-7-9
0.28
0.26
35
5-7-9
230
0.16
0.15
15
1-2-6
0.10
0.10
15
1-2-6
260
0.20
0.19
18
1.5-3-6.5
0.13
0.12
18
2-3-6
290
0.25
0.24
21
2-4-7
0.16
0.16
21
2-4-7
315
0.29
0.28
22
3-5-8
0.19
0.18
22
3-5-8
345
0.35
0.34
25
4-5.5-8
0.23
0.22
25
4-5.5-7.5
375
0.42
0.40
28
4.5-6-8.5
0.27
0.26
28
4.5-6-8.5
Airflow, CFM
Total Pressure
36" x 24"
Static Pressure
or
NC
900 mm x 600 mm
Throw
Total Pressure
48" x 24"
Static Pressure
or
NC
1200 mm x 600 mm
Throw
Total Pressure
60" x 24"
Static Pressure
or
NC
1500 mm x 600 mm
Throw
Airflow, CFM
Total Pressure
48" x 24"
Static Pressure
or
NC
1200 mm x 600 mm
Throw
Total Pressure
60" x 24"
Static Pressure
or
NC
1500 mm x 600 mm
Throw
CFM
FPM
Pt
Ps
T
NC
Back
Home
Contents
400
430
0.48
0.55
0.46
0.53
30
32
5-7-9.5 5.5-7.5-10
0.31
0.36
0.30
0.34
30
32
5-6.5-9 5.5-7.5-9.5
460
490
520
0.63
0.71
0.80
0.61
0.69
0.78
35
38
42
6-8-11 6.5-8.5-11.5 7-9-12
0.41
0.47
0.53
0.39
0.44
0.50
35
38
42
6-8-10.5 6-8.5-11 6.5-8.5-11.5
Performance Notes:
1. Throws are the average vertical
distance in feet to terminal velocities of
100, 75 and 50 fpm. Based upon a
cooling T of 10F. 9 ft. ceiling.
Dimensions
Data
Spec
42
HOSPITAL/CLEANROOM DIFFUSERS
Airflow, L/S
Total Pressure
Static Pressure
NC
Throw
Total Pressure
Static Pressure
NC
Throw
47
57
66
76
85
94
104
113
123
132
137
42
60
82
107
137
169
204
244
283
331
353
40
60
80
104
132
164
196
234
276
318
343
17
19
22
25
27
29
31
34
35
37
0.2-0.3-0.6 0.2-0.3-0.9 0.3-0.5-1.2 0.5-0.6-1.2 0.5-0.8-1.5 0.6-1.1-1.5 0.8-1.2-1.8 0.9-1.4-2.1 0.9-1.4-2.3 1.2-1.7-2.4 1.4-1.8-2.7
27
40
55
70
89
109
134
159
186
216
231
27
37
52
67
84
104
127
152
177
206
221
16
18
21
24
25
28
30
33
34
36
0.2-0.3-0.6 0.3-0.3-0.9 0.3-0.5-1.2 0.3-0.6-1.2 0.3-0.8-1.4 0.6-1.1-1.5 0.6-1.2-1.7 0.9-1.2-2.0 0.9-1.5-2.1 1.2-1.5-2.4 1.2-1.8-2.6
Airflow, L/S
Total Pressure
610 mm x 610 mm
Static Pressure
or
NC
600 mm x 600 mm
Throw
Total Pressure
914 mm x 610 mm
Static Pressure
or
NC
900 mm x 600 mm
Throw
Total Pressure
1219 mm x 610 mm
Static Pressure
or
NC
1200 mm x 600 mm
Throw
47
57
66
76
85
94
104
113
123
132
139
42
60
80
104
134
164
199
236
278
323
358
40
57
77
102
129
159
191
229
268
311
346
17
19
22
25
27
29
31
34
35
37
0.2-0.3-0.6 0.2-0.3-0.9 0.3-0.5-1.2 0.5-0.6-1.2 0.5-0.8-1.5 0.6-1.1-1.8 0.8-1.2-1.8 0.9-1.4-2.1 0.9-1.4-2.3 1.2-1.7-2.4 1.4-1.8-2.7
17
25
35
45
57
72
87
102
119
139
154
17
25
32
40
52
64
80
94
112
129
144
15
18
21
24
26
28
30
33
34
36
0-0.3-0.5 0-0.3-0.6 0-0.3-0.9 0.3-0.6-1.1 0.3-0.6-1.4 0.6-0.9-1.5 0.6-0.9-1.7 0.6-1.1-1.8 0.8-1.4-2.1 0.9-1.5-2.4 0.9-1.5-2.4
12
17
22
30
37
45
55
67
77
89
99
10
15
20
25
32
40
50
60
70
80
89
17
20
23
25
27
30
32
33
35
0-0.2-0.5 0.2-0.3-0.6 0.2-0.3-0.8 0.3-0.5-0.9 0.3-0.6-1.2 0.3-0.6-1.5 0.5-0.8-1.5 0.6-0.9-1.8 0.6-1.2-2.0 0.6-1.4-2.1 0.9-1.5-2.1
1219 mm x 305 mm
or
1200 mm x 300 mm
1524 mm x 305 mm
or
1500 mm x 300 mm
Module Size
914 mm x 610 mm
or
900 mm x 600 mm
1219 mm x 610 mm
or
1200 mm x 600 mm
1524 mm x 610 mm
or
1500 mm x 600 mm
Airflow, L/S
Total Pressure
Static Pressure
NC
Throw
Total Pressure
Static Pressure
NC
Throw
Total Pressure
Static Pressure
NC
Throw
76
85
94
104
113
123
132
142
151
160
170
35
45
55
67
80
92
107
124
139
159
177
35
42
52
65
75
89
102
119
134
152
172
15
18
20
21
23
26
28
30
32
34
36
0.3-0.6-1.1 0.3-0.6-1.4 0.6-0.9-1.5 0.6-0.9-1.7 0.6-1.1-1.8 0.8-1.2-2.1 0.9-1.5-2.4 0.9-1.5-2.4 1.2-1.7-2.6 1.2-1.8-2.7 1.5-2.1-2.9
20
25
32
37
45
52
62
70
80
92
102
20
25
30
35
42
50
57
67
75
85
94
15
18
19
22
25
27
29
31
33
35
0.3-0.3-0.9 0.3-0.6-1.2 0.3-0.6-1.5 0.5-0.8-1.5 0.6-0.9-1.8 0.6-1.2-2.0 0.6-1.4-2.1 0.9-1.5-2.1 0.9-1.5-2.4 1.2-1.8-2.6 1.5-2.1-2.7
15
17
22
27
32
37
42
50
55
62
70
12
15
20
25
27
32
37
45
50
57
65
17
19
22
24
27
29
31
33
35
0.3-0.3-0.9 0.3-0.6-1.2 0.3-0.6-1.5 0.5-0.8-1.5 0.6-0.9-1.8 0.6-1.2-2.0 0.6-1.4-2.1 0.9-1.5-2.1 0.9-1.5-2.4 1.2-1.8-2.6 1.5-2.1-2.7
Airflow, L/S
Total Pressure
1219 mm x 610 mm
Static Pressure
or
NC
1200 mm x 600 mm
Throw
Total Pressure
1524 mm x 610 mm
Static Pressure
or
NC
1500 mm x 600 mm
Throw
L/S
M/S
Pt
Ps
T
NC
109
123
137
149
163
177
189
203
217
231
245
40
50
62
72
87
104
119
137
157
177
199
37
47
60
70
85
99
114
132
152
172
194
15
18
21
22
25
28
30
32
35
38
42
0.3-0.6-1.8 0.5-0.9-2.0 0.6-1.2-2.1 0.9-1.5-2.4 1.2-1.7-2.4 1.4-1.8-2.6 1.5-2.1-2.9 1.7-2.3-3.0 1.8-2.4-3.4 2.0-2.6-3.5 2.1-2.7-3.7
25
32
40
47
57
67
77
89
102
117
132
25
30
40
45
55
65
75
85
97
109
124
15
18
21
22
25
28
30
32
35
38
42
0.3-0.6-1.8 0.6-0.9-1.8 0.6-1.2-2.1 0.9-1.5-2.4 1.2-1.7-2.3 1.4-1.8-2.6 1.5-2.0-2.7 1.7-2.3-2.9 1.8-2.4-3.2 1.8-2.6-3.4 2.0-2.6-3.5
Back
Home
Contents
Performance Notes:
1. Throws are the average vertical
distance in feet to terminal velocities of
0.51, 0.38 and 0.25 m/s. Based upon a
cooling T of 5.5C. 2.7 m ceiling.
Dimensions
Data
Spec
43
HOSPITAL/CLEANROOM DIFFUSERS
Airflow, CFM
Total Pressure
48" x 12"
Static Pressure
or
NC
1200 mm x 300 mm
Throw
Total Pressure
60" x 12"
Static Pressure
or
NC
1500 mm x 300 mm
Throw
Module Size
Airflow, CFM
Total Pressure
24" x 24"
Static Pressure
or
NC
600 mm x 600 mm
Throw
Total Pressure
36" x 24"
Static Pressure
or
NC
900 mm x 600 mm
Throw
Total Pressure
48" x 24"
Static Pressure
or
NC
1200 mm x 600 mm
Throw
100
0.20
0.19
.5-1-2
0.13
0.12
.5-1-2
120
0.29
0.28
17
.5-1-3
0.18
0.18
16
1-1-3
140
0.39
0.38
19
1-1.5-4
0.25
0.24
18
1-1.5-4
160
0.51
0.50
22
1.5-2-4
0.33
0.31
21
1-2-4
180
0.65
0.63
25
1.5-2.5-5
0.42
0.40
24
1-2.5-4.5
200
0.80
0.78
27
2-3.5-5
0.51
0.49
25
2-3.5-5
220
0.96
0.94
29
2.5-4-6
0.62
0.60
28
2-4-5.5
240
1.15
1.12
31
3-4.5-7
0.74
0.71
30
3-4-6.5
260
1.35
1.31
34
3-4.5-7.5
0.87
0.83
33
3-5-7
280
1.56
1.52
35
4-5.5-8
1.01
0.96
34
4-5-8
290
1.68
1.63
37
4.5-6-9
1.08
1.03
36
4-6-8.5
100
0.19
0.19
.5-1-2
0.08
0.08
0-1-1.5
0.05
0.05
0-.5-1.5
120
0.28
0.27
17
.5-1-3
0.12
0.11
15
0-1-2
0.07
0.07
.5-1-2
140
0.38
0.37
19
1-1.5-4
0.16
0.15
18
0-1-3
0.10
0.09
17
.5-1-2.5
160
0.50
0.48
22
1.5-2-4
0.21
0.19
21
1-2-3.5
0.13
0.12
20
1-1.5-3
180
0.63
0.61
25
1.5-2.5-5
0.26
0.25
24
1-2-4.5
0.17
0.15
23
1-2-4
200
0.78
0.75
27
2-3.5-6
0.32
0.30
26
2-3-5
0.20
0.18
25
1-2-5
220
0.94
0.91
29
2.5-4-6
0.39
0.37
28
2-3-5.5
0.25
0.22
27
1.5-2.5-5
240
1.12
1.09
31
3-4.5-7
0.47
0.44
30
2-3.5-6
0.29
0.26
30
2-3-6
260
1.31
1.28
34
3-4.5-7.5
0.55
0.51
33
2.5-4.5-7
0.34
0.31
32
2-4-6.5
280
1.52
1.48
35
4-5.5-8
0.64
0.59
34
3-5-8
0.40
0.36
33
2-4.5-7
295
1.69
1.64
37
4.5-6-9
0.71
0.66
36
3-5-8
0.44
0.40
35
3-5-7
160
0.17
0.16
15
1-2-3.5
0.09
0.09
1-1-3
0.06
0.06
1-1-3
180
0.21
0.20
18
1-2-4.5
0.12
0.11
15
1-2-4
0.08
0.07
1-2-4
200
0.26
0.25
20
2-3-5
0.15
0.14
18
1-2-5
0.10
0.09
17
1-2-5
220
0.31
0.30
21
2-3-5.5
0.18
0.17
19
1.5-2.5-5
0.12
0.11
19
1.5-2.5-5
240
0.37
0.36
23
2-3.5-6
0.21
0.20
22
2-3-6
0.14
0.13
22
2-3-6
260
0.44
0.42
26
2.5-4-7
0.25
0.23
25
2-4-6.5
0.17
0.15
24
2-4-6.5
280
0.51
0.49
28
3-5-8
0.29
0.27
27
2-4.5-7
0.19
0.18
27
2-4.5-7
300
0.58
0.56
30
3-5-8
0.33
0.31
29
3-5-7
0.22
0.20
29
3-5-7
320
0.66
0.64
32
4-5.5-8.5
0.37
0.35
31
3-5-8
0.25
0.23
31
3-5-8
340
0.75
0.72
34
4-6-9
0.42
0.40
33
4-6-8.5
0.29
0.26
33
4-6-8.5
360
0.84
0.81
36
5-7-9.5
0.47
0.44
35
5-7-9
0.32
0.29
35
5-7-9
230
0.18
0.18
15
1-2-6
0.12
0.11
15
1-2-6
260
0.23
0.23
18
1.5-3-6.5
0.15
0.14
18
2-3-6
290
0.29
0.28
21
2-4-7
0.19
0.18
21
2-4-7
315
0.34
0.33
22
3-5-8
0.22
0.21
22
3-5-8
345
0.41
0.40
25
4-5.5-8
0.27
0.25
25
4-5.5-7.5
375
0.49
0.47
28
4.5-6-8.5
0.32
0.30
28
4.5-6-8.5
Airflow, CFM
Total Pressure
36" x 24"
Static Pressure
or
NC
900 mm x 600 mm
Throw
Total Pressure
48" x 24"
Static Pressure
or
NC
1200 mm x 600 mm
Throw
Total Pressure
60" x 24"
Static Pressure
or
NC
1500 mm x 600 mm
Throw
Airflow, CFM
Total Pressure
48" x 24"
Static Pressure
or
NC
1200 mm x 600 mm
Throw
Total Pressure
60" x 24"
Static Pressure
or
NC
1500 mm x 600 mm
Throw
CFM
FPM
Pt
Ps
T
NC
Back
Home
Contents
400
430
0.55
0.64
0.54
0.62
30
32
5-7-9.5 5.5-7.5-10
0.36
0.41
0.34
0.39
30
32
5-6.5-9 5.5-7.5-9.5
460
490
520
0.73
0.83
0.93
0.71
0.80
0.91
35
38
42
6-8-11 6.5-8.5-11.5 7-9-12
0.47
0.54
0.61
0.45
0.51
0.58
35
38
42
6-8-10.5 6-8.5-11 6.5-8.5-11.5
Performance Notes:
1. Throws are the average vertical
distance in feet to terminal velocities of
100, 75 and 50 fpm. Based upon a
cooling T of 10F. 9 ft. ceiling.
Dimensions
Data
Spec
44
HOSPITAL/CLEANROOM DIFFUSERS
Airflow, L/S
Total Pressure
Static Pressure
or
NC
1200 mm x 300 mm
Throw
Total Pressure
1524 mm x 305 mm
Static Pressure
or
NC
1500 mm x 300 mm
Throw
47
57
66
76
85
94
104
113
123
132
137
50
72
97
127
162
199
239
286
336
388
418
47
70
94
124
157
194
234
278
326
378
405
17
19
22
25
27
29
31
34
35
37
0.2-0.3-0.6 0.2-0.3-0.9 0.3-0.5-1.2 0.5-0.6-1.2 0.5-0.8-1.5 0.6-1.1-1.5 0.8-1.2-1.8 0.9-1.4-2.1 0.9-1.4-2.3 1.2-1.7-2.4 1.4-1.8-2.7
32
45
62
82
104
127
154
184
216
251
268
30
45
60
77
99
122
149
177
206
239
256
16
18
21
24
25
28
30
33
34
36
0.2-0.3-0.6 0.3-0.3-0.9 0.3-0.5-1.2 0.3-0.6-1.2 0.3-0.8-1.4 0.6-1.1-1.5 0.6-1.2-1.7 0.9-1.2-2.0 0.9-1.5-2.1 1.2-1.5-2.4 1.2-1.8-2.6
*
1219 mm x 305 mm
Module Size
Airflow, L/S
Total Pressure
610 mm x 610 mm
Static Pressure
or
NC
600 mm x 600 mm
Throw
Total Pressure
914 mm x 610 mm
Static Pressure
or
NC
900 mm x 600 mm
Throw
Total Pressure
1219 mm x 610 mm
Static Pressure
or
NC
1200 mm x 600 mm
Throw
47
57
66
76
85
94
104
113
123
132
139
47
70
94
124
157
194
234
278
326
378
420
47
67
92
119
152
186
226
271
318
368
408
17
19
22
25
27
29
31
34
35
37
0.2-0.3-0.6 0.2-0.3-0.9 0.3-0.5-1.2 0.5-0.6-1.2 0.5-0.8-1.5 0.6-1.1-1.8 0.8-1.2-1.8 0.9-1.4-2.1 0.9-1.4-2.3 1.2-1.7-2.4 1.4-1.8-2.7
20
30
40
52
65
80
97
117
137
159
177
20
27
37
47
62
75
92
109
127
147
164
15
18
21
24
26
28
30
33
34
36
0-0.3-0.5 0-0.3-0.6 0-0.3-0.9 0.3-0.6-1.1 0.3-0.6-1.4 0.6-0.9-1.5 0.6-0.9-1.7 0.6-1.1-1.8 0.8-1.4-2.1 0.9-1.5-2.4 0.9-1.5-2.4
12
17
25
32
42
50
62
72
85
99
109
12
17
22
30
37
45
55
65
77
89
99
17
20
23
25
27
30
32
33
35
0-0.2-0.5 0.2-0.3-0.6 0.2-0.3-0.8 0.3-0.5-0.9 0.3-0.6-1.2 0.3-0.6-1.5 0.5-0.8-1.5 0.6-0.9-1.8 0.6-1.2-2.0 0.6-1.4-2.1 0.9-1.5-2.1
914 mm x 610 mm
or
900 mm x 600 mm
1219 mm x 610 mm
or
1200 mm x 600 mm
1524 mm x 610 mm
or
1500 mm x 600 mm
Airflow, L/S
Total Pressure
Static Pressure
NC
Throw
Total Pressure
Static Pressure
NC
Throw
Total Pressure
Static Pressure
NC
Throw
76
85
94
104
113
123
132
142
151
160
170
42
52
65
77
92
109
127
144
164
186
209
40
50
62
75
89
104
122
139
159
179
201
15
18
20
21
23
26
28
30
32
34
36
0.3-0.6-1.1 0.3-0.6-1.4 0.6-0.9-1.5 0.6-0.9-1.7 0.6-1.1-1.8 0.8-1.2-2.1 0.9-1.5-2.4 0.9-1.5-2.4 1.2-1.7-2.6 1.2-1.8-2.7 1.5-2.1-2.9
22
30
37
45
52
62
72
82
92
104
117
22
27
35
42
50
57
67
77
87
99
109
15
18
19
22
25
27
29
31
33
35
0.3-0.3-0.9 0.3-0.6-1.2 0.3-0.6-1.5 0.5-0.8-1.5 0.6-0.9-1.8 0.6-1.2-2.0 0.6-1.4-2.1 0.9-1.5-2.1 0.9-1.5-2.4 1.2-1.8-2.6 1.5-2.1-2.7
15
20
25
30
35
42
47
55
62
72
80
15
17
22
27
32
37
45
50
57
65
72
17
19
22
24
27
29
31
33
35
0.3-0.3-0.9 0.3-0.6-1.2 0.3-0.6-1.5 0.5-0.8-1.5 0.6-0.9-1.8 0.6-1.2-2.0 0.6-1.4-2.1 0.9-1.5-2.1 0.9-1.5-2.4 1.2-1.8-2.6 1.5-2.1-2.7
Airflow, L/S
Total Pressure
1219 mm x 610 mm
Static Pressure
or
NC
1200 mm x 600 mm
Throw
Total Pressure
1524 mm x 610 mm
Static Pressure
or
NC
1500 mm x 600 mm
Throw
L/S
M/S
Pt
Ps
T
NC
109
123
137
149
163
177
189
203
217
231
245
45
57
72
85
102
122
137
159
181
206
231
45
57
70
82
99
117
134
154
177
199
226
15
18
21
22
25
28
30
32
35
38
42
0.3-0.6-1.8 0.5-0.9-2.0 0.6-1.2-2.1 0.9-1.5-2.4 1.2-1.7-2.4 1.4-1.8-2.6 1.5-2.1-2.9 1.7-2.3-3.0 1.8-2.4-3.4 2.0-2.6-3.5 2.1-2.7-3.7
30
37
47
55
67
80
89
102
117
134
152
27
35
45
52
62
75
85
97
112
127
144
15
18
21
22
25
28
30
32
35
38
42
0.3-0.6-1.8 0.6-0.9-1.8 0.6-1.2-2.1 0.9-1.5-2.4 1.2-1.7-2.3 1.4-1.8-2.6 1.5-2.0-2.7 1.7-2.3-2.9 1.8-2.4-3.2 1.8-2.6-3.4 2.0-2.6-3.5
Back
Home
Contents
Performance Notes:
1. Throws are the average vertical
distance in feet to terminal velocities of
0.51, 0.38 and 0.25 m/s. Based upon a
cooling T of 5.5C. 2.7 m ceiling.
Dimensions
Data
Spec
45
HOSPITAL/CLEANROOM DIFFUSERS
STERI-SYSTEM LINEAR
SLOT DIFFUSERS
OPERATING ROOM
AIR CURTAIN
SINGLE SLOT
REMOVABLE FACE
STAINLESS STEEL
Models:
92LS-SS
Stainless Steel
92LS-SS-O
Stainless Steel
with Opposed
Blade Damper
92LS-SS
The Nailor 92LS-SS Series Steri-System Linear Slot Diffusers are specially designed to provide an air curtain for
operating rooms. The 92LS-SS Series unique slot design creates a continuous curtain of air, angled outwards 5 15
degrees, that encloses the operating area and minimizes the possibility of contaminated air entering the surgical area. The
single slot design creates a uniform low velocity curtain that minimizes entrainment of contaminated air into the curtain air
stream. It also creates a wider velocity profile with less turbulence and hence less induction over similar two slot designs.
The face design incorporates longitudinal deflectors that horizontally deflect a small amount of air lengthwise. This
effectively joins the airflow through sections and corners forming a truly continuous air curtain, resulting in enhanced
isolation of the surgical area.
FEATURES:
The entire slot assembly including
the pressure plate is removable for
cleaning and is secured by 1/4 turn
stainless steel fasteners.
Safety cables are included as
standard and prevent accidental
dropping of the removable face.
Perforated pressure plate has 3/32"
(2.4) dia. holes on 60 degree 1/4" (6)
staggered centers (13% free area).
Model 92LS-SS
Operating Room Plenum Detail
8" (203)
1" (25)
13% FA
PERFORATED
PRESSURE
PLATE
Home
Contents
11 13/16"
(300)
5"
(127)
SPACERS SUPPLIED
AND INSTALLED
(BY OTHERS)
Back
8" (203)
R0.75
1 1/4" (32)
1" (25)
R0.75
SAFETY
CHAIN
11 13/16"
(300)
Dimensions
Data
Spec
SAFETY
CHAIN
1" (25)
OPPOSED
BLADE
DAMPER
WING NUT
FASTENER
5"
(127)
1" (25)
LEVER
OPERATOR
13% FA
PERFORATED
PRESSURE
PLATE
46
HOSPITAL/CLEANROOM DIFFUSERS
10.75"
(273)
13% FA PERFORATED
PRESSURE PLATE
10"
(254)
1" (25)
SAFETY
CHAIN
5" (127)
12"
(305)
10.75"
(273)
66.75" (1695)
1" (25)
16" (406)
SAFETY
CHAIN
5" (127)
12"
(305)
Back
Home
Contents
Dimensions
Data
Spec
47
HOSPITAL/CLEANROOM DIFFUSERS
10.75"
(273)
10" (254)
1" (25)
13% FA
PERFORATED
PRESSURE
PLATE
5" (127)
12"
(305)
FLANGE CONNECTION
10.75"
(273)
13% FA
PERFORATED
PRESSURE
PLATE
114.75" (2915)
1" (25)
12" (305)
SAFETY
CHAIN
5" (127)
FLANGE CONNECTION
Back
Home
Contents
Dimensions
Data
12"
(305)
Spec
48
HOSPITAL/CLEANROOM DIFFUSERS
13% FA
PERFORATED
PRESSURE
PLATE
1" (25)
SAFETY
CHAIN
5" (127)
12"
(305)
FLANGE CONNECTION
13% FA
PERFORATED
PRESSURE
PLATE
18" (457)
SAFETY
CHAIN
12"
(305)
5" (127)
FLANGE CONNECTION
189.5" (4813)
14"
(356)
5" (127)
FLANGE CONNECTION
Back
Home
Contents
Dimensions
FLANGE CONNECTION
Data
Spec
13% FA
PERFORATED
PRESSURE
PLATE
SAFETY
CHAIN
12"
(305)
49
HOSPITAL/CLEANROOM DIFFUSERS
92LS-SS - 12 x 5 - 10 - S - #3 - 316
MODEL
OPTIONS
92LS-SS
- None (default)
FINISH
316
- 10 x 5
- 16 x 5
- Appliance White
AW
- 10 x 5
- Special
SP
- 12 x 5
FRAME TYPE
- 16 x 5
- Lay-in T-Bar
- 18 x 5
- Surface Mount
- 14 x 5
#3
(1219)
- 6 ft.
(1829)
- 8 ft.
(2438)
- 10 ft.
(3048)
- 12 ft.
(3658)
- 14 ft.
(4267)
- 16 ft.
(4677)
SUGGESTED SPECIFICATION:
Furnish and install Nailor Model 92LS-SS Steri-System Linear Slot Diffusers of the size and type shown on the
plans and air distribution schedules. The diffusers shall be constructed entirely from 304 stainless steel (316 optional),
minimum 24 ga.. The diffuser shall incorporate a non-adjustable single slot designed to create a vertical air curtain
angled outwards 5 15 degrees. The diffuser shall incorporate a pressure plate behind the slot to ensure uniform slot
velocity. The pressure plate shall be 13% free area with 3/32" (2.4) dia. holes on 1/4" (6) staggered centers. The slot
and pressure plate shall be attached with 1/4 turn fasteners to allow for complete removal and access to the interior
for cleaning. The plenum shall incorporate radiused corners lengthwise to facilitate cleaning. Flanged plenum inlets
are to be maximum 5" (127) in height to allow duct clearance over standard light fixtures. Plenums over 7 ft. (2134) in
length shall be supplied in multiple sections with flange connections and stainless steel fasteners for field assembly.
All diffusers are to include safety cables to prevent accidental dropping of the removable face. Integral earthquake
hanger tabs shall be included with all units.
(Optional) An opposed blade damper, adjustable from the face of the diffuser, shall be provided with all units. Dampers
shall be held in place with wing nut fasteners and be removable from the face of the diffuser.
All exposed surfaces shall have a #3 satin polished finish.
The manufacturer shall provide published performance data for the diffuser, which shall be tested in accordance with
ANSI/ASHRAE Standard 70 1991.
Back
Home
Contents
Dimensions
Data
Spec
50
HOSPITAL/CLEANROOM DIFFUSERS
CFM
TP
VP
T
NC
Slot
Length
(ft)
3.646
5.458
7.125
10
9.125
12
11.125
14
13.125
16
14.792
Airflow (cfm/ft)
Airflow (cfm)
NC
TP
VP
T
Airflow (cfm)
NC
TP
VP
T
Airflow (cfm)
NC
TP
VP
T
Airflow (cfm)
NC
TP
VP
T
Airflow (cfm)
NC
TP
VP
T
Airflow (cfm)
NC
TP
VP
T
Airflow (cfm)
NC
TP
VP
T
25
30
35
40
45
91
0.029
0.004
1-1-3
136
0.025
0.004
1-1-4
178
0.028
0.004
1-1-4
228
0.031
0.005
1-1-5
278
0.026
0.004
1-2-5
328
0.029
0.004
1-2-5
370
0.027
0.004
1-2-5
109
0.042
0.006
1-1-4
164
0.037
0.005
1-2-4
214
0.040
0.006
1-2-5
274
0.045
0.007
1-2-5
334
0.038
0.006
1-2-6
394
0.042
0.006
1-2-6
444
0.039
0.006
1-2-6
128
0.057
0.008
1-2-4
191
0.050
0.007
1-2-5
249
0.054
0.008
1-2-6
319
0.062
0.009
1-2-6
389
0.052
0.008
1-3-7
459
0.057
0.008
1-3-7
518
0.053
0.008
1-3-7
146
0.074
0.011
1-2-5
218
0.065
0.010
1-2-5
285
0.071
0.011
1-2-6
365
0.081
0.012
1-3-6
445
15
0.067
0.010
1-3-7
525
16
0.074
0.011
1-3-7
592
17
0.069
0.010
1-3-7
164
0.094
0.014
1-2-5
246
15
0.082
0.012
1-2-5
321
16
0.090
0.013
1-3-6
411
17
0.102
0.015
1-3-7
501
18
0.085
0.013
2-3-7
591
19
0.094
0.014
2-3-7
666
19
0.088
0.013
2-3-7
Performance Notes:
1. Data derived from tests conducted in accordance with
ANSI/ASHRAE Standard 70 1991.
2. Noise Criteria (NC) values based on 10 dB room
absorption re 10 -12 watts with dampers fully open.
3. Dash () in space indicates an NC level of less than 15.
4. Throws are given at 150, 100 and 50 fpm terminal
velocities under isothermal conditions.
Back
Home
Contents
Dimensions
Airflow Measurements
1. Take velocity readings at a number of locations along
the length of the slot.
2. Total the various readings and divide by the number of
readings taken to arrive at an average slot discharge
velocity (Vk in FPM).
3. Calculate the airflow (CFM/ft) by multiplying the average
velocity by the Ak factor per foot which is 0.078.
Airflow (CFM/ft) = Average Slot Velocity (Vk) x Ak.
4. Calculate the total airflow (CFM) by multiplying by the
actual slot length (ft) shown above.
Airflow (CFM) = Airflow (CFM/ft) x Slot Length (ft).
Data
Spec
51
HOSPITAL/CLEANROOM DIFFUSERS
L/S
TP
VP
T
NC
Slot
Length
(m)
1219
1.11
1829
1.66
2438
2.17
3048
2.78
3658
3.39
4267
4.00
4677
4.51
38.7
46.4
54.2
61.9
69.7
43
7
1.0
0.3-0.3-0.9
64
6
1.0
0.3-0.3-1.2
84
7
1.0
0.3-0.3-1.2
108
8
1.2
0.3-0.3-1.5
131
6
1.0
0.3-0.6-1.5
155
7
1.0
0.3-0.6-1.5
175
7
1.0
0.3-0.6-1.5
51
10
1.5
0.3-0.3-1.2
77
9
1.2
0.3-0.6-1.2
101
10
1.5
0.3-0.6-1.5
129
11
1.7
0.3-0.6-1.5
158
9
1.5
0.3-0.6-1.8
186
10
1.5
0.3-0.6-1.8
209
10
1.5
0.3-0.6-1.8
60
14
2.0
0.3-0.6-1.2
90
12
1.7
0.3-0.6-1.5
118
13
2.0
0.3-0.6-1.8
151
15
2.2
0.3-0.6-1.8
184
13
2.0
0.3-0.9-2.1
217
14
2.0
0.3-0.9-2.1
244
13
2.0
0.3-0.9-2.1
69
18
2.7
0.3-0.6-1.5
103
16
2.5
0.3-0.6-1.5
134
18
2.7
0.3-0.6-1.8
172
20
3.0
0.3-0.9-1.8
210
15
17
2.5
0.3-0.9-2.1
248
16
18
2.7
0.3-0.9-2.1
279
17
17
2.5
0.3-0.9-2.1
77
23
3.5
0.3-0.6-1.5
116
15
20
3.0
0.3-0.6-1.5
151
16
22
3.2
0.3-0.9-1.8
194
17
25
3.7
0.3-0.9-2.1
236
18
21
3.2
0.6-0.9-2.1
279
19
23
3.5
0.6-0.9-2.1
314
19
22
3.2
0.6-0.9-2.1
Performance Notes:
1. Data derived from tests conducted in accordance with
ANSI/ASHRAE Standard 70 1991.
2. Noise Criteria (NC) values based on 10 dB room
absorption re 10 -12 watts with dampers fully open.
3. Dash () in space indicates an NC level of less than 15.
4. Throws are given at 0.76, 0.51 and 0.25 m/s terminal
velocities under isothermal conditions.
Back
Home
Contents
Dimensions
Airflow Measurements
1. Take velocity readings at a number of locations along
the length of the slot.
2. Total the various readings and divide by the number of
readings taken to arrive at an average slot discharge
velocity (Vk in m/s).
3. Calculate the airflow (l/s per m) by multiplying the
average velocity by the Ak factor per meter which is 23.8.
Airflow (l/s per m) = Average Slot Velocity (Vk) x Ak.
4. Calculate the total airflow (l/s) by multiplying by the
actual slot length (m) shown above.
Airflow (l/s) = Airflow (l/s per m) x Slot Length (m).
Data
Spec
52
HOSPITAL/CLEANROOM DIFFUSERS
STERI-SYSTEM
HOSPITAL OPERATING
ROOM AIR SYSTEM
STAINLESS STEEL
CONSTRUCTION
Models:
92STSYS
Stainless Steel
92STSYS-O
Stainless Steel
with Perimeter
Inlet Dampers
Model 92STSYS
The Nailor Steri-System is a complete operating room ventilation system specially designed to reduce airborne
contaminants, and thus, the risk of patient infection during surgery. By using directed airflow, a protective 'clean zone' is
created around the patient. The system consists of two main components.
Model 92LS-SS Linear Slot Diffusers, located around the perimeter, create a continuous curtain of air angled outwards
5 15 degrees. The curtain encloses the operating area and minimizes the possibility of contaminated air entering the
surgical area. The single slot design creates a uniform low velocity curtain that minimizes entrainment of contaminated air
into the curtain air stream. It also creates a wider velocity profile with less turbulence and hence less induction over similar
two slot designs. The face design incorporates longitudinal deflectors that horizontally deflect a small amount of air
lengthwise. This effectively joins the airflow through sections and corners forming a truly continuous air curtain, resulting in
enhanced isolation of the surgical area.
Model 92LFD-SS Laminar Flow Diffusers, installed above the operating table, produce a low velocity, non-aspirating,
vertical air pattern. This 'clean' conditioned air flows over the operating table protecting the patient while greatly increasing
the ventilation rate within the surgical area. The unique design incorporates a second pressure plate as an integral
assembly to ensure true laminar airflow.
The Steri-System is available in fourteen standard module sizes with a wide variety of custom variations that allow it to be
tailored to suit almost any application or configuration.
FEATURES:
All face plates and assemblies are
removable for cleaning and are
secured by 1/4 turn stainless steel
fasteners.
Safety cables are included as standard
and prevent accidental dropping of
the removable faces.
Standard units are designed for both
lay-in T-Bar ceiling systems and
surface mount applications.
Back
Home
Contents
Dimensions
Data
Spec
OPTIONS:
Perimeter Inlet Balancing Dampers
(Face operated and removable).
316 Stainless Steel construction.
53
HOSPITAL/CLEANROOM DIFFUSERS
35.75"
(908)
69.5"
(1765)
48"
(1219)
23.75"
(603)
96" (2438)
93.5" (2375)
1.25" (32)
10.75" (273)
117.5" (2985)
34.25" (870)
(CEILING OPENING)
33" (838)
14.46
22.25" (565)
(CEILING
OPENING)
14.46
16.67
21" (533)
16.67
66.75" (1695)
9.44
50.75"
(1289)
FLANGE
CONNECTION
(TYP. 2)
9.44
98.75" (2508)
9.44
4" (102)
9.44
8"
(203)
2.5" (64)
90.75" (2305)
Section Detail A A
Back
9.25"
(235)
(CEILING
OPENING)
114.75" (2915)
8"
(203)
9.875"
(251)
12"
(305)
Home
98.75" (2508)
5"
(127)
2 1/2" (64)
6"
(152)
Contents
Dimensions
Data
Spec
54
HOSPITAL/CLEANROOM DIFFUSERS
23.75"
(603)
12.25"
(311)
47.75"
(1213)
93.5"
(2375)
72"
(1829)
96" (2438)
93.5" (2375)
1.25" (32)
10.75" (273)
117.5" (2985)
8.33
15"
(381)
45"
(1143)
74.75"
(1899)
46.25"
(1175)
(CEILING
OPENING)
8.33
8.33
21" (533)
FLANGE
CONNECTION
(TYP. 4)
98.75" (2508)
8.33
4" (102)
2.5" (64)
8.33
8"
(203)
9.25"
(235)
(CEILING OPENING)
90.75" (2305)
92" (2337) (CEILING OPENING)
114.75" (2915)
8"
(203)
11.875"
(302)
12"
(305)
Back
Home
2 1/2" (64)
6"
(152)
Contents
8.33
16.67
22.25" (565)
(CEILING OPENING)
Section Detail A A
16.67
90.75" (2305)
8.33
8.33
98.75" (2508)
5"
(127)
12.25"
(311)
Dimensions
Data
Spec
55
HOSPITAL/CLEANROOM DIFFUSERS
117.5"
(2985)
35.75"
(908)
96"
(2438)
23.75"
(603)
96" (2438)
93.5" (2375)
1.25" (32)
10.75" (273)
117.5" (2985)
7.31
114.75" (2915)
33"
(838)
11.11
11.11
9.36
98.75"
(2508)
21" (533)
22.25" (565)
(CEILING OPENING)
Section Detail A A
7.31
4" (102)
8"
(203)
9.25"
(235)
(CEILING OPENING)
7.31
9.875"
(251)
98.75" (2508)
5"
(127)
12"
(305) 6"
(152)
Home
Contents
9.36
90.75" (2305)
8"
(203)
9.36
11.11
34.25"
(870)
(CEILING
OPENING)
9.36
Back
7.31
Dimensions
Data
Spec
56
HOSPITAL/CLEANROOM DIFFUSERS
93.5"
(2375)
72"
(1829)
35.75"
(908)
23.75"
(603)
120" (3048)
117.5" (2985)
1.25" (32)
10.75" (273)
141.5" (3594)
9.36
9.36
11.11
90.75" (2305)
7.31
11.11
7.31
11.11
33"
(838)
74.75"
(1899)
34.25"
(870)
(CEILING
OPENING)
7.31
7.31
21" (533)
FLANGE
CONNECTION
(TYP. 4)
22.25" (565)
(CEILING OPENING)
122.75" (3118)
Section Detail A A
2.5" (64)
9.36
4" (102)
8"
(203)
9.36
114.75" (2915)
9.25"
(235)
(CEILING OPENING)
138.75" (3524)
8"
(203)
9.875"
(251)
12"
(305)
Back
Home
122.75" (3118)
5"
(127)
2 1/2" (64)
6"
(152)
Contents
Dimensions
Data
Spec
57
HOSPITAL/CLEANROOM DIFFUSERS
47.75"
(1213)
117.5"
(2985)
96"
(2438)
23.75"
(603)
120" (3048)
117.5" (2985)
1.25" (32)
10.75" (273)
141.5" (3594)
8.33
114.75" (2915)
11.11
11.11
8.33
11.11
98.75"
(2508)
46.25"
(1175)
(CEILING
OPENING)
8.33
8.33
21" (533)
22.25" (565)
(CEILING OPENING)
FLANGE CONNECTION
(TYP. 4)
2.5" (64)
Section Detail A A
Back
45"
(1143)
8.33
8.33
8.33
4" (102)
8.33
8"
(203)
114.75" (2915)
116" (2946) (CEILING OPENING)
9.25" (235)
(CEILING OPENING)
138.75" (3524)
8"
(203)
9.875" (251)
12"
(305)
Home
122.75" (3118)
5" (127)
2 1/2" (64)
6" (152)
Contents
Dimensions
Data
Spec
58
HOSPITAL/CLEANROOM DIFFUSERS
141.5"
(3594)
47.75"
(1213)
120"
(3048)
23.75"
(603)
STERI-SYSTEM LINEAR DIFFUSERS
10 FT. (3048) NOMINAL MODULE SIZE
TWO 12" x 5" (305 x 127) FLANGED INLETS
MODEL: 92LS-SS-12x5-10-S-#3
(TYP. 2)
120" (3048)
117.5" (2985)
10.75" (273)
1.25" (32)
141.5" (3594)
7.51
7.51
138.75" (3524)
9.16
45"
(1143)
11.11
11.11
122.75"
(3118)
9.16
9.16
21" (533)
22.25" (565)
(CEILING OPENING)
Section Detail A A
11.11
46.25"
(1175)
(CEILING
OPENING)
9.16
2.5" (64)
4" (102)
8"
(203)
122.75" (3118)
7.51
7.51
114.75" (2915)
116" (2946) (CEILING OPENING)
11.875" (302)
8"
(203)
9.25"
(235)
(CEILING
OPENING)
138.75" (3524)
122.75" (3118)
2 1/2" (64)
12"
(305)
Back
Home
5" (127)
6" (152)
Contents
Dimensions
Data
Spec
59
HOSPITAL/CLEANROOM DIFFUSERS
93.5"
(2375)
72"
(1829)
35.75"
(908)
23.75"
(603)
144" (3658)
1.25" (32)
10.75" (273)
165.5" (4204)
10.16
10.16
6.51
6.51
8.33
90.75" (2305)
8.33
8.33
8.33
33"
(838)
74.75"
(1899)
34.25"
(870)
(CEILING
OPENING)
6.51
Section Detail A A
141.5" (3594)
Back
6.51
21" (533)
FLANGE
CONNECTION
(TYP. 4)
22.25" (565)
(CEILING OPENING)
146.75" (3727)
2.5" (64)
10.16
4" (102)
10.16
138.75" (3524)
8"
(203)
9.25"
(235)
(CEILING OPENING)
162.75" (4134)
8"
(203)
146.75" (3727)
9.875"
(251)
12"
(305)
Home
5"
(127)
2 1/2" (64)
6"
(152)
Contents
Dimensions
Data
Spec
60
HOSPITAL/CLEANROOM DIFFUSERS
47.75"
(1213)
117.5"
(2985)
12.25"
(311)
12.25"
(311)
96"
(2438)
23.75"
(603)
144" (3658)
141.5" (3594)
1.25" (32)
10.75" (273)
165.5" (4204)
9.16
9.16
11.11
114.75" (2915)
7.51
45"
(1143)
11.11
15"
(381)
7.51
11.11
15"
(381)
98.75"
(2805)
46.25"
(1175)
(CEILING
OPENING)
7.51
7.51
21" (533)
22.25" (565)
(CEILING OPENING)
Section Detail A A
FLANGE CONNECTION
(TYP. 4)
146.75" (3727)
2.5" (64)
9.16
4" (102)
9.16
8"
(203)
138.75" (3524)
146.75" (3727)
11.875"
(302)
12"
(305)
Back
9.25"
(235)
(CEILING
OPENING)
8"
(203)
Home
2 1/2" (64)
6" (152)
Contents
12.25"
(311)
Dimensions
5" (127)
12.25"
(311)
Data
Spec
61
HOSPITAL/CLEANROOM DIFFUSERS
141.5"
(3594)
12.25"
(311)
47.75"
(1213)
12.25"
(311)
120"
(3048)
23.75"
(603)
144" (3658)
141.5" (3594)
1.25" (32)
10.75" (273)
165.5" (4204)
8.33
8.33
8.33
138.75" (3524)
11.11
11.11
15"
(381)
122.75"
(3118)
8.33
8.33
21" (533)
22.25"
(565)
(CEILING OPENING)
16" x 5" (406 x 127)
FLANGED INLET
(TYP. 8)
FLANGE CONNECTION
(TYP. 4)
Section Detail A A
Back
11.11
15"
(381)
46.25"
45"
(1175) (1143)
(CEILING
OPENING)
8.33
2.5" (64)
4" (102)
8"
(203)
11.875" (302)
12"
2 1/2" (64)
(305) 6" (152)
Home
Contents
146.75" (3727)
8"
(203)
8.33
8.33
138.75" (3524)
140" (3556) (CEILING OPENING)
162.75" (4134)
146.75" (3727)
12.25"
12.25"
(311)
(311)
Dimensions
Data
9.25"
(235)
(CEILING
OPENING)
5" (127)
Spec
62
HOSPITAL/CLEANROOM DIFFUSERS
165.5"
(4204)
47.75"
(1213)
144"
(3658)
23.75"
(603)
STERI-SYSTEM LINEAR DIFFUSERS
12 FT. (3658) NOMINAL MODULE SIZE
TWO 16" x 5" (406 x 127) FLANGED INLETS
MODEL: 92LS-SS-16x5-12-S-#3
(TYP. 2)
144" (3658)
141.5" (3594)
1.25" (32)
10.75" (273)
165.5" (4204)
7.65
7.65
162.75" (4134)
9.02
8.33
8.33
8.33
9.02
146.75"
(3727)
9.02
21"
(533)
22.25"
(565)
(CEILING OPENING)
Section Detail A A
FLANGE CONNECTION
(TYP. 4)
2.5" (64)
4" (102)
8"
(203)
Back
Home
8.33
46.25" 45"
(1175) (1143)
(CEILING
OPENING)
9.02
2 1/2"
(64)
12"
(305) 6" (152)
Contents
146.75" (3727)
8"
(203)
7.65
7.65
138.75" (3524)
140" (3556) (CEILING OPENING)
162.75" (4134)
146.75" (3727)
11.875" (302)
9.25"
(235)
(CEILING
OPENING)
5" (127)
Dimensions
Data
Spec
63
HOSPITAL/CLEANROOM DIFFUSERS
117.5"
(2985)
35.75"
(908)
96"
(2438)
23.75"
(603)
1.25" (32)
10.75" (273)
189.5" (4813)
9.83
9.83
6.84
8.33
114.75" (2915)
6.84
Back
8.33
8.33
8.33
34.25"
33"
(870)
(CEILING (838)
OPENING)
93.75"
(2508)
6.84
Section Detail A A
165.5" (4204)
21" (533)
FLANGE CONNECTION
(TYP. 4)
170.75" (4337)
2.5" (64)
9.83
4" (102)
9.83
162.75" (4134)
164" (4166) (CEILING OPENING)
186.75" (4743)
8"
(203)
6.84
22.25" (565)
(CEILING OPENING)
8"
(203)
9.25"
(235)
(CEILING
OPENING)
170.75" (4337)
9.875" (251)
12"
(305)
Home
5" (127)
2 1/2" (64)
6" (152)
Contents
Dimensions
Data
Spec
64
HOSPITAL/CLEANROOM DIFFUSERS
141.5"
(3594)
120"
(3048)
47.75"
(1213)
23.75"
(603)
168" (4267)
165.5" (4204)
1.25" (32)
10.75" (273)
189.5" (4813)
9.02
9.02
7.65
138.75" (3524)
7.65
8.33
46.25"
(1175)
45"
(CEILING (1143)
OPENING)
8.33
8.33
122.75"
(3118)
7.65
7.65
21" (533)
22.25"
(565)
(CEILING OPENING)
Section Detail A A
FLANGE CONNECTION
(TYP. 4)
2.5" (64)
4" (102)
8"
(203)
12"
(305)
Back
8.33
Home
170.75" (4337)
9.02
9.02
162.75" (4134)
164" (4166) (CEILING OPENING)
186.75" (4743)
170.75" (4337)
11.875" (302)
8"
(203)
5" (127)
2 1/2" (64)
6" (152)
Contents
9.25"
(235)
(CEILING
OPENING)
Dimensions
Data
Spec
65
HOSPITAL/CLEANROOM DIFFUSERS
165.5"
(4204)
47.75"
(1213)
144"
(3618)
23.75"
(603)
168" (4267)
165.5" (4204)
1.25" (32)
10.75" (273)
189.5" (4813)
8.33
8.33
162.75" (4134)
8.33
8.33
8.33
21" (533)
22.25"
(565)
(CEILING
OPENING)
8.33
FLANGE
CONNECTION
(TYP. 4)
2.5" (64)
4" (102)
8"
(203)
12"
(305)
Home
8.33
146.75"
(3727)
8.33
Section Detail A A
Back
8.33
46.25"
45"
(1175) (1143)
(CEILING
OPENING)
8.33
170.75" (4337)
8"
(203)
8.33
8.33
162.75" (4134)
164" (4166) (CEILING OPENING)
186.75" (4743)
170.75" (4337)
11.875" (302)
5" (127)
2 1/2" (64)
6" (152)
Contents
9.25"
(235)
(CEILING
OPENING)
Dimensions
Data
Spec
66
HOSPITAL/CLEANROOM DIFFUSERS
189.5"
(4813)
47.75"
(1213)
168"
(4267)
23.75"
(603)
LAMINAR FLOW DIFFUSERS
48 x 24 (1219 x 610) MODULE SIZE
12" (305) DIA. INLET
MODEL: 92LFD-SS-12-48x24-S-#3
(TYP. 4)
168" (4267)
165.5" (4204)
1.25" (32)
10.75" (273)
189.5" (4813)
7.84
7.84
186.75" (4743)
5.89
5.89
5.89
8.33
8.33
8.33
8.33
45"
46.25" (1143)
(1175)
(CEILING
OPENING)
170.75"
(4337)
21" (533)
22.25"
(565)
(CEILING
OPENING)
5.89
Section Detail A A
5.89
FLANGE CONNECTION
(TYP. 6)
2.5" (64)
4" (102)
8"
(203)
Back
Home
8"
(203)
7.84
7.84
162.75" (4134)
164" (4166) (CEILING OPENING)
11.875" (302)
12"
(305)
170.75"
(4337)
9.25" (235)
(CEILING OPENING)
186.75" (4743)
170.75" (4337)
2 1/2" (64)
6" (152)
Contents
Dimensions
5.89
5" (127)
Data
Spec
67
HOSPITAL/CLEANROOM DIFFUSERS
92STSYS - 12 x 10 - S - #3 - 316
MODEL
OPTIONS
92STSYS
- None (default)
(2438 x 1219)
-8x6
(2438 x 1829)
-8x8
(2438 x 2438)
- 10 x 6
(3048 x 1829)
- 10 x 8
(3048 x 2438)
- 10 x 10
(3048 x 3048)
- 12 x 6
(3658 x 1829)
- 12 x 8
(3658 x 2438)
- 12 x 10
(3658 x 3048)
- 12 x 12
(3658 x 3658)
- 14 x 8
(4267 x 2438)
- 14 x 10
(4267 x 3048)
- 14 x 12
(4267 x 3658)
- 14 x 14
(4267 x 4267)
316
FINISH
#3
- Special
SP
FRAME TYPE
- Lay-in T-Bar
- Surface Mount
SUGGESTED SPECIFICATION:
Furnish and install Nailor STERI-SYSTEM Model 92STSYS Hospital Operating Room Air Systems of the size and
type shown on the plans and air distribution schedules. The system shall be specially designed to reduce airborne
contaminants, and thus, the risk of patient infection during surgery. The system shall be composed of two main
components, Model 92LFD-SS Laminar Flow Diffusers and Model 92LS-SS Linear Slot Diffusers, constructed as follows:
The Laminar Flow Diffusers shall be constructed entirely from 304 stainless steel (316 optional), minimum 24 ga.. The
perforated face of the diffuser shall have 13% free area with 3/32" (2.4) dia. holes on 1/4" (6) staggered centers. The
face shall incorporate a second pressure plate as an integral assembly to ensure true laminar airflow. The face shall
be attached with 1/4 turn fasteners to allow for complete removal and access to the interior for cleaning. All diffusers
are to include safety cables to prevent accidental dropping of the removable face. A disk type damper, adjustable from
the face of the diffuser, shall be provided with all units. Integral earthquake hanger tabs shall be included with all units.
The Linear Slot Diffusers shall be constructed entirely from 304 stainless steel (316 optional), minimum 24 ga.. The
diffuser shall incorporate a non-adjustable single slot designed to create a vertical air curtain angled outwards 5 15
degrees. The diffuser shall incorporate a pressure plate behind the slot to ensure uniform slot velocity. The pressure
plate shall be 13% free area with 3/32" (2.4) dia. holes on 1/4" (6) staggered centers. The slot and pressure plate shall
be attached with 1/4 turn fasteners to allow for complete removal and access to the interior for cleaning. The plenum
shall incorporate radiused corners lengthwise to facilitate cleaning. Flanged plenum inlets are to be maximum 5" (127)
in height to allow duct clearance over standard light fixtures. Plenums over 7 ft. (2134) in length shall be supplied in
multiple sections with flange connections and stainless steel fasteners for field assembly. All diffusers are to include
safety cables to prevent accidental dropping of the removable face. Integral earthquake hanger tabs shall be included
with all units.
(Optional) An opposed blade damper, adjustable from the face of the diffuser, shall be provided on all perimeter inlets.
Dampers shall be held in place with wing nut fasteners and be removable from the face of the diffuser.
All exposed surfaces shall have a #3 satin polished finish.
The manufacturer shall provide published performance data for the system, which shall be tested in accordance with
ANSI/ASHRAE Standard 70 1991.
Back
Home
Contents
Dimensions
Data
Spec
68
HOSPITAL/CLEANROOM DIFFUSERS
SELECTION
OF
Source
Room
Types
ASHRAE
1999 Handbook
HVAC Applications
Operating Room
Delivery Room
American Institute
of Architects
2001 Edition
Guidelines for
Design & Construction
of Hospital & Health
Care Facilities
Canadian Standards
Assoc. CSA Standard
Z317.201
September, 2001
Minimum Air
Minimum
Changes/Hour
Outside Air
ACH
ACH
25
5
(Recirculating Air System)
or
15
15
(All Outdoor Air System)
Operating/Surgical
Cystoscopic Rooms
Delivery Room
Trauma Room
Procedure Room
Bronchoscopy,
Triage, ER or
Radiology Waiting Rooms
Endoscopy
Operating Rooms
Endoscopy,
Bronchoscopy,
Cystoscopy, PACU,
Surgical Day Care,
Caesarean Delivery
15
Minimum
Filtration
Efficiency
99.97% for Orthopedic,
Bone Marrow and
Organ Transplant.
90% for General Procedure
and Delivery Rooms.
3
90%
12
20
99.97%
This table summarizes some of the current recommendations for operating room ventilation rates. Consult the actual
documents for specific requirements and exceptions.
Back
Home
Contents
Dimensions
Data
Spec
69
HOSPITAL/CLEANROOM DIFFUSERS
Performance Data
Steri-System Hospital Operating Room Air Distribution Systems
System Selection Chart:
Imperial Units
Module
Size
Perimeter
Slot Length
(ft)
Perimeter
Inlet Size(s)
(Qty @ W x H)
Perimeter CFM
Range
(25-35-45 cfm/ft)
8x4
8x6
8x8
10 x 6
10 x 8
10 x 10
12 x 6
12 x 8
12 x 10
12 x 12
14 x 8
14 x 10
14 x 12
14 x 14
25.17
28.5
32.5
32.5
36.5
40.5
36.5
40.5
44.5
48.5
44.5
48.5
52.5
55.83
2 @ 16 x 5, 4 @ 10 x 5
8 @ 10 x 5
4 @ 12 x 5, 4 @ 10 x 5
4 @ 12 x 5, 4 @ 10 x 5
8 @ 12 x 5
4 @ 16 x 5, 4 @ 12 x 5
4 @ 16 x 5, 4 @ 10 x 5
4 @ 16 x 5, 4 @ 12 x 5
8 @ 16 x 5
4 @ 18 x 5, 4 @ 16 x 5
4 @ 18 x 5, 4 @ 12 x 5
4 @ 18 x 5, 4 @ 16 x 5
8 @ 18 x 5
6 @ 14 x 5, 4 @ 18 x 5
630-880-1135
715-1000-1285
815-1140-1465
815-1140-1465
915-1280-1645
1015-1420-1825
915-1280-1645
1015-1420-1825
1115-1560-2005
1215-1700-2185
1115-1560-2005
1215-1700-2185
1315-1840-2365
1395-1955-2510
Center Panels
Center Panels
Recommended Size
CFM Range
(Qty @ Inlet Module) (Low-Med-High)
2 @ 10" dia 36 x 24
2 @ 12" dia 48 x 24
3 @ 10" dia 36 x 24
3 @ 10" dia 36 x 24
3 @ 10" dia 48 x 24
3 @ 12" dia 48 x 24
4 @ 10" dia 36 x 24
3 @ 12" dia 48 x 24
3 @ 12" dia 48 x 24
4 @ 12" dia 48 x 24
4 @ 10" dia 36 x 24
4 @ 12" dia 48 x 24
4 @ 12" dia 48 x 24
4 @ 12" dia 48 x 24
315-440-565
355-500-640
405-570-730
405-570-730
455-640-825
505-710-910
455-640-825
505-710-910
555-780-1000
605-850-1090
555-780-1000
605-850-1090
655-920-1180
700-975-1255
Total System
CFM Range
(Low-Med-High)
Total System
NC
(Low-Med-High)
945-1320-1700
1070-1500-1925
1220-1710-2195
1220-1710-2195
1370-1920-2470
1520-2130-2735
1370-1920-2470
1520-2130-2735
1670-2340-3005
1820-2550-3275
1670-2340-3005
1820-2550-3275
1970-2760-3545
2095-2930-3765
25-29-34
23-25-29
25-29-33
25-29-33
25-28-32
24-26-29
25-29-32
24-26-29
24-27-32
22-27-28
26-30-34
22-27-28
26-26-30
24-24-32
Total System
l/s Range
(Low-Med-High)
Total System
NC
(Low-Med-High)
446-623-802
505-708-908
576-807-1036
576-807-1036
647-906-1166
717-1005-1291
647-906-1166
717-1005-1291
788-1104-1418
859-1203-1545
788-1104-1418
859-1203-1545
930-1302-1673
989-1383-1777
25-29-34
23-25-29
25-29-33
25-29-33
25-28-32
24-26-29
25-29-32
24-26-29
24-27-32
22-27-28
26-30-34
22-27-28
26-26-30
24-24-32
Metric Units
Module
Size
Perimeter
Slot Length
(m)
Perimeter
Inlet Size(s)
(Qty @ W x H)
8x4
8x6
8x8
10 x 6
10 x 8
10 x 10
12 x 6
12 x 8
12 x 10
12 x 12
14 x 8
14 x 10
14 x 12
14 x 14
7.672
8.687
9.906
9.906
11.125
12.344
11.125
12.344
13.564
14.783
13.564
14.783
16.002
17.017
Performance Notes:
1. Data derived from tests conducted
in accordance with ANSI/ASHRAE
Standard 70 1991.
2. Noise Criteria (NC) values based
on 10 dB room absorption re 10 -12
watts with dampers fully open.
Back
Home
Contents
Perimeter l/s
Center Panels
Center Panels
Range
Recommended Size
l/s Range
(38.7-54.2-69.7 l/s/m) (Qty @ Inlet Module) (Low-Med-High)
297-415-536
337-472-606
385-538-691
385-538-691
432-604-776
479-670-861
432-604-776
479-670-861
526-736-946
573-802-1031
526-736-946
573-802-1031
621-868-1116
658-923-1184
Dimensions
Data
Spec
149-208-267
168-236-302
191-269-344
191-269-344
215-302-389
238-335-429
215-302-389
238-335-429
262-368-472
285-401-514
262-368-472
285-401-514
309-434-557
330-460-592
70
HOSPITAL/CLEANROOM DIFFUSERS
Performance Data
STERI-SYSTEM HOSPITAL OPERATING ROOM AIR DISTRIBUTION SYSTEMS
QUICK SELECTION CHART
14 x 14
14 x 12
12 x 12 OR 14 x 10
12 x 10 OR 14 x 8
10 x 10 OR 12 x 8
10 x 8 OR 12 x 6
8 x 8 OR 10 x 6
8x6
8x4
500
(236)
1000
(472)
1500
(708)
2000
(944)
2500
(1180)
3000
(1412)
3500
(1652)
4000
(1888)
SELECTION EXAMPLE
Design Criteria: General Procedure Operating Room
Room Size: 20 ft wide x 25 ft long x 10 ft ceiling height
= 5000 ft 3 Room Volume
Minimum: 8 ft x 8 ft Clean Zone Required
Supply Air Temperature: 55F
Room Temperature Set Point Range: 62 80F
Airflow: Minimum 25 ACH (recirculating system)
Positive room pressure
Sound Level: 25 35 NC
Calculate required room airflow rate:
Airflow (cfm) = Room Volume (ft 3) x ACH
60
Airflow (cfm) = 5000 x 25/60 = 2083 cfm
We must then confirm that this airflow will meet the
maximum cooling load requirement for the room (not
shown). Note that the room temperature must be able to be
maintained at the lowest specified temperature for some
procedures (62F in this example). With a 55F supply air
temperature the load may, in some cases, require an
increase in airflow to compensate for the low T between
supply air and room temperature. Also some procedures
may require the system to quickly reduce or increase the
room temperature and humidity during or between
procedures. One of the features of the Steri-System design
concept is the creation of a micro-climate within the clean
zone. The enhanced air change rate within the curtain
(Refer to Table 1 in the Engineering Section) and the use of
non-aspirating Laminar Flow Diffusers create a room within
a room effect. An analysis of the cooling load within the
air curtain should be considered for critical
Back
Home
Contents
Dimensions
projects. Obviously, for the 80F set point, the reheat coil
and modulating valve must be sized accordingly. (Refer
to the Nailor VAV Terminal Units catalog for more
information on reheat coil selection).
From the selection chart we see that the airflow falls
midrange for a 12 x 8 Steri-System module size which
meets our minimum specified clean zone size.
From the module layout page we have all the pertinent
dimensions as well as recommended inlet sizes and
airflows. This should be co-ordinated with the desired
ceiling layout for surgical lighting, utility columns,
monitors and equipment etc.. Several different module
sizes will meet the specified criteria and the choice will
generally depend on the layout. (Placement of diffusers
above the table should take priority over placement of
light fixtures).
Also from the selection chart, we find a system NC level
of 26 which falls well within the recommended sound
levels. Therefore a standard 12 x 8 Module Steri-System
will meet our criteria for this example.
For return air grille sizing and room pressurization we will
use the recommended 85% of the supply air total and a
minimum of two inlets.
Therefore:
Total Return Air = Supply Airflow x 0.85 = 2083 x 0.85
= 1770 cfm total
or for two inlets
= 885 cfm each
For a standard Model 67FB45 and sizing for low sound
and pressure drop we find that two grilles 18" x 18" (or
equivalent size) will be sufficient, resulting in a low noise
level (< NC 20) and pressure drop (< 0.1" w.g.).
Data
Spec
71
HOSPITAL/CLEANROOM DIFFUSERS
Performance Data
STERI-SYSTEM HOSPITAL OPERATING ROOM AIR DISTRIBUTION SYSTEMS
PERFORMANCE TEST 12 x 8 STERI-SYSTEM MODULE
(Medium Airflow Range 35 cfm/ft Perimeter / 30 cfm/sq. ft Center Panels)
12
24
36
48
60
72
84
96
140 - 150
130 - 140
120 - 130
110 - 120
100 - 110
90 - 100
80 - 90
70 - 80
60 - 70
50 - 60
40 - 50
30 - 40
20 - 30
10 - 20
AIR VELOCITY
(ft/min)
90
84
78
72
66
60
54
48
42
36
30
24
18
12
-6
-12
-18
-24
-30
-36
-42
-48
-54
-60
-66
-72
-78
-84
-90
108
The graph above shows actual air velocities and the associated isovels. This data was obtained in a full scale
mock-up test performed on a standard 12 x 8 Steri-System module under isothermal conditions.
Performance Notes:
1. Data derived from tests conducted in accordance with
ANSI/ASHRAE Standard 70 1991.
2. Performance is for standard 12 x 8 module SteriSystem under isothermal conditions.
Back
Home
Contents
Dimensions
Data
Spec
72
HOSPITAL/CLEANROOM DIFFUSERS
STAINLESS STEEL
RETURN GRILLES AND
REGISTERS
LOUVERED FACE
FIXED 45 BLADE
DEFLECTION
3/4" (19) SPACING
1/4 TURN FASTENERS
Model:
67FB45
(Suffix 'O' adds stainless
steel opposed blade
damper)
Model 67FB45
Model 67FB45 Return Grilles and Registers have fixed horizontal blades (parallel to width/first specified dim.) spaced on 3/4"
(19) centers with 45 straight face deflection. The grille core is secured to the face of the outer frame with stainless steel 1/4 turn
fasteners allowing quick removal for cleaning or changing the filters.
The streamlined blades and open spacing maintain a minimum effective free area of 50%, which minimizes intake velocity,
reduces inlet pressure and provides quiet operation. Deflected blade grilles installed in a low or high side wall location are visionproof with the grille blade deflection facing away from the line of sight.
Stainless steel grilles and registers are well suited for applications involving corrosive environments, high humidity or frequent
cleaning with strong chemicals. Typical projects include hospitals, cleanrooms, laboratories, industrial and manufacturing facilities.
OPTIONS:
316 Stainless Steel construction.
AW Appliance White finish.
F2
WT
4 7/8" (121)
3 7/8" (95)
2 7/8" (70)
OPT.
O.B.D.
Model 67FB45
Home
Contents
OPTIONAL
1" OR 2"
(25 OR 51)
FILTER CLIPS
1 3/4"
1"
(44) (25)
2 1/4" (57)
3 1/4" (83)
Back
F1
FEATURES:
Dimensions
Data
Spec
73
HOSPITAL/CLEANROOM DIFFUSERS
67FB 45 - O - 24 x 12 - S - #3 - A - 316
MODEL
- 304 Stainless Steel
(Blades louvered)
ACCESSORIES
- Standard (default) None
67FB
BLADE DEFLECTION
- 45 Defl., 3/4" (19) Spacing
45
DAMPER (OBD)
- Stainless Steel (standard)
- No Damper
FASTENING
- Standard (default) Screw Holes A
WIDTH
FINISH
- #3 Satin Polished (default)
- Appliance White
- Special
inches (mm)
HEIGHT
inches (mm)
#3
AW
SP
Notes:
1. These grilles feature a subframe as standard for applications which may require frequent removal for cleaning.
You must specify filter clips for filter applications.
2. For Frame/Border Type S, duct size is listed + 1/4" (6).
3. Core fastening: Standard core is secured with four 1/4 turn slotted fasteners.
SUGGESTED SPECIFICATION:
Furnish and install Nailor Model 67FB45 Return Grilles of the size and type shown on the plans and air distribution
schedules. The grilles shall be constructed entirely from 304 stainless steel (316 optional), minimum 24 ga..
Streamlined shaped roll-formed blades shall be fixed on 3/4" (19) centers. The grille core shall be secured to the outer
frame with stainless steel 1/4 turn fasteners to allow for complete removal and access to the interior for cleaning.
(Optional) An opposed blade damper, adjustable from the face of the grille, shall be provided with all units. Dampers
shall be attached to the grille core and be completely removable.
All exposed surfaces shall have a #3 satin polished finish.
The manufacturer shall provide published performance data for the grille, which shall be tested in accordance with
ANSI/ASHRAE Standard 70 1991.
Back
Home
Contents
Dimensions
Data
Spec
74
HOSPITAL/CLEANROOM DIFFUSERS
Performance Data
Fixed Blade Return Grilles and Registers
Model Series: 67FB45
Imperial Units
Listed
Duct Size
(inches)
6x6
8x6
10 x 6
Alternate
Size
(inches)
8x4
10 x 4
10 x 5
12 x 4
12 x 5
16 x 4
Core
Area
(sq. ft.)
Ak
Factor
0.20
0.23
0.28
0.30
0.35
0.37
8x8
14 x 5
0.38
0.40
12 x 6
18 x 4
0.42
0.45
0.58
0.59
0.61
0.62
0.65
0.67
0.74
0.74
0.90
0.89
1.24
1.22
1.37
1.34
1.52
1.49
1.64
1.58
1.85
1.78
2.10
2.01
2.32
2.23
2.61
2.48
3.17
3.00
3.54
3.34
3.79
3.56
4.27
4.01
4.47
4.19
4.77
4.46
5.20
4.85
5.74
5.35
5.99
5.57
12 x 8
10 x 10
18 x 6
12 x 10
12 x 12
14 x 14
18 x 12
24 x 10
16 x 16
24 x 12
18 x 18
30 x 12
20 x 20
22 x 22
30 x 18
24 x 24
36 x 18
26 x 26
30 x 24
28 x 28
36 x 24
30 x 30
16 x 6
24 x 4
14 x 7
26 x 4
14 x 8
28 x 4
16 x 8
24 x 5
14 x 10
18 x 8
16 x 12
20 x 10
16 x 14
22 x 10
20 x 12
30 x 8
18 x 14
22 x 12
18 x 16
20 x 14
20 x 16
24 x 14
20 x 18
22 x 16
24 x 18
26 x 16
24 x 20
26 x 18
24 x 22
34 x 16
26 x 22
28 x 20
32 x 20
40 x 16
28 x 24
48 x 14
28 x 26
32 x 22
30 x 26
36 x 22
30 x 28
40 x 22
34 x 26
38 x 24
Back
30 x 4
20 x 6
24 x 6
38 x 4
24 x 8
34 x 6
28 x 8
38 x 6
30 x 8
30 x 10
36 x 8
28 x 12
32 x 10
26 x 14
36 x 10
30 x 14
36 x 12
30 x 16
36 x 14
40 x 14
32 x 18
36 x 16
46 x 14
36 x 20
40 x 18
40 x 20
44 x 20
48 x 20
Home
Contents
Core Velocity
VP
Neg. SP
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
100
.001
.003
20
28
35
38
42
58
61
65
74
90
124
137
152
164
185
210
232
261
317
354
379
427
447
477
520
574
599
200
.002
.014
40
56
70
76
84
116
122
130
148
180
248
274
304
328
370
420
464
522
634
708
758
854
894
954
1040
1148
1198
Dimensions
300
.006
.031
60
84
105
114
126
174
183
195
222
270
372
411
456
492
555
630
696
783
951
1062
1137
1281
1341
1431
15
1560
15
1722
15
1797
15
Data
400
.010
.055
80
112
140
152
168
232
244
260
15
296
15
360
16
496
16
548
17
608
17
656
18
740
18
840
18
928
19
1044
19
1268
20
1416
20
1516
20
1708
21
1788
21
1908
22
2080
22
2296
22
2396
22
500
.016
.086
100
140
15
175
16
190
17
210
18
290
19
305
19
325
20
370
20
450
21
620
21
685
22
760
22
820
23
925
23
1050
23
1160
24
1305
24
1585
25
1770
25
1895
25
2135
26
2235
26
2385
27
2600
27
2870
28
2995
28
Spec
600
.022
.124
120
19
168
20
210
21
228
22
252
23
348
24
366
24
390
25
444
25
540
26
744
26
822
27
912
27
984
28
1110
28
1260
29
1392
29
1566
30
1902
31
2124
31
2274
31
2562
32
2682
32
2862
33
3120
33
3444
34
3594
34
700
.031
.168
140
24
196
25
245
26
266
27
294
27
406
28
427
29
455
30
518
30
630
31
868
31
959
32
1064
32
1148
33
1295
33
1470
34
1624
34
1827
35
2219
35
2478
36
2653
36
2989
37
3129
37
3339
38
3640
38
4018
38
4193
39
800
.040
.220
160
28
224
29
280
30
304
31
336
32
464
33
488
34
520
34
592
35
720
36
992
36
1096
37
1216
38
1312
38
1480
38
1680
39
1856
39
2088
40
2536
40
2832
41
3032
41
3416
42
3576
42
3816
42
4160
43
4592
43
4792
43
900
.050
.278
180
32
252
33
315
34
342
35
378
36
522
37
549
37
585
38
666
39
810
39
1116
40
1233
40
1368
41
1476
41
1665
41
1890
42
2088
42
2349
43
2853
43
3186
44
3411
44
3843
45
4023
45
4293
46
4680
46
5166
47
5391
47
1000
.062
.344
200
36
280
37
350
38
380
39
420
40
580
41
610
41
650
41
740
42
900
42
1240
43
1370
43
1520
44
1640
44
1850
45
2100
45
2320
46
2610
46
3170
47
3540
48
3790
48
4270
49
4470
49
4770
50
5200
50
5740
51
5990
51
75
HOSPITAL/CLEANROOM DIFFUSERS
Performance Data
Fixed Blade Return Grilles and Registers
Model Series: 67FB45
Imperial Units
Listed
Duct Size
(inches)
Core
Area
(sq. ft.)
Ak
Factor
6.84
6.34
7.69
7.13
8.69
8.02
9.70
8.94
10.77
9.90
11.89
10.92
13.07
11.98
46 x 46
14.30
13.10
48 x 48
15.59
14.26
32 x 32
48 x 24
36 x 36
38 x 38
40 x 40
42 x 42
44 x 44
Alternate
Size
(inches)
36 x 30 46 x 22
38 x 28
34 x 34 38 x 30
36 x 32 48 x 28
38 x 34 46 x 28
42 x 30 48 x 26
42 x 34 48 x 30
44 x 34
42 x 36 48 x 32
46 x 34
44 x 40 48 x 36
46 x 38
46 x 42
Core Velocity
VP
Neg. SP
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
100
.001
.003
684
769
869
970
1077
1189
1307
1430
1559
200
.002
.014
1368
1538
1738
1940
2154
2378
2614
2860
3118
300
.006
.031
2052
16
2307
17
2607
17
2910
18
3231
18
3567
19
3921
19
4290
20
4677
20
CFM
VP
Neg. SP NC
-
Back
Home
Contents
Dimensions
400
.010
.055
2736
23
3076
23
3476
24
3880
24
4308
24
4756
25
5228
25
5720
26
6236
26
500
.016
.086
3420
29
3845
29
4345
29
4850
30
5385
30
5945
31
6535
31
7150
32
7795
32
600
.022
.124
4104
35
4614
35
5214
36
5820
36
6462
36
7134
37
7842
37
8580
38
9354
38
700
.031
.168
4788
39
5383
40
6083
41
6790
41
7539
42
8323
42
9149
42
10010
43
10913
43
800
.040
.220
5472
44
6152
44
6952
45
7760
45
8616
45
9512
46
10456
46
11440
47
12472
47
900
.050
.278
6156
48
6921
48
7821
49
8730
49
9693
50
10701
50
11763
50
12870
51
14031
51
1000
.062
.344
6840
52
7690
52
8690
53
9700
53
10770
54
11890
54
13070
54
14300
55
15590
55
Air Measurement
1"
(25)
Data
Spec
76
HOSPITAL/CLEANROOM DIFFUSERS
Performance Data
Fixed Blade Return Grilles and Registers
Model Series: 67FB45
Metric Units
Listed
Duct Size
(mm)
Alternate
Size
(mm)
203 x 102
152 x 152
254 x 102
254 x 127
203 x 152
305 x 102
305 x 127
254 x 152
406 x 102
Core
Area
(sq. m)
Ak
Factor
.019
21
.026
28
.033
34
.035
37
.039
42
.054
55
.057
58
.060
62
.069
69
.084
83
.115
113
.127
125
.141
139
.152
147
.172
165
.195
187
.216
207
.242
231
.294
279
.329
310
.352
331
.397
373
.415
390
.443
415
.483
451
.533
497
.556
518
305 x 203
254 x 254
457 x 152
305 x 254
305 x 305
356 x 356
457 x 305
610 x 254
406 x 406
610 x 305
457 x 457
762 x 305
508 x 508
559 x 559
762 x 457
610 x 610
914 x 457
660 x 660
762 x 610
711 x 711
914 x 610
762 x 762
406 x 152
610 x 102
356 x 178
660 x 102
356 x 203 762 x 102
711 x 102
406 x 203 508 x 152
610 x 127
356 x 254 610 x 152
457 x 203 965 x 102
406 x 305 610 x 203
508 x 254 864 x 152
406 x 356 711 x 203
559 x 254 965 x 152
508 x 305
762 x 203
457 x 356 762 x 203
559 x 305
457 x 406 762 x 254
508 x 356 914 x 203
508 x 406 711 x 305
610 x 356 813 x 254
508 x 457 660 x 356
559 x 406 914 x 254
610 x 457 762 x 356
660 x 406 914 x 305
610 x 508 762 x 406
660 x 457 914 x 356
610 x 559 1016 x 356
863 x 406
660 x 559 813 x 457
711 x 508 914 x 406
813 x 508 1168 x 356
1016 x 406
711 x 610
1219 x 356
711 x 660 914 x 508
813 x 559 1016 x 457
762 x 660 1016 x 508
914 x 559
762 x 711 1118 x 508
1016 x 559
864 x 660 1219 x 508
965 x 610
Back
Home
Contents
Core Velocity
VP
Neg. SP
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
0.51
0.2
0.7
9
13
17
18
20
27
29
31
35
42
59
65
72
77
87
99
109
123
150
167
179
202
211
225
245
271
283
Dimensions
1.01
0.5
3.5
19
26
33
36
40
55
58
61
70
85
117
129
143
155
175
198
219
246
299
334
358
403
422
450
491
542
565
1.52
1.5
7.7
28
40
50
54
59
82
86
92
105
127
176
194
215
232
262
297
328
369
449
501
537
605
633
675
15
736
15
813
15
848
15
Data
2.03
2.5
14
38
53
66
72
79
109
115
123
15
140
15
170
16
234
16
259
17
287
17
310
18
349
18
396
18
438
19
493
19
598
20
668
20
715
20
806
21
844
21
900
22
982
22
1083
22
1131
22
2.54
4.0
21
47
66
15
83
16
90
17
99
18
137
19
144
19
153
20
175
20
212
21
293
21
323
22
359
22
387
23
437
23
495
23
547
24
616
24
748
25
835
25
894
25
1008
26
1055
26
1125
27
1227
27
1354
28
1413
28
Spec
3.05
5.5
31
57
19
79
20
99
21
108
22
119
23
164
24
173
24
184
25
210
25
255
26
351
26
388
27
430
27
464
28
524
28
595
29
657
29
739
30
898
31
1002
31
1073
31
1209
32
1266
32
1351
33
1472
33
1625
34
1696
34
3.55
7.7
42
66
24
92
25
116
26
126
27
139
27
192
28
202
29
215
30
244
30
297
31
410
31
453
32
502
32
542
33
611
33
694
34
766
34
862
35
1047
35
1169
36
1252
36
1411
37
1477
37
1576
38
1718
38
1896
38
1979
39
4.06
10
55
76
28
106
29
132
30
143
31
159
32
219
33
230
34
245
34
279
35
340
36
468
36
517
37
574
38
619
38
698
38
793
39
876
39
985
40
1197
40
1336
41
1431
41
1612
42
1688
42
1801
42
1963
43
2167
43
2261
43
4.57
12
69
85
32
119
33
149
34
161
35
178
36
246
37
259
37
276
38
314
39
382
39
527
40
582
40
646
41
697
41
786
41
892
42
985
42
1108
43
1346
43
1503
44
1610
44
1814
45
1898
45
2026
46
2208
46
2438
47
2544
47
5.08
15
86
94
36
132
37
165
38
179
39
198
40
274
41
288
41
307
41
349
42
425
42
585
43
647
43
717
44
774
44
873
45
991
45
1095
46
1232
46
1496
47
1671
48
1789
48
2015
49
2109
49
2251
50
2454
50
2709
51
2827
51
77
HOSPITAL/CLEANROOM DIFFUSERS
Performance Data
Fixed Blade Return Grilles and Registers
Model Series: 67FB45
Metric Units
Listed
Duct Size
(mm)
813 x 813
1219 x 610
914 x 914
965 x 965
1016 x 1016
1067 x 1067
1118 x 1118
1168 x 1168
1219 x 1219
Alternate
Core
Ak
Core Velocity
Size
Area Factor VP
(mm)
(sq. m)
Neg. SP
914 x 762 1168 x 559
L/S
.635
589
965 x 711
NC
864 x 864 965 x 762
L/S
.714
663
914 x 813 1219 x 711
NC
965 x 864 1168 x 711
L/S
.807
746
1067 x 762 1219 x 660
NC
1067 x 864 1219 x 762
L/S
.901
831
1118 x 864
NC
1067 x 914 1219 x 813
L/S
1.00
920
1168 x 864
NC
1118 x 1016 1219 x 914
L/S
1.10
1015
1168 x 965
NC
1168 x 1067
L/S
1.21
1114
NC
L/S
1.33
1218
NC
L/S
1.45
1326
NC
0.51
0.2
0.7
323
363
410
458
508
561
617
675
736
1.01
0.5
3.5
646
726
820
915
1016
1122
1234
1350
1471
1.52
1.5
7.7
968
16
1089
17
1230
17
1373
18
1525
18
1683
19
1850
19
2024
20
2207
20
L/S
VP
Neg. SP NC
-
Back
Home
Contents
Dimensions
2.03
2.5
14
1291
23
1452
23
1640
24
1831
24
2033
24
2244
25
2467
25
2699
26
2943
26
2.54
4.0
21
1614
29
1814
29
2050
29
2289
30
2541
30
2805
31
3084
31
3374
32
3678
32
3.05
5.5
31
1937
35
2177
35
2460
36
2746
36
3049
36
3367
37
3701
37
4049
38
4414
38
3.55
7.7
42
2259
39
2540
40
2871
41
3204
41
3558
42
3928
42
4317
42
4724
43
5150
43
4.06
10
55
2582
44
2903
44
3281
45
3662
45
4066
45
4489
46
4934
46
5399
47
5886
47
4.57
12
69
2905
48
3266
48
3691
49
4120
49
4574
50
5050
50
5551
50
6073
51
6621
51
5.08
15
86
3228
52
3629
52
4101
53
4577
53
5082
54
5611
54
6168
54
6748
55
7357
55
Air Measurement
1"
(25)
Data
Spec
78
HOSPITAL/CLEANROOM DIFFUSERS
STAINLESS STEEL
RETURN GRILLES AND
REGISTERS
LOUVERED FACE
FIXED 45 BLADE
DEFLECTION
1/2" (13) SPACING
1/4 TURN FASTENERS
Model:
67FB55
(Suffix 'O' adds stainless
steel opposed blade
damper)
Model 67FB55
Model 67FB55 Return Grilles and Registers have fixed horizontal blades (parallel to width/first specified dim.) spaced on 1/2"
(13) centers with 45 straight face deflection. The grille core is secured to the face of the outer frame with stainless steel 1/4 turn
fasteners allowing quick removal for cleaning or changing the filters.
The streamlined blades and open spacing maintain a minimum effective free area of 40%, which minimizes intake velocity,
reduces inlet pressure and provides quiet operation. Deflected blade grilles installed in a low or high side wall location are visionproof with the grille blade deflection facing away from the line of sight.
Stainless steel grilles and registers are well suited for applications involving corrosive environments, high humidity or frequent
cleaning with strong chemicals. Typical projects include hospitals, cleanrooms, laboratories, industrial and manufacturing facilities.
OPTIONS:
316 Stainless Steel construction.
AW Appliance White finish.
F2
WT
4 7/8" (121)
3 7/8" (95)
2 7/8" (70)
OPT.
O.B.D.
Model 67FB55
Home
Contents
OPTIONAL
1" OR 2"
(25 OR 51)
FILTER CLIPS
1 3/4"
1"
(44) (25)
2 1/4" (57)
3 1/4" (83)
Back
F1
FEATURES:
Dimensions
Data
Spec
79
HOSPITAL/CLEANROOM DIFFUSERS
67FB 55 - O - 24 x 12 - S - #3 - A - 316
MODEL
- 304 Stainless Steel
(Blades louvered)
ACCESSORIES
- Standard (default) None
67FB
BLADE DEFLECTION
- 45 Defl., 1/2" (13) Spacing
55
DAMPER (OBD)
- Stainless Steel (standard)
- No Damper
FASTENING
- Standard (default) Screw Holes A
WIDTH
FINISH
- #3 Satin Polished (default)
- Appliance White
- Special
inches (mm)
HEIGHT
inches (mm)
#3
AW
SP
Notes:
1. These grilles feature a subframe as standard for applications which may require frequent removal for cleaning.
You must specify filter clips for filter applications.
2. For Frame/Border Type S, duct size is listed + 1/4" (6).
3. Core fastening: Standard core is secured with four 1/4 turn slotted fasteners.
SUGGESTED SPECIFICATION:
Furnish and install Nailor Model 67FB55 Return Grilles of the size and type shown on the plans and air distribution
schedules. The grilles shall be constructed entirely from 304 stainless steel (316 optional), minimum 24 ga..
Streamlined shaped roll-formed blades shall be fixed on 1/2" (13) centers. The grille core shall be secured to the outer
frame with stainless steel 1/4 turn fasteners to allow for complete removal and access to the interior for cleaning.
(Optional) An opposed blade damper, adjustable from the face of the grille, shall be provided with all units. Dampers
shall be attached to the grille core and be completely removable.
All exposed surfaces shall have a #3 satin polished finish.
The manufacturer shall provide published performance data for the grille, which shall be tested in accordance with
ANSI/ASHRAE Standard 70 1991.
Back
Home
Contents
Dimensions
Data
Spec
80
HOSPITAL/CLEANROOM DIFFUSERS
Performance Data
Fixed Blade Return Grilles and Registers
Model Series: 67FB55
Imperial Units
Listed
Duct Size
(inches)
6x6
8x6
10 x 6
Alternate
Size
(inches)
8x4
10 x 4
10 x 5
12 x 4
12 x 5
16 x 4
Core
Area
(sq. ft.)
Ak
Factor
0.20
0.23
0.28
0.30
0.35
0.37
8x8
14 x 5
0.38
0.40
12 x 6
18 x 4
0.42
0.45
0.58
0.59
0.61
0.62
0.65
0.67
0.74
0.74
0.90
0.89
1.24
1.22
1.37
1.34
1.52
1.49
1.64
1.58
1.85
1.78
2.10
2.01
2.32
2.23
2.61
2.48
3.17
3.00
3.54
3.34
3.79
3.56
4.27
4.01
4.47
4.19
4.77
4.46
5.20
4.85
5.74
5.35
5.99
5.57
12 x 8
10 x 10
18 x 6
12 x 10
12 x 12
14 x 14
18 x 12
24 x 10
16 x 16
24 x 12
18 x 18
30 x 12
20 x 20
22 x 22
30 x 18
24 x 24
36 x 18
26 x 26
30 x 24
28 x 28
36 x 24
30 x 30
16 x 6
24 x 4
14 x 7
26 x 4
14 x 8
28 x 4
16 x 8
24 x 5
14 x 10
18 x 8
16 x 12
20 x 10
16 x 14
22 x 10
20 x 12
30 x 8
18 x 14
22 x 12
18 x 16
20 x 14
20 x 16
24 x 14
20 x 18
22 x 16
24 x 18
26 x 16
24 x 20
26 x 18
24 x 22
34 x 16
26 x 22
28 x 20
32 x 20
40 x 16
28 x 24
48 x 14
28 x 26
32 x 22
30 x 26
36 x 22
30 x 28
40 x 22
34 x 26
38 x 24
Back
30 x 4
20 x 6
24 x 6
38 x 4
24 x 8
34 x 6
28 x 8
38 x 6
30 x 8
30 x 10
36 x 8
28 x 12
32 x 10
26 x 14
36 x 10
30 x 14
36 x 12
30 x 16
36 x 14
40 x 14
32 x 18
36 x 16
46 x 14
36 x 20
40 x 18
40 x 20
44 x 20
48 x 20
Home
Contents
Core Velocity
VP
Neg. SP
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
100
.001
.005
20
28
35
38
42
58
61
65
74
90
124
137
152
164
185
210
232
261
317
354
379
427
447
477
520
574
599
200
.002
.018
40
56
70
76
84
116
122
130
148
180
248
274
304
328
370
420
464
522
634
708
758
854
894
954
1040
1148
1198
Dimensions
300
.006
.041
60
84
105
114
126
174
183
195
222
270
372
411
15
456
15
492
16
555
16
630
16
696
16
783
16
951
17
1062
17
1137
17
1281
18
1341
18
1431
19
1560
19
1722
19
1797
19
Data
400
.010
.073
80
112
140
152
168
15
232
16
244
16
260
17
296
17
360
18
496
18
548
20
608
20
656
21
740
21
840
21
928
22
1044
22
1268
23
1416
23
1516
23
1708
25
1788
25
1908
26
2080
26
2296
26
2396
26
500
.016
.114
100
16
140
17
175
18
190
19
210
20
290
21
305
21
325
22
370
22
450
23
620
23
685
25
760
25
820
26
925
26
1050
26
1160
27
1305
27
1585
28
1770
28
1895
28
2135
29
2235
30
2385
31
2600
31
2870
32
2995
32
Spec
600
.022
.164
120
21
168
22
210
23
228
24
252
25
348
26
366
26
390
27
444
27
540
28
744
28
822
30
912
30
984
31
1110
31
1260
32
1392
32
1566
33
1902
34
2124
34
2274
34
2562
36
2682
36
2862
37
3120
37
3444
38
3594
38
700
.031
.223
140
26
196
27
245
28
266
29
294
29
406
30
427
31
455
32
518
32
630
33
868
33
959
35
1064
35
1148
36
1295
36
1470
37
1624
37
1827
38
2219
38
2478
39
2653
39
2989
41
3129
41
3339
42
3640
42
4018
42
4193
43
800
.040
.292
160
30
224
31
280
32
304
33
336
34
464
35
488
36
520
36
592
37
720
38
992
38
1096
40
1216
41
1312
41
1480
41
1680
42
1856
42
2088
43
2536
43
2832
44
3032
44
3416
46
3576
46
3816
46
4160
47
4592
47
4792
47
900
.050
.369
180
34
252
35
315
36
342
37
378
38
522
39
549
39
585
40
666
41
810
41
1116
42
1233
43
1368
44
1476
44
1665
44
1890
45
2088
45
2349
46
2853
46
3186
47
3411
47
3843
49
4023
49
4293
50
4680
50
5166
51
5391
51
1000
.062
.456
200
38
280
39
350
40
380
41
420
42
580
43
610
43
650
43
740
44
900
44
1240
45
1370
46
1520
47
1640
47
1850
48
2100
48
2320
49
2610
49
3170
50
3540
51
3790
51
4270
53
4470
53
4770
54
5200
54
5740
55
5990
55
81
HOSPITAL/CLEANROOM DIFFUSERS
Performance Data
Fixed Blade Return Grilles and Registers
Model Series: 67FB55
Imperial Units
Listed
Duct Size
(inches)
Core
Area
(sq. ft.)
Ak
Factor
6.84
6.34
7.69
7.13
8.69
8.02
9.70
8.94
10.77
9.90
11.89
10.92
13.07
11.98
46 x 46
14.30
13.10
48 x 48
15.59
14.26
32 x 32
48 x 24
36 x 36
38 x 38
40 x 40
42 x 42
44 x 44
Alternate
Size
(inches)
36 x 30 46 x 22
38 x 28
34 x 34 38 x 30
36 x 32 48 x 28
38 x 34 46 x 28
42 x 30 48 x 26
42 x 34 48 x 30
44 x 34
42 x 36 48 x 32
46 x 34
44 x 40 48 x 36
46 x 38
46 x 42
Core Velocity
VP
Neg. SP
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
CFM
NC
100
.001
.005
684
769
869
970
1077
1189
1307
1430
15
1559
15
200
.002
.018
1368
15
1538
16
1738
17
1940
18
2154
18
2378
19
2614
19
2860
20
3118
20
300
.006
.041
2052
20
2307
21
2607
21
2910
22
3231
23
3567
24
3921
24
4290
25
4677
25
CFM
VP
Neg. SP NC
-
Back
Home
Contents
Dimensions
400
.010
.073
2736
27
3076
27
3476
28
3880
28
4308
29
4756
30
5228
30
5720
31
6236
31
500
.016
.114
3420
33
3845
33
4345
33
4850
34
5385
35
5945
36
6535
36
7150
37
7795
37
600
.022
.164
4104
39
4614
39
5214
40
5820
40
6462
41
7134
42
7842
42
8580
43
9354
43
700
.031
.223
4788
43
5383
44
6083
45
6790
45
7539
47
8323
47
9149
47
10010
48
10913
48
800
.040
.292
5472
48
6152
48
6952
49
7760
49
8616
50
9512
51
10456
51
11440
52
12472
52
900
.050
.369
6156
52
6921
52
7821
53
8730
53
9693
55
10701
55
11763
55
12870
56
14031
56
1000
.062
.456
6840
56
7690
56
8690
57
9700
57
10770
59
11890
59
13070
59
14300
60
15590
60
Air Measurement
1"
(25)
Data
Spec
82
HOSPITAL/CLEANROOM DIFFUSERS
Performance Data
Fixed Blade Return Grilles and Registers
Model Series: 67FB55
Metric Units
Listed
Duct Size
(mm)
Alternate
Size
(mm)
203 x 102
152 x 152
254 x 102
254 x 127
203 x 152
305 x 102
305 x 127
254 x 152
406 x 102
Core
Area
(sq. m)
Ak
Factor
.019
21
.026
28
.033
34
.035
37
.039
42
.054
55
.057
58
.060
62
.069
69
.084
83
.115
113
.127
125
.141
139
.152
147
.172
165
.195
187
.216
207
.242
231
.294
279
.329
310
.352
331
.397
373
.415
390
.443
415
.483
451
.533
497
.556
518
305 x 203
254 x 254
457 x 152
305 x 254
305 x 305
356 x 356
457 x 305
610 x 254
406 x 406
610 x 305
457 x 457
762 x 305
508 x 508
559 x 559
762 x 457
610 x 610
914 x 457
660 x 660
762 x 610
711 x 711
914 x 610
762 x 762
406 x 152
610 x 102
356 x 178
660 x 102
356 x 203 762 x 102
711 x 102
406 x 203 508 x 152
610 x 127
356 x 254 610 x 152
457 x 203 965 x 102
406 x 305 610 x 203
508 x 254 864 x 152
406 x 356 711 x 203
559 x 254 965 x 152
508 x 305
762 x 203
457 x 356 762 x 203
559 x 305
457 x 406 762 x 254
508 x 356 914 x 203
508 x 406 711 x 305
610 x 356 813 x 254
508 x 457 660 x 356
559 x 406 914 x 254
610 x 457 762 x 356
660 x 406 914 x 305
610 x 508 762 x 406
660 x 457 914 x 356
610 x 559 1016 x 356
863 x 406
660 x 559 813 x 457
711 x 508 914 x 406
813 x 508 1168 x 356
1016 x 406
711 x 610
1219 x 356
711 x 660 914 x 508
813 x 559 1016 x 457
762 x 660 1016 x 508
914 x 559
762 x 711 1118 x 508
1016 x 559
864 x 660 1219 x 508
965 x 610
Back
Home
Contents
Core Velocity
VP
Neg. SP
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
L/S
NC
0.51
0.2
0.7
9
13
17
18
20
27
29
31
35
42
59
65
72
77
87
99
109
123
150
167
179
202
211
225
245
271
283
Dimensions
1.01
0.5
3.5
19
26
33
36
40
55
58
61
70
85
117
129
143
155
175
198
219
246
299
334
358
403
422
450
491
542
565
1.52
1.5
7.7
28
40
50
54
59
82
86
92
105
127
176
194
15
215
15
232
16
262
16
297
16
328
16
369
16
449
17
501
17
537
17
605
18
633
18
675
19
736
19
813
19
848
19
Data
2.03
2.5
14
38
53
66
72
79
15
109
16
115
16
123
17
140
17
170
18
234
18
259
20
287
20
310
21
349
21
396
21
438
22
493
22
598
23
668
23
715
23
806
25
844
25
900
26
982
26
1083
26
1131
26
2.54
4.0
21
47
16
66
17
83
18
90
19
99
20
137
21
144
21
153
22
175
22
212
23
293
23
323
25
359
25
387
26
437
26
495
26
547
27
616
27
748
28
835
28
894
28
1008
29
1055
30
1125
31
1227
31
1354
32
1413
32
Spec
3.05
5.5
31
57
21
79
22
99
23
108
24
119
25
164
26
173
26
184
27
210
27
255
28
351
28
388
30
430
30
464
31
524
31
595
32
657
32
739
33
898
34
1002
34
1073
34
1209
36
1266
36
1351
37
1472
37
1625
38
1696
38
3.55
7.7
42
66
26
92
27
116
28
126
29
139
29
192
30
202
31
215
32
244
32
297
33
410
33
453
35
502
35
542
36
611
36
694
37
766
37
862
38
1047
38
1169
39
1252
39
1411
41
1477
41
1576
42
1718
42
1896
42
1979
43
4.06
10
55
76
30
106
31
132
32
143
33
159
34
219
35
230
36
245
36
279
37
340
38
468
38
517
40
574
41
619
41
698
41
793
42
876
42
985
43
1197
43
1336
44
1431
44
1612
46
1688
46
1801
46
1963
47
2167
47
2261
47
4.57
12
69
85
34
119
35
149
36
161
37
178
38
246
39
259
39
276
40
314
41
382
41
527
42
582
43
646
44
697
44
786
44
892
45
985
45
1108
46
1346
46
1503
47
1610
47
1814
49
1898
49
2026
50
2208
50
2438
51
2544
51
5.08
15
86
94
38
132
39
165
40
179
41
198
42
274
43
288
43
307
43
349
44
425
44
585
45
647
46
717
47
774
47
873
48
991
48
1095
49
1232
49
1496
50
1671
51
1789
51
2015
53
2109
53
2251
54
2454
54
2709
55
2827
55
83
HOSPITAL/CLEANROOM DIFFUSERS
Performance Data
Fixed Blade Return Grilles and Registers
Model Series: 67FB55
Metric Units
Listed
Duct Size
(mm)
813 x 813
1219 x 610
914 x 914
965 x 965
1016 x 1016
1067 x 1067
1118 x 1118
1168 x 1168
1219 x 1219
Alternate
Core
Ak
Core Velocity
Size
Area Factor VP
(mm)
(sq. m)
Neg. SP
914 x 762 1168 x 559
L/S
.635
589
965 x 711
NC
864 x 864 965 x 762
L/S
.714
663
914 x 813 1219 x 711
NC
965 x 864 1168 x 711
L/S
.807
746
1067 x 762 1219 x 660
NC
1067 x 864 1219 x 762
L/S
.901
831
1118 x 864
NC
1067 x 914 1219 x 813
L/S
1.00
920
1168 x 864
NC
1118 x 1016 1219 x 914
L/S
1.10
1015
1168 x 965
NC
1168 x 1067
L/S
1.21
1114
NC
L/S
1.33
1218
NC
L/S
1.45
1326
NC
0.51
0.2
0.7
323
363
410
458
508
561
617
675
15
736
15
1.01
0.5
3.5
646
15
726
16
820
17
915
18
1016
18
1122
19
1234
19
1350
20
1471
20
1.52
1.5
7.7
968
20
1089
21
1230
21
1373
22
1525
23
1683
24
1850
24
2024
25
2207
25
L/S
VP
Neg. SP NC
-
Back
Home
Contents
Dimensions
2.03
2.5
14
1291
27
1452
27
1640
28
1831
28
2033
29
2244
30
2467
30
2699
31
2943
31
2.54
4.0
21
1614
33
1814
33
2050
33
2289
34
2541
35
2805
36
3084
36
3374
37
3678
37
3.05
5.5
31
1937
39
2177
39
2460
40
2746
40
3049
41
3367
42
3701
42
4049
43
4414
43
3.55
7.7
42
2259
43
2540
44
2871
45
3204
45
3558
47
3928
47
4317
47
4724
48
5150
48
4.06
10
55
2582
48
2903
48
3281
49
3662
49
4066
50
4489
51
4934
51
5399
52
5886
52
4.57
12
69
2905
52
3266
52
3691
53
4120
53
4574
55
5050
55
5551
55
6073
56
6621
56
5.08
15
86
3228
56
3629
56
4101
57
4577
57
5082
59
5611
59
6168
59
6748
60
7357
60
Air Measurement
1"
(25)
Data
Spec
84
HOSPITAL/CLEANROOM DIFFUSERS
Notes:
Back
Home
Contents
Dimensions
Data
Spec
85
HOSPITAL /CLEANROOM
DIFFUSERS ENGINEERING
Back
Home
Contents
Dimensions
Data
Spec
86
HOSPITAL/CLEANROOM DIFFUSERS
OPERATING ROOM
AIR DISTRIBUTION:
ENGINEERING GUIDELINES
INTRODUCTION
In the United States there are approximately 46.5 million
surgical procedures performed each year (1996 Data
published November 1998 by CDC/National Center for
Health Statistics). An analysis of 1.16 million surgical
procedures reported 29.4 thousand (2.54%) Surgical Site
Infections (SSI's) (Data Summary from January 1992
June 2001 CDC/National Nosocomial Infections
Surveillance System Report published August 2001).
While 2.54% may appear to be a relatively small and
acceptable incidence of surgical site infection we must
consider a broader scope and allow some assumptions
to fully understand its true implications and effect on our
lives and those around us. When we look at the total
number of procedures itself we must realize that in 1996
the United States population was approximately 264
million people. Therefore, there is an overall average of
17.6% percent of Americans (1 in every 5.7 people) that
have some kind of surgical procedure performed each
year. If we further expand this and assume the average
lifespan to be 75 years we see that the average person
will have 13.2 surgical procedures performed in their
lifetime. With a 2.54% average incidence of infection
each time, this means that over a lifetime at current rates
the average American actually has a 28.8% chance (1 in
every 3.5 people) of getting a surgical site infection.
A 1992 analysis showed that each SSI resulted in an
additional 7.3 postoperative hospital days adding $3,152
in extra charges. With almost 1.2 million incidences of
SSI each year that adds up to a truly staggering figure of
over 3.7 billion dollars each year. For the case of a typical
operating room we find that the average time for a
procedure is about 2.1 hours. As most operating rooms
are available for eight hours a day, this results in
approximately 3 operations per day per room. This works
out to 750 procedures per year resulting in an average of
19 cases of SSI per year with an extra annual cost of
$60,000 per operating room.
When we examine the nature of these surgical site
infections we find that approximately two thirds are
confined to the incision, and one third involved organs or
spaces accessed during the operation (deep SSI's). Data
is not available on the total number of deaths each year
caused by SSI, however when patients with SSI died,
77% of the deaths were reported to be related to the
infection and the majority (93%) were serious infections
involving organs or spaces accessed during the
operation (deep SSI's) (the mortality rate is currently
estimated to be between 1 and 3%, or 12,000 36,000
people per year).
Despite continuing advances in medical science surgical
site infections remain a substantial cause of morbidity
Back
Home
Contents
Dimensions
Data
Spec
87
HOSPITAL/CLEANROOM DIFFUSERS
SYSTEM SELECTION
Selecting the proper air distribution system for the
modern operating room can be a very confusing process.
There are a wide variety of sources of conflicting
information, studies and papers on the subject. Over the
past 50 years there have been many attempts to justify
particular systems and many manufacturers have made
claims as to the suitability and superiority of their
particular system with little or no consensus on the
subject of whether a specialty system should exist at all.
While some authorities believe clean air systems are not
necessary, recent testing and various studies have
shown a reduction in infection rates and, as far as we are
aware, no studies have shown, and common sense
would agree, that supplying clean or ultra clean air in a
directed fashion within the operating room is in any way
detrimental to the patient. The modern hospital
environment is rapidly changing; with the increased
numbers of elderly and/or immunocompromised patients
and new treatment resistant diseases, the prevention of
infection is becoming more important than ever. When
one considers the financial costs associated with
surgical site infections due to increased hospital stays,
treatments, and potential litigation, not to mention
increased mortality rates, it seems obvious that if the
system prevents even one infection over its lifetime it is
well worth the minor cost associated with it (especially to
that one patient). It is also important to note that a
standard Steri-System module generally costs much less
than the operating table itself, while providing much
greater benefit to the patient.
The major source of microbiological particles in the
operating room is from the surgical staff and is
proportional to the number of people moving about in the
room. Therefore the goal of any system has to be the
isolation of the patient from the microbiological particles
produced by the surgical team and the support staff in
the operating room.
TYPES OF SYSTEMS
There are three basic types of specialty systems:
Back
Home
Contents
Dimensions
Data
Spec
88
HOSPITAL/CLEANROOM DIFFUSERS
WITH
AIR CURTAIN
FIGURE 1:
Complete Laminar Flow Ceiling System. Excellent protection of the patient from all sources of contaminants. Requires
very high air volumes.
Back
Home
Contents
Dimensions
Data
Spec
89
HOSPITAL/CLEANROOM DIFFUSERS
FIGURE 2:
Large Area Laminar Flow Ceiling System. Very good protection of the patient from all sources of contaminants.
Requires high air volumes.
FIGURE 3:
Small Area Laminar Flow System. Marginal protection of the patient from contaminants. Physical movement of
personnel can disrupt flow field. Requires low to moderate air volumes.
Back
Home
Contents
Dimensions
Data
Spec
90
HOSPITAL/CLEANROOM DIFFUSERS
FIGURE 4:
Laminar Flow System with Ceiling Hung Deflection Walls. Good protection of the patient from all sources of
contaminants. Requires moderate air volumes.
FIGURE 5:
Laminar Flow System with Perimeter Air Curtain. Good protection of the patient from all sources of contaminants.
Requires low to moderate air volumes.
Back
Home
Contents
Dimensions
Data
Spec
91
HOSPITAL/CLEANROOM DIFFUSERS
FIGURE 6:
Horizontal Laminar Flow System. Marginal protection of the patient from all sources of contaminants. Requires
moderate to high air volumes.
Back
Home
Contents
Dimensions
Data
Spec
92
HOSPITAL/CLEANROOM DIFFUSERS
Module
Size
8x4
8x6
8x8
10 x 6
10 x 8
10 x 10
12 x 6
12 x 8
12 x 10
12 x 12
14 x 8
14 x 10
14 x 12
14 x 14
Total System
CFM Range
Low
945
1070
1220
1220
1370
1520
1370
1520
1670
1820
1670
1820
1970
2095
Med
1320
1500
1710
1710
1920
2130
1920
2130
2340
2550
2340
2550
2760
2930
High
1700
1925
2195
2195
2470
2735
2470
2735
3005
3275
3005
3275
3545
3765
Low
59.1
44.4
38.0
40.5
34.1
30.3
37.9
31.6
27.8
25.2
29.7
25.9
23.4
21.4
Med
82.5
62.5
53.4
57.0
48.0
42.6
53.3
44.4
39.0
35.4
41.8
36.4
32.9
29.8
High
105.9
80.0
68.4
73.0
61.9
54.6
68.8
56.9
50.0
45.4
53.6
46.7
42.1
38.4
APPLICATION GUIDELINES
The operating room environment is one of the most
critical areas requiring air distribution. Any type of system
has to include in its design the ability to isolate
contaminates and reduce the risk of infection to the
patient. To accomplish this effectively a large volume of
clean air must be supplied into the room at relatively low
velocities and acceptable noise levels. The high air change
rate dilutes the microbiological contaminants present in the
room or within the clean zone. A low air velocity is required
to allow the heavier particles to settle and be exhausted
out as well as reduce the impingement of particles
generated by the surgical team onto the patient.
FIGURE 7:
Back
Home
Contents
Dimensions
Data
Spec
93
HOSPITAL/CLEANROOM DIFFUSERS
8 10
9 10
Back
Home
Contents
Dimensions
SELECTION
OF
Data
Spec
94
HOSPITAL/CLEANROOM DIFFUSERS
We must then confirm that this airflow will fulfill the other
requirements of the room such as cooling load and
humidity requirements as well as maintaining the
pressure relationships with the adjoining areas. Some
systems must be capable of quickly reducing or
increasing the room temperature and humidity during or
between procedures and/or maintaining a lowered
design set point temperature of 60 65F (15 18C)
during procedures. Also, best air distribution and comfort
conditions are generally obtained when the supply air
temperature differential during surgery is small and
relatively constant. When the total room airflow is
determined we can choose our Steri-System module
size. From the chart on page 70 the total system airflow
ranges and noise levels are shown. The system should
be selected within the ranges shown on the chart with
consideration as to final module size and its ability to
accommodate the personnel and equipment as
necessary. The standard systems shown have been
designed to simplify the selection and layout process
while providing maximum protection to the patient within
the airflow ranges shown. The interior and perimeter
pressure and flow relationships are maintained with 1/3
of the airflow being supplied through the laminar flow
center panels and the remaining 2/3 through the
perimeter curtain diffusers. Inlet sizes and air volumes
per inlet have been designed to minimize sound and
Source
Room
Types
ASHRAE
1999 Handbook
HVAC Applications
Operating Room
Delivery Room
American Institute
of Architects
2001 Edition
Guidelines for
Design & Construction
of Hospital & Health
Care Facilities
Canadian Standards
Assoc. CSA Standard
Z317.201
September, 2001
Minimum Air
Minimum
Changes/Hour
Outside Air
ACH
ACH
25
5
(Recirculating Air System)
or
15
15
(All Outdoor Air System)
Operating/Surgical
Cystoscopic Rooms
Delivery Room
Trauma Room
Procedure Room
Bronchoscopy,
Triage, ER or
Radiology Waiting Rooms
Endoscopy
Operating Rooms
Endoscopy,
Bronchoscopy,
Cystoscopy, PACU,
Surgical Day Care,
Caesarean Delivery
15
Minimum
Filtration
Efficiency
99.97% for Orthopedic,
Bone Marrow and
Organ Transplant.
90% for General Procedure
and Delivery Rooms.
3
90%
12
20
99.97%
TABLE 3:
This table summarizes some of the current recommendations for operating room ventilation rates. Consult the
actual documents for specific requirements and exceptions.
Back
Home
Contents
Dimensions
Data
Spec
95
HOSPITAL/CLEANROOM DIFFUSERS
SELECTION
OF
SELECTION EXAMPLE
Design Criteria: General Procedure Operating Room
Room Size: 20 ft wide x 25 ft long x 10 ft ceiling height
= 5000 ft 3 Room Volume
Minimum: 8 ft x 8 ft Clean Zone Required
Supply Air Temperature: 55F
Room Temperature Set Point Range: 62 80F
Airflow: Minimum 25 ACH (recirculating system)
Positive room pressure
Sound Level: 25 35 NC
Calculate required room airflow rate:
Back
Home
Contents
Dimensions
Data
Spec
96
HOSPITAL/CLEANROOM DIFFUSERS
FILTER SELECTION
AND
APPLICATIONS
Back
Home
Contents
Dimensions
FIGURE 8:
Data
Spec
97
HOSPITAL/CLEANROOM DIFFUSERS
Maximum Airflow
Ceiling Module
Size
(ft.2)
(m 2)
(cfm)
(l/s)
(cfm)
(l/s)
1.93
2.50
1.96
3.37
4.77
6.17
0.179
0.232
0.182
0.313
0.443
0.573
193
250
196
337
477
617
91
118
92
159
225
291
290
375
294
506
716
926
137
177
139
239
338
437
Maximum Airflow
Ceiling Module
Size
(ft. )
(m )
(cfm)
(l/s)
(cfm)
(l/s)
1.89
2.45
1.87
3.22
4.56
5.91
0.176
0.228
0.174
0.299
0.424
0.549
189
245
187
322
456
591
89
116
88
152
215
279
284
368
281
483
684
887
134
173
132
228
323
418
TABLE 4:
This table gives net media face area of the standard HEPA and ULPA Filters. The recommended maximum airflow
shown is based on 100 ft/min (0.51 m/s) velocity and the maximum airflow is based on 150 ft/min (0.76 m/s) velocity.
DISINFECTION, STERILIZATION
AND MATERIALS
The subject of disinfection and sterilization in healthcare
facilities (like most healthcare related issues) is
extremely controversial. Most authorities do not agree on
the type, frequency or effectiveness of the various
methods and chemicals. The result is that many hospitals
use many different methods and new research and
product developments continue to influence actual
practices. The evolving trend seems to be towards
stricter controls and higher levels of disinfection. Newer
construction guidelines focus on surfaces that are
resistant to harsh cleaners, have no cracks or crevices
and are easier to clean such as monolithic ceilings in
operating rooms, etc..
The sanitation requirements in the operating room are
the most severe as they are aimed at total asepsis. This
requires the use of strong cleaners, usually highly
alkaline soaps reinforced with synthetic detergents. In
addition to meeting the regular standards of cleanliness,
the general cleaning is supplemented with sanitizers,
disinfectants and sterilants. These chemical formulations
are functional against different levels and types of
contamination. Sanitizers reduce but not necessarily
eliminate microorganisms. These cleaners contain lye
(caustic soda, sodium hydroxide) and alkaline
hypochlorites (equivalent to bleach). Often these and
other cleaning and sanitizing agents will have the alkaline
salts aided by 'quats' (quaternary ammonium
derivatives). Disinfectants go one step further than
sanitizers in that they eliminate all pathogenic
Back
Home
Contents
Dimensions
Data
Spec
98
HOSPITAL/CLEANROOM DIFFUSERS
Back
Home
Contents
Dimensions
SYSTEM TESTING
Testing any operating room system is a very
controversial process. There are no common standards
to which to test to and many factors can influence the
results. There are, however, some very important tests
that can be performed that will give the engineers and
infection control personnel valuable information and help
in diagnosing potential problems.
Most tests in operating rooms are typically looking for cfu
concentration (colony forming units) generally expressed
as cfu/ft 3 (cfu/m 3). These tests generally do not determine
the specific type of microbiological contaminants present.
In some instances this will be very important and should
be performed especially as part of an epidemiological
investigation. In cleanrooms, generally all particles of a
specific size are counted including the microbiological
ones. To understand the value of these test results we
must first look at the nature of the contaminants involved
and their likely sources. To fully consider the myriad
assortment and quantity of different viruses, bacteria and
fungi as well as their various properties is truly a daunting
endeavor for any HVAC engineer and well outside the
scope of this text. We can however make a few
assumptions, that will in most cases be correct, and that
will provide valuable information.
Data
Spec
99
HOSPITAL/CLEANROOM DIFFUSERS
Back
Home
Contents
Dimensions
Data
Spec
100
HOSPITAL/CLEANROOM DIFFUSERS
SUGGESTED SPECIFICATION
Furnish and install Nailor STERI-SYSTEM Model
92STSYS Hospital Operating Room Air Systems of
the size and type shown on the plans and air distribution
schedules. The system shall be specially designed to
reduce airborne contaminants, and thus, the risk of
patient infection during surgery. The system shall be
composed of two main components Model 92LFD-SS
Laminar Flow Diffusers and Model 92LS-SS Linear Slot
Diffusers constructed as follows:
The Laminar Flow Diffusers shall be constructed entirely
from 304 stainless steel (316 optional), minimum 24 ga..
The perforated face of the diffuser shall have 13% free
area with 3/32" (2.4) dia. holes on 1/4" (6) staggered
centers. The face shall incorporate a second pressure
plate as an integral assembly to ensure true laminar
airflow. The face shall be attached with 1/4 turn fasteners
to allow for complete removal and access to the interior
for cleaning. All diffusers are to include safety cables to
prevent accidental dropping of the removable face. A disk
type damper, adjustable from the face of the diffuser,
shall be provided with all units. Integral earthquake
hanger tabs shall be included with all units.
The Linear Slot Diffusers shall be constructed entirely
from 304 stainless steel (316 optional), minimum 24 ga..
The diffuser shall incorporate a non-adjustable single slot
designed to create a vertical air curtain angled outwards
5 15 degrees. The diffuser shall incorporate a pressure
plate behind the slot to ensure uniform slot velocity. The
pressure plate shall be 13% free area with 3/32" (2.4) dia.
holes on 1/4" (6) staggered centers. The slot and
pressure plate shall be attached with 1/4 turn fasteners to
allow for complete removal and access to the interior for
cleaning. The plenum shall incorporate radiused corners
lengthwise to facilitate cleaning. Flanged plenum inlets
are to be maximum 5" (127) in height to allow duct
clearance over standard light fixtures. Plenums over 7 ft
(2134) in length shall be supplied in multiple sections with
flange connections and stainless steel fasteners for field
assembly. All diffusers are to include safety cables to
prevent accidental dropping of the removable face.
Integral earthquake hanger tabs shall be included with all
units.
(Optional) An opposed blade damper, adjustable from the
face of the diffuser, shall be provided on all perimeter
inlets. Dampers shall be held in place with wing nut
fasteners and be removable from the face of the diffuser.
All exposed surfaces shall have a #3 satin polished
finish.
Back
Home
Contents
Dimensions
Data
Spec
HOSPITAL/CLEANROOM DIFFUSERS
1) ASHRAE HANDBOOK
1999 HVAC APPLICATIONS
CHAPTER 7 HEALTH CARE FACILITIES
COMMENTS
Excellent source for general design information.
HIGHLIGHTS
Laminar airflow has shown promise in rooms used for
treatment of patients that are highly susceptible to
infection.
The unidirectional laminar airflow pattern is commonly
attained at a velocity of 0.35 to 0.55 m/s (70 to 110
ft/min).
Surgery and critical care areas require careful design to
reduce to a minimum the concentrations of airborne
organisms.
The greatest amount of bacteria found in the operating
room comes from the surgical team and is a result of their
activities during surgery.
Studies and observations indicate that that delivery of air
from the ceiling, with a downward movement to several
exhaust outlets located along the walls is probably the
most effective air movement pattern for maintaining the
concentration of contamination at an acceptable level.
System should maintain positive pressurization at all
times, even under periods of reduced air volumes, to
maintain sterile conditions.
Home
Contents
AVAILABILITY
Copies of this document can be ordered from the
ASHRAE Bookstore online at www.ashrae.org
COMMENTS
SELECTED RECOMMENDATIONS
Back
Dimensions
HIGHLIGHTS
Continual health care facility upgrade through renovation
and new construction of hospital facilities can create
conditions that are hazardous to patients. Design and
planning for such projects shall require consultation with
infection control professionals and safety personnel, with
documentation obtained to verify consultation. Early
involvement of these professionals is required for an
"Infection Control Risk Assessment" (ICRA).
Data
Spec
102
HOSPITAL/CLEANROOM DIFFUSERS
SELECTED RECOMMENDATIONS
Airborne infection isolation rooms and protective
environment rooms shall have a device to monitor either
pressure or differential airflow and shall activate a local
alarm in the event the desired status is no longer present.
Protective environment rooms shall have a positive
pressure with respect to adjoining spaces with all supply
air passing through HEPA filters.
Psychiatric patient occupied areas shall have all air
grilles and diffusers of a type that prohibits the insertion
of foreign objects and all exposed fasteners shall be
tamper-resistant.
General operating rooms shall have minimum clear area
of 400 square feet (37.16 square meters).
Operating rooms for cardiovascular, orthopedic,
neurological and other special procedures that require
additional personnel and/or large equipment shall have a
minimum clear area of 600 square feet (55.74 square
meters).
Operating rooms for surgical cystoscopic and other endourologic procedures shall have a minimum clear area of
350 square feet (32.52 square meters).
Outpatient operating rooms have different (smaller)
dimensions and classifications. Refer to guidelines for
more information.
Back
Home
Contents
Dimensions
OPERATING/SURGICAL CYSTOSCOPIC
DELIVERY ROOMS:
ROOMS AND
AVAILABILITY
Copies of this document can be ordered from the
American Institute of Architects Bookstore online at
www.aia.org
Data
Spec
HOSPITAL/CLEANROOM DIFFUSERS
COMMENTS
Probably the most comprehensive source available for
medical information and causes of infections in operating
rooms. HVAC information is very current with research
findings.
HIGHLIGHTS
Currently in the United States alone, an estimated 27
million surgical procedures are performed each year.
The CDCs National Nosocomial Infections Surveillance
(NNIS) system over a ten-year period (1986 1996)
reported 15,523 surgical site infections (SSIs) following
593,344 operations (2.6 %).
Of these SSIs approximately two thirds were confined to
the wound or the incision and the remaining one third
were considered deep SSIs involving organs or spaces
accessed during the operation.
A 1992 analysis showed that each SSI resulted in an
additional 7.3 postoperative hospital days adding $3,152
in extra charges. Deep SSIs are associated with even
greater increases in hospital stays and costs.
When patients with SSIs died 77 % of the deaths were
reported to be related to the infection and the majority
(93 %) were serious infections involving deep SSIs.
SSIs remain a substantial cause of morbidity and
mortality among hospitalized patients due to the
emergence of antimicrobial-resistant pathogens,
increased number of patients that are elderly and/or have
a variety of chronic, debilitating or immunocompromising
underlying diseases. Also increased numbers of organ
transplant and prosthetic implant operations.
Operating room air may contain microbial-laden particles
and has been shown as a transmission route of infection
to the patient. The microbial level in the room air is
proportional to the number of people moving about in the
room.
All ventilation or air conditioning systems in hospitals,
including those in operating rooms, should have two filter
beds in series, with efficiency of the first filter bed being
> = 30 % and that of the second bed > = 90 %.
Back
Home
Contents
Dimensions
SELECTED RECOMMENDATIONS
1) Maintain positive-pressure ventilation in the
operating room with respect to corridors and
adjacent areas. Category IB
2) Maintain at least 15 air changes per hour, of which
at least 3 (20 %) should be fresh air. Category IB
3) Filter all air, recirculated and fresh, through the
appropriate filter beds per the American Institute
of Architects recommendations. (see above)
Category IB
4) Introduce all air at ceiling, and exhaust near the
floor. Category IB
5) Do not use UV radiation in the operating room to
prevent SSI. Category IB
6) Keep operating room doors closed except as
needed for passage of equipment, personnel and
the patient. Category IB
7) Consider
performing
orthopedic
implant
operations in operating rooms supplied with
ultraclean air. Category II
8) Limit the number of personnel entering the
operating room to necessary personnel. Category II
9) No recommendation on disinfecting environmental
surfaces or equipment used in the operating room
between operations or in the absence of visible
soiling. Unresolved issue
10) Do not perform routine environmental sampling of
the operating room. Perform microbiologic
sampling of operating room environmental
surfaces or air only as part of an epidemiological
investigation. Category IB
Data
Spec
104
HOSPITAL/CLEANROOM DIFFUSERS
RANKINGS:
Category IA Strongly recommended for implementation
and supported by well-designed experimental, clinical, or
epidemiological studies.
Category IB Strongly recommended for implementation
and supported by some experimental, clinical, or
epidemiological studies and strong theoretical rationale.
Category II Suggested for implementation and
supported by suggestive clinical or epidemiological
studies and strong theoretical rationale.
No recommendation; unresolved issue Practices for
which insufficient evidence or no consensus regarding
efficacy exists.
AVAILABILITY
Copies of this document can be downloaded free of charge
from the Centers for Disease Control website www.cdc.gov
COMMENTS
This draft document is still under review, however it
contains a great deal of very current and useful
information and recommendations. It has extensive
information on a variety of topics including protective
environments, isolation areas, operating rooms,
construction and renovation, HVAC systems, water
systems, cooling towers, evaporative condensers, water
treatment etc.. It is an excellent source of various
engineering recommendations and references for
construction and renovation of healthcare facilities.
HIGHLIGHTS
Approximately 10 % of healthy carriers will disseminate
Staphylococcus aureus into the air (the most common
pathogen associated with surgical site infection).
Outbreaks of surgical site infections have been traced to
Back
Home
Contents
Dimensions
SELECTED RECOMMENDATIONS
Air-Handling Systems in Healthcare Facilities
1) In the absence of locally recommended standards,
use ANSI/ASHRAE Standard 62, Ventilation for
Acceptable Indoor Air Quality, as a ventilation
standard for healthcare facilities. Category 1C
2) Ensure that HVAC filters are properly installed and
maintained to prevent air leakages and dust
overloads. Category 1C
3) Monitor
areas
with
special
ventilation
requirements (e.g., operating rooms, protective
environments, isolation rooms etc) for ACH and
pressure differentials. Document pressure
differentials. Category 1B
4) Engineer humidity controls into the HVAC system
and monitor these to ensure proper moisture
removal. Category 1C
a. Locate duct humidifiers upstream of the final
filters. Category 1C
b. Incorporate a water-removal mechanism into
the system. Category 1C
c. Locate all duct takeoffs sufficiently downstream
of the humidifier so that moisture is completely
absorbed. Category 1C
Data
Spec
HOSPITAL/CLEANROOM DIFFUSERS
5)
6)
7)
8)
9)
10)
RANKINGS:
Category IA Strongly recommended for implementation
and strongly supported by well-designed experimental,
clinical, or epidemiological studies.
Category IB Strongly recommended for implementation
and supported by some experimental, clinical, or
epidemiological studies and a strong theoretical
rationale.
Category IC Required by state or federal regulations,
rules, or standards.
Category II Suggested for implementation and
supported by suggestive clinical or epidemiological
Back
Home
Contents
Dimensions
AVAILABILITY
Copies of this document can be downloaded free of
charge from the Centers for Disease Control website at
the following address.
www.cdc.gov/ncidod/hip/enviro/env_guide_draft.pdf
COMMENTS
Very informative source for detailed requirements in
hospital HVAC systems. Specifically intended for VA
hospitals but very useful for other projects.
HIGHLIGHTS
Operating room design conditions
Summer 19C (68F) Db 55% RH
Winter 23C (75F) Db 50% RH
All thermostats adjustable from 15C (60F) to 29C (85F)
Operating Rooms 15 ACH (occupied) 8 ACH
(unoccupied)
100 % outdoor air supply to operating rooms
Operating rooms design noise criteria NC 40
Constant volume terminal reheat system (2 position) for
operating rooms.
Filter efficiencies
operating rooms 30% pre-filters, 95% after-filters
orthopedic surgery 30 % pre-filters, HEPA
(99.97 %) after-filters
Duct lining
Air terminal units in supply air duct for operating
rooms shall be unlined
Note: Air terminal units with factory applied fiberglass
liner, coated to prevent erosion and no exposed edges, is
permitted in terminal units located down stream of afterfilters in other areas.
Each operating room shall have individual temperature
and humidity control.
Exhaust duct shall be equipped with corresponding 2
position tracking airflow to maintain pressure relationship
during occupied and unoccupied times.
Air Distribution in Surgery Suite supply air duct on the
down stream side of the after-filters shall be stainless
steel with air tight access panels at each elbow and at 6
Data
Spec
106
HOSPITAL/CLEANROOM DIFFUSERS
AVAILABILITY
Copies of this document can be downloaded free of
charge from the department of Veterans Affairs website
at www.va.gov/facmgt/standard/
COMMENTS
Very detailed standard on testing cleanrooms and
procedures and equipment used. Has little or nothing
relevant to operating room design, classification, or
evaluation of the effectiveness of the air system in
controlling airborne microbiological contaminants.
Commonly cited by manufacturers in their testing and
evaluation of operating room systems.
HIGHLIGHTS
This document establishes standard and alternate
classes of air cleanliness for cleanrooms and clean
zones based on specified concentrations of airborne
particles.
This document is not intended to characterize the physical,
chemical, radiological, or viable nature of airborne
particles. No universal relationship has been established
between the concentration of airborne particles and the
concentration of viable airborne particles.
The following table defines the various airborne
particulate cleanliness classes. The limits shown are the
number of particles per unit volume equal to or larger
than the sizes shown.
AVAILABILITY
The U.S. General Services Administration (GSA) has
released, on November 29, 2001, a notice of cancellation
for this standard. It is now superceded by ISO 14644-1
Part 1: Classification of Air Cleanliness; and ISO 14644-2
Part 2: Specifications For Testing and Monitoring to
Prove Continued Compliance with ISO 14664-1.
Class Name**
SI
M1
M 1.5
M2
M 2.5
M3
M 3.5
M4
M 4.5
M5
M 5.5
M6
M 6.5
M7
English***
1
10
100
1000
10000
100000
0.1 m
Volume Units
(m 3)
(ft.3)
350
9.91
1240
35.0
3500
99.1
12400
350
35000
991
0.2 m
Volume Units
(m 3)
(ft.3)
75.7
2.14
265
7.50
757
21.4
2650
75.0
7570
214
26500
750
75700
2140
Class Limits
0.3 m
Volume Units
(m 3)
(ft.3)
30.9
0.875
106
3.00
309
8.75
1060
30.0
3090
87.5
10600
300
30900
875
0.5 m
Volume Units
(m 3)
(ft.3)
10.0
0.283
35.3
1.00
100
2.83
353
10.0
1000
28.3
3530
100
10000
283
35300
1000
100000
2830
353000 10000
1000000 28300
3530000 100000
10000000 283000
5 m
Volume Units
(m 3)
(ft.3)
247
7.00
618
17.5
2470
70.0
6180
175
24700
700
61800
1750
Airborne particulate cleanliness classes class limits are given for each class name. The limits designate specific
concentrations (particles per unit volume) of airborne particles with sizes equal to and larger than the particle size
shown.
Back
Home
Contents
Dimensions
Data
Spec
HOSPITAL/CLEANROOM DIFFUSERS
8) INTERNATIONAL STANDARD
ISO 14644-1
COMMENTS
COMMENTS
This standard is similar to the now cancelled FED-STD209E which it replaces. This part of ISO 14644 covers the
classification of air cleanliness in cleanrooms and
associated controlled environments exclusively in terms
of concentration of airborne particles.
HIGHLIGHTS
The standard provides various definitions related to
cleanrooms such as airborne particles, U and M descriptors,
occupancy states and classifications. It defines the proper
designation of airborne particulate cleanliness as well as a
reference test method for compliance, test report criteria and
statistical treatment of particle concentration data.
AVAILABILITY
Copies of this standard as well as other standards and
publications relating to cleanrooms can be purchased
from the Institute of Environmental Sciences and
Technology (IEST). Visit their website and online
publication store at www.iest.org
9) DEFINITION OF SURGICAL
MICROBIOLOGIC CLEAN AIR
COMMITTEE ON OPERATING ROOM
ENVIRONMENT, AMERICAN COLLEGE
OF SURGEONS
REPRINTED FROM THE AMERICAN COLLEGE
OF SURGEONS BULLETIN JANUARY 1976
ISO
Class
1
2
3
4
5
6
7
8
9
0.2 m
0.3 m
0.5 m
1 m
5 m
10
100
1,000
10,000
100,000
1,000,000
2
24
237
2,370
23,700
237,000
10
102
1,020
10,200
102,000
4
35
352
3,520
35,200
352,000
3,520,000
35,200,000
8
83
832
8,320
83,200
832,000
8,320,000
29
293
2,930
29,300
293,000
Selected airborne particulate cleanliness classes for cleanrooms and clean zones. This table shows maximum
concentration limits for particles equal to and larger than the considered sizes shown.
Back
Home
Contents
Dimensions
Data
Spec
108
HOSPITAL/CLEANROOM DIFFUSERS
HIGHLIGHTS
This definition is presented by the Committee on
Operating Room Environment as a concept of a tentative
statement of the definition of microbiologic air cleanliness
in response to a resolution adopted in November 1974 at
a workshop jointly sponsored by the Academy of
Orthopaedic Surgeons and the Assembly of Life
Sciences of the National Research Council held in
Washington, D.C.
States that Federal Standard 209B (now superceded by
ISO 14644) does not provide adequate definitions and
that there is no consistent ratio between viable
(microbially inhabited) airborne particulates and
nonviable ones.
The objective of this definition is to establish a
classification of environmental air cleanliness so that its
effects can be evaluated and controlled.
DEFINES THREE CLASSES:
CLASS 1 MICROBIOLOGIC CLEANLINESS: Viable
microbiologic airborne particle counts not to exceed
one particle per cubic foot of air with minimum
sample of 30 cubic feet of air.
CLASS 5 MICROBIOLOGIC CLEANLINESS: Viable
microbiologic airborne particles to average more
than one and up to five per cubic foot of air with
minimum sample of 30 cubic feet of air.
CLASS 20 MICROBIOLOGIC CLEANLINESS: Viable
microbiologic airborne particles to average more
than five and not to exceed twenty per cubic foot of
air with minimum sample of 10 cubic feet of air.
AVAILABILITY
This document is no longer available from the American
College of Surgeons.
AVAILABILITY
10) MILITARY HANDBOOK MIL-HDBK-1191
DEPARTMENT OF DEFENSE - UNITED STATES
OF AMERICA
MEDICAL AND DENTAL TREATMENT FACILITIES
DESIGN AND CONSTRUCTION CRITERIA
CHAPTER 8 HEATING VENTILATION AND AIR
CONDITIONING
COMMENTS
General guidelines for design and construction.
References ASHRAE and other sources for specific
information.
HIGHLIGHTS
All air supplied to cardiac catherization rooms (hospital
based), delivery rooms, nurseries, operating rooms,
specialized patient bedrooms and surgical cleanrooms
shall be as specified in Appendix A. Air movement shall
range from a preferred 25 fpm (0.127 m/s) to a maximum
of 100 fpm (0.508 m/s) over the sterile field.
Back
Home
Contents
Dimensions
Data
Spec
HOSPITAL/CLEANROOM DIFFUSERS
HIGHLIGHTS
All rooms and areas within a health care facility shall be
ventilated to ensure an air exchange adequate to control
contaminant levels, temperature and humidity. The
ventilation system shall be designed to provide air
movement that is generally from clean to less clean
areas. Air quality guidelines shall be developed for all
occupants, functions, procedures and areas in the health
care facility at the conceptual design stage. HVAC
systems shall be designed, installed, operated and
maintained to minimize the potential for infection via
airborne transmission. Smoke management shall be part
of the HVAC system design and shall be approved by the
authority having jurisdiction in the early stages of design.
SELECTED RECOMMENDATIONS
Air handling systems for Class I areas (operating rooms,
recovery rooms, intensive and cardiac care, delivery
rooms etc...) may operate at a minimum level when the
space is unoccupied. A minimum level shall consist of at
least 6 ACH of recirculated air and the maintenance of
pressure relationships with adjacent areas.
Where present, HEPA filters in the supply air system shall
be; located at the point where the air enters the room;
provided with test ports before and after the filters and
tested for integrity using a scan test upon installation;
designed to permit removal, disposal and replacement of
filters without introducing contamination into the
downstream air delivery system or the area being served;
and provided with a means to indicate operating pressure
drop via the building management system or a local alarm.
Access doors shall be located at not more than 6 m (20 ft.)
intervals on supply air ductwork installed after a HEPA filter.
Diffuser, grille and register cores in air systems shall be
removable for cleaning.
Class I air handling systems shall be cleaned and
disinfected prior to occupancy.
The pressure differential between areas shall be greater
than 0.762 mm (0.03" ) of water pressure.
Air supply for operating rooms, delivery rooms and other
rooms used for invasive procedures shall be through
non-aspirating ceiling outlets near the centre of the work
area. Each operating and delivery room shall have at
least two return or exhaust air inlets located remotely
from each other. The position of the inlets shall be such
Back
Home
Contents
Dimensions
AVAILABILITY
Copies of this document can be purchased from the
Canadian Standards Association online at www.csa.ca
Data
Spec
110
HOSPITAL/CLEANROOM DIFFUSERS
12) CONSTRUCTION-RELATED
NOSOCOMIAL INFECTIONS IN
PATIENTS IN HEALTH CARE FACILITIES:
DECREASING THE RISK OF
ASPERGILLUS, LEGIONELLA AND
OTHER INFECTIONS
CCDR VOLUME: 27S2
JULY, 2001
DIVISION OF NOSOCOMIAL AND
OCCUPATIONAL INFECTIONS
BUREAU OF INFECTIOUS DISEASES,
CENTRE FOR DISEASE PREVENTION & CONTROL
POPULATION AND PUBLIC HEALTH BRANCH
HEALTH CANADA
COMMENTS
This document contains some very useful suggestions
for decreasing the risk to patients and health care
workers during construction and renovation. It
summarizes some documented cases of infections and
deaths associated with construction activity. It provides a
risk assessment and preventative measures checklist. It
also provides a detailed specification on the infection
prevention and control measures that should be
undertaken. It recommends various procedures,
preventative measures and construction techniques that
should be considered before, during and after
construction.
AVAILABILITY
Copies of this document can be downloaded free of
charge from Health Canadas website
www.hc-sc.gc.ca/pphb-dgspsp/dpg_e.html
Back
Home
Contents
Dimensions
Data
Spec
HOSPITAL/CLEANROOM DIFFUSERS
Notes:
Back
Home
Contents
Dimensions
Data
Spec
112
HOSPITAL/CLEANROOM DIFFUSERS
Notes:
Back
Home
Contents
Dimensions
Data
Spec
www.nailor.com
Control Dampers
Fire Dampers
Ceiling Dampers
Smoke Dampers
Combination Fire/Smoke
Dampers
Access Doors
Canadian Headquarters:
Nailor Industries Inc.
98 Toryork Drive,
Toronto, Ontario M9L 1X6
Canada
Tel: 416-744-3300
Fax: 416-744-3360
Single Duct
Dual Duct
Fan Powered
Bypass
Retrofit
European Headquarters:
Advanced Air (UK) Ltd.
Burrell Way,
Thetford,
Norfolk IP24 3WB
England
Tel: (0) 1842 765657
Fax: (0) 1842 753493
www.advancedair.co.uk
Digital Catalog:
The above three catalogs
are also available together
on CD Rom.
HCRDCAT- 11.02
Back
Home
Contents
Dimensions
USA
Data
Spec
CANADA
ENGLAND