Energy Efficient Building Design

College Of Architecture
Illinois Institute of Technology (IIT), Chicago

Stairwell
Pressurization

ASHRAE 1999 HVAC Applications Handbook 51.9


B = 7.64 * ( 1/To - 1/Ts )
DPsbt = DPsbb + [ By / { 1 + ( Asb/Abo)2 } ]
Q = 1740 * N * Asb * X
X = [ (DPsbt)3/2 - (DPsbb)3/2 ] / [ DPsbt - DPsbb ]
Table-1: Door Leakage Area
Height (ft)
7
User
Width (ft)
3
Leak-Area (ft2)
Input
Doors in Parallel: Leakage Areas = A1 , A2, --- An
Area (ft2)
21
Avge 1/8"
0.21
Calculated
Effective Leakage Area (Ae)
Perim (ft)
20
3/4" Undercut
0.36
by Program
Ae = A1 + A2 + ----- + An
Table-2: Elevator Doors
Leak Area (ft2)
Minim
0.55
Maxim
0.70
Table-3: Leakage Areas: Walls, Floors
A = Leakage Are As = Surface Area
Construction
A/As
Exterior Walls
Tight
0.00007
Avg
###
Loose
0.00042
Stairwell Walls Tight
0.00002
Avg
###
Loose
0.00035
Elevator Shaft WaTight
0.00018
Avg
0.00084
Loose
0.00180
Floors
Avg
0.00005

To
Ts
DPsbb
B
N
y
Asdb

Aswb

Abo
Asb
DPsbt
DPsb
X -n
X -d
Q

Table-4 Additional CFM for Open Doors


Vel thru # of Doors (7' x 3') Open
Door
1
3
4
25
525
1,575
2,100
50
1,050
3,150
4,200
100
2,100
6,300
8,400
150
3,150
9,450
12,600

A1

An
Doors in Series: Leakage Areas = A1 , A2, A3, --- An
A1

An

Effective Leakage Area (Ae) Doors in Series


Ae = [ 1/A12 + 1/A22 + 1/A32 + ----- + 1/An2 ] -0.5
ASHRAE Pressure Minimum Stairwell Pressure (in. H2 0.052
Recommendatio Maximum Stairwell Pressure (in. H2 0.551

Building Length (
Use square root of floor area i 115
Building Width (ft)
building is not rectangular 104
Stairwell Plan View Length (ft)
10
Stairwell Plan View Width (ft)
10
Temperature of Outdoor Air in Winter (deg F)
-4
Temperature of Outdoor Air (deg Rankine)
456
Temperature of Stairwell Air (deg F)
70
Temperature of Stairwell Air (deg Rankine)
530
MIN Press Difference Stair & Bldg at Bottom of St 0.05
B = 7.64 * ( 1/To - 1/Ts )
0.00234
Number of Floors
36
Floor to Floor Height (ft)
11
Distance between Stairwell Bottom and Top (ft)
396
Leakage Area between Stairwell Door & Bldg Space per 0.21
Wall Surface Area between Stairwell & Bldg Space per f 440
Stairwell Wall Tightness Leakage Area (ft2)
###
Flow Area between Stairwell Wall & Bldg per Floor (ft2 0.0484
Exter Wall Surface Area between Bldg and Outside per 4818
Building Exterior Wall Tightness Leakage Area (ft2)
###
Flow Area between Building & Outside per Floor (ft2) 1.01178
Total Flow Leakage Area Stairwell & surrounding Space0.25840
MAX Press Difference Stair & Bldg at Top of Stair ###
AVG Press Difference between Stair & Bldg Spac ###
[ (DPsbt)3/2 - (DPsbb)3/2 ]
0.87073
[ DPsbt - DPsbb ]
0.86964
Supply Air (cfm)
16,207

Instructor: Varkie C. Thomas, Ph.D., P.E.


Skidmore, Owings Merrill LLP

Lb
Wb
Ls
Ws
to
To = to + 460
Ts = ts + 460
PD-min
B = 7.64 * ( 1/To - 1/Ts )
N
H
y=N*H
Dor-lkg See Table-1 or -2
W-sb = 2 * ( Ls + Ws ) * H
Str-lkg See Table-3
F-sb = W-sb * Str-lkg
Wall-ext = 2 * ( Lb + Wb ) * H * N
Bld-lkg See Table-3
F-bo = W * Bld-lkg
Tot-lkg = Dor-lkg + Str-lkg
Fan Static Pressure
PD-avg = ( PD-min + PD-max ) / 2
PD-max = PD-min +
(B*y) / (1+(Tot-lkg/F-bo)^2 )
Q = 1740*N*Asb*X-n/X-d

Arch-551 (Fall) Arch-552 (Spring)

Energy Efficient Building Design

College Of Architecture
Illinois Institute of Technology (IIT), Chicago

Example

= A1 , A2, --- An

Table-4 Additional CFM for Open Doors


Vel thru # of Doors (7' x 3') Open
Door
1
3
4
25
525
1575
2100
50
1050
3150
4200
100
2100
6300
8400
150
3150
9450
12600

Building Length (fUse square root of floor area if


115
Building Width (ft)
building is not rectangular
104
Stairwell Plan View Length (ft)
10
Stairwell Plan View Width (ft)
10
Temperature of Outdoor Air in Winter (deg F)
-4
To
Temperature of Outdoor Air (deg Rankine)
456
Temperature of Stairwell Air (deg F)
70
Ts
Temperature of Stairwell Air (deg Rankine)
530
DPsbb MIN Press Difference Stair & Bldg at Bottom of Stair (i 0.05
###
B
B = 7.64 * ( 1/To - 1/Ts )
N
Number of Floors
36
Floor to Floor Height (ft)
11
y
Distance between Stairwell Bottom and Top (ft)
396
Asdb Leakage Area between Stairwell Door & Bldg Space per 0.21
Wall Surface Area between Stairwell & Bldg Space per 440
0.0001
Stairwell Wall Tightness Leakage Area (ft2)
Aswb Flow Area between Stairwell Wall & Bldg per Floor (ft 0.048
Exter Wall Surface Area between Bldg and Outside per 4818
0.0002
Building Exterior Wall Tightness Leakage Area (ft2)
Abo
Flow Area between Building & Outside per Floor (ft2) 1.0118
Asb
Total Flow Leakage Area Stairwell & surrounding Spac 0.258
###
DPsbt MAX Press Difference Stair & Bldg at Top of Stair (in)
DPsb AVG Press Difference between Stair & Bldg Space (in) ###
###
X -n
[ (DPsbt)3/2 - (DPsbb)3/2 ]
###
X -d
[ DPsbt - DPsbb ]
###
Q
Supply Air (cfm)
Supply CFM = 16,000

Instructor: Varkie C. Thomas, Ph.D., P.E.


Skidmore, Owings Merrill LLP

16,207
2,100
18,307

for stair pressurization


4 doors open at 25 fpm
Total Fan CFM

No. of Floor No. Fan Total


Floors
Roof
CFM = 16,000
1
Mech-36
2
35
3
34
2,000
4
33
5
32
6
31
7
30
2,000
8
29
9
28
10
27
11
26
2,000
12
25
13
24
14
23
15
22
2,000
16
21
17
20
18
19
19
18
2,000
20
17
21
16
22
15
23
14
2,000
24
13
25
12
26
11
27
10
2,000
28
9
29
8
30
7
31
6
2,000
32
5
33
4
34
3
35
2
2,000
36
1
37
B1

cfm

cfm

cfm

cfm

cfm

cfm

cfm

cfm

cfm

Arch-551 (Fall) Arch-552 (Spring)

Energy Efficient Building Design

College Of Architecture
Illinois Institute of Technology (IIT), Chicago

2,000 cfm

2,000 cfm

2,000 cfm

2,000 cfm

2,000 cfm

2,000 cfm

2,000 cfm

2,000 cfm

2,000 cfm

Instructor: Varkie C. Thomas, Ph.D., P.E.


Skidmore, Owings Merrill LLP

Arch-551 (Fall) Arch-552 (Spring)

Energy Efficient Building Design

College of Architecture

Zone & Stair Pressurization

Illinois Institute of Technology (IIT), Chicago

ASHRAE 1999 HVAC Applications Handboo

for Fire Control

Default User Input

Uniform Building Code (UBC Project User Input

Project Name

Calculated

Table-1: Door Leakage Area

Doors in Series: Leakage Areas = A1 , A2, A3, --- An

Height (ft)

Width (ft)

Area (ft2)

21

Avge 1/8"

0.21

Perim (ft)

20

3/4" Undercut

0.36

Leak-Area (ft2)
A1

An

Table-2: Elevator Doors

Effective Leakage Area (Ae) Doors in Series

Leak Area (ft2)

Ae = [ 1/A12 + 1/A22 + 1/A32 + ----- + 1/An2 ] -0.5

Minimum

0.55

Maximum

0.70

Doors in Parallel: Leakage Areas = A1 , A2, --- An


Effective Leakage Area (Ae). Ae = A1 + A2 + ----- + An

Table-3: Leakage Areas for Walls and Floors

Stairwell Walls

A/As
UBC

Tight

###

Avg

###

Loose

###

Tight

###

Avg

###

Loose

###

Elev. Shaft Wal Tight

Floors & Roofs

Supply only

Qs

Pressurized
Sandwich Floor

###
Exhaust only
###

###

Avg

###

Loose

###

Avg

###

###

###

Exit Enclosures UBC

Normal
An

###

Fire Floor

Qe

Exhaust
Supply only

Qs

Pressurized
Sandwich Floor

Elevators
Shafts

Exterior Walls

A/As
ASHRAE

AC Return

Pressurized Stairs

Construction

Smoke Exhaust

AC Supply

A/As = Leakage Area / Surface Area

Normal
Normal Operation
(All Other Floors)

A1

Fire Floor: Smoke Exhaust Damper is Open. HVAC Supply, Return and Exhaust (TX & GX) Air Dampers are Closed
Sandwich Floors: (above & below fire floor) HVAC Supply Damper is Open. Return and all Exhaust Dampers are Closed
All Other Floors: Smoke Exhaust Damper is Closed. Normal Supply, Return & Exhaust (TX & GX) operating conditions
Color Key
Total Leakage Area between Fire Space and Adjacent Spaces
Fire Space Area (ft2) = 7,400

Elev Shaft Area/Flr (ft2)

950

Floor to Ceiling Height (

Number of Elevators =

A (leakage) / As (floor) 0.0005

A (leakage) / As (elev)

0.0008

Flr & Clg Leakage Area

Elev Leakage Area (ft2)

Total Leakage Area (A)

15.46

12
7.4

Wall Area/Flr (ft2) =

1500

Number of Walls =

A (leakage) / As =

0.0002

Wall Leakage Area (ft2) 1.26


Door Leakage Area per
Number of Doors =
Total Door Leakage =

Project User Input


Calculated
F = Fdc + (5.2 x W x A x DP) / (2 x (W - d))
d = distance from door handle to
latch edge of door (ft)
A = Exit Door Area (ft2) =

Press. Fire Space (in.) =

Press. Adjac Space (in.)

0.05

0.36
5

Default User Input

W = Door Width (ft) =

1.8

Qs = 2610 x A x sqrt(DP)

Instructor: Varkie C. Thomas, Ph.D., P.E.

CFM/FT2 =

1.2

ACH @ Ceiling H

6.1

Skidmore, Owings Merrill, LLP

21
3

DP = Press Diff. Across Door (in 0.05


Fdc = Force to overcome Door
Closing Device (lbf) =

Min Exh fr Fire Space 9,023

0.25

10

F = Exit Door Opening Force 13.0

Arch-551 (Fall) Arch-552 (Spring)

Energy Efficient Building Design

Boston

College of Architecture

British Standards Inst

Stairwell Pressurization

BSI 5588 Part 4 : Fire design 1978


In. H2O to N/m2 (Pa) 248.76

1.7

cfm to L/s

0.472

3.281

m2 to ft2

10.764

m3/hr to cfm
meters to feet

Door Leakage
Door opens rela Ht
Pressurized Sp

Illinois Institute of Technology (IIT), Chicago

Space Pressurization Levels


Wd

Perimter Leak Area


Leak-A / Perim
Bldng Height
Emergency Operation

(1) Single open 2

0.8

5.6

18 0.01 ### ### ### < 12 < 40 50 ###

(2) Single ope

0.8

5.6

18 0.02 ### ### ###>= 12


>= 40 50 ### 15 ###

ft

m2

ft2 m2/mft2/ft

ft

Pa

In

Pa

In

###

Doors in Series: Leakage Areas = A1 , A2, A3, --- Effective Leakage Area (Ae)
Doors in Parallel: Leakage Areas = A1 , A2, A3, --- An
Ae = A1 + A2 + ----- + An
A1

An
A1

Ex: Stairwell (doors in parallel)

SI

Effective Leakage Area (Ae) Doors in Series

IP

Leakage Area/Door ### ###

Ae = [ 1/A12 + 1/A22 + 1/A32 + ----- + 1/An2 ] -0.5

Total floors

36

36

Required Air Supply to maintain pressure difference

Eff. Leakage Area ( ### ###

between Pressurized Space and Adjacent Space

Stairwell Pressure ( 120 ###

Q = 0.827 x A x P0.5

Space Pressure (Pa) 12 ###

Q = Air Supplr (m3/s) to the pressurized space

Supply Air (m3/s### cfm

A = Total effective leakage area (m2)

Supply Air (L/s) ###

P = Pressure Level (Pa) in pressurized spa

###

An

Stair Pressure - Space Pressure


NoteInput to this Program can be entered on the ASHRAE Sheet
You can override the ASHRAE input by entering
data directly in the orange cells
Info from ASHRAE Form or enter input directly
Calculated by Program

Instructor: Varkie C. Thomas, Ph.D., P.E.

Skidmore, Owings Merrill LLP

Arch-551 (Fall) Arch-552 (Spring)

Energy Efficient Building Design

College of Architecture

Illinois Institute of Technology (IIT), Chicago

ign 1978

Instructor: Varkie C. Thomas, Ph.D., P.E.

Skidmore, Owings Merrill LLP

Arch-551 (Fall) Arch-552 (Spring)

Energy Efficient Building Design

College of Architecture

Natural Ventilation

Illinois Institute of Technology (IIT), Chicago

User Input

Wind Only
Q=C4*Cv*A*U

InsideTempTi

50

HourstoMinutes

60

2xgrav.Const

64.4

OpeningAreaft2

100

HeightBot-Topft

110

Flow Due to Thermal Forces


To

Cd

(Ti-To)/Ti

Flow Due to Wind Only

Q=AirFlowRate,cfm

Q
CFM

Cv=OpeningEffectivenessCoeff
A=OpeningArea,ft2

0.525

1.000

265,124

U=WindVelocity,mph

10

0.500

0.800

225,842

g=GravitationalConstant

Dir

10

20

40

60

80

90

20

0.475

0.600

185,806

Spd

Cv

Cv

Cv

Cv

Cv

Cv

30

0.450

0.400

143,725

Thermal Only

mph

0.2

0.3

0.4

0.5

0.6

0.7

40

0.425

0.200

95,983

Q=60*Cd*A*sqrt(2*g*DH*abs(Ti-To)Ti)

50

0.400

0.000

8,800

13,200

17,600

22,000

26,400

30,800

60

0.375

0.200

84,691

Cd=DischargeCoeffforOpening

10

17,600

26,400

35,200

44,000

52,800

61,600

70

0.350

0.400

111,786

DH=DifferenceinOpeningHeights,ft

15

26,400

39,600

52,800

66,000

79,200

92,400

80

0.325

0.600

127,130

Ti=InsideTemp,F

20

35,200

52,800

70,400

88,000 105,600 123,200

90

0.300

0.800

135,505

To=OutsideTemp,F

25

44,000

66,000

88,000 110,000 132,000 154,000

100

0.275

1.000

138,875

30

52,800

79,200 105,600 132,000 158,400 184,800

110

0.250

1.200

138,300

Instructor: Varkie C. Thomas, Ph.D., P.E.

Skidmore, Owings Merrill LLP

Cd=0.4+0.0025*(Ti-To)

Arch-551 (Fall) Arch-552 (Spring)