Presentation Overview
What is surge?
How does CCC control surge?
Deviation, Recycle Fast & Safety-On
Pressure
erusserP
What is surge?
Compressor
Map
Resistance curve
Nmax
Operating Point
P1
Performance
Performancecurve
for afor
specific
curve
speedaN1
specific speed N1
Nmin
Q1
Flow
Flow
What is surge?
Pd rises
Operating
point
moves up
the curve
Ps
Pd
What is surge?
Flow reverses
P
D
C
Ps
Pd
Operating point
jumps from +ve and
-ve flow
What is surge?
What is surge?
Flow
(2 )
Pressure
3
Rapid pressure
swings & instability
Temperature
Operator error
Process Upsets
Gas composition changes
Filter / strainer problems
The Solution
Invent a number called deviation that is only
dependent on flow / pressure / temperature
where:
h
where:
h
Output
to Valve
Total Response
PI Control Response
qr2
Original
SOL RTL
Original
SCL
New RTL
& SCL
Qs2
Typical response:
SLL
SOL
SLL
RTL
SOL RTL
DC B
HHpp
SCL
SCL
E
A
O.P.
2
Q
2
s
Q
Step
Step 22
output
Output
A B
Step
1
Step 1
C D
Time
Time
STL
(-0.2) (-0.1)
(Dev = 0)
(Dev = 0.15)
SOL
SCL
TSL
RTL
STL:
Surge Trip Line
SOL:
Safety-On Line
RTL: Recycle-trip Line
SCL: Surge Control Line
TSL: Tight Shut-off Line
Speed curves
0
0
Performance Controller
Used to control compressor throughput
blow-off
used more for plant air systems
discharge throttling
inefficient
suction throttling
often used on electric-drive compressors
speed variation
Used in Domgas & LNG
Performance Controller
Nmax
Pd
Rprocess
NOP
Nmin
Controller
Setpoint
qr2
Shaft
Power
P1
qr2
Performance Controller
Limit Control
Ensures a physical constraint is not exceeded.
E.g:
Pd max of 2350kPa on K1440 discharge
Temp tracking:
Mark IV or V may limit on EGT
CCC designed to track speed
provides bumpless transfer back to CCC control
Load Sharing
Regulate capacity & maximise efficiency
Provides control of a network
DCS
(APC)
CCC Master
Controller
(14PC215)
P66
Load Sharing
Comprises of two types of response:
Primary Capacity Control
Manipulates a variable by adjusting speed / recycle
e.g. Suction pressure on K30
Load-balancing
Ensures both compressors operate in the same region
I.e. minimise un-necessary recycle
Load Balancing
Equidistant control
Compressors in series
Equalise normalised compression ratio
Used on LNG MR and C3 circuits
Compressors in parallel
Equalise recycle deviation
Used on Domgas K30
Note: Domgas K20 load-sharing performed in DCS
PV
PID
DCS
setpoint
Master Controller
Analog
inputs
Antisurge
Controller
Mode
DEV
PI
SP
RT
Primary
Response
Loop
Decouple
To recycle
valve
Loadshare
Controller
DEV
Primary
Response
Loop
Decouple
To
Speedtronics
XCC
CCC
System
Alarm
04
1 1 A
Card #
FAR #
Cabinet #
Tag Type
descriptor
Fallback Alarm
This alarm means CCC has lost the ability to
control
e.g. lost both flow transmitters
Response:
Recycle valve opened in manual to approx 50%
exact amount depends on the controller setting
minimum flow required to stay out of surge for all conditions
Trainview