1. PLTU Maluku Utara is designed not to use medium voltage bus, another word only
th
'I
, .
LV Bus is available, because the plant is considered very small, normally no need
~i
big motors for their auxiliary system, unfortunately there is one motor having size
of 150 kW for BFP, which have to be connected to LV Bus. It is fully aware in the
contract stating that motors having capacity of 150 kW or larger should be
supplied from Medium Voltage. Basically it can be understood that this is general
,f
requirement, particularly more suitable for requirement for power plant having
~,;
i::
MODEL 1001
[=41
~
PT PLN (PERSERO)
PEMBANGKITAN SULAWESI, MALUKU DAN PAPUA
Halaman No. :
)....
Surat No.
: C04I /1'2.1/
: 04N~y<..'f
Tanggal
clear and
~\..MAf'A- /2..D\O
18, 20.0
understand what is
crucial to be taken into account for designing Plant Electrical System, particularly
for PlTU Maluku Utara (2 X 7 MW).
Thank you for your kind attention and cooperation .
.-;;:=::::::-~:--...
/~~_J~:E~~l
/./
.,.".....
// " "
.r
// .......~ 1/
Ii
II
\~)-~.\~
i'['M8;-\Ij':;KiT.I\N
'\
'
\\"'- -,
~~,,~~,
~,,,,, ~
I..
'i~
rn
II
/ ---- I
<,__
r--
._._~~.D!'P.~RANGI JAYA
...~::::::::;::;.
MODEL 1006
\.
. "\. ,~
",.,_' s. r..-?/
. . .~. . . . (
MANAGER
\~~
<;
Consortium
Shandong Machinery I & E Corporation
PT Rekadaya Elektrika
r::::J
r-:[eKtr~ ka. t:..J
rekadaya
: 2 (two) sets
Subject
Dear Sir,
According to our design for motors which have capacity more than 160 kW supplied by low voltage i.e 400
Volts, here by we submit our study for voltage drop at steady state and voltage dip at motor starting for
your review and approval. Based on our study as attached it is technically able to have motor 160 kW
supplied from low voltage system.
We guarantee that our system and design are very strictly follow to the International Standards. (i.e lEe
and IEEE) and also based on practical experience in other projects.
Please be noted that the motor operating power will be 125 kW as shown on motor characteristic curve as
attached. However the manufacturer's standard classify motor with 160 kW capacity to be rated 380 volt.
Therefore, hopefully you would accept our design that motor above 150 kW may be supplied from low
voltage systems. In addition, for safety concern and the reliability of the power plant operation to avoid
excessive voltage drop, we will provide soft starter for motor above 150 kW which are supplied from low
voltage systems.
Please don't be hesitated to have discussion with us.
Thank you for your attention and good cooperation.
'1
cc. :
.,__ 1
Jl;!J' ENJINIRING
No.
Attachment
SUbject
: 11.050fTM.12.2008/121/PLNE/1/201 0
: 1 (one) Set
: Single Line Diagram
PLTU Maluku Utara 2X7 MW Tidore
start operation and sudden change of motor's speed due to sudden change of motor's load
2.
The use of fuses, combined with Load Break Switch (LBS), as a protection between Unit Auxiliary
Transformer (UAT) and 6.3 MV Bus.
Concerning the operation and maintenance of Steam Power Plant, also the important aspect of
PLTU Maluku Utara in the North Maluku Region; it is our opinion that the use of Fuses (combined
with LBS as disconnecting apparatus), as protection devices for such important equipments, is not
appropriate. We have insisted the Contractor to propose Circuit Breakers.