Académique Documents
Professionnel Documents
Culture Documents
SPEEDTRONIC
Mark V
Turbine Control
Time Synchronization
SPEEDTRONIC
Mark V
Turbine Control
Time Synchronization
GEH-6370
Issue Date: June 1996
These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible
contingency to be met during installation, operation, and maintenance. If further information is desired or if particular
problems arise that are not covered sufficiently for the purchasers purpose, the matter should be referred to GE
Industrial Systems.
This document contains proprietary information of General Electric Company, USA and is furnished to its customer
solely to assist that customer in the installation, testing, operation, and/or maintenance of the equipment described. This
document shall not be reproduced in whole or in part nor shall its contents be disclosed to any third party without the
written approval of GE Industrial Systems.
GEH-6370
WARNING
Indicates a procedure, practice, condition, or statement that, if not strictly observed, could result in
personal injury or death.
CAUTION
Indicates a procedure, practice, condition, or statement which, if not strictly observed, could result in
damage to or destruction of equipment.
NOTE
Indicates an essential operation or important procedure, practice, condition, or statement.
GEH-6370
Mark V Time Synchronization
WARNING
This equipment contains a potential hazard of electric shock or burn. Only personnel who are adequately
trained and thoroughly familiar with the equipment and the instructions should install, operate, or maintain
this equipment.
Isolation of test equipment from the equipment under test presents potential electrical hazards. If the test
equipment cannot be grounded to the equipment under test, the test equipments case must be shielded to
prevent contact by personnel.
To minimize hazard of electrical shock or burn, approved grounding practices and procedures must be
strictly followed.
WARNING
To prevent personal injury or equipment damage caused by equipment malfunction, only adequately trained
personnel should modify any programmable machine.
GEH-6370
TABLE OF CONTENTS
Section/Subject
Page
CHAPTER 1. OVERVIEW
1-1.
Introduction....................................................................................................................................................................
1
1-2. Time Synchronization Features......................................................................................................................................
1
1-2.1. Time Signal Sources....................................................................................................................................................
1
1-2.2. General
Architecture....................................................................................................................................................
1
1-2.3. Backup Synchronization..............................................................................................................................................
2
1-3. Manual
Organization......................................................................................................................................................
2
1-4. Related Documents.........................................................................................................................................................
3
CHAPTER 2. TIME SYNCHRONIZATION THEORY
2-1.
Introduction..................................................................................................................................................................... 5
2-2. Timesync Protocol..........................................................................................................................................................
5
2-3. Supported
GTSs..............................................................................................................................................................
5
CHAPTER 3. HARDWARE SETUP
3-1.
Introduction....................................................................................................................................................................
7
3-2. Board Installation...........................................................................................................................................................
7
3-3. Setting Base I/O Address................................................................................................................................................
7
3-4. Setting the
IRQ...............................................................................................................................................................
8
3-5. Connecting the GTS to the Board...................................................................................................................................
8
3-6. Connecting the <I>'s or <G>'s........................................................................................................................................
9
CHAPTER 4. SOFTWARE SETUP
4-1.
Introduction..................................................................................................................................................................... 11
4-2. Timesync
Datafile...........................................................................................................................................................
11
i
GEH-6370
4-3. File
Configuration...........................................................................................................................................................
11
ii
GEH-6370
Section/Subject
Page
LIST OF FIGURES
Figure
Figure 1-1.
2
Figure 3-1.
7
Figure 3-2.
8
Figure 3-3.
8
Figure 3-4.
Page
Typical Time Synchronization Architecture........................................................................................................
bc620AT Time and Frequency Module...............................................................................................................
SW1 Base I/O Address switch selections.............................................................................................................
IRQ selection on bc620AT board.... ...................................................................................................................
iii
GEH-6370
iv
GEH-6370
CHAPTER 1
OVERVIEW
1-1. INTRODUCTION
The Time Synchronization option for SpeedTronic Mark V control systems synchronizes all Mark V control panels on
the stagelink to a Global Time Source (GTS) with a limited loss of accuracy. In addition, this option sets all <I> and/or <G>
interface computer timeclocks to the GTS. It is recommended that the remaining plant equipment, including DCSs
(Distributed Control Systems), synchronize to this common GTS.
If assistance is needed, contact:
GE Motors & Industrial Systems
Product Service Engineering, Rm. 191
1501 Roanoke Blvd.
Salem, VA 24153 - 6492 USA
Phone 001-540-387-7595
Fax 001-540-387-8606
1-2. TIME SYNCHRONIZATION FEATURES
1-2.1. Time Signal Sources
Mark V Time Synchronization supports several GTSs.
Timecode signals supported (see section 2-3 for details):
IRIG-A
IRIG-B
NASA-36
2137
Supported GTSs that use periodic pulses (see section 2-3 for details):
1 PPS
1 PPM
1 PPH
Typical GTSs are GPS (Global Positioning Satellite) receivers such as the StarTime GPS Clock, or other time processing
hardware. The preferred time sources are UTC (Universal Time Coordinated) or GPS. However, the Time Synchronization
option also supports a GTS using local time as its base time reference. See chapter 5, Local Time vs. UTC Considerations,
for more details.
Chapter 4, Software Setup, discusses the setup for specifying local or global.
GEH-6370
purpose Stagelink Timesync protocol. This protocol minimizes time losses. Figure 1-1 shows a general plant-wide time
synchronization setup.
MK V
MK V
MK V
MK V
TERMINATION
RESISTOR
STAGE LINK
TERMINATION
RESISTOR
<I>
<I>
<I>
<I>
GLOBAL
TIME SOURCE
TIME LINK
TO
DCS EQUIPMENT
* Optional
Figure 1-1. Typical Time Synchronization Architecture
Chapter 1, Overview
GEH-6370
Chapter 1, Overview
GEH-6370
Notes:
Chapter 1, Overview
GEH-6370
CHAPTER 2
TIME SYNCHRONIZATION THEORY
2-1. INTRODUCTION
This chapter explains the basic theory of synchronizing Mark V time to the GTS. Selection of the Stagelink Time Master is
discussed in this chapter, as well as supported GTSs.
GEH-6370
1PPS (one pulse per second) using the External 1PPS input signal of the bc620AT board
1PPM (one pulse per minute) using the Event Capture input signal of the bc620AT board
1PPH (one pulse per hour) using the Event Capture input signal of the bc620AT board
No Signal using the low-drift clock on the bc620AT board in FLYWHEEL mode as the sole time source for the plant
There are two time sources supported by the bc620AT board but not supported by the Time Synchronization software.
These signals are XR3 timecodes and Negative Edge on time inputs.
NOTE
Nomenclature for IRIG timecodes is defined in Appendix B.
GEH-6370
CHAPTER 3
HARDWARE SETUP
3-1. INTRODUCTION
To set up the Time Synchronization hardware, the bc620AT board must be correctly installed in the <I> or <G> and then
configured for this application. The setup of the Bancomm bc620AT board for the Mark V Time Synchronization option,
involves setting hardware jumpers to select the base I/O address of the board (see section 3-3), and disabling the IRQ
(Interrupt Request) since the software makes no use of interrupts for this board (see section 3-4). Then the GTS and the
<I>'s or <G>'s must be connected (sections 3-5 and 3-6).
Figure 3-1 shows the general layout of the bc620AT board
J1
BANCOMM bc620AT
I/O ADDRESS
JP1
IRQ JUMPERS
J2
SW1
GEH-6370
ON
ON = 0
OFF = 1
OFF
A9 A8
1
A7 A6 A5 A4
1
A3 A2 A1 A0
0
= 0x0280
OPEN
SW1
IR9
IR7
IR6
IR5
IR4
IR3
11
13
15
17
19
21
NO IRQ
IR10
9
IR12
5
IR11
IR14
3
IR15
Pin
23
JP1
IRQ
Adapter
GEH-6370
Receptacle
BNC's
To
bc620AT
J1
(GTS Source)
Timecode Input
(Modulated)
(IRIG-A, IRIG-B,
NASA36, or 2137)
Event Input
(1 PPM or 1 PPH)
1 PPS Output
1 PPS Input
(1 PPS)
Timecode Output
15-pin
D Plug
Figure 3-4. 15-Pin D to BNC Adapter.
For dc Level Shifted timecode inputs, an adapter is required for J1 pin 12 (Ground) and pin 10 (DCLS Timecode Input) to a
BNC receptacle connector.
CAUTION
Use the same lightning protection techniques for the timelink as for Stagelink or Ethernet. See the
documentation for these networks for protection techniques to be used.
CAUTION
The timelink cabling (RG-58) is identical to that used for Ethernet and very similar to that used for
Stagelink (RG-62). Label all cables used for timelink differently than the other network cables.
Damage to equipment is possible if these cables are interconnected.
GEH-6370
Notes:
GEH-6370
CHAPTER 4
SOFTWARE SETUP
4-1. INTRODUCTION
The Timesync software must be configured correctly in order to communicate over the Stagelink. Data files must be
modified to define the Stagelink Time Master and specify the time base.
GEH-6370
;
TIMESYNC Parameters.
11-JUL-1995
;
; The line beginning with "TIMESYNC" indicates time acquisition hardware
; exists in the system. The only card supported thus far is the bc620AT
; Time/Frequency board. The syntax of this line is:
; TIMESYNC <controller> BASE_PORT <port address> MODE <mode>
[LEVEL_SHIFT]
;
where <controller> is: BC620AT
;
<port address> is the base port address of the card in
hex.
;
<mode> is one of the following:
;
IRIG-A
IRIG-A Timecode.
;
IRIG-B
IRIG-B Timecode.
;
NASA-36
NASA-36 bit timecode.
;
2137
2137 Timecode.
;
1PPS
1 pulse per second.
;
1PPM
1 pulse per minute.
;
1PPH
1 pulse per hour.
;
FLYWHEEL
Free Running Clock.
;
"DC_SHIFT" is specified if the timecode is DC Level Shifted
rather
;
than modulated.
TIMESYNC BC620AT
BASE_PORT 280
MODE IRIG-B
;
; "I_TIMESET [ENABLED | DISABLED]" is used to allow the <I>'s time to
; be set to the same time as the Stagelink Time Master. Note the <I>
does
; not require a time/frequency board in order to be a time slave.
I_TIMESET
ENABLED
;
; "I_TIME", "PANEL_TIME" and "TIME_SOURCE" identify what timebase is
used
; in <I>, the Mark V, and the Global Time Source. Choices are UTC and
LOCAL.
I_TIME
LOCAL
PANEL_TIME
LOCAL
TIME_SOURCE
UTC
;
; "TIME_LOAD [MANUAL | LOCAL | NETWORK]" defines whether major time
elements
; (year, day-of-year etc.) are derived from the PC automatically (i.e.
LOCAL);
; or obtained from other Stagelink Time Masters (i.e. NETWORK),
; or whether TIMESYNC functions are disabled until major time is
entered
; manually via TIMEUTIL (i.e. MANUAL).
TIME_LOAD
LOCAL
;
; Time Offset Definition Table. Each entry defines number of minutes
; correction to use when Global Time Source Time hits:
;
GLOBAL TIME SOURCE
;
----------UTC---------Minutes Correction to LOCAL
Time
TIME_OFFSET
25-OCT-1992 06:00:00.00
-300
TIME_OFFSET
04-APR-1993 07:00:00.00
-240
TIME_OFFSET
31-OCT-1993 06:00:00.00
-300
TIME_OFFSET
03-APR-1994 07:00:00.00
-240
TIME_OFFSET
30-OCT-1994 06:00:00.00
-300
TIME_OFFSET
02-APR-1995 07:00:00.00
-240
TIME_OFFSET
29-OCT-1995 06:00:00.00
-300
12 Chapter 4, Software Setup
TIME_OFFSET
TIME_OFFSET
GEH-6370
07-APR-1996 07:00:00.00
27-OCT-1996 06:00:00.00
-240
-300
LEVEL_SHIFT
"LEVEL_SHIFT" is used if IRIG-x, NASA-36, or 2137 timecodes are dc Level Shifted instead of modulated signals.
GEH-6370
BASE_PORT xxxx
"xxxx" is the HEX Base I/O address of the Time/Frequency Processor board; this parameter is normally 0280.
I_TIMESET [ENABLED | DISABLED]
This line defines whether the <I> or <G> time is set to the time defined by the stagelink time master (ENABLED), or
follows the CMOS clock (DISABLED).
I_TIME [LOCAL | UTC]
"I_TIME" is only applicable if the line "I_TIMESET ENABLED" line (above) exists in the data file. This customer
specified parameter defines whether the <I>'s internal time is set to UTC or Local Time.
PANEL_TIME [LOCAL | UTC]
This customer specified parameter defines whether the Mark V panel time is UTC based or Local Time based.
TIME_SOURCE [LOCAL | UTC]
This line specifies whether the GTS is UTC based or Local Time based. This parameter applies only to timecode
GTSs; it does not apply to pulse input time sources.
TIME_LOAD [MANUAL | LOCAL | NETWORK]
time
This line enables or disables the automatic loading of initial major time fields. No Stagelink Timemaster will send
until all major time elements are loaded, and time is locked to the GTS.
" MANUAL" disables the <I> as a Stagelink time master until major time elements are manually entered. See section
describing the TIMEUTIL program for more details.
"LOCAL" specifies that major time is loaded automatically from the <I>'s CMOS clock.
"NETWORK" specifies that major time is loaded from another Stagelink Timemaster, assuming multiple <I>'s on the
Stagelink have Time/Frequency processor boards installed.
For IRIG-A, IRIG-B and NASA-36 timecodes, major time elements consist only of the year (since these are time-ofyear
timecodes). For 2137 timecode, major time consists of current year, month and day, as this is a time-of-day
timecode. For pulse input styles of GTS, major time consists of current year, month, day, hour, minute, and seconds.
NOTE
"TIME_LOAD LOCAL" is not recommended for 1PPS Global Time Sources, since the CMOS
clock may have errors in time on the order of several seconds.
TIME_OFFSET dd-mmm-yyyy hh:mm:ss.cc mmmm
"TIME_OFFSET" lines can be specified more than once. For normal operation, where the global timecode source is
UTC, these lines define the correction applied to the global time source in order to display timetagged data in local
time.
In this case, "dd-mmm-yyyy hh:mm:ss.cc" defines the UTC Time at which "mmmm" minutes of correction takes
place.
Example: Enter Eastern Daylight Time on April 3, 1994.
TIME_OFFSET 03-APR-1994 07:00:00.00 -240
GEH-6370
This example says that beginning on 3-APR-1994 at 07:00 AM UTC, the local correction added to UTC to arrive at EDT
(Eastern Daylight Time) is -240 minutes. (Eastern Standard Time correction would be -300 minutes.)
NOTE
All <I>'s or <G>'s in a system must be setup in F:\TIMESYNC.DAT in an identical fashion, with the
exception of those computers not having a bc620AT card installed. Failure to have identical system
setup can cause shifts in the Stagelink Time Reference upon power down of the primary Stagelink
Time Master.
NOTE
<I>'s or <G>'s not containing a bc620AT time/frequency processor card should have the identical
lines in F:\TIMESYNC.DAT, but with the "TIMESYNC..." line commented out.
GEH-6370
CHAPTER 5
LOCAL TIME vs. UTC CONSIDERATIONS
5-1. INTRODUCTION
This chapter defines the use of F:\TIMESYNC.DAT and F:\GSM_SERV.DAT and how each of these configuration files
interact relative to the time sources. Mark V panel system time, <I> / <G> local time, the CMOS clock, and the GTS time
references are discussed in this chapter, as well as UTC and Local GTSs.
GEH-6370
Both <I> and Mark V times must currently use the same time base for the plotting programs to execute
properly.
GEH-6370
CHAPTER 6
TIMESYNC OPERATION
6-1. INTRODUCTION
This chapter covers normal timesync/timeset operations, as well as use of the TIMEUTIL program.
Major time elements (year, month, day etc.) have been acquired from CMOS memory, another Stagelink Time Master,
or manually through the TIMETUTIL program.
2.
The GTS has established its presence and the bc620AT board has asserted its tracking status bit. (This is ignored if
mode is set to FLYWHEEL.) For pulse input GTS, at least one reference pulse must have been recorded after major
time was loaded.
NOTE
Item number one above does not occur automatically upon <I> or <G> bootup if the line
"TIMELOAD MANUAL" is specified in F:\TIMESYNC.DAT. Use of the TIMEUTIL program is
required to load major time elements in this case.
Every 20 seconds, each available Stagelink Time Master broadcasts an identification message announcing its availability.
Every 32 seconds, each Mark V panel asks the selected Stagelink Time Master for the current date/time. It jumps or slews
its internal time based on the time error calculated. The rate of slew allows for sub-millisecond errors, assuming the GTS is
stable.
Every 60 seconds, all nodes select the Stagelink Time Master of choice (if more than one is available) based on Stagelink
address, timesync accuracy, and tracking status (as stated in chapter 2, Time Synchronization Theory).
Every 20 minutes, each <I> or <G> with the "I_TIMESET ENABLED" line in F:\TIMESYNC.DAT performs a TIMESET
function, by asking the selected Stagelink Time Master for the current date/time. Unlike the timesync function in Mark V,
the timeset function in <I> or <G> does not slew its internal time, it jumps. The time error in this timeset function is
typically 27 ms, assuming the GTS is stable.
Each available Stagelink Time Master does a limited amount of stability checking on the Global Time Source (timecode
GTSs only). If the time-of-year ever changes by more than 30 seconds (except changing from December 31, 23:59:59 to
January 1, 00:00:00), the timesync function is disabled for a minimum of three minutes. If the time-of-year continuously
increases at a normal rate for more than three consecutive minutes, the timesync function automatically resumes.
GEH-6370
GEH-6370
CHAPTER 7
DIAGNOSTICS AND TROUBLESHOOTING
7-1. INTRODUCTION
This chapter covers some of Mark V Time Synchronizations built-in diagnostics and troubleshooting features. TIMEUTIL
and the trace buffers are discussed here.
GEH-6370
TIMESYNC STATUS
Overall TIMESYNC Function: ENABLED
TIMESYNC Controller: bc620AT
IRQ: None
Status: TRACKING
YES
Year: 1994
Days: 308
LOCAL CMOS
UTC
LOCAL
LOCAL
Selected
x
[LOCAL | UTC]
[LOCAL | UTC]
[LOCAL | UTC]
Chapter 7, Diagnostics and Troubleshooting 21
GEH-6370
The status is displayed in hexadecimal. The current definition for each bit is shown below. Bit 0 is considered the least
significant (rightmost) bit.
Bit 0:
Bit 1:
Bits 2-7
Bit 8:
Bit 9:
Bit 10:
Bits 11-15:
Get a copy of the trace buffer into a binary file by entering at the DOS prompt:
C:\> GBL2FILE timesync_trace TIMESYNC.BIN
The timesync_trace parameter must be in lowercase letters.
2.
Now this information is in the file TIMESYNC.OUT. The timesync protocol traces for Message Type: 4 (Time Diagnostic).
These time diagnostic messages contain error corrections between the Stagelink Time Master and the time slave. Other
message type dumps are used for development purposes only, and are not discussed here. A portion of a sample output from
TS_DUMP is shown in Figure 7-2 below:
GEH-6370
GEH-6370
GEH-6370
CHAPTER 8
EXAMPLE TIMESYNC CONFIGURATIONS
8-1. EXAMPLE 1 USING A SINGLE <I> AS THE GLOBAL TIME SOURCE
This example uses a single <I> as the GTS for the entire plant, using the low-drift capabilities of the bc620AT board.
Figure 8-1 shows a typical layout. Follow the steps below for setup.
1.
If multiple <I>'s exist, install the bc620AT board into the <I> containing the lowest Stagelink address. This <I> is
referred to as the PRIMARY <I> in this example.
2.
If redundant bc620 boards exist, install the board(s) in the <I>('s) with higher Stagelink addresses than the PRIMARY
<I> described in step 1. These <I>'s are referred to as SECONDARY <I>'s in this example.
3.
Connect RG-58 cable from the TIMECODE OUTPUT BNC connector of the PRIMARY <I> to the TIMECODE INPUT
BNC connectors on each SECONDARY <I>. Use T-connectors to parallel the signal from computer to computer. In
addition, parallel this cable to any DCS equipment which are to act as time slaves to the PRIMARY <I>.
4.
Optionally, the 1PPS output can be connected to DCS equipment that are to act as time slaves to the PRIMARY <I>.
5.
6.
7.
If TIMESET capability is wanted in any <I> or <G> without a bc620AT board installed, configure
F:\TIMESYNC.DAT in those computers with I_TIMESET ENABLED. (Other parameters are not required.)
GEH-6370
STAGELINK (ARCNET)
(RG-62 COAX CABLE)
TIMECODE
OUT BNC
PRIMARY
<I>
<C>
MK V
#1
<C>
MK V
#2
<C>
MK V
#3
1PPS
OUT BNC
RG-58
COAX
CABLE
1 PPS
TO
DCS EQUIPMENT
TIMECODE
IN BNC
SECONDARY
<I>
TIMECODE
IN BNC
SECONDARY
<I>
* Optional
IRIG-B TIMECODE
TO DCS EQUIPMENT
TERMINATION
RESISTOR
TERMINATION
RESISTOR
8-2. EXAMPLE 2 USING IRIG-B TIMECODE AS THE GTS WITH MULTIPLE <I> STAGELINK
TIMEMASTERS AND MULTIPLE <C>/<D> STAGELINKS
This example uses a single box as the GTS for the entire plant, possibly a satellite receiver, that generates an IRIG-B
timecode signal. Figure 8-2 shows a typical layout. Follow the steps below for setup.
NOTE
For redundancy requirements, no more than two <I> computers per Stagelink need to have
bc620AT boards installed.
1.
Install a bc620AT board in each <I> or <G> to be used as an available Stagelink Time Master.
2.
Connect RG-58 cable from the source of the IRIG-B timecode signal to each bc620AT board, using the TIMECODE
INPUT BNC connector. Use T-connectors to parallel the signal to each board.
3.
Continue the RG-58 cabling to any other piece of equipment in the plant that is to act as a time slave.
4.
GEH-6370
Configure F:\TIMESYNC.DAT in each of the <I>'s or <G>'s that have bc620AT boards installed as follows:
TIMESYNC BC620AT MODE IRIG-B BASE_PORT 0280
TIME_SOURCE LOCAL
PANEL_TIME LOCAL
I_TIME
LOCAL
TIME_LOAD LOCAL
I_TIMESET ENABLED
NOTE
If the timebase of the IRIG-B timecode signal is UTC, change the "TIME_SOURCE LOCAL"
line above to "TIME_SOURCE UTC".
5.
If TIMESET capability is wanted in any <I> or <G> without a bc620 AT board installed, configure
F:\TIMESYNC.DAT in those computers with I_TIMESET ENABLED. (Other parameters are not required.)
IRIG-B TIMECODE
SIGNAL FROM SATELLITE
RECEIVER OR
OTHER DEVICE
<C>
TIMECODE
IN BNC
TERMINATION
RESISTOR
STAGELINK (ARCNET)
(RG-62 COAX CABLE)
<I> # 1
<C>
MK V
#1
<D>
TIMECODE
IN BNC
<I> # 2
TERMINATION
RESISTOR
<C>
MK V
#2
<D>
RG-58
COAX
CABLE
TIMECODE
IN BNC
TERMINATION
RESISTOR
<I> # 3
<C>
MK V
#3
<D>
TIMECODE
IN BNC
<I>
IRIG-B TIMECODE
TO OTHER PLANT
EQUIPMENT
TERMINATION
RESISTOR
#4
<D>
STAGELINK (ARCNET)
(RG-62 COAX CABLE)
Figure 8-2. - Typical Layout for External IRIG-B GTS, using redundancy and multiple Stagelink Networks
GEH-6370
8-3. EXAMPLE 3 USING PULSE INPUTS AS THE GTS WITH MULTIPLE <I> STAGELINK
TIMEMASTERS
AND MULTIPLE <C>/<D> STAGELINKS
This example uses a single box as the GTS for the entire plant, possibly a satellite receiver, that generates one pulse per
minute (or hour) as a time reference. Figure 8-3 shows a typical layout. Follow the steps below for setup.
NOTE
For redundancy requirements, no more than two <I> computers per Stagelink need to have
bc620AT boards installed.
1.
Install a bc620AT board in each <I> or <G> to be used as an available Stagelink Time Master.
2.
Connect RG-58 cable from the source of the pulse input signals to each bc620AT board, using the EVENT INPUT
BNC connector. Use T-connectors to parallel the signal to each board.
3.
Continue the RG-58 cabling to any other piece of equipment in the plant that is to act as a time slave.
4.
Configure F:\TIMESYNC.DAT in each of the <I>'s or <G>'s that have bc620AT boards installed as follows:
TIMESYNC BC620AT MODE 1PPM BASE_PORT 0280
TIME_SOURCE LOCAL
PANEL_TIME LOCAL
I_TIME
LOCAL
TIME_LOAD LOCAL
I_TIMESET ENABLED
NOTE
If the pulse rate is 1 pulse per hour, change 1PPM above to 1PPH.
5.
If TIMESET capability is wanted in any <I> or <G> without a bc620 AT board installed, configure
F:\TIMESYNC.DAT in those computers with I_TIMESET ENABLED. (Other parameters are not required.)
GEH-6370
TERMINATION
RESISTOR
<C> STAGELINK
(RG-62 COAX CABLE)
EVENT IN
BNC
<C>
<I> # 1
MK V
#1
<D>
EVENT IN
BNC
<I> # 2
TERMINATION
RESISTOR
<C>
MK V
#2
<D>
RG-58
COAX
CABLE
TERMINATION
RESISTOR
EVENT IN
BNC
<I>
#3
<C>
MK V
#3
<D>
EVENT IN
BNC
TERMINATION
RESISTOR
<I> # 4
<D>
PULSE CODES
TO OTHER PLANT
EQUIPMENT
STAGELINK (ARCNET)
(RG-62 COAX CABLE)
Figure 8-3. - Typical Layout for External 1PPM or 1PPH GTS, with Redundant Stagelink Time Masters and Multiple Stagelink
Networks
GEH-6370
Notes:
GEH-6370
APPENDIX A
GLOSSARY OF TERMS
NOTE
Some of these terms are taken from the Bancomm bc620AT Time and Frequency Module, Operation
and Technical Manual.
NOTE
In the description of the various timecode signals below, resolution of the timecode signal should not
be confused with available accuracy. Special circuitry on the bc620AT allows the TFP to phase-lock
to the timecodes, achieving much higher accuracy than the base resolution of the timecode signal
itself.
2137 A 1 kHz modulated signal. Frame rate is 1 code per second. This is a time-of-day reference. Resolution: 1 ms.
ARCNET A LAN communications protocol developed by Datapoint Corporation, used to link exciters, drives, and
controllers. Allows a maximum of 255 drops with transmission at 25 Mbit/s.
BCD Binary Coded Decimal.
CF Control Functions.
Daylight Savings Time Time change observed in parts of the world to extend the number of daylight hours.
DCS Distributed Control Systems.
EDT Eastern Daylight Time. Reference to Daylight Savings Time in the Eastern United States.
EST Eastern Standard Time.
EPOCH A reference event. In timing applications, epoch often refers to a one pulse per second event.
FLYWHEEL In the timekeeping vernacular to 'flywheel' means to maintain time or frequency or both after the input
reference is removed or lost.
<G> GSM Gateway computer interface for the Mark V Turbine Control System using Ethernet in place of the Stagelink.
See <I>.
GPS Global Positioning Satellite. The fleet of GPS vehicles is used worldwide for navigational purposes by aircraft and
ships for position and velocity measurements. In addition, time-of-year information can be obtained by a GPS
receiver.
GPS Time Time reference available from GPS space vehicles which includes the accumulation of leap seconds. Leap
seconds are typically added or subtracted on June 30th and December 31st of each year as needed to correct UTC.
GSM GE Drive Systems Standard Message.
GTS Global Time Source. This is the source of time reference used for synchronization of time for all Mark V's and DCS
subsystems.
GEH-6370
<I> The Mark V Turbine Control Systems primary operator interface. Consists of a computer interface with GEs version
of ARCNET called the Stagelink.
I/O Input/output. Interfaces that allow the flow of data into and out of a device
IRIG Inter-Range Instrumentation Group. This group defines a family of timecode signals (both modulated and dc level
shifted) at various frequencies and frame rates. The IRIG timecodes are time-of-year references.
IRIG-A A 10 kHz modulated or dc level shifted signal. Frame rate is 10 codes per second. Resolution: 0.1 ms.
IRIG-B A 1 kHz modulated or dc level shifted signal. Frame rate is 1 code per second. Resolution: 1 ms.
IRIG-G A 100 kHz modulated or dc level shifted signal. Frame rate is 100 codes per second. Resolution: 0.01 ms.
IRQ Interrupt Request
Local Time A time reference commonly used in the geographic locale of the equipment. Local time is subject to jerks in
time caused by jumping the time reference forward in the spring for Daylight Savings Time, and jumping backward
in the fall to return to Standard Time (in the Northern hemisphere).
MAJOR TIME Units of time equal to or larger than seconds. Years, days, hours, minutes, and seconds are usually
implied.
MINOR TIME Subsecond time to whatever resolution is supported.
NASA-36 A 1 kHz modulated or dc level shifted signal. Frame rate is 1 code per second. This is a time-of-year
reference.
Resolution: 1 ms.
PPx Pulse Per x. A GTS using periodic pulses to mark an epoch as a time reference. Typical rates are 1 PPS (Pulse Per
Second), 1 PPM (Pulse Per Minute) or 1 PPH (Pulse Per Hour).
Receptacle A type of electrical fitting designed to connect with a plug, or prong, connector. Formerly referred to as
female.
SBS Straight Binary Seconds
Slave Device that follows commands from a remote master control device. Also referred to as follower.
Stagelink GEs version of ARCNET used in Turbine applications. See ARCNET.
Timeset The act of setting a clock to a time reference. This action does not imply any particular accuracy.
Timesync The act of locking a clock to a time reference. This action implies a continuous operation used to minimize
loss
of accuracy of the clock being synchronized referenced to the global time source.
UTC Universal Time Coordinated. This is the time reference used at the zero meridian. Also known as GMT
(Greenwich
Mean Time).
XR3 A 250 Hz modulated signal. Frame rate is 1 code per second. This is a time-of-day reference. Resolution: 4 ms.
GEH-6370
APPENDIX B
IRIG NOMENCLATURE
IRIG Time Codes have alphabetical as well as numerical designations. The nomenclature is defined as follows:
Rate Designation
A:
B:
D:
E:
G:
H:
1000
100
1
10
10000
1
pps
pps
ppm
pps
pps
pps
Form Designation
0:
1:
Pulse, width-coded
Sine wave, amplitude-modulated
Carrier/Resolution
0:
1:
2:
3:
4:
Coded Expressions
0:
1:
2:
3:
A000,
B000,
D001,
E001,
G001,
H001,
A003,
B003,
D002,
E002,
G002,
H002,
A130,
B120,
D111,
E111,
G141,
H111,
A133
B123
D112,
E112,
G142
H112,
D121,
E121,
D122
E122
H121,
H122
GE Motors &
Industrial
Systems
General Electric Company
Industrial Systems
1501 Roanoke Blvd.
Salem, VA 24153-6492 USA