Académique Documents
Professionnel Documents
Culture Documents
Perturbations
Affecting the
Performance of
Laminar Flow in
Operating
Theatres
by
C Hartung and J Kugler, Hannover, Germany
Introduction
Measures to reduce germs in operating areas and thus entailing risks
of infection had already been taken in the last century. Only by the
beginning of this century was the indispensable reduction of airborne
particles enabled by technical progress, eg particle counters to
quantify the actual hygienic situation; air-conditioning; protecting
overpressure; filtering; and humidification. The next important step of
progress was achieved in 1965, when Whitcomb et al.1 introduced the
technology of clean rooms to hospitals. The number of airborne
particles was reduced to such low levels that the wound infection rate
for treatments in bone surgery was acceptable. During the period after
1965 Charnley2, Lidewell3 and Whyte et al.4 intensively studied the
transmission of airborne germs in operating rooms. These investigations resulted in the finding that hygienic safety was definitely
achieved if less than 10 CFU/m3 air was detected in the operating area.
Considering that an average level of 2000 CFU/m3 is normally detected
in rooms for unspecified use, the effectiveness of laminar flow systems
is quite obvious.
Problem
Laminar flow systems operate on the basis of displacement flow5.
Germ-free air passes through a dense-meshed tissue to achieve low
turbulence. Normally the air inlet is positioned directly above the
operating area. Generally, the low inlet velocity does not suffice to
achieve a penetration of the inlet jet into the operating area. A
stabilization of the inlet jet by an extremely high inlet velocity, as
realized in industrial clean-room technology, would reduce the
comfort of the operating team in an intolerable way. Therefore the
temperature of the inlet jet is reduced below average room
temperature and thus sinks down into the operating area on account
of its higher density. As well as by temperature and velocity of the inlet
air, the resultant flow in the operating area is perturbed by thermal
buoyancy and obstacles such as operating physicians and medical
personnel, operating lamps, and medico-technical devices.
Hence, before surgical treatment the air-conditioning system undergoes standard testing in order to ensure a sufficient stable inlet jet.
Two standards have to be followed in Germany: DIN 1946, Part 4
Requirements of Hospital Air-Conditioning6 and DIN 4799 Test
Requirement of Air-Conditioning7. The latter forms the basis of
hygienic rating of air-conditioning quality. If one compares the
idealization and simplicity of required test conditions with the
complexity of performing flow, doubts simply must arise as to whether
test flow conditions occur in reality at all.
Thus, the targets of the present investigation are
to demonstrate the effect of thermal buoyancy and obstacles on
displacement flow by simulation; and particularly
to detect breakdowns of the inlet jet on account of varying
operating constellations.
CONTENTS
89
Methods
Flow in operating rooms equipped with laminar flow systems develops
by forming two regions beneath the inlet: a core zone of low
turbulence from beneath the inlet to the operating area, and a
turbulent region in the rest of the room. The resulting flow process is
not at all simple, and requires turbulence modelling to simulate the
occurring constellations. Our present investigation is based on the socalled k model developed by Wilcox8. This model was especially
designed to simulate turbulent flow at low Reynolds numbers, as
occurring in operating theatres. The effect of heat sources is included
by Boussinesq-approximation. Mesh optimization proved that the
extension of the core zone of low turbulence strongly depends on
mesh resolution. If a coarse mesh has to be introduced, as in the case
of 3D simulations for restrictions in computer capacity, breakdowns of
the core zone are observed, which are obviously unrealistic. Hence, we
restrict our considerations to 2D simulations of the displacement flow,
meanwhile maintaining the necessary mesh density.
Figure 2 Scene 1 vector plot of flow velocity. The inlet air flushes the
operating area. Buoyancy-induced eddies only occur close by the
ventral side of both operators. Dark areas indicate areas of maximum
flow velocity, 0.3 m/s. Inlet air: Tinlet = 20.5C, vinlet = 0.19 m/s.
Results
CONTENTS
90
Figure 4 Response of relative vertical velocity vy/vinlet above table level on account of varying flow obstacles. Inlet air: Tinlet = 20.5C, vinlet =
0.19 m/s.
lowering of inlet velocity from 0.21 m/s to 0.17 m/s at varying inlet
temperatures between 18C and 22C affects the flow considerably.
Flow still remains stable. Below inlet velocities of 0.17 m/s flow stability
ceases. The fact that turbulent kinetic energy hardly alters in the
operating area proves that flow instability is not caused by a transition
from laminar to turbulent mode but by alterations of flow profiles
resulting in generation of large eddies and flow deviations. In the
remaining areas of the operating theatre eddies increase with increasing inlet velocity and difference between inlet air temperature and
averaged room temperature.
CONTENTS
91
Figure 6 Effect of inlet air temperature Tinlet on relative vertical velocity vy/vinlet at constant inlet air velocity vinlet = 0.19 m/s. Arrangement of
flow obstacles according to Figure 1.
Figure 7 Effect of inlet air velocity vinlet on relative vertical velocity vy/vinlet at constant inlet air temperature Tinlet = 20.5C. Arrangement of
flow obstacles according to Figure 1.
a stable displacement flow cannot perform at lower inlet
velocities. Supply to the operating area of germ-free air can then
no longer be guaranteed.
Obstacles (eg lamps, personnel and equipment) in the operating
area should be arranged symmetrically. Asymmetrical arrangement of
obstacles results in jet deflections and should be avoided. Heat sources
CONTENTS
92
References
1
5
6
7
8
Figure 8 Moving a lamp into the operating area causes constriction
and may lead to complete collapse of core flow on account of
inappropriate choice of operating parameters, such as inlet air: Tinlet
= 22C, vinlet = 0.15 m/s.
temperature. Thus, every operating room needs additional heating for
reasons of comfort. Laminar flow systems cannot be used stand-alone
to achieve both thermal comfort and hygienic safety.
Obstructing the operating area by lamps worsens flow conditions in
the operating area.
Hygienic quality increases with increasing dimensions of inlets.
Owing to operating restrictions in velocity as mentioned above,
however, larger inlets result in an increase of volume flow and
consequent energy expenditures. Thus an increased use of circulating
air is recommended. For reasons of personnel protection, however,
suction lines for anaesthetics and closed devices for anaesthesia must
still be provided.
Complementary investigations will elucidate the effects on flow in
the operating area by varying inlet dimensions and by an apron
surrounding the inlet. At present our findings are checked by experiments. Results of these will be presented at the conference.
CONTENTS