Vous êtes sur la page 1sur 42

19/11/2013

Grounding

Arc Flash Hazard: HRG Technology can play a role in prevention

Why Ground?

Arc Flash Hazard: HRG Technology can play a role in prevention

19/11/2013

Industrial Power System


Grounding Methods

Resistance Grounded

Arc Flash Hazard: HRG Technology can play a role in prevention

Industrial Power System


Grounding Methods

Solidly Grounded

Arc Flash Hazard: HRG Technology can play a role in prevention

19/11/2013

Industrial Power System


Grounding Methods

Solidly Grounded

Arc Flash Hazard: HRG Technology can play a role in prevention

Industrial Power System


Grounding Methods

Solidly Grounded

Arc Flash Hazard: HRG Technology can play a role in prevention

19/11/2013

Industrial Power System


Grounding Methods

Ungrounded

Arc Flash Hazard: HRG Technology can play a role in prevention

What are the main Hazards with


Ungrounded/Solidly Grounded?
Ungrounded: Method used to ground first power
systems
Very large transient over-voltage conditions may exist.
Insulation not rated, therefore, hazard to personnel and
equipment.
Very difficult to locate ground fault.
Good chance of second ground fault on a different phase due to
prolonged ground fault.

Solidly Grounded: Replaced Ungrounded Systems


Very high ground fault currents.
Fault must be cleared, shutting down equipment.
Generators may not be rated for ground fault .
Tremendous amount of arc flash / blast energy.
Equipment and people are not rated for energy.
Arc Flash Hazard: HRG Technology can play a role in prevention

19/11/2013

Do others agree?
To HRG or to not HRG?
IEEE Std 242-2001 (Buff Book)
Recommended Practice for Protection and
Coordination of Industrial and Commercial Power
Systems
8.2.5 If this ground fault is intermittent or allowed to continue,
the system could be subjected to possible severe over-voltages
to ground, which can be as high as six to eight times phase
voltage. Such over-voltages can puncture insulation and result in
additional ground faults. These over-voltages are caused by
repetitive charging of the system capacitance or by resonance
between the system capacitance and the inductance of equipment in
the system.

Arc Flash Hazard: HRG Technology can play a role in prevention

Do others agree?
To HRG or to not HRG?
IEEE Std 141-1993 (Red Book)
Recommended Practice for Electric Power
Distribution for Industrial Plants
7.2.1 Accumulated operating experience indicates that, in general
purpose industrial power distribution systems, the overvoltage incidents associated with ungrounded operation
reduce the useful life of insulation so that electric
current and machine failures occur more frequently
than they do on grounded power systems.

Arc Flash Hazard: HRG Technology can play a role in prevention

19/11/2013

Do others agree?
To HRG or to not HRG?
IEEE Std 242-2001 (Buff Book)
Recommended Practice for Protection and
Coordination of Industrial and Commercial Power
Systems
8.2.5Ungrounded low-voltage systems employ ground detectors
to indicate a ground fault. These detectors show the
existence of a ground on the system and identify the faulted
phase, but do not locate the ground, which can be
anywhere on the entire system.
One disadvantage of the solidly grounded 480V system
involves the high magnitude of destructive, arcing
ground-fault currents that can occur. However, if these
currents are promptly interrupted, the equipment
damage is kept to acceptable levels.
Arc Flash Hazard: HRG Technology can play a role in prevention

Do others agree?
To HRG or to not HRG?
IEEE Std 141-1993 (Red Book)
Recommended Practice for Electric Power
Distribution for Industrial Plants
7.2.4The solidly grounded system has the highest probability of
escalating into a phase-to-phase or three-phase arcing fault,
particularly for the 480V and 600V systems. The danger of
sustained arcing for phase-to-ground fault probability is also
high for the 480V and 600V systems, and low for the 208V
systems. For this reason ground fault protection shall be
required for system over 1000A. A safety hazard exists
for solidly grounded systems from the severe flash, arc
burning, and blast hazard from any phase-to-ground
fault.
Arc Flash Hazard: HRG Technology can play a role in prevention

19/11/2013

What causes the Hazards in


Ungrounded Systems?
System Capacitance
Unable to discharge leading to transient overvoltages
No direct return path for ground fault current
Prolonged fault conditions due to inability to quickly
locate fault.
NEC 250.21(B) Ground Detectors. Ungrounded
alternating current systems as permitted in
250.21(A)(1) through (A)(4) operating at not less than
120 volts and not exceeding 1000 volts shall have
ground detectors installed on the system.
Arc Flash Hazard: HRG Technology can play a role in prevention

Ungrounded Systems
Ungrounded systems do not have an intentional
connection from the source generator or transformer to
ground
Typically a three wire delta system.
Can be a four wire system where the source neutral is
not connected to ground.
A

B
C

Arc Flash Hazard: HRG Technology can play a role in prevention

19/11/2013

Ungrounded Systems
Unintentionally grounded through system capacitance
Such as cables, transformers, motors, surge suppressors, etc.
480V Delta Source
3 Load

277V

Total Capacitive Current


c + I c + Ic
0 = Ia
c
b
c
I a,b,c =

Vl-n
c
X a,b,c

Xc
c

c
Xb

Xc
a

Ic
c

c
Ib

Ic
a

c
Xa,b,c = 277ohms
(typical)

Ground 0V

[120 apart]

Arc Flash Hazard: HRG Technology can play a role in prevention

Ground Faults
Unintentionally grounded through system capacitance
Such as cables, transformers, motors, surge suppressors, etc.
480V Delta Source
3 Load

Total Capacitive Current


c + I c + Ic )
I f = (I a
c
b
c
Ia = 0A (short-circuited)
V l-l
V l-l
c
c
Ic =
Ib =
c
c
Xb
Xc

480V
Xc
c

c
Xb

Xc
a

Ic
c

c
Ib

Ic
a

If

Ground A

Arc Flash Hazard: HRG Technology can play a role in prevention

19/11/2013

Ground Faults
Ground Fault voltage distribution (voltage rise)
C
C
C

B
N
a

a
G

B
N

A
A

A
Vag = 277V
Vbg = 277V
Vcg = 277V
Vng = 0V
a = 120
(0% Fault)

Vag = 138V
Vbg = 367V
Vcg = 367V
Vng = 138V
a = 82
(50% Fault)

Vag = 0V
Vbg = 480V
Vcg = 480V
Vng = 277V
a = 60
(100% Fault)

Arc Flash Hazard: HRG Technology can play a role in prevention

Ground Faults
Ground Fault current distribution (current rise)
If

If
C
C
C

a
G

Ibg

I cg

If

B
I cg

Ibg

a
I ag

A
A
I ag = 1.00A<0
I bg = 1.00A<120
I cg = 1.00A<240
I f = 0A
a = 120
(0% Fault)

I ag = 0.50A<0
I bg = 1.32A<139
I cg = 1.32A<221
I f = 1.50A<180
a = 82
(50% Fault)

I ag = 0.00A
I bg = 1.73A<60
I cg = 1.73A<120
I f = 3.00A<90
a = 60
(100% Fault)

Arc Flash Hazard: HRG Technology can play a role in prevention

19/11/2013

Ground Faults

Arc Flash Hazard: HRG Technology can play a role in prevention

What Causes the Hazards in Solidly


Grounded Systems?
Very low impedance in ground path
o High fault current
High fault energy

Ground Fault Coordination


o Long time delays on upstream devices
High fault energy

Arc Flash Hazard: HRG Technology can play a role in prevention

10

19/11/2013

Solidly Grounded Systems


Grounded systems have an intentional connection
from the source generator or transformer to ground
Typically a four wire delta system
Can be a three wire system where the source
neutral is not connected to loads
A

B
N
C

Arc Flash Hazard: HRG Technology can play a role in prevention

Solidly Grounded Systems


Intentionally grounded through ground wire
480V Wye Source
3 Load

~0

~277

In

Icc

Icb

Ica

Total Capacitive Current


I ca + I cb + I cc = 0

Arc Flash Hazard: HRG Technology can play a role in prevention

11

19/11/2013

Bolted Grounded Systems


Ground fault current distribution on A
480V W ye Source
3 Load

I cc

In

I cb

If

I ca

~60kA
Estim ated Total Fault Current
If =

* I fla

Z pu

~0A (3A)

+ (I cb + I cc ) = ~I n

Exam ple (2500kVA, 480V, Z = 5 % )


1

In = If =

* 3000A = ~60,000A

0.05

Arc Flash Hazard: HRG Technology can play a role in prevention

Arcing Grounded Systems


Ground fault current distribution on A
480V W ye Source
3 Load

I cc

In

I cb

I ca

If

~23kA
Estim ated Total Fault Current
If =

1
Z pu

~0A (3A)

* I fla * .38 + (I cb + I cc ) = ~I n

Exam ple (2500kVA, 480V, Z = 5 % )


In = If =

1
0.05

* 3000A * .38 = ~23kA

Arc Flash Hazard: HRG Technology can play a role in prevention

12

19/11/2013

Arcing Grounded Systems


Arcing ground fault: Lower fault current, so OCPDs
may not clear fault. Delay will cause severe equipment
and personnel damage due to tremendous amount of
energy released.
No transient
over-voltages

High fault
current

Arcing ground faults are approximately 38% bolted faults.


Arc Flash Hazard: HRG Technology can play a role in prevention

Locating Ground Faults

Follow the Smoke!


Direct return to source provides over-current conditions that
allow for OCPD to operate, hence, clearing the fault.
OK, IF the following condition is met (and you like repair
work):
Acceptable Damage
People???
Equipment???
Costs???
Who decides???
Not OK, IF
You do not want to accept damaging people
You pay for equipment repairs
Arc Flash Hazard: HRG Technology can play a role in prevention

13

19/11/2013

Coordination Problems
Discussed Over-Voltage and Over-Current
Hazards ...
Now discuss time factor
Energy is also a function of time
E = volts * amps * time
Large radial systems have long time delays for
coordination
Arc Flash Hazard: HRG Technology can play a role in prevention

Coordination Problems
24 Cycles
(0.4 seconds)
IG = Fault Current
(A)
Va = 100V (typical)
t = time (cycles)

Typical Transformer:
2500 kVA, 5% impedance
Ground condition Ig=23kA

12 Cycles
(0.2 seconds)
6 Cycles
(0.1 seconds)

KWC = 55,200

Acceptable???
Arc Flash Hazard: HRG Technology can play a role in prevention

14

19/11/2013

Coordination Problems
A)

100 Kilowatt Cycles


Fault location identifiable at close inspection - spit marks on metal and
some smoke marks.

B)

2000 Kilowatt Cycles


Equipment can usually be restored by painting smoke marks and
repairing punctures in insulation.

C)

6000 Kilowatt Cycles


Minimal amount of damage, but fault more easily located.

D)

10,000 Kilowatt Cycles


Fault probably contained by the metal enclosure.

E)

20,000 Kilowatt Cycles


Fault probably burns through single thickness enclosure and spreads
to other sections.

F)

Over 20,000 Kilowatt Cycles


Considerable destruction.
Arc Flash Hazard: HRG Technology can play a role in prevention

Hazards with Ungrounded and Solidly


Grounded
Ungrounded

SolidlyGrounded

Transient
Over-Voltage

High Risk

Low Risk

Transient
Over-Current

Low Risk

High Risk

High Risk
(Good Luck)

High Risk
(Follow Smoke)

High Risk
(2nd Fault)

High Risk

Fault
Location
High Fault
Energy

Arc Flash Hazard: HRG Technology can play a role in prevention

15

19/11/2013

High Resistance Grounding


How does HRG solve these hazards?
Inserts a resistor between neutral and ground
Eliminates 98% of Arc Flash / Blast Injuries
Source
(Wye)
A

B
N

HRG

Arc Flash Hazard: HRG Technology can play a role in prevention

High Resistance Grounding


What if no neutral exists (i.e. delta systems)?
A grounding transformer is installed (either a zig zag or a wyedelta) from all three phases to create an artificial neutral for
grounding purposes only.

Arc Flash Hazard: HRG Technology can play a role in prevention

16

19/11/2013

High Resistance Grounding


Intentionally grounded through neutral resistor
480V Wye Source
3 Load

B
N
C

HRG

277V
Vng0V

c
Ic

Ir

c
Ib

c
Ia

Ground 0V
Arc Flash Hazard: HRG Technology can play a role in prevention

High Resistance Grounding


Compared to Ungrounded Systems (voltage rise)
480V Wye Source
3 Load

B
N
C

HRG

VngVan
(277V)

480V

Ir

Additionalreturnpath,onlydifference
betweenUngroundedandHRG!

c
Ic

c
Ib

c
Ia

If

GroundA

Arc Flash Hazard: HRG Technology can play a role in prevention

17

19/11/2013

High Resistance Grounding


Voltages:
Normal Operation
Vag = 277V
Vbg = 277V
Vcg = 277V
Vng = 0V
Fault conditions
Vag = 0V (Faulted phase is at
ground potential)
Vbg = 480V
Vcg = 480V
Vng = 277V
Arc Flash Hazard: HRG Technology can play a role in prevention

High Resistance Grounding


Importance of additional path versus Solidly Grounded
480V Wye Source
3 Load

HRG

Ir

Ca

c
Ic

c
Ib

c
Ia

If

Resistor(HRG)inlieuofwireaddssignificantamountofresistancetolowergroundfaulttoa
predeterminedvaluepreventingdestructivefaultcurrentsandshutdown!
Arc Flash Hazard: HRG Technology can play a role in prevention

18

19/11/2013

High Resistance Grounding


Compared with Solidly Grounded (current rise)
480V Wye Source
3 Load

HRG

55.4

277

Ir

5.00A

c
Ic

c
Ib

c
Ia

If

1.73A

Resistorinreturnpath,onlydifference
betweenSolidlyGroundedandHRG!

5.83A
GroundA

5.83A 3.00A+5.00A

Arc Flash Hazard: HRG Technology can play a role in prevention

High Resistance Grounding


Currents:
Normal Operation:
( Ia Ib Ic ) 0 A
c

Ir

Vng
Rr

I f I r ( I a I b I c )2 0 A
2

0V
0A
55.4

Fault conditions;
( I a I b I c ) (0 1.7360 1.73120 ) 3.0090 A
c

Ir

Vng
Rr

277V
5.000 A
55.4

I f I r ( I a I b I c ) 2 5.83 A
2

I f 3.0090 5.000 5.8331 A


Arc Flash Hazard: HRG Technology can play a role in prevention

19

19/11/2013

High Resistance Grounding


Another advantage of return path: ground fault
location
480V Wye Source

3 Load

HRG

Ca

Ir

c
Ic

c
Ib

c
Ia

If

Contactorshortsoutpartoftheresistorchangingtheresistance,hence,changingthecurrent.
Groundfaultcurrentnowisapulsesignalthatallowsfordetection!
Arc Flash Hazard: HRG Technology can play a role in prevention

High Resistance Grounding


Meter reading will
alternate from 5A
to 10A every 2
seconds.

Method to quickly locate ground faults.


480V Wye Source

85A

55A

80A

50A

5A
A

HRG

80A

55.4
ohms

50A
30A

30A

55A

30A

50A

50A
5A

0A
5A

ZSCT

ZSCT
Meter

Meter
5A

0A
ZSCT
30A

30A

30A

Motor

50A

50A

50A

Meter

Motor

Arc Flash Hazard: HRG Technology can play a role in prevention

20

19/11/2013

Ground Faults
Damage to Power System Components:
Thermal Damage

(Irms)2 * t

Mechanical Damage

(Ip)2

Comparison between S-G example and HRG


System Grounding

Ground Fault (A) Damage to Equipment (1 sec)

HRG

S-G

22,800

1 per unit
(22,800 / 5)2 = 20.8x106 p.u.

SolidlyGroundedSystemshave20.8milliontimesmoredamage thanHRG!!!
Arc Flash Hazard: HRG Technology can play a role in prevention

Do Others Agree?
To HRG or not HRG?
IEEE Std 142-1991 (Green Book)
Recommended Practice for Grounding of Industrial and
Commercial Power Systems
1.4.2 Numerous advantages are attributed to grounded
systems, including greater safety, freedom from
excessive system over-voltages that can occur on
ungrounded systems during arcing, resonant or nearresonant ground faults, and easier detection and location of
ground faults when they do occur.
1.4.3 A system properly grounded by resistance is not
subject to destructive transient over-voltages.

Arc Flash Hazard: HRG Technology can play a role in prevention

21

19/11/2013

Do Others Agree?
To HRG or not HRG?
IEEE Std 142-1991 (Green Book)
Recommended Practice for Grounding of Industrial and Commercial
Power Systems
1.4.3 The reasons for limiting the current by resistance
grounding may be one or more of the following.
1)

To reduce burning and melting effects in faulted electric


equipment, such as switchgear, transformers, cables, and
rotating machines.

2)

To reduce mechanical stresses in circuits and apparatus


carrying fault currents.

3)

To reduce electric-shock hazards to personnel caused


by stray ground-fault currents in the ground return path.

Arc Flash Hazard: HRG Technology can play a role in prevention

Do Others Agree?
To HRG or not HRG?
IEEE Std 142-1991 (Green Book)
Recommended Practice for Grounding of Industrial and Commercial
Power Systems
1.4.3 The reasons for limiting the current by resistance
grounding may be one or more of the following.
4)

To reduce the arc blast or flash hazard to personnel who


may have accidentally caused or who happen to be in close
proximity to the ground fault.

5)

To reduce the momentary line-voltage dip occasioned by


the clearing of a ground fault.

6)

To secure control of transient over-voltages while at the


same time avoiding the shutdown of a faulty circuit on
the occurrence of the first ground fault (high resistance
grounding).

Arc Flash Hazard: HRG Technology can play a role in prevention

22

19/11/2013

Do Others Agree?
To HRG or not HRG?
IEEE Std 141-1993 (Red Book)
Recommended Practice for Electric Power Distribution for
Industrial Plants
7.2.2
There is no arc flash hazard, as there is with solidly
grounded systems, since the fault current is limited to
approximately 5A.
Another benefit of high-resistance grounded systems is the
limitation of ground fault current to prevent damage to
equipment. High values of ground faults on solidly grounded
systems can destroy the magnetic core of rotating machinery.

Arc Flash Hazard: HRG Technology can play a role in prevention

Do Others Agree?
To HRG or not HRG?
IEEE Std 242-2001 (Buff Book)
Recommended Practice for Electric Power Distribution for
Industrial Plants
8.2.5 Once the system is high-resistance grounded, overvoltages are reduced; and modern, highly sensitive groundfault protective equipment can identify the faulted feeder on
the first fault and open one or both feeders on the second
fault before arcing burndown does serious damage.

Arc Flash Hazard: HRG Technology can play a role in prevention

23

19/11/2013

Advanced High Resistance Grounding


SENTINEL/OHMNI DSP
The only SMART HRG
Selective instantaneous feeder
isolation 2nd fault
Mitigate 95-98% of arc flash
incidents - on 1st phase to
ground fault
Assisted fault location
Resistor-integrity monitoring
Time-selective feeder isolation
For more information pick up a product brochure or visit us at www.i-gard.com
Arc Flash Hazard: HRG Technology can play a role in prevention

Advanced High Resistance Grounding


Avoiding second ground fault

Arc Flash Hazard: HRG Technology can play a role in prevention

24

19/11/2013

Advanced High Resistance Grounding:


Assisted Fault Location
Phase Indication

SENTINEL/OHMNI DSP
The only SMART HRG

DSP HRG

TRIP

TRIP

ZSCT

ZSCT

MODBUS
. . . Several Feeders . . .

Motor

Motor

Arc Flash Hazard: HRG Technology can play a role in prevention

Advanced High Resistance Grounding:


Assisted Fault Location
Feeder Indication

SENTINEL/OHMNI DSP
The only SMART HRG

DSP HRG

TRIP

TRIP

ZSCT

ZSCT

MODBUS
. . . Several Feeders . . .

Motor

Motor

Arc Flash Hazard: HRG Technology can play a role in prevention

25

19/11/2013

Advanced High Resistance Grounding:


Avoiding 2nd Ground Fault
SENTINEL/OHMNI DSP
The only SMART HRG

DSP HRG

TRIP

TRIP

ZSCT

ZSCT

Options for Faulted


Feeder:
1) Alarm Only (No Trip)
OR

MODBUS

2) Trip with Time Delay

. . . Several Feeders . . .

Motor

Motor

Arc Flash Hazard: HRG Technology can play a role in prevention

Advanced High Resistance Grounding:


Avoiding 2nd Ground Fault
SENTINEL/OHMNI DSP
The only SMART HRG

2nd Ground Fault:

DSP HRG

TRIP

TRIP

ZSCT

ZSCT

Prioritize Feeders

Trips least important,


maintaining operation on
most important

Up to 50 Feeders

MODBUS
. . . Several Feeders . . .

Motor

Motor

Arc Flash Hazard: HRG Technology can play a role in prevention

26

19/11/2013

Advanced High Resistance Grounding:


Neutral Path
SENTINEL/OHMNI DSP
The only SMART HRG

System Ground Monitor:


DSP HRG

TRIP

TRIP

ZSCT

ZSCT

MODBUS
. . . Several Feeders . . .

Motor

Continually monitors
circuit from Neutral to
Ground

Alarms if OPEN circuit

Alarms if SHORT circuit

Motor

Arc Flash Hazard: HRG Technology can play a role in prevention

Advanced High Resistance Grounding:


Neutral Path
SENTINEL/OHMNI DSP
The only SMART HRG

DSP HRG

TRIP

TRIP

ZSCT

ZSCT

Remote Monitoring:

Tie into Internet

Monitor plant anywhere


in world

Notify maintenance or
local qualified electrical
contractor to locate
ground fault

MODBUS
. . . Several Feeders . . .

Motor

Motor

Arc Flash Hazard: HRG Technology can play a role in prevention

27

19/11/2013

Minimizing Second Simultaneous Ground


Fault

Arc Flash Hazard: HRG Technology can play a role in prevention

DSP Relay Double Ended Unit Sub


Application

Arc Flash Hazard: HRG Technology can play a role in prevention

28

19/11/2013

Design Considerations when applying


HRG Systems
HRG is the best Grounding Method available today
oFirst developed with resistor and pulsing contactor (Analog)
oLeast Hazards of all grounding methods, but some still exist
Elevated Voltages
Trained Personnel
Cables, TVSSs, VFDs Insulation
Line-to-Neutral Loads
Phase-to-ground-to-phase Faults
Bypasses neutral grounding resistor
Single-poling circuit breakers

HRG Systems Resolve these Hazards

Arc Flash Hazard: HRG Technology can play a role in prevention

ASD, UPS

Arc Flash Hazard: HRG Technology can play a role in prevention

29

19/11/2013

AMPLITUDE

ASD, UPS

800
600
400
200
0
-200 0
-400
-600
-800

200

400

600

800

TIME
A-G

B-G

C-G

N-G

Arc Flash Hazard: HRG Technology can play a role in prevention

ASD, UPS

Arc Flash Hazard: HRG Technology can play a role in prevention

30

19/11/2013

Design Considerations when Applying


HRG Systems
NFPA 70: National Electrical Code (2005)
250.36/186 High-impedance grounded neutral systems in which a
grounding impedance, usually a resistor, limits the ground-fault current
to a low value shall be permitted for 3-phase ac systems of 480 volts
to 1000 volts where all the following conditions are met:
1) The conditions of maintenance and supervision
ensure that only qualified persons service the
installation.
2) Ground detectors are installed on the system.
3) Line-to-neutral loads are not served .
Continuity of power is required.(Removed 2008).

Arc Flash Hazard: HRG Technology can play a role in prevention

Elevated Voltage Hazard


Properly rated equipment prevents Hazards.
480V Wye Source

0V
A

B
N

277V

3 Load

480V

HRG

480V

0V
GroundA

Maintenancemustbeawareofelevatedvoltagesandmethodtolocatefault.IFNOT,DO
NOTHAVETOMAINTAINPOWER.Allowedtotrip(sameasSG)butwithoutthehazards.
Arc Flash Hazard: HRG Technology can play a role in prevention

31

19/11/2013

Elevated Voltage Hazard


Properly rated equipment prevents Hazards.
480V Wye Source

0V
A

B
N

277V

3 Load

480V

HRG

480V

0V
Cables,TVSSs,VFDs,etc.andother
equipmentmustberatedforelevated
voltages(UngroundedSystems).

GroundA

Arc Flash Hazard: HRG Technology can play a role in prevention

Resolve Cable Insulation Issue


600V Cables

Insulation thickness based on mechanical strength, not electrical


Extra thickness exceeds 600V electrical rating
Therefore, should be used on 600V systems (HRG)

1000V Cables

Only CSA listed, not UL

5000V Cables

Non-shielded: Should be used on 2400V systems (HRG)


Shielded: Should be used on 4160V systems (HRG)

8000V Cables

Non-shielded: Should be used on 4160V systems (HRG)

Arc Flash Hazard: HRG Technology can play a role in prevention

32

19/11/2013

Resolve NEC Requirement

Add small 1:1


transformer and solidly
ground secondary for 1
loads (i.e. lighting).
Arc Flash Hazard: HRG Technology can play a role in prevention

Resolve NEC Requirement


Advantages of 1:1 transformer
oAbility to retrofit HRG Systems
oOnly ~20% of facility / plant load is 1
No neutral required from main source and main
switchgear (cost savings,)
oSignificantly reduced risk of Arc Blast / Flash Hazard
Only small portion of power system is solidly
grounded
Lighting Ballasts

Arc Flash Hazard: HRG Technology can play a role in prevention

33

19/11/2013

Phase-to-Ground-to-Phase Fault
Single-poling circuit breaker
480V Wye Source

2000A/3P/65kAIC

3 Load

B
N

HRG

During phase-ground-phase fault, single-pole of MCB has to clear the 480V


fault at 65kA. However, per UL 489, single-pole interrupting rating is only at
20kAIC. HAZARDOUS?
Arc Flash Hazard: HRG Technology can play a role in prevention

Phase-to-Ground-to-Phase Fault
For condition to occur, all of the following must be true:

1) One fault must be on line side of MCB


Very uncommon
2) Low impedance per ground fault
Very uncommon
Ground faults are usually arcing faults (high impedance faults
per IEEE Std 241, 9.2.5)
3) Faults on different phases
4) No other over-current protective devices in fault path
Very uncommon
If so, they will open: eliminating the single-pole interruption

Although remote, HAZARD may still exists:


Should be considered during coordination study
Detect ground faults per NEC 250-36

Arc Flash Hazard: HRG Technology can play a role in prevention

34

19/11/2013

Resolving Hazard via New Technology


First fault:
Sound Alarm
Send signal

Second fault:
Open feeder with lower
priority

Third fault:
Open feeder with lower
priority

DFM DFM DFM DFM DSM

M M M M

Arc Flash Hazard: HRG Technology can play a role in prevention

Additional Advancements in HRG


Systems
Communications
RS232 (Serial) / RS485 (Modbus, Profibus) / TCP/IP
(Ethernet)
Control and monitor relay remotely via existing
SCADA system
Data Logging & Trending
Most ground faults are intermittent, so when you go
to locate via pulse, fault may have cleared
Data log can link ground faults with equipment
starting or running
Arc Flash Hazard: HRG Technology can play a role in prevention

35

19/11/2013

Additional Advancements in HRG


Systems
Filters Harmonics / Noise / RF
Monitors fundamental voltage and current for ground faults
Avoids nuisance tripping
Monitors 3rd harmonic voltage and current
High Harmonics may require de-rating resistor
Low Harmonics may indicate ground fault near generator
neutral
Zone Selective Interlocking
Allows coordination between interlocked protection relays on the
same system
Continuously measures system impedance
Electrical systems are perpetual systems
System capacitance may increase causing grounding resistor to
be incorrectly sized
Undesirable, higher fault current may flow
Transient over-voltage may occur
Arc Flash Hazard: HRG Technology can play a role in prevention

To Summarize

Hazards with Ungrounded Systems


Severe transient over-voltages
Cannot efficiently locate ground faults
Hazards with Solidly-Grounded Systems
Very high fault currents and time delays
Causing severe arc blast / flash conditions
Ground fault coordination problems

Arc Flash Hazard: HRG Technology can play a role in prevention

36

19/11/2013

To Summarize
High-Resistance Grounded Systems
Best Grounding Method today
Resolves Ungrounded hazards
Resolves Solidly-Grounded hazards

Technology continues to make HRG Systems


safer than any other grounding method, but need
help
Continue to educate and train personnel (engr and maint.)
NETA

Update standards and guideline that hinder HRG


NEC
NFPA 70E and IEEE 1584
Arc Flash Hazard: HRG Technology can play a role in prevention

Optical or Pressure Detection


Which one is faster?
Speed of light = 300 x 106 meters/sec
Speed of sound =350 meters/sec
Pressure travels at the speed of sound

Arc Flash Hazard: HRG Technology can play a role in prevention

37

19/11/2013

Optical Arc Fault Detection


Relies on detecting a high- intensity light
Fastest method of arc detection
Can issue a command to trip in 1 ms to 7 ms
Detectors are light sensors.
Sensors local to the relay, rely on Fibre optic to
conduct light to the relay
Sensor remote to the relay, are hard wired to the
relay

Arc Flash Hazard: HRG Technology can play a role in prevention

Pressure Detection
Pressure wave of an arc travels at the speed of
sound
Ralph Lees research shows that arcing faults can
produce 20-1000 psi
Depending on placement of pressure sensors,
detection can be as fast as 8-18 ms
Can still trip in less than 100 ms
Commercially available

Arc Flash Hazard: HRG Technology can play a role in prevention

38

19/11/2013

Temperature Detection
Temperature detection is a slower technique to
detect the presence of an arc
This method is more effective as an early detection
system for series faults
Can easily detect loose connections by monitoring
the outgases of products produced by overheating

Arc Flash Hazard: HRG Technology can play a role in prevention

Distance
Effect on Personal Protective Equipment (PPE)
requirements
Remote operation inherently increases distance
from arc source

Arc Flash Hazard: HRG Technology can play a role in prevention

39

19/11/2013

Reduce Incident Energy


Reduce Time
Reduce Bolted Fault Current
Do both.

Arc Flash Hazard: HRG Technology can play a role in prevention

Reduce Incident Energy

Activate a current limiting device that will quickly


insert an impedance into the circuit on the
occurrence of an arc fault;
Can reduce the fault current from 50 kA to 0.4 kA in
approximately cycle.

Arc Flash Hazard: HRG Technology can play a role in prevention

40

19/11/2013

Reduce Incident Energy

This conceptual unit will reduce the incident energy


from 5.7 cal/cm2 to 0.9 cal/cm2
Arc Flash Hazard: HRG Technology can play a role in prevention

Thank You!
Questions?

41

19/11/2013

How to Get in Touch


I-Gard Corporation
Head Office
7615 Kimbel St., Unit 1
Mississauga, Ontario Canada L5S 1A8

Phone: 905.673.1553 Toll Free 1.888.737.4787


Fax:
905.673.8472 E-mail: info@i-gard.com

Our business hours are Monday to Friday 9:00 a.m. to 5:00 p.m. (EST), if during those
hours you are not able to call us, simply send us an e-mail or leave us a message.
The following members of our inside sales team will be pleased to assist you:

Mr. Doug Gonyou


Mr. Edmundo Perich
Mrs. Kavita Raghunathan
Mr. Upul Herath

dgongou@i-gard.com
eperich@i-gard.com
kraghunathan@i-gard.com
uherath@i-gard.com

www.i-gard.com

42

Vous aimerez peut-être aussi