Function Block
Parameters
1757 Series
Reference Manual
!
ATTENTION
!
IMPORTANT
Rockwell Automation
Support
Table of Contents
Important User Information . . . . . . . . . . . . . . . . .
Rockwell Automation Support . . . . . . . . . . . . . . .
Local Product Support . . . . . . . . . . . . . . . . . .
Technical Product Assistance . . . . . . . . . . . . .
Your Questions or Comments on this Manual .
Preface
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
iii
iv
iv
iv
iv
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vii
Parameter Attriubutes. . . . . . . . . . . . . . . . . . . . . . . . . . . vii
.............................................. 1
Appendix A
Display Elements Appendix
Appendix B
Allen-Bradley Interface Appendix Array Channel Block Configuration for
Allen-Bradley Interface . . . . . . . . . . . . . . . . . . . . . . . . . .
About Allen-Bradley Interface. . . . . . . . . . . . . . . . . . .
AUXDATA Parameter Configuration . . . . . . . . . . . . . .
AUXDATA[6] Parameter Setting Details . . . . . . . . . . . .
DEVADDR Parameter Configuration . . . . . . . . . . . . . .
STARTINDEX and Number of Elements Parameter. . . .
Report by Exception Requirements . . . . . . . . . . . . . . .
Performance Considerations . . . . . . . . . . . . . . . . . . . .
Array Channel Block Execution State . . . . . . . . . . . . .
Write processing considerations . . . . . . . . . . . . . . . . .
Diagnostic procedures and data configuration. . . . . . .
Time-Out gate configuration. . . . . . . . . . . . . . . . . . . .
Status and error checking . . . . . . . . . . . . . . . . . . . . . .
Error messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Special FTA to KE/KF cabling considerations . . . . . . .
FTA direct to PLC-5 RS-232 Port cable considerations: .
Reference Specifications . . . . . . . . . . . . . . . . . . . . . . .
.
.
.
.
.
.
.
.
B-1
B-1
B-1
B-3
B-5
B-6
B-7
B-8
B-10
B-11
B-11
B-14
B-15
B-15
B-17
B-18
B-19
.
.
.
.
.
.
.
.
.
C-1
C-1
C-1
C-2
C-4
C-4
C-6
C-6
C-7
Appendix C
MODBUS Interface Appendix
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
vi
Preface
Introduction
Parameter Attriubutes
The following table describes the attributes used to define each
parameter. If an attribute does not appear for a specific parameter, it
is not applicable to that parameter.
Table P.1 Parameter Attribute Descriptions
vii
Attribute
Description
Specific to
Block(s)
Defines which function block (or blocks) the table applies to. If a
parameter has different properties for different function blocks, there
will be multiple tables for the parameter.
Description
Data Type
Range
Defines the range of values for the data type (also defines ranges for
ViewOnly parameters).
Default Value
Config Load
Access Lock
Residence
Active Connector
Related
Parameters
Remarks
Preface
viii
Data Type
Multiple data types are supported in ProcessLogix. See Table P.2 for a
listing and description of these data types.
Table P.2 Supported Parameter Data Types
Boolean
Enumeration
Connection
Output Connection
16-Bit Integer
Input Connector
32-Bit Integer
Structure
Constant Integer
Float
Float64/Real64
String
TIME
BlockId(1) / Entity ID
Self-Defining Enumeration(2)
(1)
BlockId - A BlockId parameter value is text describing a blocks name. Example BlockId values are
SCM3.Step7 and SCM7.
(2)
Self-Defining Enumeration (SDEnum) - This data type is just like an Enumeration, except the enumeration
members are user-defined. Parameter A being an SDEnum of B means that B (String data type) defines the
enumeration members for A (SDEnum data type).
TIP
Preface
ix
Access Lock
The ProcessLogix system supports six access levels. Each parameter
includes an Access Lock attribute that defines what access level a
program or operator must have in order to change the value of the
parameter. See Table P.3 for lists of these access levels and to see the
relationship between the access lock and the access level.
Table P.3 Supported Parameter Access Lock Levels
Access
Lock
Access Level
Operator Supervisor Engineer Program
Operator
Supervisor
Engineer
Continuous
Control
Applications
Developer
ViewOnly
Applications
Developer
Only
Engineer/
Applications
Developer
Program
Other
Function
Block
X
X
Control
Engineer Only
Preface
Residence
Parameters in ProcessLogix control strategies may reside in several
places. See Table P.4 for a listing and definition of the valid
residences.
Table P.4 Parameter Residences
Residence
Description
CEE
(Control Execution
Environment)
SR
(System Repository)
ProcessLogix Server
ProcessLogix server:
Parameters resident at the server control how data for the point is
accessed or viewed by the operator, using the ProcessLogix Station
software.
TIP
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
ABORTALM.FL
SCM
Boolean
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
ABORTALM.PR,
ABORTALM.SV,
STATE
ABORTALM.PR
SCM
None (0)
Journal (1)
Low (2)
High (3)
Urgent (4)
Low (2)
Yes
Engineer/
Application
Developer
CEE
No
ABORTALM.FL,
ABORTALM.SV
ABORTALM.SV
SCM
Yes
Engineer
CEE
No
ABORTALM.FL,
ABORTALM.PR
ABORTLOCK
SCM
Abort Command
Access Lock
Engineer
CEE
No
COMMAND
ACCDEV.FL [1..4]
Totalizer, Pulse
Input Totalizer
Accumulator
Boolean
Deviation Flag Indicates when an
accumulator
deviation trip point
(ACCDEV.TP [1-4])
has been reached.
There is one flag per
trip point.
View Only
CEE
No
ACCDEV.TP [1..4],
ACCTV, PV
Off (0):
Off (0)
ACCDEV.TP [n]
is less than or
equal to
ACCTV PV
On (1):
ACCDEV.TP [n]
is greater than
or equal to
ACCTV PV
No
Value of ABORTLOCK
restricts who can issue the
Abort command.
Parameter
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Accumulator
64-Bit Real
Deviation Trip Point - Number
Used to determine
when the
accumulated value
(PV) is getting "near"
the target value
(ACCTV). Trip point
values are
expressed as
deviations from the
target value.
NaN, or
greater than
or equal to
0.0.
NaN
Yes
Engineer
CEE
No
Pulse Input
Totalizer
Accumulator
Real
Deviation Trip Point Used to determine
when the
accumulated value
(PV) is getting near
the target value
(ACCTV). Trip point
values are
expressed as
deviations from the
target value.
NaN or
NaN
greater-than
or equal to 0.0
Yes
Engineer
CEE
No
Flag, Numeric
FLAGARRAY,
NUMERICARRAY,
TEXTARRAY
SIFLAGARRCH,
SINUMARRCH,
SITEXTARRCH
Operator (0)
Engineer (1)
OtherFB (2)
Operator Yes
(0)
Engineer
CEE
No
Numeric only:PV
Flag only: PVFL
FLAGARRAY only:
PVFL [1..1000], STR
[1..120]
NUMERICARRAY
only: PV [1..200]
SI Channels only: PV
[1..64], PVFL [1..512],
STR [1..8]
Totalizer
NaN, or
0
greater-than
or equal-to 0.
Yes
Operator
CEE
No
PV, ACCTVFL,
ACCDEV.TP [1..4],
ACCDEV.FL [1..4]
Pulse Input
Totalizer
NaN, or
greater-than
or equal-to
zero
Yes
Operator
CEE
No
PV, ACCTVFL,
ACCDEV.TP [1..4],
ACCDEV.FL [1..4]
ACCTV
Description
Data Type
Notes
Function Block Parameters
Specific to
Block(s)
Parameter
Specific to
Block(s)
Description
Data Type
ACCTVFL
Totalizer
Accumulated-Target Boolean
-Value Reached Flag
- The "target
reached" flag for the
Totalizer function
block. It indicates if
the present variable
(PV) has reached the
target value
[ACCTV].
Pulse Input
Totalizer
ACTIVEFL
ACTIVEHANDLR
[1..8]
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
No
View Only
CEE
No
PV, ACCTV
Accumulated-Target Boolean
-Value Reached Flag
- The "target
reached" flag for the
Totalizer function
block. It indicates if
the present variable
(PV) has reached the
target value
(ACCTV).
Off (0): PV is
less-than
ACCTV
On (1) PV is
greater-than
or equal-to
ACCTV
No
View Only
CEE
No
PV, ACCTV
Step
Boolean
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
SCM
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
Notes
Specific to
Block(s)
Description
Data Type
ACTIVELOC.
HANDLER
SCM
Active Handler
Name
ACTIVELOC.
HANDLERN
SCM
Active Handler
Name
ACTIVELOC.
HNDTYPE
SCM
ACTIVELOC.
STEP [1..10]
SCM
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
BlockId
Null
String
No
View Only
CEE
No
32-Bit Integer
Null
String
No
View Only
CEE
No
No
View Only
CEE
No
TYPE
Null
String
No
View Only
CEE
No
ACTIVELOC.STEPN
[1..10]
BlockId
Range
Notes
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
ACTIVELOC.
STEPN [1..10]
SCM
ACTIVELOC.
TIME [1..10]
SCM
32-Bit Integer 0 to
2147483647
ACTSOAKTIME
RampSoak
[1..NUMPROFILES
]
[1..NUMRAMPSO
AK]
ACTSOAKVAL
RampSoak
[1..NUMPROFILES
]
[1..NUMRAMPSO
AK]
0.0 to 120.0
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
No
View Only
CEE
No
ACTIVELOC.STEP
[1..10]
No
View Only
CEE
No
NaN
No
View Only
CEE
No
RampSoak
0.0
No
View Only
CEE
No
NUMPROFILES,
NUMRAMPSOAK
[1..NUMPROFILES],
ACTRAMPRATE
[1..NUMPROFILES]
[1..NUMRAMPSOAK]
, ACTSOAKVAL
[1..NUMPROFILES]
[1..NUMRAMPSOAK]
, ACTSTARTOP
[1..NUMPROFILES],
ACTSTARTSEG
[1..NUMPROFILES]
NaN
No
View Only
CEE
No
NUMPROFILES,
NUMRAMPSOAK
[1..NUMPROFILES],
ACTSOAKTIME
[1..NUMPROFILES]
[1..NUMRAMPSOAK]
, ACTRAMPRATE
[1..NUMPROFILES]
[1..NUMRAMPSOAK]
, ACTSTARTOP
[1..NUMPROFILES],
ACTSTARTSEG
[1..NUMPROFILES]
ACTRAMPRATE RampSoak
[1..NUMPROFILES
]
[1..NUMRAMPSO
AK]
Range
Parameter
Description
Data Type
ACTSTARTOP
RampSoak
[1..NUMPROFILES
]
Actual Starting
Output Value
ACTSTARTSEG
RampSoak
[1..NUMPROFILES
]
ACTVTNTIME
Step
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Real
View
Only
No
CEE
No
NUMPROFILES,
NUMRAMPSOAK
[1..NUMPROFILES],
ACTSOAKTIME
[1..NUMPROFILES]
[1..NUMRAMPSOAK]
, ACTSOAKVAL
[1..NUMPROFILES]
[1..NUMRAMPSOAK]
, ACTRAMPRATE
[1..NUMPROFILES]
[NUMRAMPSOAK],
ACTSTARTSEG
[1..NUMPROFILES]
Actual Starting
Segment ID
Real
View
Only
No
CEE
No
NUMPROFILES,
NUMRAMPSOAK
[1..NUMPROFILES],
ACTSOAKTIME
[1..NUMPROFILES]
[1..NUMRAMPSOAK]
, ACTSOAKVAL
[1..NUMPROFILES]
[1..NUMRAMPSOAK]
, ACTRAMPRATE
[1..NUMPROFILES]
[1..NUMRAMPSOAK]
, ACTSTARTOP
[1..NUMPROFILES]
Activation Time
Integer
No
View Only
CEE
Yes
Operator
CEE
No
ADVDEVALM.DBU
64-Bit Real
Number
Range
Notes
Function Block Parameters
Specific to
Block(s)
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Enumeration
ALMDBU
Percent (0)
EU(1)
Percent
(0)
Yes
Engineer
CEE
No
ADVDEVALM.DB
ADVDEVALM.FL
Boolean
Off (0)
No
View Only
CEE
No
ADVDEVALM.PR
Enumeration
ALPRIOR
None (0)
Journal (1)
Low (2)
High (3)
Urgent (4)
Low (2)
Yes
Engineer
CEE
No
ADVDEVALM.SV
Yes
Engineer
CEE
No
0 to 60
Yes
CEE
No
ADVDEVAL
M.TP
If ADVDEVALM.TM
equals zero, an alarm
will be generated as
soon as the advisory
deviation exceeds
the trip point.
ADVDEVALM.TP
NaN, or
greater-than
or equal-to
zero.
NaN
Yes
Operator
CEE
No
PV, ADVSP
Notes
Specific to
Block(s)
ADVDEVOPT
ADVS
64-Bit Real
Number
ADVSPP
64-Bit Real
Number
ALARM
nooN
ALIAS [ ].AL
SCM
ALIAS [ ].STATU
SCM
Internal parameter
for system use only.
ALIAS [ ].VALUE
SCM
Internal parameter
for system use only.
ALIASBLKTYP [ ] SCM
Alias Table
parameter
ALIASDATATYP [ SCM
]
ALIASOPT
Description
Data Type
16-Bit Integer
(Template ID)
Integer
(TEMPLATE
ID)
Access
Lock
Residence
Active
Connector
Enable (0):
Enable (0) Yes
Advisory
deviation
alarming is
requested
Disable (1):
Advisory
deviation
alarming is
not requested
Engineer
CEE
No
SPLOLM to
SPHILM
Yes
Operator
CEE
No
ADVSPP
No
View Only
CEE
No
ADVSP
No
View Only
CEE
No
No
Application
Developer
CEE
No
NUMALIASES
Yes
Application
Developer
ERDB
No
NUMALIASES
Sized by NUMALIASES.
Application
Developer
ERDB
Yes
Application
Developer
ERDB
No
If ALIASOPT is
configured to False,
all the alias
parameters will not
be exposed in the
SCM configuration
form.
Yes
Application
Developer
ERDB
No
NUMALIASES
Off (0)
On (1)
Default
Off (0)
Config
Load
Related
Parameters
Notes
Internal parameter
for system use only.
Alias Table
parameter
Internal parameter
for system use only.
SCM
ALIASPRMTYP [ ] SCM
Range
Parameter
Parameter type of
the aliases defined
in the Alias Table.
16-Bit Integer
(Param ID)
False (0)
True (1)
False (0)
Sized by NUMALIASES.
Parameter
Specific to
Block(s)
Description
Data Type
ALIASREF [ ] [ ]
SCM
Internal parameter
for system use only.
ALIASSRC [ ] [ ]
SCM
Internal parameter
for system use only.
ALMDB
DataAcq,
Overall Deadband
64-Bit Real
All RegCtl Blocks
for all analog alarms Number
except Fanout:
AutoMan, OvrdSel,
PID, PIDFF, PosProp,
PulseCount,
PulseLength,
RampSoak,
RemCas, RatioBias,
RegCalc, and
Switch.
ALMDBU
DataAcq,
Overall Deadband
All RegCtl Blocks
unit for all analog
except Fanout:
alarms
AutoMan, OvrdSel,
PID, PIDFF, PosProp,
PulseCount,
PulseLength,
RampSoak,
RemCas, RatioBias,
RegCalc, and
Switch.
ALMENBSTATE
Enumeration
ALMDBU
Range
Default
Config
Load
Access
Lock
0.00
Yes
Percent (0)
Engineering
Units (1)
Percent
(0)
Off (0)
On (1)
On (1)
Residence
Related
Parameters
Notes
Engineer/Ap CEE
plication
Developer
No
ADVDEVALM.DB,
DEVHIALM.DB,
DEVLOALM.DB,
OPHIALM.DB,
OPLOALM.DB,
PVHHALM.DB,
PVHIALM.DB,
PVLLALM.DB,
PVLOALM.DB
Yes
Application
Developer
CEE
No
ADVDEVALM.DBU,
DEVHIALM.DBU,
DEVLOALM.DBU,
OPHIALM.DBU,
OPLOALM.DBU,
PVHHALM.DBU,
PVHIALM.DBU,
PVLLALM.DBU,
PVLOALM.DBU
Yes
Operator
CEE
RM only:
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
INALM
Active
Connector
Description
Data Type
Range
Default
Config
Load
Access
Lock
ALMTM
DataAcq,
Filter Time for all
All RegCtl Blocks
alarms
except Fanout:
AutoMan, OvrdSel,
PID, PIDFF, PosProp,
PulseCount,
PulseLength,
RampSoak,
RemCas, RatioBias,
RegCalc, and
Switch.
32-Bit
Unsigned
Integer
0 to 60
Yes
AREVISION
RM
Application
8-Bit
Revision. Identifies Unsigned
the minor revision of Integer
the RM application
code.
0 to 255
ARWNET [1..8]
Normal (0):
The input is
free to move
in any
direction.
Hi (1):
The input
cannot move
higher, but is
free to move
lower.
Lo (2):
The input
cannot move
lower, but is
free to move
higher.
HiLo (3):
The input
cannot move
in any
direction.
Normal
(0)
Residence
Active
Connector
Related
Parameters
Notes
Engineer/Ap CEE
plication
Developer
No
ADVDEVALM.TM,
CMDDISALM.TM
[0..2],
CMDFALALM.TM
[0..2],
DEVHIALM.TM,
DEVLOALM.TM,
OPHIALM.TM,
OPLOALM.TM,
PVHHALM.TM,
PVHIALM.TM,
PVLLALM.TM,
PVLOALM.TM
No
View Only
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
No
View Only
No
ARWOP
ARWNET(1) computation is
independent of whether gain
(K) is positive or negative.
CEE
Specific to
Block(s)
10
Parameter
Specific to
Block(s)
Description
Data Type
ARWOP
ARWOP [1..8]
Fanout
ASACONNSTS
ASA Connection
Status
ASACONNSTS
[0..7]
Serial Interface
IOM
ASA Connection
Status
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Normal (0):
Normal
OP is free to (0)
move in either
direction.
Hi (1):
OP is free to
move in the
lower
direction.
Lo (2):
OP is free to
move in the
higher
direction.
HiLo (3):
OP cannot
move in any
direction.
No
View Only
CEE
No
ARWNET [1..8]
Normal:
Free to move
in either
direction.
Hi:
Free to move
in the lower
direction.
Lo:
Free to move
in the higher
direction.
HiLo:
Cannot move
in any
direction.
No
View Only
CEE
No
ARWNET [1..8]
No
View Only
CEE
No
0x4000 indicates
running/connected (good
status).
No
View Only
CEE
No
0x4000 indicates
running/connected (good
status).
Normal
Notes
Parameter
11
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
ASAERRCODE
32-Bit Integer
No
View Only
CEE
No
ASAERRINFO
ASAERRCODE
[0..7]
Serial Interface
IOM
32-Bit Integer
No
View Only
CEE
No
ASAERRINFO [0..7]
ASAERRINFO
32-Bit Integer
No
View Only
CEE
No
ASAERRCODE
ASAERRINFO
[0..7]
Serial Interface
IOM
ASA Error
Information
32-Bit Integer
No
View Only
CEE
No
ASAERRCODE [0..7]
ASTEPID
DevCtl,
All RegCtl Blocks:
AutoMan, Fanout,
OvrdSel, PID, PIDFF,
PosProp,
PulseCount,
PulseLength,
RampSoak,
RemCas, RatioBias,
RegCalc, and
Switch.
No
View Only
CEE
No
CONTROLREQ,
SCMASTEP [1..10]
AUTOSYNCCMD RM
Description
Auto
Synchronization
Command
Data Type
Enumeration
Range
Default
Never (0)
Never (0) No
Always (1)
Conditional (2)
Operator
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
Specific to
Block(s)
12
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
AUTOSYNCOPT
RM
Auto
Synchronization
Option.
Enumeration
Never (0)
Never (0) No
Always (1)
Conditional (2)
View Only
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
Disabled (0)
Enabled (1)
Disabled No
(0)
View Only
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
Auto
Enumeration
Synchronization
State - Present State
of Redundancy
Module
Auto-Synchronizatio
n
AUXCMD
SCM
No
Operator
CEE
No
AUXDATA [0..7]
SIFLAGARRCH,
SINUMARRCH,
SITEXTARRCH
Auxiliary
64-Bit Real
Configuration Data Number
Used for specifying
additional
configuration
parameters for the
FTA application; a
generic array is
provided because
each value can mean
different things for
different FTA
applications.
AUXDATA is
writable while
online.
NaN
Yes
Application
Developer
CEE
No
AUXDESC [0..10]
CEE, CPM
Internal parameter
for system use only.
AUXOPT
SCM
No
Engineer
CEE
No
Notes
AUXSTS,
AUXREQDATA [1..5]
AUTOSYNCSTAT RM
Related
Parameters
13
Description
AUXREQ
SCM
AUXREQDATA
[1..5]
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
No
Operator
CEE
No
AUXCMD, AUXSTS,
AUXREQDATA [1..5]
SCM
Auxiliary SCM
Request Data
NaN
No
Operator
CEE
No
AUXCMD, AUXSTS,
AUXREQ
AUXSTS
SCM
No
Operator
CEE
No
AUXUNIT
SCM
Auxiliary Unit.
No
Operator
CEE
No
AV
NaN
No
View Only
CEE
Yes
AVSTS
AV [0..7]
NaN
No
View Only
CEE
Yes
AVERSION
RM
No
View Only
Not Loaded No
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
AVRAW
32-Bit
Unsigned
Integer
No
View Only
CEE
No
AVRAW [0..7]
32-Bit
Unsigned
Integer
No
View Only
CEE
Yes
Raw Accumulated
Value Raw pulse
count.
Data Type
Range
64-Bit Real
Number
32-Bit Integer
0 to 255
Greater-than
or equal-to
zero.
AVRAWSTS
Specific to
Block(s)
14
Parameter
Parameter
Specific to
Block(s)
AVRAWSTS
Data Type
Range
Enumeration
Bad (0)
Uncertn (1)
Normal (2)
Manual (3)
AVSTS
Enumeration
Bad (0)
Uncertn (1)
Normal (2)
Manual (3)
B[1..6]
RegCalc
Real
Description
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
No
View Only
CEE
No
AVRAW
Off
No
View Only
CEE
No
AV
0.0
Yes
Operator
CEE
No
X[1..6]
No
Application
Developer
CEE
Yes
BACKCALCOUT,
BACKCALCIN establishes the
BACKCALCOUT[1..4], initialization, override, and
BACKCALCOUT[1..8] windup propagation
between connected
Regulatory Control (RegCtl)
and Analog Output (AO)
Blocks. This is one half of
the
BACKCALCIN/BACKCALCOU
T connection.
Secondary Data
Structure
structure associated
with Regulatory
Control Block
output(s). Contains
Calculated Value
(CV) limits,
initialization, and
data windup status,
etc.. BACKCALCIN
is associated with
the secondary block,
and therefore is
related to the
number of outputs
used on the primary
block. Connecting
BACKCALCIN to its
BACKCALCOUT
partner is required
in order to establish
the initialization
path between the
two blocks.
Default
15
Description
BACKCALCIN
BACKCALCIN
[1..3]
DevCtl
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Secondary Data
Structure
structure associated
with Regulatory
Control Block
output(s). Contains
Calculated Value
(CV) limits,
initialization, and
data windup status,
etc.. BACKCALCIN
is associated with
the secondary block,
and therefore is
related to the
number of outputs
used on the primary
block. Connecting
BACKCALCIN to its
BACKCALCOUT
partner is required
in order to establish
the initialization
path between the
two blocks.
No
View Only
CEE
Yes
BACKCALCOUT,
BACKCALCIN establishes the
BACKCALCOUT[1..4], initialization, override, and
BACKCALCOUT[1..8] windup propagation
between connected
Regulatory Control (RegCtl)
and Analog Output (AO)
Blocks. This is one half of
the
BACKCALCIN/BACKCALCOU
T connection.
No
View Only
CEE
Yes
BACKCALCOUT
Specific to
Block(s)
16
Parameter
Parameter
Specific to
Block(s)
Description
BACKCALCIN
[1..8]
Fanout
BACKCALCOUT
Data Type
Range
Default
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Secondary Data
Structure
structure associated
with the Fanout
block output(s).
Contains Calculated
Value (CV) limits,
initialization, and
data windup status,
etc.. BACKCALCIN
is associated with
the secondary block,
and therefore is
related to the
number of outputs
used on the primary
block. Connecting
BACKCALCIN to its
BACKCALCOUT
partner is required
in order to establish
the initialization
path between the
two blocks.
No
View Only
CEE
Yes
BACKCALCOUT,
X1BACKCALOUT,
X2BACKCALOUT
BACKCALCIN establishes
the initialization, override,
and windup propagation
between connected
Regulatory Control (RegCtl)
and Analog Output (AO)
blocks. This is one half of
the
BACKCALCIN/BACKCALCOU
T connection.
No
View Only
CEE
No
BACKCALCIN,
BACKCALCIN[1..8]
BACKCALCOUT establishes
the initialization, override,
and windup propagation
between connected
Regulatory Control (RegCtl)
and Analog Output (AO)
blocks. This is one half of
the
BACKCALCIN/BACKCALCOU
T connection.
Config
Load
17
Description
BACKCALCOUT
[1..4]
OvrdSel
BACKCALCOUT
[1..8]
Switch
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Secondary Data
Structure
structure associated
with Regulatory
Control block
input(s). Contains
Calculated Value
(CV) limits,
initialization, and
data windup status,
etc. BACKCALCOUT
is associated with
the primary block,
and therefore is
related to the
number of inputs
used on the
secondary block.
Connecting
BACKCALCIN to its
BACKCALCOUT
partner is required
in order to establish
the initialization
path between the
two blocks.
No
View Only
CEE
No
BACKCALCIN
BACKCALCOUT establishes
the initialization, override,
and windup propagation
between connected
Regulatory Control (RegCtl)
and Analog Output (AO)
blocks. This is one half of
the
BACKCALCIN/BACKCALCOU
T connection.
Secondary Data
Structure
structure associated
with Regulatory
Control block
input(s). Contains
Calculated Value
(CV) limits,
initialization, and
data windup status,
etc. BACKCALCOUT
is associated with
the primary block,
and therefore is
related to the
number of inputs
used on the
secondary block.
Connecting
BACKCALCIN to its
BACKCALCOUT
partner is required
in order to establish
the initialization
path between the
two blocks.
No
View Only
CEE
No
BACKCALCIN
BACKCALCOUT establishes
the initializaiton, override,
and windup propagation
between connected
Regulatory Control (RegCtl)
and Analog Output (AO)
blocks. This is one half of
the
BACKCALCIN/BACKCALCOU
T connection.
Specific to
Block(s)
18
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
BACKLASHL
PosProp,
PidPosProp
Backlash Lower
compensation of
actuator (in
seconds).
Real
0.0 to 60.0
seconds
0.0
seconds
Yes
Supervisor
CEE
No
BACKLASHR
PosProp,
PidPosProp
Backlash Raise
Compensation of
actuator (in
seconds).
Real
0.0 to 60.0
seconds
0.0
seconds
Yes
Supervisor
CEE
No
BADCAL
AIC, AOC
Bad Calibration
Boolean
Indicator On a per
channel basis, this
parameter indicates
if calibration is bad
or missing.
Ok (0)
Ok (0)
BadCalibratio
n (1)
No
View Only
CEE
Bad Calibration
Boolean
Indicator On a per
channel basis, this
parameter indicates
if calibration is bad
or missing.
Ok (0)
Ok (0)
BadCalibratio
n (1)
No
View Only
CEE
BADCODE
All IO Channels,
SIFLAGARRCH,
SINUMARRCH,
SITEXTARRCH
No
View Only
CEE
BADCTLALM.FL
Off (0)
On (1)
Off (0)
No
View Only
BADCTLALM.PR
None (0)
Journal (1)
Low (2)
High (3)
Urgent (4)
Low (2)
Yes
Engineer
Integer
Boolean
Related
Parameters
Notes
No
CALBIAS
No
CALBIAS
CEE
No
BADCTLFL,
BADCTLALM.PR,
BADCTLALM.SV
CEE
No
BADCTLFL,BADCTLA
LM.FL,BADCTLALM.
SV
Parameter
19
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
BADCTLALM.SV
Yes
Engineer
CEE
No
BADCTLFL,
BADCTLALM.FL,
BADCTLALM.PR
BADCTLFL
Boolean
No
View Only
CEE
No
BADCTLALM.FL,
BADCTLALM.PR,
BADCTLALM.SV
BADCTLOPT
Engineer
CEE
No
BADCTLFL, ESWENB,
MODE, MODEATTR,
OP
Notes
Specific to
Block(s)
20
Parameter
Engineer /
Application
Developer
CEE
No
BADPV
DIC
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
BADPVALM.FL
DataAcq, DevCtl
Boolean
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
BADPVALM.PR,
BADPVALM.SV,
HIALM, HIALM.PR,
HIALM.SV,
HIALM.TYPE
BADPVALM.PR
DataAcq, DevCtl
Bad PV Alarm
Priority
Enumeration
ALMPR
None (0)
Journal (1)
Low (2)
High (3)
Urgent (4)
DataAcq Yes
only: Low
(2)
DevCtl
only:
None (0)
Engineer
CEE
No
DataAcq only:
BADPVALM.FL,
BADPVALM.SV,
PVSTSFL.BAD
DevCtl only:
BADPVALM.FL,
BADPVALM.SV,
NUMDINPTS
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
BADPVALM.SV
DataAcq, DevCtl
Bad PV Alarm
Severity
16-Bit Integer 0 to 15
Yes
Engineer
CEE
No
DevCtl Only:
BADPVALM.FL,
BADPVALM.PR,
NUMDINPTS
DataAcq Only:
BADPVALM.FL,
BADPVALM.PR,
PVSTSFL.BAD
BADPVFL
SIFLAGARRCH,
SINUMARRCH,
SITEXTARRCH
Off (0)
No
View Only
CEE
No
ERRFL
BADSO
No
View Only
CEE
No
Off (0)
On (1)
Parameter
21
Description
Data Type
Range
Default
BADSO[6..7]
BASEPERIOD
CEE
5 ms (0)
50ms (1)
50 ms (1)
BATTERYNOTOK CPM
Off (0)
On (1)
Off (0)
BECMPRICMD
RM
Become Primary
Command
Boolean
True (0)
False (1)
True (0)
BFF
PIDFF
Feedforward Input
Bias
Real
Config
Load
Access
Lock
Residence
Active
Connector
No
View Only
CEE
No
Application
Developer
CEE
No
View Only
CEE
No
Operator.
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
Operator
CEE
Related
Parameters
Notes
Affects channels 6-7 only.
No
Specific to
Block(s)
22
Parameter
Specific to
Block(s)
Description
Data Type
BOOLVALUEOFF
TypeConvert
Used to convert
Boolean values to
Enumeration.
BOOLVALUEON
TypeConvert
Used to convert
Boolean values to
Enumeration.
BREVISION
RM
Boot Revision.
8-Bit
Identifies the minor Unsigned
revision of the RM Integer
boot code.
BVERSION
RM
BYPASS
BYPPERM
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Enumeration Enum0 to
TCGENERICEN Enum63
UM
Enum0
Yes
Engineer
CEE
No
BOOLVALUEON
Enumeration Enum0 to
TCGENERICEN Enum63
UM
Enum1
Yes
Engineer
CEE
No
BOOLVALUEOFF
0 to 255
No
View Only
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
Boot Version.
8-Bit
Identifies the major Unsigned
revision of the RM Integer
boot code.
0 to 255
No
View Only
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
DevCtl
Permissive and
Interlock Bypass
Boolean
Off (0)
On (1)
Off (0)
Yes
Operator
CEE
No
BYPPERM,
Can be changed only where
NUMDOUTS, OI[0..2], BYPPERM = On. When On,
OP, PI[0..2]
Override and Permissive
Interlocks are bypassed.
Default to Off when
BYPPERM is set to Off.
Illegal if NUMDOUTS = 0.
DevCtl
Override and
Permissive Bypass
Permit
Boolean
Off (0)
On (1)
Off (0)
Yes
Engineer
CEE
No
BYPASS, OI[0..2],
When On, allows BYPASS to
PI[0..2],NUMDOUTS be set to bypass the
Permissive and Override
Interlocks OI[0..2] and
PI[0..2].
Illegal if NUMDOUTS = 0.
Parameter
23
Description
Data Type
C [1..8]
Auxcalc
Results of up to
eight calculator
expressions.
64-Bit Real
Number
RegCalc
Range
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
NaN
No
View Only
CEE
No
CSTS[1..8]
NaN
No
View Only
CEE
No
CSTS[1..8]
Off (0)
Yes
Engineer
CEE
No
C [1..10].BYPREQ, C
[1..10].FL
C [1..10].BYPPERM, C
[1..10].FL
Notes
C
Transition
[1..10].BYPPERM
Conditional Force
Permit
Boolean
C [1..10].BYPREQ Transition
Conditional Force
Request
None (2)
No
Operator
CEE
No
C
Transition
[1..10].CONFIGCO
DE
Condition
Configuration Code
None (0)
No
View Only
CEE
No
CEE
No
None (0)
Ok (1)
UnknownError (2)
ImplictConv (3)
LossOfPrecsn (4)
UnexpctEnd (5)
UnexpctComma (6)
ColonWoQMark (7)
FctNotMltArg (8)
ClosParenExp (9)
OperandExp (10)
MissingArg (11)
OperatorExp (12)
ColonExp (13)
TypeMismatch (14)
TypeNotSupp (15)
SyntaxError (16)
ExprTooCmplx (17)
NotEPcodeMe (18)
NotEDataStak (19)
UnsuppFeatur (20)
C
Transition
[1..10].CONFIGDE
SC
Conditional
Configuration
Descriptor
String
Off (0)
On (1)
Default
Range
ExprTooLong (21)
DivideByZero (22)
UnknownToken (23)
UnexpTokenOS (24)
UnknownFunc (25)
UnexpOCExpr2 (26)
UnexpOCExpr3 (27)
ZeroArgument (28)
UnexpToken (29)
InvalResult (30)
InvalTokenTb (31)
IntegerExp (32)
DoubleExp (33)
MissedImpl (34)
UnicodeConv (35)
ConstExprRem (36)
DuplExprRem (37)
ExtUse38 (38)
ExtUse39 (39)
ExtUse40 (40)
ExtUse41 (41)
None
If C [i].BYPPERM is On, C
[i].FL will be set according to
C [i].BYPREQ.
ExtUse42 (42)
ExtUse43 (43)
ExtUse44 (44)
ExtUse45 (45)
ExtUse46 (46)
ExtUse47 (47)
ExtUse48 (48)
ExtUse49 (49)
ExtUse50 (50)
UnSupConType (51)
UnExpClsParn (52)
CantAssRVal (53)
UnExpArrOpen (54)
ArrClsExpect (55)
ArrOpnExpect (56)
ArrIndxError (57)
StringExpect (58)
InvalidRefer (59)
TooManyConns (60)
CantConvInpt (61)
No
View Only
Specific to
Block(s)
24
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
C
[1..10].CONFIGCODE,
C
[1..10].CONFIGDESC
Condition
Enumeration Ok (0)
Ok (0)
Configuration Status CSCOCONFIG Information (1)
Warning (2)
SevereWarn
(3)
Fail (4)
Error (5)
SevereError
(6)
No
View Only
CEE
No
C [1..10].DESC
Transition
Condition
Description
Yes
Application
Developer
SR
No
C [1..10].
EXECCODE
Transition
No
View Only
CEE
No
C [1..10].
EXECDESC
Transition
None
No
View Only
CEE
No
C [1..10].
EXECSTS
Transition
No
View Only
CEE
No
C [1..10].EXPR
Transition
Yes
Application
Developer
SR
No
String
Maximum
string length
is 23
characters.
Length: 255
characters.
Null
String
Null
String
C
Transition
[1..10].CONFIGST
S
25
Description
C [1..10].
EXPRPCODE
Transition
Internal parameter
for system use only.
C [1..10].FL
Transition
Condition Status
Flag
C [1..10].
GATEASGN
Transition
Internal parameter
for system use only.
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Boolean
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
Boolean
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
C [1..10].FL
C [i].INVOKFL on invoke
transition is updated from C
[i].FL at the time of handler
invocation.
C [1..10].INVOKFL Transition
Invoke Transition
Condition Invoke
Flag
C1
Engineering Units
64-Bit Real
scaling factor for the Number
calculation of
DELAYTIME or
Totalizer Process
Variable (PV).
Any Real
1.0
Number, NaN
is not allowed.
Yes
Deadtime:
Engineer
Totalizer,
Pulse Input
Totalizer:
Operator
CEE
No
DELAYTIME, D1
Any Real
1.0
Number, NaN
is not allowed.
Yes
View Only
CEE
No
C2, AV, PV
3.4 e 38 to
3.4 e 38
Yes
Application
Developer
CEE
No
C1[0..7]
Totalizer, Pulse
Input Totalizer,
Deadtime
Engineering Units
64-Bit Real
scale factor
Number
(dimensionless) for
example, a factor to
convert gallons to
barrels.
1.0
Specific to
Block(s)
26
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
C2
Pulse Input
Totalizer
Deadtime
Range
Config
Load
Access
Lock
Residence
Active
Connector
Any Real
1.0
number, NaN
not allowed.
Yes
Operator
CEE
No
Any Real
1.0
Number, NaN
not allowed.
Yes
Engineer
CEE
No
1.0
Yes
View Only
CEE
1.0
Yes
Application
Developer
1.0
Yes
1.0
3.4 e 38 to
3.4 e 38
Default
Related
Parameters
Notes
No
AV,PV
CEE
No
View Only
CEE
No
Yes
Application
Developer
CEE
No
C2[0..7]
Meter factor in
64-Bit Real
pulses per
Number
Engineering Unitls
for example, number
of pulses per gallon.
C3
C3[0..5]
Pulse Length
64-Bit Real
measurement
Number
Engineering Units
conversion factor (in
Engineering Units
per unit of time).
CALBIAS
AIC, AOC
Calibration Bias
Specifies a bias
value which is
applied to the raw
analog data.
64-Bit Real
Number
No
View Only
CEE
No
BADCAL
CALBIAS[0..5] is accessible
by the Application Developer
on the Configuration Form
only.
CALBIAS
[0..numChans-1]
AIM, AOM
Calibration Bias
Specifies a bias
value which is
applied to the raw
analog data.
64-Bit Real
Number
Yes
Application
Developer
CEE
No
BADCAL
CALBIAS[0..5] is accessible
by the Application Developer
on the Configuration Form
only.
3.4 e 38 to
3.4 e 38
Description
CASREQFL
CATNUMBER
Catalog Number
Data Type
Range
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Off (0)
Off (0)
On (1): Mode
was shed due
to timeout;
waiting to
return to
cascade
mode.
No
Other
Function
Block
CEE
No
MODE
See
below
Yes
Application
Developer
CEE
No
No
32-Bit Integer
Default
Notes
Specific to
Block(s)
Default
1756-IF6I: 1
1756-IF16: 6
1756-IA16: 5
1756-IB32: 12
1756-IB16I: 6
1756-IA16I: 5
1756-IM16I: 6
1756-IA8D: 1
CCLCNT
CPM
Number of Loaded
Control Component
Libraries (CCLs) in
the Control
Processor Module
(CPM).
16-Bit Integer
CCLINFO
CPM
Control Component
Library (CCL)
management
information.
String (One
Dimensional
Array)
CCLLOADSTAT
CPM
Control Component
Library (CCL) load
status.
CCLNAME
CPM
List of loaded
libraries.
CCLPACKET
CPM
Library Load
Parameter
1756-IB16D: 2
1756-IR6I: 2
1756-IT6I: 5
TC- MUX021: 0
1756-OF6CI: 4
1756-OF6VI: 3
1756-OF8: 9
1756-OA16: 7
1756-OB32: 17
1756-OB16I: 7
1756-OA16I: 7
1756-OA8D: 4
1756-OB16D: 4
1757-PIM: 8
No
View Only
CEE
Null
String
No
View Only
CEE
No
View Only
CEE
No
String (One
Dimensional
Array)
Null
String
No
View Only
CPM
No
Engineer
CEE
0 to 49
0 to 40
CCLCNT, CCLNAME
CCLCNT, CCLINFO
28
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
CEECOMMAND
CEE, CPM
Control Execution
Environment
Command
CEESTATE
Control Execution
Enumeration
Environment State - CEESTATE
Gives current state
of CEE.
Default
Config
Load
Access
Lock
None (2)
No
No
Idle(0)
Idle(0)
Run(1)
Failed(2)
NotLoaded(3)
Residence
Related
Parameters
Notes
Supervisor or CEE
Engineer
whan an Idle
command is
stored to
CEECOMMA
ND and the
CEE is in the
Run state.
Supervisor,
Engineer or
Operator
when a
CEECOMMA
ND of Run is
stored and
the CEE is in
Idle.
No
CEESTATE
View Only
No
CEECOMMAND,
EXECSTATE,
PCMSTATE
CEE
Active
Connector
29
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Channel In Use
Boolean
Indicates whether
the Channel is
currently being used
(a value of On) or not
(a value of Off).
Off (0)
On (1)
Off (0)
No
View Only
CEE
RM only:
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
CHANSTS[0..31]
CHANSTS[0..31]
RM, Serial
Interface IOM
Channel Status
Enumeration
Provides a status for
each channel of the
module.
NotUsed(0)
Ok(1)
Bad(2)
NotUsed( No
0)
View Only
CEE
RM only:
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
CHANINUSE[0..31],
ERRFL[0..31]
CHANTEXT
IOM
Channel In Use
Boolean
Indicates whether
the Channel is
currently being used
(a value of On) or not
(a value of Off).
Off (0)
On (1)
Off (0)
View Only
CEE
No
CIPNAME
RSPNUMARRAY
RSPFLAGARRAY
RSPTEXTARRAY
Maximum of Blank
Yes
40 characters (no name)
Application
Developer
CEE
CJDISABLE
AIM, RM
Cold Junction
Boolean
Disable Appears
as a configuration
checkbox that when
enabled allows
CJOFFSET to be
configured.
Off (0)
On (1)
Yes
Application CEE
Developer
RM only:
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
CJOFFSET
CJOFFSET
AIC
-5 to +5
0.0
degrees (C or
F)
No
View Only
No
CJDISABLE,
CALBIAS</HH.
String
Off (0)
No
Not Loaded
30
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Yes
Application
Developer
CEE
(1756-IF16
not loaded)
No
CJDISABLE,
CJOFFSET is accessible by
CALBIAS[0..numChan the Application Developer on
s-1] (AIM only).
the Thermocouple AIM
Configuration Form only.
Configurable only when
CJDISABLE is set.
Standard No
(0)
View Only
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
-5 to +5
0.0
degrees (C or
F)
CLKADJUST
RM
Local clock
adjustment
Enumeration
Standard (0)
Daylight (1)
CLKTIME
RM
Clock time, as
reported by the
Redundancy
Module.
TIME
No
View Only
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
CLKZONE
RM
Time zone
16-Bit
Unsigned
Integer
No
View Only
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
CLROPREQFL
DevCtl
Clear Requested
Output Value
(OPREQ) Flag
Boolean
CMDATTR
Totalizer, Pulse
Input Totalizer
Off (0)
On (1)
Off (0)
No
Other
Function
Block
CEE
No
GOPREQ, OPREQ,
OPTYPE
Operator (0)
OtherFB (1)
Operator Yes
(0)
Operator
CEE
No
COMMAND
CJOFFSET[0..num AIM
Chans-1]
Notes
31
Description
CMDDISALM.FL
DevCtl
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
CMDDISALM.PR,
CMDDISALM.SV,
CMDDISALM.TM[0..
2], GOP, GPV, HIALM,
NUMDINPTS,
NUMDOUTS, OP,
OPFINAL, PV
Illegal if NUMDINPTS = 0 or
NUMDOUTS = 0.
Illegal if all
CMDDISALM.TM[0..2] = 0.
CMDDISALM.PR DevCtl
None (0)
Journal (1)
Low (2)
High (3)
Urgent (4)
Low (2)
Yes
Engineer
CEE
No
CMDDISALM.FL,
CMDDISALM.SV,
CMDDISALM.TM[0..
2], NUMDINPTS,
NUMDOUTS
Illegal if NUMDINPTS = 0 or
NUMDOUTS = 0.
Illegal if
CMDDISALM.TM[0..2]= 0.
CMDDISALM.SV DevCtl
Yes
Engineer
CEE
No
CMDDISALM.FL,
CMDDISALM.PR,
CMDDISALM.TM[0..
2], NUMDINPTS,
NUMDOUTS
Illegal if NUMDINPTS = 0 or
NUMDOUTS = 0.
Illegal if all
CMDDISALM.TM[0..2] = 0.
CMDDISALM.TM[ DevCtl
0..2]
0 seconds Yes
Engineer
CEE
No
CMDDISALM.FL,
CMDDISALM.PR,
CMDDISALM.SV,
NUMDINPTS,
NUMDOUTS,
NUMSTATES
CMDEXEC
SCM
None (0)
Resume (1)
CheckConfig
(2)
None (0)
No
View Only
CEE
No
COMMAND
CMDFALALM.FL
DevCtl
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
CMDFALALM.PR,
CMDFALALM.SV,
CMDFALALM.TM[0..
2], GOP, GPV, HIALM,
NUMDINPTS,
NUMDOUTS, OP,
OPFINAL, PV
Illegal if NUMDINPTS = 0 or
NUMDOUTS = 0.
Illegal if all
CMDFALALM.TM[0..2] = 0.
CMDFALALM.PR DevCtl
None (0)
Journal (1)
Low (2)
High (3)
Urgent (4)
Low (2)
Yes
Engineer
CEE
No
CMDFALALM.FL,
CMDFALALM.SV,
CMDFALALM.TM[0..
2], NUMDINPTS,
NUMDOUTS
Illegal if NUMDINPTS = 0 or
NUMDOUTS = 0.
Illegal if all
CMDFALALM.TM[0..2] = 0.
CMDFALALM.SV DevCtl
Yes
Engineer
CEE
No
CMDFALALM.FL,
CMDFALALM.PR,
CMDFALALM.TM[0..
2], NUMDINPTS,
NUMDOUTS
Illegal if NUMDINPTS = 0 or
NUMDOUTS = 0.
Illegal if all
CMDFALALM.TM[0..2] = 0.
Specific to
Block(s)
32
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
0 seconds Yes
Engineer
CEE
No
CMDDISALM.TM[0..
2], CMDFALALM.FL,
CMDFALALM.PR,
CMDFALALM.SV,
NUMDINPTS,
NUMDOUTS,
NUMSTATES
COMMAND
SCM
None (0)
Inactive (1)
Start (2)
Reset (3)
Interrupt (4)
Restart (5)
Hold (6)
Stop (7)
Abort (8)
Resume (9)
Active (10)
None (0)
No
Operator
CEE
No
STATE, MODE,
MODEATTR,
SSTEPLOCK,
ABORTLOCK,
CONTROLLOCK
Ability to change
COMMAND depends on the
current value of related
variables (listed above). See
the SCM State Transition
diagram for more details.
Timer
None (0)
Reset (1)
Stop (2)
Restart (3)
Start (4)
None (0)
No
Operator
CEE
No
STATE, RESETFL,
Start: Timer is started; PV
STOPFL, RESTARTFL, starts incrementing.
STARTFL
Stop: Timer is stopped; PV
freezes.
Reset: Timer is reset; PV is
set to 0, and RV is set to SP.
Restart: Timer continues
from the point it last
stopped.
Totalizer, Pulse
Input Totalizer
Totalizer Command
Allows the
operator to control
the operation of a
Totalizer.
None (0):
No effect on
Totalizer.
Start (1):
Starts the
Totalizer.
Stop (2):
Stops the
Totalizer
Reset (3):
Resets the
Totalizer to
RESETVAL.
None (0)
No
Other
Function
Block
CEE
No
CMDATTR
Enumeration
COMMAND
CMDFALALM.TM[ DevCtl
0..2]
33
Description
COMMAND
(cont)
REQFLAGARRAY,
REQNUMARRAY,
REQTEXTARRAY
Method that
Enumeration
specifies the type of
communication that
this block is
configured to
perform.
PLC5TypRead
CONFIGCODE
SCM, Handler,
RegCalc, Step,
Transition
Data Type
Configuration Code
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
See below
PLC5Typ
Read
Yes
Application
Developer
CEE
No
Range
Used if this block is to read data from a PLC-5 or a
CL5550 using the PLC-5 Typed Read Command.
PLC5TypWrite
CIPRead
CIPWrite
None (0)
UnknownError (1)
InternalErr (2)
ILLOwnHandle (3)
ILLHndlrHndl (4)
NextHNotNull (5)
ILLNNextTrns (6)
ConnInvObjs (7)
InvNextType (8)
NotImplNxTyp (9)
ILLExcConds (10)
ILLConds (11)
ILLOutputs (12)
IncObjects (13)
ILLNOutputs (14)
ILLNConds (15)
None (0)
No
View Only
Range
ILLGateLogic (16)
ActIgnored (32)
IncGateLogic (17)
EditIgnored (33)
NullGateUsed (18) TooFewCond (34)
OvlpGateInps (19)
MaxTmLtMinT (35)
SkipGateInps (20)
NegativeTime (36)
ILLInvkTObj (21)
EnbHdUnavail (37)
ILLInvkTCnfg (22)
DisHdUnavail (38)
ILLHndlrType (23)
EditNotPermt (39)
ILLHndlrSel (24)
IntGateError (40)
HndlrInstMis (25)
UserNullHnd (41)
ILLExcCProp (26)
UserEditHnd (42)
IncOpProp (27)
ILLObjAsHnd (43)
IncCondProp (28)
NonEditLostO (44)
IncInvkTProp (29)
NonOptGatLog (45)
IncPropagtn (30)
RefusedConn (46)
LostObjects (31)
ILLMultRef (47)
CEE
ConfHndErr (48)
CnfHndSurWrn (49)
ConfHndWarn (50)
ConfHndInfo (51)
ConfUnknCnfSt (52)
Spare53 (53)
Spare54 (54)
Spare55 (55)
Spare56 (56)
Spare57 (57)
Spare58 (58)
Spare59 (59)
Spare60 (60)
Spare61 (61)
No
Related
Parameters
Notes
Specific to
Block(s)
34
Parameter
Parameter
Specific to
Block(s)
CONFIGCODE[1..8 Auxcalc
]
Description
Data Type
Configuration Code
None (0)
Ok (1)
UnknownError (2)
ImplicitConv (3)
LossOfPrecsn (4)
UnexpctEnd (5)
UnexpctComm (6)
ColonWoQMar (7)
FctNotMltArg (8)
ClosParenExp (9)
OperandExp (10)
MissingArg (11)
OperatorExp (12)
ColonExp (13)
TypeMismatch (14)
TypeNotSupp (15)
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
CEE
No
Handler, RegCalc,
SCM, Step,
Transition
Configuration
Descriptor
String
Maximum of None
39 characters.
No
View Only
CEE
No
CONFIGDESC
[1..8]
Auxcalc
Configuration
Descriptor
String
Maximum of None
39 characters.
No
View Only
CEE
No
CONFIGSTS
Handler, RegCalc,
SCM, Step,
Transition
Ok (0)
Ok (0)
Information (1)
Warning (2)
SevereWarnin
g (3)
Fail (4)
Error (5)
SevereError
(6)
No
View Only
CEE
No
Ok (0)
Ok (0)
Information (1)
Warning (2)
SevereWarnin
g (3)
Fail (4)
Error (5)
SevereError
(6)
No
View Only
CEE
No
CONFIGSTS[1..8] Auxcalc
Notes
CONFIGDESC
Related
Parameters
35
Description
CONFIGURED
RM
CONFIRM[0..15]
Message
CONFIRMED[0..15 Message
]
Data Type
Range
Default
RM Configuration
Enumeration
Status. Value of
USER indicates the
module has been
configured to do
something different
than the
out-of-the-box
default.
Factory (0)
User (1)
Factory (0) No
View Only
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
Confirmation
Boolean
Off (0)
On (1)
Off (0)
Operator
CEE
No
Confirmed
Boolean
Off (0)
On (1)
View Only
CEE
No
CONNLISTSIZE
CM
Integer
CONTROLLOCK
SCM
CONTROLREQ
Sequential Control
DevCtl
All RegCtl Blocks: Module (SCM)
AutoMan, Fanout, Control Request
OvrdSel, PID, PIDFF,
PosProp,
PulseCount,
PulseLength,
RampSoak,
RemCas, RatioBias,
RegCalc, and
Switch.
Structure
COS
DIC
Change of State.
Boolean
Off (0)
On (1)
COS
[0..NumChans-1]
DIM
Change of State.
Boolean
Off (0)
On (1)
No
CPMSTATE
Access
Lock
Residence
View Only
CPMCOMMAND CPM
[0..numChans-1]
CPM
Config
Load
Active
Connector
Related
Parameters
Notes
Specific to
Block(s)
36
Parameter
No
Engineer
CEE
No
MODE, COMMAND
No
Other
Function
Block
CEE
No
GOPREQ,
Invalid if Control Module
MODEATTR, OPREQ, SCMOPT = None.
OPTYPE,
SCMASTEP[1..10],
SCMID, SCMOPT
Off (0)
No
View Only
CEE
No
Off (0)
No
View Only
CEE
No
Specific to
Block(s)
Description
Data Type
CPUCYCLEAVG
[0..39]
CEE
Greater-than,
or equal-to
zero
CPUCYCLEMAX
[0..39]
CEE
Greater-than
or equal-to
zero.
CPUFREEAVG
CEE, CPM
0.0 to 100.0
CPUFREEMIN
CPM
CPV
Real Number
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
No
View Only
CEE
No
No
View Only
CEE
No
No
View Only
CEE
No
CPUFREEMIN,
STATSRESET
0 to 100.0
No
View Only
CEE
No
CPUFREEAVG,
STATSRESET
Any Real
1.0
Number, NaN
not allowed.
Yes
Engineer
CEE
No
Parameter
37
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
CRCYCLEOVRN
[0..40]
CEE
16-Bit Real
Number
0 to 32767
No
View Only
CEE
No
Internal parameter
for system use only.
CSTS[1..8]
AuxCalc
Bad (0)
Uncertn (1)
Normal (2)
Manual (3)
Bad (0)
No
View Only
CEE
No
RegCalc
Expression result
Enumeration
status for each
PVSTS
result C [1] through C
[8].
No
View Only
CEE
No
CTLACTN
PID, PIDFF
Direct (0)
Reverse (1)
Reverse
(1)
Yes
Engineer
CEE
No
CTLEQN
EqA (0)
EqB (1)
EqC (2)
EqD (3)
EqE (4)
EqF (5)
EqG (6)
EqA (0)
Yes
Engineer /
Application
Developer
CEE
No
CTLINIT
Off (0)
On (1)
Off (0)
No
Other
Function
Block
CEE
No
CURPROFILEID
RampSoak
Current Profile ID
Integer
1 to 10
Operator No
CEE
No
CURSEGID
CURSEGID
RampSoak
1 to 60
No
CEE
No
CURPROFILEID
Enumeration
CTLEQN
Operator
C [1..8]
Notes
Specific to
Block(s)
38
Parameter
Parameter
Specific to
Block(s)
Description
CURSEGTYP
RampSoak
CUTOFF.LM
Data Type
Range
Default
Current Segment
Enumeration
Type (Ramp or Soak).
Ramp (0)
Soak (1)
Totalizer, Pulse
Input Totalizer,
Deadtime
Zero-Flow Cutoff
64-Bit Real
Limit in Engineering Number
Units - Allows the
user to specify a
cutoff limit such
that, when the value
of the RATE falls
below this limit, PV
remains constant (no
accumulation).
NaN, or
greater-than
or equal-to
0.0.
CV
CV[1..8]
CVEUHI
Residence
Active
Connector
Ramp (0) No
View Only
CEE
No
Deadtime Yes
: NaN
Totalizer,
Pulse
Input
Totalizer:
0.0
Totalizer,
Pulse Input
Totalizer:
Engineer
Deadtime:
Supervisor
CEE
No
NaN
No
Other
Function
Block
CEE
No
Fanout
NaN
Yes
Other
Function
Block
CEE
No
100.0
Yes
Engineer
CEE
No
Related
Parameters
Notes
CVEULO
Access
Lock
Greater-than
or equal-to
CVEULO
Config
Load
39
Description
CVEUHI[1..8]
Fanout
CVEULO
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Greater-than
or equal-to
CVEULO[1..8]
100.0
Yes
Engineer
CEE
No
CVEULO[1..8]
Less-than or
equal-to
CVEUHI
0.0
Yes
Engineer
CEE
No
CVEUHI
CVEULO[1..8]
Fanout
Less-than or
equal-to
CVEUHI[1..8]
0.0
Yes
Engineer
CEE
No
CVEUHI
CVINIT
RegCalc
NaN
No
Other
Function
Block
CEE
No
CVINITSRC
RegCalc
CVINIT (Calculated
Variable under
initialization
conditions) source
selector.
X1 (0)
Yes
Engineer
CEE
No
CVORFB
RegCalc
NaN
No
Other
Function
Block
CEE
No
Enumeration X1 to C8STS
REGCALCSELE (0 - 27)
CTOR
Specific to
Block(s)
40
Parameter
Parameter
Specific to
Block(s)
Description
CVORFBSRC
RegCalc
CVSRC
RegCalc
Data Type
Default
Config
Load
Access
Lock
Residence
Active
Connector
X1 (0)
Yes
Engineer
CEE
No
X1 (0)
Yes
Engineer
CEE
No
Engineer
CEE
CYCLEOPT
RampSoak
[1..NUMPROFILES
]
Cycle Option.
Integer
CYCLETIME
PosProp,
PidPosProp
D1
Deadtime
D2
Range
Single (0)
RoundRob
RoundRob (1) (1)
Cyclic (2)
0.020 to
1000.0
Yes
Supervisor
CEE
No
Real Number
0.0
Yes
Supervisor
CEE
No
Deadtime
0.0
Yes
Supervisor
CEE
No
DATATYPE
RSPNUMARRAY
DataType for
Enumeration
PCCC/CIP Access.
The type of data that
can be read from or
written to by a
remote device.
32-Bit Real
32-Bit
Number,
Real
8-Bit Signed Number
Integer,
16-Bit Signed
Integer,
32-Bit Signed
Integer,
Yes
Application
Developer
CEE
No
DEADBAND
Deadband Value
64-Bit Real
Defines the value of
the deadband for
Comparison
Functions.
Greater-than 0.005
or equal-to 0.
Yes
Engineer
CEE
No
DEADBAND1
EQ, NE
Greater-than 0.005
or equal-to 0.
Less-than or
equal-to
DEADBAND2
Yes
Engineer
CEE
No
Notes
DELAYTIME, C1
10.0
Related
Parameters
41
Description
Data Type
DEADBAND2
EQ, NE
DEBUG
All IO Channels,
SIFLAGARRCH,
SINUMARRCH,
SITEXTARRCH.
Integer
DELAYTABLE
[1..60]
Deadtime
Delay Table.
Real Number
DELAYTIME
2oo3, Delay,
Delay in seconds
MVote, Ondelay,
Offdelay, Watchdog
Integer
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Yes
Engineer
CEE
No
View Only
CEE
No
ViewOnly
CEE
No
Yes
Delay,
Ondelay,
Offdelay,
Watchdo
g:
2 seconds
2oo3,
MVote:
5 seconds
Engineer
CEE
No
Fixed
Delay:
Yes
Variable
Delay: No
No
Fixed (0)
Yes
Engineer
CEE
No
No
ViewOnly
CEE
No
Greater-than 0.01
or equal-to
DEADBAND1
0
0-8000
seconds
Deadtime
Greater-than 0.0
or equal-to 0.0
minutes.
DELAYTYPE
Deadtime
Delay Type
DELCV
PID, PIDFF
NaN
DELTATIME
Totalizer
Delta Time
Real
View Only
Related
Parameters
Notes
Specific to
Block(s)
42
Parameter
NUMLOC
DELAYTYPE
DELAYTIME (cont.)
Parameter
Specific to
Block(s)
Description
Data Type
Range
DESC
String
Length: 24
Null
characters
string
Exceptions:
40 characters
for Step,
Transition,
and Handler.
23 characters
for DevCtl.
DEV
DEVADDR
SIFLAGARRCH,
SINUMARRCH,
SITEXTARRCH.
DEVHIALM.DB
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Yes
Application
Developer
SR
No
NaN
No
ViewOnly
CEE
No
PV, SP
Yes
Application
Developer
CEE
No
Yes
Engineer/Ap CEE
plication
Developer
No
PV, SP,
DEVHIALM.DBU,
DEVHIALM.FL,
DEVHIALM.PR,
DEVHIALM.SV,
DEVHIALM.TM,
DEVHIALM.TP
Notes
43
DEVHIALM.DBU
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Percent (0)
EU (1)
Percent
(0)
Yes
Application
Developer
CEE
No
PV, SP,
DEVHIALM.DB,
DEVHIALM.FL,
DEVHIALM.PR,
DEVHIALM.SV,
DEVHIALM.TM,
DEVHIALM.TP
DEVHIALM.FL
Boolean
Off (0):
Off (0)
DEVHIALM.TP
has not been
exceeded (i.e.,
no Deviation
High alarm).
On (1):
DEVHIALM.TP
has been
exceeded.
No
ViewOnly
CEE
No
PV, SP,
DEVHIALM.DB,
DEVHIALM.DBU,
DEVHIALM.PR,
DEVHIALM.SV,
DEVHIALM.TM,
DEVHIALM.TP
DEVHIALM.PR
Enumeration
ALPRIOR
None (0)
Journal (1)
Low (2)
High (3)
Urgent (4)
Low (2)
Yes
Engineer
CEE
No
PV, SP,
DEVHIALM.DB,
DEVHIALM.DBU,
DEVHIALM.FL,
DEVHIALM.SV,
DEVHIALM.TM,
DEVHIALM.TP
DEVHIALM.SV
16-Bit Integer 0 to 15
Yes
Engineer
CEE
No
PV, SP,
DEVHIALM.DB,
DEVHIALM.DBU,
DEVHIALM.FL,
DEVHIALM.PR,
DEVHIALM.TM,
DEVHIALM.TP
Specific to
Block(s)
44
Parameter
Parameter
Specific to
Block(s)
DEVHIALM.TM
DEVHIALM.TP
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
0 to 60
Yes
Engineer
CEE
No
PV, SP,
DEVHIALM.DB,
DEVHIALM.DBU,
DEVHIALM.FL,
DEVHIALM.PR,
DEVHIALM.SV,
DEVHIALM.TP
If DEVHIALM.TM = 0, an
alarm will be generated as
soon as the deviation
exceeds the high deviation
trip point.
Individual alarm deadbands
are not individually
configurable. The ALMDB
that is configured is loaded
to the block, then the block
copies the ALMDB value to
all the xxALM.DB of all
analog alarms on the block.
This includes ALMDBU and
ALMTM - thus, all analog
alarms get the same three
values through a one-time
configuration entering of the
three values.
If desired, the individual
alarm parameters
(xxALM.DB, xxALM.DBU, and
xxALM.TM) may be modified
after the block is loaded.
The block load will always
set all individual alarm
parameters to the three
configured values.
Yes
Engineer
CEE
No
Description
Data Type
DEVLOALM.DB
Range
Default
Config
Load
Access
Lock
to 100.0 if
0.0
alarm
deadband
units
(DEVLOALM.D
BU) are
Percent
Greater-than
or equal to 0.0
if alarm
deadband
units
(DEVLOALM.D
BU) are
Engineering
Units (EUs).
Yes
Percent (0)
EU (1)
No
Percent
(0)
Residence
Active
Connector
Related
Parameters
Notes
Engineer/Ap CEE
plication
Developer
No
DEVLOALM.DBU
Application
Developer
No
DEVLOALM.DB
CEE
Specific to
Block(s)
46
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
DEVLOALM.FL
DEVLOALM.PR
DEVLOALM.SV
DEVLOALM.TM
Range
Config
Load
Access
Lock
Residence
Active
Connector
Off (0):
Off (0)
DEVLOALM.TP
has not been
exceeded,;
i.e., no
Deviation Low
alarm.
On (1):
DEVLOALM.TP
has been
exceeded.
No
ViewOnly
CEE
No
None (0)
Journal (1)
Low (2)
High (3)
Urgent (4)
Low (2)
Yes
Engineer
CEE
No
Yes
Engineer
CEE
No
DEVLOALM.FL,
DEVLOALM.PR
Yes
Engineer
CEE
No
DEVLOALM.TP
0 to 60
Default
Related
Parameters
Notes
If DEVLOALM.TM = 0, an
alarm will be generated as
soon as the deviation falls
below the low deviation trip
point.
Individual alarm deadbands
are not individually
configurable. The ALMDB
that is configured is loaded
to the block, then the block
copies the ALMDB value to
all the xxALM.DB of all
analog alarms on the block.
This includes ALMDBU and
ALMTM - thus, all analog
alarms get the same three
values through a one-time
configuration entering of the
three values.
If desired, the individual
alarm parameters
(xxALM.DB, xxALM.DBU, and
xxALM.TM) may be modified
after the block is loaded.
The block load will always
set all individual alarm
parameters to the three
configured values.
47
Description
Data Type
DEVLOALM.TP
DHCHANNEL
REQFLAGARRAY,
REQNUMARRAY,
REQTEXTARRAY:
when using PCCC
and COMMAND is
either:
PLC5TypRead or
PLC5TypWrite
and the target is on
DH+. This
parameter is
enabled only when
DHFL is True.
DHDESTLINK
REQFLAGARRAY,
REQNUMARRAY,
REQTEXTARRAY:
when using PCCC
and COMMAND is
either:
PLC5TypRead or
PLC5TypWrite
and the target is on
DH+. This
parameter is
enabled only when
DHFL is True.
DHFL
REQFLAGARRAY,
REQNUMARRAY,
REQTEXTARRAY:
when using PCCC
and COMMAND is
either PLC5TypRead
or PLC5TypWrite
Range
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Yes
Engineer
CEE
No
A,B
Yes
Application
Developer
CEE
No
Yes
Application
Developer
CEE
No
Off(0)
Yes
Application
Developer
CEE
No
Off(0)
On(1)
Default
Notes
Specific to
Block(s)
48
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Default
Config
Load
Access
Lock
Residence
Active
Connector
DHNODE
REQFLAGARRAY,
REQNUMARRAY,
REQTEXTARRAY:
when using PCCC.
I.e., when the
COMMAND is one
of the following:
PLC5TypRead
PLC5TypWrite
And the target is on
DH+. This
parameter is
enabled only when
DHFL is True.
0 to 77 octal.
0 octal
Yes
Application
Developer
CEE
No
DHSRCLINK
REQFLAGARRAY,
REQNUMARRAY,
REQTEXTARRAY:
when using PCCC.
I.e., when the
COMMAND is one
of the following:
PLC5TypRead
PLC5TypWrite
And the target is on
DH+. This
parameter is
enabled only when
DHFL is True.
Yes
Application
Developer
CEE
No
DI [1..4]
DevCtl
Boolean
Off (0)
On (1)
Off (0)
No
ViewOnly
CEE
Yes, Inside
Input
DIGFILTER
1797-IBN16
Enumeration
.25 ms Delay
.5 ms Delay
1 ms Delay
2 ms Delay
4 ms Delay
8 ms Delay
16 ms Delay
32 ms Delay
.25 ms
Delay
Yes
Application
Developer
CEE
No
Related
Parameters
Notes
DIPVMAP [0..15],
GPVAUTO,
NUMDINPTS,
NUMSTATES,
PVAUTO
Range
49
Description
DIGFILTER
[0..numChans-1]
AIM
DIPVMAP [0..15]
Data Type
Range
Default
If [0],
minimum to
20100 ms
If not [0],
minimum to
100 ms
DevCtl
Actual State
Definitions.
String
DISCREP
2oo3, MVote
Discrepancy output
value.
Boolean
DISPPOS
RM
Display position.
Enumeration
Identifies the
Chassis A vs.
Chassis B
workstation display
field groups to which
the remainder of this
objects data should
be applied.
ViewOnly
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
DISQSECCMD
RM
Disqualify
Secondary
Command
True (0)
False (1)
Operator
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
Boolean
Access
Lock
Residence
Active
Connector
0
Yes
(indicates
digital
filtering is
off)
CEE
No
Bad (0)
InBet (1)
State0 (4)
State1 (5)
State2 (6)
Bad (0)
Yes
Engineer
CEE
No
Off (0)
On (1)
Off (0)
No
ViewOnly
CEE
No
True (0)
Config
Load
No
Related
Parameters
Notes
DIGFILTER [0..5] is accessible
by the Application Developer
on the Configuration Form
only.
DI [1..4], GPVAUTO,
NUMDINPTS,
NUMSTATES,
PVAUTO
Specific to
Block(s)
50
Parameter
Parameter
Specific to
Block(s)
Description
DLCNBSLOT
IOM
DO [1..3]
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Yes
Application
Developer
SR
No
IOMSLOT,
ULCNBMAC
DevCtl
Digital Output
Values
Boolean
Off (0)
On (1)
Off (0)
No
ViewOnly
CEE
No
GOPFINAL,
NUMDOUTS,
OPDOMAP [0..3]
[1..3], OPFINAL
DOMSO
DOC
Output value
Boolean
Off (0)
On (1)
Off (0)
No
ViewOnly
CEE
No
DOMSO
[0..numChans-1]
DOM
Output value
Boolean
Off (0)
On (1)
Off (0)
No
ViewOnly
CEE
No
DONEFL
All Exchange
Library Request
Array function
blocks:
REQFLAGARRAY,
REQNUMARRAY,
REQTEXTARRAY
Flag indicating a
Boolean
successful response
was received for the
last request sent by
this request block.
Off(0)
On(1)
Off(0)
No
View Only
CEE
No
DOTYPE
DOC
Digital Output or
Pulse Width
Null (0)
So (1)
OnPulse (2)
OffPulse (3)
So (1)
Yes
Application
Developer
CEE
No
DPV
0.0
Yes
Deadtime:
Supervisor
LeadLag:
Engineer
CEE
No
DRIVERNAME
CPM, RM
Null
String
No
Engineer
SR
No
Modulation
output type
String
Range
Length: 255
characters
ABORTALM.PR
Default
Network Driver
Name
Data Type
51
Description
Data Type
EDGEDETECT
EDGEDETECT
[0..7]
ELOF
[0..numChans-1]
DIM (only
Enable Loss of
configurable on the Power
8-channel, 120
VAC, Diagnostic
module)
Boolean
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Rising Edge
Rising
(0):
Edge (0)
Signal
transitions
from low
voltage to
high voltage
will cause an
Off-to-On
transition in
the ASIC
functions of
the module.
Falling Edge
(1):
Signal
transitions
from high
voltage to low
voltage will
cause an
Off-to-On
transition in
the ASIC
functions of
the module.
Yes
View Only
CEE
No
Yes
Application
Developer
CEE
No
RisingEdge mode
refers to
screw-terminal-input
transitions from low
voltages to high
voltage will cause an
Off-to-On transition
in the ASIC functions
of the module.
FallingEdge mode
refers to
screw-terminal-input
transitions from high
voltages to-low
voltage will cause an
Off-to-On transition
in the ASIC functions
of the module.
Off (0)
On (1)
Yes
Application
Developer
CEE
No
NOFIELDPWR
[0..numChans-1]
Off (0)
Related
Parameters
Notes
Specific to
Block(s)
52
Parameter
Parameter
Specific to
Block(s)
Description
ENBHANDLER
[1..8]
SCM
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Off (0)
On (1)
Off (0)
No
Engineer
CEE
No
TYPE
Enable No Load
Boolean
Off (0)
On (1)
Off (0)
Yes
Application
Developer
CEE
No
NOLOAD
ENOLOAD is only
configurable on diagnostic
modules.
ENTERSBYCMD
Enter Standby
Command
Boolean
True (0)
False (1)
True (0)
No
Operator
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform .
No
Off (0)
On (1)
Off (0)
Yes
Engineer
No
RM
ENUMBOOLMAP TypeConvert
[0..63]
Data Type
CEE
Description
Data Type
ERRCODE
ERRCODE
SIFLAGARRCH,
SINUMARRCH,
SITEXTARRCH.
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
See below
Null
String
No
ViewOnly
CEE
No
ERRFL
Range
Length: 8 characters
Possible String values:
Ch_Incty:
Md_Incty:
The SIM function block is InActive, so the Channel block cannot obtain new array data.
CEE_Idle:
ChCfgErr:
A Channel block configuration error exists. Check that the Number of Elements configured is
appropriate for the Starting Index of the device. Or for the Serial Interface Text Array Channel
function block, that the configured NSTRING and STRLEN do not exceed 64 characters.
No_SIMFB:
The Channel block cannot locate its assigned SIM function block. Check that the SIM function
block is loaded to the CEE.
No_Data:
ERRCODE is setNo_Data when the Channel block is activated. This value should only be seen
for a short period of time before ERRCODE is set to either a good or bad value.
No_Conn:
The Channel block cannot obtain array data because a proper connection does not exist between
the CPM and SIM.
IO_Comm:
DataCond:
The Channel block has received a Data Conditioner it does not understand. A Data Conditioner is
an internal value sent by the FTA that indicates how the 64 bytes of data should be interpreted.
REQFLAGARRAY,
REQNUMARRAY,
REQTEXTARRAY
No
View Only
CEE
No
Notes
Specific to
Block(s)
54
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
ERRCODE [0..31]
Serial Interface
IOM
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
See below
Null
String
No
ViewOnly
CEE
No
ERRFL [0..31]
BADPVFL, ERRCODE,
INITREQ
Notes
Range
Length: 8 characters
Possible String values:
ERRFL
NO_CONF:
CFG_LOAD:
ARR_INIT:
CONFIG:
FTA COMM:
#ELEMNT:
SIFLAGARRCH,
SINUMARRCH,
SITEXTARRCH
No
ViewOnly
CEE
No
All Exchange
Library Request
Array function
blocks:
REQFLAGARRAY,
REQNUMARRAY,
REQTEXTARRAY
Flat indicating an
Boolean
error response was
received for the last
request sent by this
request block.
Off(0)
On(1)
No
View Only
CEE
No
Off(0)
55
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
ERRFL [0..31]
Serial Interface
IOM
Off (0)
On (1)
Off (0)
No
ViewOnly
CEE
No
ERRCODE [0..31]
ERRINFO
REQFLAGARRAY,
REQNUMARRAY,
REQTEXTARRAY
Extended Error
Status on the last
request operation.
No
ViewOnly
CEE
No
ERRORCODE
RM
Maximum of 6
characters
No
ViewOnly
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
ERRORDBL
PosProp,
PidPosProp (when
PV > SP)
Real
Yes
Supervisor
CEE
No
ERRORDBR
PosProp,
PidPosProp (when
PV < SP)
Real
Yes
Supervisor
CEE
No
ERRORMSGIDX
RM
0 to 65535
No
ViewOnly
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
32-Bit Integer
No
Notes
56
Parameter
Parameter
Specific to
Block(s)
Description
ESWFL.CAS
ESWFL.MAN
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Off (0)
On (1)
Off (0)
No
Other
Function
Block
CEE
No
ESWENB, ESWPERM
Off (0)
On (1)
Off (0)
No
Other
Function
Block
CEE
No
ESWENB, ESWPERM
ESWPERM
External Mode
Enumeration
Switch Permissive - MODEPERM
Indicates if external
mode switching is
permitted.
Permit (0):
Not
External mode Permitted
switching is (1)
permitted.
Not Permitted
(1): External
mode
switching is
not permitted.
No
ESWENB,
ESWFL.AUTO,
ESWFL.BCAS,
ESWFL.CAS,
ESWFL.MAN
ETRANS
DOM
Off (0)
On (1)
Off (0)
Yes
Application
Developer
CEE
No
EUDESC
Length: 15
characters
Null
String
Yes
Application
Developer
SR
No
DESC, KEYWORD
Boolean
Notes
57
Specific to
Block(s)
Description
EVALTRANS
[1..10] [1..10]
SCM
EVALTRANSN
[1..10] [1..10]
SCM
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Null
String
No
ViewOnly
CEE
No
ACTIVELOC.STEP
EVALTRANS [i] [j] contains
[1..10], EVALTRANSN the name (eg.
[1..10] [1..10]
SCMName.TransitionName)
of the currently evaluated
transition of branch j of
thread i.
EVALTRANS [1..10] [1..10] is
a BlockId parameter and not
supported in expressions. Its
Integer-32 Partner Parameter
EVALTRANSN [1..10] [1..10]
can be used in Transition
Condition expressions and
Step Output expressions.
Null
String
No
ViewOnly
CEE
No
ACTIVELOC.STEP
[1..10], EVALTRANS
[1..10] [1..10]
Off (0)
No
ViewOnly
CEE
No
VERIFYLOST
[0..numChans-1]
EVENTFL
RampSoak
[1..NUMEVENTS]
RampSoak Event
Flags
Boolean
Off (0)
On (1)
EVENTBGNTIME RampSoak
[1..NUMPROFILES
]
[1..NUMEVENTS]
Real
NaN, or
0.0
Greater-than
or equal-to 0.0
Yes
Supervisor
CEE
No
EVENTENDTIME RampSoak
[1..NUMPROFILES
]
[1..NUMEVENTS]
Real
NaN, or
0.0
Greater-than
or equal-to 0.0
Yes
Supervisor
CEE
No
EVENTSEGID
RampSoak
[1..NUMPROFILES
]
[1..NUMEVENTS]
Event Segment ID
Integer
0 to 100
Yes
Supervisor
CEE
No
EVERIFY
[0..numChans-1]
Off (0)
On (1)
Off (0)
Yes
Application
Developer
CEE
No
Notes
58
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
EWIREOFF
[0..numChans-1]
DIM (configurable
only on Diagnostic
modules)
Enable Wire-Off
Diagnostic
Boolean
Wire-Off
Diagnostic
disabled (0)
Wire-Off
Diagnostic
enabled (1)
EXCMODEOPT
SCM
Execution Mode
Option
EXECCODE
Handler, SCM,
Step, Transition.
EXECCODE [1..8]
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Wire-Off Yes
Diagnosti
c disabled
(0)
Application
Developer
CEE
No
WIREOFF
[0..numChans-1]
Auto (1)
No
Engineer
CEE
No
Execution Code
No
ViewOnly
CEE
No
EXECDESC, EXECSTS
AuxCalc, RegCalc
Execution Code
None (0)
Enumeration None (0)
AUXCALCEXE ConfigError (1)
CCODE
ExprEvalFail
(2)
StoreFailed (3)
CommError (4)
StoreWarning
(5)
InternalErr (6)
CtrlReqErr (7)
DataTypeErr
(8)
StorePending
(9)
No
ViewOnly
CEE
No
EXECDESC [1..8],
EXECSTS [1..8]
EXECCOUNT
All IO Channels,
PWM Channel,
SIFLAGARRCH,
SINUMARRCH,
SITEXTARRCH
Execution Count
Integer
View Only
CEE
EXECDES
Handler, SCM,
Step, Transition,
AuxCalc, RegCalc
Execution Code
Descriptor
String
ViewOnly
CEE
No
EXECSTS, EXECCODE
Maximum of None
39 characters
No
Notes
When EXCMODEOPT is
Auto, the SCMMODE is
automatically set to Auto
whenever the active handler
changes.
59
Specific to
Block(s)
Description
Data Type
Range
EXECDESC [1..8]
Auxcalc
Execution Code
Descriptor
String
Maximum of None
39 characters.
EXECSTATE
Execution state of
the block and its
components.
EXECSTS
SCM, Handler,
Step, Transition,
AuxCalc, RegCalc.
Execution Status
Enumeration Ok (0)
Ok (0)
CSCOEXECST Bypass (1)
S
Info (2)
Warning (3)
Fail (4)
Error (5)
OkPaused (6)
BypassPaused
(7)
InfoPaused (8)
WarnPaused
(9)
FailPaused
(10)
ErrorPaused
(11)
TypeConvert
Ok (0)
Warning (1)
Error (2)
Default
Inactive
(0)
Ok (0)
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
No
ViewOnly
CEE
No
EXECSTS [1..8],
EXECCODE [1..8]
No
Supervisor
CEE
No
CEESTATE, STATE
(for SCM)
No
ViewOnly
CEE
No
No
ViewOnly
CEE
No
60
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Default
Config
Load
Access
Lock
Residence
Active
Connector
EXECSTS [1..8]
Auxcalc
Execution Status
Enumeration Ok (0)
AUXCALCEXE Bypass (1)
CSTS
Info (2)
Warning (3)
Fail (4)
Error (5)
Ok (0)
No
ViewOnly
CEE
No
EXPR [1..8]
AuxCalc, RegCalc
Calculator
String
Expressions Each
may contain a
user-specified
logical, arithmetic or
conditional
expression of up to
eighty characters.
Length: up to Null
255
string
characters.
(This will be
unlimited in a
future
release.)
Yes
Engineer
CEE
No
Expression
Pseudo-code
String
Maximum of
220
characters.
Yes
Application
Developer
CEE
No
EXTRAPULSE
Boolean
Off (0)
On (1)
Off (0)
Yes
Supervisor
CEE
No
0.0
No
View Only
CEE
No
PosProp,
PidPosProp
Range
Related
Parameters
Notes
EXTRAPULSETM PosProp,
PidPosProp
EZCROSS
[0..numChans-1]
DOM
Enable Loss of
Power
Boolean
Off (0)
On (1)
Off (0)
Yes
Application
Developer
CEE
No
NOFIELDPWR
[0..numChans-1]
FAILALM.FL
SCM
Sequential Control
Module (SCM) Fail
Alarm Flag
Boolean
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
EXECSTS
FAILALM.PR
SCM
Sequential Control
Module (SCM) Fail
Alarm Priority
Enumeration
ALPRIOR
None (0)
Journal (1)
Low (2)
High (3)
Urgent (4)
Low (2)
Yes
Engineer
CEE
No
FAILALM.FL,
FAILALM.SV
FAILALM.SV
SCM
Sequential Control
Module (SCM) Fail
Alarm Severity
16-Bit Integer 0 to 15
Yes
Engineer
CEE
No
FAILALM.FL,
FAILALM.PR
61
Specific to
Block(s)
Description
Data Type
Range
Default
FAILSTATE
[0..numChans-1]
DOM
Boolean
Use Safe
State (0)
Hold Last
Output State
(1)
FAULTDELAY
1797-OB4D
Fault Detection
Delay Time
Enumeration
FAULTENB [ ]
1797-OB4D
Enable Fault
Detection
FAULTRESET
1797-OB4D
Fault Reset
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Application
Developer
CEE
No
SAFESTATE
[0..numChans-1]
11 ms
12 ms
14 ms
18 ms
26 ms
42 ms
11 ms
Yes
Application
Developer
CEE
No
FAULTENB [ ],
LATCHENB
Boolean
Off(0)
On(1)
Off(0)
Yes
Application
Developer
CEE
No
FAULTRESET,
LATCHENB
Boolean
Off(0)
On(1)
Off(0)
Yes
Engineer
CEE
No
FAULTENB [ ],
LATCHENB
62
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
FAULTVALUE
[0..numChans-1]
AOM
FBORSTS
FBTYPE
PID
Enumeration
PTORST
Range
NotCon (0)
Sel (1)
NotSel (2)
Default
Access
Lock
Residence
Active
Connector
Related
Parameters
50 for
Yes
modules
operating
in voltage
mode
only.
-25 for
modules
operating
in current
mode (or
current
and
voltage
modes).
Application
Developer
CEE
No
SAFESTATE
-25 is the recommended Safe
[0..numChans-1] (for Value for current mode.
DOM)
50 is the recommended Safe
Value for voltage mode.
Note that the non-isolated
(high-density) AOM allows
channels to be configured for
use in either voltage or
current mode. Since only
one default value can be
specified (-25), it is
recommended that the user
change the value to 50 (or
other safe value) if using
voltage mode.
NotCon
(0)
No
View Only
No
View Only
Null
Null
PID and all
Regulatory
Control
function
blocks
DataAcq
and all
Auxiliary
function
blocks
DigComp
DisDev
All Logic
function
blocks
All Utility
function
blocks
Sco
Config
Load
No
CEE
Notes
No
63
Specific to
Block(s)
Description
FETCHMODE
All IO Channels,
PWM Channel,
SIFLAGARRCH,
SINUMARRCH,
SITEXTARRCH
FF
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Off (0)
No
Engineer
CEE
No
PIDFF
NaN
FFCONN
PIDFF
FFOPT
PIDFF
Engineer
FFSTS
PIDFF
View Only
FILENUM
REQFLAGARRAY,
REQNUMARRAY,
REQTEXTARRAY
Maximum of Null
40 characters String
FILTERHDR
[0..numChans-1]
DIM
Maximum of Null
20 characters String
Related
Parameters
SIFL, PV, SP
Application
Developer
Integer
String
Yes
Application
Developer
CEE
View Only
SR
Notes
64
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
FILTEROFF
DIM
[0..numChans / 8]
DC Modules:
Enumeration
of
FILTERONOFF
AC Modules:
Enumeration
of
ACFILTERONO
FF
FILTEROFFON:
No Delay (0)
1 ms Delay (1)
2 ms Delay (2)
9 ms Delay (9)
18 ms Delay
(18)
ACFILTEROFFO
N:
9 ms Delay (9)
18 ms Delay
(18)
FILTERON
DIM
[0..numChans / 8]
FILTEROFFON:
No Delay (0)
1ms Delay (1)
2 ms Delay (2)
ACFILTEROFFO
N:
1 ms Delay (1)
2 ms Delay (2)
FREEMEM
CPM
FREEMEMINK
CPM
Amount of free
32-Bit Integer 0 to 4194304
memory in CEE user
Kbytes
memory pool.
FREEZETIME
All IO Channels,
PWM Channel,
SIFLAGARRCH,
SINUMARRCH,
SITEXTARRCH
Maximum Freeze
Time
Real
Access
Lock
Residence
Active
Connector
Related
Parameters
DC
Yes
Modules:
No Delay
(0)
AC
Modules:
9 ms
Delay (9)
Application
Developer
CEE
No
FILTERON
[0..numChans / 8]
DC
Yes
Modules:
No Delay
(0)
AC
Modules:
1 ms
Delay (1)
Application
Developer
CEE
No
FILTEROFF
[0..numChans / 8]
No
View Only
CEE
No
TOTALMEM,
USEDMEM,
MAXFREEBLKSZ
No
View Only
CEE
No
TOTALMEMINK,
USEDMEMINK,
MAXFREEINK
Config
Load
Notes
View Only
65
Specific to
Block(s)
FREQPERIOD
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
25ms (0)
50ms (1)
100ms (2)
200ms (3)
500ms (4)
1000ms (5)
2000ms (6)
1000ms
(5)
Yes
View Only
CEE
No
FREQPERIOD
[0..7]
Frequency
Enumeration
Integration Period
Period at which
Module calculates
frequency.
25ms (0)
50ms (1)
100ms (2)
200ms (3)
500ms (4)
1000ms (5)
2000ms (6)
1000ms
(5)
Yes
Application
Developer
CEE
No
FTAAOVRNFL
Serial Interface
IOM
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
FTABOVRNFL
FTAASTS
Serial Interface
IOM
FTA A Status
Enumeration
Provides the current
status of the FTA.
FtaNotPresnt FtaNotPre No
(0)
snt (0)
TfaOk (1)
FtaConfig (2)
FtaSoftFail (3)
View Only
CEE
No
FTABSTS
FTABOVRNFL
Serial Interface
IOM
Off (0)
On (1)
No
View Only
CEE
No
FTAAOVRNFL
FTABSTS
Serial Interface
IOM
FTA B Status
Enumeration
Provides the current
status of the FTA.
FtaNotPresnt FtaNotPre No
(0)
snt (0)
TfaOk (1)
FtaConfig (2)
FtaSoftFail (3)
View Only
CEE
No
FTAASTS
Sel, Selreal
G Selector input
value
Off (0)
On (1)
Engineer
CEE
No
Boolean
Off (0)
Off (0)
Yes
Related
Parameters
Notes
PV in EU = (C1/C2) *
TIMEBASE *
pulses/(Frequency
Integration Period)
When an Overrun is
indicated, some requested
writes are not being
completed. Check the
application to see if the
quantity or rate of writes can
be reduced, or if possible,
split the load between two
FTAs, so that no overruns
occur.
When an Overrun is
indicated, some requested
writes are not being
completed. Check the
application to see if the
quantity or rate of writes can
be reduced, or if possible,
split the load between two
FTAs, so that no overruns
occur.
66
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
G [1..4].ALGID
Transition
Gate Algorithm ID
G [1].ALGID:
Secondary Gate (S)
Type
G [2..4].ALGID:
Primary Gate (Px)
Type
Enumeration
CSCOALGID
None (0)
On (1)
Off (2)
Connect (3)
Not (4)
Or (5)
Nor (6)
And (7)
Nand (8)
Xor (9)
None (0)
Yes
Application
Developer
CEE
No
G
Transition
[1..4].FIRSTCOND
No
ViewOnly
CEE
No
G
Transition
[1..4].NUMINPTS
Gate Number of
Inputs
32-Bit Integer 0 to 10
Yes
Application
Developer
CEE
No
G [1..4].SO
Transition
Boolean
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
GAINHILM
Any value
greater than
GAINLOLM.
240.00
Yes
Engineer
CEE
No
GAINLOLM
Yes
Engineer
CEE
No
GAINOPT
PID, PIDFF
Gain Option.
Specifies how the
PID gain should be
calculated.
Enumeration
GAINOPT
Yes
Engineer/Ap CEE
plication
Developer
No
GAPHILM
PID, PIDFF
64-Bit Real
Number
0.00
Yes
Engineer
CEE
No
GAPLOLM
PID, PIDFF
64-Bit Real
Number
0.00
Yes
Engineer
CEE
No
67
Specific to
Block(s)
Description
GENSTATE
RM
View Only
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
GENSTATEA
RM
View Only
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
GOP
DevCtl
See below.
Other
Function
Block
CEE
Active (2):
Data Type
Range
Default
S0 (4)
Config
Load
No
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
No
GOPFINAL, GOPREQ,
MODEATTR,
NUMDOUTS,
NUMSTATES, OP,
OPFINAL, OPREQ,
SAFEOP,
SAFEREDTAG
Access is illegal if
NUMDOUTS = 0.
S2 is illegal if NUMSTATES =
2.
Once SAFEOP is configured,
GOP always defaults to
SAFEOP.
Active is illegal if
NUMSTATES = 3.
Range
Not configured SafeOP for two state device (i.e., if
SafeOp = State 0, Active will set OP to state 1).
Safe (3):
S0 (4):
S1 (5):
S2 (6):
GOPFINAL
DevCtl
S0 (4)
S1 (5)
S2 (6)
S0 (4)
No
ViewOnly
CEE
No
GOP, MODEATTR,
NUMDOUTS,
NUMSTATES, OP,
OPDOMAP [0..3]
[1..3], OPFINAL
Access is illegal, if
NUMDOUTS = 0.
GOPREQ
DevCtl
Generic Requested
Output Value
(OPREQ)
Null (0)
Active (2)
Safe (3)
S0 (4)
S1 (5)
S2 (6)
Null (0)
No
Other
Function
Block
CEE
No
CONTROLREQ, GOP,
OPREQ, OPTYPE,
NUMSTATES, OP,
SCMOPT
S2 is illegal if NUMSTATES =
2.
GOPREQ is illegal if
CONTROLOPT = None.
Enumeration
GENSTATE
68
Parameter
Parameter
Specific to
Block(s)
Description
GOPSCADA
DevCtl
GPV
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
State_0
(0)
No
Operator
CEE
No
GOP, OP
DevCtl
Generic Process
Variable (PV)
Enumeration
GENSTATE
Null (0)
Inbet (1)
S0 (4)
S1 (5)
S2 (6)
Null (0)
No
View Only,
Other
Function
Block (see
Notes)
CEE
No
DIPVMAP [0..15],
GPVAUTO,
NUMDINPTS,
NUMSTATES, PV,
PVAUTO, PVSOURCE,
PVSRCOPT
Access is illegal, if
NUMDINPTS = 0.
S2 is illegal, if
NUMSTATES = 2.
InBet is illegal, if DIPVMAP
is not assigned to InBet.
Access Lock is View Only if
PVSOURCE = AUTO, MAN or
TRACK; or if PVSRCOPT is
ONLYAUTO.
Access Lock is Other
Function Block if PVSOURCE
= SUB.
GPVAUTO
DevCtl
Generic PVAUTO
Enumeration
GENSTATE
Null (0)
Inbet (1)
S0 (4)
S1 (5)
S2 (6)
Null (0)
No
View Only
CEE
No
DIPVMAP [0..15],
GPV, NUMDINPTS,
NUMSTATES, PV,
PVAUTO, PVSOURCE
Access is illegal, if
NUMDINPTS = 0.
S2 is illegal, if
NUMSTATES = 2.
InBet is illegal, if DIPVMAP
is not assigned to InBet.
HANDLER
Step, Transition,
Handler
BlockId
Null
String
No
View Only
CEE
No
NUM
HANDLERREF
Handler, Step,
Transition
Internal parameter
for system use only.
HIALM.PR
RegCtl, DevCtl,
DataAcq, SCM,
Flag
Highest Alarm
Enumeration
Priority - Indicates ALPRIOR
the priority of the
highest-level alarm
that currently exists
for the function
block.
None (0)
No
View Only
CEE
No
HIALM.TYPE,
HIALM.SV
None (0)
Journal (1)
Low (2)
High (3)
Urgent (4)
Notes
69
Specific to
Block(s)
Description
HIALM.TYPE
RegCtl, DataAcq,
SCM
Highest Alarm
Enumeration See below.
Detected - This
DACALMTYPE
variable is used by
the system to ensure
None (0):
that, when alarm
conditions exist for a
function block at the
NegROC (1):
same time, the most
PosROC (2):
important or
highest-level alarm
PvLo (3):
condition will
appear on both
PvHi (4):
detail and group
PvLoLo (5):
displays.
PvHiHi (6):
HIALM.TYPE
Data Type
Range
BadPV (7):
DevCtl
Flag
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
None (0)
No
View Only
CEE
No
HIALM.PR,
HIALM.SV
No
CEE
HIALM.PR,
HIALM.SV
No
CEE
OFFNRMALM.FL,
OFFNRMALM.PR,
OFFNRMALM.SV,
INALM
Range
No alarm exists
(Lowest-level alarm condition)
Negative Rate-of-Change alarm
Positive Rate-of-Change alarm
PV Low alarm
PV High alarm
PV Low Low alarm
PV High High alarm
Bad PV alarm
Highest Alarm
Enumeration See below.
None (0) No
View Only
Detected - This
DEVHIALM
variable is used by
Range
the system to ensure
None
(0)
No
alarm
that, when alarm
conditions exist for a
BadPv (1)
Bad PV alarm
function block at the
OffNormal
(2)
Off Normal alarm
same time, the most
important or
CmdDisagree (3)
Command Disagree alarm
highest-level alarm
condition will
CommandFail (4)
Command Fail alarm
appear on both
UnCommanded (5) Uncommanded alarm
detail and group
displays.
SafetyIlock (6)
Safety Interlock alarm
Oride0Ilock (7)
Oride1Ilock (8)
Oride2Ilock (9)
Highest Alarm
Enumeration
Detected - Ensures HIALMFlag
that when alarm
conditions exist for a
function block at the
same time, the most
important or
highest-level alarm
condition will
appear on both
detail and group
displays.
None (0)
None (0)
OffNormal (1)
No
Engineer
Notes
70
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
HIGHENG
[0..numChans-1]
AIM, AOM
This parameter is
configurable only
on the AIM.
HIGHSIGNAL
[0..numChans-1]
AIM, AOM
High Signal
64-Bit Real
Number
HISTDESC
SCM
History Parameter
Descriptor
HOLDALM.FL
SCM
HOLDALM.PR
SCM
HOLDALM.SV
SCM
HOLDCMD
RampSoak
Range
Default
Config
Load
NaN,
greater-than
LOWENG
100.0
Residence
Active
Connector
Related
Parameters
CEE
No
LOWENG
[0..numChans-1]
See
Notes.
No
View Only
CEE
No
SIPTYPE
[0..numChans-1],
INPUTRANGE
[0..numChans-1],
LOWSIGNAL
[0..numChans-1]
String
Maximum of Null
63 characters. String
Yes
Engineer
CEE
No
NUMHISTPARMS
Boolean
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
HOLDALM.PR,
When this is On, it indicates
HOLDALM.SV, STATE that the Hold Alarm
condition (SCMSTATE has
transitioned to Hold or
Holding) exists.
None (0)
Journal (1)
Low (2)
High (3)
Urgent (4)
Low (2)
Yes
Engineer
CEE
No
HOLDALM.FL,
HOLDALM.SV
Yes
Engineer
CEE
No
HOLDALM.FL,
HOLDALM.PR
Off (0)
No
Other
Function
Block
CEE
No
Off (0)
On (1)
Access
Lock
Notes
71
Specific to
Block(s)
Description
Data Type
HOLDOPT
DevCtl,
All RegCtl Blocks:
AutoMan, Fanout,
OvrdSel, PID, PIDFF,
PosProp,
PulseCount,
PulseLength,
RampSoak,
RemCas, RatioBias,
RegCalc, and
Switch.
HOLDRATE
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Yes
Engineer
CEE
No
Yes
Engineer
CEE
No
HOLDOPT
72
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
HOLDVAL
OPEXLOLM to NaN
OPEXHILM,
when
HOLDOPT =
Fixed Output
(OP)
SPLOLM to
SPHILM,
when
HOLDOPT =
Fixed Set
Point (SP) or
Ramped Set
Point (SP)
(NaN, 0.0, or
positive and
negative real
numbers)
Yes
Engineer
CEE
No
HOLDOPT
HWFAULT
DIC
Hardware fault
detected.
Boolean
No Fault
No Fault No
Detected (0) Detected
Fault Detected (0)
(1)
View Only
CEE
No
HWFAULT
[0..numChans-1]
DIM
Hardware fault
detected.
Boolean
No Fault
No Fault No
Detected (0) Detected
Fault Detected (0)
(1)
View Only
CEE
No
IC.BYPPERM
Step
Step Interrupt
Condition Bypass
Permit.
Boolean
Off (0)
On (1)
IC.BYPREQ
Step
Step Interrupt
Condition Bypass
Request.
Off (0)
Yes
Engineer
CEE
No
IC.BYPREQ, IC.FL
None (2)
No
Operator
CEE
No
IC.BYPPERM, IC.FL
73
Specific to
Block(s)
Description
Data Type
IC.CONFIGCODE
Step
Common Interrupt
Condition
Configuration Code
None (0)
Ok (1)
UnknownErr (2)
ImplicitConv (3)
LossOfPrecsn (4)
UnexpctEnd (5)
UnexpctComma (6)
ColonWoQMark (7)
FctNotMltArg (8)
ClosParenExp (9)
OperandExp (10)
MissingArg (11)
OperatorExp (12)
ColonExp (13)
TypeMismatch (14)
TypeNotSupp (15)
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
None (0)
No
View Only
CEE
No
Range
SyntaxError (16)
IntegerExp (32)
ExprTooCmplx (17)
DoubleExp (33)
NotEPcodeMe (18) MissedImpl (34)
NotEDataStak (19)
UnicodeConv (35)
UnsuppFeatur (20)
ConstExprRem (36)
ExprTooLong (21)
DuplExprRem (37)
DivideByZero (22)
ExtUse38 (38)
UnknownToken (23) ExtUse39 (39)
UnexpTokenOS (24) ExtUse40 (40)
UnknownFunc (25)
ExtUse41 (41)
UnexpOCExpr2 (26) ExtUse42 (42)
UnexpOCExpr3 (27) ExtUse43 (43)
ZeroArgument (28) ExtUse44 (44)
UnexpToken (29)
ExtUse45 (45)
InvalResult (30)
ExtUse46 (46)
InvalTokenTb (31)
ExtUse47 (47)
String
Step
Common Interrupt
Condition
Configuration
Descriptor
Maximum of None
39 characters
No
View Only
CEE
No
IC.CONFIGSTS
Step
No
View Only
CEE
No
IC.DESC
Step
Step Interrupt
String
Condition Descriptor
Yes
Application
Developer
SR
No
Null
String
Notes
ExtUse48 (48)
ExtUse49 (49)
ExtUse50 (50)
UnSupConType (51)
UnExpClsParn (52)
CantAssRVal (53)
UnExpArrOpen (54)
ArrClsExpect (55)
ArrOpnExpect (56)
ArrIndxError (57)
StringExpect (58)
InvalidRefer (59)
TooManyConnS (60)
CantConvInpt (61)
IC.CONFIGDESC
Length: 64
characters
Related
Parameters
IC.CONFIGCODE,
IC.CONFIGDESC
74
Parameter
Parameter
Specific to
Block(s)
Description
IC.EXECCODE
Step
IC.EXECDESC
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Step Interrupt
Enumeration None (0)
None (0)
Condition Execution CSCOEXECCO ConfigError (1)
Code
DE
ExprEvalFail
(2)
StoreFailed (3)
CommError (4)
StoreWarning
(5)
InternalErr (6)
CtrlReqErr (7)
DataTypeErr
(8)
StorePending
(9)
No
View Only
CEE
No
Step
Step Interrupt
String
Condition Execution
Code Descriptor
Maximum of None
39 characters.
No
View Only
CEE
No
IC.EXECSTS
Step
Step Interrupt
Enumeration Ok (0)
Ok (0)
Condition Execution CSCOEXECST Bypass (1)
Status
S
Info (2)
Warning (3)
Fail (4)
Error (5)
OkPaused (6)
BypassPaused
(7)
InfoPaused (8)
WarnPaused
(9)
FailPaused
(10)
ErrorPaused
(11)
No
View Only
CEE
No
IC.EXPR
Step
Step Interrupt
String
Condition Expression
Yes
Application
Developer.
SR
No
IC.EXPRPCODE
Step
Internal parameter
for system use only.
IC.FL
Step
Step Interrupt
Condition Status
Flag
Boolean
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
IC.INVOKFL
Step
Step Interrupt
Condition Invoke
Flag
Boolean
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
IC.OPT
Step
Step Interrupt
Condition Option
Boolean
Off (0)
On (1)
Off (0)
Yes
Application
Developer
CEE
No
IC.EXECCODE,
IC.EXECDESC
Notes
IC.FL
75
Specific to
Block(s)
Description
Default
Config
Load
Access
Lock
Residence
Active
Connector
ICSRC [1..6]
Step
Internal parameter
for system use only.
ID
Step
Step ID (User
Defined)
No
Operator
CEE
No
IFTRANS
AIM, excluding
non-isolated
(high-density)
modules
On (1)
Yes
Application
Developer
CEE
No
IN
Limit, Checkbad
64-Bit Real
Number
NaN
Yes
Engineer
CEE
No
Delay, FTrig,
Maxpulse,
Minpulse, Not,
Offdelay, Ondelay,
Pulse, RTrig, Trig,
Watchdog
Boolean
Off (0)
No
Engineer
CEE
No
Yes
Engineer
CEE
No
Real
NaN
No
Engineer
CEE
No
Sel
Boolean
Off (0)
On (1)
Off (0)
No
Engineer
CEE
No
2oo3
Off (0)
On (1)
Off (0)
No
Engineer
CEE
No
IN [0..12]
Genlin
Each
NaN
coordinate
must be
greater-than
the previous
coordinate,
and less-than
the next
coordinate.
Yes
Engineer
CEE
No
IN [1..8]
Boolean
Off (0)
On (1)
Off (0)
Yes
Engineer
CEE
No
64-Bit Real
Number
NaN
No
Engineer
CEE
No
Off (0)
No
Engineer
CEE
No
IN [0..2]
IN [1..20]
NooN
Data Type
Range
Off (0)
On (1)
Off (0)
On (1)
Off (0)
On (1)
Related
Parameters
OUT [0..12],
NUMSEGS
Notes
76
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
IN.BOOLEAN
TypeConvert
IN.ENUM
TypeConvert
Enumerated Input
Value
Off (0)
On (1)
Off (0)
No
View Only
CEE
Yes. The
EXECSTS
connection is
to IN.Src
No
View Only
CEE
Yes. The
EXECSTS
connection is
to IN.Src
IN.FLOAT32
TypeConvert
NaN
No
View Only
CEE
Yes. The
EXECSTS
connection is
to IN.SRC
IN.FLOAT64
TypeConvert
NaN
No
View Only
CEE
Yes. The
EXECSTS
connection is
to IN.SRC
IN.INT8
TypeConvert
8-Bit Integer
-32768 to
32767
No
View Only
CEE
Yes. The
EXECSTS
connection is
to IN.SRC
IN.INT16
TypeConvert
No
View Only
CEE
Yes. The
EXECSTS
connection is
to IN.SRC
IN.INT32
TypeConvert
No
View Only
CEE
Yes. The
EXECSTS
connection is
to IN.SRC
IN.SDENUM
TypeConvert
Self Defining
Enumeration Input.
Integer
No
View Only
CEE
Yes. The
EXECSTS
connection is
to IN.SRC
IN.UINT16
TypeConvert
Unsigned 16-Bit
Input Value
Provides the value
fetched from the
TypeConvert
function blocks
source.
Unsigned
0 to 65535
16-Bit Integer
No
Other
Function
Block
CEE
Yes. The
EXECSTS
connection is
to IN.SRC
IN.UINT32
TypeConvert
Unsigned 32-Bit
Input Value
Unsigned
0 to
32-Bit Integer 4294967295
No
Other
Function
Block
CEE
Yes. The
EXECSTS
connection is
to IN.SRC
Enumeration
Positive
Integers
Related
Parameters
Notes
77
Specific to
Block(s)
Description
Data Type
INALM
Function Block In
Boolean
Alarm Flag
Indicates if an alarm
condition has been
detected with this
function block.
INBADOPT
DIC
INBETFL
INITCONNECTD
[1..3]
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Off (0):
Off (0)
Function block
is not in alarm
On (1):
Function block
is in alarm
No
View Only
CEE
No
ALMENBSTATE
DevCtl only:
CMDDISALM.FL,
CMDFALALM.FL,
SIALM.FL,
UNCMDALM.FL
Off (0)
On (1)
Hold (2)
NaN (3)
Value (4)
Off (0)
Yes
Engineer
CEE
No
DevCtl
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
DIPVMAP [0..15],
GPV, PV,
NUMDINPTS
DevCtl
Initialization
Connection Flag
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
BACKCALCIN [1..3]
INITCONNECTD [i] is
automatically set to On (1) by
the function block (on the
Control Modules EXECSTATE
transition to Active) if the
BACKCALCIN [i] is connected
to a BACKCALCOUT
structure.
Boolean
Range
Default
78
Parameter
Parameter
Specific to
Block(s)
INITMAN
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
Illegal if NUMDOUTS = 0.
Pulse Length only: When the
Pulse Length function block
goes into initialization mode,
either because its Secondary
(DOC) requested it or
because the LOCALMAN is
On, INITMAN goes On. It is
reset to Off only when its
Primary (usually PosProp)
receives the initialization
request and its Secondary is
out of initialization.
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
BACKCALCIN,
BACKCALCIN [1..3],
BACKCALCIN [1.8]
INITOPOPT
DevCtl
Output (OP)
Enumeration
Initialization Option ENABLE
Disable (0)
Enable (1)
Disable
(0)
Yes
Engineer
CEE
No
GOP, INITMAN,
NUMDOUTS, OP
Illegal if NUMDOUTS = 0.
INITREQ
Pulse Length
Control, Pulse
Count Control
Off (0)
(1)
On Off (0)
No
View Only
CEE
No
BACKCALCOUT
Off (0)
Off (0)
Initialization is
not requested.
On (1)
Initialization is
requested.
No
Other
Function
Block
CEE
No
79
Specific to
Block(s)
Description
INITREQ (cont.)
SIFLAGARRCH,
SINUMARRCH,
SITEXTARRCH
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Initialization
Boolean
Request Flag
Indicates the validity
of the array data.
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
BADPVFL, ERRFL,
Initialization
Boolean
Request Flags - Used
by a function block;
it requests a primary
to initialize. There is
one flag for each
primary.
Off (0)
(1)
On Off (0)
No
View Only
CEE
No
INITVAL
INITREQ [0..2]
DevCtl
Initialization
Request Flag
Boolean
Off (0)
(1)
On Off (0)
No
View Only
CEE
No
GOP, OP
INITREQ [1..8]
Initialization
Boolean
Request Flags
Used by a function
block to request a
primary to initialize.
There is one flag for
each primary.
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
INITVAL [1..8]
INITREQSRC
RegCalc
INITREQ
Enumeration X1 TOC8STS
(Initialization
REGCALCSELE
Request Flag) source CTOR
selector
No
Engineer
CEE
No
INITVAL
NaN
No
View Only
CEE
No
NaN
INITREQ
80
Parameter
Parameter
Specific to
Block(s)
Description
INITVAL [1..8]
INITVALSRC
RegCalc
Initialization Value
(INITVAL) source
selector.
Enumeration X1 to C8STS
REGCALCSELE (0 - 27)
CTOR
Input Inversion
Status
Boolean
AIM
Input Range
INSERTINDEX
CM, SCM
The number of
Integer
blocks ever inserted.
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
No
View Only
CEE
No
X1 (0)
Yes
Engineer
CEE
No
Off (0)
On (1)
Off (0)
Yes
Engineer
CEE
No
Boolean
Off (0)
On (1)
Off (0)
Yes
Engineer
CEE
No
Enumeration
of
INPUTRANGE
Enumeration
of
INPUTRANGE
_TC for
Thermocouple
modules
Enumeration
of
INPUTRANGE
_RTD for RTD
modules
INPUTRANGE
-10V_to_10V
(0)
0V_to_5V (1)
0V_to_10V (2)
4mA_to_20m
A (3)
INPUTRANGE
_TC
12_to_78mV
(4)
12_to_30mV
(5)
INPUTRANGE
_RTD
1-487_ohms
(6)
2-1000_ohms
(7)
4-2000_ohms
(8)
8-4020_ohms
(9)
INPUTRA Yes
NGE:
4mA_to_
20mA (3)
INPUTRA
NGE_TC:
-12_to_7
8mV (4)
INPUTRA
NGE_RTD
:
1-487_oh
ms (6)
Application
Developer
CEE
No
View Only
Related
Parameters
Notes
NUMOFINPUTS
81
Specific to
Block(s)
Description
INSTSELECT
SCM
Alias instance
16-Bit Integer 1
1
selection.
NUMINSTAN
Represents selected
CES
instance column.
Alias Table
parameter
Currently selected
instance.
INTISWCMD
RM
INVCOND [1..8]
SCM
Invoke Condition
Number
Invoked From
Handler Name
INVFRMHNDLER SCM
[1..8]
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Yes
Engineer
CEE
No
NUMINSTANCES
Can be configured at
configuration time, and
modified at run-time.
Engineer
CEE
Integer
True (0)
False (1)
True (0)
No
Operator
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
32-Bit Integer 0 to 10
No
View Only
CEE
No
TYPE
BlockId
Null
String
No
View Only
CEE
No
TYPE,
INVFRMHNDLERN
[1..8]
82
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
INVFRMHNDLER SCM
N [1..8]
Invoked From
Handler Name
INVFRMHNDTYP SCM
[1..8]
INVFROMSTEP
[1..8] [1..10]
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
32-Bit Integer
No
View Only
CEE
No
TYPE,
NVFRMHNDLER
[1..8]
Invoked From
Handler Type
32-Bit Integer 0 to 8
No
View Only
CEE
No
TYPE
SCM
BlockId
Null
String
No
View Only
CEE
No
TYPE,
INVFROMSTEP [i] [j] contains
NVFROMSTEPN [1..8] the name (eg.
[1..10]
SCMName.StepName) of
the step in thread j that was
active at the time of the
TYPE i handlers last
invocation.
INVFROMSTEP [1..8] is a
BlockId parameter and not
supported in expressions. Its
Integer-32 Partner Parameter
INVFROMSTEPN [1..8] can
be used in Transition
Condition expressions and
Step Output expressions.
INVFROMSTEPN SCM
[1..8] [1..10]
32-Bit Integer
No
View Only
CEE
No
Specific to
Block(s)
Description
INVOKE [1..8]
SCM
Internal parameter
for system use only.
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
No
View Only
CEE
No
NUM
2V
Yes
Application
Developer
CEE
No
INVOKT.HANDLE Handler
Invoke Transition
Handle
INVOKT.NEXTCO Handler
MP
Internal parameter
for system use only.
INVOLTTHRESH
Input Voltage
Threshold
Specifies level of
input.
Enumeration
Handler Invoke
Reason
View Only
CEE
No
TYPE
Invoke Thread
Number
32-Bit Integer 0 to 10
No
View Only
CEE
No
TYPE, INVREASON
[1..8]
INVTIME [1..8]
SCM
Invoke Time of
Handler
32-Bit Integer 0 to
2147483647
No
View Only
CEE
No
IOCNUMBER
All IO Channels,
SIFLAGARRCH,
SINUMARRCH,
SITEXTARRCH
Internal parameter
for system use only.
2V
8V
Range is zero
based. This
parameters
range was 1
based in
previous
releases.
84
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
IOCSTATE
All IO Channels,
SIFLAGARRCH,
SINUMARRCH,
SITEXTARRCH
IOC State
Integer
View Only
IOCTYPE
All IO Channels
except Pulse Input
IOM,
SIFLAGARRCH,
SINUMARRCH,
SITEXTARRCH.
Channel Type
Integer
Varies
View Only
IOMCONN
All IO Channels,
SIFLAGARRCH,
SINUMARRCH,
SITEXTARRCH
IO Module
Connector
IOMSLOT
IO Module Slot
Number in Chassis
Yes
IOMTYPE
This
non-configurable
parameter is a
description of the
respective IO
module type.
String
Length: 64
characters
Defined
appropria
tely on
each I/O
module
type. See
Note
below.
IOSCHEDOPT
CM, IOM
Internal parameter
for system use only.
IPADDRESS
CPM, RM
Length: 15
characters
Null
String
Residence
Active
Connector
Related
Parameters
Notes
SR
No
DLCNBSLOT,
ULCNBMAC
Not
View Only
configura
ble, but
loaded to
SR
SR
No
No
SR
No
SR
Application
Developer
Application
Developer
Engineer
ABORTALM.PR
85
Specific to
Block(s)
Description
Data Type
Mux, Muxreal
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
0 to 7
Yes
Engineer
CEE
No
Related
Parameters
GAINLOLM to 1.0
GAINHILM
Yes
Automan,
Fanot,
RegCalc,
QOR:
Engineer
PID, PIDFF:
Supervisor
CEE
No
Qor
K Selector
Integer
1 to 8
Yes
Engineer
CEE
No
K [1..4]
OvrdSel
Real
GAINLOLM to 1.0
GAINHILM
Yes
Operator
CEE
No
GAINLOLM,
GAINHILM
K [1..8]
Fanout
64-Bit Real
Number
GAINLOLM to 1.0
GAINHILM
Yes
Engineer
CEE
No
GAINLOLM and
GAINHILM
K1
Fanout, RatioBias,
GenCas,
PidExtReset
Real
GAINLOLM to 1.0
GAINHILM
Yes
Operator
CEE
No
GAINLOLM and
GAINHILM
K2
Fanout, RatioBias,
GenCas,
PidExtReset
Real
GAINLOLM to 1.0
GAINHILM
Yes
Operator
CEE
No
GAINLOLM and
GAINHILM
KEYWORD
Length: 16
characters
Yes
Application SR
Developer
RM only:
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform .
No
DESC, EUDESC
KFF
PIDFF
Real
KL
PosProp,
PidPosProp
Real
KLIN
PID, PIDFF
Null
String
1
0.0 to 10.0
Operator
CEE
GAINLOLM and
GAINHILM
1.0
Yes
Supervisor
CEE
No
GAINLOLM to 1.0
GAINHILM
Yes
Engineer
CEE
No
Notes
GAINLOLM and
GAINHILM
86
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
KMODIFEXT
PID, PIDFF
External Gain
Modifier. Used if
GAINOPT = Ext
(configured).
64-Bit Real
Number
KMODIFGAP
PID, PIDFF
64-Bit Real
Number
KMODIFNL
PID, PIDFF
Nonlinear Gain
64-Bit Real
Modifier (calculated) Number
KR
PosProp,
PidPosProp
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
GAINLOLM to 1.0
GAINHILM
Yes
Program
CEE
Default
Connector:
Input
GAINLOLM and
GAINHILM
0.0 to 1.0
Yes
Engineer
CEE
No
1.#QNAN No
0
ViewOnly
CEE
No
0.0 to 10.0
1.0
Yes
Supervisor
CEE
No
LAG1TIME
LeadLag
0.0 to 1440.0
minutes
0.0
Yes
Engineer
CEE
No
LAG2TIME
LAG2TIME
LeadLag
0.0 to 1440.0
minutes
0.0
Yes
Engineer
CEE
No
LAG1TIME
LASTGOOD
Totalizer, Pulse
Input Totalizer
NaN
No
View Only
CEE
No
PV
LASTGOODPV
NaN
No
View Only
CEE
No
PV, PVSTS
LASTGOPREQ
DevCtl
Null (0)
No
Other
Function
Block
CEE
No
GOPREQ,
LASTOPREQ,
LASTREQFL,
NUMSTATES,
OPREQ,
RESTARTOPT,
SCMOPT, STATETEXT
[0..6], SCMSTATE
Real
64-Bit Real
Number
Last Generic
Enumeration
Requested Output GENSTATE
Value (GOPREQ)
while
ControlModule.SMC
STATE is Running
Null (0)
S0 (1)
S1 (2)
S2 (3)
Default
1.0
Notes
NLFORM, NLGAIN
S2 is illegal if NUMSTATES =
2.
Illegal if
ControlModule.SCMOPT =
None.
87
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
LASTMODEREQ
Last value of
MODEREQ (Mode
Request), when
SCMMODE is
Running.
Enumeration
REGMODE
Man (0)
Auto (1)
Cas (2)
None (3)
None (3)
No
View Only
CEE
No
RESTARTOPT,
SCMSTATE, SCMOPT
LASTOPREQ
OPEXLOLM to 0
OPEXHILM
No
View Only
CEE
No
RESTARTOPT,
SCMSTATE, SCMOPT
DevCtl
Length: 12
characters
STATETEX No
T [0]
View Only
CEE
No
GOPREQ,
LASTGOPREQ,
LASTREQFL,
NUMSTATES,
OPREQ,
RESTARTOPT,
SCMOPT</HH >,
SCMSTATE,
STATETEXT [0..6]
Notes
LASTOPTYPE
DevCtl,
Last OPTYPE (Output Enumeration
All RegCtl Blocks: Type) stored when OPTYPE
AutoMan, Fanout, SCM was Running.
OvrdSel, PID, PIDFF,
PosProp,
PulseCount,
PulseLength,
RampSoak,
RemCas, RatioBias,
RegCalc, and
Switch.
Null (0)
Null (0)
Set (1)
NotStored (2)
Default (3)
No
View Only
CEE
No
LASTGOPREQ,
Illegal if
LASTOPREQ,
ControlModule.SCMOPT =
LASTREQFL, OPTYPE, None.
RESTARTOPT,
SCMOPT, SCMSTATE
LASTRATEREQ
No
View Only
CEE
No
RESTARTOPT,
SCMSTATE, SCMOPT
88
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
LASTREQFL
DevCtl
Last Requested
All RegCtl Blocks: Parameters Flag
AutoMan, Fanout,
OvrdSel, PID, PIDFF,
PosProp,
PulseCount,
PulseLength,
RampSoak,
RemCas, RatioBias,
RegCalc, and
Switch.
Boolean
LASTRESPTM
REQFLAGARRAY,
REQNUMARRAY,
REQTEXTARRAY
The number of
32-Bit Integer
execution cycles of
the container block
(Control Module)
between sending
the last request and
receipt of the
corresponding
response. If the
request is sent
during one execution
cycle and the
response received
before the next
execution cycle, this
parameter has a
value of 1.
LASTSERIAL
DOC
LASTSPREQ
SPLOLM to
SPHILM
No
LASTSPTVREQ
SPLOLM to
SPHILM
No
Integer
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
No
View Only
CEE
No
LASTOPREQ,
LASTOPTYPE,
RESTARTOPT,
SCMMODE,
SCMOPT,
SCMSTATE,
SCMASTEP [1..10]
Illegal if
ControlModule.SCMOPT =
None.
No
View Only
CEE
No
View Only
CEE
No
RESTARTOPT,
SCMSTATE, SCMOPT
View Only
CEE
No
RESTARTOPT,
SCMSTATE, SCMOPT
View Only
89
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
LASTSTEP
DevCtl
Last value of
String
SCMASTEP [1..10]
(SCM Active STEP),
when SCMMODE is
Running.
Length: 8
characters
LASTSYNCABRT RM
NoAbort (0)
NoAbort
ModInsert (1) (0)
ModRemoval
(2)
ModMismatch
(3)
Editing (4)
StalledSync
(5)
SecFault (6)
LASTSYNCARES RM
LATCHENB
No
View Only
CEE
No
LASTOPREQ,
Illegal if
LASTOPTYPE, NUM, ControlModule.SCMOPT =
RESTARTOPT,
None.
SCMASTEP [1..10],
SCMMODE,
SCMOPT, SCMSTATE
Null
String
No
View Only
CEE
No
No
View Only
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
View Only
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
1797-OB4D
Boolean
Off(0)
On(1)
Off(0)
Yes
Application
Developer
CEE
No
LEADTIME
LeadLag
Real Number
-1440.0 to
1440.0
minutes
0.0
Yes
Engineer
CEE
No
FAULTENB [ ],
FAULTRESET
Notes
90
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
LOADSTATE
CM, SCM
LOCALMAN
Off (0)
On (1)
LOCUTOFF
DataAcq
LOWENG
[0..numChans-1]
AIM, AOM
LOWENG is
configurable only
on the AIM.
64-Bit Real
Number
LOWERDEADTM PosProp,
PidPosProp
LOWERDESC
Lower Output
Descriptor.
PosProp,
PidPosProp
String
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
No
View Only
CEE
No
PREVLOADSTAT
No
DevCtl:
CEE
Other
Function
Block
Pulse Count,
Pulse
Length:
Program
No
GOP, GPV,
Illegal if NUMDOUTS = 0 or
NUMDINPTS,
NUMDINPTS = 0.
NUMDOUTS, OP, PV LOCALMAN can be used to
indicate to the Pulse Length
Control function block that
the connected device is
being controlled locally and
not by the CEE.
PVEULO to
NaN
PVEUHI, NaN,
Greater-than
or equal-to 0.
See Notes
Yes
Engineer,
CEE
Applications
Developer
No
PVEULO, PVEUHI,
PVCHAR
NaN,
less-than
HIGHENG
CEE
No
HIGHENG
[0..numChans-1]
No
View Only
CEE
No
Yes
Engineer
SR
No
LOADFAILED
(0)
UNLOADED
(1)
LOADINGPRO
G (2)
LDNGCMPTYP
ES (3)
CMLOADINGT
BR (4)
LOADINGCON
FIG (5)
LOADINGCON
N (6)
READY (7)
Off (0)
0.0
Lower
91
Specific to
Block(s)
Description
Data Type
LOWERLMFL
PosProp,
PidPosProp
LOWERRATE
PosProp,
PidPosProp
LOWERTIME
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
No
Other
Function
Block
CEE
No
0.0 to 100.0
Yes
Supervisor
CEE
No
PosProp,
PidPosProp
MINPULSEL,
lesser of
MAXPULSEL,
and
CYCLETIME.
Yes
View Only
CEE
No
LOWSIGNAL
[0..numChans-1]
AIM, AOM
Low Signal
64-Bit Real
Number
See
Notes.
No
View Only
CEE
No
SIPTYPE
[0..numChans-1],
INPUTRANGE
[0..numChans-1],
HIGHSIGNAL
[0..numChans-1]
LSCYCLEOVRN
[0..40]
CEE
Count of Cycle
Overruns in Last
Hour
No
View Only
CEE
No
CRCYCLEOVRN
[0..40]
MAINTOPT
DevCtl
Maintenance
Statistics Option
Boolean
Yes
Application
Developer
CEE
No
MAXTIME [0..2],
MAXTRANS [0..2],
NUMSIOVRD,
NUMTRANS [0..2],
RESETFL, STATETIME
[0..2]
100.0%
per
second
Off (0):
Off (0)
Maintenance
Statistics not
enabled.
On (1) :
Maintenance
Statistics
enabled.
Related
Parameters
Notes
If LOWERTIME <
MINPULSEL, no pulse is
issued.
92
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
MAJ
2oo3, MVote
Majority output
value
Boolean
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
MAJORREV
Yes
Application
Developer
CEE
No
MAJRECFAULT
RM
Ok (0)
Fault (1)
Ok (0)
No
View Only
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform
(through
Control
Builder or
Server).
No
MAJURECFAULT RM
Ok (0)
Fault (1)
Ok (0)
No
View Only
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform
(through
Control
Builder or
Server).
No
Related
Parameters
Notes
MINORREV
93
Specific to
Block(s)
MANPULSECMD PosProp,
PidPosProp
Description
Data Type
Range
Manual Pulse
Enumeration See below
Command Defines
the type of pulse
command the
Range
operator wants
None (0):
No change.
to issue.
Default
Config
Load
Access
Lock
Residence
Active
Connector
None (0)
Yes
Operator
CEE
No
Raise1 (1):
Lower1 (2):
Raise10 (3):
Raise output by
10 * MANPULSETIME each keystroke.
Lower10 (4):
Lower output by
10 * MANPULSETIME each keystroke.
MANPULSETIME PosProp,
PidPosProp
0.0 to 60.0
seconds
1.0
seconds
Yes
Engineer
CEE
No
MAX
Maximum Limit.
Any real
number, not
NaN.
0.0
Yes
Engineer
CEE
No
No
View Only
CEE
No
Limit
MAXFREEBLKSZ CPM
64-Bit Real
Number
Size of largest
32-Bit Integer 0 to 4194304
contiguous memory
Bytes
block in CEE user
memory pool.
Related
Parameters
Notes
TOTALMEM,
FREEMEM,
USEDMEM
94
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
MAXFREEINK
CPM
Size of largest
32-Bit Integer 0 to 4194304
contiguous memory
Kbytes
block in CEE user
memory pool.
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
No
View Only
CEE
No
TOTALMEMINK,
FREEMEMINK,
USEDMEMINK
MAXHISOAKDEV RampSoak
[1..NUMPROFILES
]
NaN, or
NaN
greater-than
or equal-to 0.0
Yes
Engineer
CEE
No
MAXLOSOAKDEV
[1..NUMPROFILES]
MAXLOSOAKDEV RampSoak
[1..NUMPROFILES
]
NaN, or
NaN
greater-than
or equal-to 0.0
Yes
Engineer
CEE
No
MAXHISOAKDEV
[1..NUMPROFILES]
MAXPULSEL
PosProp,
PidPosProp
Maximum Output
Real
Pulse Time for Lower
Pulses (in seconds).
NaN,
60.0
MINPULSEL to seconds
60.0 seconds.
Yes
Supervisor
CEE
No
MAXPULSER
PosProp,
PidPosProp
Maximum Output
Real
Pulse Time for Raise
Pulses (in seconds).
NaN,
MINPULSER
to 60.0
seconds.
Yes
Supervisor
CEE
No
60.0
seconds
95
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
NaN, or
NaN
greater-than
or equal-to 0.0
Yes
Engineer
CEE
No
Related
Parameters
Notes
MAXRAMPDEV RampSoak
[1..NUMPROFILES
]
Maximum Ramp
Real
Deviation - i.e.,
maximum deviation
between PV and CV
during ramp
segments. Applies
to all ramp segments
in a profile.
MAXSOAKVAL
RampSoak
[1..NUMPROFILES
]
Maximum Soak
Target Value in a
profile.
Real
NaN
Yes
View Only
CEE
No
MAXTIME
Step
Maximum Active
Time
32-Bit Integer 0 or
greater-than
MINTIME
Yes
Operator
CEE
No
MINTIME, TIME
MAXTIME [0..2]
DevCtl
Maximum Duration
per State
64-Bit Real
Number
Yes
Engineer
CEE
No
MAINTOPT,
NUMSTATES
MAXTIMEFL
Step
Maximum Step
Expired Flag.
Boolean
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
TIME, MAXTIME
MAXTIMEFL is On when
Step TIME is greater-than
MAXTIME.
Maximum
Transitions per
State.
64-Bit Real
Number
0.0 to
Maximum
Real Number
0.0
Yes
Engineer
CEE
No
MAINTOPT,
NUMSTATES
Message Text
String
Maximum of Null
60 characters String
Yes
Operator
SR
MIN
Limit
Minimum input
value
64-Bit Real
Number
Any real
number, not
NaN.
0.0
Yes
Engineer
CEE
No
MINORREV
Yes
Application
Developer
CEE
No
MAJORREV
96
Parameter
Parameter
Specific to
Block(s)
Description
MINPULSEL
PosProp,
PidPosProp
MINPULSER
MINRECFAULT
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Minimum Output
Real
Pulse Time for Lower
Pulses (in seconds).
NaN, 0.0 to
MAXPULSEL
0.0
seconds
Yes
Supervisor
CEE
No
PosProp,
PidPosProp
Minimum Output
Real
Pulse Time for Raise
Pulses (in seconds).
NaN, 0.0 to
MAXPULSER
0.0
seconds
Yes
Supervisor
CEE
No
RM
Ok (0)
Fault (1)
Ok (0)
No
View Only
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
MINSOAKVAL
RampSoak
[1..NUMPROFILES
]
Minimum Soak
Value in a profile.
Real
NaN
Yes
View Only
CEE
No
MINTIME
Step
Step Minimum
Active Time
Yes
Operator
CEE
No
MINURECFAULT
RM
Ok (0)
No
View Only
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
Ok (0)
Fault (1)
Related
Parameters
TIME, MAXTIME
Notes
No
97
Specific to
Block(s)
Description
Data Type
Range
Default
MODCOMPATA
RM
Indication of the
Enumeration
module pairs
[20]
assessment of their
compatibility
View Only
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
MODE
SCM
None (0)
Auto (1)
Auto (1)
SemiAuto (2)
SingleStep (3)
Manual (4)
Normal (5)
No
Operator
CEE
See below
No
Operator
Manual
(Man)
Config
Load
Access
Lock
Manual (0):
Range
OP is stored by either the operator or a user program. The function
block doesnt derive OP, so the input (SP, X1, etc.) is ignored.
Automatic (1):
The function block derives OP. The input (SP, X1, etc.) may be
stored by either the operator or a user program.
Cascade (2):
The function block derives OP. The input is pulled from another
function block (the primary).
Backup
Cascade (3):
The function block derives OP. The input is pulled from a backup
cascade. (Note: Bcas only applies to the Remote Cascade FB.)
Residence
Active
Connector
Related
Parameters
Notes
No
CONTROLLOCK,
COMMAND,
EXCMODEOPT,
MODEATTR,
SSTEPLOCK
CEE
No
MODEATTR
CEE
No
Normal (4)
None (5)
DevCtl
Mode
Enumeration
MODE
Manual
Manual
No
View Only
Access is illegal if
NUMDOUTS = 0.
The value of this parameter
is fixed Manual to be
compatible with other
function blocks.
98
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
No
View Only
CEE
No
MODE
Operator
MODEATTR
SCM
Operator (1)
Program (2)
Normal (3)
CEE
No
COMMAND,
MODE and COMMAND can
CONTROLLOCK,
only be accessed by an
MODE, SSTEPLOCK, Operator, when MODEATTR
is Operator. When
MODEATTR is Program, only
programs can store to MODE
and COMMAND.
DevCtl
Mode Attribute
Enumeration See below
Operator Yes
Operator
CEE
determines where MODEATTR
(0)
state commands to
the Device Control
Function Blocks may
Range
originate, that is,
None (0):
who may set OP.
Operator (1): Only the operator may command the output state.
No
CONTROLREQ, GOP,
GOPREQ,
MODETRACK,
NUMDOUTS, OP,
OPREQ, REDTAG.
Access is illegal, if
NUMDOUTS = 0.
MODEATTR may not be
changed if REDTAG is on.
No
Operator No
(1)
Program (2):
Normal (3):
Operator
CEE
99
Specific to
Block(s)
Description
Data Type
Range
Normal Mode
Attribute Flag
Indicates if mode
attribute is normal;
i.e., MODEATTR =
NORMMODEATTR
Boolean
Normal Mode
Attribute Indicator
Flag
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
No
View Only
CEE
No
MODEATTR,
NORMMODEATTR
Boolean
No
View Only
CEE
No
MODEATTR,
Value is On if MODEATTR =
MODEATTRFL.OPER, NORMMODEATTR
MODEATTRFL.PROG,
Operator Mode
Boolean
Attribute Flag
Indicates if the mode
attribute is Operator
No
View Only
CEE
No
MODEATTR
Operator Mode
Attribute Indicator
Flag
No
View Only
CEE
No
MODEATTR,
Value is On if MODEATTR =
MODEATTRFL.NORM Operator.
Boolean
Default
Notes
100
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Program Mode
Boolean
Attribute Flag
Indicates if the mode
attribute is Program.
Off (0):
Off (0)
MODEATTR is
not currently
Program.
On (1):
MODEATTR is
currently
Program.
No
View Only
CEE
No
MODEATTR
Program Mode
Attribute Flag
Boolean
Off (0):
Off (0)
MODEATTR is
not currently
Program.
On (1):
MODEATTR is
currently
Program.
No
View Only
CEE
No
MODEATTR,
Value is On if MODEATTR =
MODEATTRFL.OPER, Program.
MODEATTRFL.NORM
MODEFL.AUTO
No
View Only
CEE
No
MODE
MODEFL.BCAS
Backup Cascade
Boolean
Mode Flag
Indicates if the mode
is Backup Cascade.
No
View Only
CEE
No
MODE
MODEFL.CAS
No
View Only
CEE
No
MODE
DevCtl
101
Specific to
Block(s)
Description
Data Type
MODEFL.MAN
MODEFL.NORM
MODEPERM
MODEREQ
The requested
Enumeration
MODE. The SCM
REGMODE
CONTROLREQ
(Control Request)
wants to change the
Regulatory Blocks
MODE.
Boolean
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
No
View Only
CEE
No
MODE
Off (0)
On (1)
No
View Only
CEE
No
Engineer
CEE
No
MODE
Man (0)
Auto (1)
Cas (2)
None (3)
Operator
CEE
No
CONTROLREQ,
LASTMODEREQ,
SCMOPT
Off (0)
None (3)
No
Notes
102
Parameter
Parameter
Specific to
Block(s)
Description
MODETRACK
DevCtl
All RegCtl Blocks:
AutoMan, Fanout,
OvrdSel, PID, PIDFF,
PosProp,
PulseCount,
PulseLength,
RampSoak,
RemCas, RatioBias,
RegCalc, and
Switch.
MODISREDUN
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
None (0)
OneShot (1)
SemiCont (2)
ContRtn (3)
Cont (4)
OneShot
(1)
Yes
Engineer
CEE
No
MODEATTR,
Is invalid if
ControlModule.SCM ControlModule.SCMOPT =
OPT,
None.
ControlModule.SCM
MODE,
ControlModule.SCM
STATE
CPM
Off (0)
On (1)
Off (0)
No
Engineer
SR
No
ABORTALM.PR
MODTYPEA
RM
UNK (0)
--- (1)
CPM (2)
CNB (3)
RM (4)
AC (5)
OM (6)
SP1 (7)
SP2 (8)
SP3 (9)
SP4 (10)
SP5 (11)
--- (1)
No
View Only
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
PRODTYPEA,
PRODCODEA
MOMSTATE
DevCtl
Momentary Output
States
Enumeration
MOMSTATE
None (0)
None (0)
Mom_1 (1)
Mom_0 (2)
Mom_2 (3)
Mom_1_2 (4)
Mom_0_2 (5)
Mom_0_1 (6)
Yes
Engineer
CEE
No
Message Type
Enumeration
Info (0)
Confirm (1)
Yes
Operator
CEE
No
MULREDUNSTAT CPM, RM
Enumeration
CONFIGREDU CONFIGR No
N (0)
EDUN (0)
FORCEDREDU
N (1)
NONREDUN
(2)
Application
Developer
SR
No
MXRFBDEV
Maximum deviation
allowed between CV
and RFB, in percent.
PidExtReset
Data Type
Info (0)
ABORTALM.PR
Notes
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
NAME
Name
Access
Lock
Residence
Active
Connector
Engineer
CEE
No
Related
Parameters
Notes
NETELAPSEDTM RampSoak
Greater-than 0.0
or equal to 0.0
No
NETWORKTYPE
CPM, RM
Network Type
Enumeration
NEXTCOMP
Transition
Next Component
Reference
Output
Connection
Yes
View Only
CEE
No
TOTELAPSEDTM
Engineer
SR
No
ABORTALM.PR
Application
Developer
CEE
No
104
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
NEXTCOMP
[1..10]
Step
Next Component
Reference
Output
Connection
NEXTHANDLE
Transition
Next Component
Handle
NEXTHANDLE
[1..10]
Step
Next Component
Handle
NEXTNUMBER
Step
NFLAG
NLFORM
Config
Load
Access
Lock
Residence
Active
Connector
Yes
Application
Developer
CEE
No
No
View Only
CEE
No
NUM, NEXTCOMP
No
View Only
CEE
No
NUM, NEXTCOMP
[1..10]
Step Next
Component Handle
Count.
32-Bit Integer 0 to 10
No
View Only
CEE
No
NEXTCOMP [1..10]
FLAGARRAY,
SIFLAGARRCH
Number of Flag
Values Specifies
the number of
boolean values in
the array of data
from the serial
device.
Yes
Application
Developer
CEE
No
SIFLAGARRCH only:
PVFL [1..512]
FLAGARRAY only:
PVFL [1..1000]
REQFLAGARRAY,
RSPFLAGARRAY
The number of
32-Bit Integer 1 to 512
Boolean values that
must be read or
written by this block.
Yes
Application
Developer
CEE
No
PID, PIDFF
Non-linear Gain
form. Used if
GAINOPT = Nonlin
(configured)
Yes
Engineer
CEE
No
Integer
Range
0 or 1
Default
Related
Parameters
Notes
NEXTCOMP specifies the
SCM component that follows
the step. The steps
NEXTCOMP [1] block pin is
exposed by default. It may
be connected to a single
transition through the
transitions DESC parameter
(which may have additional
corrections from other steps
NEXTCOMP [i]).
If left open, the handler will
end when the step
completes. The block pins
NEXTCOMP [2] through
NEXTCOMP [i] can be
exposed for i transitions out
of a step (with a maximum of
10).
105
Specific to
Block(s)
Description
Data Type
Range
Config
Load
Access
Lock
Residence
Active
Connector
NLGAIN
PID, PIDFF
Non-linear Gain
factor. Used if
GAINOPT = Nonlin
(configured).
64-Bit Real
Number
GAINLOLM to 0.0
GAINHILM
Yes
Engineer
CEE
No
NNUMERIC
NUMERICARRAY,
SINUMARRCH
SINUMARRCH 1
: 0 to 64
NUMERICARR
AY: 0 to 200
Yes
Application
Developer
CEE
No
REQNUMARRAY,
RSPNUMARRAY
The number of
32-Bit Integer 1 to 64
integer or real
values that must be
read or written by
this block.
Yes
Application
Developer
CEE
No
NOFIELDPWR
DIC, DOC
No loss of
power
detected (0)
Loss of power
detected (1)
No loss of No
power
detected
(0)
View Only
CEE
No
ELOF
Previously the LOF and
[0..numChans-1] (DIC ZCROSS parameters.
only), EZCROSS
[0..numChans-1]
(DOC only)
NOFIELDPWR
[0..numChans-1]
DIM, DOM
No loss of
power
detected (0)
Loss of power
detected (1)
No loss of No
power
detected
(0)
View Only
CEE
No
ELOF
Previously the LOF and
[0..numChans-1]
ZCROSS parameters.
(DIM only), EZCROSS
[0..numChans-1]
(DOM only)
NOLOAD
DOC
Indicates when
Boolean
output current draw
is below the
threshold.
Current draw
is not below
threshold (0)
Current draw
is below
threshold (1)
Current No
draw is
not below
threshold
(0)
View Only
CEE
No
ENOLOAD
[0..numChans-1]
NOLOAD
[0..numChans-1]
DOM
Indicates when
Boolean
output current draw
is below the
threshold.
Current draw
is not below
threshold (0)
Current draw
is below
threshold (1)
Current No
draw is
not below
threshold
(0)
View Only
CEE
No
ENOLOAD
[0..numChans-1]
NORMAL
Flag
StateText (0)
StateText (1)
None
None
Supervisor
Engineer is
limited to
change
to/from
None.
CEE
No
Enumeration
STATETEXT,
None
Default
Yes
Related
Parameters
Notes
106
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
NORMMODE
DevCtl
All RegCtl Blocks:
AutoMan, Fanout,
OvrdSel, PID, PIDFF,
PosProp,
PulseCount,
PulseLength,
RampSoak,
RemCas, RatioBias,
RegCalc, and
Switch.
Enumeration
REGMODE
Manual (Man)
Automatic
(Auto)
Cascade (Cas)
Backup
Cascade
(Bcas)
None
DevCtl:
Manual
(Man)
RegCtl:
None
Yes
Engineer
CEE
No
MODE
DevCtl
Normal Mode
Enumeration
MODE
Manual
Manual
Yes
Engineer
CEE
No
MODE
SCM
Enumeration
MODE
None (0)
SCM:
Auto (1)
None (0)
SemiAuto (2)
SingleStep (3)
Manual (4)
Normal (5)
Yes
Engineer
CEE
No
MODE
Normal Mode
Attribute - Defines
the Normal Mode
Attribute of a
Regulatory Control
function block.
Enumeration
MODEATTR
None (0)
Oper (1)
Program (2)
None (0)
Yes
Engineer
CEE
No
MODEATTR
DevCtl only:
MODEATTR,
MODETRACK,
NUMDOUTS
NOTCHFILTER
[0..numChans-1]
Isolated Modules:
Notch Filter
Non_Isolated
Modules: 3 dB Filter
Non-Isolated
Modules:
Enumeration
of
THREEDBFILT
R
Isolated
Modules:
Enumeration
of
NOTCHFILTER
Non-Isolated
Modules:
20 Hz (0)
Isolated
Modules:
50Hz (1)
60Hz (2)
Non-Isola Yes
ted
Modules:
20Hz (0)
Isolated
Modules:
60Hz (2)
Application
Developer
CEE
No
AIM
107
Specific to
Block(s)
Description
Data Type
NSTRING
TEXTARRAY,
SITEXTARRCH
Number of String
32-Bit Integer
Values Specifies
the number of string
values in the array of
data from the serial
device.
Range
Default
SITEXTARRCH 1
only: 0 to 8
TEXTARRAY
only: 0 to 120
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Yes
Application
Developer
CEE
No
Notes
The Text Array block supports a maximum size of 960 two-byte characters. This number
is chosen based on the amount of data that can fit in one ControlNet message. This is
important when full array access is supported.
SITEXTARRCH only: With the interface to the serial device having a maximum size of
64-bytes, the table below shows how the 64-bytes are interpreted, based on the
NSTRING and STRLEN configured, and the resulting STR [ ] range. Illegal combinations
of NSTRING and STRLEN (those requiring more than 64-bytes of data) will be rejected.
NSTRING
1
2
4
8
STRLEN
64
32
16
8
REQTEXTARRAY,
RSPTEXTARRAY
The number of
32-Bit Integer 1 to 8
strings that must be
read or written by
this block. The
product of NSTRING
and STRLEN cannot
exceed 64.
Yes
Application
Developer
CEE
No
NULLPVFL
DevCtl
Off (0)
No
View Only
CEE
No
NUM
Handler, Step,
Transition
No
View Only
CEE
No
Greater-than 0
or equal to 0.0
No
View Only
CEE
No
NUMACCRQUAV CEE
G
Boolean
Notes
Off (0)
On (1)
STR [ ] Range
1..1
1..2
1..4
1..8
DIPVMAP [0..15],
GPV, NUMDINPTS,
PV
NUMACCRQUMAX,
STATSRESET
108
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
NUMACCRQUMA CEE
X
NUMALIASES
SCM
Number of aliases
configured in the
Alias Table.
Alias Table
parameter
NUMCCLRQU
CEE
Number of Cyclic
64-Bit Real
parameter requests Number
for peer data per
second.
Greater-than
or equal-to 0.0
NUMCHANS
Defines the
32-Bit Integer
maximum number of
channels supported
by the respective
IOM type.
Dependent
upon module
type.
(i.e., Pulse
Input IOM: 8)
NUMCMPCONTF CM
B
Internal parameter
for system use only.
NUMCOMPFB
CM, SCM
Internal parameter
for system use only.
NUMCONDS
Transition
Number of Input
Conditions
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
No
View Only
CEE
No
NUMACCRQUAVG,
STATSRESET
Historical maximum of
acyclic parameter request
throughput since last store to
STATSRESET. SCM step
outputs are the only block
mechanisms to cause acyclic
peer to peer communication
traffic.
Yes
Application
Developer
CEE
No
Application
Developer
CEE
View Only
CEE
No
SUBSCPERIOD
Value of NUMCCLRQU is
associated with the currently
loaded block configuration
and SUBSCPERIOD.
Note that this statistical
parameter is not affected by
STATSRESET.
Dependen Yes
t upon
module
type.
(i.e., Pulse
Input
IOM: 8)
Application
Developer
CEE
No
Application
Developer
CEE
No
Greater-than
or equal-to 0.0
32-Bit Integer 0 to 10
No
Yes
109
Specific to
Block(s)
Description
NUMCONN
Data Type
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Number of
32-Bit Integer
Connections
Indicates a running
count of the number
of times that a
connection has been
formed to the
associated device.
No
View Only
CEE
No
NUMDISCONN,
NUMSHUTDOWN
Number of
32-Bit Integer
Connections
Indicates a running
count of the number
of times that a
connection has been
formed to the
associated device.
No
View Only
CEE
No
NUMDISCONN [0..7],
NUMSHUTDOWN
[0..7]
NUMDINPTS
DevCtl
Number of Digital
Inputs
No
Engineer
CEE
No
See below
NUMDISCONN
Number of
32-Bit Integer
Disconnects
Indicates a running
count of the number
of times that a
connection has been
closed due to fault
(rather than due to a
commanded
operation).
No
View Only
CEE
No
Integer
Range
0 to 4
Default
Notes
110
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
NUMDISCONN
[0..7]
Serial Interface
IOM.
32-Bit Integer
Number of
Disconnects
Indicates a running
count of the number
of times that a
connection has been
closed due to fault
(rather than due to a
commanded
operation).
NUMDOUTS
DevCtl
Number of Digital
Outputs
Integer
Range
0 to 3
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
No
View Only
CEE
No
NUMCONN [0..7],
NUMSHUTDOWN
[0..7]
No
Engineer
CEE
No
See below
Notes
Related Parameters
BYPASS,
OIALM.PR [0..2],
CMDDISALM.FL,
OIALM.SV [0..2],
CMDDISALM.PR,
OP,
CMDDISALM.SV,
OPDOMAP [0..3] [1..3],
CMDDISALM.TM [0..2], OPFINAL,
CMDFALALM.FL,
OROPT,
CMDFALALM.PR,
PI [0..2],
CMDFALALM.SV,
PO [1..3],
CMDFALALM.TM [0..2], PULSEWIDTH [1..3],
DO [1..3],
PVSOURCE, REDTAG,
GOP,
SAFEOP, SEALOPT,
GOPFINAL,
SI,
INITMAN,
SIALM.FL, SIALM.OPT,
INITOPOPT,
SIALM.PR, SIALM.SV,
LOCALMAN,
STATETEXT [0..6],
MODEATTR,
UNCMDALM.FL,
OI [0..2],
UNCMDALM.PR,
OIALM.FL [0..2],
UNCMDALM.SV
OIALM.OPT [0..2],
NUMEVENTS
RampSoak
[1..NUMPROFILES
]
1 to 16
Yes
Application
Developer
CEE
No
NUMRAMPSOAK
[1..NUMPROFILES]
NUMHANDLERS SCM
Internal parameter
for system use only.
NUMHISTPARMS SCM
Number of History
Parameters
32-Bit Integer 0 to 50
Yes
Application
Developer
CEE
No
HISTDESC
111
Specific to
Block(s)
NUMINSTANCES SCM
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Yes
Application
Developer
CEE
No
Application
Developer
CEE
Yes
Engineer
CEE
No
DELAYTABLE [1..60],
DELAYTIME
Notes
Alias Table
parameter
NUMLOC
Deadtime
2 to 60
NUMNTFRQUAV
G
CEE
Number of
64-Bit Real
Notification
Number
Requests per second
Average.
Greater-than 0
or equal-to 0.0
No
View Only
CEE
No
NUMNTFRQUMAX,
STATSRESET
Rolling average of
notification request
throughput.
NUMNTFRQUMA CEE
X
Number of
64-Bit Real
Notification
Number
Requests per second
Maximum.
Greater-than
or equal-to 0.0
No
View Only
CEE
No
NUMNTFRQUAVG,
STATSRESET
Historical maximum of
notification request
throughput since last store of
STATSRESET.
NUMOFINPUTS
Number of
configured inputs
Integer
1 to 8
MVote: 3 Yes
Min, Max:
2
Engineer
CEE
No
Number of
configured inputs
Integer
1 to 2
Yes
Engineer
CEE
No
60
NUMONESHOT
No
View Only
CEE
No
NUMOUTPUTS
Step
Yes
Application
Developer
CEE
No
32-Bit Integer 0 to 16
112
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
NUMPARRSPAV
G
CEE
NUMPARRSPMA CEE
X
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Greater-than
or equal to 0.0
No
View Only
CEE
No
NUMPARRSPMAX,
STATSRESET
Greater-than
or equal-to 0.0
No
View Only
CEE
No
NUMPARRSPAVG,
STATSRESET
NUMPRI
0 to 8
0
(dependent on
the function
block)
No
View Only
CEE
No
NUMPROFILES
RampSoak
1 to 10
Yes
Application
Developer
CEE
No
NUMPROPREQ
No
View Only
Not Loaded
No
Yes
Application
Developer
CEE
No
Integer
32-Bit Integer
Number of
Integer
Ramp/Soak Pairs in
a Profile
1 to 50
NUMEVENTS
[1..NUMPROFILES]
113
NUMRAMPSOAK RampSoak
[1..NUMPROFILES
]
Number of Profiles
Specific to
Block(s)
NUMRECPARMS SCM
Description
Data Type
Number of Recipe
Parameters
32-Bit Integer 0 to 50
NUMSEC
NUMSEGS
Genlin
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Yes
Application
Developer
CEE
No
RECDESC [1..50],
RECSCALE [1..50],
RECMATCODE
[1..50], RECTARGET
[1..50],
RECTARGETMAX
[1..50],
RECTARGETMIN
[1..50]
32-Bit Integer 0 to 8
0
(dependent on
the function
block)
No
View Only
CEE
No
Yes
Engineer
CEE
No
IN, OUT
Number of
Integer
Segments - Total
number of segments
defined to the
General
Linearization
function block.
Range
1 to 12
Number of
32-Bit Integer
Shutdowns
Indicates a running
count of the number
of times that a
connection to the
associated device
has been closed due
to either a fault or
commanded
shutdown.
No
View Only
CEE
No
NUMCONN
Number of
32-Bit Integer
Shutdowns
Indicates a running
count of the number
of times that a
connection to the
associated device
has been closed due
to either a fault or
commanded
shutdown.
No
View Only
CEE
No
NUMCONN [0..7]
114
Parameter
Parameter
Specific to
Block(s)
Description
NUMSIOVRD
DevCtl
NUMSLOTS
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Number of Safety
64-Bit Real
Interlock Trips The Number
accumulated number
of Safety Override
Interlocks since the
last reset of
maintenance
Statistics.
0.0 to
Maximum
Real Number
0.0
No
View Only
CEE
No
RM
Number of slots in
the host chassis
1 to 20
No
View Only
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
NUMSTATES
DevCtl
Yes
Engineer
No
CMDDISALM.FL,
CMDDISALM.PR,
CMDDISALM.SV,
CMDDISALM.TM
[0..2],
CMDFALALM.FL,
CMDFALALM.PR,
CMDFALALM.SV,
CMDFALALM.TM
[0..2], DIPVMAP
[0..15], GOP,
GOPFINAL, GPV,
GPVAUTO,
LASTOPREQ,
MAXTIME,
MAXTRANS [0..2],
MOMSTATE,
NUMTRANS [0..2],
OP, OPDOMAP [0..3]
[1..3], OPFINAL,
OPREQ, PI [0..2], PV,
PVAUTO, PVFL [0..2],
SAFEOP, STATETIME
[0..2]
NUMSTEPS
SCM
Internal parameter
for system use only.
NUMSYNCS
SCM
Internal parameter
for system use only.
NUMTBR
CM
Internal parameter
for system use only
32-Bit
Unsigned
Integer
2 to 3
CEE
Notes
115
Specific to
Block(s)
Description
Data Type
NUMTHREADS
SCM
SCM Current
Number of Active
Threads
32-Bit Integer 0 to 10
NUMTRANS
SCM
Total Number of
State Transitions
The accumulated
number of
transitions to the
reference state
since the last reset
of Maintenance
Statistics.
NUMXFERINST]
CM
Internal parameter
for system use only.
OFFNRMALM.FL
Flag
DevCtl
OFFNRMALM.PR Flag
DevCtl
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
No
View Only
CEE
No
0.0
No
View Only
CEE
No
64-Bit Real
Number
0.0 to
Maximum
Real Number
0.0
No
View Only
CEE
No
GPV, MAINTOPT,
NUMSTATES, PV,
RESETFL
Defaulted to 0.0 if
MAINTOPT is not set On.
Reset to 0.0 whenever
RESETFL is set from Off to
On.
NUMTRANS [2] is illegal if
NUMSTATES = 2.
Boolean
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
OFFNRMALM.PR,
OFFNRMALM.SV,
NORMAL, PV</HH
Boolean
Off Normal Alarm
Flag - Indicates the
OFF-Normal
condition. The
Device is
OFF-Normal
wherever the
Process Variable (PV)
does not equal
OPREQ.
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
BYPASS,
InActive when GOPREQ is
CMDDISALM.FL,
Null.
CMDDISALM.PR,
CMDDISALM.SV,
CMDDISALM.TM
[0..2], GOPREQ, GPV,
HIALM, OPREQ, PV
Enumeration
ALMPR
None (0)
Journal (1)
Low (2)
High (3)
Urgent (4)
Low (2)
Yes
Engineer
CEE
No
OFFNRMALM.FL,
OFFNRMALM.SV
Enumeration
ALPRIOR
None (0)
Journal (1)
Low (2)
High (3)
Urgent (4)
None (0)
Yes
Engineer
CEE
No
GOPREQ, OPREQ
116
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Integer
0 to 15
Yes
Engineer
CEE
No
OFFNRMALM.FL,
OFFNRMALM.PR
DevCtl Only:
GOPREQ, OPREQ
OFFPULSE
DOC
No
Operator
CEE
Yes
ONPULSE
OHMOFFSET
AIC
No
View Only
CEE
No
CALBIAS,
SENSORTYPE
[0..numChans-1]
OHMOFFSET
[0..numChans-1]
AIM
Yes
Application
Developer
CEE
No
CALBIAS
[0..numChans-1],
SENSORTYPE
[0..numChans-1]
OI [0..2]
DevCtl
Override Interlock
Boolean
Off (0)
On (1)
Off (0)
No
Engineer/
Other
Function
Block (see
Notes)
CEE
No
BYPASS, BYPPERM,
GOP, NUMDOUTS,
OIALM.FL [0..2],
OIALM.OPT [0..2],
OIALM.PR [0..2],
OIALM.SV [0..2], OP,
SAFEOP, SI,
SIALM.FL,
SIALM.OPT,
SIALM.PR, SIALM.SV
OIALM.FL [0..2]
DevCtl
Override Interlock
Alarm Flag
Boolean
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
Override Interlock
Alarm Option.
Enumeration
OVRDALOP
No (0)
Yes (1)
Yes
Engineer
CEE
No
NUMDOUTS
Illegal if NUMDOUTS = 0.
117
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
OIALM.PR [0..2]
DevCtl
Override Interlock
Alarm Priority
Enumeration
ALPRIOR
None (0)
Journal (1)
Low (2)
High (3)
Urgent (4)
Low (2)
Yes
Engineer
CEE
No
NUMDOUTS, OI
[0..2], OIALM.FL
[0..2], OIALM.OPT
[0..2], OIALM.SV
[0..2]
Illegal if NUMDOUTS = 0.
OIALM.SV [0..2]
DevCtl
Override Interlock
Alarm Severity
Yes
Engineer
CEE
No
NUMDOUTS, OI
[0..2], OIALM.FL
[0..2], OIALM.OPT
[0..2], OIALM.PR
[0..2]
Illegal if NUMDOUTS = 0.
OLDAV
Totalizer, Pulse
Input Totalizer
Old Accumulated
64-Bit Real
Value - The value of Number
the Process Variable
(PV), just before it
was reset. This
parameter makes
the old value
available to those
functions that need
it.
No
View Only
CEE
No
PV
ONPULSE
DOC
No
Operator
CEE
Yes
OP
No
Operator
CEE
No
64-Bit Real
Number
Greater-than
or equal-to 0.0
OPEXLOLM to 0.0
OPEXHILM
OPEU
118
Parameter
Parameter
Specific to
Block(s)
Description
OP (cont.)
DevCtl
AOC, PWM
Channel
Output Value in
percent
Fanout
OP [1..8]
Data Type
Real Number
Range
Default
Length: 12
characters
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
STATETEX No
T [4]
Operator
CEE
No
BYPASS,
CMDDISALM.FL,
CMDDISALM.PR,
CMDDISALM.SV,
CMDDISALM.TM
[0..2],
CMDFALALM.FL,
CMDFALALM.PR,
CMDFALALM.SV,
CMDFALALM.TM
[0..2], GOP,
GOPFINAL, GOPREQ,
MOMSTATE,
NUMDOUTS,
NUMSTATES, OI
[0..2], OPDOMAP
[0..3] [1..3], OPFINAL,
OPREQ, SAFEOP,
SAFEREDTAG, SI,
STATETEXT [0..6],
UNCMDALM.FL,
UNCMDALM.PR,
UNCMDALM.SV.
No
Operator
CEE
Yes
OPEXLOLM to OPEXLOL No
OPEXHILM
M
Operator
CEE
No
OPEU [1..8]
OP is represented in
percentage of the Calculated
Variable (CV) range (CVEULO
and CVEUHI).
119
Specific to
Block(s)
Description
Data Type
OP [1..16].
CONFIGCODE
Step
No
See OP [1..16].CONFIGSTS
for additional information.
OP [1..16].
CONFIGDESC
Step
Maximum of Null
39 characters. String
No
View Only
CEE
No
See OP [1..16].CONFIGSTS
for additional information.
OP [1..16].
CONFIGSTS
Step
No
View Only
CEE
No
OP [1..16].DESC
Step
Output Description
Yes
Application
Developer
SR
No
OP [ ].DSTN
Step
Internal parameter
for system use only.
String
Range
Maximum
Length: 64
characters
Default
Null
String
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
OP
[1..16].CONFIGCODE,
OP
[1..16].CONFIGDESC
Notes
120
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
OP [1..16].
DSTNCTRLREQ
Step
Output Destination
Control Request
Connector
OP [1..16].
EXECCODE
Step
OP [1..16].
EXECDESC
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Output
Connector
No
Application
Developer
CEE
No
CONTROLREQ
Output Execution
Code
No
View Only
CEE
No
Step
Output Execution
Code Descriptor
String
Maximum of Null
39 characters. String
No
View Only
CEE
No
OP [1..16].
EXECSTS
Step
Output Execution
Status
Enumeration Ok (0)
Ok (0)
CSCOEXECST Bypass (1)
Info (2)
Warning (3)
Fail (4)
Error (5)
OkPaused (6)
BypassPaused
(7)
InfoPaused (8)
WarnPaused
(9)
FailPaused
(10)
ErrorPaused
(11)
No
View Only
CEE
No
OP [1..16].
EXPRPCODE
Step
Internal parameter
for system use only.
OP
Step output execution status
[1..16].EXECCODE,
parameters OP
OP [1..16].EXECDESC [1..16].EXECSTS, OP
[1..16].EXECCODE, and OP
[1..16].EXECDESC are
updated when the step is in
the SCMs current scope of
execution.
121
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
OP [1..16].
SRCEXPR
Step
Output Source
Expression
String
Maximum
Length: 255
characters
Null
String
Yes
Application
Developer
SR
No
OP [1..16].STATE
Step
No
View Only
CEE
No
OP [1..16].TYPE
Step
Output Type
Yes
Application
Developer
CEE
OPBIAS
No
Operator
OPBIAS [1..8]
Fanout
No
Operator
Related
Parameters
Notes
No
SCMOPT,
CONTROLREQ,
MODEREQ, OPREQ,
SPREQ, SPRATEREQ,
SPTVREQ
CEE
No
OPBIAS.FIX,
OPBIAS.FLOAT,
OPBIAS.RATE
CEE
No
OPBIAS.FIX,
OPBIAS.FLOAT,
OPBIAS.RATE
122
Parameter
Parameter
Specific to
Block(s)
Description
OPBIAS.FIX
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
0.0
Yes
Operator
CEE
No
OPBIAS,
OPBIAS.FLOAT,
OPBIAS.RATE
CV = OP + OPBIAS.FIX +
OPBIAS.FLOAT
0.0
Yes
Operator
CEE
No
OPBIAS [1..8],
OPBIAS [1..8].FLOAT,
OPBIAS [1..8].RATE
OPBIAS.FLOAT
No
View Only
CEE
No
OPBIAS [1..8].
FLOAT
Fanout
No
View Only
CEE
No
OPBIAS [1..8],
OPBIAS [1..8].FIX,
OPBIAS [1..8].RATE
OPBIAS.FLOAT(new value) =
OPBIAS.FLOAT(current value)
- (OPBIAS.RATE/ cycles/min)
where cycles per minute is
the number of function block
executions per minute.
123
Specific to
Block(s)
Description
OPBIAS.RATE
OPBIAS [1..8].
RATE
Data Type
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
NaN
Yes
Engineer
CEE
No
Fanout
NaN
Yes
Engineer
CEE
No
OPBIAS [1..8],
OPBIAS [1..8].FIX,
OPBIAS [1..8].FLOAT
OPCMD [0..2]
DevCtl
Output Command
Boolean
Off (0)
On (1)
Off (0)
No
Program
CEE
No
GOPREQ, OPREQ,
OPTYPE
OPDOMAP [0..3]
[1..3]
DevCtl
Output (OP) to
Boolean
Digital Output
Values (DO) Map of
Settable State
Assignments.
Off (0)
On (1)
Off (0)
Yes
Engineer
CEE
No
DO [1..3], GOP,
Illegal if NUMDOUTS = 0.
GOPFINAL, PO [1..3], OPDOMAP [2, x] is illegal, if
NUMDOUTS,
NUMSTATES = 2.
NUMSTATES, OP,
OPFINAL
OPEU
No
Operator
CEE
Default
Connector:
Output
OP
64-Bit Real
Number
Range
Notes
124
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
OPEU [1..8]
Fanout
OPEUX
OPEUX [1..8]
OPEXHIFL
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
64-Bit Real
Number
No
Operator
CEE
Default
Connector:
Output
OP [1..8]
Structure
No
View Only
CEE
No
OPEU
Fanout
No
View Only
CEE
No
Output (OP)
Boolean
Extended High Limit
Flag. Indicates if OP
is at its extended
high limit.
No
View Only
CEE
No
OPEXHILM
Notes
OPEUX is a hidden
connection in Control Builder.
OPEUX is a two-part data
structure that contains:
OPEU (the output value in
engineering units) and a
status component. OPEUX
should be used when making
a cascade connection to a
secondary control block. The
OPEUX connection is
required in order for the
initialization path to be
established between the
primary and secondary
blocks.
This parameter will not
indicate any value on the
chart when the pin is
exposed, it shows ****.
125
Specific to
Block(s)
Description
Data Type
OPEXHIFL [1..8]
Fanout
Output (OP)
Boolean
Extended High Limit
Flag. Indicate if OP
[1..8] are at their
extended high limit.
OPEXHILM
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Off (0):
Off (0)
Corresponding
OP is below
its extended
high limit.
On (1):
Corresponding
OP is at its
extended high
limit.
No
View Only
CEE
No
OPEXHILM
Greater than
OPLOLM
Yes
Engineer
CEE
No
OPEXHIFL
OPEXLOFL
Output (OP)
Boolean
Extended Low Limit
Flag. Indicates if OP
is at its extended
low limit.
No
View Only
CEE
No
OPEXLOLM
OPEXLOFL [1..8]
Fanout
Output (OP)
Boolean
Extended Low Limit
Flag. Indicates if OP
[1..8] are at their
extended low limit.
Off (0):
Off (0)
Corresponding
OP is above its
extended low
limit.
On (1):
Corresponding
OP is at its
extended low
limit.
No
View Only
CEE
No
OPEXLOLM
106.9%
Notes
126
Parameter
Parameter
Specific to
Block(s)
OPEXLOLM
OPFINAL
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Less than
OPHILM
-6.9%
Yes
Engineer
CEE
No
OPEXLOFL
DevCtl
String
Length: 12
characters
STATETEX No
T [4]
View Only
CEE
No
GOPFINAL, DO [1..3],
NUMDOUTS,
NUMSTATES,
NUMTRANS,
OPDOMAP [0..3]
[1..3], PO [1..3],
SEALOPT,
STATETEXT [0..6],
TATETIME [0..2]
AOC
Adjusted Output
Value
64-Bit Real
Number
No
View Only
CEE
No
OPFINAL
[0..numChans-1]
AOM
Adjusted Output
Value.
64-Bit Real
Number
No
View Only
CEE
No
OPHIALM.DB
64-Bit Real
Number
Yes
Engineer/Ap CEE
plication
Developer
No
OP, OPHIALM.DBU,
OPHIALM.FL,
OPHIALM.PR,
OPHIALM.SV, ,
OPHIALM.TM,
OPHIALM.TP
See below.
Notes
Notes
The following rule is applied to OPHIALM.DB to prevent OPHI and OPLO alarm are both active at the
same time:
OPHIALM.DB <= (OPHIALM.TP - OPLOALM.TP)/2
(or PVLOALM.TP <= PVHIALM.TP - 2 PVLOALM.DB)
Individual alarm deadbands are not individually configurable. The ALMDB that is configured is
loaded to the block, then the block copies the ALMDB value to all the xxALM.DB of all analog
alarms on the block. This includes ALMDBU and ALMTM - thus, all analog alarms get the same
three values through a one-time configuration entering of the three values.
If desired, the individual alarm parameters (xxALM.DB, xxALM.DBU, and xxALM.TM) may be
modified after the block is loaded. The block load will always set all individual alarm parameters to
the three configured values.
When OPHIALM.DB is in Percent, the deadband units (OPHIALM.DBU) cannot be changed.
127
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
OPHIALM.DBU
Enumeration
ALMDBU
Percent (0)
EU (1)
Percent
(0)
Yes
Application
Developer
CEE
No
OP, OPHIALM.DB,
OPHIALM.FL,
OPHIALM.PR,
OPHIALM.SV,
OPHIALM.TM,
OPHIALM.TP
OPHIALM.FL
Off (0)
No
View Only
CEE
No
OP, OPHIALM.DB,
OPHIALM.DBU,
OPHIALM.PR,
OPHIALM.SV,
OPHIALM.TM,
OPHIALM.TP
OPHIALM.PR
None (0)
Journal (1)
Low (2)
High (3)
Urgent (4)
Low (2)
Yes
Engineer
CEE
No
OP, OPHIALM.DB,
OPHIALM.DBU,
OPHIALM.FL,
OPHIALM.SV,
OPHIALM.TM,
OPHIALM.TP
Enumeration
ALPRIOR
128
Parameter
Parameter
Specific to
Block(s)
Description
OPHIALM.SV
OPHIALM.TM
OPHIALM.TP
Data Type
Range
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Yes
Engineer
CEE
No
OP, OPHIALM.DB,
OPHIALM.DBU,
OPHIALM.FL,
OPHIALM.PR,
OPHIALM.TM,
OPHIALM.TP
0 to 60
Yes
Engineer/Ap CEE
plication
Developer
No
OP, OPHIALM.DB,
OPHIALM.DBU,
OPHIALM.FL,
OPHIALM.PR,
OPHIALM.SV,
OPHIALM.TP
If OPHIALM.TM = 0, alarm
will be generated as soon as
OP exceeds the high trip
point.
Individual alarm deadbands
are not individually
configurable. The ALMDB
that is configured is loaded
to the block, then the block
copies the ALMDB value to
all the xxALM.DB of all
analog alarms on the block.
This includes ALMDBU and
ALMTM - thus, all analog
alarms get the same three
values through a one-time
configuration entering of the
three values.
If desired, the individual
alarm parameters
(xxALM.DB, xxALM.DBU, and
xxALM.TM) may be modified
after the block is loaded.
The block load will always
set all individual alarm
parameters to the three
configured values.
NaN, or
OPLOLM to
OPEXHILM
NaN
Yes
Engineer
No
OP, OPHIALM.DB,
OPHIALM.DBU,
OPHIALM.FL,
OPHIALM.PR,
OPHIALM.SV
OPHIALM.TM
If OPHIALM.TP = NaN, OP
high alarms are inhibited.
The following restriction is
applied to OPHIALM.TP to
prevent that OPHI and OPLO
alarm are both active at the
same time:
OPHIALM.DB <=
(OPHIALM.TP OPLOALM.TP)/2
(or OPHIALM.TP >=
OPLOALM.TP +
2 OPHIALM.DB)
16-Bit Integer 0 to 15
64-Bit Real
Number
CEE
Notes
129
Default
Specific to
Block(s)
Description
Data Type
OPHIFL
OPHIFL [1..8]
Fanout
OPHILM
OPLOALM.DB
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
No
View Only
CEE
No
OPHILM
No
View Only
CEE
No
OPHILM
NaN, or
OPLOLM to
OPEXHILM
Yes
Engineer
CEE
No
OPHIFL
Yes
Engineer/Ap CEE
plication
Developer
No
64-Bit Real
Number
Range
Default
105.0%
Notes
Notes
The following restriction is applied to OPLOALM.DB to prevent that OPHI and OPLO alarm are both
active at the same time:
OPLOALM.DB <= (OPHIALM.TP - OPLOALM.TP)/2
Individual alarm deadbands are not individually configurable. The ALMDB that is configured is
loaded to the block, then the block copies the ALMDB value to all the xxALM.DB of all analog
alarms on the block. This includes ALMDBU and ALMTM - thus, all analog alarms get the same
three values through a one-time configuration entering of the three values.
If desired, the individual alarm parameters (xxALM.DB, xxALM.DBU, and xxALM.TM) may be
modified after the block is loaded. The block load will always set all individual alarm parameters to
the three configured values.
When the OPLOALM.DB is in Percent; the deadband units (OPLOALM.DBU) cannot be changed.
130
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
OPLOALM.DBU
Enumeration
ALMDBU
Percent (0)
EU (1)
Percent
(0)
Yes
Application
Developer
CEE
No
OP, OPLOALM.DB,
OPLOALM.FL,
OPLOALM.PR,
OPLOALM.SV,
OPLOALM.TM,
OPLOALM.TP
OPLOALM.FL
Boolean
No
View Only
CEE
No
OP, OPLOALM.DB,
OPLOALM.DBU,
OPLOALM.PR,
OPLOALM.SV,
OPLOALM.TM,
OPLOALM.TP
OPLOALM.PR
Enumeration
ALPRIOR
None (0)
Journal (1)
Low (2)
High (3)
Urgent (4)
Engineer Yes
CEE
No
OP, OPLOALM.DB,
OPLOALM.DBU,
OPLOALM.FL,
OPLOALM.SV,
OPLOALM.TM,
OPLOALM.TP
Low (2)
131
Specific to
Block(s)
Description
OPLOALM.SV
OPLOALM.TM
OPLOALM.TP
Data Type
Range
16-Bit Integer 0 to 15
64-Bit Real
Number
0 to 60
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Yes
Engineer
CEE
No
OP, OPLOALM.DB,
OPLOALM.DBU,
OPLOALM.FL,
OPLOALM.PR,
OPLOALM.TM,
OPLOALM.TP
Yes
EngineerApp CEE
lication
Developer
No
OP, OPLOALM.DB,
OPLOALM.DBU,
OPLOALM.FL,
OPLOALM.PR,
OPLOALM.SV,
OPLOALM.TP
If OPLOALM.TM = 0, an
alarm will be generated as
soon as OP falls below the
low trip point.
Individual alarm deadbands
are not individually
configurable. The ALMDB
that is configured is loaded
to the block, then the block
copies the ALMDB value to
all the xxALM.DB of all
analog alarms on the block.
This includes ALMDBU and
ALMTM - thus, all analog
alarms get the same three
values through a one-time
configuration entering of the
three values.
If desired, the individual
alarm parameters
(xxALM.DB, xxALM.DBU, and
xxALM.TM) may be modified
after the block is loaded.
The block load will always
set all individual alarm
parameters to the three
configured values.
Yes
Engineer
No
OP, OPLOALM.DB,
OPLOALM.DBU,
OPLOALM.FL,
OPLOALM.PR,
OPLOALM.SV,
OPLOALM.TM,
If OPLOALM.TP = NaN, OP
low alarms are inhibited.
The following restriction is
applied to OPLOALM.TP to
prevent that OPHI and OPLO
alarm are both active at the
same time:
OPLOALM.DB <=
(OPHIALM.TP OPLOALM.TP)/2
(or OPLOALM.TP <=
OPHIALM.TP 2 OPLOALM.DB)
NaN, or
NaN
OPEXLOLM to
OPHILM
CEE
Notes
132
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
OPLOFL
OPLOFL [1..8]
Fanout
OPLOLM
OPMINCHG
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
No
View Only
CEE
No
OPLOLM
No
View Only
CEE
No
OPLOLM
NaN, or
-5.0%
OPEXLOLM to
OPHILM
Yes
Engineer
CEE
No
OPLOFL
Yes
Engineer
CEE
No
OP
64-Bit Real
Number
Range
Default
Notes
133
Specific to
Block(s)
Description
Data Type
OPREQ
The requested OP
64-Bit Real
(Output) value. The Number
SCM CONTROLREQ
wants to change the
regulatory control
blocks output (OP).
OPEXLOLM to 0
OPEXHILM
DevCtl
Length: 12
characters
String
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
No
Operator
CEE
No
SCMOPT,
CONTROLREQ,
LASTOPREQ,
OPTYPE,
LASTOPTYPE,
RESTARTOPT,
STARTOPT,
HOLDOPT, STOPOPT
OPREQ is illegal if
ControlModule.SCMOPT =
None.
While MODEATTR is
Operator, a pending OPREQ
can be terminated by the
operator setting it to NaN.
STATETEX No
T [0]
Other
Function
Block
CEE
No
GOP, GOPREQ,
HOLDOPT,
LASTOPREQ,
LASTOPTYPE,
MODEATTR,
NUMSTATES, OP,
OPTYPE,
RESTARTOPT,
SAFEOP, STARTOPT,
STATETEXT [0..6],
STOPOPT
OPROCLM
NaN, or
NaN
Greater-than
or equal-to 0.1
Yes
Engineer
CEE
No
OPROCNEGFL,
OPROCPOSFL
OPROCNEGFL
Off (0): OP
Off (0)
negative rate
of change is
above the
limit.
On (1): OP
negative rate
of change is
less-than or
equal-to the
limit.
No
View Only
CEE
No
OPROCLM
Boolean
134
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
OPROCNEGFL
[1..8]
Fanout
Output (OP)
Negative Rate of
Change Flag
Boolean
OPROCPOSFL
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Off (0): OP
Off (0)
negative rate
of change is
above the
limit.
On (1): OP
negative rate
of change is
below or
equal to the
the limit.
No
View Only
CEE
No
OPROCLM
Off (0): OP
Off (0)
positive rate
of change is
below the
limit.
On (1): OP
positive rate
of change is
above or equal
to the limit.
No
View Only
CEE
No
OPROCLM
OPROCPOSFL
[1..8]
Fanout
Off (0): OP
Off (0)
positive rate
of change is <
the limit.
On (1): OP
positive rate
of change is
>= the limit.
No
View Only
CEE
No
OPROCLM
OPSECDATA
Default
Internal parameter
for system use only.
135
Specific to
Block(s)
Description
Data Type
Range
OPSECDATA.
ARWSTS
Integer
View Only
OPSECDATA.
EUHI
Real
NaN
View Only
OPSECDATA.
EULO
Real
NaN
View Only
OPSECDATA.
INITREQ
Boolean
Off (0)
View Only
Off (0)
On (1)
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
136
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
OPSECDATA.
INITVAL
Real
NaN
View Only
OPSECDATA.
ONESHOT
Integer
View Only
OPSECDATA.
ORFBVA
64-Bit Real
Number
NaN
View Only
OPSECDATA.
OROFFS
Boolean
Off (0)
View Only
OPSOURCE
AOC, PWM
Channel
Output Source
Connector
OPSRC [1..16]
[1..6]
Step
Internal parameter
for system use only.
Off (0)
On (1)
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Application
Developer
137
Specific to
Block(s)
Description
Data Type
OPTYPE
DevCtl,
All RegCtl Blocks:
AutoMan, Fanout,
OvrdSel, PID, PIDFF,
PosProp,
PulseCount,
PulseLength,
RampSoak,
RemCas, RatioBias,
RegCalc, and
Switch.
OPX
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
No
View Only
CEE
No
RegCtl only:
SCMOPT,
CONTROLREQ,
SCMSTATE,
SCMASTEP [1..10],
ASTEPID,
LASTOPTYPE, OP
[1..16].TYPE
DevCtl only:
HOLDOPT,
LASTOPTYPE,
OPREQ,
RESTARTOPT,
STARTOPT, STOPOPT
No
View Only
CEE
No
OPEU
OPX [1..8]
Fanout
Structure
No
View Only
CEE
No
OPEU
ORBYPASSFL
[1..4]
OvrdSel
Override Bypass
Flags Indicates
which Override
Selector inputs (if
any) should be
bypassed.
Boolean
Yes
Engineer
CEE
No
ORBYPPERM
Ovrdsel
Bypass Enable
Boolean
Off (0)
On (1)
Yes
Engineer/Ap CEE
plications
Developer
No
Null (0)
Null (0)
Set (1)
NotStored (2)
Default (3)
Off (0)
Notes
138
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
ORDER
DevCtl
Execution Order
within containing
Control Module
Integer
0 to 65535
ORDERINCEE
ORDERINCM
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
A multiple Yes
of 10,
establish
ed by
Control
Builder
when the
block is
created.
Point Build
CEE
No
10
Yes
Application
Developer
CEE
No
PHASE, PERIOD,
ORDERINCM
1 to 32,767
10
A linearly
increasing
multiple of 10
starting at 10,
the actual
value
assigned by
Control
Builder
according to
the order of
insertion into
a CM function
block during
configuration.
Yes
Application
Developer
SR
No
ORDERINCEE,
PHASE, PERIOD
Other Notes
Enter a number to specify the desired
execution order for the block. For individual
function blocks, execution order specifies
the disignated order of execution of each
block relative to the other blocks in the
same Control Module. The block with the
lowest number in this parameter is
executed first, followed by the next lowest
and so on.
139
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
ORED
NooN
Boolean
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
ORFBSTSSRC
RegCalc
Override feedback
status (ORFBSTS)
source selector.
Enumeration
X1 to C8STS
(0 - 27)
X1 (0)
Yes
Engineer
CEE
No
ORFBVALSRC
RegCalc
Override feedback
value source
selector
Enumeration X1 to C8STS
REGCALCSELE (0 - 27)
CTOR
X1 (0)
Yes
Engineer
CEE
No
OROFFSET
OvrdSel
Override Offset
Boolean
Off (0)
On (1)
Off (0)
Yes
Engineer/Ap CEE
plication
Developer
No
OROPT
OvrdSel
Boolean
Off (0):
Off (0)
Nonselected
inputs do not
use override
feedback
data. The
block acts as a
simple
high/low
selector.
On (1):
Nonselected
inputs should
use override
feedback
data.
Yes
Engineer/Ap CEE
plications
Developer
No
OUT
And, Checkbad,
Current output value Boolean
Delay, EQ, FTrig, GE,
GT, LE, LT,
Maxpulse,
Minpulse, Mux,
Nand, NE, Nor, Not,
Offdelay, Ondelay,
Or, Pulse, Qor, RTrig,
Sel, Trig,
Watchdog, Xor
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
NaN
No
View Only
CEE
No
No
View Only
CEE
No
Limit, Muxreal,
Current output value 64-Bit Real
Max, Min, SelReal
Number
ROL, ROR, SHL,
SHR
Related
Parameters
Notes
OROPT
140
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
OUT [0..12]
Genlin
Any Real
Number, not
NaN.
Yes
Engineer
CEE
No
IN [0..12], NUMSEGS
OUT.BOOLEAN
TypeConvert
Boolean Output
Value
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
OUT.ENUM
TypeConvert
ENUM0
No
View Only
CEE
No
OUT.FLOAT32
TypeConvert
NaN
No
View Only
CEE
No
OUT.FLOAT64
TypeConvert
NaN
No
View Only
CEE
No
OUT.INT8
TypeConvert
No
View Only
CEE
No
OUT.INT16
TypeConvert
16-Bit Integer
Output Value
No
View Only
CEE
No
OUT.INT32
TypeConvert
32-Bit Integer
Output Value
No
View Only
CEE
No
OUT.SDENUM
TypeConvert
Self-defining
SDENUM
Enumeration Output
12 character SDENUM No
string
0
corresponding
to ordinal
value.
ViewOnly
OUT.UINT16
TypeConvert
16-Bit Unsigned
Integer
Integer Output Value
0 to 65535
No
View Only
CEE
No
OUT.UINT32
TypeConvert
32-Bit Unsigned
Integer
Integer Output Value
0 to
4294967295
No
View Only
CEE
No
OUTSENSE
Off (0)
On (1)
Off (0)
Yes
Application
Developer
CEE
No
Boolean
Range
-128 to 127
Default
Notes
No
141
Specific to
Block(s)
Description
OUTSENSE [6..7]
OVERRANGE
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Off (0)
On (1)
Off (0)
Yes
Application
Developer
CEE
No
AIC
Input is not in
an over-range
state (0)
Input is in an
over-range
state (1)
No
View Only
CEE
UNDERRANGE
OVERRANGE
[0..numChans-1]
AIM
Input is not in
an over-range
state (0)
Input is in an
over-range
state (1)
No
View Only
CEE
UNDERRANGE
[0..numChans-1]
P[1..6]
Auxcalc
NaN
No
View Only
CEE
Yes, Input
P1
DataAcq,
Process Input Value 64-Bit Real
Deadtime, Totalizer, #1 - The current
Number
Genln, LeadLag.
value of the process
input to a Data
Acquisition function
block.
NaN
No
View Only
CEE
No
EqA
Yes
Engineer
CEE
0 EqA
1 EqB
2 EqC
3 EqD
4 EqE
5 - EqF
Related
Parameters
Notes
Affects Channels 6-7 only.
P1STS
142
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
P1CLAMPOPT
DataAcq
Yes
Engineer
CEE
No
P1EU
DataAcq
P1EU value
P1FILTINIT
DataAcq
Off (0):
Off (0)
Initialization is
not requested.
On (1):
Initialization is
requested.
No
Other
Function
Block
CEE
No
P1FILTTIME
DataAcq
0.0 to 60.0
minutes
0.0
Yes
Engineer
CEE
No
P1STS
DataAcq,
Deadtime, Totalizer,
Genlin, Leadlag,
Pulse Input Totalizer
Status of the
Enumeration
Process Input #1 PVVALSTS
Indicates the current
status of P1.
Bad (0)
Pulse
Input
Totalizer
only:
Normal
(2)
No
View Only
CEE
No
P1
P2
Deadtime
NaN
No
View Only
CEE
No
P2STS
Real
NaN
Related
Parameters
Notes
View Only
143
Specific to
Block(s)
Description
Data Type
Range
P2STS
Deadtime
Status of Process
Input #2
Enumeration
PVVALSTS
PATH
REQFLAGARRAY,
REQNUMARRAY,
REQTEXTARRAY
PAUSEFL
SCM
PCMCOMMAND CPM
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Bad (0):
Normal
(ORD.0)The
(2)
value is bad
and has been
replaced with
NaN.
Uncertn (1):
(ORD.1)The
status of the
value is
uncertain.
Normal (2):
(ORD.2)The
value is good.
Manual (3):
(ORD.3)The
value was
manually
stored.
No
View Only
CEE
No
P2
Maximum of Null
40 characters String
Yes
Application
Developer
CEE
No
Pause Flag
Off (0)
On (1)
CEE
No
Boolean
Default
Off (0)
Notes
View Only
No
Engineer
PCMSTATE
Shutdown can be
commanded when the
CEESTATE is IDLE, which
takes the CPM to the
PIREADY (RDY) state. No
other value of PCMSTATE
can be commanded.
Note that in the future the
name of this parameter will
be changed to
CPMCOMMAND.
144
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
PCMSTATE
CPM
Current state of
CPM block.
OK (5)
No
View Only
CEE
No
PCMCOMMAND
PDELAYDIRCHG
Pulse Length
Control, Pulse
Count Control
Yes
Engineer
CEE
No
PERIOD
No
Greater-than 0.0
or equal-to 0.0
and a multiple
of the
containing
Control
Module
PERIOD.
145
Specific to
Block(s)
Description
PHASE
PI[0..2]
Data Type
Range
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Yes
Engineer
CEE
No
ORDERINCM,
ORDERINCEE,
PERIOD,
CPUCYCLEAVG[0..39]
DevCtl
On (1)
No
Other
Function
Block (see
Notes)
CEE
No
BYPASS, GOP,
NUMDOUTS,
NUMSTATES, OP
PL
NaN
No
View Only
CEE
No
PLSTS
PL = C3 * (pulse / period
length in microseconds)
PL[0..5]
NaN
No
View Only
CEE
No
PLSTS
Enumeration
No
View Only
CEE
No
PL
PO
Pulse Length
Control, Pulse
Count Control
Boolean
Off (0)
On (1)
No
View Only
CEE
No
PO[1..3]
DevCtl
Pulsed Output
Values
Structure
No
View Only
CEE
No
Off (0)
On (1)
Default
Off (0)
146
Parameter
Parameter
Specific to
Block(s)
Description
POCONNECTED
[1..3]
DevCtl
PODIR
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Pulse Connection
Boolean
Flag - Whenever the
respective PO(1..3) is
connected to a
DOC.ONPULSE or
DOC.OFFPULSE, the
parameter
POCONNECTED(1..3)
must be set to On.
This allows the
Device Control
function block to
know which outputs
are configured for
pulsing.
POCONNECTED[ ]
may not be
configured on the
form until at least
one PO[ ] parameter
is exposed on the
block.
Off (0)
On (1)
Off (0)
Yes
Operator
CEE
No
PULSEWIDTH,
PO[1..3]
Pulse Length
Control, Pulse
Count Control
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
PORAISE, POLOWER,
PO.
POLOWER
Pulse Length
Control, Pulse
Count Control
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
POPERIOD
Greater-than 0.010
0.0. Only
values that
are multiples
of two times
the FBs
execution
period are
valid, other
values are
clamped to
the greatest
multiple of
two times the
function
blocks
execution
period less
than the
entered value.
Yes
Engineer
CEE
No
Boolean
Notes
147
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
PORAISE
Pulse Length
Control, Pulse
Count Control
Boolean
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
POLOWER, PO,
PODIR
PREVISION
RM
No
View Only
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform
(through
Control
Builder or
Server).
No
PREVLOADSTAT
CM, SCM
Previous container
block load state.
No
View Only
CEE
No
LOADSTATE
PROCESSED
Handler, Step,
Transition
Component has
Boolean
been processed flag.
No
View Only
CEE
No
0 to 255
Enumeration LOADFAILED
of LOADSTATE (0)
UNLOADED
(1)
LOADINGPRO
G (2)
LOADINGCMP
TYPES (3)
CMLOADINGT
BR (4)
LOADINGCON
FG (5)
LOADINGCON
N (6)
READY (7)
Off (0)
On (1)
Off (0)
An SCM components
Processed flag is set if it has
been included in the SCMs
execution thread. All
components processed flags
reset only when the SCM
STATE transitions to
Checking (either by a Reset
command or Check Handlers
Invoke Transition).
148
Parameter
Parameter
Specific to
Block(s)
Description
PRODCODE
RM
PRODCODEA
PRODTYPE
Data Type
Range
Default
Config
Load
Access
Lock
Product Code.
16-Bit
Identification of RM Unsigned
within product type Integer
(per ASA
specification).
0 to 65535
No
View Only
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform
(through
Control
Builder or
Server).
No
Handler, Step,
Transition
Module Product
Code. For each
module in the host
chassis, factory
assigned product
code
0 to 65535
No
View Only
CEE
No
10 for
Yes
Analog
Input/Out
put
Modules,
including
Thermoco
uple and
RTD.
7 for
Digital
Input/Out
put
Modules
12 for
Serial
Interface
Module
109 for
Pulse
Input
Module
Application
Developer
CEE
No
RM
Product Type.
16-Bit
Identification of
Unsigned
general RM type (per Integer
ASA specification).
View Only
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
16-Bit
Unsigned
Integer [20]
0 to 65535
No
Residence
Active
Connector
Related
Parameters
Notes
IOMTYPE
No
149
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
PRODTYPEA
RM
Module Product
Type. For each
module in the host
chassis, factory
assigned product
type.
16-Bit
Unsigned
Integer [20]
0 to 65535
No
View Only
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
PROFILEDESC
RampSoak
[1..NUMPROFILES
]
Profile Descriptor
String
15 Characters Profile<#>
where
<#> is the
number of
profile.
PROFILEID
RampSoak
Profile ID
Integer
PROGCMD
RM
Program Command
Recognition
Enumeration
PROGCMDRECOG RM
PROGPACKET[0.. SCM, CM
2]
Internal parameter
for system use only.
Engineer
Residence
Active
Connector
No
CEE
View Only
Disabled (0)
Enabled (1)
Disabled No
(0)
Operator
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
Disabled (0)
Enabled (1)
Disabled No
(0)
View Only
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
Related
Parameters
Notes
150
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
PSTS[1..6]
Auxcalc
PULSECMD
PosProp,
PidPosProp
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Bad (0):The
Bad (0)
value is bad
and has been
replaced with
NaN.
Uncertn
(1):The status
of the value is
uncertain.
Normal
(2):The value
is good.
Manual
(3):The value
was manually
stored.
No
View Only
CEE
No
P[1..6]
Idle (0):
Output is not
being affected
by
PULSECMD.
Lower
(1):Output is
being
lowered.
Raise
(2):Output is
being raised.
No
View Only
CEE
No
Notes
151
Specific to
Block(s)
PULSEMODE
Description
Data Type
Pulse Length
Enumeration
Measurement Mode
Selects the portion
of pulse whose time
is measured.
Range
Default
PulseHigh (0)
PulseLow (1)
Period (2)
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
PulseHigh Yes
(0)
Application
Developer
CEE
No
PulseHigh Yes
PulseHigh
(0)
(0):Provides
the elapsed
time between
an Off-to-On
transition and
the next
On-to-Off
transition.
PulseLow
(1):Provides
the elapsed
time between
an On-to-Off
transition and
the next
Off-to-On
transition.
Period
(2):Provides
the elapsed
time between
two
consecutive
Of-to-On
transitions.
Application
Developer
CEE
No
152
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
PULSETIME
Pulse Length
Control, Pulse
Count Control,
PosProp,
PidPosProp.
Pulse Time
requested (in
seconds)
64-Bit Real
Number
PULSEWIDTH
NooN
Pulsewidth in
seconds
Pulse, Maxpulse,
Minpulse
Pulsewidth in
Seconds
Integer
PULSEWIDTH[1..3 DevCtl
]
Output Pulsewidth
64-Bit Real
Number
PV
DataAcq
Flag
Numeric
Timer
Default
Config
Load
Access
Lock
Residence
Active
Connector
No
View Only
CEE
Yes
5 seconds Yes
Engineer
CEE
No
0 to 8000
seconds
2 seconds Yes
Engineer
CEE
No
0.000 to
60.000
seconds
1.0
Yes
Engineer
CEE
No
DO[1..3],
NUMDOUTS
NaN
No
Operator
CEE
No
PVSRCOPT,
PVSOURCE.
A PV change by an operator
requires that PVSRCOPT =
All, and PVSOURCE = Man.
A PV change by a program
requires that PVSRCOPT =
All, and PVSOURCE = Sub.
STATETEXT[0]: STATETEX No
PVFL = OFF
T[0]
STATETEXT[1]:
PVFL = ON
Defined by
ACCLOCK
CEE
No
STATETEXT[0..1],
PVFL
PVLOLM to
PVHILM
No
Defined by
ACCLOCK
CEE
No
PVLOLM, PVHILM
Elapsed Time
Integer
Indicates the current
elapsed time value
of the Timer function
block.
0 to
0
2,147,483,647
(2^31 1)
No
View Only
CEE
No
NaN
Related
Parameters
Notes
This parameter is a structure,
the main value of which is
the Pulse Time requested, in
seconds. This parameter
usually gets its input from
the PosProp function block
153
Specific to
Block(s)
Description
PV (cont.)
DevCtl
AIC
PV[0..7]
Data Type
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
STATETEX No
T[0]
View Only,
Operator,
Other
Function
Block (see
Notes)
CEE
No
BADPVALM.FL,
BADPVALM.PR,
BADPVALM.SV,
CMDDISALM.FL,
CMDDISALM.PR,
CMDDISALM.SV,
CMDDISALM.TM[0..
2], CMDFALALM.FL,
CMDFALALM.PR,
CMDFALALM.SV,
CMDFALALM.TM[0..
2], DIPVMAP[0..15],
GPV, GPVAUTO,
NUMDINPTS,
NUMSTATES,
PVAUTO, PVSOURCE,
PVSRCOPT,
STATETEXT[0..6],
UNCMDALM.FL,
UNCMDALM.PR,
UNCMDALM.SV.
Access is illegal if
NUMDINPTS = 0.
PV is a String set equal to
STATETEXT(GPV).
Access lock is View Only if
PVSOURCE = AUTO or
TRACK or PVSRCOPT is
ONLYAUTO.
Access lock is Operator if
PVSOURCE = MAN.
Access lock is Other Function
Block if PVSOURCE = SUB.
STATETEXT[6] [State2] is
illegal if NUMSTATES = 2.
No
View Only
CEE
No
NaN
No
View Only
CEE
Default
Connector:
Input
PVSTS, PVVALSTS
Totalizer, Pulse
Input Totalizer,
Deadtime, LeadLag,
Genlin, Auxcalc,
RampSoak
Function Block
64-Bit Real
Output - The
Number
calculated output of
an Auxiliary function
block.
NaN
No
View Only
CEE
No
NaN
No
View Only
CEE
No
PVSTS
NaN
No
ViewOnly
CEE
No
PVSTS, PVVALSTS
Frequency/Rate
64-Bit Real
Value Engineering Number
Units value
corresponding to the
rate of pulses.
Range
Default
Length: 12
characters
Config
Load
PV = C1 / C2 * TIMEBASE *
pulses / (frequency
integration period)
154
Parameter
Parameter
Specific to
Block(s)
Description
PV[0..63]
REQNUMARRAY,
RSPNUMARRAY
PV[1..64]
Data Type
Default
Config
Load
Access
Lock
Residence
Active
Connector
NaN
Yes
Operator
CEE
No
SINUMARRCH
NaN
Yes
Determined CEE
by ACCLOCK
PV[1..200]
NUMERICARRAY
Numeric Data
64-Bit Real
Provides access to Number
the Numeric values,
one element at a
time, for all other
function blocks of
the CEE. Initial
values can be
configured.
NaN
Yes
PVAUTO
DataAcq
NaN
DevCtl
State of Actual
Inputs
String
Range
Length: 12
characters
Related
Parameters
Notes
No
ERRFL, NNUMERIC.
Determined CEE
by ACCLOCK
No
NNUMERIC.
No
View Only
CEE
No
STATETEX No
T[0]
View Only
CEE
No
DIPVMAP[0..15],
GPV, GPVAUTO,
NUMDINPTS,
NUMSTATES, PV,
PVSOURCE,
STATETEXT[0..6]
Access is illegal if
NUMDINPTS = 0.
PVAUTO is a String set equal
to STATETEXT(GPVAUTO).
STATETEXT[6] [State2] is
illegal if NUMSTATES = 2.
155
Specific to
Block(s)
Description
Data Type
PVAUTOSTS
DataAcq
PVCHAR
DataAcq
PV Characterization Enumeration
Option: Defines the PVCHAR
characterization to
be used for
characterizing the PI
value.
PVCONN
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
No
View Only
CEE
No
Yes
Application
Developer
CEE
No
Related
Parameters
Notes
156
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
PVEQN
Totalizer, Pulse
Input Totalizer
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
See below.
EqA (0)
Yes
Engineer
CEE
No
Related
Parameters
Notes
Range
EqA (0)
EqB (1)
EqC (2)
EqD (3)
EqE (4)
EqF (5)
PVERSION
SR
Platform Version.
8-Bit
Identifies the major Unsigned
revision of the RM. Integer
0 to 255
No
View Only
CEE
No
PVEUHI
DataAcq, PID,
PIDFF, PosProp,
RampSoak.
Greater-than
PVEULO and
less-than or
equal to
PVEXHILM.
100.0
Yes
Engineer
CEE
No
PVEULO
DataAcq, PID,
PIDFF, PosProp,
RampSoak
Less-than
PVEUHI and
Greater-than
or equal to
PVEXLOLM.
0.0
Yes
Engineer
CEE
No
PVEXHIFL
DataAcq
No
View Only
CEE
No
PVEXHILM
DataAcq
Greater-than
or equal to
PVEUHI.
Yes
Engineer
CEE
No
102.9
157
Specific to
Block(s)
Description
Data Type
PVEXLOFL
DataAcq
PVEXLOLM
DataAcq
PVFL
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
No
View Only
CEE
No
Less than or
equal to
PVEULO
-2.9
Yes
Engineer
CEE
No
Flag
Off (0)
On (1)
Off (0)
No
Defined by
ACCLOCK
CEE
No
DIC
Boolean
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
PVFL[0..2]
DevCtl
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
PVFL[0..511]
REQFLAGARRAY,
RSPFLAGARRAY
Array of Boolean
Boolean
values to be read
from or written to
the third-party
device. Stores are
accepted to this
parameter only if the
COMMAND
indicates that this is
a write block.
Off (0)
On (1)
Off (0)
Yes
Operator
CEE
No
PVFL[1..512]
SIFLAGARRCH
Off (0)
On (1)
Off (0)
Yes
Determined CEE
by ACCLOCK
No
Related
Parameters
Notes
PV, STATETEXT[0..1],
STATE0, STATE1
GPV, PV,
DIPVMAP[0..15],
NUMDINPTS,
NUMSTATES
Access is illegal if
NUMDINPTS = 0.
PVFL[2] is illegal if
NUMSTATES =2.
ERRFL, NFLAG.
158
Parameter
Parameter
Specific to
Block(s)
Description
PVFL[1..1000]
FLAGARRAY
PVFORMAT
Data Type
Range
Default
Config
Load
Access
Lock
Off(0)
On(1)
Off(0)
Yes
DataAcq, Numeric,
PID, PIDFF, PosProp,
Auxcalc, Genlin,
Totalizer, LeadLag,
Deadtime, Pulse
Input Totalizer,
NUMERICARRAY.
PVHHALM.DB
DataAcq
PVHHALM.DBU
DataAcq
Active
Connector
Related
Parameters
Determined CEE
by ACCLOCK
No
NFLAG.
D0 (-XXXXXX.) D1
Yes
D1 (-XXXXX.X) (-XXXXX.
D2 (-XXXX.XX) X)
D3 (XXX.XXX)
Engineer
CEE
No
PV, SP.
No
Operator
CEE
No
PV, PVHHALM.DBU,
PVHHALM.FL,
PVHHALM.PR,
PVHHALM.SV,
PVHHALM.TM,
PVHHALM.TP.
Percent (0)
EU (1)
No
Engineer
CEE
No
PV, PVHHALM.DB,
PVHHALM.FL,
PVHHALM.PR,
PVHHALM.SV,
PVHHALM.TM,
PVHHALM.TP.
Percent
(0)
Residence
Notes
159
Specific to
Block(s)
Description
Data Type
PVHHALM.FL
DataAcq
PVHHALM.PR
DataAcq
PVHHALM.SV
DataAcq
PVHHALM.TM
PVHHALM.TP
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Off (0): PV
Off (0)
High High
alarm is not
active; PV is
less than
PVHHALM.TP
On (1): PV
High High
alarm is
active; PV is
greater than
or equal to
PVHHALM.TP
No
View Only
CEE
No
None (0)
Journal (1)
Low (2)
High (3)
Urgent (4)
Low (2)
Yes
Engineer
CEE
No
0.0
Yes
Engineer
CEE
No
DataAcq
0 to 60
No
Engineer
CEE
No
DataAcq
NaN or
PVHIALM.TP
to PVEUHI.
NaN
Yes
Engineer
CEE
No
PV, PVHHALM.DB,
PVHHALM.DBU,
PVHHALM.FL,
PVHHALM.PR,
PVHHALM.SV,
PVHHALM.TP.
Notes
160
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
PVHIALM.DB
DataAcq
PVHIALM.DBU
DataAcq
PVHIALM.FL
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
No
Operator
CEE
No
PV, PVHIALM.DBU,
PVHIALM.FL,
PVHIALM.PR,
PVHIALM.SV,
PVHIALM.TM,
PVHIALM.TP
Percent (0)
EU (1)
No
Engineer
CEE
No
PV, PVHIALM.DB,
PVHIALM.FL,
PVHIALM.PR,
PVHIALM.SV,
PVHIALM.TM,
PVHIALM.TP
DataAcq
Off (0): PV
Off (0)
High alarm is
not active; PV
is less than
PVHIALM.TP.
On (1): PV
High alarm
present; PV is
greater than
or equal to
PVHIALM.TP
for the
configured
alarm time.
No
View Only
CEE
No
PVHIALM.PR
DataAcq
None (0)
Journal (1)
Low (2)
High (3)
Urgent (4)
Low (2)
Yes
Engineer
CEE
No
PVHIALM.SV
DataAcq
Yes
Engineer
CEE
No
Percent
(0)
161
Specific to
Block(s)
Description
PVHIALM.TM
DataAcq
PVHIALM.TP
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
0 to 60
No
Engineer
CEE
No
PV, PVHIALM.DB,
PVHIALM.DBU,
PVHIALM.FL,
PVHIALM.PR,
PVHIALM.SV,
PVHIALM.TP
DataAcq
NaN or
NaN
PVLOALM.TP
to
PVHHALM.TP
Yes
Engineer
CEE
No
PVHILM
Numeric
Greater than
PVLOLM
Yes
Engineer
CEE
No
PVLOLM, PV.
PVHISIGCHG.CT
DataAcq
No
View Only
CEE
No
PVHISIGCHG.TP
PVHISIGCHG.TP
DataAcq
Yes
Engineer
CEE
No
PVHISIGCHG.CT
NaN, or
greater-than
0.0.
NaN
NaN
162
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
PVLLALM.DB
DataAcq
PVLLALM.DBU
DataAcq
PVLLALM.FL
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Yes
Operator
CEE
No
PV, PVLLALM.DBU,
PVLLALM.FL,
PVLLALM.PR,
PVLLALM.SV,
PVLLALM.TM,
PVLLALM.TP.
Percent (0)
EU (1)
Yes
Engineer
CEE
No
PV, PVLLALM.DB,
PVLLALM.FL,
PVLLALM.PR,
PVLLALM.SV,
PVLLALM.TM,
PVLLALM.TP.
DataAcq
No
View Only
CEE
No
PVLLALM.PR
DataAcq
None (0)
Journal (1)
Low (2)
High (3)
Urgent (4)
Low (2)
Yes
Engineer
CEE
No
PVLLALM.SV
DataAcq
Yes
Engineer
CEE
No
Percent
(0)
Notes
163
Specific to
Block(s)
Description
PVLLALM.TM
DataAcq
PVLLALM.TP
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
0 to 60
Yes
Engineer
CEE
No
PV, PVLLALM.DB,
PVLLALM.DBU,
PVLLALM.FL,
PVLLALM.PR,
PVLLALM.SV,
PVLLALM.TP.
DataAcq
Yes
Engineer
CEE
No
PVLOALM.DB
DataAcq
Yes
Operator
CEE
No
PV, PVLOALM.DBU,
PVLOALM.FL,
PVLOALM.PR,
PVLOALM.SV,
PVLOALM.TM,
PVLOALM.TP
PVLOALM.DBU
DataAcq
Percent (0)
EU (1)
No
Engineer
CEE
No
PV, PVLOALM.DB,
PVLOALM.FL,
PVLOALM.PR,
PVLOALM.SV,
PVLOALM.TM,
PVLOALM.TP.
Percent
(0)
164
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
PVLOALM.FL
DataAcq
PVLOALM.PR
DataAcq
PVLOALM.SV
DataAcq
PVLOALM.TM
PVLOALM.TP
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
No
View Only
CEE
No
None (0)
Journal (1)
Low (2)
High (3)
Urgent (4)
Low (2)
Yes
Engineer
CEE
No
0.0
Yes
Engineer
CEE
No
DataAcq
0 to 60
0.0
No
Engineer
CEE
No
DataAcq
NaN, or
PVLLALM.TP
to
PVHIALM.TP
NaN
Yes
Engineer
CEE
No
Related
Parameters
Notes
The flag is set only when PV
is below the trip point for the
configured alarm time.
PV, PVLOALM.DB,
PVLOALM.DBU,
PVLOALM.FL,
PVLOALM.PR,
PVLOALM.SV,
PVLOALM.TP.
165
Specific to
Block(s)
Description
Data Type
PVLOLM
Numeric
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Real number
less than
PVHILM
NaN
Yes
Engineer
CEE
No
PVHILM, PV
PVLOSIGCHG.CT DataAcq
No
View Only
CEE
No
PVLOSIGCHG.TP
PVLOSIGCHG.TP DataAcq
NaN
No
Engineer
CEE
No
PVLOSIGCHG.CT
NaN, or
greater-than
0.0.
Re-alarming is disabled if
PVLOSIGCHG.TP = NaN.
166
Parameter
Parameter
Specific to
Block(s)
Description
PVMANOPT
PID, PIDFF
PosProp
Data Type
Range
Default
Config
Load
See below.
ShedHold Yes
(1)
Access
Lock
Residence
Active
Connector
Related
Parameters
Engineer
CEE
No
PVSTS, ESWENB,
MODE, MODEATTR,
OP
Notes
Range
Do nothing (i.e., behave the same as if PVSTS = Normal).
ShedHold (1):
ShedLow (2):
ShedHigh (3):
ShedSafe (4):
PVP
PVRAW
AIC
Process Variable
from Analog Input
device.
64-Bit Real
Number
PVRAW
[0..numChans-1]
AIM
Process Variable
from Analog Input
device, indexed by
channel number.
64-Bit Real
Number
NO_SHED
Idle
SHEDHIGH
Raise
SHEDLOW
Lower
SHEDSAFE
Depends on
Safe State
SHEDHOLD Idle
ShedHold Yes
(1)
Engineer
CEE
No
PVSTS, ESWENB,
MODE, MODEATTR,
OP
NaN
No
View Only
CEE
No
No
View Only
CEE
No
No
View Only
CEE
No
167
Specific to
Block(s)
Description
Data Type
PVSOURCE
DataAcq, DevCtl
PVSRC
Auxcalc
PVSRCOPT
DevCtl, DataAcq
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Yes
DataAcq:
Operator
DevCtl:
ViewOnly,
Operator
(see Notes)
CEE
No
Access illegal if
NUMDINPTS = 0.
PVSOURCE may not be set =
Track if NUMDOUTS = 0.
ViewOnly and defaulted to
Auto if PVSRCOPT =
OnlyAuto.
If PVSOURCE is not Man and
the function block is
InActive, PV is defaulted to
Null.
Engineer
CEE
No
PVSTSSRC
Engineer
CEE
No
Sub (0):PV
Auto (2)
value is
provided by a
user program.
Man (1):PV
value is
provided by
the operator
Auto (2):PV
value is
fetched from
another
function block.
OnlyAuto
OnlyAuto Yes
(0):PV may
(0)
only be
fetched from
another
function
block, via an
active input
connection;
PV source
selection is
not available.
All (1):PV may
be fetched
from another
function block,
or provided by
an operator or
a user
program, it
depends on
the
PVSOURCE.
DevCtl Only:
Access is illegal if
NUMDINPUTS = 0.
If set to OnlyAuto, and the
function block is Inactive, PV
is set to Null.
168
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
PVSTS
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
See below.
Bad (0)
No
View Only
CEE
No
PV, PVVALSTS
Notes
Range
The PV value was bad and replaced with NaN.
Bad (0):
Uncertain (1):
Normal (2):
Manual (3):
No
View Only
CEE
No
PV, PVSTS,
PVSTSFL.BAD,
PVSTSFL.MAN,
PVSTSFL.NORM,
PVSTSFL.UNCER.
AIC
Good (0)
No
View Only
CEE
No
PV, PVVALSTS
DIC
PV Status
Boolean
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
DIM: PV Status
DOM: Echoback
Status
Boolean
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
PVSTS[0..63]
REQNUMARRAY,
RSPNUMARRAY
Array of Status
Enumeration
Values. These
values are obtained
from the Status of
the last request.
View Only
CEE
No
PVSTS[1..64]
SINUMARRCH
Bad (0)
Uncertain (1)
Normal (2)
Manual (3)
No
View Only
CEE
No
ERRFL, PV[1..64].
PVSTSFL.BAD
No
View Only
CEE
No
PV, PVSTS,
PVSTSFL.MAN,
PVSTSFL.NORM,
PVSTSFL.UNCER,
PVVALSTS.
PVSTSFL.MAN
Manual Process
Boolean
Variable (PV) Status
Flag - Indicates that
the PVSTS is
Manual.
No
View Only
CEE
No
PV, PVSTS,
PVSTSFL.BAD,
PVSTSFL.NORM,
PVSTSFL.UNCER,
PVVALSTS.
Normal
(2)
169
Deadtime, Genlin,
Leadlag, Totalizer
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
PVSTSFL.NORM
Normal Process
Boolean
Variable (PV) Status
Flag - Indicates that
the PVSTS is
Normal.
No
View Only
CEE
No
PV, PVSTS,
PVSTSFL.BAD,
PVSTSFL.MAN,
PVSTSFL.UNCER,
PVVALSTS.
No
View Only
CEE
No
PV, PVSTS,
PVSTSFL.BAD,
PVSTSFL.MAN,
PVSTSFL.NORM,
PVVALSTS.
PVSTSSRC
Auxcalc
Engineer
CEE
No
PVSRC
PVTRAKOPT
Yes
Operator
CEE
No
PVVAL
DIC
Process Value.
Boolean
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
PVVAL
[0..numChans-1]
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
Notes
SP is set equal to PV if
PVTRAKOPT = Track and the
function block is:
in manual mode.
being initialized from a
secondary.
undergoing a 1-shot
initialization.
170
Parameter
Parameter
Specific to
Block(s)
PVVALSTS
Description
Data Type
Range
Default
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
No
View Only
CEE
Default
Connector:
Input
PV, PVSTS
No
View Only
CEE
No
PV, PVSTS
PVVALSTS[0..63]
REQNUMARRAY,
RSPNUMARRAY
No
View Only
CEE
No
PVVALSTS[1..64]
SINUMARRCH
No
View Only
CEE
No
ERRFL, PVFL[1..512]
This structure is
automatically used when the
block fetching PVFL[i] is
capable of interpreting the
ValueStatus structure.
PVVALSTS[0..511] SIFLAGARRCH
No
View Only
CEE
No
ERRFL, PVFL[1..512]
This structure is
automatically used when the
block fetching PVFL[i] is
capable of interpreting the
ValueStatus structure.
RSPFLAGARRAY
No
View Only
CEE
No
PWMPERIOD
PWM Channel
PWM Period in
Seconds
64-Bit Real
Number
10
Yes
Engineer
CEE
No
PWMPERIOD is configured
on the PWM Channel block.
PWMPERIOD
[0..numChans-1]
DOM
PWM Period in
Seconds
64-Bit Real
Number
10
No
View Only
CEE
No
PWMPERIOD is not
configured on the DOM.
171
Config
Load
Specific to
Block(s)
Description
SR, RS
QUALPROGA
RM
Qualification
progress indication
for each module in
the host chassis
SR, RS
RAISEDEADTM
PosProp,
PidPosProp
RAISEDESC
PosProp,
PidPosProp
Raise Output
Descriptor.
RAISELMFL
PosProp,
PidPosProp
RAISERATE
PosProp,
PidPosProp
0.0 to 100.0
RAISETIME
PosProp,
PidPosProp
MINPULSER,
Lesser of
MAXPULSER
and
CYCLETIME.
RAMPRATE
RampSoak
[1..NUMPROFILES
] [1..NUMRAMP
SOAK]
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Off (0)
On (1)
Off (0)
Yes
Engineer
CEE
No
8-Bit
Unsigned
Integer [20]
0 to 255
No
View Only
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
Boolean
Off (0)
On (1)
Off (0)
Yes
Engineer
CEE
No
No
View Only
CEE
No
Yes
Engineer
SR
No
No
Other
Function
Block
CEE
No
100%/sec Yes
.
Supervisor
CEE
No
No
View Only
CEE
Yes
Supervisor
CEE
String
Real
Raise
NaN
Related
Parameters
Notes
No
MINPULSER
No
NUMPROFILES,
Negative values are
NUMRAMPSOAK
accepted to allow ramping
[1..NUMPROFILES], down.
SOAKTIME
[1..NUMPROFILES]
[1..NUMRAMPSOAK]
, SOAKVAL
[1..NUMPROFILES]
[1..NUMRAMPSOAK]
, STARTOPT,
STARTSEG
[1..NUMPROFILES].
172
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
RAMSCRUBERRS CPM
Indicates presence
of RAM error when
On.
Boolean
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
RAMSWEEPERR
CPM
Indicates presence
of RAM error when
On.
Boolean
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
RATE
NAN, or
greater-than
or equal-to
zero.
0.0
Yes
Engineer
CEE
No
RDNCAPABILITY CPM
No
View Only
CEE
No
RDNCHASSISID
View Only
CEE
No
CPM
Off (0)
On (1)
Related
Parameters
RDNCHASSISID
Notes
173
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
RDNDELAYAVG
CPM
Redundancy Delay
Average
64-Bit Real
Number
0.0 to 100.0
0.0
No
View Only
CEE
No
RDNDELAYMAX,
STATSRESET
RDNDELAYMAX
CPM
Redundancy Delay
Maximum
64-Bit Real
Number
0.0 to 100.0
0.0
No
View Only
CPM
No
RDNDELAYMAX,
STATSRESET
Historical maximum
redundancy delay Central
Processing Unit (CPU) value
observed since last store to
STATSRESET.
RDNSYNCSTATE CPM
Control Processor
Module (CPM)
Synchronization
State
View Only
CEE
No
RDNCAPABILITY
RDNXFERAVG
CPM
Greater-than 0.0
or equal-to 0.0
No
View Only
CEE
No
RDNXFERMAX,
STATSRESET
RDNXFERMAX
CPM
Greater-than 0.0
or equal-to 0.0
No
View Only
CEE
No
RDNXFERAVG,
STATSRESET
Historical maximum of
Control Processor Module
(CPM) generated redundancy
private path throughput
since last store to
STATSRESET.
READINESS
RM
No
174
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
READINESSA
RM
Enumeration
[20]
No
READYFL
All Exchange
Library Request
Array function
blocks:
REQFLAGARRAY,
REQNUMARRAY,
REQTEXTARRAY
Off(0)
On(1)
Off(0)
No
View Only
CEE
No
RECDESC [1..50]
SCM
Recipe Parameter
Descriptor
String
Length: 23
characters
Null
String
Yes
Engineer
CEE
RECMATCODE
[1..50]
SCM
Recipe Parameter
Material Code
Yes
Engineer/Ap CEE
plication
Developer
RECOVMSGIDX
RM
0 to 65535
No
Recipe Parameter
Scale Allowed
Option
Boolean
Off (0)
On (1)
Off (0)
Yes
Engineer
RECTARGET
[1..50]
Recipe Parameter
Target Value
64-Bit Real
Number
NaN
Yes
Operator
SCM
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
No
NUMRECPARMS
No
NUMRECPARMS
CEE
No
NUMRECPARMS
CEE
No
NUMRECPARMS
175
Specific to
Block(s)
Description
Data Type
RECTARGETMAX SCM
[1..50]
Recipe Parameter
Target Value
Maximum
64-Bit Real
Number
RECTARGETMIN
[1..50]
SCM
Recipe Parameter
Target Value
Minimum
64-Bit Real
Number
REDTAG
DevCtl,
All RegCtl Blocks:
AutoMan, Fanout,
OvrdSel, PID, PIDFF,
PosProp,
PulseCount,
PulseLength,
RampSoak,
RemCas, RatioBias,
RegCalc, and
Switch.
REDUNSTATE
RM
No
REDUNSTATEA
RM
No
REFRESHMS
RM
Refresh Interval in
milliseconds.
0 to
4294967295
No
View Only
Not Loaded
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
REMSOAKTIME
RampSoak
Remaining Soak
Real
Time for the current
SOAK segment.
0.0 - 120.0
0.0
No
Operator
No
32-Bit
Unsigned
Integer
Range
Default
NaN
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Yes
Engineer
CEE
No
NUMRECPARMS
Yes
Engineer
CEE
No
NUMRECPARMS
No
Engineer
CEE
No
DevCtl only:
MODEATTR,
NUMDOUTS
CEE
SOAKTIME
[1..NUMPROFILES]
[1..NUMRAMPSOAK]
Notes
DevCtl:
Illegal if NUMDOUTS = 0.
Illegal if MODEATTR is not
Operator.
Illegal if present state is
Momentary.
RegCtl MODE must be
Manual before REDTAG can
be turned On.
176
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
RESADDR [1..10]
SCM
Resume Address
Name
RESADDRFUTUR SCM
[1..10]
Resume Address
Future Name
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
BlockId
Null
String
No
Engineer
CEE
No
RESADDRFUTUR
RESADDR [i] contains the
[1..10], UPDRESOPT, name (eg.
RESADDRN [1..10]
SCMName.StepName) of the
Step in thread i that will
become the active step on
return to the Main or
Interrupt handlers from an
exception.
It can only be set to a valid
step name in the Main or
Interrupt handler that was
preempted.
RESADDR [1..10] is a BlockId
parameter and not supported
in expressions. Its
Integer-32 Partner Parameter
RESADDRN [1..10] can be
used in Transition Condition
expressions and Step Output
expressions.
BlockId
Null
String
No
Engineer
CEE
No
RESADDR [1..10],
UPDRESOPT,
RESADDRFUTRN
[1..10]
177
Specific to
Block(s)
Description
Data Type
RESADDRFUTRN SCM
[1..10]
Resume Address
Future Number
Resume Address
Number
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
32-Bit Integer
No
Engineer
CEE
No
RESADDR [1..10],
UPDRESOPT
32-Bit Integer
No
Engineer
CEE
No
RESADDRFUTUR
RESADDR [i] contains the
[1..10], UPDRESOPT, name (eg.
RESADDR [1..10]
SCMName.StepName) of the
Step in thread i that will
become the active step on
return to the Main or
Interrupt handlers from an
exception.
It can only be set to a valid
step name in the Main or
Interrupt handler that was
preempted.
RESADDRN [1..10] may be
used in Transition Condition
expressions and Step Output
expressions, whereas
RESADDR [1..10] (a BlockId
parameter) is not supported
in expressions.
178
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
RESETFL
Totalizer, Pulse
Input Totalizer
Reset Totalizer
Boolean
Command Flag When this flag
changes from Off to
On, the Totalizer
function block resets
the PV to equal the
value of the
RESETVAL variable.
RESETFL (cont.)
Timer
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
No
Other
Function
Block
CEE
No
RESETVAL, STARTFL,
STOPFL
Reset Command
Boolean
Flag Provides
ability to issue Reset
command to the
Timer function block
using Boolean
parameter.
No
Other
Function
Block
CEE
No
No
Operator
CEE
No
SO,
DevCtl
Boolean
Maintenance
Statistics Reset Flag
When set from Off
to On, resets all
Maintenance
Statistics to their
default or 0 values.
No
Operator,
Other
Function
Block (see
Notes)
CEE
No
MAINTOPT,
MAXTIME [0..2],
MAXTRANS [0..2],
NUMSIOVRD,
NUMTRANS [0..2],
REDTAG, STATETIME
[0..2].
RESETFL [0..7]
No
Engineer
CEE
No
SO [6..7]
RESETTIMR
RampSoak
Reset Segment
Timer On Profile.
Engineer
CEE
No
Boolean
Range
Default
Notes
Specific to
Block(s)
Description
Data Type
Range
RESETVAL
Totalizer, Pulse
Input Totalizer
RESTARTFL
Timer
Restart Command
Boolean
Flag - Provides
ability to issue
Restart command to
the Timer function
block.
RESTARTOPT
DevCtl
All RegCtl Blocks:
AutoMan, Fanout,
OvrdSel, PID, PIDFF,
PosProp,
PulseCount,
PulseLength,
RampSoak,
RemCas, RatioBias,
RegCalc, and
Switch.
RFB
PidExtReset
Reset feedback
value.
ROCNEGALM.FL
DataAcq
Negative
Rate-of-Change
Alarm Flag
Indicates if a
negative
rate-of-change
alarm has been
issued.
Boolean
Off (0):
Off (0)
Negative
rate-of-chang
e alarm does
not exist.
On (1):
Negative
rate-of-chang
e alarm
present.
No
View Only
CEE
No
ROCNEGALM.PR DataAcq
Negative
Rate-of-Change
Alarm Priority
Enumeration
ALPRIOR
None (0)
Journal (1)
Low (2)
High (3)
Urgent (4)
Yes
Engineer
CEE
No
Off (0)
On (1)
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
0.0
Yes
Engineer
CEE
No
RESETFL
Off (0)
No
Other
Function
Block
CEE
No
RESETFL, STOPFL,
STARTFL,
COMMAND
None (0)
Yes
Engineer
CEE
No
HOLDOPT,
Illegal if
LASTOPREQ,
ControlModule.SCMOPT =
LASTOPTYPE,
None.
LASTSTEP, OPREQ,
OPTYPE, SAFEOP,
SCMASTEP [1..10],
SCMOPT,
SCMSTATE,
STARTOPT, STOPOPT
An Off-to-On transition of
RESTARTFL causes the timer
to restart.
Low (2)
180
Parameter
Parameter
Specific to
Block(s)
Data Type
ROCNEGALM.SV DataAcq
Negative
Rate-of-Change
Alarm Severity
16-Bit Integer 0 to 15
ROCNEGALM.TP DataAcq
Negative
64-Bit Real
Rate-of-Change
Number
Alarm Trip Point (in
Engineering Units
per minute) Maximum change in
the Process Variable
(PV), in the negative
direction, before a
negative
rate-of-change
alarm is issued.
NaN, or
greater-than
or equal-to
0.0.
ROCPOSALM.FL
DataAcq
Positive
Rate-of-Change
Alarm Flag Indicates if a
positive
rate-of-change
alarm has been
issued.
Boolean
ROCPOSALM.PR DataAcq
Positive
Rate-of-Change
Alarm Priority
Enumeration
ALPRIOR
ROCPOSALM.SV DataAcq
Positive
Rate-of-Change
Alarm Severity
16-Bit Integer 0 to 15
ROCPOSALM.TP
Positive
64-Bit Real
Rate-of-Change
Number
Alarm Trip Point (in
Engineering Units
per minute) Maximum change in
the Process Variable
(PV), in the positive
direction, before a
positive
rate-of-change
alarm is issued.
DataAcq
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Yes
Engineer
CEE
No
NaN
Yes
Engineer
CEE
No
Off (0):
Off (0)
Positive
rate-of-chang
e alarm does
not exist.
On (1):
Positive
rate-of-chang
e alarm
present.
No
View Only
CEE
No
PV, ROCPOSALM.PR,
ROCPOSALM.SV,
ROCPOSALM.TP.
None (0)
Journal (1)
Low (2)
High (3)
Urgent (4)
Low (2)
Yes
Engineer
CEE
No
PV, ROCPOSALM.FL,
ROCPOSALM.SV,
ROCPOSALM.TP.
Yes
Engineer
CEE
No
PV, ROCPOSALM.FL,
ROCPOSALM.PR,
ROCPOSALM.TP.
NaN
Yes
Engineer
CEE
No
NaN, or
greater-than
or equal-to
0.0.
Related
Parameters
Notes
181
Description
Specific to
Block(s)
Description
Data Type
Range
Default
RSTPROCESSED
SCM
Reset Processed
Command
Boolean
Off (0)
On (1)
Off (0)
RT
RatioBias
RTLOLM to
RTHILM
Config
Load
Access
Lock
Residence
Operator
Active
Connector
Related
Parameters
Notes
RT is an initializable input.
No
Yes
Operator
CEE
No
RTHILM, RTLOLM
No
View Only
CEE
No
RatioBias function
block maintains
separate BACKCALC
records for each of
its primaries, i.e.,
RTBACKCALOUT for
RT primary and
X1BACKCALOUT for
X1 primary.
CEE
No
RTLOLM
RTHILM
RTBACKCALOUT RatioBias
RTCONN
RatioBias
RT Connector
RTHIFL
RatioBias
RT High Flag
Boolean
Off (0)
On (1)
Off (0)
RTHILM
RatioBias
Real
Greater-than
RTLOLM
100.0
RTLOFL
RatioBias
RT Low Flag
Boolean
Off (0)
On (1)
Off (0)
RTLOLM
RatioBias
Real
Less-than
RTHILM
0.001
Yes
Engineer
CEE
No
RTPPRESENT
AIM
RTP Present.
Boolean
Off (0)
On (1)
Off (0)
Yes
Application
Developer
CEE
No
RV
Timer
0 to
0
2,147,483,647
(2^31-1)
No
View Only
CEE
No
RS, SR
S input value
Off (0)
On (1)
Yes
Engineer
CEE
No
S1
PidExtReset
Tracking control
switch.
Application
Developer
Boolean
Off (0)
View Only
Yes
Engineer
View Only
RTPPRESENT is only
configurable on the
Thermocouple module.
SP, PV, SO,
TIMEBASE
182
Parameter
Parameter
Specific to
Block(s)
SAFEOP
Description
Data Type
Range
RegCtl Blocks:
Safe Output (OP)
AutoMan, Fanout, Value (in Percent)
OvrdSel, PID, PIDFF,
PosProp,
PulseCount,
PulseLength,
RampSoak,
RemCas, RatioBias,
RegCalc, and
Switch.
64-Bit Real
Number
DevCtl
SAFEOPCMD
PosProp,
PidPosProp
SAFEOUTPUT
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
NaN, or
NaN
OPEXLOLM to
OPEXHILM
Yes
Engineer
CEE
No
Enumeration
GENSTATE
Yes
Engineer
No
CEE
DIPVMAP [0..15],
STOPOPT, GOP,
GOPREQ, GPV,
HOLDOPT,
NUMDOUTS,
NUMSTATES, OI
[0..2], OP, OPCMD
[0..2], OPDOMAP
[0..3] [1..3], OPREQ,
PV, RESTARTOPT,
SEALOPT, SI,
STARTOPT
Enumeration
PULSECMD
Idle (0)
Raise (1)
Lower (2)
Idle (0)
Yes
Operator
CEE
No
PULSECMD,
Off (0)
On (0)
Off (0)
Yes
Application
Developer
CEE
No
SAFEOUTPUT
[6..7]
Off (0)
On (0)
Off (0)
Yes
Application
Developer
CEE
No
SAFEREDTAG
DevCtl
Off (0)
On (1)
Off (0)
Yes
Engineer
CEE
No
Illegal if NUMDOUTS = 0.
SAFEOP may not be assigned
to a Momentary State.
S2 is illegal if NUMSTATES =
2.SAFEOP (cont.)
Illegal if NUMDOUTS = 0.
183
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
SAFESTATE
[0..numChans-1]
DOM
Safe State
Boolean
Specifies a safe
output state to be
assumed in the
event of a controller
failure or loss of
communication
between the
controller and IOM.
Off (0)
On (1)
Off (0)
Yes
Application
Developer
CEE
No
FAILSTATE
[0..numChans-1]
SAMPLERATE
AIM, AOM
(Note that although
a part of the
configuration
assembly,
SAMPLERATE is not
used for output
modules.)
25 msec, No
with the
following
exception
s:
50 msec
for
Thermoco
uple and
RTD AIM
250 msec
for
Non-Isola
ted
(high-den
sity) AIM
AIM:
Application
Developer
AOM: View
Only
CEE
No
SIPTYPE
[0..numChans-1]
SC.BYPPERM
Step
Off (0)
Yes
Engineer
CEE
No
SC.BYPREQ, SC.FL
SC.BYPREQ
Step
None (2)
No
Operator
CEE
No
Off (0)
On (1)
184
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
SC.CONFIGCODE Step
CEE
No
SC.CONFIGDESC Step
Maximum of None
39 characters.
No
View Only
CEE
No
SC.CONFIGSTS
Step
No
View Only
CEE
No
SC.DESC
Step
Yes
Application
Developer
SR
No
SC.EXECCODE
Step
No
View Only
CEE
No
SC.CONFIGCODE,
SC.CONFIGDESC
185
Specific to
Block(s)
Description
Data Type
SC.EXECDESC
Step
SC.EXECSTS
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Maximum of None
39 characters.
No
View Only
CEE
No
Step
No
View Only
CEE
No
SC.EXPR
Step
Yes
Application
Developer
SR
No
SC.EXPRPCODE
Step
Internal parameter
for system use only.
SC.FL
Step
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
SC.INVOKFL
Step
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
SC.OPT
Step
Off (0)
On (1)
Off (0)
Yes
Application
Developer
CEE
No
SCANAREA
Maximum of 2 Null
characters
string
Application SCAN
Developer
RM only:
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
Related
Parameters
Notes
See SC.EXECSTS for
additional information.
SC.EXECCODE,
SC.EXECDESC
SC.FL
186
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
String
Maximum of
255
characters
Null
String
Application SCAN
Developer
RM only:
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
SCANCTRLLVL
0 to 255
200
Application SCAN
Developer.
RM only:
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
SCANEUHI
String
Maximum of
255
characters.
Null
String
Application SCAN
Developer
RM only:
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
SCANEULO
String
Maximum of
255
characters.
Null
String
Application SCAN
Developer
RM only:
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
Related
Parameters
Notes
187
Specific to
Block(s)
SCANGRPDTL
SCANPNTDTL
Description
Data Type
Range
Default
String
Maximum of
255
characters.
Null
String
Application SCAN
Developer
RM only:
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
String
Maximum of
255
characters
Null
String
Application SCAN
Developer.
RM only:
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
0 to 32,767
No
View Only
CEE
Null
String
Yes
Engineer
Manual
(4)
No
View Only
SCMASTEP [1..10] CM
Monitored
Sequential Control
Module (SCM)
Active Step
Integer
SCMID
CM
Sequential Control
Module Identifier
Entity Id
(Independent
Block Code)
SCMMODE
CM
Monitored
Enumeration None (0)
Sequential Control of SCMMODE Auto (1)
Module (SCM) Mode
SemiAuto (2)
SnglStep (3)
Manual (4)
Normal (5)
SCMMONITOR
SCM
Internal parameter
for system use only.
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
No
SCMOPT,
SCMMODE,
SCMSTATE
CEE
No
SCMOPT
CEE
No
188
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
SCMMONSRC
CM
Internal parameter
for system use only.
SCMNAME
CM
Yes
Application
Developer
SR
No
SCMOPT
CM
Sequential Control
Module (SCM)
Option
None (0)
Fixed (1)
Dynamic (2)
Yes
Application
Developer
CEE
No
SCMID
Enumeration
SCMOPT
None (0)
189
Specific to
Block(s)
Description
Data Type
Range
SCMSTATE
CM
Monitored
Enumeration
Sequential Control SCMSTATE
Module (SCM) State
SCSRC [1..6]
Step
Internal parameter
for system use only.
SDENUMTEXT
Type Convert
Enumeration Text
String
Maximum 12
characters
SEALOPT
DevCtl
Seal-in Option.
Enumeration
ENABLE
Disable (0)
Enable (1)
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
No
View Only
CEE
No
SDENUM Yes
0 to
SDENUM
63
Engineer
SR
No
Disable
(0)
Engineer
CEE
No
Loading (0)
Null (2)
Loaded (1)
Inactive (2)
Validated (3)
Running (4)
Complete (5)
Checking (6)
Idle (7)
Interrupting
(8)
Interrupted (9)
Restarting (10)
Restarted (11)
Holding (12)
Held (13)
Stopping (14)
Stopped (15)
Aborting (16)
Aborted (17)
CommErr (18)
Yes
GOP, GOPFINAL,
MOMSTATE,
NUMDOUTS,
NUMDINPTS, OP,
OPFINAL, SAFEOP
Notes
Illegal if NUMDOUTS = 0 or
NUMDINPTS = 0.
Function block must be
InActive to change
SEALOPT.
Illegal if MOMSTATE is not
NONE.
Illegal if Command Disagree
is not configured [All
CMDDISALM.TM [x] = 0].
190
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Secondary
Enumeration
Initialization Option ENBSTATE
Indicates if a
Regulatory Control
function block
should accept or
ignore initialization
requests, and
override feedback
data from the
secondary. There is
one option
parameter for each
secondary. (The
number of
secondaries
depends on the
function block type.)
Range
Default
Config
Load
Disable (0):
Ignore
initialization
and override
data from
secondary.
Enable (1):
Accept
initialization
and override
data from
secondary.
Access
Lock
Residence
Active
Connector
Related
Parameters
Engineer
CEE
No
BACKCALCIN,
BACKCALCIN [1..3],
BACKCALCIN [1..8]
SECINITOPT1
RampSoak
SECMODNAME
CPM, RM
BLOCKID
None
No
Engineer
SR
No
ABORTALM.PR
SECNAMESTRIN CPM, RM
G
String
None
Engineer
SR
No
ABORTALM.PR
SECTMPNAME
None
Application
Developer
SR
No
ABORTALM.PR
CPM, RM
Checked
(X)
Notes
No
191
Specific to
Block(s)
Description
Data Type
SELHANDLER
[1..8]
SELHANDLER
[1..8]
SCM
Selected Handler
Handle
BlockId
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Null
String
Yes
Engineer
CEE
No
TYPE
A handler of TYPE is
assigned by setting
SELHANDLER [i] to that
handlers name (eg.
SCMName.HandlerName).
For example, to change the
selected Hold Handler (TYPE
6) to another named
Long-Hold, the assignment
SELHANDLER [6] =
LONGHOLD.Name would be
made. The recommended
method of deselecting a
handler of TYPE i is to set
SELHANDLER [i] = 0.
The selected handler of a
given TYPE can only be
changed if it is not currently
executing. The Main handler
selection cannot be changed
once the SCM transitions to
Running. The Interrupt
handler selection cannot be
changed if the currently
selected Interrupt handler is
being preempted. The Null
and Edit handler selections
cannot be changed by the
user or program.
192
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
SELHANDLERN
[1..8]
SCM
Specifies the
32-Bit Integer
component number
(within the CM) of
the selected handler
of the SCM for each
handler type.
No
Engineer
CEE
No
SELHANDLER [1..8]
SELXDESC
Switch, OvrdSel,
RemCas
Selected Input
String
Descriptor 15-character
descriptor for the
currently-selected
input to the OvrdSel
and Switch function
blocks.
Length: 15
characters
Null
String
No
View Only
CEE
No
XDESC [1..8]
SELXFL [1..4]
OvrdSel
SELXFL [1] No
= On (1)
All others
=Off (0)
View Only
CEE
No
SELXINP
193
Specific to
Block(s)
Description
SELXFL [1..8]
Switch, OvrdSel
SELXINP
Data Type
Range
Default
Switch
Selection ID Integer
Identifies the
currently-selected
input to the function
block.
OvrdSel, RemCas
SENDFL
SENDFL [0..15]
Access
Lock
Residence
Active
Connector
Related
Parameters
SELXFL [1] No
= On (1)
All others
=Off (0)
Operator
CEE
No
SELXINP
1 to 8
No
Operator
CEE
No
SELXFL [1..8],
SELXDESC
Selection ID Integer
Identifies the
currently-selected
input to the function
block.
1 to 4
No
View Only
CEE
No
SELXFL [1..8],
SELXDESC
All Exchange
Library Request
Array function
blocks:
REQFLAGARRAY,
REQNUMARRAY,
REQTEXTARRAY
Off(0)
On(1)
Off(0)
No
View Only
CEE
No
Message
Send Flag
Off (0)
On (1)
Off (0)
Operator
CEE
Boolean
Config
Load
Notes
194
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
SENSORTYPE
[0..numChans-1]
AIM
Sensor Type
SERIALNUM
RM
0 to
4294967295
SHORT
DOC
Indicates that a
short circuit or
overload condition
exists.
Boolean
Short
condition does
not exist (0)
Short
condition
exists (1)
SHORT
[0..numChans-1]
DOM
Indicates that a
short circuit or
overload condition
exists.
Boolean
SI
DevCtl
Safety Override
Interlock
Boolean
No
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
No
OHMOFFSET
[0..numChans-1]
GOP, NUMDOUTS, OI
[0..2], OP, SAFEOP,
SIALM.FL,
SIALM.OPT,
SIALM.PR,
SIALM.SV.
No
Short
No
condition
does not
exist (0)
View Only
CEE
No
Short
condition does
not exist (0)
Short
condition
exists (1)
Short
No
condition
does not
exist (0)
View Only
CEE
No
Off (0)
On (1)
Off (0)
Engineer,
Other
Function
Block, (see
Notes)
CEE
No
No
195
Specific to
Block(s)
SIALM.FL
SIALM.OPT
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
DevCtl
Safety Override
All RegCtl Blocks: Alarm
AutoMan, Fanout,
OvrdSel, PID, PIDFF,
PosProp,
PulseCount,
PulseLength,
RampSoak,
RemCas, RatioBias,
RegCalc, and
Switch.
Boolean
Off (0)
No
View Only
CEE
No
SIFL, SIALM.OPT,
DevCtl Only: Illegal if
SIALM.PR, SIALM.SV NUMDOUTS = 0.
DevCtl Only: INALM,
HIALM, NUMDOUTS,
SI
DevCtl
Safety Interlock
Alarm Option
Enumeration
OVRDALOP
No
Yes
Yes
Engineer
CEE
No
SIFL, SIALM.FL,
Illegal if NUMDOUTS = 0.
SIALM.PR, SIALM.SV To change, function block
must be InActive.
Safety Interlock
Enumeration
Alarm Option ENBSTATE
Indicates if Safety
Interlock alarming is
enabled.
Yes
Engineer/Ap CEE
plication
Developer
No
SIFL, SIALM.FL,
SIALM.OPT
SIALM.PR, SIALM.SV
None (0)
Journal (1)
Low (2)
High (3)
Urgent (4)
Low (2)
Yes
Engineer
CEE
No
SIFL, SIALM.FL,
SIALM.OPT,
SIALM.SV
DevCtl Only:
NUMDOUTS, SI
Yes
Engineer
CEE
No
SIFL, SIALM.FL,
SIALM.OPT,
SIALM.PR
DevCtl Only:
NUMDOUTS, SI
SIALM.PR
DevCtl
Safety Interlock
All RegCtl Blocks: Alarm Priority
AutoMan, Fanout,
OvrdSel, PID, PIDFF,
PosProp,
PulseCount,
PulseLength,
RampSoak,
RemCas, RatioBias,
RegCalc, and
Switch.
Enumeration
ALPRIOR
SIALM.SV
DevCtl
Safety Interlock
All RegCtl Blocks: Alarm Severity
AutoMan, Fanout,
OvrdSel, PID, PIDFF,
PosProp,
PulseCount,
PulseLength,
RampSoak,
RemCas, RatioBias,
RegCalc, and
Switch.
16-Bit Integer 0 to 15
Notes
196
Parameter
Parameter
Specific to
Block(s)
SIFL
SIOPT
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Off (0)
On (1)
Off (0)
No
Other
Function
Block
CEE
Default
Connector:
Input
SIOPT, SIALM.FL,
SIALM.OPT,
SIALM.PR, SIALM.SV
See below.
ShedHold Yes
(1)
Engineer
CEE
No
SIFL, ESWENB,
MODE, MODEATTR,
OP
Safety Interlock
Enumeration
Option Indicates BADCTLOPT
what to do when
Safety Interlock Flag
(SIFL) is On.
No_Shed (0):
Notes
Range
MODE remains unchanged and OP is held at the last good value.
AIM, AOM
Channel Type /
Range Mode
Enumeration:
SIPTYPE
Enumeration:
RANGEMODE
(8-channel
AOM only)
SIPTYPE:
10V_Input (65)
RTD_SIP (66)
Thermocouple
(67)
10V_Output
(88)
4-20mA_Cur
(89)
RANGEMODE:
Voltage_Mod
e (0)
Current Mode
(1)
SLOTNUMBER
CPM, RM
Specified Yes
appropria
tely on a
per
module
basis.
Application
Developer
CEE
No
Engineer
SR
No
No
ABORTALM.PR,
197
Specific to
Block(s)
Description
SO
Timer, Transition
DOC
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
SP, PV, RV
Status Output
Boolean
Off (0)
On (1)
Off (0)
No
Operator
CEE
Yes
DOMSO
[0..numChans-1]
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
Output State
Boolean
Indicates current
state of the Output
associated with the
Pulse Input Channel.
No
Engineer
CEE
No
SO
SOAKTIME
RampSoak
[1..NUMPROFILES
]
[1..NUMRAMPSO
AK]
0.0 to 120.0
0.0
Yes
Supervisor
CEE
No
NUMRAMPSOAK
[1..NUMPROFILES],
RAMPRATE
[1..NUMPROFILES]
[1..NUMRAMPSOAK]
, SOAKVAL
[1..NUMPROFILES]
[1..NUMRAMPSOAK]
, STARTOP
[1..NUMPROFILES],
<STARTSEG
[1..NUMPROFILES]
SOAKVAL
RampSoak
[1..NUMPROFILES
]
[1..NUMRAMPSO
AK]
NaN
Yes
Supervisor
CEE
No
NUMRAMPSOAK
[1..NUMPROFILES],
RAMPRATE
[1..NUMPROFILES]
[1..NUMRAMPSOAK]
, SOAKTIME
[1..NUMPROFILES]
[1..NUMRAMPSOAK]
, STARTOP
[1..NUMPROFILES],
STARTSEG
[1..NUMPROFILES]
SO [6..7]
Data Type
Real
198
Parameter
Parameter
Specific to
Block(s)
SOCMDOFF
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Off (0)
On (1)
Off (0)
No
Operator
CEE
No
SO
SOCMDON
Off (0)
On (1)
Off (0)
No
Operator
CEE
No
SO
SOSOURCE
DOC
SOSTS
Boolean
Good (0)
Bad (1)
Good (0)
No
View Only
CEE
No
SO
SP
64-Bit Real
Number
SPLOLM to
SPHILM
0.0
Yes
Operator
CEE
Yes
Timer
Integer
0 to
0
2,147,483,647
(2^31-1)
Yes
Operator
CEE
No
Notes
Application
Developer
199
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
SPCONN
SPEUHI
Same as
PVEUHI
Same as
PVEUHI
No
View Only
CEE
No
PVEUHI, PVEULO,
SPEULO
SPEULO
Same as
PVEULO
Same as
PVEULO
No
View Only
CEE
No
PVEUHI, PVEULO,
SPEUHI
SPFORMAT
D0 (0)
D1 (1)
D2 (2)
D3 (3)
D1 (1)
No
View Only
No
PVFORMAT
Enumeration
PVFORMAT
200
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
SPHIFL
SPHILM
Range
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Off (0): SP
Off (0)
high limit is
not exceeded.
On (1): SP high
limit is
exceeded.
No
View Only
CEE
No
SPHILM
NaN, or
SPLOLM to
PVEUHI
100.00
Yes
Engineer
CEE
No
SPHIFL
SPLOFL
No
View Only
CEE
No
SPLOLM
SPLOLM
NaN, or
PVEULO to
SPHILM
0.00
Yes
Engineer
CEE
No
SPLOFL
SPP
NaN
No
Operator
CEE
No
SP
SPRATEREQ
No
Operator
CEE
No
CONTROLREQ,
SPTVREQ,
LASTRATEREQ,
RESTARTOPT,
SCMOPT
SPREQ
SPLOLM to
SPHILM
No
Operator
CEE
No
CONTROLREQ,
LASTSPREQ,
RESTARTOPT,
SCMOPT
64-Bit Real
Number
Default
Notes
201
Specific to
Block(s)
SPTV
SPTVDEVFL
SPTVDEVMAX
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
NaN or
SPLOLM to
SPHILM
No
Operator
CEE
No
SPTVP
Off (0):
Off (0)
Deviation is
within limits.
On (1):
Deviation
exceeds
maximum; Set
Point (SP)
ramping has
temporarily
stopped.
No
View Only
CEE
No
SPTVDEVMAX
See below.
NaN, or
greater than
0.0.
NaN
Notes
If the function block has a SP and PV input, the user can specify a maximum ramp deviation
(SPTVDEVMAX). If the maximum deviation is exceeded, SP ramping will stop until PV catches up
with the SP.
SPTVDEVMAX is the maximum deviation allowed during set point ramping, in engineering
units/min.
Guaranteed Maximum Ramp processing works as follows:
SPTVDEVMAX may be NaN or greter than zero. NaN means do not check ramp deviation.
If SPTVDEVMAX is not NaN, set point ramping stops when the absolute value of the deviation
(|PV - SP|) exceeds SPTVDEVMAX. The deviation flag (SPTVDEVFL) is set, and SPTVSTATE
remains in Run.
Ramping resumes as soon as the absolute value of the deviation returns within the limit. When
ramping resumes, the deviation flag (SPTVDEVFL) is reset.
Note: If the user has specified a ramp time, and ramping is interrupted by Guaranteed Max Ramp
processing, then the actual ramp time will be greater than the user-specified time.
Yes
Engineer
CEE
No
SPTVDEVFL
202
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
SPTVNORMRATE PID, PIDFF, PosProp Set Point (SP) Target 64-Bit Real
Value Normal Ramp Number
Rate - The rate that
the set point will
ramp, in engineering
units/min.
NaN, or
greater than
0.0.
NaN
Yes
Operator
CEE
No
SPTVTIME
SPTVOPT
Disable (0):
Disable
Target value (0)
processing is
not requested.
Enable (1):
Target value
processing is
requested.
Yes
Engineer
CEE
No
SPTVP
NaN
No
View Only
CEE
No
SPTV
SPTVRATE
NaN
No
View Only
CEE
No
SPTVTIME
SPTVREQ
No
Operator
CEE
No
SPRATEREQ
NaN, or
SPLOLM to
SPHILM
203
Specific to
Block(s)
Description
Data Type
SPTVSTATE
SPTVTIME
SRC
Auxcalc, RegCalc
SSTEPLOCK
SCM
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Off (0): No
Off (0)
target value
processing.
Preset (1):
Set-up the SP
target value
and ramp
time.
Run (2):
Perform the
SP ramping
function.
No
Operator
CEE
No
Greater than
or equal to
0.0.
Yes
Operator
CEE
No
SPTVRATE
Engineer
CEE
No
MODE
0.0
Related
Parameters
Notes
204
Parameter
Parameter
Specific to
Block(s)
Description
STARTFL
Totalizer, Pulse
Input Totalizer
STARTINDEX
Data Type
Range
Default
Start Totalizer
Boolean
Command Flag When this flag
changes from Off to
On, the Totalizer
function block starts
the accumulator.
Timer
Off (0)
On (1)
SIFLAGARRCH,
SINUMARRCH,
SITEXTARRCH
Starting Element
Index Identifies
the start of the
contiguous array in
the device.
STARTOP
RampSoak
[1..NUMPROFILES
]
STARTOPT
Starting State
Option - A
configurable
parameter that
specifies the action
the control device
takes, when
SCMSTATE is
Checking, Idle, or
Complete.
DevCtl,
All RegCtl Blocks:
AutoMan, Fanout,
OvrdSel, PID, PIDFF,
PosProp,
PulseCount,
PulseLength,
RampSoak,
RemCas, RatioBias,
RegCalc, and
Switch.
Enumeration
REGEXCOPT
None (0):
See below.
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Off (0): Do No
not start
the
accumula
tor
Other
Function
Block
CEE
No
RESETFL, STOPFL
Off (0)
No
Other
Function
Block
CEE
No
RESETFL, STOPFL,
RESTARTFL,
COMMAND
Yes
Application
Developer
CEE
No
0.0
Yes
Operator
CEE
No
STARTSEG
[1..NUMPROFILES]
None (0)
Yes
Engineer
CEE
No
STARTRATE,
STARTVAL
Range
No changes
Man (1):
Auto (2):
Cas (3):
FixedOP (4):
HoldPV (5):
Set SPREQ = PV
FixedSP (6):
Notes
An Off-to-On transition of
STARTFL starts the timer.
205
Specific to
Block(s)
Description
STARTRATE
STARTSEG
RampSoak
[1..NUMPROFILES
]
STARTVAL
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Yes
Engineer
CEE
No
STARTOPT
Greater than
zero
Yes
Operator
CEE
No
STARTOP
[1..NUMPROFILES]
OPEXLOLM to NaN
OPEXHILM,
when
STARTOPT =
FixedOP.
SPLOLM to
SPHILM,
when
STARTOPT =
FixedSP or
RampedSP.
(NaN, 0.0,
positive or
negative real
numbers)
Yes
Engineer
CEE
No
STARTOPT
206
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
STATE
Totalizer, Pulse
Input Totalizer
Timer
SCM
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Stopped (0)
Stopped
Running (1) - (0)
(accumulating)
No
View Only
CEE
No
RESETFL, STARTFL,
STOPFL
Enumeration
TIMERSTATE
Stopped (0)
Running (1)
Stopped
(0)
No
View Only
CEE
No
COMMAND
Enumeration
CSCOSTATE
See below.
Inactive
(2)
No
View Only
CEE
No
STATE (cont.)
Loading (0)
Loaded (1)
Inactive (2)
Validated (3)
Running (4)
Complete (5)
Checking (6)
Range
Range
Idle (7)
Interrupting (8)
Interrupted (9)
Restarting (10)
Restarted (11)
Holding (12)
Held (13)
Default
Stopping (14)
Stopped (15)
Aborting (16)
Aborted (17)
CommErr (18)
Notes
Handler, Step,
Transition
Sequential Control
Module (SCM)
Component State
No
View Only
CEE
No
STATE0
Flag
State 0 Indicator
Boolean
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
STATE1
Flag
State 1 Indicator
Boolean
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
207
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
State Descriptor
String
Text - Defines text
for the two states of
the Flag FB;
STATETEXT [0]
corresponds to the
Boolean state of Off
for the Flag, while
STATETEXT [1]
corresponds to On.
Length: 12
characters
Off,
On
Yes
Engineer
CEE
No
NORMAL, PV
String
Length: 12
characters
Null
String
Yes
Engineer
CEE
No
LASTOPREQ,
NUMDINPTS,
NUMDOUTS, PV,
PVAUTO, OP,
OPFINAL, OPREQ
Access is illegal if
NUMDINPTS = 0, and
NUMDOUTS = 0.
Accumulated State
Time - The amount
of time (in hours)
that the device has
spent in any of the
settable states.
DeltaTime
0 to 4000 days 0
No
View Only
CEE
No
GPV, MAINTOPT,
NUMSTATES, PV,
RESETFL
Defaulted to 0 if MAINTOPT
is not set On.
Reset to 0 whenever
RESETFL is set from Off to
On.
STATETIME [2] is illegal if
NUMSTATES = 2.
STATSRESET
Reset statistics
Boolean
command parameter
On (0)
Off (1)
No
Operator
CEE
No
CPUFREEAVG,
CPUFREEMIN,
CPUCYCLEAVG
[0..39],
CPUCYCLEMAX
[0..39],
NUMPARRSPAVG,
NUMPARRSPMAX,
NUMNTFRQUAVG,
NUMNTFRQUMAX,
NUMACCRQUMAX,
RDNDELAYAVG,
RDNDELAYMAX,
RDNXFERAVG,
RDNXFERMAX
CEE, CPM
Off (0)
208
Parameter
Parameter
Specific to
Block(s)
Description
STDTIME
RM
STEPALM.FL
Data Type
Range
Default
Standard (0)
Daylight (1)
Standard No
(0)
SCM
Off (0)
(1)
STEPALM.PR
SCM
None (0)
Journal (1)
Low (2)
High (3)
Urgent (4)
STEPALM.SV
SCM
STICTIONL
STICTIONR
On Off (0)
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Operator
Not Loaded
RM only:
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform
(through
Control
Builder or
Server).
No
View Only
CEE
No
STEPALM.PR,
STEPALM.SV,
MAXTIME
Low (2)
Yes
Engineer
CEE
No
STEPALM.FL,
STEPALM.SV
Yes
Engineer
CEE
No
STEPALM.FL,
STEPALM.PR
PosProp,
PidPosProp
Stiction Lower
Compensation of
actuator (in
seconds).
Real
0.0 to 60.0
0.0
Yes
Supervisor
CEE
No
PosProp,
PidPosProp
Stiction Raise
Compensation of
actuator (in
seconds).
Real
0.0 to 60.0
0.0
Yes
Supervisor
CEE
No
209
Specific to
Block(s)
Description
STOPALM.FL
SCM
STOPALM.PR
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
STOPALM.PR,
When On, it indicates that
STOPALM.SV, STATE the Stop Alarm condition
(SCM STATE has transitioned
to Stopping or Stopped)
exists.
SCM
None (0)
Journal (1)
Low (2)
High (3)
Urgent (4)
Low (2)
Yes
Engineer
CEE
No
STOPALM.FL,
STOPALM.SV
STOPALM.SV
SCM
Yes
Engineer
CEE
No
STOPALM.FL,
STOPALM.PR
STOPFL
Totalizer, Pulse
Input Totalizer
Stop Totalizer
Boolean
Command Flag When flag changes
form Off to On, the
Totalizer block stops
the accumulator.
Off (0): Do No
not stop
the
accumula
tor
Other
Function
Block
CEE
No
RESETFL, STARTFL
Timer
Off (0)
On (1)
Off (0)
Other
Function
Block
CEE
No
RESETFL,
RESTARTFL,
STARTFL,
COMMAND
No
Notes
An Off-to-On transition of
STOPFL stops the timer.
210
Parameter
Parameter
Specific to
Block(s)
Description
STOPOPT
STOPRATE
Data Type
Active
Connector
Related
Parameters
No
DevCtl
Enumeration
DDOPTIONS
Range
None (0)
SafeOp (1)
Default
None (0)
NaN, 0.0,
NaN
positive or
negative Real
numbers
Config
Load
Access
Lock
Residence
Notes
Yes
Engineer
CEE
No
HOLDOPT, OPREQ,
Illegal if
OPTYPE,
ControlModule.SCMOPT =
RESTARTOPT,
None.
SAFEOP, SCMASTEP
[1..10], SCMOPT,
SCMSTATE,
STARTOPT
Yes
Engineer
CEE
No
STOPOPT
211
Specific to
Block(s)
Description
Data Type
STOPVAL
STR [0..7]
REQTEXTARRCH,
RSPTEXTARRAY
STR [1..8]
SITEXTARRCH
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
OPEXLOLM to NaN
OPEXHILM
when
STOPOPT =
FixedOP
SPLOLM to
SPHILM when
STOPOPT =
FixedSP or
RampedSP.
(NaN, 0.0,
positive or
negative Real
numbers)
Yes
Engineer
CEE
No
STOPOPT
Length: 8, 16,
or 64
characters, as
specified by
STRLEN.
Yes
Operator
CEE
No
ERRFL, NSTRING,
STRLEN
Process Value
Provides String
value from the
device.
Yes
Determined CEE
by ACCLOCK
No
ERRFL, NSTRING,
STRLEN
String
Range
Default
212
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
STR [1..120]
TEXTARRAY
String Data
Provides access to
the String values,
one element at a
time, for all other
function blocks of
the CEE. Initial
values can be
configured.
String
STRLEN
TEXTARRAY,
SITEXTARRCH
String Length of
32-Bit Integer Length: 8, 16, 8
String Values
32, or 64
Specifies the
characters.
number of
characters per string
value.
Config
Load
Access
Lock
Yes
Yes
Residence
Active
Connector
Related
Parameters
Determined CEE
by ACCLOCK
No
NSTRING, STRLEN
Application
Developer
No
TEXTARRAY:
See below.
NSTRING, STR
[1..120]
SITEXTARRCH:
NSTRING, STR [1..8]
CEE
Notes
Notes
The Text Array block supports a maximum size of 960 two-byte characters. This number is
chosen based on the amount of data that can fit in one ControlNet message. This is important
when full array access is supported. The following table shows the maximum data
combinations of NSTRING and STRLEN that are possible. Illegal combinations of NSTRING
and STRLEN (those requiring more than 960 two-byte characters of data) will be rejected.
NSTRING
STRLEN
STR [ ] Range
15
64
1..15
30
32
1..30
60
16
1..60
120
1..120
SITEXTARRCH only: With the interface to the serial device haivng a maximum size of
64-bytes, the table below shows how the 64-bytes are interpreted, based on the NSTRING
and STRLEN configured, and the resulting STR [ ] range. Illegal combinations of NSTRING and
STRLEN (those requiring more than 64-bytes of data) will be rejected.
REQTEXTARRAY,
RSPTEXTARRAY
STRLEN
STR [ ] Range
64
1..1
32
1..2
16
1..4
1..8
Yes
Application
Developer
CEE
No
213
NSTRING
Specific to
Block(s)
Description
SUBSCPERIOD
CEE
Configurable
Range:
10 to 1000 ms
DEFAULT (0)
10 ms (1)
20 ms (2)
50 ms (3)
100 ms (4)
200 ms (5)
500 ms (6)
1000 ms (7)
Range
Valid Range for
50 ms CEE:
100 to 1000 ms
DEFAULT (0)
100 ms (4)
200 ms (5)
500 ms (6)
1000 ms (7)
Data Type
Range
Default
Config
Load
DEFAULT Yes
(0)
DEFAULT
is
converted
to an
actual
value
upon
load:
Converted
to 500 ms
for the 50
ms CEE
Converted
to 100 ms
to the 5
ms CEE
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Engineer
CEE
No
BASEPERIOD
See below.
Notes
The Peer Update Rate (SUBSCPERIOD parameter is the rate at which
this CEE subscribes to data from other CEEs through peer-to-peer
communications. In the event of a peer-to-peer communications
problem such as a broken cable, the connection will timeout, returning
an error. The valid values and function of the DEFAULT value for
SUBSCPERIOD are different for the 50 and 5 ms CEE personalities as
described below.
50 ms CEE:
Valid Range: DEFAULT, 100, 200, 500, 1000 ms
DEFAULT value is converted to 500 ms upon load to a 50 ms CEE.
Connection timeout time is approximately 5.2 seconds.
5 ms CEE:
Valid Range: DEFAULT, 10, 20, 50, 100, 200, 500, 1000 ms
DEFAULT value is converted to 100 ms upon load to a 5 ms CEE.
Connection timeout time is approximately 5.2 seconds.
SWAPCTRLCMD
RM
Swap Control
Command
Boolean
True (0)
False (1)
No
Not Loaded
Operator
RM only:
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
SWAPPOSCMD
RM
Swap Position
Command
Enumeration
Chassis_A (0)
Chassis_B (1)
No
Operator
Not Loaded
RM only:
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
214
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
SWAPSBYCMD
RM
Swap to Standby
Command
Boolean
True (0)
False (1)
SYNCSECCMD
RM
Synchronize
Secondary
Command
Boolean
True (0)
False (1)
T1
PID, PIDFF
Integral Time
Constant (in
Minutes)
64-Bit Real
Number
T1HILM
PID, PIDFF
T1 High Limit
T1LOLM
PID, PIDFF
T2
Config
Load
Access
Lock
No
Operator
Not Loaded
RM only:
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
True (0)
No
Operator
Not Loaded
RM only:
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
T1LOLM to
T1HILM
0.0
Yes
Supervisor
64-Bit Real
Number
T1LOLM to
1660.0
1440.0
Yes
T1 Low Limit
64-Bit Real
Number
Greater than
T1HILM
0.0
PID, PIDFF
Derivative Time
Constant (in
Minutes)
64-Bit Real
Number
T2LOLM to
T2HILM
T2HILM
PID, PIDFF
T2 High Limit
64-Bit Real
Number
T2LOLM to
1440.0
T2LOLM
PID, PIDFF
T2 Low Limit
64-Bit Real
Number
TARGETSTEP
[1..10]
SCM
BlockId
TBREF [0..2]
CM
Structure
Default
Related
Parameters
CEE
No
T1HILM, T1LOLM
Engineer
CEE
No
T1, T1LOLM
Yes
Engineer
CEE
No
T1, T1HILM
0.0
Yes
Supervisor
CEE
No
T2HILM, T2LOLM
1440.0
Yes
Engineer
CEE
No
T2, T2LOLM
Yes
Engineer
CEE
No
T2, T2HILM
No
Operator
CEE
No
MODE, STATE,
SSTEPLOCK
No
Application
Developer
CEE
No
Notes
Active
Connector
Null
String
Residence
Specific to
Block(s)
Description
Data Type
Range
Default
TEMPMODE
AIM
Temperature Mode
Enumeration
of
TEMPMODE
Celcius (0)
Farenheit (1)
TGTDATATYPE
REQNUMARRAY
when COMMAND
is PLC5TypWrite or
CIPWrite
Access
Lock
Residence
Active
Connector
Application
Developer
CEE
No
Yes
Application
Developer
CEE
No
TGTRNGDEF
SCM
Internal parameter
for system use only.
TGTRNGDEFOPT SCM
Internal parameter
for system use only.
THREAD [1..10]
SCM
Internal parameter
for system use only.
THRESHOLD
TypeConvert
Threshold for
converting floating
point values to
boolean values
0.001
Yes
Engineer
CEE
No
IN.FLOAT32,
IN.FLOAT64,
OUT.BOOLEAN
TIME
Step
No
View Only
CEE
No
32-Bit Real
Number
Real
Config
Load
Related
Parameters
Notes
Configurable only on RTD
and Thermocouple AIMs.
216
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
TIME [1..8]
SCM
Current Time in
Handler
32-Bit Integer 0 to
2147483647
No
View Only
CEE
No
TYPE
TIMEBASE
Totalizer
Seconds (0)
Minutes (1)
Hours (2)
Minutes
(1)
Yes
Engineer
CEE
No
Timer
Enumeration
TIMEBASE
Seconds (0)
Minutes (1)
Cycles (2)
Seconds
(0)
Yes
Engineer
CEE
No
SP, PV, RV
Seconds (0)
Minutes (1)
Hours (2)
Seconds
(0)
Yes
Application
Developer
Pulse Input
Totalizer
only:
Engineer
CEE
No
TIMEBASE [0..7]
Seconds (0)
Minutes (1)
Hours (2)
Seconds
(0)
Yes
Application
Developer
CEE
No
TMOUTFL
Off (0): No
Off (0)
time-out
On (1): Input
has timed-out
No
View Only
CEE
No
Boolean
Range
TMOUTMODE,
TMOUTTIME
217
Specific to
Block(s)
Description
Data Type
TMOUTMODE
Fanout, OvrdSel,
PID, PIDFF, PosProp,
RemCas, RatioBias,
and RegCalc.
TMOUTTIME
TOTALMEM
CPM
TOTALMEMINK
CPM
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Yes
Engineer
CEE
No
TMOUTFL,
TMOUTTIME
0 to 1000
seconds
Yes
Engineer
CEE
No
TMOUTFL,
TMOUTMODE
No
View Only
CEE
No
FREEMEM,
USEDMEM,
MAXFREEBLKSZ
No
View Only
CEE
No
FREEMEMINK,
USEDMEMINK,
MAXFREEINK
Total (configured)
Real
Time for a
RampSoak Profile (in
Minutes)
Greater-than
or equal to 0.0
No
View Only
CEE
No
TOTELAPSEDTM RampSoak
Greater-than 0.0
or equal to 0.0
No
View Only
CEE
No
NETELAPSEDTM
Notes
218
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
TP
64-Bit Real
Number
TRACKING
RemCas, Switch
Input Tracking
Boolean
Option Allows the
selected input to be
changed without
bumping the output.
TRFB
PidExtReset
Tracking value.
TRUNCATEOPT
TypeConvert
TV
TV [6..7]
TVPROC
Range
Default
Config
Load
Access
Lock
0.5
Yes
Engineer/Pro CEE
gram
No
Yes
Engineer/Ap CEE
plication
Developer
No
Off (0):
On (1)
Tracking is
disabled
On (1):
Tracking is to
be done
Residence
Active
Connector
Related
Parameters
Notes
Used to compare against
constant values, when only
one input is configured.
Yes
Engineer
CEE
None
IN.FLOAT32,
IN.FLOAT64,
OUT.INT16,
OUT.INT32,
OUT.UINT16,
OUT.UINT32
Greater-than 0.0
or equal-to 0.0
No
Operator
CEE
No
SO
Greater-than 0.0
or equal-to 0.0
No
Engineer
CEE
Yes
SO [6..7], TVRAW
[6..7],
Off (0)
On (1)
No
View Only
CEE
No
SO, TV,
Off (0)
219
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
TVPROC [6..7]
Target Value
Boolean
Processing Flag. If
On, it indicates Pulse
Input Module fast
cutoff comparison is
enabled.
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
SO [6..7], TVRAW
[6..7],
TVRAW [6..7]
No
View Only
CEE
No
SO [6..7], TV [6..7]
TYPE
Handler
Handler Type
Yes
Engineer
CEE
No
SELHANDLER [1..8],
ENBHANDLER [1..8],
INVREASON [1..8],
INVCOND [1..8],
INVFROMSTEP [1..8]
[1..10],
INVFRMHNDTYP
[1..8],
INVFRMHNDLER
[1..8], TIME [1..8],
ACTIVEHANDLR
[1..8]
Hold (6)
Notes
220
Parameter
Parameter
Specific to
Block(s)
Description
ULCNBMAC
IOM
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
Yes
Application
Developer
SR
No
DLCNBSLOT,
IOMSLOT
CPM, RM
No
Engineer
SR
No
ABORTALM.PR
UNCMDALM.FL
DevCtl
Uncommanded
Change Alarm Flag
Boolean
Off (0)
On (1)
Off (0)
No
View Only
CEE
No
GOP, GPV,
CMDDISALM.FL,
CMDDISALM.PR,
CMDDISALM.SV,
CMDDISALM.TM
[0..2], NUMDINPTS,
PV, OP
Illegal if NUMDINPTS = 0, or
if NUMDOUTS = 0.
UNCMDALM.FL is always
enabled, when
CMDDISALM.xx is enabled.
UNCMDALM.PR
DevCtl
Uncommanded
Change Alarm
Priority
Enumeration
ALPRIOR
None (0)
Journal (1)
Low (2)
High (3)
Urgent (4)
Low (2)
Yes
Engineer
CEE
No
UNCMDALM.SV
DevCtl
Uncommanded
Change Alarm
Severity
0.0
Yes
Engineer
CEE
No
221
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
UNDERRANGE
AIC
Input is not in No
an
under-range
state (0)
Input is in an
under-range
state (1)
UNDERRANGE
[0..numChans-1]
AIM
Input is not in
an
under-range
state (0)
Input is in an
under-range
state (1)
Input is No
not in an
under-ran
ge state
(0)
UNITTEXT
CM, SCM
Unit Text
String
Length: 2
characters
Null
String
UPDATOPT
All IO Channels,
IOM,
SIFLAGARRCH,
SINUMARRCH,
SITEXTARRCH
Update Option
Integer
UPDRESOPT
Step
Update Resume
Address Option
Boolean
Residence
Active
Connector
No
OVERRANGE
ViewOnly
CEE
No
Engineer
CEE
No
CEE
No
ViewOnly CEE
Yes
Access
Lock
Related
Parameters
Notes
OVERRANGE
[0..numChans-1]
View Only
Yes
Engineer
RESADDRFUTUR
[1..10], RESADDR
[1..10]
222
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
USEDMEM
CPM
Total amount of
unused memory in
CEE user memory
pool.
USEDMEMINK
CPM
Total amount of
unused memory in
CEE user memory
pool.
USESIM
CPM
VENDOR
Numeric code
representing I/O
vendor identity.
32-Bit Integer
Range
Off (0)
On (1)
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
No
View Only
CEE
No
TOTALMEM,
FREEMEM,
MAXFREEBLKSZ
No
View Only
CEE
No
TOTALMEMINK,
FREEMEMINK,
MAXFREEINK
Off (0)
No
Application
Developer
SR
No
ABORTALM.PR
3
Yes
Note that
this
paramete
r is not
currently
set with
specific
default
values for
different
IO
vendors.
Application
Developer
CEE
No
223
Specific to
Block(s)
Description
VENDORID
RM
VERIFYLOST
Range
Default
Config
Load
Access
Lock
0 to 65535
No
ViewOnly
Not Loaded
RM only:
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
DOC
Output Verify
Indicates that the
actual state of the
output does not
match the
commanded state.
Boolean
Output
matches the
commanded
state: (0)
Output does
not match the
commanded
state: (1)
Output
No
matches
the
command
ed state:
(0)
ViewOnly
CEE
No
EVERIFY
[0..numChans-1]
VERIFYLOST
[0..numChans-1]
DOM
Output Verify
Indicates that the
actual state of the
output does not
match the
commanded state.
Boolean
Output
matches the
commanded
state: (0)
Output does
not match the
commanded
state: (1)
Output
No
matches
the
command
ed state:
(0)
ViewOnly
CEE
No
EVERIFY
[0..numChans-1]</HH
>
VERSION
SCM, CM
Version Descriptor
String
Engineer
CEE
No
VOLTAGE
Enumeration
See below.
Application
Developer
CEE
No
Application
Developer
CEE
No
Low (0):
High (1):
VOLTAGE [0..7]
Input Voltage
Threshold
specifies level of
input.
Data Type
Yes
Residence
Active
Connector
Range
Signals with a voltage lower than 2 volts are
considered to be low voltage while signals
with a voltage equal-to or highter-than 2 volts
are considered to be high voltage
Related
Parameters
Notes
Low (0)
High (1)
2V (0)
Yes
224
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
Notes
VOTED
nooN
Boolean
Off (0)
On (1)
Off(0)
No
View Only
CEE
No
WCTCLKTIME
RM
Clock Time
TIME
N/A
No
Not Loaded
Operator
RM only:
Requests to
read or store
to any RM
parameter
must come
from the
Supervisory
platform.
No
WIREOFF
DIC
Indicates the
Boolean
absence of a field
wire (sensor /
actuator) or the
break in field wiring.
Wire-off
condition not
detected (0)
Wire-off
condition
detected (1)
Wire-off No
condition
not
detected
(0)
ViewOnly
CEE
No
EWIREOFF[0..numCh
ans-1]
WIREOFF
[0..numChans-1]
DIM
Indicates the
Boolean
absence of a field
wire (sensor /
actuator) or the
break in field wiring.
Wire-off
condition not
detected (0)
Wire-off
condition
detected (1)
Wire-off No
condition
not
detected
(0)
ViewOnly
CEE
No
EWIREOFF[0..numCh
ans-1]
X [1..4]
OvrdSel
XEULO to
XEUHI
NaN
No
View Only
Not Loaded
Yes
X [1..6]
RegCalc
XEULO to
XEUHI
NaN
No
View Only
Not Loaded
Yes
225
Specific to
Block(s)
Description
X [1..8]
Switch, Ovrdsel,
and RegCalc
X1
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
XEULO to
XEUHI
NaN
No
View Only
Not Loaded
Yes
XEULO to
XEUHI
NaN
No
View Only
CEE
No
No
View Only
CEE
No
AutoMan, Fanout,
RemCas
Internal parameter
for system use only.
X1P
Fanout, AutoMan
The X1 Value in
Percent
X1SECDATA
X1STS
Fanout, AutoMan
64-Bit Real
Number
0 to 100
NaN
No
View Only
CEE
No
Bad (0)
Uncertn (1)
Normal (2)
Manual (3)
Bad (0)
No
View Only
CEE
No
Related
Parameters
BACKCALCIN,
BACKCALCIN [1..8]
X1
Notes
X1BACKCALOUT establishes
the initialization, override,
and windup propagation
between connected Remote
Cascade (REMCAS) and
Regulatory Control Blocks.
This is one half of the
BACKCALCIN/X1BACKCALO
UT connection. Applicable to
the REMCAS block.
226
Parameter
Parameter
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
X2
RemCas
64-Bit Real
Number
XEULO to
XEUHI
NaN
No
View Only
CEE
Default
Connector:
Input for the
RemCas
function
block.
No
View Only
CEE
No
BACKCALCOUT,
X2BACKCALOUT establishes
BACKCALCOUT [1..8] the initialization, override,
and windup propagation
between connected Remote
Cascade (RemCas) and
Regulatory Control (RegCtl)
blocks. This is one half of
the
BACKCALCIN/X2BACKCALO
UT connection.
0.0
Yes
Engineer
CEE
No
X [1..6], XK [1..6],
XKB [1..6]
X2BACKCALOUT RemCas
Back Calculation
Structure
Data from secondary
block - Secondary
Data structure
associated with
Remote Cascade
(RemCas) block X2
input. Contains
Control Variable (CV)
limits, initialization,
and data windup
status, etc.
X2BACKCALOUT is
associated with the
primary block.
Connecting
BACKCALCIN to its
X2BACKCALOUT
partner is required
in order to establish
the initialization
path between the
two blocks.
X2CONN
RemCas
Internal parameter
for system use only.
X2SECDATA
RemCas
Internal parameter
for system use only.
XB [1..6]
RegCalc
XCONN [1..4]
Switch
Internal parameter
for system use only.
XCONN [1..8]
OvrdSel, Switch
Internal parameter
for system use only.
XDESC [1..2]
RemCas.
The X-Input
Descriptors
String
Length - 15
characters
Null
String
Yes
Operator
CEE
No
XDESC [1..4]
OvrdSel
The X-Input
Descriptors
String
Length - 15
characters
Null
String
Yes
Operator
CEE
No
Related
Parameters
Notes
X2 is an initializable input for
the RemCas function block.
227
Specific to
Block(s)
Description
Data Type
Range
Default
Config
Load
Access
Lock
Residence
Active
Connector
Related
Parameters
XDESC [1..8]
Switch
The X-Input
Descriptors
String
Length - 15
characters
Null
String
Yes
Operator
CEE
No
XEUHI
64-Bit Real
Number
Greater than
or equal to
XEULO
100.0
Yes
Engineer
CEE
No
XEULO
64-Bit Real
Number
Less than or
equal to
XEUHI
0.0
Yes
Engineer
CEE
No
XK [1..6]
RegCalc
1.0
Yes
Engineer
CEE
No
X [1..6], XB [1..6],
XKB [1..6]
XKB [1..6]
RegCalc
Individual input
Real
values after
individual biases
and gains have been
applied to X [1]
through X [6].
NaN
No
ViewOnly
CEE
No
X [1..6], XB [1..6], XK
[1..6]
XSTS [0..5]
RegCalc
X Input Status
Integer
XWHIFL
RegCalc
X input windup
high flag
Boolean
Off (0)
On (1)
Off (0)
No
Other
Function
Block
CEE
No
XWLOFL
XWLOFL
RegCalc
X input windup
low flag
Boolean
Off (0)
On (1)
Off (0)
No
Other
Function
Block
CEE
No
XWHIFL
View Only
Notes
228
Parameter
Appendix
Display Elements
Notes
Background Display
sys205.dsp
It is necessary to replace the existing background display to use the new faceplate
displays.
CEE
sysGrpCEEA.dsp
sysGrpIOMA.dsp
AI Modules
sysGrpAIA.dsp
Hi Density AI Modules
sysGrpAI16A.dsp
AO Modules
sysGrpAOA.dsp
sysGrpDXA.dsp
sysGrpDX32A.dsp
sysGrpDO32A.dsp
Note: Due to the large number of dynamic points contained on these displays, only 4 of
these group faceplates may be configured for any one group display.
Note that sysGrpDO32A.dsp should be used as the group display for the 32-point
output modules. This is not currently the default value. The user must modify the
default entry so that it reads sysGrpDO32A.dsp.
sysGrpFlexDimCntr.dsp
sysGrpFlexAI8A.dsp
1794-IE8
sysGrpAO4A.dsp
1794-OE4
Flex EX 4 Channel
Digital Output
sysGrpDO4A.dsp
1797-OB4D
sysGrpRailAI8A.dsp
CPM
sysGrpCPMA.dsp
CPMSA
sysGrpCPMSA.dsp
SIM
sysGrpSIA.dsp
PIM
sysGrpPIA.dsp
A-2
Display Elements
Notes
RM
sysGrpRMA.dsp
Redundancy Module
sysGrpLD.dsp
FIM
sysGrpFIM.dsp
LINK
sysGrpLINK.dsp
Fieldbus Link
Fieldbus Device
sysGrpFFDevice.dsp
Fieldbus Device
Profibus Interface
Module
sysGrpPBIM.dsp
Generic Profibus
Device
sysGrpPfbDevice.dsp
sysGrpPfbAim.dsp
sysGrpPfbAom.dsp
sysGrpPfbDim.dsp
sysGrpPfbDom.dsp
Profibus Encoder
Device
sysGrpPfbEncoder.dsp
sysGrpPfbProfiDrive.dsp
sysGrpPIDA.dsp
PID Control CMs. NOTE: PID BLOCK IN CONTROL MODULE MUST BE NAMED PIDA
AND DATA ACQUISITION BLOCK MUST BE NAMED DACA.
SCM
sysGrpSCMA.dsp
Device Control
sysGrpDEVCTLA.dsp
Device Control CMs. NOTE: Device Control BLOCK IN CONTROL MODULE MUST BE
NAMED DEVCTLA.
sysGrpRAMPA.dsp
Data Acquisition
sysGrpDACA.dsp
CMs with Data Acq block. NOTE: Data Acq BLOCK IN CONTROL MODULE MUST BE
NAMED DACA.
A-3
Display Elements
Notes
Generic
sysDtlCDA.dsp
The display used if no detail display is specified in the system. From here, you can
access the main page for any other template.
CEE
sysDtlCEEA.dsp
sysDtlCEEB.dsp
sysDtlCEEC.dsp
sysDtlDEVCTLA.dsp
Main Device Control Page (Execution State, alarms, interlocks, etc.) NOTE: DEVICE
CONTROL BLOCK IN CONTROL MODULE MUST BE NAMED DEVCTLA
sysDtlDEVCTLB.dsp
sysDtlDEVCTLC.dsp
sysDtlDEVCTLD.dsp
SysDtlDEVCTLE.dsp
Maintenance Page
SysDtlDEVCTLF.dsp
sysDtlDEVCTLG.dsp
CB Visualization Chart
sysDtlIOMA.dsp
I/O Module Main Page (Execution State, Slot Number, etc.) for any I/O Module.
sysDtlIOMB.dsp
sysDtlAIA.dsp
sysDtlAIB.dsp
sysDtlAOA.dsp
sysDtlAOB.dsp
SysDtlAI16A.dsp
SysDtlAI16B.dsp
Device Control
Control Module
Generic IOM
AI IOM
AO IOM
AI IOM
(Hi Density)
A-4
Display Elements
Notes
AO IOM
(Hi Density)
SysDtlAO8A.dsp
SysDtlAO8B.dsp
SysDtlDIA.dsp
SysDtlDIB.dsp
sysDtlDIC.dsp
SysDtlDOA.dsp
SysDtlDOB.dsp
sysDtlDOC.dsp
sysDtlDI32A.dsp
sysDtlDI32B.dsp
sysDtlDI32C.dsp
SysDtlDO32A.dsp
SysDtlDO32B.dsp
sysDtlDO32C.dsp
sysDtlRailCAI8A.dsp
sysDtlRailCAI8B.dsp
sysDtlRailCAI8C.dsp
sysDtlRailTAI8A.dsp
sysDtlRailTAI8B.dsp
sysDtlRailTAI8C.dsp
Configuration Page
sysDtlRailCAO8A.dsp
1797-OE8
sysDtlRailCAO8B.dsp
sysDtlRailCAO8C.dsp
Configuration Page
sysDtlRailBI16A.dsp
sysDtlRailBI16B.dsp
sysDtlRailBI16C.dsp
Configuration Page
sysDtlRailBO4A.dsp
sysDtlRailBO4B.dsp
sysDtlRailBO4C.dsp
Configuration Page
sysDtlFlexCAI8A.dsp
sysDtlFlexCAI8B.dsp
sysDtlFlexCAI8C.dsp
Configuration Page
sysDtlFlexCAO4A.dsp
DI IOM
DO IOM
32 POINT DI
(Hi Density)
32 POINT DO
(Hi Density)
Flex EX AI IOM
Flex EX AO IOM
Flex EX DI IOM
Flex EX DO IOM
Flex AI IOM
Flex AO IOM
A-5
Display Elements
Notes
sysDtlFlexCAO4B.dsp
sysDtlFlexCAO4C.dsp
Configuration Page
sysDtlFlexDimA.dsp
sysDtlFlexDimB.dsp
sysDtlFlexDimC.dsp
Configuration Page
sysDtlFlexBOA.dsp
sysDtlFlexBOB.dsp
sysDtlFlexTIMA.dsp
sysDtlFlexTIMB.dsp
sysDtlFlexTIMC.dsp
Configuration Page
CPM
(Non Redundant &
Primary)
SysDtlCPMA.dsp
CPM
(Secondary)
SysDtlCPMSA.dsp
PID Control
Control Module
SysDtlPIDA.dsp
PID Main Page (Execution State, alarms, set point ramping, etc.)
Note: Pid block in Control Module must be named PIDA and Data Acquisition
Block must be named DACA.
SysDtlPIDB.dsp
sysDtlPIDC.DSP
sysDtlPIDD.dsp
PV, OP Configuration
sysDtlPIDE.dsp
sysDtlPIDF.dsp
sysDtlPIDG.dspCB
Visualization Chart
sysDtlSCMA.dsp
sysDtlSCMB.dsp
sysDtlSCMC.dsp
sysDtlSCMC2.dsp
sysDtlSCMC3.dsp
sysDtlSCMD.dsp
sysDtlSCMD2.dsp
sysDtlSCMD3.dsp
sysDtlSCME.dsp
Flex DI IOM
Flex DO IOM
Flex Temperature
IOM
SCM
A-6
Display Elements
Notes
Ramp/Soak
Control Module
SysDtlRAMPA.dsp
SysDtlRAMPB.dsp
Ramp/Soak (Graph)
SysDtlRAMPC.dsp
SysDtlRAMPD.dsp
Ramp/Soak (Alarms)
SysDtlRAMPE.dsp
Ramp/Soak (Connections)
SysDtlProfile1.dsp
SysDtlProfile2.dsp
SysDtlProfile3.dsp
SysDtlProfile4.dsp
SysDtlProfile5.dsp
SysDtlProfile6.dsp
SysDtlProfile7.dsp
SysDtlProfile8.dsp
SysDtlProfile9.dsp
SysDtlProfile10.dsp
SysDtlPIB.dsp
SysDtlPIC.dsp
SysDtlSIA.dsp
SysDtlSIB.dsp
sysDtlDACA.dsp
sysDtlDACB.dsp
SysDtlDACC.dsp
sysDtlRMA.dsp
sysDtlRMB.dsp
SysDtlRMC.dsp
SysDtlRMD.dsp
SysDtlRME.dsp
Fieldbus Linking
Device
sysDtlLD.dsp
FIM
sysDTLFIM.dsp
Fieldbus Link
sysdtlLink.dsp
Fieldbus Device
SysDtlFFDEVICE.dsp
Profibus Interface
Module
sysDtlPBIM.dsp
Profibus Devices
sysDtlPfbAim.dsp
sysDtlPfbAom.dsp
sysDtlPfbDevice.dsp
Serial Interface
Module
Data Acquisition
Control Module
RM
A-7
Analog Point
Display Elements
Notes
sysDtlPfbDim.dsp
sysDtlPfbDom.dsp
sysDtlPfbEncoder.dsp
sysDtlPfbProfiDrive.dsp
sysDtlAna.dsp
sysDtlAnaScanDetail.dsp
Scanning Page
sysDtlAnaAlarms.dsp
Alarm Page
sysDtlAnaHistory.dsp
History Page
sysDtlAnaAuxiliary.dsp
Auxiliary Page
sysDtlSta.dsp
sysDtlStaScanDetail.dsp
Scanning Page
sysDtlStaAlarms.dsp
Alarm Page
sysDtlStaHistory.dsp
History Page
sysDtlStaHistorySummary.dsp
A-8
Appendix
B-2
Function
Description
AUXDATA[0] to
AUXDATA[3]
These parameters
are not applicable to
an Allen-Bradley
interface.
AUXDATA[4]
Specifies the
Allen-Bradley PLC
family type.
AUXDATA[5]
Specifies the
Allen-Bradley PLC
file number.
AUXDATA[6]
See the paragraph following this table for details about making AUXDATA[6] settings for a
given PLC type.
Different settings are required for diagnostic related Array Channel blocks. See the following
section Diagnostic data configuration for details.
AUXDATA[7]
Specifies the
Allen-Bradley PLC
scan rate.
Each Array Channel block can have a different scan rate. The Allen-Bradley interface supports
either polling or Report by Exception (RBE) independent of the scan rate. Use the following
setting for a given scan rate.
0 to scan the channel as fast as possible
1 to 255 to scan the channel once every 1 to 255 seconds
256 to scan the channel once after configuration or after link or device failure recovery (then
only Report by Exception)
Notes:
Use higher priority scanning for time-critical data, and slower scanning or RBE for lower
priority channels where data changes infrequently.
If all channels are set for very fast scan (0 to 2 seconds), actual performance may be less than
one update per second, especially when writes are used.
A setting greater than 256 causes a POL FREQ error.
If more than one Array Channel block is configured to map the same PLC memory area, only
one of the blocks will be updated with RBE data.
After the first scan is completed with a setting of 256, Array data is updated when RBE data is
received for that channel or after any communication error (but not after configuration errors).
The RBE feature is independent of the scan rate. See the section Report by Exception
requirements for details.
B-3
ATTENTION
AUXDATA[6] Setting
Data Range
Output
SIFLAGARRCH
ON/OFF
512
Input
SIFLAGARRCH
ON/OFF
512
Status
SIFLAGARRCH
ON/OFF
512
Bit
SIFLAGARRCH
ON/OFF
512
Integer
4,5
0 to 65535
32
Floating Point
Integer
-32768 to 32767 32
Floating Point
-34E38 to 34E38 16
ASCII
SITEXTARRCH
Printable
Characters
TIP
8 of 8
4 of 16
2 of 32
1 of 64
B-4
AUXDATA[6] Setting
Data Range
Max. No.
Elem.
Output
SIFLAGARRCH
ON/OFF
512
Input
SIFLAGARRCH
ON/OFF
512
Integer
-32768 to 32767
32
Floating Point
Binary
SIFLAGARRCH
ON/OFF
512
ASCII
SITEXTARRCH
Printable Characters
8 of 8
4 of 16
2 of 32
1 of 64
Status
13
SIFLAGARRCH
ON/OFF
512
TIP
AUXDATA[6]
Setting
Data Range
Max. No.
Elem.
Output
SIFLAGARRCH
ON/OFF
512
Input
SIFLAGARRCH
ON/OFF
512
Status
SIFLAGARRCH
ON/OFF
512
Bit
SIFLAGARRCH
ON/OFF
512
Integer
4,5(1)
0 to 65535
32
Integer
-32768 to 32767
32
Floating Point
-34E38 to 34E38
16
ASCII
SITEXTARRCH
Printable Characters
8 of 8
4 of 16
2 of 32
1 of 64
(1)
These Allen-Bradley file types are read only and writes to them are ignored.
TIP
B-5
B-6
B-7
B-8
Table B.5
Function
PLC-2
PLC-3
PLC-5
(1)
Specific command
Read-Modify-Write
CMD:0F
FNC: 26
These functions must use the Logical Binary Addressing format or the RBE message is rejected by the SIM. Other formats including PLC-3 Symbolic and PLC-5 Logical
ASCII will be rejected.
Performance Considerations
IMPORTANT
B-9
An active SIM function block processes the following actions once per
its publication period of 250 milliseconds. The publication rate is the
same whether the SIM block is assigned to a 5ms-CEE or a 50ms-CEE
type.
Load Serial Interface Array Channel block configurations to the
SIM.
Send Array Channel block write requests to the SIM.
Monitor status of the SIM, and report diagnostics, as applicable.
Of course, these actions are not performed when the SIM block is
inactive. When the SIM block is inactive, the Array Channel blocks set
their data to applicable default values.
The SIM block collects the writes for each array channel and sends
them to the SIM every 250ms. The following table lists the maximum
number writes a SIM block supports per channel in every 250ms
cycle. If the SIM blocks write list becomes full, it rejects a write to the
array channel block.
Table B.6 Max number of writes per channel
Array Channel Block
SINUMARRCH
SIFLAGARRCH
16
SITEXTARRCH (STRLEN = 8)
Writes to Array Channel Blocks can also be rejected because the SIM
is not keeping up with the writes being sent by the SIM block. Write
overruns are indicated by the SIM block FTAAOVRNFL and
FTABOVRNFL parameters. To provide an overrun condition alarm,
connect the overrun parameters to a FLAG function block configured
to generate an OffNormal alarm.
For an Allen-Bradley interface, all configured Array Channel blocks
scan the PLC devices in a circular sequence at the specified scan rate
with the read data requests. A write data request preempts the read
requests (and/or response to any RBE requests). The number of
consecutive write data requests is limited to eight (8), after which a
Report by Exception request or scan read request is serviced. If
outputs, RBE requests, and scan read requests are stacked
continuously, the RBE requests and scan read requests are alternately
serviced after every eight outputs. This slows data acquisition
considerably.
Publication 1757-RM811A-EN-P - May 2002
B-10
B-11
B-12
DEVADDR
AUXDATA[4]
0 (indicates CIM)
AUXDATA[5]
AUXDATA[6]
AUXDATA[7]
Scan frequency
STARTINDEX
NNUMERIC
(1)
You must know which CIM is used because each model can have different meanings for its offset values.
B-13
DEVADDR
AUXDATA[4]
AUXDATA[5]
AUXDATA[6]
AUXDATA[7]
Scan frequency
STARTINDEX
NNUMERIC
(1)
You must know which PLC model is used because each model can have different meanings for its offset values.
DEVADDR
AUXDATA[4]
NaN
AUXDATA[5]
-3
AUXDATA[6]
NaN
AUXDATA[7]
STARTINDEX
STRLEN
64 characters
NSTRING
B-14
B-15
Error messages
The following table lists some possible Serial Interface and
Allen-Bradley communication errors for reference. You may also need
to refer to the Allen-Bradley documentation for error messages
specific to the PLC.
Table B.10 Select Error Code Descriptions
ERRCODE String
Description
Number of elements is out of range for the given Array Channel block.
ARR INIT
Array Channel block is configured, but no valid data has been received.
AUXMATCH
AUXDATA[2] and AUXDATA[3] configuration settings do not match the other channels in the FTA. All channels must
agree.
BAUD/PAR
CEE Idle
CFG LOAD
ChCfgErr
Array Channel block configuration error exists. Check block configuration carefully.
Ch Inctv
CONFIG
Can not load configuration to the SIM. Check all configuration data carefully.
DataCond
Array Channel block does not understand Data Conditioner (internal value) sent by the FTA.
B-16
Description
Array Channel block is not supported or out of range for this device.
DEV ADDR
Fac Test
FTA COMM
Inv Resp
IO Comm
There is an I/O communications problem between the CPM and the SIM.
KPA ADDR
MAX CONF
Md Inctv
The SIM function block is inactive, so the Array Channel block can not get new array data.
NO CONF
No Conn
The Array Channel block can not get data because a proper connection does not exist between the CPM and the SIM.
No Data
Transient condition that occurs when the Control Module containing the Array Channel block is activated. Condition
clears once ERRFL is set OFF or ON.
No SIMFB
Array Channel block can not locate its assigned SIM block. Be sure the SIM block is loaded to the CEE.
PLC TYPE
POL FREQ
SIG/MOD
Startidx
STR LEN
TMOT VAL
Allen-Bradley remote station specific EXT STS error (refer to Allen-Bradley documentation).
ABSTS_nn
ACKTMOUT
ARR INIT
CHECKSUM
CIM_NAK
INV RESP
MAXMSGST
MSGTMOUT
Timed out waiting for the Allen-Bradley device to reply to the last request.
OK_POLL
No errors exist against the Array Channel block whose poll rate is within 0 to 255.
OK_RBE
No errors exist against the Array Channel block whose poll rate is 256.
PARITY
RBE_FULL
RBE buffer full due to too many Report by Exception requests from the PLC devices.
B-17
42780
B-18
42781
B-19
Reference Specifications
The following table lists some general specifications relevant to the
Serial Interface function.
Table B.11 Serial Interface Specifications
Function
Description
Up to 2048 Booleans/second, or
Up to 128 integers/second, or
Up to 64 reals/second, or
Up to 4, 64-character strings/second, or
Weighted combinations of the above
10 channels/second
B-20
Description
????????
SIM
TC-MUX021
General
Interface Type
EIA-RS232-D
Baud Rate
19,200 baud
ESD Protection
EIA-RS232-D Support
Interface Type
Serial asynchronous
Lines Supported
TXD, RXD, Logic GND, Protectiv GND (Compatible with CCIT V.24; CCIT V.28)
Allen-Bradley Specific
Protocol
Transmission Mode
Character oriented
RS232
Parity
Even
Off
ACK Timeout
3.2 seconds
4.0 seconds
PLC-2
PLC-3 (Native Mode and PLC-2 Mode)
PLC-5, except PLC-5/20 (Native Mode and PLC-2 Mode)
(1)
Read and write performance is sensitive to a number of variables, including the PLC type, scan time, PLC network configuration and traffic, amount of data access from
other devices, and the overall health of the PLC network. For best results, a direct PLC connection is recommended. The ratings listed do not represent best performance
figures. Read performance degrades with increased writes.
Appendix
Function
Description
AUXDATA[0]
This parameter tells the Modbus system that the ProcessLogix subsystem is
functioning. It can be configured separately on each array channel block, but
no two array channel blocks should write to the same coil. The coil address
must be within the range 00001 to 09999.
Note: When this parameter is NaN, the Keep Alive function is inactive. If you
want to check the Keep Alive coil, you must program the Modbus device to do
so.
AUXDATA[1]
If a valid response is not received after three tries (original plus two retires), a
MSGTMOUT error results. The range is 0.25 to 5 seconds on NaN. If NaN is
specified, the default timeout is 1.5 seconds. A timeout value can be
configured separately for each array channel block.
C-2
Table C.A Serial Interface Array Channel Communications with Generic Modbus
The first valid array channel block loaded to the Controller with values in
AUXDATA[2] and AUXDATA[3] sets the mode and baud rate for the FTA
communications. This means that AUXDATA[2] AUXDATA[3] must contain the
same value for all array blocks configured through the same FTA. If array
blocks loaded later to that FTA have different AUXDATA[2]/[3] values, an
AUXMATCH error results.
The modem control feature switches the following signals: RTS, CTS, DSR,
DTR, and DCD. When AUXDATA[2] is NaN, the protocol is EIA-232 and modem
control is OFF.
AUXDATA[2]
AUXDATA[3]
AUXDATA[4] to These parameters are not applicable to Set these parameters to NaN when communicating with a Modbus.
AUXDATA[7]
a Generic Modbus interface.
C-3
Table C.B
Start Index Modbus Function
Ranges
00001 09999
Read FC
Data Range
Max. No.
Elem.
SIFLAGARRCH
Read/Write Bit Flags
ON/OFF
512
SIFLAGARRCH
Read Only Bit Flags
ON/OFF
512
SINUMARRCH
Word Swapped IEEE FI.Pt Read/Write
-34E38 to
34E38
16
SINUMARRCH
Signed Integer Words Read only
-32768 to
32767
32
SINUMARRCH
Signed Integer Array Read/Write
-32768 to
32767
32
SITEXTARRCH
ASCII Encoded Bytes Read/Write
Printable
Characters
8 0f 8
4 or 16
2 or 32
1 of 64
Write FC
01
05
02
Not Applicable
N/A
03
16(2)
04
Not Applicable
N/A
03
06
03
06
60000(1)
Loopback Diagnostics
08
SITEXTARRCH
Loopback Test
None
1 of 64
70001
79999
03
SINUMARRCH
IEEE Floating Point Read/Write
-34E38 to
34E38
16
16(2)
03
SINUMARRCH
IEEE FI. Pt in Addr-1 Read/Write
-34E38 to
34E38
16
16(2)
03
SINUMARRCH
Unsigned Integer Words Read/Write
0 to 65535
32
06
10001
19999
20001
29999(1)
30001
39999
40001
49999
50001
59999(1)
80002
89999(1)
90001
99999
(1)
These ranges are extensions to the Modbus protocol specifications to support certain Modbus devices.
(2)
C-4
Pass xxxxx
Performance Considerations
IMPORTANT
C-5
An active SIM function block processes the following actions once per
its publication period of 250 milliseconds. The publication rate is the
same whether the SIM block is assigned to a 5ms-CEE or a 50ms-CEE
type.
Load Serial Interface Array Channel block configurations to the
SIM.
Send Array Channel block write requests to the SIM.
Monitor status of the SIM, and report diagnostics, as applicable.
Of course, these actions are not performed when the SIM block is
inactive. When the SIM block is inactive, the Array Channel blocks set
their data to applicable default values.
The SIM block collects the writes for each array channel and sends
them to the SIM every 250ms. The following table lists the maximum
number writes a SIM block supports per channel in every 250ms
cycle. If the SIM blocks write list becomes full, it rejects a write to the
array channel block.
Table C.C
Array Channel Block
SINUMARRCH
SIFLAGARRCH
16
SITEXTARRCH (STRLEN = 8)
Writes to Array Channel Blocks can also be rejected because the SIM
is not keeping up with the writes being sent by the SIM block. Write
overruns are indicated by the SIM block FTAAOVRNFL and
FTABOVRNFL parameters. To provide an overrun condition alarm,
connect the overrun parameters to a FLAG function block configured
to generate an OffNormal alarm.
C-6
C-7
Error Messages
The following table lists some possible Serial Interface and
Allen-Bradley communication errors for reference. You may also need
to refer to the Allen-Bradley documentation for error messages
specific to the PLC.
Table C.D Select Error Code Descriptions
ERRCODE String
Description
Number of elements is out of range for the given Array Channel block.
ARR INIT
Array Channel block is configured, but no valid data has been received.
AUXMATCH
AUXDATA[2] and AUXDATA[3] configuration settings do not match the other channels in the FTA. All channels must
agree.
BAUD/PAR
CEE Idle
CFG LOAD
ChCfgErr
Array Channel block configuration error exists. Check block configuration carefully.
Ch Inctv
CONFIG
Can not load configuration to the SIM. Check all configuration data carefully.
DataCond
Array Channel block does not understand Data Conditioner (internal value) sent by the FTA.
C-8
Description
Array Channel block is not supported or out of range for this device.
DEV ADDR
Fac Test
FTA COMM
Inv Resp
IO Comm
There is an I/O communications problem between the CPM and the SIM.
KPA ADDR
MAX CONF
Md Inctv
The SIM function block is inactive, so the Array Channel block can not get new array data.
NO CONF
No Conn
The Array Channel block can not get data because a proper connection does not exist between the CPM and the SIM.
No Data
Transient condition that occurs when the Control Module containing the Array Channel block is activated. Condition
clears once ERRFL is set OFF or ON.
No SIMFB
Array Channel block can not locate its assigned SIM block. Be sure the SIM block is loaded to the CEE.
PLC TYPE
POL FREQ
SIG/MOD
Startidx
STR LEN
TMOT VAL
Ex or xx
NO CTS
Modem did not respond with Clear To Send within the message timeout time.
NO DSR
Parity
Checksum
MSGTMOUT
ChrTmout
RX OVFLO
A receive buffer overflow occurred on a message response received from the Modbus device.
C-9
Action/Reference
Restrictions
Configuration
In each Master and Slave Array Channel pair, configure the identical settings for the device address (DEVADDR)
and start index (STARTINDEX) parameters.
Configure identical, non-overlapping data areas in Master and Slave Array Channel pairs. For example, if Array 1
is 32 integers with a STARTINDEX of 90001, then Array 2 must have a STARTINDEX of 00033. If Array 1 is 512
Booleans with a STARTINDEX of 00000 and Array 2 is 16 floating points, then Array 2 must have a STARTINDEX
of 70513 and Array 3 must have a STARTINDEX of x00001 + 512 +16 = 529.
In all Slave Array Channels, set AUXDATA[4] parameter to a non-zero value (1.0) to enable the Remote Terminal
Unit (RTU) protocol.
In all Master Array Channels, set AUXDATA[1] parameter to recommended 3.0 second timeout.
In all Master and Slave Array Channel pairs, configure the identical settings for AUXDATA[2] and AUXDATA[3]
parameters.
For short distances, the default is RS-232 direct connection with NaN settings for both AUXDATA[2] and
AUXDATA[3] parameters.
For long distance, use RS485 connection with a 485.0 setting for the AUXDATA[2] parameter and a 19200.1
setting for the AUXDATA[3] parameter.
Common Errors
If the Master accesses a device address that does not match an existing Slave Array configuration, the Slave
responds with an Ex-2 error and freezes. After the Master address is corrected, you must restart or reconfigure
the Slave.
If the Slave Array is configured with overlapping data areas between arrays, it returns the STRTINDX error code.
If the Slave Array is configured with a conflicting device address, it returns the DEV ADDR error code.
If the Slave is configured for a STARTINDEX address of 8xxxx, it causes an Ex-2 error code in the Master. The
8xxxx address (IEEE Float at address 1) is not supported.
C-10
Reference Specifications
The following table lists some general specifications relevant to the
Serial Interface function.
Table C.F Serial Interface Specifications
Function
Description
Up to 2048 Booleans/second, or
Up to 128 integers/second, or
Up to 64 reals/second, or
Up to 4, 64-character strings/second, or
Weighted combinations of the above
10 channels/second
TC-MUX021
C-11
Description
General
Interface Type
EIA-RS232-D or EIA-485
Protocol
Modbus
Transmission Mode
RTU
RS232 or RS485
Selectable Parity
ESD Protection
IEEE 801.2
Surge Protection
Selectable On/Off
Configurable address
Configurable timeout
Keep Alive, Message Response Timeout, Signaling Mode/Modem Support, Baud Rate, Parity
EIA-RS232-D Support
Interface Type
Serial asynchronous
Lines Supported
TXD, RXD, Logic GND, Protectiv GND (Compatible with CCIT V.24; CCIT V.28)
EIA-485 Support
Interface Type
Lines Supported
Number of Transceivers
15 drops maximum
(1)
Read and write performance is sensitive to a number of variables, including the PLC type, scan time, PLC network configuration and traffic, amount of data access from
other devices, and the overall health of the PLC network. For best results, a direct PLC connection is recommended. The ratings listed do not represent best performance
figures. Read performance degrades with increased writes.
C-12
1757 Series
Pub. No.
1757-RM811A-EN-P
Part No.
957603-63
Please complete the sections below. Where applicable, rank the feature (1=needs improvement, 2=satisfactory, and 3=outstanding).
Overall Usefulness
Completeness
(all necessary information
is provided)
Technical Accuracy
(all provided information
is correct)
Clarity
1
(all provided information is
easy to understand)
Other Comments
Your Name
procedure/step
illustration
feature
example
guideline
other
explanation
definition
illustration
Location/Phone
Your Title/Function
PN 955107-82
NO POSTAGE
NECESSARY
IF MAILED
IN THE
UNITED STATES
1 ALLEN-BRADLEY DR
MAYFIELD HEIGHTS OH 44124-9705
PLEASE REMOVE
Other Comments
PN 957603-63
2002 Rockwell International Corporation. Printed in the U.S.A.