Exceptions:
1. Floor assemblies located directly over a space protected by an automatic sprinkler system in accordance with Section
P2904, NFPA13D, or other approved equivalent sprinkler system.
2. Floor assemblies located directly over a crawl space not intended for storage or fuel-fired appliances.
3. Portions of floor assemblies can be unprotected when complying with the following:
3.1 The aggregate area of the unprotected portions shall not exceed 80 square feet per story.
3.2 Fire blocking in accordance with Section R302.11.1 shall be installed along the perimeter of the unprotected portion
to separate the unprotected portion from the remainder of the floor assembly.
4. Wood floor assemblies using dimension lumber or structural composite lumber equal to or greater than 2-inch by 10-inch
nominal dimension, or other approved floor assemblies demonstrating equivalent fire performance.
70
WWW.APAWOOD.ORG
It should be noted that these fire protective membrane provisions apply to not only I-joist floors but all residential floor
assemblies, including floor trusses, light-gauge steel framing, and dimension lumber and structural composite lumber
less than 2-inch by 10-inch nominal dimension. They will become effective when adopted by the local jurisdiction. While
most jurisdictions will consider the adoption of the 2012 IRC after it is published in late 2011, some local jurisdictions
may elect to adopt them sooner, and others may not adopt them at all.
Based on this, APA supports the addition of a 1/2-inch gypsum wall board or 5/8-inch wood structural panel fire protective membrane, or equivalent, to the underside of floor framing, as required by Section R501.3 of the 2012 IRC. The
designer and builder shall consult with the local building department or authority having jurisdiction for specific requirements of fire protection in any building construction.
FIGURE 27
ONE-HOUR COMBUSTIBLE FLOOR-CEILING AND ROOF-CEILING ASSEMBLIES LUMBER JOISTS
Some rated assemblies incorporate proprietary products. When designing and specifying, check the Underwriters Laboratories Inc.
(U.L.) Fire Resistance Directory for complete details on a particular assembly. A change in details may affect the fire resistance of the
assembly.
For details, see U.L. Design No. L513. Also see U.L. Design
Nos. L504 for stressed-skin panel (5/8" APA RATED
STURD-I-FLOOR or SHEATHING plywood with joists spaced
12" o.c.), L507 for 5/8" APA RATED STURD-I- FLOOR plywood
with joists spaced 16" o.c., L508 for 1-1/8" APA RATED
STURD-I-FLOOR plywood with joists spaced 48" o.c., and
L539, L540 with joists spaced 16" or 24" o.c. and separate
ceiling assembly (for modular housing units). Also see U.L.
Design Nos. L524 and L543 with steel joists spaced 19.2" or
24" o.c. (L543 with separate ceiling assembly).
19/32" T&G
APA plywood
underlayment
5/8"
Type X gypsum
wallboard ceiling
Resilient furring
channels max.
16" o.c.
Building
paper
71
Construction
adhesive at joists
and T&G edges(d)
5/8" proprietary*
Type X gypsum
wallboard ceiling
WWW.APAWOOD.ORG
FIGURE 28
ONE-HOUR COMBUSTIBLE FLOOR-CEILING AND ROOF-CEILING ASSEMBLIES I-JOISTS
28.A ONE-HOUR FIRE-RESISTIVE/CEILING ASSEMBLY
Min. 23/32" T&G
APA Sturd-I-Floor
Min. 1/2"
Type C gypsum
wallboard taped
STC
IIC
STC
IIC
46
68
STC
IIC
STC
IIC
51
47
50
73
STC
IIC
STC
59
50
55
54
(b)
IIC
68(b)
68
Construction
adhesive
at joists and
T&G edges(c)
With Insulation
Without Insulation
STC
IIC
60
51
STC
63(b)
65(b)
58
55(b)
(b)
IIC
72
WWW.APAWOOD.ORG
Building Requirements
In many fire-resistant floor-ceiling assemblies, a two-layer floor system (Performance Category 15/32 subfloor and
Performance Category 19/32 underlayment) is used, although several have single-layer Performance Category 5/8 or
larger combination subfloor-underlayment panels. Any finish floor material may be used. The International Building
Code permits omission of the top panel layer in roof assemblies or where unusable space occurs above (Table 720.1(3)).
Plywood siding or wall sheathing in combination with gypsum sheathing and wallboard on studs is recognized by
code officials for one-hour load-bearing exterior walls. A typical example APA RATED SIDING over 5/8-inch Type X
gypsum sheathing attached to 2x studs 16 or 24 inches on center is illustrated in Figure 29. Under the International
Building Code, Section 705.5, the fire-resistive rating for exterior walls applies only to the inside of the wall when separation to the property line is greater than 10 feet. In this common situation, the gypsum sheathing can be omitted
under the siding as noted in Figure 29.
Fire-rated protected wall assemblies will qualify for the one-hour rating if other materials are added over the fire-resistive
materials. For example, APA RATED SIDING panels or lap siding may be attached to the outside of a rated wall without
impairing the rating. APA RATED SHEATHING is also permitted between the fire protection and wood studs (Table 720.1(2)
of the 2009 IBC). For additional information, see APA Design/Construction Guide: Fire-Rated Systems, Form W305 and APA
Technical Topic: Load-Bearing Fire-Rated Wall Assemblies with OSB and Plywood Wall Sheathing, Form TT-063.
FIGURE 29
ONE-HOUR FIRE-RATED EXTERIOR LOAD-BEARING WALL ASSEMBLY(a)
2x4 studs all 16" or 24" o.c.
Mineral or glass fiber insulation (optional)
5/8" Type X gypsum wallboard
5/8" Type X gypsum sheathing(b)
Building paper or other code-approved weather-resistive barrier
APA RATED
SIDING 16 or 24 oc
(or panel sheathing).
Panel siding meets code
requirement for wall bracing.
(a) Generic, non-proprietary assembly based on GA File No. WP8105 listed in Gypsum
Association Fire Resistance Design Manual, referenced in the model building codes.
Mineral or glass fiber batt insulation (optional).
(b) Exterior layer of gypsum sheathing not required under the International Building
Code, when separation is greater than ten feet. Check local provisions. Also see U.L.
Design Nos. U344 and U356 in U.L. Fire Resistance Directory.
Roof Coverings
The fire resistance ratings of roofing materials are listed as Class A, B, or C in descending order of fire protection afforded.
Their use is prescribed by building codes, and also affects insurance rates. Untreated APA RATED SHEATHING panels are recognized as a structural roof deck substrate for rated roof coverings. For individual requirements, see the U.L.
Roofing Materials and Systems Directory.
73
WWW.APAWOOD.ORG
Columns. Column length determines the minimum size for one-hour ratings. The
column size needed for a one-hour fire rating is determined by calculating the ,/d
and then using the appropriate minimum dimensions (see Table 40).
Columns generally need no special layup to qualify for a one-hour fire rating.
For both 8-3/4- and 10-3/4-inch widths, all columns meeting the minimum
size standard satisfy the one-hour fire rating requirement.
As with all structural framing, final specifications of members designed to
have one-hour fire resistance should be carefully checked by a professional
engineer or architect to assure compliance with all local building codes.
The use of pressure impregnated fire retardants is not recommended
for glulam.
TABLE 39
ONE-HOUR FIRE-RATED GLULAM
BEAMS MINIMUM DEPTHS FOR
6-3/4" AND 8-3/4" WIDE BEAMS
Minimum
Depth (in.)
Beam Width 3 Sides
4 Sides
(in.)
Exposed Exposed
6-3/4
13-1/2
27
8-3/4
7-1/2
13-1/2
TABLE 40
ONE-HOUR FIRE-RATED
GLULAM COLUMNS MINIMUM
DEPTHS FOR 8-3/4" AND 10-3/4"
COLUMN WIDTHS
Minimum
Depth (in.)
Column
,/d
Width 3 Sides 4 Sides
Criteria (in.) Exposed Exposed
8-3/4
15
,/d>11
10-3/4 10-1/2
30
13-1/2
8-3/4
,/d 11
10-3/4
12
10-1/2
9
7-1/2
FIGURE 30
ONE-HOUR FIRE-RATED
GLULAM BEAM
(Layup for simple span)
Compression lam
at top
For further information, see APA Technical Note: Calculating Fire Resistance of
Glulam Beams and Columns, Form Y245.
74