Vous êtes sur la page 1sur 6

DATA SHEET

CABLE SYSTEM

DATA SHEET
SECTION

13

CABLE SYSTEM

MONENCO IRAN CONSULTING ENGINEERS CO.

Page 1 of 6

Rev-Z

SECTION 13

DATA SHEET
CABLE SYSTEM

Cable System Data Sheet


DATA SHEET FOR
CABLE SYSTEM
DESCRIPTION

ITEM
A)

TECHNICAL
REQUIRMENTS

HIGH VOLTAGE CABLE

Maximum system voltage...............(KV rms )

Rated frequency ......................................... Hz

Type of conductor.........................................

Stranded

Conductor material......................................

High conductivity
plain annealed
cupper

Type of insulation......................................

Shield material......................

Inner sheath material........................................

Water blocking tape is required? .

Type of armour material............................................

Al./CU wire or
tape

10

Outer sheath material................................................

Extruded P.V.C.

11

Core identification required......................................

Yes

12

Type and routine tests required..............................

Yes

13

Distance between cables laid horizontally or in flat ...

14

System grounding..........................................

Page 2 of 6

72.5
50

XLPE
Copper wire or
strips

Rev-Z

Extruded P.V.C.
Yes

Equal to the
outer diameter of
cables
effective

SECTION 13

DATA SHEET
CABLE SYSTEM

DATA SHEET FOR


CABLE SYSTEM
DESCRIPTION

ITEM

TECHNICAL
REQUIRMENTS

15

Basic Insulation level................................... kV peak

325

16

Short time 1 sec.withstand current.............. kA rms

31.5

17

Min. power capacity .................................... M.V.A


B) MEDIUM VOLTAGE CABLE

As per SLD

Maximum system voltage (KV rms )........................

24

Rated frequency................................................HZ

50

Type of conductor......................................................

Conductor material..............................

Type of insulation......................................

XLPE

Shield material.........................................

Copper wire or
strips

Inner sheath material.................................

Extruded P.V.C.

Type of armour material............................................

Al./CU wire or
tape

Outer sheath material................................................

Extruded P.V.C.

10

Core identification required......................................

Yes

11
12

Type and routine tests required..............................


Distance between cables laid horizontally or in
flat ...

Yes
Equal to the
outer diameter of
cables

Page 3 of 6

Rev-Z

Stranded
High conductivity
plain annealed
cupper

SECTION 13

DATA SHEET
CABLE SYSTEM

DATA SHEET FOR


CABLE SYSTEM
DESCRIPTION

ITEM
13

System grounding....................................................

14

Basuc insulation (kV peak)...............................

15

Max. continuous current :


For incoming feeder................................... A
For outgoing feeder................................... A

16

Short time 1 sec.withstand current.................. kA


rms

C)

TECHNICAL
REQUIRMENTS
non-effective
125

According to
S.L.D

20

CONTROL CABLES

Type of conductor......................................................

Conductor material.......................................

Type of
insulation.......................................................

Inner sheath material...............................................

Type of Shield material.....................................

Type of sheath between shield and armour

Stranded
High conductivity
plain annealed
copper
P.V.C. or XLPE

Extruded P.V.C.
Lead or cupper
P.V.C

Type of armour material...........................................

Galvanized steel
wire

Outer sheath details..................................................

Extruded P.V.C.

Core identification required.......................................

Yes

10

Type and routine tests required..............................

Yes

Page 4 of 6

Rev-Z

SECTION 13

DATA SHEET
CABLE SYSTEM

DATA SHEET FOR


CABLE SYSTEM
DESCRIPTION

ITEM

TECHNICAL
REQUIRMENTS

11

Minimum cross section of each wire ............


mm

2.5

12

Minimum cross section of CT and CVT cable...


mm

D)

LV CABLES

Type of insulation.................................................

Type of conductor .............................................

Stranded

Conductor material................................................

High conductivity
plain annealed
copper

Inner sheath details..............................................

Extruded P.V.C.

Type of armour material......................................

Galvanized steel
wire

Shield material......................................................

Not required

Outer sheath details.............................................

Extruded P.V.C.

Core identification required..................................

yes

Type and routine tests required.........................

yes

10

Distance between cables laid horizontally or in


flat

11

Minimum cross section of each core mm

Page 5 of 6

Rev-Z

P.V.C.

Equal to the
outer diameter of
cables
2.5

SECTION 13

DATA SHEET
CABLE SYSTEM

DATA SHEET FOR


CABLE SYSTEM
DESCRIPTION

ITEM

TECHNICAL
REQUIRMENTS

E) M.V. cable sealing ends


1

Type.......................................................................

Heat shrinkable

Rated voltage..........................................................

20 KV

Color...................................................................

Red

None tracking..................................................

Yes

Min. creepage distance .mm

750

Page 6 of 6

Rev-Z

SECTION 13

Vous aimerez peut-être aussi