SF6 GAS-INSULATED
METAL-ENCLOSED SWITCHGEAR

72.5kV~126kV Single-phase-enclosure type GIS

Xian Electric Import & Export Co.,Ltd.


A Member of China Xian Electric Group

China Xian Electric Group ( XD for short ):


XD is the largest base for manufacturing complete sets of ultra-high voltage AC transmission
and transformation equipment in China.
XD is the largest base for manufacturing complete sets of ultra-high voltage DC transmission
and transformation equipment in China.
XD is the largest base for researching and developing complete sets of ultra-high voltage AC
& DC transmission and transformation equipment in China , and is appointed by the state as
the national profession center responsible for the quality supervision, examination and test.
XD is the largest base for exporting complete sets of ultra-high voltage AC & DC transmission
and transformation equipment in China.

Main Products


126kV /72.5kV Single-phase-enclosure type GIS

126kV/72.5kV GIS

The product is a compact GIS designed for system voltages up to 126kV and for rated
short-circuit currents up to 31.5kA. The circuit breaker is operated by a spring operating
mechanism which is used for three pole operation.

FEATURES
1 Compact design
It is one of the most compact designs of single phase enclosure GIS in the world. The width of a typical bay
is 1200mm or 1500mm. The inner conductors and enclosures are made of corrosion-resistant aluminum. A
bay with double busbar weights approx. 2,500 kg.

2 Superior interrupting capability


The circuit breaker is equipped with self-energized interrupter that is characterized by a self-adapting ability
breaking of both small and large currents.
These breakers can cope with all known switching phenomena. Their efficiently designed interrupter clears
both the severe rate of rise of the recovery voltage of short-line faults and the high recovery voltage peak of
out-of-phase interruption. In magnetizing current switching, the overvoltage is less than twice the applied
voltage. No restrike or reignition occurs in charging current switching.

3 Reduced maintenance work


Since the spring operating mechanism requires neither compressed air nor hydraulic fluid, inspection and
maintenance work is minimized. Also, these breakers seldom require inspection since SF6 gas deterioration
and arcing contact wear, owing to arc breaking, are negligible.

4 Perfect assembling and testing conditions and minimum work at site


The GIS is assembled and tested against similar conditions of assembling site, packed in transport unit after
tested, for easy and convenient transport and minimizing work at site.

5 Lower leakage of SF6 gas


The mode of separated monitoring is used in the SF6 gas system of GIS, doing away with SF6 valves and SF6
piping system. New self-sealed adapters and SF6 gas densimeters are used to get rid of the possibility of SF6
leakage outside the GIS, lowering the SF6 gas leakage.

STRUCTION

In the GIS all elements are single phase enclosure except the main bus which is three phase enclosure. The
enclosure is coaxial with the inner conductor supported by the insulators or spacers. Tulip contactors are
used to adjoin the inner conductors together. Cable sealing end or SF6 outdoor bushing can be used to
connect GIS with overhead lines or transformers.
The auxiliary electrical units required for command input, warning, locking, SF6 density monitoring etc are
accommodated in local control panel of each bay.

=N O

Key

4
2

1

2

3

4

5

6

7

8

9

10

11


2
3

7
11

11

Double-Busbar Scheme (Bushing inlet/outlet)

4
2

11

11

Double-Busbar Scheme (Cable inlet/outlet)

CB Circuit breaker
DS Disconnector ( isolator )
ES Earthing ( grounding ) switch
CT Current transformer
LA Lightning Arrestor
PT Voltage ( potential) transformer
LCP Local contring mechanism
CSE Cable-sealing-end chamber
BSG Bushing
GCB Gas Circuit breaker
M1-M2 Main busbar

7
11

Single-Busbar Scheme

STANDARD BAYS
At present, the design and production of the GIS have been performed according to the special properties of
program and standard function units and bays, accomplishing the standard and modular design and production.
Several typical standard bays are shown below.

1 InIet or Outlet bay


Single-Busbar Scheme

BSG
ES
DS

850

CT

DS
ES

DS

GCB

CT

ES
ES

ES
LCP
1575

CB
DS

ES

AM
120

BUS
915

520

BSG

ES
DS

ES

850

CT
DS

GCB
LCP

DS

CT

ES

ES
ES

1575

CB
DS

ES

AM

915

BUS

120

520

CSE

DS
CT

ES

850

DS
ES

DS

GCB

ES

CSE
ES

CT

ES

LCP
1575

CB
M

DS

ES

120

AM

520

915

BUS

=P Q

Double-Busbar Scheme

BSG
ES
DS

850

GCB

ES

DS

CT

ES

ES

DS

DS

CT

ES
CB

1575

LCP

DS

DS
M1

M2

ES
BUS1

AM
120

BUS2
520

769

915

CSE

DS
850

CT

ES
DS

GCB

ES

DS

ES

DS
CSE

ES

ES
CT

LCP
1575

CB
M2

M1

ES

AM

DS

DS

120

BUS1
BUS2
520

769

915

1368

Bridge-Type Scheme

BSG
ES
DS

ES

DS

LA

DS

850

CT
DS

GCB

ES
ES

ES

CT

ES
DS

1575

LCP

LA

CB
DS

ES

AM
120

BUS
520

915

1995

619

ES

ES
BSG

DS
DS
ES

ES

DS

ES

ES

2028

ES
PT

PT
M

120

BUS

2 Busbar connection bay


ES
CT

ES

850

DS
DS

GCB

ES
CT

ES
LCP
1575

CB
M1

ES

DS

M2

AM
120

BUS1
520

915

BUS2

769

3 Measurement and protection bay


ES

ES

CT

ES

DS

DS
ES
DS

LA

LA

DS

PT
BUS1

PT

520

PT

1220

769

1220

ES

ES

LA

M2

M1

ES

LA
PT

BUS2

619

=R S

TYPICAL LAYOUT
1 Single-Busbar Sectional Scheme

BSG

BSG

CSE
BSG

CSE
DS

ES

DS

ES

DS

DS
CT

ES

CT

ES

CT

ES

DS

DS

ES

ES

ES

CB

CB
ES

DS

ES

ES
CT

CB

ES

DS

BSG

ES

ES

CB
DS

DS

CT

ES

DS

ES

CT

DS

LA

DS

PT

DS

ES
CT

CB

CB

ES

ES

ES

DS

DS

BUS1
PT

7500

1500

1500

1500

1500

1500

1500

10500

1500

1500

ES

CB
ES

LA
BUS2

ES

ES

2 Bridge-Type Scheme
BSG

BSG
ES

DS

LA

DS

ES DS
ES

CT

ES

CT

CB

CB
ES

DS

DS

ES

DS

ES

DS

DS

ES

ES

DS

LA

ES

CT

CB

DS

ES

ES

ES

ES

PT

ES

BSG

DS
DS

ES

PT

7000

BSG

1500

500

1500

1500

1500

500

1500

12000

=T U

3 Double-Busbar Sectional Scheme

CSE

BSG
DS
CT

ES
ES

CT
ES

CB
DS

DS

DS

ES
ES

CT
ES

CB
DS

DS

DS

ES

ES

ES

ES

CT

ES

CB
DS

DS

ES
DS

DS
ES
CT

DS
CB

ES
LA

DS
PT

DS

LA
PT

ES

ES

DS

ES

CT
ES

CB
DS

BSG

CSE

CSE

CSE

DS

ES
ES

CT
ES

CB
DS

DS

DS

DS

BUS1

10500

1500

1500

1500

1500

1500

1500

ES

CB

BUS2

1500

ES

1500

ES
DS

RATINGS
Main Technical Data for 72.5kV~126kV GIS ( Based on IEC )
Ratings
Remarks

Item
72.5kV

126kV

Indoor or outdoor

Installaton
Ambient temperature

-30~40

Humidity (per month)

 95

Height above sea level

1000

Wind velocity

m/s

 35

Earthquake intensity

Horizontal acceleration: 0.4


Vertical acceleration: 0.2

Creepage distance

cm/kV

3.2

Rated voltage

kV

Rated current

1250/1600/2000

Rated short-time withstand current (3s)

kA

31.5

Peak withstand current

kA

80

Lightning impulse withstand voltage(peak)

kV

325

550

Power frequency withstand voltage(r.m.s)

kV

140

230

Rated SF6 gas pressure(exclusive of CB)

MPa

CB: 0.5
Other unit: 0.45

Annual leakage rate of SF6 gas

1

Rated current

1250/1600/2000

Rated breaking current

kA

31.5

Rated short-time withstand current (3s)

kA

31.5

Peak withstand current

kA

80

Full breaking time

ms

 60

At 25

Applied ambient
conditions

General data

72.5

Accelerated
simultaneously
Calculated to
rated voltage

126

1 min
20

Circuit breaker
Rated operating duty

O-0.3s-CO-180s-CO

First-pole-clean factor

1.5

Operating mechanism

Spring

==V

NM

Ratings
Item

Unit

Remarks
72.5kV

Operating time

Open: 8;
Close: 8

Disconnector
Operating mechanism
Operating time
Earthing switch

Motor/Motor spring
Open: 8;
Close: 8

Motor spring for FES;


Manual or Motor for ES

Operating mechanism
Rated current

126kV

1250/1600/2000

Type of enclosure

3 phases in 1 enclosure

Material enclosure

Al.

Material conductor

Al.

Rated current ratio

300-500-750-1000-1250-1500-2000/5

Busbar

Current transformer

Capacitive

VA

Measurement: 0.5;
Protection: 5P20

Accuracy

Voltage transformer

Rated primary voltage

kV

Rated secondary voltage

100/ 3

Voltage of remaining voltage winding

100

Rated burden

VA

100~150

Type

Lightning arrester

20/30/40/50

72.5/ 3

126/ 3

Metal oxide-zinc

Rated voltage of LA

kV

42

73

DC 1mA, reference voltage

kV

 128

 145

Max, lightning impulse residual voltage(peak)(8/20us)

kV

==== 235

 260