Primary Distribution

Switchgear
Product /Service Offering

Casablanca, 10/2010

Primary Distribution: Offering


Engineered
Switchgear
Solutions
Power Houses / Trackside subs

Packages

Innovative solutions

Switchgears
(Indoor
& Outdoor)
Motor starter
AIS & AIS
Motor Starter

Live tank / Dead Tank


GIS
Outdoor

GIS

Components
VCB
VCB

Core
components

Contactor
Contactor

VCB
VCB

SF6
SF6 CB
CB

Vacuum interrupters,
mechanisms,
actuators

Schneider Electric -Energy J. VAGNON 12/10/2010

Circuit Breaker

Circuit breaker range


Actual range of PDS circuit breaker (IEC, GB, GOST & IEEE)
HVX & FPX

PIX range

HVX-O

China

HVXO 36 FP

36/40.5kV
app.

Core business market

Schneider Electric -Energy J. VAGNON 12/10/2010

VX range

Railway
Furnace

BLV

VA/H

VISAX EOX

Local offering
GCB

Niche segment market and


legacy product

>
15

Circuit Breaker Range


HVX range
VA & VX range
BLV range
FP & FPX range

Schneider Electric -Energy J. VAGNON 12/10/2010

16

HVX range
Un

Isc

In

Applications & Comments

Open Pole
Overmolded

HVX S

12kV

25kA

1250A

PIX, PI, PMX, OEM

HVX A

17,5kV
24kV

40kA
31,5kA

2500A

PIX, PIX double busbar, PMX, OEM

HVX B

17,5kV

50kA

3150A
5000A*

PIX, PIX High, GCB up to 15kA 50kA


* Up to 5000A with air forced cooling

HVX
compact

17,5kV

31,5kA

2500A

PIX-Compact, PIX-MV, OEM

HVX O

12kV
24 kV

50kA
31.5kA

3150A
3150A

Chinese OEM (KYN28), OEM

HVX O

36kV

31,5kA

2500A

DNF7 China, EOX

Schneider Electric -Energy J. VAGNON 12/10/2010

17

HVX range
Existing and on going HVX range for 12kV

kA
50
HVX-B

40
HVX
Compact

31,5
25

HVX-S

HVX-0

HVX-A

20
630

Schneider Electric -Energy J. VAGNON 12/10/2010

1250

1600

2500

3150

18

HVX range
Existing and on going HVX range for 17,5kV

kA
50
HVX-B

40
31,5

HVX-A
HVX-0

25

HVX
Compact

20
630

1250

Schneider Electric -Energy J. VAGNON 12/10/2010

1600

2500

3150

19

HVX range
Existing and on going HVX range for 24kV

kA
50
40
31,5
25
HVX-A

20
630

1250

Schneider Electric -Energy J. VAGNON 12/10/2010

1600

2500

3150

20

HVX
Type and variants with circuit-breaker
HVX - F

Fixed type
Schneider Electric -Energy J. VAGNON 12/10/2010

HVX - E

Draw-out type
manual/motor operation
21

MTX and UTX - Variant modules

Metering Truck
MTX-E with primary fuse

Schneider Electric -Energy J. VAGNON 12/10/2010

Disconnecting Truck
UTX-E up to 12 kV

Disconnecting Truck
UTX-E up to 24 kV

22

HVX range
HVX up to 24kV

HVX is the consequent development of a new


generation of circuit breakers as part of a long term
product platform.
Core product, designed for the worldwide use up to 24
kV.
Very compact design for use in metal-clad switchgear
through metal enclosed design.
The HVX block structure creates a economical
solution for each application.

Schneider Electric -Energy J. VAGNON 12/10/2010

23

HVX up to 24kV

HVX S

HVX Compact
(for PIX Compact)

HVX B
(for PIX)
Schneider Electric -Energy J. VAGNON 12/10/2010

HVX A
(for PIX)

HVX B
(for PIX High)
24

HVX Ratings
HVX Standard
Rated current

12 kV
630-2500

Rated short-circuit
making current

kA

40-100

PCS (pole centre spacing)

Rated short-time
current

17,5 kV
630-2500

24 kV
630-2500

40-100

40-80

(mm)

165(-F)
185/ 210

185/
210

210/
275(-F)

kA

16-40
3s

16-40
3s

16-31,5
3s

IEC 60056, VDE 0670 part 101-108, BS5311, NF-C64

Schneider Electric -Energy J. VAGNON 12/10/2010

25

HVX Ratings
HVX High Performance
Rated current

Rated short-circuit
making current

kA

PCS (pole centre spacing) (mm)


Rated short time
current

kA

12 kV
1250-3150

17,5 kV
3150

80-125

80-125

210/254

210/254

31-50
3s

31-50
3s

IEC 60056, VDE 0670 part 101-108, BS5311, NF-C64

Schneider Electric -Energy J. VAGNON 12/10/2010

26

PIX Compact Truck with Vacuum Circuit


Breaker HVX Compact
Two cubicle width 600mm and 800mm
Two CB for the range

Standard = IEC + GOST + 50/60Hz


Open pole design
Range optimised for 12kV and use at 17.5kV with
additional insulation material

Up to 1250A

Up to 2500 A

2 new VCBs based on standard components


Schneider Electric -Energy J. VAGNON 12/10/2010

<

back
27

HVX range
HVX O

Embedded pole design


Design for OEM China market
Up to 12kV 50kA 3150A
Version for 17.5kV/ 24kV available
Fully compatible with KYN28 (ZS1)
Proven mechanical drive
All test performed according new IEC 62271-100

Embedded pole design

<

back

Schneider Electric -Energy J. VAGNON 12/10/2010

28

HVX range
HVX O 36/40.5

Compact 36/40.5kV vacuum circuit breaker


Up to 36kV 25kA 2000A & 40.5 kV, 31.5 kA, 2500A
Using solid encapsulation technology
Poles are fully insensitive to the environment
Proven mechanical drive
All test performed according new IEC 62271-100

Our latest 36/40.5kV Vacuum Circuit breaker

<

back

Schneider Electric -Energy J. VAGNON 12/10/2010

29

Circuit Breaker Range


HVX range
VA & VX range
BLV range
FP & FPX range

Schneider Electric -Energy J. VAGNON 12/10/2010

43

FP & FPX range


Un

Isc

In

Applications & Comments

FP

12kV
17,5kV
24Kv
36kV

...50kA
...40kA
...40kA
...31,5kA

...3150A
...3150A
...3150A
...3150A

DNF7, OEM

FPX

12kV
17,5kV
24kV

...40kA
...31,5kA
...31,5kA

...4000A
...4000A
...3150A

PIX

Schneider Electric -Energy J. VAGNON 12/10/2010

44

FP range
Up to 36kV 31,5kA 3150A
Use puffer or combination of thermal
expansion and puffer technology
Proven circuit breaker
Fitted in DNF7

Proven range of SF6 circuit breaker


Schneider Electric -Energy J. VAGNON 12/10/2010

45

FP range
AREVA engineers have been working on SF6
gas filled circuit breakers since as early as 1959.
FP range of circuit breakers is a result of many
years of experience.
Designed for the worldwide use up to 40.5kV.
Well suited for capacitor current switching
applications.
The modular structure creates a wide range and
an ideal breaker exists for each particular
application.
Schneider Electric -Energy J. VAGNON 12/10/2010

46

FP range
Type and variants with circuit-breaker

Front
arrangement

Longitudinal
arrangement

FP with Reflex
action Device

<

back

Schneider Electric -Energy J. VAGNON 12/10/2010

47

FPX
Fitted in PIX
Use thermo puffing technology
Lower operating forces
Low operating pressure
High level of operation (10.000)
Fast reclosing cycle

High end SF6 circuit breaker


Schneider Electric -Energy J. VAGNON 12/10/2010

48

FPX
Disjoncteur / Circuit Breaker
Tension assigne
Rated voltage
Pouvoir de coupure
Breaking capacity
Pression de remplissage (bar relatif 20 ) (1)
Filling SF6 pressure (bar relative at 20C) (1)

7,2 kV &
7.2 kV &
< 25 kA
< 25 kA
1.2
1.2

12 kV
12 kV
>25kA <16 kA
>25kA <16 kA
2.7
1.2
2.7
1.2

17,5 kV & 24 kV
17.5 kV & 24 kV
>16 kA <31,5 kA
>16 kA <31,5 kA
2.7
2.7

> 31,5 kA
> 31,5 kA
3.5
3.5

Dures de fonctionnement assignes


Operating times
ouverture / opening (ms)
coupure / breaking (ms)
fermeture / closing (ms)
Squences de manuvres assignes
Rated operating sequences

Endurance mcanique
Mechanical endurance
(1) Disjoncteur sans pressostats / Circuit breaker without pressure switch

50
70
50
O - 3mn - FO - 3mn - FO
O - 3mn - CO - 3mn - CO
O - 0,3sec - FO - 3mn - FO
O - 0.3sec - CO - 3mn - CO
O - 0,3sec - FO - 15sec - FO
O - 0.3sec - CO - 15sec - CO
10 000 F/O
10.000 C/O

<

back

Schneider Electric -Energy J. VAGNON 12/10/2010

49

Contactors

Contactor range
Actual range of PDS Contactor (IEC & GB)
Vacuum
CPX*

CLX

3,6 kV Compact
Contactor For
General Duty and
Capacitor Switching

7,2 kV Slimline
Contactor For
General Duty

CBX*

Schneider Electric -Energy J. VAGNON 12/10/2010

Vacuum

SF6

GFA

CVX 7 &12*

GFX

7,2kV & 12kV


for general duty and
Capacitor Switching

Loose components for panel


builder

* Also used in China

SF6

7,2kV & 12kV


Fused contactor

PIX MCC
PIX
AMS

PIX

Integrate in our range of


Switchgear

>
51

GEC ALSTHOM
T&D Vacuumrange
Equipment
Vacuum Contactorexpanding

Ltd

The benefits of switching motors with Vacuum contactors is well


known.
Reliable, compact equipment with high number of operations.
Fuse protection provides fast clearance of fault and limited fault
energy.
Cabling to equipment is rated for the load not the fault rating
therefore reducing costs.
Schneider Electric -Energy J. VAGNON 12/10/2010

52

Vacuum Contactor - todays range


AC4
Current
(A)
400

CLX3 & CBX3

CBX3-C

CPX2

315

CPX2-C

3,6

7,2

12

Voltage (kV)

Motors, Transformers, Resistors And General Switching


Up to 12 kV / 315A & 7.2 kV / 400A AC4
Schneider Electric -Energy J. VAGNON 12/10/2010
PCMVB-NA-04

53

Vacuum Contactor - todays range


Capacitor
Switching
Current
(A)
400

CBX3-C

200

CPX2-C

3,6

7,2

12

Voltage (kV)

Capacitor Switching
Up to 12 kV / 400A
Schneider Electric -Energy J. VAGNON 12/10/2010
PCMVB-NA-04

54

Vacuum Contactor - todays range


CBX
Comply with IEC 60470 Standard
Size (W x D x H) 343 x 333 x 258 mm
Free Auxiliary Contact : 1O + 1C (Option 1)
3O + 3C(Option 2)
Mechanically Latched Or Magnetically Held
Control Voltage Range 24-240 Vdc
Used within PIX and PIX MCC (CVX)
Rated
Voltage

Rated
Operational
Current

Interrupting
Current

Average
Chopping
Current

(A)

Capacitor
Switching
Operating
Current
(A)

(kV)

CBX3-07
CBX3-C-12

(kA)

(A)

7,2

400

0,5

General Duty (AC1, AC2, AC3, AC4)

12

315

2,3

General Duty (AC1, AC2, AC3, AC4)


Capacitor Switching

270 400

Use

7.2 & 12 kV Contactor for general duty and capacitor


switching
Schneider Electric -Energy J. VAGNON 12/10/2010

<

57
back

Fused Vacuum-Contactor Trucks


CVX 7

CVX 12

up to 7.2 kV
cubicle width 400 mm

for 12 kV
cubicle width 650 mm

CVX suitable for use in PIX and PIX MCC


Schneider Electric -Energy J. VAGNON 12/10/2010

58

Fused Contactor Combinations


The need for high rated
fused contactors in heavy
industry is extensive Oil &
Gas, Mining & Metals,
Power generation..
PIX MCC offers
Fused vacuum
Contactors
Compact dimensions
Up to 50kA, 4000A
busbars
Highest levels of
operator safety

Schneider Electric -Energy J. VAGNON 12/10/2010

<

59
back

SF6 Contactors
Design & range

Schneider Electric -Energy J. VAGNON 12/10/2010

60

SF6 Contactor - todays range


GYROFLUOR GFA
7,2/12 kV
200A & 400 A
Rotating arc SF6 switching technology
Electrically held or mechanically latched
Ease of installation
Low switching transients
Simple & robust design for a high
reliability
Up to 300,000 operations
Low maintenance

Schneider Electric -Energy J. VAGNON 12/10/2010

<

61
back

Fused SF6 Contactor Truck


GFX
Major ratings
315 A AC4 Fuse contactor drawer
for PIX12 kV- 40kA
GFA contactor
Major variants
292 mm Din fuses
Mechanical latch or magnetically
held contactor

GFX suitable for mounting PIX


Schneider Electric -Energy J. VAGNON 12/10/2010

<

62
back

AIS up to 48kV

Air-insulated switchgear
Single busbar

63 kA
50 kA
PIX MCC 50
(5000A)

40 kA
31.5 kA

PIX High rating


(5000A)
PIX
(4000A)

PIX MCC 40
(4000A)

25 kA

PIX Compact
(2500A)

PIX
(2500A)

DNF7
(3150A)

16 kA
7.2 kV

Schneider Electric -Energy J. VAGNON 12/10/2010

12 kV

17.5 kV

24 kV

36 kV

48 kV

64

Rated short circuit current in kA

Air-insulated switchgear up to 24 kV
50

40

L-TRI
PIX High
PIX MCC

30
PIX
PIX Compact

20
PI
PN

HVX

10

630

1250

4000

5000
Rated current in A

DBB offer available up to 24 kV (WBD, PIX 2B, PAUD)


Schneider Electric -Energy J. VAGNON 12/10/2010

65

Air-insulated switchgear up to 36/40.5


(48) kV
Rated short circuit current in kA

FP
40

31.5
DNF7 - AMS
25

20
HVX / HVX-O

630

1250

2000

3150 A
Rated current in A

Schneider Electric -Energy J. VAGNON 12/10/2010

>

66

PIX family
AIS up to 24kV

PIX Family overview

PIX Family
PIX Standard
PIX Compact
PIX High
PIX Motor Control Center

Schneider Electric -Energy J. VAGNON 12/10/2010

68

PIX - The Switchgear Family

PIX

PIX
PIX Marine

Schneider Electric -Energy J. VAGNON 12/10/2010

PIX
High

PIX
Motor Control
Center
PIX Compact

69

PIX - The Switchgear Family


Single busbar
63 kA
50 kA
PIX MCC 50
(5000A)

40 kA
31.5 kA

PIX High rating


(5000A)
PIX
(4000A)

PIX MCC 40
(4000A)

25 kA

PIX Compact
(2500A)

PIX
(2500A)

16 kA
7,2 kV

Schneider Electric -Energy J. VAGNON 12/10/2010

12 kV

17,5 kV

24 kV

36 kV

70

Product benchmark AIS

PIX Family
PIX Standard
PIX High
PIX Motor Control Center

Schneider Electric -Energy J. VAGNON 12/10/2010

71

PIX - Definition
PIX

Core product of AIS PDS range


Universal and International solution for
withdrawable air insulated switchgear,
Fitted with :
HVX Vacuum circuit breaker
FPX SF6 circuit breaker
CVX Vacuum contactor
GFX SF6 contactor
Back to wall with optional rear and top
access
Up to 17,5kV 40kA 4000A
24kV 31,5kA 2500A

PIX is the core product of


AIS PDS range
Schneider Electric -Energy J. VAGNON 12/10/2010

72

PIX - Technical Data with Vacuum Circuit Breaker


Rated voltage

kV

12

17.5

24

Rated frequency withstand voltage

kV

28(42)

38(42)

50

Rated impulse withstand voltage (BIL)

kV

75

Rated frequency

Hz

50/60

50/60

up to A

3150/
40001)

3150/
40001)

Rated current

95

125
50/60
2500

Rated peak current

kA

100

100

80

Rated short time current (1s - 3s)

kA

40

40

31.5

Internal arc fault tested (1s)

kA

40

40

31.5

Degree of protection

IP

3X(4X)

3X(4X)

3X(4X)

1) with fan cooling


Schneider Electric -Energy J. VAGNON 12/10/2010

73

PIX Technical Data with SF6-Circuit Breaker


Rated voltage

kV

12

17.5

24

Rated frequency withstand voltage

kV

28(42)

38

50

Rated impulse withstand voltage (BIL)

kV

75

95

125

Rated frequency

Hz

50/60

50/60

50/60

up to A

3150

2500

2500

Rated peak current

kA

100

100

80

Rated short time current (1s - 3s)

kA

40

31.5

31.5

Internal arc fault tested (1s)

kA

40

31.5

31.5

Degree of protection

IP

3X(4X)

3X(4X)

3X(4X)

Rated current

Schneider Electric -Energy J. VAGNON 12/10/2010

74

PIX - Easy Access


Easy assembly
All assembly procedures can be
performed from the front.

Schneider Electric -Energy J. VAGNON 12/10/2010

75

PIX - Easy Access


Easy assembly
All assembly procedures can be
performed from the front.
Removable division plate and
cross member between circuit
breaker and cable connection
compartments allows enhanced
access

Schneider Electric -Energy J. VAGNON 12/10/2010

76

PIX - Easy Access


Easy assembly
All assembly procedures can be
performed from the front.
Removable division plate and
cross member between circuit
breaker and cable connection
compartments allows enhanced
access
Cable compartment easily
accessible and spacious,
facilitating cable connection.

Schneider Electric -Energy J. VAGNON 12/10/2010

77

PIX - Easy Access


Easy assembly
All assembly procedures can be
performed from the front.
Removable division plate and
cross member between circuit
breaker and cable connection
compartments allows enhanced
access
Cable compartment easily
accessible and spacious,
facilitating cable connection.
In addition to the top covers
removable bus bar partitions allow
full installation from the front

Schneider Electric -Energy J. VAGNON 12/10/2010

78

PIX Switch disconnector


Switch disconnector

LTRI 5
Schneider Electric -Energy J. VAGNON 12/10/2010

79

PIX - Fused Contactor Trucks CVX


SF6 contactor

GFX
Up to 12kV

Schneider Electric -Energy J. VAGNON 12/10/2010

Vacuum contactor

CVX 12
up to 12kV

<

back
80

PIX Family overview

PIX Family
PIX Standard
PIX Compact
PIX High
PIX Motor Control Center

Schneider Electric -Energy J. VAGNON 12/10/2010

81

PIX Compact Scope and Definition


PIX Compact
Partition class : PM
Loss in service continuity cat. : LSC2B
Segment : Utilities and light industries
Market: Worldwide (except ANSI, GB)
Common size between 12kV and 17.5kV
Up to 31.5kA and 2500A
Internal arc classification :
IAC AFLR 31.5 kA 1s

A cubicle designed to suit


volume market at the right price
Schneider Electric -Energy J. VAGNON 12/10/2010

82

PIX Compact
Technical Data with Vacuum Circuit Breaker
Rated voltage

kV

12

17.5

Rated frequency withstand voltage

kV

28

38

Rated impulse withstand voltage (BIL)

kV

75

95

Rated frequency

Hz

50/60

50/60

up to A

2500

2500

Rated peak current

kA

82

82

Rated short time current (1s - 3s)

kA

31,5

31,5

Internal arc fault tested (1s)

kA

31,5

31,5

Degree of protection

IP

3X(4X)*

Rated current

3X(4X)*

*IP41 in option
Schneider Electric -Energy J. VAGNON 12/10/2010

83

PIX compact - Compartment description


1 Busbar compartment

2 Low-voltage cabinet
1

3 Withdrawable circuit breaker


module with HVX-Compact
3

4 Cable compartment

Schneider Electric -Energy J. VAGNON 12/10/2010

84

PIX Compact - Easy and Safe Operation


Safe operation
Improved door opening mechanism
Ergonomic front only operation
latest industrial design
All mechanical operation can
be done with doors closed
Mechanical indication
for all switching positions
High operator safety completely integrated
interlocking system
Three clearly identified
functional areas

Schneider Electric -Energy J. VAGNON 12/10/2010

85

PIX Compact Dimensions with Vacuum Circuit Breaker


Same dimension in 12 and 17.5 kV
Rated voltage
Height (Basic cubicle)
Depth
Width
Heigth of low-voltage cabinet
Complete height with low-voltage cabinet

kV
mm
mm
mm
mm
mm

12/17,5
1950
1550 / 1800*
600 / 800
standard 735 mm
2300 mm

* 1800 mm (extended depth) for specific options as 2 cable CTs and/or Busbar CT

Schneider Electric -Energy J. VAGNON 12/10/2010

86

PIX Compact
Optimized rack-in mechanism

No need for long handle to


rack-in the circuit breaker

Schneider Electric -Energy J. VAGNON 12/10/2010

87

Main differences between PIX and PIX Compact


PIX

PIX Compact

Up to 40 kA at 17,5 kV

Up to 31,5 kA at 17,5 kV

Up to 4000 A

Up to 2500 A

Slim PIX-MCC (400 mm) associated


for 7,2 kV motors application

CVX-X will be available in phase C only in


600 mm width
PIX Compact MCC (400mm) to follow after
phase C

Rear access cable option


No T-off CT

No rear access cable


Busbar CT and T-off CT
Isolatable circuit VT with cover closed

SF6 and vacuum CB or Contactor

Simplified MV door operating mechanism

Vacuum circuit breakers/contactors only


Long crank handle to rack in and out
the CB
Simple crank handle to rack in and out the
CB
IP4X without derating
2500 A in 800 mm
Schneider Electric -Energy J. VAGNON 12/10/2010

88

PIX Compact
Truck with Vacuum Circuit Breaker HVX Compact
Up to 1250A

Up to 2500 A

Two cubicle width 600mm and 800mm  Two CB for the range
Standard = IEC + GOST + 50/60Hz
Open pole design
Range optimised for 12kV and use at 17.5kV with additional insulation
material

2 new VCBs based on standard components


Schneider Electric -Energy J. VAGNON 12/10/2010

<

back
89

PIX Family overview

PIX Family
PIX Standard
PIX Compact
PIX High
PIX Motor Control Center

Schneider Electric -Energy J. VAGNON 12/10/2010

90

PIX High - Definition


PIX High

Developed for high rating


Same architecture as PIX
Fitted with :
HVX Vacuum circuit breaker
Back to wall design
Up to 17,5kV

50kA, 4000/5000A

CB 3150A with natural cooling


CB 4000A with forced cooling enhanced
5000A design
Generator switching to IEEE C37.013

Available with Is Limiter

PIX High for high level of


performance
Schneider Electric -Energy J. VAGNON 12/10/2010

91

PIX High - Regarding IEC 62271-200

PIX High was developed and tested


according to IEC 62271-200
Classification according IEC 62271200
Partition class : PM
Loss in service continuity cat. : LSC2B

IAC
AFL(R) 50kA 1s

Internal arc classification :

All operations made from the


front of the unit

Optimum operator safety


Schneider Electric -Energy J. VAGNON 12/10/2010

92

PIX-High Rating
Technical data in accordance to IEC 62271-200

Rated voltage

kV

12

17.5

Rated impulse withstand voltage (BIL)

kVp

75

95

Rated frequency

Hz

50/60

50/60

Rated current of busbar

up to A

5000

5000

Rated current of feeder

up to A

5000

5000

kA

50 (3s)

50 (3s)

kAp

125

125

kA

50 (1s)

50 (1s)

Rated short time withstand current


Rated peak current
Internal Arc Classification (IAC) AFL

Schneider Electric -Energy J. VAGNON 12/10/2010

93

PIX-High Rating - Description of Compartments


1 Busbar compartment
1

2 Low-voltage cabinet
3 Withdrawable circuit breaker
module with HVX

4 Cable compartment
4

Schneider Electric -Energy J. VAGNON 12/10/2010

94

PIX High - Dimensions

Height
Depth
Width

2330 mm (w/o extensions)


1490 mm
800 mm and 1000 mm
H

Width depends on feeder currents:


1250 A
800 mm
2500 A
800 mm
3150 A
1000 mm
4000 A
1000 mm
5000 A
1000 mm

Schneider Electric -Energy J. VAGNON 12/10/2010

95

PIX High - Main Differentiators


No Ventilation openings at the front of the unit.
Compact dimensions 2500A in 800mm wide cubicle
Single point operation of the circuit breaker compartment
ensures safety
Produced (Customized) in PDS units worldwide
Fully designed and tested to IEC62271-200 IAC for 1 Second
Many solutions for cabling/connections

Schneider Electric -Energy J. VAGNON 12/10/2010

<

back
96

PIX Family overview

PIX Family
PIX Standard
PIX Compact
PIX High
PIX Motor Control Center

Schneider Electric -Energy J. VAGNON 12/10/2010

97

PIX Motor Control Center - Definition


PIX MCC

Develop for MCC application


Fully compatible with PIX and PIX High
Fitted with CVX 7 Fused Vacuum contactor
Back to wall design
Optimized with GEMSTART
Slimline 400mm width
Up to 7.2kV, 40kA, 315A (with PIX)
7.2kV, 50kA, 315A (with PIX High)
developed and tested according to IEC
62271-200
Loss in service continuity cat. : LSC2B-PM
Internal arc classification

40kA 1s for PIX MCC 40


IAC AFL 50kA 1s for PIX MCC 50

IAC AFLR

Fused vacuum contactor


Motor Control Center
Schneider Electric -Energy J. VAGNON 12/10/2010

98

PIX Motor Control Center


Technical data in accordance to IEC 62271-200
PIX MCC

PIX MCC

Rated frequency

Hz

50/60*

Degree of protection, external


(optional)

IP

3X
(4X)

3X
(4X)

Degree of protection btw. compartments

IP

3X

3X

Degree of protection with open door

IP

2X

2X

Internal Arc Classification (IAC) AFLR

kA**

40 (1s)

50 (1s)

PM

PM

1,000,000

1,000,000

Partition class
Mechanical switching cycles C/O

50/60*

* No test report for 60Hz


** The internal arc withstand values on the load side (feeder)
is limited by the properties of the fuses.
Schneider Electric -Energy J. VAGNON 12/10/2010

99

PIX Motor Control Center


Technical data in accordance to IEC 62271-200
PIX MCC

PIX MCC

3.6

7.2*

Rated voltage

kV

Power frequency withstand

kV

Impulse withstand voltage (BIL)

kV

40

60

A max.

400

400

Maximum motor rating

kW

1400

2700

Maximum transformer rating

kVA

1600

3100

Maximum capacitor bank rating

kVAr

1300

1700

Rated current contactor (AC4)

10(16)**

20(32)**

* On request: 12 kV version with 60 kV BIL


** Optional request (China)
Schneider Electric -Energy J. VAGNON 12/10/2010

100

PIX Motor Control Center


Technical data in accordance to IEC 62271-200
PIX MCC

PIX MCC

Rated voltage

kV

3.6

7.2

Maximum motor rating

kW

1500

3000

430(292)

400(270)

kVA

1600

3100

Max. fuse current transformers

430(268)

400(250)

Maximum capacitor bank rating

kVAr

1300

1700

400(240)

250(220)

Max. fuse (motor current)


Maximum transformer rating

Max. fuse current capacitor banks


(one voltage level higher selected)

Schneider Electric -Energy J. VAGNON 12/10/2010

101

PIX Motor Control Center - Dimensions

PIX MCC

up to 40kA

for 50kA

Height

mm

2130

2330

Depth
(w. door)

mm

1405

1490

Width

mm

400

400

400

Space saving slimline design


Schneider Electric -Energy J. VAGNON 12/10/2010

102

PIX Motor Control Center - Description of


compartments
1 Low-voltage
compartment

2 Busbar
compartment
3 Compartment with
CVX vacuum
contactor on truck

4 Cable compartment
with ring core CTs

Metal enclosed with


4 metallic compartments
Schneider Electric -Energy J. VAGNON 12/10/2010

103

PIX Motor Control Center - Vacuum Contactor


Fused Vacuum contactor

Fitted with electronic control card


Mechanical latched or Magnetically held
Fused DIN 442mm or BS 403mm
Auxiliary VT in option

CVX 7

Schneider Electric -Energy J. VAGNON 12/10/2010

104

PIX Motor Control Center - Gemstart


Motor Control GEMSTART 5, Version 5.4
Monitoring
Control
Protection
Measurements
Serial communications
GEMSTART 5
5.1 for LV monitoring
5.3 for LV motors
5.3 for MV motors

THE standard in O&G


Schneider Electric -Energy J. VAGNON 12/10/2010

<

back
105

Switchgear Control
GEMSTART 5 & GEMVIEW

Class leading Intelligent Motor Control


for Medium Voltage applications

- GEMSTART 5, Version 5.4

Schneider Electric -Energy J. VAGNON 12/10/2010

107

Types of equipment
Designed for both Galaxis & PIX MCC
Modular for simple LV or complex MV applications

Schneider Electric -Energy J. VAGNON 12/10/2010

108

GEMSTART 5
Motor Control GEMSTART 5
Monitoring
Control
Protection
Measurements
Serial communications
GEMSTART 5
5.1 for LV monitoring
5.3 for LV Motors

5.4 for MV Motors


Schneider Electric -Energy J. VAGNON 12/10/2010

109

GEMSTART 5
GEMSTART 5

Unique separate LCD display

DIN-rail mounting Power Module

- with 7 rows/ 11 variables

- with integral current sensing

- LED status indication


- RS232 interface
Schneider Electric -Energy J. VAGNON 12/10/2010

Unique to PIX MCC


110

Clients
Industry Types
Our clients are industry leaders - world-wide

 Conoco Philips
 Exxon
 Chevron
 Total
 GASCO
 ADCO
 Shell
 PREEM
 Statoil
 Petrogal

Schneider Electric -Energy J. VAGNON 12/10/2010

 BHP
 BP
 Lasmo
 Diversey Lever
 Kemira
 SIDMAR
 Aventis
 Courtaulds
 Rhodia
 Corus
 Kimberley Clarke

111

Potential Starter Components


Gemstart 5 will reduce project management & maintenance costs

Conventional
1 Motor Protection relay eg MiCOM P225
2 Push Buttons (Start, Trip)
4 Lamps (Running, Stop, Overload Trip,
Earth Fault Trip)
1 Manual/Auto Selector Switch
1 Ammeter (With Max. Demand Indicator)
1 KwHr Meter
1 Operations Counter
1 Hours Run Counter
2
Interposing Relays
3
1 Pneumatic timer

Schneider Electric -Energy J. VAGNON 12/10/2010

Gemstart 5
1 GEMSTART Power Block
1 GEMSTART Display Module

112

Gemstart 5.4 Block diagram


CURRENT
CURRENT
CURRENT
monitoring
monitoring
monitoring

START
STOP

VOLTAGE
DETECTION

Earth Fault
Monitoring
Protection

PLANT TRIP
INTERLOCK

SERIAL LINK
Service Pos
PAMM

Isolated Pos
Earthed

Communications

Run Confirm
Start Confirm
Control
HIGH TEMP
Monitoring

CONTACTOR
Star Point

Schneider Electric -Energy J. VAGNON 12/10/2010

CONTACTOR
Starting

CONTACTOR
Running

REMOTE
SIGNAL

113

GEMSTART 5
Optional modules
PAMM (Plant Associated Memory Module)
non-volatile memory - no battery,
allows extremely fast replacement,
fully self-booting - error free, prevents
addressing errors, patented design.
RTD-Module
with 6 temperature sensing
inputs for PT100 sensors and
4 additional multi-voltage inputs
Input-Module
with 4 multi-voltage inputs.
both modules can be easily connected
by a simple RJ 45 plug-in connection,
to the main body.
Schneider Electric -Energy J. VAGNON 12/10/2010

114

GEMSTART 5
GEMSTART 5, ANSI/IEEE protection functions
ANSI/IEEE Description
14

Under speed - Speed switch

27

Under voltage

30

Annunciator - display of faults

37

Undercurrent / Under power

46

Reverse phase current / phase balance

48

Incomplete sequence - motor start

49

Thermal overload

50

Instantaneous overcurrent

50N

Instantaneous earth fault

50S

Start overcurrent

51

Time overcurrent

51LR

Locked rotor

55

Power factor

59

Over voltage

66

Notching or jogging - No. of starts/inch

74

Alarm relay

79

Motor Reclosing

86

Locking out relay - use of output 3


PTC Thermistor monitoring & protection

Schneider Electric -Energy J. VAGNON 12/10/2010

5.3

5.4







































115

DNF7
Air-insulated Switchgear up to 40.5 kV

DNF7 - Description
Basic description :

Universal and International solution for


withdrawable air insulated switchgear, using both
vacuum or SF6 Circuit breaker
Universal application: Utilities, industry
Developed according to the IEC and GB standard

Key customer benefits :

Ideal to convey high current load


Fully interlocked and comprehensive operation
from the front, all operation possible by closed
door
IP4X as standard

Main characteristics and option list :

Ratings up to 40.5

kV / 2500 A / 31.5 kA

3150 A on request with forced cooling

Fitted with new HVX embedded pole or SF6 circuit


breaker

IAC AFLR 31,5 kA / 1s


Schneider Electric -Energy J. VAGNON 12/10/2010

117

DNF7 - Design
AREVA T&D's DNF7 cubicle has been designed with operator safety
as the number one priority.
INTERNAL ARC CLASSIFICATION (IAC) AFLR 31,5 kA / 1s
ALL OPERATIONS WITH DOORS CLOSED
INGRESS PROTECTION : IP 4X AS STANDARD
CLEAR, VISIBLE SWITCHING DEVICES
Inspection windows for both breakers and cable compartments This
allows the positions of the withdrawable unit, earthing switch and the
situation of the cable connection to be easily observed
COMPLETE SET OF INTERLOCKS
All necessary positive interlocks are installed according to IEC standards

Operator safety first


Schneider Electric -Energy J. VAGNON 12/10/2010

118

DNF7 - Technical characteristics


Unit
Rated voltage

kV

36 / 40.5

Rated frequency

Hz

50/60

Rated current

1250/1600/2000/2500**/3150*

Rated lightning impulse withstand voltage

kVp

170 / 185

Rated power frequency withstand voltage

kVrms

95

Rated short circuit breaking current

kA

31.5

Internal Arc classification A FLR

kA

31.5 / 1s

Rated shortshort-time withstand current (4s)

kA

31.5

Rated peak value withstand current

kA

82

Ingress protection degree


Overall dimensions (w x h x d)

Enclosure IP4X , Compartment IP2X


mm

1200x2400x2500

* With forced cooling (on request)


** 2500 A with vacuum CB and 2000 A with SF6 CB

Schneider Electric -Energy J. VAGNON 12/10/2010

119

DNF7 - Dimensions

2500 A in 1200 mm width natural cooling


Schneider Electric -Energy J. VAGNON 12/10/2010

120

DNF7 - Components
DNF7 can be fitted either with our vacuum circuit breaker HVX or our standard
range of SF6 FP circuit breaker.

SF6 Circuit Breakers


DNF7 uses our proven range of SF6 circuit
breaker with thermo puffing technology,
installed in thousands of MV switchgear
worldwide.

Embedded Vacuum Interrupter


A new concept of encapsulation using solid
insulation, makes vacuum interrupters insensitive to
any adverse environmental conditions.
Creepage distance exceeds 20 kV per mm and
partial discharge is less than 5 pc, in accordance
with the latest IEC standards.

Vacuum or SF6 switching, it's up to you.


Schneider Electric -Energy J. VAGNON 12/10/2010

<

121

back

DNF7 - Middle rolling trolley


DNF7 is designed for cassette
type withdrawable circuit
breakers, which is the current
state of the art for MV panels, but
unique at this level of voltage.

..\AMS integration
R&D\AMS40_5-Move_in.MPG
Totally adjustable service trolley

Unique design
Schneider Electric -Energy J. VAGNON 12/10/2010

122

DNF7 - Floor rolling trolley

An optional floor rolling trolley is available DNF7


Schneider Electric -Energy J. VAGNON 12/10/2010

123

DNF7- Floor rolling trolley

Schneider Electric -Energy J. VAGNON 12/10/2010

124

DNF7 - Floor rolling trolley Circuit breaker

Schneider Electric -Energy J. VAGNON 12/10/2010

125

IP 41 ACM Design Proposal

Still Proposal state: Analysis not yet finalized (121mm / Flaps ? Temp. Rise ?)
Schneider Electric -Energy J. VAGNON 12/10/2010

126

DNF7 Vattenfall
48 kV 1250 Amps 20kA

DNF7 Vattenfall

All Switching Test Successful

Internal arc test successful in April


Schneider Electric -Energy J. VAGNON 12/10/2010

128

DNF7 Vattenfall

Equipment for IAC with Internal arc duct Tunnel

Tested at 31.5 kA / 1s
Schneider Electric -Energy J. VAGNON 12/10/2010

<

129
back

Gas-insulated switchgear
for Primary Distribution

Gas-Insulated Switchgear
Electrical Distribution Network
Secondary Distribution

Substations
MV/LV

Primary Distribution

Distribution
substations MV

Substations HV/MV

Power Plants

WI

Single-/Double busbar

GHA/WS

Single-/Double busbar

GMA
Single-/Double busbar

FBX

Schneider Electric -Energy J. VAGNON 12/10/2010

142

Rated short circuit current in kA

Gas-insulated switchgear
40
35
30
25
WI
20

GHA
WS

15
GMA

10

12

24

36

40.5

52

Rated voltage in kV

Schneider Electric -Energy J. VAGNON 12/10/2010

>

143

GMA

Gas-insulated Switchgear GMA


The switchgear for high
 economical and
 ecological
requirements.










plug and go live system


ready for connection-straight
from the crane hook
space-saving, compact design
vacuum circuit breaker
highly versatile
user-friendly
long service life
enclosed system
no gas handling during
installation on site

Schneider Electric -Energy J. VAGNON 12/10/2010

145

Gas-insulated Switchgear GMA


Ready for connection Straight from the crane hook

Schneider Electric -Energy J. VAGNON 12/10/2010

146

Gas-insulated Switchgear GMA


Functional Switchgear
GIS range

Circuit-Breaker

Switchdisconnector

FBX

FBX

GMA

GHA
SBB/DBB

GMA

GHA

WSA
WSB

WS

WIA
WIB

WI

Schneider Electric -Energy J. VAGNON 12/10/2010

Switch disconnectorfuse combination

147

Gas-insulated Switchgear GMA


Function Unit Circuit Breaker 630 A
Low-voltage
cabinet
Instrument niche
Operating
panel
Cover for
cable area

Busbar
Disconnector
Vacuum circuit
breaker
Earthing switch
Current
transformer

Width 450 mm (without voltage transformer) even smaller than secondary products
 Width 600 mm (with voltage transformer)


Schneider Electric -Energy J. VAGNON 12/10/2010

148

Gas-insulated Switchgear GMA


Dimensions
Types

CB

T1

Components set

Dimensions (mm)
Height Depth
Width

630 A
Disconnector, vacuum 1000 A
CB, earthing switch
1250 A
Switch-disconnector
+ earthing switch

800/860

450/600

1000

600

800

450

2100

Switch-disconnector fuse
combination
+ earthing switch

Schneider Electric -Energy J. VAGNON 12/10/2010

149

Gas-insulated Switchgear GMA


Heights Profile of Circuit Breaker Unit
600

2100
1500

680

800




Width 450 mm (without outgoing VT)


Width 600 mm (with outgoing VT)

Schneider Electric -Energy J. VAGNON 12/10/2010

150

Gas-insulated Switchgear GMA


GMA-Modules
Examples for arrangement of modules
A) All functional units up to 630 A have 450 mm unit width

3x 450

2x 450

4x 450

B) Mixture of functional units with 450 mm and 600 mm unit width

3x 450

600

Schneider Electric -Energy J. VAGNON 12/10/2010

600

600

2x 450

151

Gas-insulated Switchgear GMA


Busbar Connection between two Modules

Module left

Module right

Interface between feeders and modules gas-insulated


Schneider Electric -Energy J. VAGNON 12/10/2010

<

back
152

Gas-insulated Switchgear GMA


Environmental correct gas-compartment technology

Graph
with
valves

Manometer
per
module

The manometers are general temperature compensated

Decentralized monitoring of gas compartments


Schneider Electric -Energy J. VAGNON 12/10/2010

153

Gas-insulated Switchgear GMA


Environmental Aspects


Integrated recovery valve




At the end of lifetime the SF6 will be feed to the recycle


process (SF6-Recovery)

No factory-special tool for gas extraction necessary

<

back

Schneider Electric -Energy J. VAGNON 12/10/2010

154

GHA
Gas insulated switchgear and
controlgear with vacuum circuit
breaker up to 40.5 kV

GIS Circuit - Breaker Switchgear Series GHA


GIS circuit-breaker switchgear up to 40.5 kV
GHA the switchgear with B-link
Considers current environmental issues: No gas handling at
site
Simple and safe
switchgear concept (full IAC)
Vacuum circuit breaker
User-friendly operator
interface
Low life cycle costs
A great variety of cable
connection options (IC and OC)
Straightforward operations management
Schneider Electric -Energy J. VAGNON 12/10/2010

156

GIS Circuit - Breaker Switchgear Series GHA


Ratings
Rated voltage

kV

12

17.5

24

36

40.5

Rated lightning impulse withstand voltage

kV

75

95

125

170

185

Rated power frequency withstand voltage

kV

28

38
(42)

50

70

80
(85)

Rated peak withstand current,

max.

kA

100

80

Rated short-time current,

max 3 s

kA

40

31.5

Rated current of busbar,

max.

2500

Rated current of outgoing feeders, max.


natural cooling

2500

Internal arc classification IAC AFL


or AFLR (option)

kA

Schneider Electric -Energy J. VAGNON 12/10/2010

40

31.5

Duration: 1 second
157

GIS Circuit - Breaker Switchgear Series GHA


Single and double busbar GHA
1.

Circuit-breaker compartement
with vacuum CB

2.

2.
3.

2.
8.

2. 3.

Busbar compartement
with busbars and
isolating/earthing switch (upper
system) respectively isolating
switch (rear system)

8.

3.
4.

B-link
Operating panel
with drives

5.

1.
4. 3.

1.

with cable connectors and


toroidal-core current
transformers

4.
6.

5.

5.
7.

6.

Voltage transformers
(pluggable) with HV
disconnection/earhting device

7.

6.

Outgoing feeder block

7.

Cable connection
compartment
metal enclosed

8.

Low-voltage cabinet
(removable)

Single busbar
Schneider Electric -Energy J. VAGNON 12/10/2010

Double busbar
158

GIS Circuit - Breaker Switchgear Series GHA


Busbar connections B-link (1)
Current environmental issues to minimize
SF6 emissions:
No gas handling outside of the manufacturer's
site for
erection
extensions
disassembly of panels
dismantling at the end of product-life

Rapid and safe on-site assembly


Single-pole insulation of busbar connections (Busbar-link) through robust
and durable insulator of silicone rubber
Earthed and safety against contact voltage

B-link
Schneider Electric -Energy J. VAGNON 12/10/2010

Busbar-link
159

GIS Circuit - Breaker Switchgear Series GHA


Busbar connections B-link (2)
B-link main components
Left side of panel
End cap,
right-hand
(controlled and
externally
earthed)

End cap,
left-hand
(controlled,
and externally
earthed)

Busbar,
left-hand
clamping piece
(can be actuated)
Busbar, right-hand
(simulation)

Schneider Electric -Energy J. VAGNON 12/10/2010

Silicone sleeve
(controlled and
externally
earthed)

Right side
End cap
160

GIS Circuit - Breaker Switchgear Series GHA


Busbar connections B-link
B-link consists of very few
simple and robust
components per conductor
Only 1 insulating sleeve with only
2 live joints (arrangement tested for
40.5 kV, BIL 185 kV)
1 screw-type contact
type-tested with 40 kA (3s) and
peak current 104 kA

Adjacent panels are flange-mounted


under visual
supervision (you see what you do)
Busbar sections capable of forming
isolating distances
The use of surge-proof
end caps

Rapid assembly of B-link  in a blink


Schneider Electric -Energy J. VAGNON 12/10/2010

view from back


(without cover)
161

GIS Circuit - Breaker Switchgear Series GHA


Cable connection system, outer cone-type (1)
Standardized outer cone, model C acc. to IEC 50181
Up to incl. 36 kV
630 A and 1250 A (reinforced design)
Standardized connection thread M16x2

Cable cross sect. up to 630 mm


Installation depth up to 3 cable screwtype plugs/ bushing
Cable screw-type plugs can be combined
with surge arresters
Outgoing feeder currents > 1250 A up
to 2500 A: 2 outer cone-type cable
bushings per conductor
up to 2x3 cable connectors per bushing.
panel width
800 mm (> 1250 A up to 2000 A)
900 mm (2500 A)
Schneider Electric -Energy J. VAGNON 12/10/2010

162

GIS Circuit - Breaker Switchgear Series GHA


Cable connection system - inner cone up to incl. 40.5 kV
Standardized inner-cone parts acc. to EN 50181
Terminal type 1: 630 A
Terminal type 2: 800 A
Terminal type 3: 1250 A

Up to 4 inner cone cable plugs /


inner cone bushing
Cable cross sect. up to 630 mm
Special solution for insulated
busbar system 2500 A: Inner cone
bushings size 4
Number and terminal type of the inner
cone parts must be defined on
ordering the switchgear

<

back

Schneider Electric -Energy J. VAGNON 12/10/2010

163

Make the most of your energy*

*Tirez le meilleur de votre nergie


Schneider Electric -Energy J. VAGNON 12/10/2010