Slide 4
Proportional control is a simple and widely used method of control for many kinds of systems. Proportional Integral
- Derivative control, also called PID control, is somewhat more complex and may be suitable in certain situations. It is
important to note that P, PI, and PID can be used in different applications and using each one has its advantages.
As we will see, there are cases where using all P+I+D is not the best application.
Slide 5
Proportional control involves giving a response proportional to the stimulus. To say that less technically, the warmer it
gets in a certain range of temperature, the more cool air we put in. So, for instance, looking at this sample
proportional response table for a cooling application, at 22.8oC we might have cool air flowing to a room at 1,360
cubic meters per hour. If the room happens to be in the US, at 73oF we would have 800 cubic feet per minute of cool
air.
2011 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
However, if the temperature were to increase to 23.3oC or 74oF, I might proportionally adjust my air flow to 1,760
cubic meters per hour or 1,036 cubic feet per minute.
Each of these steps are at 200 cubic meters per hour or 118 cubic feet per minute, so the higher the temperature
gets, the greater my system responds to it, and the more airflow is produced. Drawing this table as a chart shows you
that the response is proportional to temperature.
Slide 6
You can think of proportional control as control that follows one simple rule, e.g. For every degree of temperature
difference from the setpoint, increase the airflow by a certain amount.
This equation represents the rule:
Output = [degrees from setpoint] * [amount of air]
Output equals degrees from setpoint multiplied by amount of air
The controller will apply this rule repeatedly by:
Checking the sensor
Changing the airflow if necessary
Waiting a fixed time, and then
Repeating as necessary
Slide 7
The control can be adapted by adding more terms. You can think of this as adding more rules to follow. When an
integral component is added, there will now be two parts in the control calculation, the proportional part plus the
integral part.
When a derivative component is added, the control calculation will now have three parts.
2011 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
Slide 8
Simply put; our proportional control term (Output = [degrees from setpoint]*[amount of air]) has more terms added to
it to become this equation:
Output = Pout + I out + D out
Slide 9
We already saw the proportional response it is the simplest to understand. Proportional response is addressing
how far from set-point the variable is.
As already mentioned, the response of the system is proportional with how far the measured variable is from the
desired set-point of that variable. The response increases as the offset increases. The proportional term tells the
system how much change to make to get back to its setpoint.
Hence, the first rule we mentioned before For every degree of temperature difference from the setpoint, increase the
airflow by a certain amount as demonstrated in this equation:
Output = [degrees from setpoint] * [amount of air]
Slide 10
The integral, when included, addresses how long the variable has been away from the setpoint. Simply put, in a
cooling application, if the variable has been above the setpoint too long, more cool air should be delivered than what
the proportional response is telling the control system to perform.
Slide 11
So, with PI control we now have two rules. The new rule which is added to the first one might be For every minute of
time and degrees of difference from the setpoint, adjust the airflow by a certain amount. Which is demonstrated in
this equation
e.g. I out = [time and degrees from setpoint calculation] * [air adjustment]
Combining the P and I gives two rules in one control algorithm:
Output = ([degrees from setpoint] * [amount of air]) +
([time and degrees from setpoint calculation] * [air adjustment])
2011 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
Slide 12
The [time and degrees from setpoint calculation] is an integral.
The mathematical symbol for it looks like this .
The graph shows you visually how the integral is calculated. It is represented by the yellow filled in area between the
tracking of the temperature and the setpoint. At each of these measurement points, the time duration between
measurements is multiplied by how far the variable is from the setpoint, thus giving us the time and the intensity of
separation between the variable and the setpoint. All of these measurement points are added up and create an
additional load that, when included in calculations, tell the controller that more of a push is needed to get the system
back to setpoint.
Slide 13
The derivative component, when included, addresses how fast the variable is approaching its setpoint. It is
compensating for the speed of response. If we were measuring temperature, this would be how fast the temperature
is falling per second.
The derivative
component
So, with PID control we would have a third rule to add to the first two. Something like If the temperature is rising at 2
degrees per minute, add a certain amount of more airflow. Or If the temperature is falling at 4 degrees per minute,
decrease a certain amount of airflow. A more general way to say that might be For every degree per minute of
change, adjust the air flow by a certain amount.
2011 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
2011 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.
Slide 19
It is important to point out that when we use the term system in this discussion, it doesn't mean an entire building's
control system. Here we mean one room with a temperature sensor, flow sensor on the VAV, VAV damper actuator,
and variable speed drive controlling a fan. A building control system may have many smaller systems it is controlling.
A slow responding system would be best fit with a proportional response.
A moderate system would be best fit with a proportional + integral or a proportional + integral + derivative response
Lastly, a fast responding system would be best fit with a floating response.
Slide 20
You may have heard that PID control is the most expensive and best solution, but there are good reasons why
floating control should be used for fast responding systems. In our next class, we will look in more detail at slow,
medium and fast responding systems, and see why each is best served by a different control response. In addition,
we will show step-by-step how the three terms of P I D function together and provide you with an interactive example
to help you understand the concepts.
Slide 21
Lets summarize some of the information that we have learned in this course.
Proportional control is a simple control method that provides a response proportional to the stimulus. It is
calculated from the difference between the actual and set-point. An integral term can be added, which is driven by
the amount of time that the measured variable has been offset from the setpoint. On a graph of actual versus setpoint
over time, it is calculated from the area under the graph. A derivative term can also be added, which is driven by the
rate of change of the measured variable. This is useful to prevent overshoots. On a graph of actual over time, it
is calculated from the slope of the line.
Finally, also we identified which response was appropriate to a slow responding system, which response was
appropriate for a moderate and fast responding system.
Slide 22
Thank you for participating in this course.
2011 Schneider Electric. All rights reserved. All trademarks provided are the property of their respective owners.