Vous êtes sur la page 1sur 4

electrical-engineering-portal.

com
http://electrical-engineering-portal.com/the-most-typical-indices-for-measuring-power-quality-disturbances

The Most Typical Indices For Measuring Power Quality


Disturbances
Google+

The Most Typical Indices For Measuring Power Quality Disturbances (photo credit: ktiengineering.com)

Power quality metrics


There are various methods for categorizing the severity of power disturbances. The most typical indices for
measuring power quality disturbances are listed and explained below:

1. Distortion Factor
The ratio of the root square value of the harmonic content to the root square value of the fundamental quantity,
expressed as a percentage of the fundamental, also known as total harmonic distortion.
where:
Vh is the RMS harmonic voltage (or current) value at a
frequency of n times the fundamental frequency
V1 is the RMS fundamental-frequency voltage or current
Alternate forms for the distortion factor are given as

percentages of the nominal voltage or demand load current for the system under consideration, for use in
evaluation of the harmonic content of the system voltage or current.
These are referred to as Total Harmonic Distortion (THDVn) and Total Demand Distortion (TDD), defined as
follows:
where:
Vh is the RMS value of the nth
harmonic component of the voltage
Vn is the RMS nominal
fundamental voltage value
Ih is the RMS value of the nth
harmonic component of the current
IL is the maximum demand load current, typically the average maximum monthly demand over a 12-month
period
Go back to Index

2. Crest Factor
The ratio of the peak value of a periodic function to the RMS value, i.e.:
where:
ypeak is the peak value of a periodic function
yrms is the RMS value of the function
Because power system voltages and currents are nominally sinusoidal, the nominal crest factor for these
would be 2.
Go back to Index

3. Notch Area
A notch in the power system voltage (or current) is illustrated in figure 1 below:
The notch area for the notch as illustrated in figure above is defined as:
where:
An is the notch area in volt-microseconds
t is the notch time duration in microseconds
d is the notch depth in volts
Go back to Index

4. Recovery time

This is the time needed for the


output voltage or current to return
to a value within the
regulation specification after a step
load or line change.
Go back to Index

5. Displacement Power
Factor
The ratio of the active power of the
fundamental wave, in watts, to the
apparent power of the fundamental
wave, in volt-amperes.
This is the traditional definition of
power factor.

Figure 1 Voltage (or current) notch illustration

Go back to Index

6. Total Power Factor


The ratio of the total input power, in watts, to the total volt-ampere input. This includes the effects of harmonics.
Go back to Index

7. K Factor
A measure of a transformers ability to serve non-sinusoidal loads. The K factor is defined as:
where:
Ih is the harmonic component at h times the fundamental frequency
h is the harmonic order of Ih in multiples of the fundamental frequency
h max is maximum harmonic order present
Go back to Index
Reference: Power Quality Considerations- Bill Brown, P.E., Square D Engineering Services

About Author //
Edvard Csanyi
Edvard - Electrical engineer, programmer and founder of EEP. Highly specialized for design of LV high power
busbar trunking (<6300A) in power substations, buildings and industry fascilities. Designing of LV/MV
switchgears. Professional in AutoCAD programming and web-design. Present on

RSS Feed for Comments

One Comment
1.
Jimmy Valeriano
Dec 27, 2014
Can you discuss how to interpret the grahical test result of power analyzer
(reply)
RSS Feed for Comments

Leave a Comment
Tell us what you're thinking... we care about your opinion!
and oh, not to forget - if you want a picture to show with your comment, go get a free Gravatar!

3 = eighteen

Vous aimerez peut-être aussi