Vous êtes sur la page 1sur 20

DVP-1050030-02

ENGLISH

Thank you for choosing Delta DVP-SV. DVP-SV is a 28-point (16 input + 12 output) PLC
MPU, offering various instructions and with 16k steps program memory, able to connect
to all DVP-SS/SA/SX/SC/SV series extension models, including digital I/O (max. 512
points), analog modules (for A/D, D/A conversion and temperature measurement) and
all kinds of high-speed extension modules. 4 groups of high-speed (200kHz) pulse
output and 2 two-axis interpolation instructions satisfy all kinds of applications. DVP-SV
is small in size and easy to install.
a This instruction sheet only provides introductory information on electrical
specifications, general specifications, installation and wiring. For detalied infromation
on programming and intructions, please refer to DVP-PLC Application Manual:
Programming. For information about optional peripherals, please see individual
product instuction sheet or DVP-PLC Application Manual: Special Modules.
a This is an OPEN-TYPE device and therefore should be installed in an enclosure free
of airborne dust, humidity, electric shock and vibration. The enclosure should prevent
non-maintenance staff from operating the device (e.g. key or specific tools are
required to open the enclosure) in case danger and damage on the device may
occur.
a DO NOT connect input AC power supply to any of the I/O terminals; otherwise
serious damage may occur. Check all the wiring again before switching on the power.
Make sure the groud terminal
is correctly grounded in order to prevent
electromagnetic interference. DO NOT touch any internal when the power is switched
off.

Product Profile
1 Left-side module

9 POWER/RUN/BAT.LOW/ERROR indicator

connection port

10 Direct fastening hole

3 COM1(RS-232) receiving

communication (Rx) indicator

11 I/O terminal

4 COM2(RS-485) sending

communication (Tx) indicator

5 I/O indicator
6 RUN/STOP switch

12 COM1(RS-232)

7 VR0: M1178 enabled /D1178

program I/O
communication
port

corresponding value

2 Nameplate

14 COM2(RS-485)

communication port
(Master/Slave)

8 VR1: M1179 enabled/D1179

corresponding value

[ Figure 1 ]

13 DIN rail clip

16 3PIN removable terminal

(standard component)

18 I/O module

positioning hole

19 I/O module

connection port

20 Mounting slot

(35mm)
15 Power input port

17 Power input connection

cable (standard component)

-1-

21 I/O module fastening clip

[ Figure 2 ]

Electrical Specifications
Model

DVP28SV11R

Item

DVP28SV11T

Power supply
voltage

24VDC (-15% ~ 20%) (with counter-connection protection on the


polarity of DC input power)

Inrush current

Max. 2.2A@24VDC

Fuse capacity

2.5A/30VDC, Polyswitch

Power consumption

6W

Insulation resistance

> 5M (all I/O point-to-ground: 500VDC)

Noise immunity

ESD (IEC 61131-2, IEC 61000-4-2): 8kV Air Discharge


EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2kV, Digital I/O: 1kV,
Analog & Communication I/O: 1kV
Damped-Oscillatory Wave: Power Line: 1kV, Digital I/O: 1kV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m

Grounding

The diameter of grounding wire shall not be less than that of the wiring
terminal of the power. (When PLCs are in use at the same time, please
make sure every PLC is properly grounded.)

Operation / storage

Operation: 0C ~ 55C (temperature); 50 ~ 95% (humidity);


pollution degree 2
Storage: -25C ~ 70C (temperature); 5 ~ 95% (humidity)

Agency approvals

UL508
European community EMC Directive 89/336/EEC and Low Voltage
Directive 73/23/EEC

Vibration / shock
immunity

International standards: IEC61131-2, IEC 68-2-6 (TEST


Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)

Weight (g)

260

240

Input Point
24VDC single common port input

Spec.
Items

200kHz

Input No.

X0, X1, X4, X5

20kHz

10kHz

X10, X11, X14, X15

X6, X7, X12, X13,


X16, X17

Input voltage (10%)


Input impedance
Action level
Response
time

24VDC, 5mA
4.7k

3.3k

4.7k

OffOn

> 4mA (16.5V)

> 6mA (18.5V)

> 4mA (16.5V)

OnOff

< 1.5mA (8V)

< 2.2mA (8V)

< 1.5mA (8V)

OffOn

< 150ns

< 3.5s

< 8s

OnOff

< 3s

< 20s

< 60s

Filter time

Adjustable within 10 ~ 60ms by D1020, D1021 (Default: 10ms)


Output Point
Spec.

Items
Output No.

Transistor

Relay

High-speed

Low-speed
Y5, Y7, Y10
~ Y13

Y14 ~ Y17,
Y20 ~ #1

10kHz

1kHz

Y0 ~ Y7, Y10 ~ Y13

Y0 ~ Y4, Y6

Max. frequency

1Hz

200kHz

Working voltage

250VAC, < 30VDC

30VDC

1.5A/1 point (5A/COM)

0.3A/1 point @ 40C; When the output of


Y0, Y1, Y10 and Y11 is high-speed pulse,
Y0,Y1, Y10 and Y11 = 30mA

Max. load

Resistive

-2-

Output Point
Spec.

Max. load
Response
time

Transistor

Relay

Items

High-speed

Inductive

#2

Lamp

20WDC/100WAC

OffOn

1.5W (30VDC)

Approx. 10ms

OnOff

Low-speed
9W (30VDC)

0.2s

20s

<100s

0.2s

30s

<100s

#1: Please refer to I/O Terminal Layout for the max. X/Y No. on each model.
#2: Life curves
120VAC Resistive
30VDC Inductive(t=7ms)

3000
2000

240VAC Inductive(cos = 0.4)

Operation(X10 3)

1000

120VAC Inductive(cos =0.4)

500
300
200
100

30VDC
Inductive
(t=40ms)

50

Contact

0.1

0.2 0.3

0.5 0.7

2 Current(A)

[ Figure 3 ]

I/O Configuration
Model

Power

Input
Point

Type

Output
Point

Type

Relay

DVP28SV11R

24VDC

16

DC
(Sink Or
Source)

12

DVP28SV11T

Transistor

I/O configuration
Relay
S/S
X0
X1
X2
X3
X4
X5
X6
X7

C0
Y0
Y1
Y2

S/S
X10
X11
X12
X13
X14
X15
X16
X17

C2
Y6
Y7
Y10

C1
Y3
Y4
Y5

C3
Y11
Y12
Y13

Transistor
S/S
X0
X1
X2
X3
X4
X5
X6
X7

C0
Y0
Y1
C1
Y2
Y3
C2
Y4
Y5

S/S
X10
X11
X12
X13
X14
X15
X16
X17

C3
Y6
Y7
C4
Y10
Y11
Y12
Y13

90
3

109.4
101

70
53.2

Installation

[ Figure 4 ]

[ Figure 6 ]

Unit: mm

Please install the PLC in an enclosure with sufficient space around it to allow heat
dissipation. See [Figure 5].
Direct Mounting: Use M4 screw according to the dimension of the product.
DIN Rail Mounting: When mounting the PLC to 35mm DIN rail, be sure to use the
retaining clip to stop any side-to-side movement of the PLC and reduce the chance of
-3-

wires being loose. The retaining clip is at the bottom of the PLC. To secure the PLC to
DIN rail, pull down the clip, place it onto the rail and gently push it up. To remove the
PLC, pull the retaining clip down with a flat screwdriver and gently remove the PLC from
DIN rail. See [Figure 6].

Wiring
1. Use 22-16AWG (1.5mm) single or multiple core wire on
22-16AWG
I/O wiring terminals. See the figure in the right hand side
for its specification. PLC terminal screws should be
tightened to 1.90 kg-cm (1.65 in-lbs) and please use only
< 1.5mm
60/75C copper conductor.
2. DO NOT wire empty terminal. DO NOT place the I/O signal cable in the same wiring
circuit.
3. DO NOT drop tiny metallic conductor into the PLC while screwing and wiring. Tear
off the sticker on the heat dissipation hole for preventing alien substances from
dropping in, to ensure normal heat dissipation of the PLC.

Power Supply
The power input of DVP-SV is DC. When operating DVP-SV, note the following points:
1. The power is connected to two terminals, 24VDC and 0V, and the range of power is
20.4 ~ 28.8VDC. If the power voltage is less than 20.4VDC, the PLC will stop running,
all outputs go Off, and the ERROR indicator will start to blink continuously.
2. The power shutdown for less than 10ms will not affect the operation of the PLC.
However, the shutdown time that is too long or the drop of power voltage will stop the
operation of the PLC, and all outputs will go off. When the power returns to normal
status, the PLC will automatically resume the operation. (Please take care of the
latched auxiliary relays and registers inside the PLC when doing the programming).

Safety Wiring
Since DVP-SV is only compatible with DC power supply, Deltas power supply modules
(DVPPS01/DVPPS02) are the suitable power supplies for DVP-SV. We suggest you
install the protection circuit at the power supply terminal to protect DVPPS01 or
DVPPS02. See the figure below.

AC power supply:100 ~ 240VAC, 50/60Hz

10

Power indicator

Breaker

Emergency stop: This button cuts off the system power supply when accidental
emergency takes place.
Power supply circuit protection fuse (2A)
DC power supply output: 24VDC, 500mA
Digital I/O module
-4-

AC power supply load


DVPPS01/DVPPS02
DVP-PLC (main processing unit)

Input Point Wiring


There are 2 types of DC inputs, SINK and SOURCE. (See the example below. For
detailed point configuration, please refer to the specification of each model.)
DC Signal IN SINK mode
Input point loop equivalent circuit
+24V
24VDC
24G
S/S
X0

X1

[ Figure 8 ]

DC Signal IN SOURCE mode


Input point loop equivalent circuit
+24V
24VDC
24G
S/S
X0
X1

[ Figure 9 ]

Output Point Wiring


1. DVP-SV has two output modules, relay and transistor. Be aware of the connection of
shared terminals when wiring output terminals.
2. Output terminals, Y0, Y1, and Y2, of relay models use C0 common port; Y3, Y4, and
Y5 use C1 common port; Y6, Y7, and Y10 use C2 common port; Y11, Y12, and Y13
use C3 common port. See [Figure 10].

When the output points are enabled, their corresponding indicators on the front
panel will be on.
3. Output terminals, Y0 and Y1, of transistor models use C0 common port; Y2 and Y3
use C1 common port; Y4 and Y5 use C2 common port; Y6 and Y7 use C3 common
port; Y10, Y11, Y12 and Y13 use C4 common port. See [Figure 11].

4. Isolation circuit: The optical coupler is used to isolate signals between the circuit
inside PLC and input modules.
Relay (R) output circuit wiring

-5-

DC power supply

Emergency stop: Uses external switch

Fuse: Uses 5~10A fuse at the shared terminal of output contacts to protect the output circuit
Transient voltage suppressor (SB360 3A 60V): Extends the life span of contact.
1. Diode suppression of DC load: Used when in smaller power [Figure 13]
2. Diode + Zener suppression of DC load: Used when in larger power and frequent On/Off
[Figure 14]

Incandescent light (resistive load)

Neon indicator

AC power supply

Manually exclusive output: For example, Y3 and Y4 control the forward running and reverse
running of the motor, forming an interlock for the external circuit, together with the PLC
internal program, to ensure safe protection in case of any unexpected errors.
9

Absorber: Reduces the interference on AC load [Figure 15]

Transistor (T) output circuit wiring

-6-

DC power supply

Emergency stop

Circuit protection fuse

The output of the transistor model is open collector. If Y0/Y1 is set to pulse output, the
output current has to be bigger than 0.1A to ensure normal operation of the model.
1. Diode suppression: Used when in smaller power [Figure 18]
2. Diode + Zener suppression: Used when in larger power and frequent On/Off [Figure 19]
Manually exclusive output: For example, Y10 and Y11 control the forward running and
reverse running of the motor, forming an interlock for the external circuit, together with the
PLC internal program, to ensure safe protection in case of any unexpected errors.

BAT.LOW indicator
BAT.LOW indicator will be on when the battery is in low voltage. When this happens,
change the battery as soon as possible in case your program and data saved in the
latched area will be lost.
After the DC24V power is switched off, the data in the latched area will be stored in
SRAM memory and its power supplied by the rechargeable battery. Therefore, when the
battery is damaged or cannot be changed, the data in the program and latched area will
be lost. If you need to permanently save the data in the latched area in the program and
device D, please refer to Flash ROM permanently saved and recover mechanism as
stated below.
Permanently saved mechanism:
You can use WPLSoft (Options -> PLC<=>Flash) to indicate whether to permanently
store the data in the latched area in Flash ROM memory (the new indicated data will
replace all data previously saved in the memory).
Recover mechanism:
If the rechargeable battery is in low voltage, resulting in possible loss of data in the
program, the PLC will automatically restore the data in the latched area in the program
and device D of Flash ROM into SRAM memory (M1176 = On) next time when DC24V is
re-powered. The ERROR LED flashing will remind you that if the recorded program is
able to resume its execution. You only need to shut down and re-power the PLC once to
restart its operation (RUN).
1. The rechargeable lithium-ion battery in DVP-SV is mainly used on the latched
procedure and data storage.
2. The lithium-ion battery has been fully charged in the factory and is able to retain the
latched procedure and data storage for 12 months. If DVP-SV has not been powered
and used for more than 12 months, the battery will be out of power upon normal
consumption, and the procedure and data will be lost.
3. The lithium-ion battery has longer life span than ordinary battery; therefore there is
no need to change battery very frequently. You can charge the battery any time
without having to worry its chargeability will decrease. You can also recharge the
battery even when there is still power in the battery.
4. Please be aware of the date of manufacturing. The charged battery can sustain for
12 months from its date of manufacture. If you find that the BAT.LOW indicator stays
on after PLC is powered, it means the battery voltage is low and the battery is being
charged. DVP-SV has to remain on for more than 24 hours to fully charge the battery.
If the indicator turns from on to flash (every 1 second), it means that the battery
cannot be charged anymore. Please correctly process your data in time and send
the PLC back to Delta for changing a new battery.

Accuracy (month/second) of RTC


Temperature (C/F)

0 / 32

25 / 77

55 / 131

Max. inaccuracy (second)

-117

52

-132

-7-

DVP DVP-SV 28 16 + 12
PLC 16k steps SS/SA/SX/SC/SV
I/O 512
A/DD/A I/O 200kHz

a
DVP-PLC

DVP-PLC

a OPEN TYPE
/

1 [Figure 1] [Figure 2]
1

10

11

12 COM1RS-232

13 DIN

14 COM2RS-485Master/Slave
COM1RS-232Rx

I/O

COM2RS-485Tx

15

16 3PIN

RUNSTOP

17

VR0M1178 D1178

18 I/O

VR1M1179 D1179

19 I/O

20 DIN (35mm)

21 I/O

DVP28SV11R

DVP28SV11T

24VDC (-15% ~ 20%)

Max. 2.2A@24VDC

2.5A/30VDC (Polyswitch)

6W

> 5M 500VDC

ESD (IEC 61131-2, IEC 61000-4-2): 8kV Air Discharge


EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2kV, Digital I/O: 1kV,
Analog & Communication I/O: 1kV
Damped-Oscillatory Wave: Power Line: 1kV, Digital I/O: 1kV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m

PLC

0C ~ 55C50 ~ 95% 2
-25C ~ 70C5 ~ 95%

UL508
European community EMC Directive 89/336/EEC and Low Voltage
Directive 73/23/EEC

IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC


68-2-27 (TEST Ea)
-8-

DVP28SV11R

DVP28SV11T

260g

240g

24VDC

No.

200kHz

20kHz

10kHz

X0, X1, X4, X5

X10, X11, X14, X15

X6, X7, X12, X13,


X16, X17

24VDC, 5mA

10%
4.7k

3.3 k

4.7 k

OffOn

> 4mA (16.5V)

> 6mA (18.5V)

> 4mA (16.5V)

OnOff

< 1.5mA (8V)

< 2.2mA (8V)

< 1.5mA (8V)

OffOn

< 150ns

< 3.5s

< 8s

OnOff

< 3s

< 20s

< 60s

D1020 D1021 10 ~ 60 ms (10ms)

No.

Y0 ~ Y4, Y6

1Hz

200kHz

Y5, Y7, Y10


~ Y13

Y14 ~ Y17,
Y20 ~ #1

10kHz

1kHz

250VAC, < 30VDC

30VDC

1.5A/1 point (5A/COM)

0.3A/1 @ 40C Y0, Y1, Y10, Y11


Y0,Y1, Y10, Y11 = 30mA

#2

9W (30VDC)

20WDC/100WAC

1.5W (30VDC)

Y0 ~ Y7, Y10 ~ Y13

OffOn

10ms

OnOff

0.2s

20s

<100s

0.2s

30s

<100s

#1

#2 3 [Figure 3]

DVP28SV11R
DVP28SV11T

24VDC

16

(Sink or Source)

12

I/O

3 [Figure 4]mm
PLC PLC
3 [Figure 5]
M4
DIN 35mm DIN
I/O
3 [Figure 6] I/O

-9-


1. / 22-16AWG (1.5mm) 4
PLC 1.90 kg-cm (1.65 in-lbs) 60/75C
2.
3. PLC PLC

DVP-SV
1. 24VDC 0V 20.4 ~ 28.8VDC
20.4VDC PLC OffERROR LED
2. 10ms PLC
PLC OffPLC
PLC

DVP-SV DC Only
(DVPPS01/DVPPS02) DVP-SV DVPPS01/DVPPS02
4 [Figure 7]
1

100 ~ 240VAC, 50/60Hz

10

2A
24VDC500mA

DVPPS01/DVPPS02
DVP PLC

DC SINK SOURCE
5 [Figure 8][Figure 9]

1. DVP-SV PLC

2. Y0Y1Y2 C0 Y3Y4Y5 C1 Y6Y7


Y10 C2 Y11Y12Y13 C3 5 [Figure
10]
3. Y0Y1 C0 Y2Y3 C1 Y4Y5 C2
Y6Y7 C3 Y10Y11Y12Y13 C4
6 [Figure 11]
4. PLC
5 [Figure 12]
1

5 ~ 10A

1. DC 6 [Figure 13]
2. DC +Zener On/Off
6 [Figure 14]

- 10 -

Y3 Y4
PLC

6 [Figure 15]

LED

Y0

< 0.3A

C0

6 [Figure 17]
1

(Open Collector) Y0/Y1


0.1A
1. 6 [Figure 18]
2. +Zener On/Off 6 [Figure 19]

Y10 Y11
PLC

BAT.LOW
BAT.LOW
24V SRAM
SRAM
D
Flash ROM
WPLSoft -->
PLC<=>Flash D Flash
ROM Flash ROM

PLC Flash ROM D


SRAM
PLC (RUN)
1. DVP-28SV

2. 12
DVP-28SV 12

3.

4. 12 BAT.LOW
DVP-28SV 24
1
PLC

(C/F)

0/32

25/77

55/131

-117

52

-132

- 11 -

DVP DVP-SV 28 16 + 12
PLC 16k steps SS/SA/SX/SC/SV
I/O 512
A/DD/A I/O 200kHz

a
DVP-PLC

DVP-PLC

a (OPEN TYPE)

1 [Figure 1] [Figure 2]
1

10

11

12 COM1RS-232

13 DIN

14 COM2RS-485Master/Slave
COM1RS-232Rx

I/O

COM2RS-485)Tx

15

16 3PIN

RUNSTOP

17

VR0M1178 D1178

18 I/O

VR1M1179 D1179

19 I/O

20 DIN 35mm

21 I/O

DVP28SV11R

DVP28SV11T

24VDC (-15% ~ 20%)

Max. 2.2A@24VDC

2.5A/30VDC (Polyswitch)

6W

> 5M 500VDC

ESD (IEC 61131-2, IEC 61000-4-2): 8kV Air Discharge


EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2kV, Digital I/O: 1kV,
Analog & Communication I/O: 1kV
Damped-Oscillatory Wave: Power Line: 1kV, Digital I/O: 1kV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m

PLC

0C ~ 55C50 ~ 95% 2
-25C ~ 70C5 ~ 95%

UL508
European community EMC Directive 89/336/EEC and Low Voltage
Directive 73/23/EEC

IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC


68-2-27 (TEST Ea)
- 12 -

DVP28SV11R

DVP28SV11T

260g

240g

24VDC

No.

200kHz

20kHz

10kHz

X0, X1, X4, X5

X10, X11, X14, X15

X6, X7, X12, X13,


X16, X17

24VDC, 5mA

10%
4.7k

3.3k

4.7k

OffOn

> 4mA (16.5V)

> 6mA (18.5V)

> 4mA (16.5V)

OnOff

< 1.5mA (8V)

< 2.2mA (8V)

< 1.5mA (8V)

OffOn

< 150ns

< 3.5s

< 8s

OnOff

< 3s

< 20s

< 60s

D1020 D1021 10 ~ 60 ms (10ms)

No.

Y0 ~ Y7, Y10 ~ Y13

Y0 ~ Y4, Y6

Y5, Y7, Y10


~ Y13

Y14 ~ Y17,

1Hz

200kHz

10kHz

1kHz

Y20 ~ #1

250VAC, < 30VDC

30VDC

1.5A/1 point (5A/COM)

0.3A/1 @ 40C Y0, Y1, Y10, Y11


Y0,Y1, Y10, Y11 = 30mA

#2

9W (30VDC)

20WDC/100WAC

1.5W (30VDC)

OffOn

10ms

OnOff

0.2s

20s

<100s

0.2s

30s

<100s

#1

#2 3 [Figure 3]

DVP28SV11R
DVP28SV11T

24VDC

16

(Sink or Source)

12

I/O

3 [Figure 4]mm
PLC PLC
3 [Figure 5]
M4
DIN 35mm DIN
I/O
3 [Figure 6] I/O

- 13 -


1. / 22-16AWG (1.5mm) 4
PLC 1.90 kg-cm (1.65 in-lbs) 60/75C
2.
3. PLC PLC

DVP-SV
1. 24VDC 0V 20.4VDC ~ 28.8VDC
20.4VDC PLC OffERROR LED
2. 10ms PLC
PLC OffPLC
PLC

DVP-SV DC Only
(DVPPS01/DVPPS02) DVP-SV DVPPS01/DVPPS02
4 [Figure 7]
1

10

100 ~ 240VAC, 50/60Hz

2A
24VDC500mA

DVPPS01/DVPPS02
DVP PLC

DC DC
5 [Figure 8][Figure 9]

1. DVP-SV PLC

2. Y0Y1Y2 C0 Y3Y4Y5 C1 Y6Y7


Y10 C2 Y11Y12Y13 C3 5 [Figure
10]
3. Y0Y1 C0 Y2Y3 C1 Y4Y5 C2
Y6Y7 C3 Y10Y11Y12Y13 C4
6 [Figure 11]
4. PLC

5 [Figure 12]
1

5 ~ 10A

1. DC 6 [Figure 13]
2. DC +Zener On/Off 6

[Figure 14]
- 14 -

Y3 Y4
PLC

6 [Figure 15]

LED

Y0

< 0.3A

C0

6 [Figure17]
1

(Open Collector) Y0/Y1


0.1A
1. 7 [Figure 18]
2. +Zener On/Off 7 [Figure 19]

Y10 Y11
PLC

BAT.LOW
BAT.LOW
24V SRAM
SRAM
D
Flash ROM
WPLSoft -->
PLC<=>Flash D Flash
ROM Flash ROM

1
PLC Flash ROM D
SRAM
PLC (RUN)
1. DVP-28SV

2. 12
DVP-28SV 12

3.

4. 12 BAT.LOW
DVP-28SV 24

1
PLC

(C/F)

0/32

25/77

55/131

-117

52

-132
- 15 -

.......

TRKE

.........

Delta DVP-SV serisi rnleri setiiniz iin teekkrler. DVP-SV serisi PLClerin CPUda 16-giri
+ 12-k olmak zere toplam 28-nokta ve 16K program kapasitesi vardr. Farkl uygulamalar
gerekletirmek iin eitli komutlar sunar. Dijital giri/k (maksimum 512 ilave giri/k), ve
analog (A/D, D/A evrim ve scaklk) gibi SS/SA/SX/SC/SV CPUlara balanabilen tm modlleri
desteklemesinin yansra her eit yeni yksek-hzl ilave modlleri destekler. 4-grup
yksek-hzl (200kHz) pulse k ve 2-eksen interpolasyon komutlar ile tm uygulamalara
uygun zmler sunar. DVP-SV serisi kk boyutlu olup kurulumu ok kolaydr.
a Bu bilgi dkman sadece rnn elektriksel zellikleri, genel zellikleri, kurulumu ve
balants ile ilgili aklamalar salar. Komutlar ve programlama ile ilgili detayl bilgi sahibi
olmak iin ltfen DVP-PLC Application Manual: Programming e baknz. Opsiyonel evre
donanmlar hakknda daha fazla bilgi sahibi olmak iin, ilgili donanma ait bilgi dkmanna
bakabilir veya DVP-PLC Application Manual: Special Modules inceleyebilirsiniz.
a DVP-SV AIK TP bir rndr. PLC toz, rutubet, elektrik oku ve titreimden uzak yerlerede
muhafaza edilmelidir. Ayrca kiisel ve/veya maddi zararlar nlemek iin rne yetkili
olmayan kiilerin mdahale etmesini engeleleyecek koruyucu nlemler alnmaldr. (rnn
kurulduu panoya kilit konulmasvb).
a rnn giri/k terminallerine kesinlikle AC power balamaynz, aksi halde rn zarar
grebilir. rne enerji vermeden nce tm balantlarn doru olduunu kontrol ediniz.
.
Elektromanyetik grlty nlemek iin PLCnin dzgn topraklandna emin olunuz
Enerji varken rn terminallerine dokunmaynz.

rn Grn
Ltfen ngilizce (English) blmde ekil 1[Figure 1] ve ekil 2 [Figure 2]ye baknz.

Elektriksel zellikler
Model

DVP28SV11R

Madde

DVP28SV11T

Power supply voltaj

24VDC (-15% ~ 20%) (DC power giri ters balant (polarite) korumas

Sznt Akm

Max. 2.2A@24VDC

Sigorta Kapasitesi

2.5A/30VDC, Polyswitch

G Tketimi

6W

Izolasyon direnci

> 5M (Tm I/O nokta-ground: 500VDC)

Ses Bakl

Topraklama
alma / Saklama
Acente Onaylar
Titreim / ok direnci
Arlk (g)

ESD (IEC 61131-2, IEC 61000-4-2): 8kV Hava Dearj


EFT (IEC 61131-2, IEC 61000-4-4): G Hatt: 2kV, Dijital I/O: 1kV, Analog &
Haberleme I/O: 1kV
Snml-Salnml Dalga: G Hatt: 1kV, Dijital I/O: 1kV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
Topraklama kablosunun kesiti power terminal kablosunun kesitinden kk
olmamaldr. (Birok PLC ayn anda kullanlaca zaman, ltfen her bir
PLCnin dzgn topraklandndan emin olunuz.)
alma: 0C ~ 55C (scaklk); 50 ~ 95% (rutubet); kirlenme derece 2
Saklama: -25C ~ 70C (scaklk); 5 ~ 95% (rutubet)
UL508
Avrupa Topluluu EMC Directive 89/336/EEC ve Low Voltage Directive
73/23/EEC
Uluslararas standartlar: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 &
IEC 68-2-27 (TEST Ea)
260

240
Giriler
24VDC tek ortak port girii

zellik
Madde
Giri No.

200kHz

20kHz

10kHz

X0, X1, X4, X5

X10, X11, X14, X15

X6, X7, X12, X13, X16,


X17

Giri voltaj (10%)


Giri empedans
Aktif seviye

24VDC, 5mA
4.7k

3.3k

4.7k

OffOn

> 4mA (16.5V)

> 6mA (18.5V)

> 4mA (16.5V)

OnOff

< 1.5mA (8V)

< 2.2mA (8V)

< 1.5mA (8V)

- 16 -

Giriler
24VDC tek ortak port girii

zellik
Madde
Cevap
Zaman

200kHz

20kHz

OffOn

< 150ns

< 3.5s

< 8s

OnOff

< 3s

< 20s

< 60s

Filtre zaman

10kHz

D1020, D1021den 10 ~ 60ms aras ayarlanabilir (Default: 10ms)


klar
zellik

Rle

Madde
k No.

Y0 ~ Y7, Y10 ~ Y13

Y0 ~ Y4, Y6

1Hz

200kHz

Maksimum frekans
alma Voltaj
Resistif
Maksimum
yk

Cevap
Zaman

Yksek-hz

Transistr
Dk-hz
Y5, Y7, Y10 ~
Y13
10kHz

Y14 ~ Y17,
Y20 ~ #1
1kHz

250VAC, < 30VDC

30VDC

1.5A/1 nokta (5A/COM)

0.3A/1 nokta @ 40Cde; Y0, Y1, Y10 ve Y11


klar yksek-hzl pulse k olarak
kullanldnda, Y0,Y1, Y10 ve Y11 = 30mA

Endktif

#2

9W (30VDC)

Lamba

20WDC/100WAC

1.5W (30VDC)

OffOn

Yaklak 10ms

OnOff

0.2s

20s

<100s

0.2s

30s

<100s

#1: Her bir modelin maksimum X/Y numaralansrmas iin ltfen I/O Terminal Layout blmne baknz.
#2: Yaam Erisi (Ltfen ngilizce (English) blmde ekil 3 [Figure 3]e baknz).

I/O Konfigurasyon
Model

Power

Giri
Tip

16

DC
(Sink veya
Source)

DVP28SV11R
DVP28SV11T

24VDC

Nokta

Nokta

I/O konfigurasyon
Tip

Rle

Transistr

Rle

ngilizce
(English)
blme
baknz

ngilizce
(English)
blme
baknz

12
Transistr

Kurulum
Ltfen ngilizce (English) blmde ekil 4 [Figure 4]e baknz.
Is dalmnn salanabilmesi iin ltfen rnn evresinde ngilizce (English) blmde ekil 5
[Figure 5]de gsterilen gerekli boluun brakldna emin olunuz.
Dorudan Montaj: Ltfen rnn llerine uygun M4 vida kullannz.
DIN Ray Montaj: PLC 35 mm DIN rayna monte edilecei zaman, rnn ray zerinde
hareket ederek balantlarn zarar grmesini nlemek iin sabitleyici klipsler kullanlmas nerilir.
PLCyi DIN Rayna sabitlemek iin alt tarafnda bulunan sabitleyici klips aa doru alr rn
raya yerletirilir daha sonra klips yukar doru geri bastrlr. PLCyi DIN rayndan karmak
iinde ince bir tornavida yardmyla sabitleyici klips aa doru bastrlr ve rn geriye doru
ekilir. ngilizce (English) blmde ekil 6 [Figure 6]y inceleyiniz.

Balant
1. I/O terminal balants iin 22-16AWG (1.5mm) tek veya ok
22-16AWG
damarl kablo kullannz. Kablo zellikleri iin sadaki ekle
baknz. PLC terminal vidalar 1.90 kg-cm (1.65 in-lbs)
orannda sklmal ve balantda sadece 60/75C bakr iletken
< 1.5mm
kullanlmaldr.
2. Bo terminallere balant yapmaynz. Power kablolar ile I/O sinyal kablolarn ayn kablo
bloundan geirmeyiniz.
3. PLC balantlar yaparken rnn iine kk metal paracklar drmeyiniz. PLCde s
dalmnn salanabilmesi iin kablo balantlarn tamamladktan sonra havalandrma
deliklerini kapatan koruyucu etiketleri sknz.

G Kayna
- 17 -

DVP-SV serisi rnlerin enerji besleme girii DCdir. DVP-SV serisi rnler kullanlaca zaman
aadaki noktalara dikkat ediniz:
1. G kayna PLCnin 24VDC ve 0V terminallerine balanr. Besleme aral 20.4 ~ 28.8V
DCdir. Eer besleme voltaj 20.4VDCden az ise, PLC almasn durdurur, tm klar
Off olur ve ERROR indikatr srekli flash yapar.
2. 10 msden daha ksa sreli enerji kesintisi durumunda PLCnin almas etkilenmez. Eer
enerji kesintisi veya voltaj dme sresi daha uzun ise PLCnin almas durur ve tm
klar OFF olur. PLC belemesi normal seviyeye geldiinde PLC otomatik olarak
almasna geri dner. (PLC program yazlaca zaman kalc yardmc rle ve registerlerin
kullanmna dikkat ediniz).

Gvenli Balant
DVP-SV serisi PLC rnleri DC beslemeli olup, Deltann g kayna rnleri olan
(DVPPS01/DVPPS02), DVP-SV PLClerin beslemesi iin ok elverilidir. DVPPS01 veya
DVPPS02 rnlerini korumak iin kullanclarn koruyucu devre kullanmas nerilir. ngilizce
(English) blmde ekil 7 [Figure 7]ye baknz.

1
3
4
6
8

2 Devre Kesici

AC g kayna:100 ~ 240VAC, 50/60Hz

Acil Stop: Acil bir durum meydana geldiinde bu buton sistemin beslemesini keser.

5 AC g kayna yk
7 DVPPS01/DVPPS02
9 DVP-PLC (Ana ilemci nitesi)

Power indikatr
G kayna devre koruma sigortas (2A)
DC g kayna k: 24VDC, 500mA
Digital I/O modl

Giri Balants
2 eit DC giri balants vardr, SINK ve SOURCE. (Aadaki rnee baknz. Detayl
konfigrasyon iin, her bir modelin zelliklerini inceleyiniz.)
DC Sinyal IN SINK mod
Giri balant edeer devresi (ngilizce (English) blmde ekil 8 [Figure 8]e baknz.)
DC Sinyal IN SOURCE mod
Giri balant edeer devresi (ngilizce (English) blmde ekil 9 [Figure 9]e baknz.)

k Balants
1. DVP-SV serisi rnlerde rle ve transistor olmak zere 2 tip k modl vardr. k
balantlarn yaparken ortak terminallerin kullanmna dikkat ediniz.
2. Rle k tip PLClerde ngilizce (English) blmde ekil 10 [Figure 10]da grld gibi Y0,
Y1 ve Y2 k terminalleri C0 ortak terminalini; Y3, Y4 ve Y5 C1 ortak terminalini; Y6, Y7 ve
Y10 C2 ortak terminalini; Y11, Y12 ve Y13 ise C3 ortak terminalini kullanr.
3. klar aktif olduu zaman, n panelde bu klara karlk gelen indikatrler ON olur.
4. Transistor k tip PLClerde ngilizce (English) blmde ekil 11 [Figure 11]de grld
gibi Y0, ve Y1 C0 ortak terminalini; Y2, ve Y3 C1 ortak terminalini; Y4 ve Y5 C2 ortak
terminalini; Y6 ve Y7 C3 ortak terminalini; Y10, Y11, Y12 ve Y13 ise C4 ortak terminalini
kullanr.
5. Izolasyon devresi: PLC ve giri modlleri devreleri arasnda sinyal izolasyonu iin optokuplr
kullanlr.
Rle (R) k devre balants (ngilizce (English) blmde ekil 12 [Figure 12]ye baknz.)

1 DC g kayna
2 Acil stop: Harici anahtar kullanr
3 Sigorta: k devrelerini korumak iin k kontaklarnn ortak terminallerinde 5~10A sigorta
kullanlr

4 Ani voltaj bastrma (SB360 3A 60V): Kontak mrn uzatr.


1. DC yk diyot bastrma: Kk glerde kullanlr (ngilizce (English) blmde ekil13 [Figure 13]e
baknz.)

2. DC yk Diyot + Zener bastrma: Byk g ve sk On/Off durumunda kullanlr. (ngilizce (English)


blmde ekil13 [Figure 13]e baknz.)

5 Akkor lamba (rezistif yk)


6 AC g kayna
7 Manual tek k: rnein, Y3 ve Y4 klar motorun ileri ve geri hareketini kontrol etsin,

beklenmeyen bir hatann olumasn daha gl nlemek iin PLCnin dahili programndan baka
klar harici olarak birbirlerin nne balanabilir.

- 18 -

8 Neon indikatr
9 Dalga Emici: AC yk zerindeki grlty drmek iin ( ngilizce (English) blmde ekil15 [Figure
15]e baknz.)

Transistr (T) k devre balants (ngilizce (English) blmde ekil16 [Figure 16] ve ekil
17 [Figure 17]ye baknz.)

2 Acil stop
3 Devre koruma sigortas
1 DC g kayna
4 Transistr modelinin k open collector dr. Eer Y0/Y1 pulse k ayarlanmsa, normal

almay salamak iin, k akm 0.1Aden byk olmaldr.


1. Diyot bastrma: Kk glerde kullanlr (ngilizce (English) blmde ekil 18 [Figure 18]e
baknz.)
2. Diyot + Zener bastrma: Byk g ve sk On/Off durumlarnda kullanlr. (ngilizce (English)
blmde ekil 19 [Figure 19]a baknz.)
Manual tek k: rnein, Y10 ve Y11 klar motorun ileri ve geri hareketini kontrol etsin,
beklenmeyen bir hatann olumasn daha gl nlemek iin PLCnin dahili programndan baka
klar harici olarak birbirlerin nne balanabilir.

BAT.LOW indikatr
BAT.LOW indikatr pilin voltaj dt zaman ON olur. Bu durum olutuu zaman, PLC
iindeki program ve kalc datalarn silinmemesi iin en ksa srede pili deitiriniz.
DC24V power kesildikten sonra, kalc datalarn iindeki deerler pil tarafndan beslenen SRAM
hafzada tutulur. Bundan dolay pil deitirilemez veya zarar grrse kalc alandaki datalar ve
program kaybolur. Eer kullancnn program iinde kalc alandaki D datalar srekli kaydetmesi
gerekiyorsa aada yazlanlar uygulanmaldr.
Srekli Kaydetme Mekanizmas
Kalc alandaki datalar Flash ROM memorye srekli kaydetmek iin WPLSoft Program
(Options -> PLC<=>Flash) kullanlr. (Yeni tanmlanm tm datalar hafzaya nceden
kaydedilen datalarla yer deitirir).
Geri arma Mekanizmas
Eer yeniden arj edilebilir pil voltaj derse, programda oluan data kayb sonucunda, PLC,
DC24V ile yeniden enerjilendirildiinde programdaki kalc alanlardaki verileri ve Flash ROM
ierisindeki D registerlarn SRAM hafzasna (M1176=On) otomatik olarak geri ykleyecektir.
ERROR LED'in flash yapmas kullancya programn almasna (RUN) devam etmesi
isteniyorsa, bir kez PLC beslemesini kapatp yeniden enerji verilmesi gerektiini bildirir.
1. DVP-28SVnin iindeki yeniden arj edilebilir lityum-ion pil kalc ilem ve datalar saklama
amacyla kullanlr.
2. Lityum-ion pil retimden kmadan nce kalc ilem ve datalar 12 ay boyunca
saklayabilecek ekilde tamamen arj edilir. Eer DVP-28SV nitesi 12 ay boyunca
kullanlmaz ve/veya enerjilenmez ise saklanan ilem ve datalar kaybolur.
3. Lityum-ion pil mr dier sradan pillere gre daha uzun olduu niin srekli arj edilmeye
ihtiya duymaz. Pil arj edilebilme zellii azalmas veya bozulmas endiesine kaplmadan
herhangi bir zamanda arj edilebilir. Pilin iinde enerji varken dahi yeniden arj edebilmek
mmkndr.
4. Ltfen PLCnin retim tarihine dikkat ediniz; arj edilen pil bu tarihten itibaren 12 ay boyunca
dayanabilir. PLC enerjilendikten sonra BAT.LOW indikatrn ON olduu fark edilirse, pil
voltaj dm ve pilin arj edildii anlamna gelir. Bu durumda pilin tamamen arj olmas iin
DVP-28SV PLC 24 saat boyunca enerjili kalmaldr. Bu durumda indikatr ONdan 1 saniyelik
flash konuma geerse bu pilin artk arj edilemeyeceinin gstergesidir. Bu durumda
program ve datalarn yedeini dzgn bir ekilde aldktan sonra pil deiimi iin rn teknik
servisimize gnderiniz.

RTC Doruluu (ay/saniye)


Scaklk (C/F)

0 / 32

25 / 77

55 / 131

Maksimum sapma (saniye)

-117

52

-132

- 19 -