T ECHNICAL S PECIFICATIONS O F
33 KV XLPE C U C ABLE (300 mm2)
7.1
GENERAL:
This section of the document includes the design, manufacture, tes ting & inspection of 33 KV
XLPE Insulated Copper Cable (300 mm 2 ) as specified.
7.2
CLIMATE DATA:
33 KV XLPE Insulated Copper Cable (300 mm 2 ) to be supplied against this tender shall be
suitable for satis factory use under the following climatic conditions:
Climate
Maximum Temperature
400 C
Minimum Temperature
030 C
300 C
Relative humidity
50-100%
75%
3454 mm
80 days/ year
300 meters
Moderately polluted
Cable as specified will be installed in tropical locations and in a hot humid environment wi th
presence of the insects and vermin. The information is given as a guide for Tender and no
responsibility for its accuracy will be accepted, nor will any claim based on the above be
entertai ned.
7.3
SYSTEM PARTICULARS :
SL.
NO.
1.
SYSTEM CHARACTERISTICS
VOLTAGE LEVEL
132
33
11
145
50
RST
36
50
RST
12
50
RST
Solid
6000
Solid
1500
Solid
381
650
170
75
(Voltage Class)
10.
Solid
7.4
C.m/W
C
C
C
m
mm
mm
1.5
30
40
90
1.0
Trefoil touching
850
Solid
RCC Slab
7.5
STANDARDS:
The cable as specified in this Section shall be conforming to the latest edition of the following
standards for operation under local ambient conditions. Design, Manufacture, Testing and Performance of the cable
shall be in accordance with the IEC 502-2, IEC 60 228, IEC 60 840 or equivalent International standards.
7.6
SPECIFICATIONS:
General
The manufacturing process shall be designed to eliminate irregularities like protrusions, voids and contamination etc.
to ensure the long-term reliability of the 33kV XLPE Cu cable. The 33kV XLPE Cu cable covered in this specification
shall be manufactured by Triple extrusion and Gas curing process ensuring circularity and concentricity of the
extruded layers around the conductor and all three layers (conductor screen, XLPE insulation and insulation screen)
shall be extruded in simultaneous triple extrusion process. The details of manufacturing process and curing to be
adopted shall be mentioned clearly in the offer.
Raw materials used to manufacture the cable shall be of highest quality and it should meet material standards
mentioned in IEC 60 502-2. The materials shall be clean and packed in moisture and dust proof packing. Material
received by manufacturer should be checked/tested to ensure that it meets material specification.
Loading of the extruder in the manufacturing plant shall be performed entirely closed and dust proof environment.
Contamination shall be avoided by the use of a fully enclosed material handling system. The use of special means
like pressurised air etc. for transport of granules, as far as practicable, shall be avoided.
The cross linking, curing and cooling may be carried out in one operation and shall be a gas curing process under
high pressure to eliminate the formation of voids in the insulation and contaminants in the dielectric. Process
conditions such as curing and cooling temperatures, production speed etc. shall be closely monitored during
manufacture to ensure a good degree of cross-linking through the whole insulation.
The cable will be laid in underground in an area with highly moist soil so metal sheath of either lead or aluminium
shall be employed to act as moisture barrier layer.
Cable Construction
The 33kV XLPE Cable shall have stranded compacted round copper conductor, conductor screening with extruded
semi conducting thermosetting compound, with completely gas cured XLPE insulation, adequate insulation screening
consisting of extruded semi conducting thermosetting compound layer, taped with semi conducting water swellable
tape, extruded/welded corrugated Aluminium sheathed and overall extruded termite repellent black PE sheathed with
outer conducting layer.
Conductor
The conductor shall be stranded compacted round copper conductor complying the requirement of flexibility Class-2
of IEC 60 228. The wires shall be made of high conductivity copper and shall be stranded mid compacted. The
copper used for the conductor shall be of highest purity. The nominal area of conductor shall be 300 sq. mm.
The minimum number of wires in conductor shall be 37 and the maximum DC resistance of conductor shall be
0.0601 /KM at 20C.
Conductor Screen
The conductor screen shall consist of an extruded layer of thermosetting semi conducting compound and shall be
continuous and cover the whole surface of the conductor. The screen shall be firmly bonded to XLPE insulation. The
minimum thickness of conductor screen shall be 0.8 mm. (approx.)
A non-hygroscopic semi conducting tape may be applied over the conductor surface under extruded layer. The outer
surface of the conductor screen shall be circular and free from irregularities.
Insulation
The insulation shall be cross-linked polyethylene (XLPE). The insulation material shall comply with the requirement
as per IEC 60 502-2. The insulation shall be applied by extrusion and vulcanisation to form a compact homogenous
body free from micro voids and contaminants. The nominal thickness of insulation shall be 8.0 mm.
Insulation Screen
The insulation screen shall consist of an extruded layer of thermosetting semi conducting compound and shall be
continuous and cover the whole surface area of insulation. It shall be firmly bonded to the insulation.
The minimum thickness of insulation screen shall be 0.5 mm.
Longitudinal Water Barrier
The under sheath water barrier shall consist of a semi conducting moisture swelling layer covering the whole surface
area of the insulation screen. The barrier shall restrict longitudinal water penetration under the metallic sheath. The
minimum thickness of water swellable tape shall be 0.35 mm.
Metal Sheath
The metallic sheath shall be of extruded/welded Corrugated Aluminium as per relevant IEC 60 840.
The nominal thickness of Corrugated Aluminium sheath shall be 2.75 mm and shall be so designed to carry the
specified earth fault current of 40 KA for 1 second.
Outer sheath
The outer sheath shall consist of an extruded layer of black medium density polyethylene. The outer sheath shall be
of sufficient hardness to discourage termite attacks. The properties of outer sheath material shall be as per IEC 60
840. The nominal thickness of outer sheath shall be 2.4 mm.
7.7
The spacing between one set of marking and lie beginning of the next on the legend shall not exceed 300 mm.
In case of printed over a tape, the same shall be provided inside the cable.
4
7.8
7.9
Conductor examination
Measurement of electrical resistance of conductor
Measurement of thickness of insulation and non-metallic sheath
Measurement of thickness of metallic sheath
Measurement of overall cable diameter
Hot set test for XLPE insulation
Measurement of capacitance
Frequency of Tests
The above special (acceptance) tests shall be made on one length from each manufacturing series of the same type
size of cable, but shall be limited to not more than 10% of the number of lengths in any contract, rounded to upper
unity.
Type Tests
The following tests shall be included in the type tests (Electrical) Tests.
a)
b)
c)
d)
7.11
DO CUMENTATION:
The following documents are to be submitted along with the Tender; otherwise the bid will be rejected:
A. COMMERCIAL:
Tenderer shall be eligible as per ITT and they should submit Bid validity, Bid Bond, Bid Bond validity, Price
Schedule, Delivery Schedule, Authorisation of the signatory, Tender Submission Sheet, Tenderer Information
Sheet & Documentary evidence for establishing the Tenderers Qualifications, etc. and all other documents
including information related to rejection clause as per Tender Document.
B.
1)
2)
3)
TECHNICAL:
Guaranteed Technical Particulars (GTP) shall be properly filled up and signed by both Manufacturer & Tenderer;
Letter of authorization from the Manufacturers, in case, the Bidder is not the manufacturer, in prescribed Form;
2 (two) nos. of Manufacturer's Supply record for similar XLPE insulated Copper Cable (having cable size of 300
mm2 at 33 kV voltage grade) or nearer higher size within the last 5 (five) years from the date of opening in the
following format (The supply record covering one fourth of the tendered quantity in a single contract will be
considered only);
Sl.
No.
Contract.
no. & Date
Contract
Value
Description of
Material with
Quantity
Date of
Completion of
Supply
1.
2.
4) Satisfactory Performance Certificate from at least 2 (two) Electricity utility for similar XLPE insulated Copper
Cable (having cable size of 300 mm2 at 33 kV voltage grade) or nearer higher size within the last 5 (five) years
from the date of opening;
5) Type Test Reports for offered XLPE insulated Copper cable (300 mm2) from an independent testing Laboratory/
Institute as per relevant Standards (unless otherwise specified);
6) Bidder shall submit at least 1 (one) piece of offered type Cable (length shall be at least 1.5 Meter) as sample
along with their bid.
7) Local manufacturers, who have supplied the same offered item to BPDB within the last 5 (five) years from the
date of opening, need not to submit any Manufacturer's Supply Record, Satisfactory Performance Certificate &
Type Test report with the tender proposal. In that case, they have to submit one Satisfactory Performance
Certificate (within last three years) from Director, Purchase, BPDB, Dhaka, for the same offered item covering
25% of the tendered quantity in a single Contract.
6
7.12
7.13
No goods shall be packed, prepared for shipment/delivery unless it has been approved and written instructions have
been received from the Purchaser.
B. Post-Landing Inspection :
The Supplier shall inform the purchaser immediately after arrival of the goods at the designated store of BPDB (as
per delivery schedule). An Inspection team of BPDB shall perform the post-landing inspection in presence of
supplier's representative. The Supplier shall arrange the program of post-landing inspection. If any defect or damage
have been found at post-landing inspection, the defective or damaged materials/ goods shall be replaced by the
supplier at his own cost within the stipulated time.
The purchaser's right to inspect, test (where necessary) and reject the goods after delivery at the designated
stores of BPDB shall in no way be limited or waived by reason of the goods having previously been inspected,
tested and passed by the purchaser prior to the goods' delivery.
The Inspection team will check the physical conditions and quantity of the goods delivered. If necessary, the
inspection team will select the sample of good(s) on random sampling basis and sent the selected sample goods to
CERS, BPDB or BUET/ CUET/ KUET /RUET (as selected by the inspection team) to carryout the test(s)
as per
contract to confirm the conformity to the approved Technical Specifications, Guaranteed Technical
Particulars
(GTP), drawings and relevant standards. If the tested sample(s) fail to confirm the specifications in tests, the full
consignment will be rejected. All cost of testing of Materials/ Goods including carrying, loading, un-loading etc.
will be borne by the supplier.
SECTION 08
8.1
(To be filled up by the Manufacturer in Manufacturer's Letterhead Pad with appropriated data)
Sl. No.
Description
2
3
4
5.
VOLTAGE
Voltage between phases of three
Phase circuit
U
Umax
CORES
Number of Cores
CONDUCTOR
material
cross sectional area
Min. No. & Dia of wires
CONDUCTOR SCREEN
Material
Nominal Thickness
Diameter over screen
INSULATION
Material
Type of dry curing
Nominal Thickness
Diameter of over Insulation
CORE SCREEN
Material
Nominal Thickness
Diameter over screen
METAL SHEATH
Material
Nominal Thickness
External diameter at crest
Purity
BEDDING/BARRIER LAYER
Material
6.
7.
8.
9.
10.
11.
12.
13.
14.
Nominal Thickness
OUTER COVERING
Material
Minimum average thickness
COMPLETED CABLE
Overall diameter
Weight per metre
Maximum drum length
Unit
Purchasers
Requirement
1CX300 mm2 33 kV XLPE
Insulated Copper Cables
Shall be mentioned
Shall be mentioned
Performance, Design and
Testing shall be in
accordance to the BS, IEC,
BDS or equivalent
International standards.
kV
kV
33
36
No.
one
mm2
Nos./mm
mm
mm
semi-conducting XLPE
0.8
To be mentioned
mm
mm
XLPE
Inert gas
8.0
To be mentioned
mm
mm
semi-conducting XLPE
0.5
To be mentioned
mm
mm
%
mm
mm
mm
kg
m
46
4.1
500
Manufacturers
Particulars
10
Sl. No.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
Description
CABLE DRUMS
Material
Overall diameter
Width
Gross weight (with cable)
CONTINUOUS CURRENT
CARRYING CAPACITY
Based on the conditions specified:
One circuit
Two circuits
Three circuits
In Air
One circuit
PERMISSIBLE OVERLOAD
In Service Conditions
For a period of
MAXIMUM CONDUCTOR
TEMPERATURE
Laid direct in ground
Drawn into ducts
Erected in air
CONDUCTOR SHORT CIRCUIT
CURRENT
Carrying capacity for one second,
Cable load as above prior to Short
circuit and final conductor
Temperature of 250C`
METALLIC LAYER/SHEATH EARTH
FAULT CURRENT
Carrying capacity for one second,
Cable loaded as above prior to Earth
fault
MINIMUM RADIUS OF BEND
Around which cable can be laid
MAXIMUM DC RESISTANCE
Per km of cable at 20C
of conductor
of metallic layer
MAXIMUM AC RESISTANCE
Of conductor per km of cable at
Maximum conductor temperature
INSULATION RESISTANCE
Per km of cable per core
at 20C
at maximum rated temperature
EQUIVALENT STAR REACTANE
Per km of 3 phase circuit at
Nominal frequency
MAXIMUM ELECTROSTATIC
CAPACITANCE
Per Km of cable
MAXIMUM INDUCED VOLTAGE
On metallic layer/sheath
Under fault condition
Unit
Purchasers
Requirement
mm
m
kg
Steel
To be mentioned
To be mentioned
To be mentioned
A
A
A
551
454
395
661
%
Hours
To be mentioned
To be mentioned
C
C
C
90
90
90
KA
42.9
KA
m
40
20 times of overall diameter
of cable
ohm
ohm
0.0601
To be mentioned
ohm
0.079
Megohm
Megohm
400
40
Ohm/Km
0.132
0.256
To be mentioned
Manufacturers
Particulars
11
Sl. No.
28.
29.
30.
31.
Description
MAXIMUM CHARGING CURRENT
Per core per metre of cable at
Nominal voltage Uo
MAXIMUM DIELECTIC LOSS
Of cable per metre of 3 phase circuit
when laid direct in the ground at
nominal voltage Uo and normal
frequency at maximum conductor
Temperature
METALLIC SHEATH LOSS
Of cable per metre of 3 phase circuit,
At nominal voltage Uo, normal
frequency And at the specified
current rating
MAXIMUM PULLING TENSION
Unit
Purchasers
Requirement
mA
To be mentioned
W/m
0.27
W
kg
To be mentioned
2100 Kg
Manufacturers
Particulars
12
Description
Manufacture's name
Place of
Place of Testing
Manufacture
& Inspection
01
13
8.3 SCHEDULE OF
PROPOSED STANDARDS TO WHICH CABLES SHALL BE PROVIDED
The Bidder shall indicate the Standard to which the materials offered by him conforms to.
Should these standards differ from the specified Standard in any respect the Bidder shall detail the differences between
the proposed and specified Standard.
Item
No
Description
Standard
1.
14
SECTION 09
DRAWINGS
15