Revised heat gain rates from typical commercial cooking

appliances from RP-1362.


Link to this page

<a href="http://w w w .thefreelibrary.com/Revised+heat+gain+rates+from+typical+commercial+cooking+appliances...-a0217848196">Revised he

INTRODUCTION
The recommended heat gain values from typical commercial cooking appliances and ancillary kitchen
equipment currently published in the ASHRAE Fundamentals Handbook were obtained through
ASHRAE 391-RP completed in 1984 (Alereza, 1984) and subsequently by Fisher (Fisher, 1998).
Although a number of revisions have been made to Table 5, Recommended Rates of Heat Gain from
Typical Commercial Cooking Appliances, in Chapter 30 (ASHRAE, 2005), there remained concern
with respect to the thoroughness and accuracy of this information. As a result, the cooling loads
currently specified for commercial kitchen HVAC systems may be difficult to estimate and potentially
inaccurate.
It was recognized that Table 5 did not provide a complete list of equipment that may be specified in a
commercial kitchen design. Thus, the test matrix for the ASHRAE 1362-RP (Swierczyna, 2008)
identified 20 additional appliances to be tested with the goal of improving the information available in
Table 5. To compliment the specified appliances, refrigeration equipment was added to the test
matrix.
To improve the usability of the data, the heat gain values are reported in more relevant parameters for
many equipment types. Similarly, the classification and reported heat gain of reach-in refrigerators
and freezers should follow industry convention (e.g., single-door, two-door, or three-door) rather than
heat gain on a volumetric basis to be consistent with industry convention and design specifications.
The objective of this ASHRAE research project was to refine and expand the database for heat gain
to space from commercial foodservice equipment and, where applicable for hooded appliances, report
the exhaust ventilation rate required for capture and containment using the same test configuration
used for heat gain testing. The primary goals of the study were to provide more reliable heat gain
data, improve appliance categorization in Table 5, and improve the application guidelines in the
ASHRAE Handbook. A parallel goal was to report the exhaust ventilation rates found for each
appliance (Sobiski, 2008). As a result, the engineer will have a more comprehensive understanding of
the overall kitchen design, which will help to accurately calculate cooling loads, design HVAC
systems, and specify exhaust hoods.
The research project undertook the testing of both hooded and un-hooded equipment types. For the
hooded cooking appliances, the study determined the radiant heat gain to space during idle (ready-tocook) conditions. For some equipment, the heat gain was determined during representative usage,
such as dishwashers washing dishes. For un-hooded appliances, where the kitchen air conditioning
load is based on total enthalpy, the radiant and convective loads for the appliances were established,
including the latent contribution.
This paper presents the heat gain to space results for 83 appliances under 100 test conditions. The
heat loads are discussed with respect to the appliances' energy consumption rates and tabulated in a
format similar to the existing Table 5, Recommended Rates of Heat Gain from Typical Commercial
Cooking Appliances.

EXPERIMENTAL DESIGN
Appliance Specifications and Calibration
Appliances were specified and chosen according to Table 5, Recommended Rates of Heat Gain from
Typical Commercial Cooking Appliances. The appliances were calibrated according to the appropriate
ASTM Standard Test Methods. In selected cases, derivatives of the test procedures were applied to
the appliance under consideration. In other cases, where the ASTM Standard Test Method did not
exist, the calibration was performed to represent the typical operation of the appliance.
Hood Specifications
Most hooded appliances were evaluated in the rightmost position under a wall-mounted canopy hood
that measured 10.0 feet long by 4.0 feet deep by 2.0 feet tall (3.05 m by 1.22 m by 0.61 m). The front
lower edge of the hood was located at 6.5 feet (1.98 m) above the finished floor. Alternative hoods
were used as needed to accommodate unique appliance dimensions. For appliances requiring a
canopy hood greater than 4.0 feet (1.22 m) deep, a 1.0-foot (0.30 m) extension was added to the
canopy hood. For appliances requiring a 5.0-foot (1.52 m) deep canopy hood but better tested on an
individual basis, a 5.0 foot by 5.0 foot (1.52 m by 1.52 m) wall-mounted canopy hood was used.
Appliances such as dishwashers and holding cabinets were well suited for this hood. In some cases,
a 1.0-foot (0.30 m) rear filler panel was used to reduce the open area of the hood. The setup of the
10.0-foot hood is shown in Figure 1, the 5.0-foot hood is shown in Figure 2, and the 2-foot hood setup
is shown in Figure 3.
[FIGURE 1 OMITTED]
[FIGURE 2 OMITTED]
[FIGURE 3 OMITTED]
Airflow Visualization Systems
Focusing schlieren and shadowgraph systems were the primary tools used for airflow visualization
(Sobiski, 2008). Airflow visualization was necessary to verify complete capture and containment of the
thermal plume from the appliance and the accurate measurement of the generated loads. The airflow
rate used in the testing was the minimum rate to capture and contain the thermal plume while not
disturbing the natural convection of the plume.
TEST PROCEDURES
The heat gain to space determinations were made in accordance with ASTM F 2474-05 Standard
Test Method for Heat Gain to Space Performance of Commercial Kitchen Exhaust
Ventilation/Appliance Systems (ASTM, 2005). The precision of the reported heat gain was within the
specifications of [+ or -] 15%; values that calculated less than zero were reported as zeroHooded
Equipment
Heat gain from hooded appliances is transferred primarily to the kitchen space by radiation. Heat gain
to space was measured indirectly using an energy balance protocol, where the radiant load was
calculated as the difference between the energy consumed by the appliance and the energy removed
by the exhaust system and food product. The energy balance as defined by ASTM 2474-05 is shown
in Equation (1).
[E.sub.appliance] + [E.sub.mua] = [E.sub.exhaust air] + [E.sub.heat gain] + [E.sub.food] (if applicable)
(1)
In commercial kitchens, appliances are typically turned on at the beginning of each day and are not
turned off until closing time. Although the appliances are "up to temperature" 100% of the time, they
may be used to cook food less than 25% of the time, even in high-volume restaurants. Therefore, idle
heat gain measurement provides a good estimate for the cooling load from the hooded appliances.

More precise analysis can be had and a load profile constructed if cooking heat gain values are
available for hooded equipment, along with an activity log from the kitchen. When the cost, time, and
level of effort was considered, along with the percentage of time appliances typically operate during
the day, cooking heat gain testing for hooded appliances was considered to be well beyond the scope
of this project and beyond typical commercial kitchen load calculations.
The heat gain testing procedure is very time-intensive. Before the first heat gain test of the day was
performed, the hood airflow was set to the required rate. The appliance was turned on and allowed to
stabilize to the specified operating temperature. The appliance/hood system was then operated for an
additional period to ensure stabilization of the laboratory, hood, ductwork, and equipment
temperatures. Following stabilization, each idle heat gain test usually required a minimum of one hour
for a non-thermostatically controlled appliance and two hours for a thermostatically controlled
appliance to generate reliable data. The schematic for hooded appliance heat gain testing and the
energy balance boundary conditions are shown in Figure 4. A photograph of a cook line during heat
gain testing is shown in Figure 5.
[FIGURE 4 OMITTED]
[FIGURE 5 OMITTED]
For some low-input equipment, more than one of the same appliance was needed to improve the heat
gain accuracy. For most other cases, the exhaust airflow was limited to the area over the single
appliance being tested by blocking filters on the inactive section of the hood. This modification
reduced the airflow rate and increased the temperature rise from the room to the exhaust airstream,
thus improving the accuracy of the measured heat gain. To ensure valid results, sensitivity testing
was performed to minimize the airflow and maximize the temperature rise in the exhaust air stream
while maintaining capture and containment of the plume. A photograph showing the hood with a
portion of the filters blocked is shown in Figure 6.
[FIGURE 6 OMITTED]
Un-Hooded Equipment
For hooded appliances, the energy balance protocol assumes that 100% of the convective load was
exhausted with the cooking effluent. For un-hooded appliances, the convective load from the
appliances put a sensible and latent load, in addition to the radiant load, on the kitchen space.
For this project, all appliances were tested under a canopy exhaust hood in order to capture, contain,
and measure the convective load. The exhaust system was instrumented to measure the airflow, dry
bulb temperature, and dew point temperature. With these measurements, the sensible and latent load
was calculated for each appliance. The test setup to measure the radiant and convective split from
un-hooded equipment is shown as a photograph in Figure 7 and a schematic in Figure 8.
[FIGURE 7 OMITTED]
[FIGURE 8 OMITTED]
Calculations
The energy balance on Figure 8 yields:
For the sensible radiant load:
[E.sub.appliance] + [E.sub.mua] - [E.sub.exhaust] - [E.sub.radiation] - [E.sub.food](if applicable) = 0
(2)
Or
[E.sub.radiation] = [E.sub.appliance] + [E.sub.mua] - [E.sub.exhaust] - [E.sub.food] (if applicable) (3)

Where:
[E.sub.mua] is the energy in the makeup air stream
[E.sub.exhaust] is the energy in the exhaust air stream
[E.sub.appliance] is the energy consumption of the appliance
[E.sub.food] is the energy required to cook the food
For the convective load:
In IP
[q.sub.sensible convective load] = 1.08 [Q.sub.exh] ([T.sub.db-exh] - [T.sub.db-mua]) (4a)
[q.sub.latent load] = 4840 [Q.sub.exh] ([W.sub.exh] - [W.sub.mua]) (5a)
for SI
[q.sub.sensible convective load] = 1.23 [Q.sub.exh] ([T.sub.db-exh] - [T.sub.db-mua]) (4b)
[q.sub.latent load] = 3010 [Q.sub.exh] ([W.sub.exh] - [W.sub.mua]) (5b)
Where:
[q.sub.sensible convective load] is the sensible convective heat load generated by the appliance in
Btu/h (W)
[q.sub.latent load] is the latent heat load generated by the appliance in Btu/h (W)
[Q.sub.exh] is the volumetric flow rate of the exhaust air stream in cfm (L/s)
[T.sub.db-mua] the dry bulb temperature of the makeup air stream in [degrees]F ([degrees]C)
[T.sub.db-exh] is the dry bulb temperature of the exhaust air stream in [degrees]F ([degrees]C)
[W.sub.mua] is the humidity ratio of the makeup air stream in pound of water per pound of dry air
(kg/kg)
[W.sub.exh] is the humidity ratio of the exhaust air stream in pound of water per pound of dry air
(kg/kg)
HEAT GAIN TO SPACE RESULTS
Heat gain to space was measured during idle conditions for most hooded appliances. For unhooded
equipment, heat gain to space was usually measured during idle and cooking conditions. In addition,
sensitivity testing was performed on some appliances to investigate different operating conditions.
The project generated a significant amount of heat gain data with the appliances at idle conditions.
The majority of appliances were shown to have heat gain values below 2,000 Btu/h (586 W). Sixteen
appliances were at or below detectable limits, as indicated with a reported heat gain to space value of
zero. The majority of the sixteen appliances used water, such as dishwashers, steam kettles,
steamers, rethermalizers, pasta cookers, and drawer warmers, at various operating modes with
cooking surface or skin temperatures below 212[degrees]F (100[degrees]C). Eight appliances were
measured with heat gain to space values ranging from 8,000 to 14,900 Btu/h (2,345 to 4,367 W),
which were the highest heat gain values measured during the project. These eight appliances
included broilers or ranges, at various operating configurations.
When the sensible heat gain values were sorted by measured appliance energy consumption rate,

the generally accepted trend of higher energy consuming appliances having a higher measured heat
gain was not well supported, since many exceptions to this trend existed. For instance, the gas
overfired broiler was measured as having the fourth-highest energy consumption rate at 87,900 Btu/h
(25,761 W), and was rated at 100,000 Btu/h (29,307 W) (nameplate). However, a heat gain of 2,500
Btu/h (733 W) was measured, which is significantly lower than the heat gain measured for other
appliances with similar energy consumption rates. A graph of the data is shown in Figures 9 and 10.
Figure 9a Sensible heat gain to space sorted by appliance energy
consumption rate below 6,000 Btu/h energy rate [I-P],
Proofing Cabinet, Electric
Popcorn Popper, Electric
2-Drawer Warmer, Electric
Rice Cooker, Gas, Cover On
Waffle Iron, Electric, Lid Down
Egg Cooker, Electric
Steamer, Bun, Electric
Smoker, Pressurized, Electric
Refrigerated Prep Table, Electric, Lid Down
Refrigerated Prep Table, Electric, Lid Up
Freezer, Portable, Electric
Holding Cabinet, Insulated, Electric
Coffee Brew Station, Electric
Waffle Iron, Etectric, Lid Up
Dishwasher, Door-Type, Rack, Chemical
Dishwasher, Door-Type, Rack, Hot Water
Espresso Machine, Electric
Proofing Cabinet, Electric
Dishwasher, Undercounter, Chemical
Dishwasher, Undercounter, Hot Water
Grill, Panini, Electric, Lid Down
Steam Kettle, 40 Gallon, Electric, Lid Down,
Fryer, Kettle, Electric
Hot Dog Roller, Electric
Hot Deli Case, Electric, Dry
Steam Kettle, 60 Gallon, Electric, Lid Down,
Fryer, Pressure, Electric
Fryer, 1 (Split) Vat, Electric
Hot Plate, Electric
Grill, Panini, Electic, Lid Up
Hot Deli Case, Etectric, Wet
Steam Kettle, 10 Gallon, Gas, Lid Down, Simmer
Holding Cabinet, Uninsulated, Electric
Steam Table, Well-Type, Electric
Toaster Conveyor Small, Electric
Oven, Convection, Half Size, Electric
Proofer/Rethermalizer, Electric
Range, 6 Element, Electric (Range: Off/Oven)
Oven, Rapid Cook, Electric
Steam Kettle, 40 Gallon, Gas, Lid Down, Simmer
Oven, Mini Revolving Rack 325[degrees]F, Electric
Fryer, 1(Split) Vat, Gas
Toaster, Vertical Contact, Electric
Braising Pan, Electric, Lid Down, Simmer
Steam Kettle, 60 Gallon, Gas, Lid Down, Simmer
Oven, Combi, Combi Mode, Electric
Oven, Combi, Convect Mode, Electric
Oven, Combi, Convect Mode, Gas
Oven, Combi, Combi Mode, Gas
Sensible Radiative Heat Gain Rate [Btu/h]

0
100
0
300
0
300
600
200
600
700
500
400
200
800
0
0
400
1,200
900
900
500
300
500
900
900
100
500
1,000
900
1,200
900
300
700
300
400
500
0
1,000
1,000
0
1,100
1,100
2,700
0
0
800
1,400
1,000
400

Note: Table made from bar graph.


Figure 9b Sensible heat gain to space sorted by appliance energy
consumption rate below 1,760 W energy rate [SI],
Proofing Cabinet, Electric
Popcorn Popper, Electric
2-Drawer Warmer, Electric
Rice Cooker, Gas, Cover On
Waffle Iron, Electric, Lid Down
Egg Cooker, Electric
Steamer, Bun, Electric
Smoker, Pressurized, Electric
Refrigerated Prep Table, Electric, Lid Down
Refrigerated Prep Table, Electric, Lid Up
Freezer, Portable, Electric
Holding Cabinet, Insulated, Electric
Coffee Brew Station, Electric
Waffle Iron, Electric, Lid Up
Dishwasher, Door-Type, Rack, Chemical
Dishwasher, Door-Type, Rack, Hot Water
Espresso Machine, Electric
Proofing Cabinet, Electric
Dishwasher, Undercounter, Chemical
Dishwasher, Undercounter Hot Water
Grill, Panini, Electric, Lid Down
Steam Kettle, 40 Gallon, Electric, Lid Down
Fryer, Kettle, Electric
Hot Dog Roller, Electric
Hot Deli Case, Etectric, Dry
Steam Kettle, 60 Gallon, Electric, Lid Down,
Fryer, Pressure, Electric
Fryer, 1 (Split) Vat, Electric
Hot Plate, Electric
Grill, Panini, Electic, Lid Up
Hot Deli Case, Electric, Wet
Steam Kettle, 10 Gallon, Gas, Lid Down, Simmer
Holding Cabinet, Uninsulated, Electric
Steam Table, Well-Type, Electric
Toaster Conveyor Small, Electric
Oven, Convection, Half Size, Electric
Proofer/Rethermalizer, Electric
Range, 6 Element Electric (Range: Off/Oven)
Oven, Rapid Cook, Electric
Steam Kettle, 40 Gallon, Gas, Lid Down, Simmer
Oven, Mini Revolving Rack 325[degrees]F, Electric
Fryer, 1 (Split) Vat, Gas
Toaster, Vertical Contact, Electric
Braising Pan, Etectric, Lid Down, Simmer
Steam Kettle, 60 Gallon, Gas, Lid Down, Simmer
Oven, Combi, Combi Mode, Electric
Oven, Combi, Convet Mode, Electric
Oven, Combi, Convect Mode, Gas
Oven, Combi, Combi Mode, Gas

0
29
0
88
0
88
176
59
176
205
147
117
59
234
0
0
117
352
264
264
147
88
147
264
264
29
147
293
264
352
264
88
205
88
117
147
0
293
293
0
322
322
791
0
0
234
410
293
117

Sensible Radiative Heat Gain Rate [W]


Note: Table made from bar graph.
Figure 10a Sensible heat gain to space sorted by appliance energy
consumption rate at or above 6,000 Btu/h energy rate [I-P],

Griddle, Small, Electric


Steam Kettle, 40 Gallon, Electric, Lid Up, Simmer

2,700
400

Oven, Mini Revolving Rack 400[degrees]F, Electric With Proofing


Cabinet 90[degrees]F

1,900

Oven, Convection, Electric

1,500

Steam Kettle, 10 Gallon, Gas, Lid Up, Simmer

500

Griddle, Clamshell, Electric, Platens Down

1,400

Range, 6 Burner, Gas (Range: Off/Oven: 350 deg F)

2,000

Steam Kettle, 60 Gallon, Electric, Lid Up, Simmer

Braising Pan, Electric, Lid Up, Simmer

Griddle Clamshell, Gas, Platens Down


Steamer, Atmospheric, Gas
Oven, Convection, Tall, Electric
Pasta Cooker, Electric, Simmer
Fryer, Pressure, Gas
Toaster, Conveyor, Electric
Braising Pan, Gas, Lid Down, Simmer
Steam Kettle, 40 Gallon, Gas, Lid Up, Simmer

1,800
0
1,300
0
800
3,000
400
0

Griddle, Electric

4,500

Griddle, Clamshell, Electric, Platens Up

3,600

Oven, Combi, Gas

3,000

Cheese Melter, Electric

4,600

Oven, Convection, Gas

1,000

Fryer, Doughnut, Gas

2,900

Oven, Countertop Conveyor, Electric

2,200

Oven, Rotisserie, Electric

4,500

Braising Pan, Gas, Lid Up, Simmer


Griddle, Clamshell, Gas, Platens Up

800
4,900

Steam Kettle, 60 Gallon, Gas, Lid Up, Simmer

200

Steamer, Atmospheric, Electric

200

Range, 6 Element, Electic (Range, 50% (3On)/Oven: Off)

6,300

Fryer, 6 Vats, Electric

5,900

Griddle, Gas

3,700

Oven, Deck, Gas

3,500

Rethermalizer, Gas
Salamander, Electric

0
7,000

Pasta Cooker, Gas, Simmer


Fryer, 6 Vats, Gas

0
7,600

Broiler, Underfired, Electric

10,800

Range, 6 Element, Electric (Range, 100%/Oven: Off)

13,900

Salamander, Gas
Range, 6 Element Electric (Range: 100%/Oven: 350 deg F)

5,300
14,500

Broiler, Underfired, Solid Fuel, 40 Pounds of Hickory Briquettes

6,200

Broiler, Underfired, Solid Fuel, 40 Pounds of Mesquite Lumps

7,000

Hot Top, Gas

11,800

Range, 6 Burner, Gas (Range: 50% (3 On)/Oven: Off)

7,100

Oven, Conveyor, Gas

7,800

Broiler, Underfired, Gas

9,000

Range, Wok, Gas

5,200

Broiler, Overfired, Gas

2,500

Broiler, Conveyor, Gas

13,200

Range, 6 Burner, Gas (Range: 100%/Oven: Off)

11,600

Range, 6 Burner, Gas (Range: 100%/Oven: 350 deg F)

13,600

Sensible Radiative Heat Gain Rate [Btu/h]


Note: Table made from bar graph.
Figure 10b Sensible heat gain to space sorted by appliance energy
consumption rate at or above 1,760 W energy rate [SI],
Griddle, Small, Electric

791

Steam Kettle, 40 Gallon, Electric, Lid Up, Simmer

117

Oven, Mini Revolving Rack 400[degrees]F, Electric With Proofing


Cabinet 90[degrees]F

557

Oven, Convection, Electric

440

Steam Kettle, 10 Gallon, Gas, Lid Up, Simmer

147

Griddle, Clamshell, Electric, Platens Down

410

Range, 6 Burner, Gas (Range: Off/Oven: 350 deg F)

586

Steam Kettle, 60 Gallon, Electric, Lid Up, Simmer

Braising Pan, Electric, Lid Up, Simmer

Griddle, Clamshell, Gas, Platens Down


Steamer, Atmospheric, Gas
Oven, Convection, Tall, Electric
Paste Cooker, Electric, Simmer

528
0
381
0

Fryer, Pressure, Gas

234

Toaster, Conveyor, Electric

879

Braising Pan, Gas, Lid Down, Simmer

117

Steam Kettle, 40 Gallon, Gas, Lid Up, Simmer

Griddle, Electric

1,319

Griddle, Clamshell, Electic, Platens Up

1,055

Oven, Combi, Gas


Cheese Melter, Electric

879
1,348

Oven, Convection, Gas

293

Fryer, Doughnut, Gas

850

Oven, Countertop Conveyor, Electric

645

Oven, Rotisserie, Electric


Braising Pan, Gas, Lid Up, Simmer
Griddle, Clamshell, Gas, Platens Up

1,319
234
1,436

Steam Kettle, 60 Gallon, Gas, Lid Up, Simmer

59

Steamer, Atmospheric, Electric

59

Range, 6 Element, Electric (Range: 50% (3 On)/Oven: Off)

1,846

Fryer, 6 Vats, Electric

1,729

Griddle, Gas

1,084

Oven, Deck, Gas

1,026

Rethermalizer, Gas
Salamander, Electric

0
2,051

Pasta Cooker, Gas, Simmer

Fryer, 6 Vats, Gas

2,227

Broiler, Underfired, Electric

3,165

Range, 6 Element, Electric (Range, 100%/Oven: Off)

4,074

Salamander, Gas

1,553

Range, 6 Element, Electric (Range, 100%/Oven: 350 deg F)

4,250

Broiler, Underfired, Solid Fuel, 40 Pounds of Hickory Briquettes

1,817

Broiler, Underfired, Solid Fuel, 40 Pounds of Mesquite Lumps

2,051

Hot Top, Gas

3,458

Range, 6 Burner, Gas (Range: 50% (3 On)/Oven: Off)

2,081

Oven, Conveyor, Gas

2,286

Broiler, Underfired, Gas

2,638

Range, Wok, Gas

1,524

Broiler, Overfired, Gas

733

Broiler, Conveyor, Gas

3,869

Range, 6 Burner, Gas (Range: 100%/Oven: Off)

3,400

Range, 6 Burner, Gas (Range: 100%/Oven: 350 deg F)

3,986

Sensible Radiative Heat Gain Rate [W]


Note: Table made from bar graph.

HEAT GAIN TO SPACE AS A FUNCTION OF APPLIANCE ENERGY CONSUMPTION RATE FOR


GAS APPLIANCES
The regression of sensible radiant heat gain versus appliance consumption rate represents the
radiation factor, [F.sub.r]=[[q.sub.sensible]/[q.sub.idle energy consumption]], as shown for gas
appliances in Figure 11. The correlation is 0.69 for a radiation factor of 0.11. The outliers were test
conditions where the appliances had either high emissivity, with high radiant gains and low input
rates, such as hot tops; or low emissivity, with low radiant gains and high energy rates such as the
shielded overfired broiler.
The regressed radiation factor for gas appliances of 0.11 compared well to the average of 0.14 and
median of 0.11 for the data from 34 hooded appliances. Even though the 0.11 would be accurate on
average, over a 100% standard deviation from the mean would allow for large errors in the heat load
calculation for specific appliance lines. Therefore, the tabulated heat gain data should be applied in
the HVAC design.
HEAT GAIN TO SPACE AS A FUNCTION OF APPLIANCE ENERGY CONSUMPTION RATE FOR
ELECTRIC APPLIANCES
The regression of sensible radiant heat gain versus electric appliance consumption rate, or [F.sub.r],
is shown in Figure 12. The correlation is 0.87 for a radiation factor, [F.sub.r], of 0.34. The test

conditions where appliances with high emissivity and high energy rates and low heat gain such as
kettles were outliers and show up as constant low loads (near zero).
The regressed radiation factor for electric appliances of 0.34 compared conservatively to the average
of 0.27 and the median of 0.28 for the data from 38 appliances. Appling the regressed value would
overstate heat gain on average by 36%. Again, the tabulated heat gain data should be applied in the
HVAC design.
TABLE 5 OF THE NONRESIDENTIAL COOLING AND HEATING LOAD CALCULATIONS CHAPTER
OF THE ASHRAE HANDBOOK OF FUNDAMENTALS
Using the measured data for heat gain, appliance usage, and stated nameplate ratings, a table similar
to the current Table 5 Recommended Rates of Heat Gain from Typical Commercial Cooking
Appliances was constructed. The sensible radiant heat gain for hooded appliances and the sensible
radiant, sensible convective and latent heat gain for unhooded appliances were categorized for 83
appliances and 100 test conditions by fuel, usage, and radiation factors and presented in Tables 1
through 4. Table 5 summarizes three types of dishwashers while operating in stand-by and washing
modes. In general, the heat gain was measured during idle (ready-to-cook) conditions. An asterisk in
the tables of this document denotes a new appliance that was added to the original table.
Table 1a. Recommended Rates of Radiant and Convective Heat Gain from
Unhooded Electric Appliances During Idle (Ready-to-Cook) Conditions
[I-P]
Electric, Exhaust Hood Not
Required

Energy Rate
[Btu/h]

Appliance

Rated

Stand-by

Sensible
Radiant

Cabinet: hot serving


(large)-insulated *

6,800

1,200

400

Cabinet: hot serving


(large)-uninsulated

6,800

3,500

700

Cabinet: proofing
(large) *

17,400

1,400

1,200

Cabinet: proofing
(small-15 shelf)

14,300

3,900

Coffee brewing station

13,000

1,200

200

4,100

500

10,900

700

300

Drawer warmers-2 drawer


(moist holding) *
Egg cooker
Espresso machine *

8,200

1,200

400

Food warmer: steam


table (2-well-type)

5,100

3,500

300

Freezer (small)

2,700

1,100

500

Hot dog roller *

3,400

2,400

900

Hot plate: single


burner, high speed

3,800

3,000

900

Hot-food case (dry

31,100

2,500

900

holding) *
Hot-food case (moist
holding) *

31,100

3,300

900

Microwave oven:
commercial (heavy
duty)

10,900

Oven: countertop
conveyorized
bake/finishing *

20,500

12,600

2,200

Panini *

5,800

3,200

1,200

Popcorn popper *

2,000

200

100

Rapid-cook Oven
(quartz-halogen) *

41,000

Rapid-cook Oven
(microwave/convection) *

24,900

4,100

1,000

Reach-in refrigerator *

4,800

1,200

300

Refrigerated prep table *

2,000

900

600

Steamer (bun)

5,100

700

600

Toaster: 4-slice pop up


(large): cooking

6,100

3,000

200

Toaster: contact
(vertical)

11,300

5,300

2,700

Toaster: conveyor
(large)

32,800

10,300

3,000

Toaster: small
conveyor

5,800

3,700

400

Waffle Iron

3,100

1,200

800

Rate of Heat Gain


[Btu/h]

Usage
Factor

Unhooded
Appliance

Sensible
Convective

Latent

Total

[F.sub.u]

Cabinet: hot serving


(large)-insulated *

800

1,200

0.18

Cabinet: hot serving


(large)-uninsulated

2,800

3,500

0.51

Cabinet: proofing
(large) *

200

1,400

0.08

Cabinet: proofing

900

3,000

3,900

0.27

(small-15 shelf)
Coffee brewing station

300

700

1,200

0.09

200

200

0.12

Egg cooker

400

700

0.06

Espresso machine *

800

1,200

0.15

Food warmer: steam


table (2-well-type)

600

2,600

3,500

0.69

Freezer (small)

600

1,100

0.41

Hot dog roller *

1,500

2,400

0.71

Hot plate: single


burner, high speed

2,100

3,000

0.79

Hot-food case (dry


holding) *

1,600

2,500

0.08

Hot-food case (moist


holding) *

1,800

600

3,300

0.11

0.00

10,400

12,600

0.61

2,000

3,200

0.55

100

200

0.10

0.00

3,100

1,000

0.16

Reach-in refrigerator *

900

1,200

0.25

Refrigerated prep table *

300

900

0.45

Steamer (bun)

100

700

0.14

Toaster: 4-slice pop up


(large): cooking

1,400

1,000

2,600

0.49

Toaster: contact
(vertical)

2,600

5,300

0.47

Toaster: conveyor
(large)

7,300

10,300

0.31

Toaster: small

3,300

3,700

0.64

Drawer warmers-2 drawer


(moist holding) *

Microwave oven:
commercial (heavy
duty)
Oven: countertop
conveyorized
bake/finishing *
Panini *
Popcorn popper *
Rapid-cook Oven
(quartz-halogen) *
Rapid-cook Oven
(microwave/convection) *

conveyor
Waffle Iron

400
Radiation
Factor

Appliance

[F.sub.r]

Cabinet: hot serving


(large)-insulated *

0.33

Cabinet: hot serving


(large)-uninsulated

0.20

Cabinet: proofing
(large) *

0.86

Cabinet: proofing
(small-15 shelf)

0.00

Coffee brewing station

0.17

Drawer warmers-2 drawer


(moist holding) *

0.00

Egg cooker

0.43

Espresso machine *

0.33

Food warmer: steam


table (2-well-type)

0.09

Freezer (small)

0.45

Hot dog roller *

0.38

Hot plate: single


burner, high speed

0.30

Hot-food case (dry


holding) *

0.36

Hot-food case (moist


holding) *

0.27

Microwave oven:
commercial (heavy
duty)

0.00

Oven: countertop
conveyorized
bake/finishing *

0.17

Panini *

0.38

Popcorn popper *

0.50

Rapid-cook Oven
(quartz-halogen) *

0.00

1,200

0.39

Rapid-cook Oven
(microwave/convection) *

0.24

Reach-in refrigerator *

0.25

Refrigerated prep table *

0.67

Steamer (bun)

0.86

Toaster: 4-slice pop up


(large): cooking

0.07

Toaster: contact
(vertical)

0.51

Toaster: conveyor
(large)

0.29

Toaster: small
conveyor

0.11

Waffle Iron

0.67

* An asterisk denotes a new appliance that was added to the original


table.
Table 1b. Recommended Rates of Radiant and Convective Heat Gain from
Unhooded Electric Appliances During Idle (Ready-to-Cook) Conditions [SI]
Electric, Exhaust Hood Not
Required

Energy Rate [W]

Appliance

Rated

Stand-by

Cabinet: hot serving


(large)-insulated *

1,993

352

117

Cabinet: hot serving


(large)-uninsulated

1,993

1,026

205

Cabinet: proofing
(large) *

5,099

410

352

Cabinet: proofing
(small-15 shelf)

4,191

1,143

Coffee brewing station

3,810

352

59

Drawer warmers-2 drawer


(moist holding) *

1,202

147

Egg cooker

3,194

205

88

Espresso machine *

2,403

352

117

Food warmer: steam


table (2-well-type)

1,495

1,026

Freezer (small)

791

322

Sensible
Radiant

88
147

Hot dog roller *

996

703

264

Hot plate: single


burner, high speed

1,114

879

264

Hot-food case (dry


holding) *

9,115

733

264

Hot-food case (moist


holding) *

9,115

967

264

Microwave oven:
commercial (heavy
duty)

3,194

Oven: countertop
conveyorized
bake/finishing *

6,008

3,693

645

Panini *

1,700

938

352

586

59

29

0
293

Popcorn popper *
Rapid-cook Oven
(quartz-halogen) *

12,016

Rapid-cook Oven
(microwave/convection) *

7,297

1,202

Reach-in refrigerator *

1,407

352

88

586

264

176

Steamer (bun)

1,495

205

176

Toaster: 4-slice pop up


(large): cooking

1,788

879

59

Toaster: contact
(vertical)

3,312

1,553

791

Toaster: conveyor
(large)

9,613

3,019

879

Toaster: small
conveyor

1,700

1,084

117

352

234

Refrigerated prep table *

Waffle Iron

909

Rate of Heat Gain


[W]

Usage
Factor

Unhooded
Appliance

Sensible
Convective

Latent

Total

[F.sub.u]

Cabinet: hot serving


(large)-insulated *

234

352

0.18

Cabinet: hot serving

821

1,026

0.51

(large)-uninsulated
Cabinet: proofing
(large) *

Cabinet: proofing
(small-15 shelf)

264

Coffee brewing station

88

Drawer warmers-2 drawer


(moist holding) *

59

410

0.08

879

1,143

0.27

205

352

0.09

59

59

0.12

Egg cooker

117

205

0.06

Espresso machine *

234

352

0.15

Food warmer: steam


table (2-well-type)

176

762

1,026

0.69

Freezer (small)

176

322

0.41

Hot dog roller *

440

703

0.71

Hot plate: single


burner, high speed

615

879

0.79

Hot-food case (dry


holding) *

469

733

0.08

Hot-food case (moist


holding) *

528

176

967

0.11

0.00

3,048

3,693

0.61

586

938

0.55

Popcorn popper *

29

59

0.10

Rapid-cook Oven
(quartz-halogen) *

0.00

Rapid-cook Oven
(microwave/convection) *

909

293

0.16

Reach-in refrigerator *

264

352

0.25

Refrigerated prep table *

88

264

0.45

Steamer (bun)

29

205

0.14

Microwave oven:
commercial (heavy
duty)
Oven: countertop
conveyorized
bake/finishing *
Panini *

Toaster: 4-slice pop up


(large): cooking

410

293

762

0.49

Toaster: contact

762

1,553

0.47

(vertical)
Toaster: conveyor
(large)

2,139

3,019

0.31

Toaster: small
conveyor

967

1,084

0.64

Waffle Iron

117

352

0.39

Radiation
Factor
Appliance

[F.sub.r]

Cabinet: hot serving


(large)-insulated *

0.33

Cabinet: hot serving


(large)-uninsulated

0.20

Cabinet: proofing
(large) *

0.86

Cabinet: proofing
(small-15 shelf)

0.00

Coffee brewing station

0.17

Drawer warmers-2 drawer


(moist holding) *

0.00

Egg cooker

0.43

Espresso machine *

0.33

Food warmer: steam


table (2-well-type)

0.09

Freezer (small)

0.45

Hot dog roller *

0.38

Hot plate: single


burner, high speed

0.30

Hot-food case (dry


holding) *

0.36

Hot-food case (moist


holding) *

0.27

Microwave oven:
commercial (heavy
duty)

0.00

Oven: countertop
conveyorized
bake/finishing *

0.17

Panini *

0.38

Popcorn popper *

0.50

Rapid-cook Oven
(quartz-halogen) *

0.00

Rapid-cook Oven
(microwave/convection) *

0.24

Reach-in refrigerator *

0.25

Refrigerated prep table *

0.67

Steamer (bun)

0.86

Toaster: 4-slice pop up


(large): cooking

0.07

Toaster: contact
(vertical)

0.51

Toaster: conveyor
(large)

0.29

Toaster: small
conveyor

0.11

Waffle Iron

0.67

* An asterisk denotes a new appliance that was added to the original


table.
Table 2a. Recommended Rates of Radiant Heat Gain from Hooded Electric
Appliances During Idle (Ready-to-Cook) Conditions [I-P]
Electric, Exhaust
Hood Required

Energy Rate
[Btu/h]

Rate of
Heat Gain
[Btu/h]

Usage
Factor

Radiation
Factor

Hooded
Appliance

Rated

Stand-by

Sensible
Radiant

[F.sub.u]

[F.sub.r]

Broiler:
underfired
3-foot

36,900

30,900

10,800

0.84

0.35

Cheesemelter *

12,300

11,900

4,600

0.97

0.39

Fryer: kettle

99,000

1,800

500

0.02

0.28

Fryer: open
deep-fat 1-vat

47,800

2,800

1,000

0.06

0.36

Fryer: pressure

46,100

2,700

500

0.06

0.19

Griddle: double
sided 3-foot
(clamshell-down) *

72,400

6,900

1,400

0.10

0.20

Griddle: double
sided 3-foot
(clamshell-up) *

72,400

11,500

3,600

0.16

0.31

Griddle: flat
3-foot

58,400

11,500

4,500

0.20

0.39

Griddle-small
3-foot *

30,700

6,100

2,700

0.20

0.44

Induction cooktop *

71,700

0.00

0.00

Induction Wok *

11,900

0.00

0.00

Oven: combi:
combi-mode *

56,000

5,500

800

0.10

0.15

Oven: combi:
convection mode

56,000

5,500

1,400

0.10

0.25

Oven: convection
full-size

41,300

6,700

1,500

0.16

0.22

Oven: convection
half-size *

18,800

3,700

500

0.20

0.14

Pasta cooker *

75,100

8,500

0.11

0.00

Range Top: top


off/oven on *

16,600

4,000

1,000

0.24

0.25

Range Top: 3
elements on/oven
off

51,200

15,400

6,300

0.30

0.41

Range Top: 6
elements on/oven
off

51,200

33,200

13,900

0.65

0.42

Range Top: 6
elements on/oven
on

67,800

36,400

14,500

0.54

0.40

Range: hot-top

54,000

51,300

11,800

0.95

0.23

Rotisserie *

37,900

13,800

4,500

0.36

0.33

Salamander *

23,900

23,300

7,000

0.97

0.30

Steam kettle:
large (60 gal)
simmer lid down *

110,600

2,600

100

0.02

0.04

Steam kettle:
small (40 gal)
simmer lid down *

73,700

1,800

300

0.02

0.17

Steamer:
compartment:
atmospheric *

33,400

15,300

200

0.46

0.01

Tilting
skillet/Braising
pan

32,900

5,300

0.16

0.00

* An asterisk denotes a new appliance that was added to the original


table.
Table 2b. Recommended Rates of Radiant Heat Gain from Hooded Electric
Appliances During Idle (Ready-to-Cook) Conditions [SI]
Electric, Exhaust
Hood Required

Energy Rate [W]

Rate of
Heat Gain
[W]

Usage
Factor

Radiation
Factor

[F.sub.u]

[F.sub.r]

Hooded
Appliance
Broiler:
underfired
3-foot
Cheesemelter *

Rated

Stand-by

Sensible
Radiant

10,814

9,056

3,165

0.84

0.35

3,605

3,488

1,348

0.97

0.39

Fryer: kettle

29,014

528

147

0.02

0.28

Fryer: open
deep-fat 1-vat

14,009

821

293

0.06

0.36

Fryer: pressure

13,511

791

147

0.06

0.19

Griddle: double
sided 3-foot
(clamshell-down) *

21,218

2,022

410

0.10

0.20

Griddle: double
sided 3-foot
(clamshell-up) *

21,218

3,370

1,055

0.16

0.31

Griddle: flat
3-foot

17,115

3,370

1,319

0.20

0.39

Griddle-small
3-foot *

8,997

1,788

791

0.20

0.44

21,013

0.00

0.00

3,488

0.00

0.00

Induction cooktop *
Induction Wok *
Oven: combi:
combi-mode *

16,412

1,612

234

0.10

0.15

Oven: combi:
convection mode

16,412

1,612

410

0.10

0.25

Oven: convection
full-size

12,104

1,964

440

0.16

0.22

Oven: convection

5,510

1,084

147

0.20

0.14

half-size *
Pasta cooker *

22,010

2,491

0.11

0.00

Range Top: top


off/oven on *

4,865

1,172

293

0.24

0.25

Range Top: 3
elements on/oven
off

15,005

4,513

1,846

0.30

0.41

Range Top: 6
elements on/oven
off

15,005

9,730

4,074

0.65

0.42

Range Top: 6
elements on/oven
on

19,870

10,668

4,250

0.54

0.40

Range: hot-top

15,826

15,035

3,458

0.95

0.23

Rotisserie *

11,107

4,044

1,319

0.36

0.33

Salamander *

7,004

6,829

2,051

0.97

0.30

Steam kettle:
large (60 gal)
simmer lid down *

32,414

762

29

0.02

0.04

Steam kettle:
small (40 gal)
simmer lid down *

21,599

528

88

0.02

0.17

Steamer:
compartment:
atmospheric *

9,789

4,484

59

0.46

0.01

Tilting
skillet/Braising
pan

9,642

1,553

0.16

0.00

* An asterisk denotes a new appliance that was added to the original


table.
Table 3a. Recommended Rates of Radiant Heat Gain from Hooded Gas
Appliances During Idle (Ready-to-Cook) Conditions [I-P]
Gas, Exhaust Hood
Required

Energy Rate
[Btu/h]

Rate of
Heat Gain
[Btu/h]

Usage
Factor

Radiation
Factor

[F.sub.u]

[F.sub.r]

Hooded
Appliance
Broiler: batch *
Broiler: chain
(conveyor)

Rated

Stand-by

Sensible
Radiant

95,000

69,200

8,100

0.73

0.12

132,000

96,700

13,200

0.73

0.14

Broiler:
overfired
(upright) *

100,000

87,900

2,500

0.88

0.03

Broiler:
underfired
3-foot

96,000

73,900

9,000

0.77

0.12

Fryer: doughnut

44,000

12,400

2,900

0.28

0.23

Fryer: open
deep-fat 1 vat

80,000

4,700

1,100

0.06

0.23

Fryer: pressure

80,000

9,000

800

0.11

0.09

Griddle: double
sided 3-foot
(clamshell-down) *

108,200

8,000

1,800

0.07

0.23

Griddle: double
sided 3-foot
(clamshell-up) *

108,200

14,700

4,900

0.14

0.33

Griddle: flat
3-foot

90,000

20,400

3,700

0.23

0.18

Oven: combi:
combi-mode *

75,700

6,000

400

0.08

0.07

Oven: combi:
convection mode

75,700

5,800

1,000

0.08

0.17

Oven: convection
full-size

44,000

11,900

1,000

0.27

0.08

Oven: conveyor
(pizza)

170,000

68,300

7,800

0.40

0.11

Oven: deck

105,000

20,500

3,500

0.20

0.17

Oven: rack
mini-rotating *

56,300

4,500

1,100

0.08

0.24

Pasta cooker *

80,000

23,700

0.30

0.00

Range Top: top


off/oven on *

25,000

7,400

2,000

0.30

0.27

Range Top: 3
burners on/oven off

120,000

60,100

7,100

0.50

0.12

Range Top: 6
burners on/oven off

120,000

120,800

11,500

1.01

0.10

Range Top: 6
burners on/oven on

145,000

122,900

13,600

0.85

0.11

Range: Wok *

99,000

87,400

5,200

0.88

0.06

Rethermalizer *

90,000

23,300

11,500

0.26

0.49

Rice cooker *

35,000

500

300

0.01

0.60

Salamander *

35,000

33,300

5,300

0.95

0.16

Steam kettle:
large (60 gal)
simmer lid down *

145,000

5,400

0.04

0.00

Steam kettle:
small (10 gal)
Simmer lid down *

52,000

3,300

300

0.06

0.09

100,000

4,300

0.04

0.00

26,000

8,300

0.32

0.00

104,000

10,400

400

0.10

0.04

Steam kettle:
small (40 gal)
simmer lid down
Steamer:
compartment:
atmospheric *
Tilting
skillet/Braising pan

* An asterisk denotes a new appliance that was added to the original


table.
Table 3b. Recommended Rates of Radiant Heat Gain from Hooded Gas
Appliances During Idle (Ready-to-Cook) Conditions [SI]
Gas, Exhaust Hood
Required

Energy Rate [W]

Rate of
Heat Gain
[W]

Usage
Factor

Radiation
Factor

[F.sub.r]

Hooded
Appliance

Rated

Stand-by

Sensible
Radiant

[F.sub.u]

Broiler: batch *

27,842

20,281

2,374

0.73

0.12

Broiler: chain
(conveyor)

38,685

28,340

3,869

0.73

0.14

Broiler:
overfired
(upright) *

29,307

25,761

733

0.88

0.03

Broiler:
underfired
3-foot

28,135

21,658

2,638

0.77

0.12

Fryer: doughnut

12,895

3,634

850

0.28

0.23

Fryer: open
deep-fat 1 vat

23,446

1,377

322

0.06

0.23

Fryer: pressure

23,446

2,638

234

0.11

0.09

Griddle: double
sided 3-foot
(clamshell-down) *

31,710

2,345

528

0.07

0.23

Griddle: double
sided 3-foot
(clamshell-up) *

31,710

4,308

1,436

0.14

0.33

Griddle: flat
3-foot

26,376

5,979

1,084

0.23

0.18

Oven: combi:
combi-mode *

22,185

1,758

117

0.08

0.07

Oven: combi:
convection mode

22,185

1,700

293

0.08

0.17

Oven: convection
full-size

12,895

3,488

293

0.27

0.08

Oven: conveyor
(pizza)

49,822

20,017

2,286

0.40

0.11

Oven: deck

30,772

6,008

1,026

0.20

0.17

Oven: rack
mini-rotating *

16,500

1,319

322

0.08

0.24

Pasta cooker *

23,446

6,946

0.30

0.00

Range Top: top


off/oven on *

7,327

2,169

586

0.30

0.27

Range Top: 3
burners on/oven off

35,169

17,614

2,081

0.50

0.12

Range Top: 6
burners on/oven off

35,169

35,403

3,370

1.01

0.10

Range Top: 6
burners on/oven on

42,495

36,018

3,986

0.85

0.11

Range: Wok *

29,014

25,614

1,524

0.88

0.06

Rethermalizer *

26,376

6,829

3,370

0.26

0.49

Rice cooker *

10,257

147

0.01

0.60

Salamander *

10,257

9,759

1,553

0.95

0.16

Steam kettle:
large (60 gal)
simmer lid down *

42,495

1,583

0.04

0.00

Steam kettle:
small (10 gal)
simmer lid down *

15,240

967

88

0.06

0.09

Steam kettle:
small (40 gal)
simmer lid down

29,307

1,260

0.04

0.00

7,620

2,432

0.32

0.00

Steamer:
compartment:

88

atmospheric *
Tilting
skillet/Braising pan

30,479

3,048

117

0.10

0.04

* An asterisk denotes a new appliance that was added to the original


table.
Table 4a. Recommended Rates of Radiant Heat Gain from Hooded Solid Fuel
Appliances During Idle (Ready-to-Cook) Conditions [I-P]
Solid Fuel,
Exhaust Hood
Required

Energy Rate
[Btu/h]

Rate of
Heat Gain
[Btu/h]

Usage
Factor

Radiation
Factor

[F.sub.u]

[F.sub.r]

Hooded
Appliance

Rated

Stand-by

Sensible

Broiler: solid
fuel--charcoal

40 lbs

42,000

6,200

n/a

0.15

Broiler: solid
fuel--wood
(mesquite) *

40 lbs

49,600

7,000

n/a

0.14

* An asterisk denotes a new appliance that was added to the original


table.
Table 4b. Recommended Rates of Radiant Heat Gain from Hooded Solid Fuel
Appliances During Idle (Ready-to-Cook) Conditions [SI]
Solid Fuel,
Exhaust Hood
Required

Energy Rate [W]

Rate of
Heat Gain [W]

Usage
Factor

Radiation
Factor

Hooded
Appliance

Rated

Stand-by

Sensible

[F.sub.u]

[F.sub.r]

Broiler: solid
fuel--charcoal

18 kg

12,309

1,817

n/a

0.15

Broiler: solid
fuel--wood
(mesquite) *

18 kg

14,536

2,051

n/a

0.14

* An asterisk denotes a new appliance that was added to the original


table.
Table 5a. Recommended Rates of Radiant and Convective Heat Gain from
Warewashing Equipment During Idle (Stand-By) or Washing Conditions [I-P]
Warewashing
Appliance
Dishwasher
(conveyor

Energy Rate [Btu/h]


Rated
46,800

Stand-by
/Washing
5,700

Sensible
Radiant
0

type, chemical
sanitizing)
stand-by
Dishwasher
(conveyor
type, chemical
sanitizing)
washing

46,800

43,600

Dishwasher
(conveyor
type, hot water
sanitizing)
stand-by

46,800

5,700

Dishwasher
(conveyor
type, hot water
sanitizing)
washing

46,800

n/a

Dishwasher
(door-type,
hot water
sanitizing)
stand-by

18,400

1,200

Dishwasher
(door-type,
chemical
sanitizing)
stand-by

18,400

1,200

Dishwasher
(door-type,
chemical
sanitizing)
washing

18,400

13,300

Dishwasher
(door-type,
hot water
sanitizing)
washing

18,400

18,700

Dishwasher *
(under-counter
type, chemical
sanitizing)
stand-by

26,600

1,700

800

Dishwasher *
(under-counter
type, chemical
sanitizing)
washing

26,600

6,700

800

Dishwasher *
(under-counter
type, hot water

26,600

1,700

800

sanitizing)
stand-by
Dishwasher *
(under-counter
type, hot water
sanitizing)
washing
Booster Heater *
Warewashing

26,600

19,700

130,000

800

500

Rate of Heat Gain [Btu/h]


Unhooded

Appliance

Sensible
Convective

Hooded

Latent

Total

Sensible
Radiant

Dishwasher
(conveyor
type, chemical
sanitizing)
stand-by

1,600

4,100

5,700

Dishwasher
(conveyor
type, chemical
sanitizing)
washing

11,100

35,400

46,500

Dishwasher
(conveyor
type, hot water
sanitizing)
stand-by

1,600

4,100

5,700

Dishwasher
(conveyor
type, hot water
sanitizing)
washing

12,100

47,000

59,100

Dishwasher
(door-type,
hot water
sanitizing)
stand-by

900

300

1,200

Dishwasher
(door-type,
chemical
sanitizing)
stand-by

900

300

1,200

Dishwasher
(door-type,
chemical
sanitizing)
washing

4,500

8,600

13,100

Dishwasher

5,500

13,200

18,700

(door-type,
hot water
sanitizing)
washing
Dishwasher *
(under-counter
type, chemical
sanitizing)
stand-by

500

400

1,700

800

Dishwasher *
(under-counter
type, chemical
sanitizing)
washing

1,400

4,900

7,100

800

Dishwasher *
(under-counter
type, hot water
sanitizing)
stand-by

500

400

1,700

800

Dishwasher *
(under-counter
type, hot water
sanitizing)
washing

2,300

9,100

12,200

800

Booster Heater *
Warewashing
Appliance

Usage
Factor
[F.sub.u]

Radiation
Factor
[F.sub.r]

Dishwasher
(conveyor
type, chemical
sanitizing)
stand-by

0.12

0.00

Dishwasher
(conveyor
type, chemical
sanitizing)
washing

0.93

0.00

Dishwasher
(conveyor
type, hot water
sanitizing)
stand-by

0.12

0.00

Dishwasher
(conveyor
type, hot water
sanitizing)
washing

n/a

0.00

0.07

0.00

Dishwasher

500

(door-type,
hot water
sanitizing)
stand-by
Dishwasher
(door-type,
chemical
sanitizing)
stand-by

0.07

0.00

Dishwasher
(door-type,
chemical
sanitizing)
washing

0.72

0.00

Dishwasher
(door-type,
hot water
sanitizing)
washing

1.02

0.00

Dishwasher *
(under-counter
type, chemical
sanitizing)
stand-by

0.06

0.47

Dishwasher *
(under-counter
type, chemical
sanitizing)
washing

0.25

0.12

Dishwasher *
(under-counter
type, hot water
sanitizing)
stand-by

0.06

0.47

Dishwasher *
(under-counter
type, hot water
sanitizing)
washing

0.74

0.04

Booster Heater *

0.00

n/a

* An asterisk denotes a new appliance that was added to the original


table.
Table 5b. Recommended Rates of Radiant and Convective Heat Gain from
Warewashing Equipment During Idle (Stand-By) or Washing Conditions [SI]
Warewashing

Energy Rate [W]

Rate of Heat Gain [W]


Unhooded

Appliance

Rated

Stand-by
/Washing

Sensible
Radiant

Sensible
Convective

Latent

Total

Dishwasher
(conveyor
type, chemical
sanitizing)
stand-by

13,716

1,671

469

1,202

1,671

Dishwasher
(conveyor
type, chemical
sanitizing)
washing

13,716

12,778

3,253

10,375

13,628

Dishwasher
(conveyor
type, hot water
sanitizing)
stand-by

13,716

1,671

469

1,202

1,671

Dishwasher
(conveyor
type, hot water
sanitizing)
washing

13,716

n/a

3,546

13,774

17,321

Dishwasher
(door-type,
hot water
sanitizing)
stand-by

5,393

352

264

88

352

Dishwasher
(door-type,
chemical
sanitizing)
stand-by

5,393

352

264

88

352

Dishwasher
(door-type,
chemical
sanitizing)
washing

5,393

3,898

1,319

2,520

3,839

Dishwasher
(door-type,
hot water
sanitizing)
washing

5,393

5,480

1,612

3,869

5,480

Dishwasher *
(under-counter
type, chemical
sanitizing)
stand-by

7,796

498

234

147

117

498

Dishwasher *
(under-counter
type, chemical
sanitizing)
washing

7,796

1,964

234

410

1,436

2,081

Dishwasher*
(under-counter
type, hot water
sanitizing)
stand-by

7,796

498

234

147

117

498

Dishwasher *
(under-counter
type, hot water
sanitizing)
washing

7,796

5,774

234

674

2,667

3,575

147

Usage
Factor

Radiation
Factor

[F.sub.u]

[F.sub.r]

Booster Heater *

38,099

Warewashing
Hooded
Appliance

Sensible
Radiant

Dishwasher
(conveyor
type, chemical
sanitizing)
stand-by

0.12

0.00

Dishwasher
(conveyor
type, chemical
sanitizing)
washing

0.93

0.00

Dishwasher
(conveyor
type, hot water
sanitizing)
stand-by

0.12

0.00

Dishwasher
(conveyor
type, hot water
sanitizing)
washing

n/a

0.00

Dishwasher
(door-type,
hot water
sanitizing)
stand-by

0.07

0.00

Dishwasher
(door-type,
chemical
sanitizing)
stand-by

0.07

0.00

Dishwasher
(door-type,
chemical

0.72

0.00

sanitizing)
washing
Dishwasher
(door-type,
hot water
sanitizing)
washing

1.02

0.00

Dishwasher *
(under-counter
type, chemical
sanitizing)
stand-by

234

0.06

0.47

Dishwasher *
(under-counter
type, chemical
sanitizing)
washing

234

0.25

0.12

Dishwasher*
(under-counter
type, hot water
sanitizing)
stand-by

234

0.06

0.47

Dishwasher *
(under-counter
type, hot water
sanitizing)
washing

234

0.74

0.04

Booster Heater *

147

0.00

n/a

* An asterisk denotes a new appliance that was added to the original


table.

For unhooded electric appliances, the largest loads were from the counter-top conveyor oven and
large conveyor toaster. A kitchen can be loaded up to 10,300 Btu/h (3,019 W) by a large conveyor
toaster, or as much as 12,600 Btu/h (3,693 W) by a small conveyor oven. The highest latent loading
was from the small proofing cabinet at 3,000 Btu/h (879 W). The usage factor
([F.sub.u]=[[q.sub.stand-by (idle) consumption]/[q.sub.rated input (nameplate)]]) and radiation factor
([F.sub.r]=[[q.sub.sensible]/[q.sub.stand-by (idle) consumption]]) were calculated for the appliances
tested.
For hooded electric appliances, ranges and broilers contributed the highest sensible radiant heat gain.
For a range top with six elements turned on, the heat gain was 13,900 Btu/h (4,074 W) and for an
underfired broiler it was 10,800 Btu/h (3,165 W). The lowest sensible radiant loads were from kettles
and braising pans at less than 300 Btu/h (88 W). The usage factor ([F.sub.u]=[[q.sub.stand-by (idle)
consumption]/[q.sub.rated input (nameplate)]]) for hooded electric appliances was highest for hot tops
and salamanders at 0.95 and 0.97 respectively. The radiation factor
([F.sub.r]=[[q.sub.sensible]/[q.sub.stand-by (idle) consumption]]) was the highest for the small griddle
and range top at 0.44 and 0.42 respectively. The lowest radiant (sensible) loading was from the tilting
skillet and pasta cooker at zero Btu/h, and appliances that idle in an unenergized "off" mode, such as
the induction wok and induction cook top.
For hooded gas appliances, the range and chain (conveyor) broiler contributed the highest sensible
radiant heat gain at 13,600 Btu/h (3,986 W) (i.e., with six burners on) and 10,800 Btu/h (3,165 W)
respectively. The lowest sensible radiant loads were from kettles and braising pans, at less than 400

Btu/h (117 W). The usage factor, [F.sub.u], for hooded gas appliances was highest for hot tops and
salamanders at 0.95 and 0.97 respectively. The radiation factor, [F.sub.r], was the highest for the
small griddle and range top at 0.44 and 0.42.
The solid fuel appliances' sensible radiant loads were measured at 6,200 Btu/h (1,817 W) for 40
pounds (18 kg) of charcoal in a 3-foot broiler, and 7,000 Btu/h (2,051 W) for 40 pounds (18 kg) of
mesquite. These sensible loads represent radiation factors of 0.15 and 0.14 respectively.
Ware washing can contribute significant latent loading to the kitchen if the machines are not hooded
(or hooded with poor capture and containment performance). An unhooded conveyor-type hot water
sanitizing machine can contribute 59,100 Btu/h (17,321 W) of heat load, of which 47,000 Btu/h
(13,774 W) was latent loading. When properly ventilated, the sensible radiant load was zero. An
unhooded door-type hot water sanitizing machine can contribute 18,700 Btu/h (5,480 W) of heat load,
of which 13,200 Btu/h (3,869 W) was latent loading. If properly ventilated, the sensible radiant load
was zero. A typically unhooded under counter-type hot water sanitizing machine can contribute
12,200 Btu/h (3,575 W) heat load, of which 9,100 Btu/h (2,667 W) was latent loading. If hooded, the
sensible radiant load was 800 Btu/h (234 W).
CONCLUSION
The results of research project ASHRAE 1362-RP significantly expanded the heat gain information
available in the ASHRAE handbook in addition to verifying and standardizing appliances that were
reported in the handbook. The heat gain results are better classified and can be used more effectively
to calculate the internal heat loads from commercial kitchens on HVAC systems. The reorganized
results will appear in the Non-Residential Cooling Load Chapter of the Fundamentals Handbook.
The design value for heat gain from a hooded appliance at idle (ready-to-cook) conditions based on
its energy consumption rate is, at best, a rough estimate. When appliance heat gain measurements
during idle (ready-to-cook) conditions were regressed against energy consumption rates for gas and
electric appliances, it was found that there was large scatter due to the affect of the appliances'
emissivity, insulation, and surface cooling due to ventilation rates, etc. that led to large deviations from
the average values. Since large errors could occur in the heat load calculation for specific appliance
lines by using a general radiation factor, the revised tabulated heat gain data should be applied in the
HVAC design. For example, the heat gain to space from the gas 60-gallon (227 L) steam kettle while
simmering with the lid up was 0 Btu/h. However, the rated energy input (nameplate) was 145,000
Btu/h (42,495 W), and the measured energy consumption rate was 5,400 Btu/h (1,583 W). If a radiant
factor of 0.11 was applied to this consumption rate, the engineer would calculate a heat gain of 594
Btu/h, significantly larger than the heat gain measured by the study.
Overall, it was shown that more than 50% of the hooded appliances tested had a very low heat gain
and, from a practical perspective, did not contribute to the design cooling load. On the other hand,
only a few high-input appliances demonstrated significant heat gains. For example, the heat load from
the ranges, underfired broilers, and conveyor broilers were the highest of the group, regardless of the
energy type used to operate the appliance. High surface temperatures along with high emisivities
drove the high heat gain to space results. However, many high input appliances had low heat gain to
space, especially when appliance surface temperatures were low due to insulation and low
emissivities. Now that this research project has quantified the heat gain for virtually all equipment
categories specified within a commercial kitchen design, there is no need for the engineer to estimate
heat gain values based on the appliance rated input. The tabluated data that will be included in the
new handbook chapter will provide an accurate estimate of heat gain for each appliance type.
For unhooded cooking appliances, the heat gain measurements from large conveyor toasters, small
countertop conveyor ovens, and vertical toasters were the highest in the group. Consideration should
be given to hooding these appliances. As an alternative, the load to the space needs to be accounted
for in the general HVAC design.
The large latent load reported for all dishwashers tested implies that this equipment should be
ventilated without exception. Latent loading from dishwashers significantly contributed to the total
convective load. An unhooded conveyor-type hot water sanitizing machine can contribute 59,100
Btu/h (17,321 W) of heat load, of which 47,000 Btu/h (13,774 W) was latent loading. When properly

ventilated, the sensible radiant load was reduced to zero. An unhooded door-type hot water sanitizing
machine can contribute 18,700 Btu/h (5,480 W) of heat load, of which 13,200 Btu/h (3,869 W) was
latent loading. If properly ventilated, the sensible radiant load again was reduced to zero. A typically
unhooded under counter-type hot water sanitizing machine can contribute 12,200 Btu/h (3,575 W)
heat load, of which 9,100 Btu/h (2,667 W) was latent loading. If hooded, the sensible radiant load was
only 800 Btu/h (234 W).
The results of the study revealed opportunities to reduce heat gain to the kitchen through the
substitution of equipment or by a change in operating procedure. Simple operational changes such as
closing appliance lids, covers, and doors proved to be a simple and cost-free method for reducing the
heat gain, appliance consumption rate, and generally reduced the capture and containment
requirement of the cooking condition. A few of the appliances tested generated no sensible or
convective load while in standby, such as induction cooking equipment, which is the typical operating
mode of appliances for up to 75% of the day. Relative to either gas-fired or conventional electrical
powered appliances, the reductions in appliance energy and the related ventilation energy using
induction technology may be significant.
This ASHRAE research project successfully provided an expanded and verified database of heat gain
values of 83 appliances in 100 conditions in a format that is familiar to consultants and designers.
This representative data, as typically specified in drawings, will be better suited for design load
calculation tools and revising handbooks, codes and standards.
ACKNOWLEDGEMENTS
The authors acknowledge the many people who helped with the planning and completion of this
research project. The enthusiasm of our industry colleagues toward this commercial kitchen HVAC
study was remarkable, while contributions of appliances and hoods by manufacturers and
organizations for testing were vital to its outcome. We found ongoing support from the kitchen
ventilation industry as we updated interested parties at professional meetings and forums,
participated in ASHRAE seminars, provided tours of the CKV laboratory, and performed
demonstrations of our findings.
The support and efforts of ASHRAE TC4.1 Load Calculation Data and Procedures are recognized by
the authors and ASHRAE TC5.10 Kitchen Ventilation. The collaboration between the two technical
committees has provided the industry with invaluable information regarding heat gain and ventilation.
The test results will be incorporated into both ASHRAE chapters and referenced by many other
documents across the country and around the world. We look forward to continued co-sponsoring
efforts and welcome the opportunity to support the advancement of ASHRAE.
We would like to recognize the co-funding from the Pacific Gas and Electric Company and the
company's commitment to the food service industry. Through the efforts of Pacific Gas and Electric
Company's Food Service Technology Center (FSTC), California utility customers and the food service
industry are provided with information to help them improve the performance and energy efficiency of
CKV systems. Furthermore, this information is openly shared by the Pacific Gas and Electric
Company with the global community to improve energy efficiency well beyond the California borders.
We recognize Greenheck Corporation for supplying the exhaust hoods and fans for this project, the
Electric Food Service Council, McDonald's Corporation and Burger King Corporation for procuring
equipment to test. We also acknowledge the manufacturers listed in Appendix A who supplied
appliances either directly to the CKV Lab or indirectly through the Food Service Technology Center,
without which the project could not have been completed.
REFERENCES
Alereza, T. and J.P. Breen, III. 1984. Estimates of recommended heat gain due to commercial
appliances and equipment. ASHRAE Transactions 90(2A): 25-58.
ASHRAE 2005. 2005 ASHRAE Handbook--Fundamentals, Chapter 30. Atlanta: American Society of
Heating, Refrigerating and Air-Conditioning Engineers, Inc.

ASTM 2005. ASTM F 2474-05 Standard test method for heat gain to space performance of
commercial kitchen exhaust ventilation/appliance systems. American Society of Testing and Materials
International. West Conshohocken, PA.
Fisher, D.R. 1998. New recommended heat gains for commercial cooking equipment. ASHRAE
Transactions 104(2):953-60.
Sobiski, P.A., R.T. Swierczyna and D.R. Fisher 2008. Capture and Containment Ventilation Rates for
Commercial Kitchen Appliances Measured during 1362-RP. ASHRAE Transactions T226-08.
Swierczyna, R., D. Fisher, P. Sobiski, T. Cole, M. Bramfitt. Effect on commercial kitchen hood
performance of appliance diversity and position 1202-RP. ASHRAE 2005.
Swierczyna, R., P. Sobiski, D. Fisher. ASHRAE Research Project 1362 Revised Heat Gain and
Capture and Containment Exhaust Rates from Typical Commercial Cooking Appliances. 1362-RP.
ASHRAE 2008.
Rich Swierczyna
Associate Member ASHRAE
Paul Sobiski
Associate Member ASHRAE
Don Fisher, PEng
Associate Member ASHRAE
This paper is based on findings resulting from ASHRAE Research Project RP-1362.
Rich Swierczyna is a lab operations manager and Paul Sobiski is a research engineer in the
Commercial Kitchen Ventilation Laboratory at the Architectural Energy Corp., Wood Dale, IL. Don
Fisher is CEO with Fisher-Nickel Inc., San Ramon, CA.
COPYRIGHT 2009 American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc.
No portion of this article can be reproduced without the express written permission from the copyright holder.
Copyright 2009 Gale, Cengage Learning. All rights reserved.