Académique Documents
Professionnel Documents
Culture Documents
Grounding
Why Ground?
19/11/2013
Resistance Grounded
Solidly Grounded
19/11/2013
Solidly Grounded
Solidly Grounded
19/11/2013
Ungrounded
19/11/2013
Do others agree?
To HRG or to not HRG?
IEEE Std 242-2001 (Buff Book)
Recommended Practice for Protection and
Coordination of Industrial and Commercial Power
Systems
8.2.5 If this ground fault is intermittent or allowed to continue,
the system could be subjected to possible severe over-voltages
to ground, which can be as high as six to eight times phase
voltage. Such over-voltages can puncture insulation and result in
additional ground faults. These over-voltages are caused by
repetitive charging of the system capacitance or by resonance
between the system capacitance and the inductance of equipment in
the system.
Do others agree?
To HRG or to not HRG?
IEEE Std 141-1993 (Red Book)
Recommended Practice for Electric Power
Distribution for Industrial Plants
7.2.1 Accumulated operating experience indicates that, in general
purpose industrial power distribution systems, the overvoltage incidents associated with ungrounded operation
reduce the useful life of insulation so that electric
current and machine failures occur more frequently
than they do on grounded power systems.
19/11/2013
Do others agree?
To HRG or to not HRG?
IEEE Std 242-2001 (Buff Book)
Recommended Practice for Protection and
Coordination of Industrial and Commercial Power
Systems
8.2.5Ungrounded low-voltage systems employ ground detectors
to indicate a ground fault. These detectors show the
existence of a ground on the system and identify the faulted
phase, but do not locate the ground, which can be
anywhere on the entire system.
One disadvantage of the solidly grounded 480V system
involves the high magnitude of destructive, arcing
ground-fault currents that can occur. However, if these
currents are promptly interrupted, the equipment
damage is kept to acceptable levels.
Arc Flash Hazard: HRG Technology can play a role in prevention
Do others agree?
To HRG or to not HRG?
IEEE Std 141-1993 (Red Book)
Recommended Practice for Electric Power
Distribution for Industrial Plants
7.2.4The solidly grounded system has the highest probability of
escalating into a phase-to-phase or three-phase arcing fault,
particularly for the 480V and 600V systems. The danger of
sustained arcing for phase-to-ground fault probability is also
high for the 480V and 600V systems, and low for the 208V
systems. For this reason ground fault protection shall be
required for system over 1000A. A safety hazard exists
for solidly grounded systems from the severe flash, arc
burning, and blast hazard from any phase-to-ground
fault.
Arc Flash Hazard: HRG Technology can play a role in prevention
19/11/2013
Ungrounded Systems
Ungrounded systems do not have an intentional
connection from the source generator or transformer to
ground
Typically a three wire delta system.
Can be a four wire system where the source neutral is
not connected to ground.
A
B
C
19/11/2013
Ungrounded Systems
Unintentionally grounded through system capacitance
Such as cables, transformers, motors, surge suppressors, etc.
480V Delta Source
3 Load
277V
Vl-n
c
X a,b,c
Xc
c
c
Xb
Xc
a
Ic
c
c
Ib
Ic
a
c
Xa,b,c = 277ohms
(typical)
Ground 0V
[120 apart]
Ground Faults
Unintentionally grounded through system capacitance
Such as cables, transformers, motors, surge suppressors, etc.
480V Delta Source
3 Load
480V
Xc
c
c
Xb
Xc
a
Ic
c
c
Ib
Ic
a
If
Ground A
19/11/2013
Ground Faults
Ground Fault voltage distribution (voltage rise)
C
C
C
B
N
a
a
G
B
N
A
A
A
Vag = 277V
Vbg = 277V
Vcg = 277V
Vng = 0V
a = 120
(0% Fault)
Vag = 138V
Vbg = 367V
Vcg = 367V
Vng = 138V
a = 82
(50% Fault)
Vag = 0V
Vbg = 480V
Vcg = 480V
Vng = 277V
a = 60
(100% Fault)
Ground Faults
Ground Fault current distribution (current rise)
If
If
C
C
C
a
G
Ibg
I cg
If
B
I cg
Ibg
a
I ag
A
A
I ag = 1.00A<0
I bg = 1.00A<120
I cg = 1.00A<240
I f = 0A
a = 120
(0% Fault)
I ag = 0.50A<0
I bg = 1.32A<139
I cg = 1.32A<221
I f = 1.50A<180
a = 82
(50% Fault)
I ag = 0.00A
I bg = 1.73A<60
I cg = 1.73A<120
I f = 3.00A<90
a = 60
(100% Fault)
19/11/2013
Ground Faults
10
19/11/2013
B
N
C
~0
~277
In
Icc
Icb
Ica
11
19/11/2013
I cc
In
I cb
If
I ca
~60kA
Estim ated Total Fault Current
If =
* I fla
Z pu
~0A (3A)
+ (I cb + I cc ) = ~I n
In = If =
* 3000A = ~60,000A
0.05
I cc
In
I cb
I ca
If
~23kA
Estim ated Total Fault Current
If =
1
Z pu
~0A (3A)
* I fla * .38 + (I cb + I cc ) = ~I n
1
0.05
12
19/11/2013
High fault
current
13
19/11/2013
Coordination Problems
Discussed Over-Voltage and Over-Current
Hazards ...
Now discuss time factor
Energy is also a function of time
E = volts * amps * time
Large radial systems have long time delays for
coordination
Arc Flash Hazard: HRG Technology can play a role in prevention
Coordination Problems
24 Cycles
(0.4 seconds)
IG = Fault Current
(A)
Va = 100V (typical)
t = time (cycles)
Typical Transformer:
2500 kVA, 5% impedance
Ground condition Ig=23kA
12 Cycles
(0.2 seconds)
6 Cycles
(0.1 seconds)
KWC = 55,200
Acceptable???
Arc Flash Hazard: HRG Technology can play a role in prevention
14
19/11/2013
Coordination Problems
A)
B)
C)
D)
E)
F)
SolidlyGrounded
Transient
Over-Voltage
High Risk
Low Risk
Transient
Over-Current
Low Risk
High Risk
High Risk
(Good Luck)
High Risk
(Follow Smoke)
High Risk
(2nd Fault)
High Risk
Fault
Location
High Fault
Energy
15
19/11/2013
B
N
HRG
16
19/11/2013
B
N
C
HRG
277V
Vng0V
c
Ic
Ir
c
Ib
c
Ia
Ground 0V
Arc Flash Hazard: HRG Technology can play a role in prevention
B
N
C
HRG
VngVan
(277V)
480V
Ir
Additionalreturnpath,onlydifference
betweenUngroundedandHRG!
c
Ic
c
Ib
c
Ia
If
GroundA
17
19/11/2013
HRG
Ir
Ca
c
Ic
c
Ib
c
Ia
If
Resistor(HRG)inlieuofwireaddssignificantamountofresistancetolowergroundfaulttoa
predeterminedvaluepreventingdestructivefaultcurrentsandshutdown!
Arc Flash Hazard: HRG Technology can play a role in prevention
18
19/11/2013
HRG
55.4
277
Ir
5.00A
c
Ic
c
Ib
c
Ia
If
1.73A
Resistorinreturnpath,onlydifference
betweenSolidlyGroundedandHRG!
5.83A
GroundA
5.83A 3.00A+5.00A
Ir
Vng
Rr
I f I r ( I a I b I c )2 0 A
2
0V
0A
55.4
Fault conditions;
( I a I b I c ) (0 1.7360 1.73120 ) 3.0090 A
c
Ir
Vng
Rr
277V
5.000 A
55.4
I f I r ( I a I b I c ) 2 5.83 A
2
19
19/11/2013
3 Load
HRG
Ca
Ir
c
Ic
c
Ib
c
Ia
If
Contactorshortsoutpartoftheresistorchangingtheresistance,hence,changingthecurrent.
Groundfaultcurrentnowisapulsesignalthatallowsfordetection!
Arc Flash Hazard: HRG Technology can play a role in prevention
85A
55A
80A
50A
5A
A
HRG
80A
55.4
ohms
50A
30A
30A
55A
30A
50A
50A
5A
0A
5A
ZSCT
ZSCT
Meter
Meter
5A
0A
ZSCT
30A
30A
30A
Motor
50A
50A
50A
Meter
Motor
20
19/11/2013
Ground Faults
Damage to Power System Components:
Thermal Damage
(Irms)2 * t
Mechanical Damage
(Ip)2
HRG
S-G
22,800
1 per unit
(22,800 / 5)2 = 20.8x106 p.u.
SolidlyGroundedSystemshave20.8milliontimesmoredamage thanHRG!!!
Arc Flash Hazard: HRG Technology can play a role in prevention
Do Others Agree?
To HRG or not HRG?
IEEE Std 142-1991 (Green Book)
Recommended Practice for Grounding of Industrial and
Commercial Power Systems
1.4.2 Numerous advantages are attributed to grounded
systems, including greater safety, freedom from
excessive system over-voltages that can occur on
ungrounded systems during arcing, resonant or nearresonant ground faults, and easier detection and location of
ground faults when they do occur.
1.4.3 A system properly grounded by resistance is not
subject to destructive transient over-voltages.
21
19/11/2013
Do Others Agree?
To HRG or not HRG?
IEEE Std 142-1991 (Green Book)
Recommended Practice for Grounding of Industrial and Commercial
Power Systems
1.4.3 The reasons for limiting the current by resistance
grounding may be one or more of the following.
1)
2)
3)
Do Others Agree?
To HRG or not HRG?
IEEE Std 142-1991 (Green Book)
Recommended Practice for Grounding of Industrial and Commercial
Power Systems
1.4.3 The reasons for limiting the current by resistance
grounding may be one or more of the following.
4)
5)
6)
22
19/11/2013
Do Others Agree?
To HRG or not HRG?
IEEE Std 141-1993 (Red Book)
Recommended Practice for Electric Power Distribution for
Industrial Plants
7.2.2
There is no arc flash hazard, as there is with solidly
grounded systems, since the fault current is limited to
approximately 5A.
Another benefit of high-resistance grounded systems is the
limitation of ground fault current to prevent damage to
equipment. High values of ground faults on solidly grounded
systems can destroy the magnetic core of rotating machinery.
Do Others Agree?
To HRG or not HRG?
IEEE Std 242-2001 (Buff Book)
Recommended Practice for Electric Power Distribution for
Industrial Plants
8.2.5 Once the system is high-resistance grounded, overvoltages are reduced; and modern, highly sensitive groundfault protective equipment can identify the faulted feeder on
the first fault and open one or both feeders on the second
fault before arcing burndown does serious damage.
23
19/11/2013
24
19/11/2013
SENTINEL/OHMNI DSP
The only SMART HRG
DSP HRG
TRIP
TRIP
ZSCT
ZSCT
MODBUS
. . . Several Feeders . . .
Motor
Motor
SENTINEL/OHMNI DSP
The only SMART HRG
DSP HRG
TRIP
TRIP
ZSCT
ZSCT
MODBUS
. . . Several Feeders . . .
Motor
Motor
25
19/11/2013
DSP HRG
TRIP
TRIP
ZSCT
ZSCT
MODBUS
. . . Several Feeders . . .
Motor
Motor
DSP HRG
TRIP
TRIP
ZSCT
ZSCT
Prioritize Feeders
Up to 50 Feeders
MODBUS
. . . Several Feeders . . .
Motor
Motor
26
19/11/2013
TRIP
TRIP
ZSCT
ZSCT
MODBUS
. . . Several Feeders . . .
Motor
Continually monitors
circuit from Neutral to
Ground
Motor
DSP HRG
TRIP
TRIP
ZSCT
ZSCT
Remote Monitoring:
Notify maintenance or
local qualified electrical
contractor to locate
ground fault
MODBUS
. . . Several Feeders . . .
Motor
Motor
27
19/11/2013
28
19/11/2013
ASD, UPS
29
19/11/2013
AMPLITUDE
ASD, UPS
800
600
400
200
0
-200 0
-400
-600
-800
200
400
600
800
TIME
A-G
B-G
C-G
N-G
ASD, UPS
30
19/11/2013
0V
A
B
N
277V
3 Load
480V
HRG
480V
0V
GroundA
Maintenancemustbeawareofelevatedvoltagesandmethodtolocatefault.IFNOT,DO
NOTHAVETOMAINTAINPOWER.Allowedtotrip(sameasSG)butwithoutthehazards.
Arc Flash Hazard: HRG Technology can play a role in prevention
31
19/11/2013
0V
A
B
N
277V
3 Load
480V
HRG
480V
0V
Cables,TVSSs,VFDs,etc.andother
equipmentmustberatedforelevated
voltages(UngroundedSystems).
GroundA
1000V Cables
5000V Cables
8000V Cables
32
19/11/2013
33
19/11/2013
Phase-to-Ground-to-Phase Fault
Single-poling circuit breaker
480V Wye Source
2000A/3P/65kAIC
3 Load
B
N
HRG
Phase-to-Ground-to-Phase Fault
For condition to occur, all of the following must be true:
34
19/11/2013
Second fault:
Open feeder with lower
priority
Third fault:
Open feeder with lower
priority
M M M M
35
19/11/2013
To Summarize
36
19/11/2013
To Summarize
High-Resistance Grounded Systems
Best Grounding Method today
Resolves Ungrounded hazards
Resolves Solidly-Grounded hazards
37
19/11/2013
Pressure Detection
Pressure wave of an arc travels at the speed of
sound
Ralph Lees research shows that arcing faults can
produce 20-1000 psi
Depending on placement of pressure sensors,
detection can be as fast as 8-18 ms
Can still trip in less than 100 ms
Commercially available
38
19/11/2013
Temperature Detection
Temperature detection is a slower technique to
detect the presence of an arc
This method is more effective as an early detection
system for series faults
Can easily detect loose connections by monitoring
the outgases of products produced by overheating
Distance
Effect on Personal Protective Equipment (PPE)
requirements
Remote operation inherently increases distance
from arc source
39
19/11/2013
40
19/11/2013
Thank You!
Questions?
41
19/11/2013
Our business hours are Monday to Friday 9:00 a.m. to 5:00 p.m. (EST), if during those
hours you are not able to call us, simply send us an e-mail or leave us a message.
The following members of our inside sales team will be pleased to assist you:
dgongou@i-gard.com
eperich@i-gard.com
kraghunathan@i-gard.com
uherath@i-gard.com
www.i-gard.com
42