Vous êtes sur la page 1sur 2

GAS SYSTEM

SERIES 4000 NATURAL GAS


400V / 50 Hz
NOx < 500 mg/Nm3

SYSTEM RATINGS
Gas genset with optional heat recovery
Genset
Type

Engine
Type

MTU 8V4000 GS
MTU 8V4000 GS
MTU 8V4000 GS
MTU 12V4000 GS
MTU 12V4000 GS
MTU 16V4000 GS
MTU 16V4000 GS
MTU 16V4000 GS
MTU 20V4000 GS
MTU 20V4000 GS

L33
L33
L64
L33
L64
L33
L64
L64
L33
L64

Output
Elect.1)
kWel.
776
854
1012
1199
1523
1718
1999
2028
2145
2530

Therm.2)
kWth.
401
443
475
616
712
974
952
965
1161
1200

Exhaust3)
kWth. (C)
422 (120)
448 (120)
461 (120)
636 (120)
691 (120)
821 (120)
930 (120)
936 (120)
1078 (120)
1147 (120)

Low Temp.
kWth. (C)
47 (40)
49 (40)
69 (43)
82 (40)
104 (43)
113 (40)
125 (43)
127 (43)
142 (40)
175 (43)

Energy
input4)
kW
1832
1993
2298
2795
3438
3991
4519
4573
4990
5748

Efciency
Electr.
nel. (%)
42.4
42.8
44.0
42.9
44.3
43.0
44.2
44.3
43.0
44.1

Total
ntot (%)
87.3
87.5
84.8
87.7
85.1
88.0
85.9
85.9
87.9
84.8

Output
Elect.1)
kWel.
776
1169
1560
1948

Therm.2)
kWth.
446
632
863
1035

Exhaust3)
kWth. (C)
420 (120)
638 (120)
805 (120)
1101 (120)

Low Temp.
kWth. (C)
32 (53)
43 (53)
76 (53)
78 (53)

Energy
input4)
kW
1853
2747
3651
4577

Efciency
Electr.
nel. (%)
41.9
42.5
42.7
42.6

Total
ntot (%)
88.6
88.8
88.4
89.2

Methane
number5)
70
80
80
80
80
80
80
80
80
80

hot ambient conditions


Genset
Type

Engine
Type

MTU 8V4000 GS
MTU 12V4000 GS
MTU 16V4000 GS
MTU 20V4000 GS

L32
L32
L32
L32

1) Rated power at nominal voltage, power factor = 1,0 and nominal frequency
2) Heat output from engine cooling with tolerance of 8%
3) Heat output from exhaust (exhaust cooling to 120C) with tolerance of 8%
4) Performance data in accordance with ISO 3046/I-2002 with tolerance of 5%
5) Referenced methane number
Project specific data on request:
- different alternator voltage
- different flow-/return-temperatures, hot cooling, methane number, installation conditions etc.
- Container

Methane
number5)
80
80
80
80

DRAWINGS AND DIMENSIONS

Note: This drawing is provided for reference only and should not be used for installation planning.

Genset Type
MTU 8V4000 GS
MTU 12V4000 GS
MTU 16V4000 GS
MTU 20V4000 GS

Dimensions Genset (L x W x H)
4200 x 2000 x 2400 mm
5000 x 2000 x 2400 mm
5500 x 2000 x 2600 mm
6000 x 2000 x 2600 mm

Heat recovery module (Lh x W x H)


1500 x 1900 x 2000 mm
1500 x 1900 x 2000 mm
1500 x 1900 x 2000 mm
1500 x 1900 x 2000 mm

4000
Conguration
No. of cylinders
Bore/Stroke
Cyl. displacement

90 V
8/12/16/20
170/210 mm
4.77 lit.

DESIGN AND EQUIPMENT (EXTRACT)


// Sliding gear starter 24V
// Gas supply with electronically controlled gas metering valve
// Electronic high-voltage capacitor ignition system with one ignition coil

per cylinder
// Electronic speed governor for speed and power output control with

automatic knocking control

Any specications, descriptions, values, data or other information related to dimensions, power or other technical performance criteria of the goods as provided in
this general productinformation are to be understood as non-binding and may be subject to further changes such as but not limited to technical evolution at any time.
Version: 01.08.2014, materials and specications subject to change without notice due to technical advances.

MTU Onsite Energy


A Rolls-Royce Power Systems Brand
www.mtuonsiteenergy.com

Subject to change. | 3234731 | Edition 02/14 | ENC 2014-08 | Printed in Germany on chlorine-free bleached papaer.

ENGINE DATA

Vous aimerez peut-être aussi