Académique Documents
Professionnel Documents
Culture Documents
Executive
HSE Books
Page 1 of 60
This guidance is issued by the Health and Safety Executive. Following the guidance
is not compulsory and you are free to take other action. But if you do follow the
guidance you will normally be doing enough to comply with the law. Health and
safety inspectors seek to secure compliance with the law and may refer to this
Page 2 of 60
Contents
Introduction 6
Scope 6
Background 6
Legislation 6
Lack of knowledge 8
Overstressing 8
Modifications 9
Lack of maintenance 10
Anti-reflex handles 10
Management of switchgear 11
Records 12
Network diagrams 12
Asset register 12
Maintenance records 13
Operational issues 13
Overstressed switchgear 14
Modifications 16
Fault clearance 16
General advice 17
Inspection 18
Switchgear environment 18
Maintenance 19
Condition-based maintenance 19
Maintenance procedures 19
Frequency of maintenance 20
Insulating oil 21
Page 3 of 60
General advice 24
Inspection 24
Maintenance 25
Maintenance procedures 25
Vacuum switchgear 26
Air-break switchgear 26
Frequency of maintenance 27
Hazards 28
Sampling 29
Topping up 29
Test probes 30
Earthing equipment 30
Testing 31
Diagnostic testing 31
Condition monitoring 35
Available techniques 35
Thermographic surveys 36
Protection 37
Fuse protection 37
General advice 39
Ratings 39
Replacement installations 40
Refurbished/retrofitted switchgear 40
Refurbishment of switchgear 40
Second-hand equipment 41
Page 4 of 60
Compartmentation 41
Prevention 42
Detection 42
Safety issues 42
Training 43
General advice 43
Disposal issues 44
Insulating oil 44
Capacitors 44
Appendices 46
A Technical definitions 46
B Further reading 48
Page 5 of 60
Introduction
Scope
3 This book provides guidance on the selection, use, care and maintenance of
three-phase electrical switchgear with voltage ratings from 400 V alternating current
(ac) up to and including 33 kV ac. It deals with circuit-breakers, switches, switch
fuses, isolators and high-voltage (HV) contactors. The types covered embrace
switchgear using oil, air, sulphur hexafluoride (SF6) or vacuum as the interrupting
medium.
4 The guidance does not address direct current (dc) switchgear, switchgear used
on single-phase ac traction systems of any voltage, low-voltage moulded case
circuit-breakers, or low-voltage contactors and miniature circuit-breakers.
Background
5 In general, switchgear has a proven record of reliability and performance.
Failures are rare but where they occur the results may be catastrophic. Tanks may
rupture and, in the case of oil-filled switchgear, can result in the ejection of burning
oil and gas clouds, causing death or serious injury and major damage to plant and
buildings in the vicinity of the failed equipment.
6 Modern switchgear using sulphur hexafluoride gas or vacuum as the insulating
medium has removed the hazard of burning oil but inevitably has introduced other
risks that need to be managed. Accident experience has shown that failure usually
occurs at, or shortly after, operation of the equipment. So the way switchgear is
operated, its condition and the circumstances existing in the system at the time of
operation to a large extent determine whether the equipment will function safely.
7 Switchgear of all types and ratings has been manufactured in accordance with
British and international standards for over 60 years. As with most equipment,
current specifications bear little resemblance to those of earlier years and the
previous specifications have been shown, by subsequent experience and by
technical developments, to be deficient. Examples of differing requirements
between earlier and current standards are those relating to operating mechanisms
and fault test sequences.
Page 6 of 60
Legislation
8 The Health and Safety at Work etc Act 1974 (HSW Act), the Management of
Health and Safety at Work Regulations 1999 (Management Regulations) and the
Electricity at Work Regulations 1989 (EAW Regulations) apply (see Appendix B
Further reading).
9 The HSW Act contains requirements to the effect that anyone employing
people should ensure their safety so far as is reasonably practicable.
10 The Management Regulations require an employer (or self-employed person)
to make an assessment of risks to employees or others, taking specialist
advice where necessary. The level of detail in the assessment should be broadly
proportionate to the risk, which means it needs to be fairly detailed in the case of
switchgear as the risk is one of serious injury or even death.
11 The EAW Regulations require electrical equipment for use at work to be
constructed, maintained and operated in such a way as to prevent danger so far as
is reasonably practicable.
12 Equipment should not to be used where its strength and capability may be
exceeded and it should be protected from excess current. This is discussed in
paragraphs 22 and 23 (see also EAW Regulations, regulation 5).
13 In any premises that require a high-voltage supply, that incoming supply often
passes through switchgear to control distribution of electricity within the site.
Switchgear varies in size, age and appearance. Typical examples are shown in
Appendix C. It is important to recognise that the different categories of switchgear,
ie switches, isolators, switch fuses, HV contactors and circuit-breakers, have a
different switching capability and you need to be familiar with the switchgear types
on the site and their purpose.
14 Switchgear is generally located in substations and/or switchrooms, ie areas
that are separated from the day-to-day activity of the premises and which, in
many instances, are visited on a very infrequent basis. Such rooms are generally
locked and access is usually restricted to authorised persons. Periodic inspection
of switchrooms is considered good practice to ensure that deterioration is
not occurring to either the switchgear or the environment. For example, it is
unacceptable for any building damage to cause water or debris build-up on
equipment that is for indoor use. Procedures should be in place to detect and
rectify such faults as quickly as possible.
15 In some premises, low-voltage switchgear will be located in work activity
areas. There will also be cases where high-voltage switchgear and motor starters
are found adjacent to the machinery that they control. It is important that the
equipment is in good condition. Operatives in the area should be made aware of
this and procedures put in place for them to report incidents and/or any damage
that occurs.
16 Occasionally switchgear is located outdoors. This can lead to even fewer
visits than to switchgear located in switchrooms and again a practice of periodic
inspection is necessary, along with procedures to deal with any deterioration that is
found.
Page 7 of 60
17 Much of the equipment still in service is some 25 years old or more. Equipment
that is 35 or more years old is usually of particularly robust construction. As a
result, it is often assumed (incorrectly) that the equipment has an unlimited life in
service. Much of the older equipment has a limited operation capability and these
limitations are not always understood by operating staff. An example of this is a
situation where a defined delay before operation is necessary after a fault clearance
to allow time for the arc extinction processes to recover.
Lack of knowledge
19 Switchgear should be operated by trained staff, who are often known as
authorised persons. In the past these were generally works electrical engineers
and senior supervisors but due to changing employment patterns this is no
longer the case. Some users may not have any authorised persons on their staff
and may have chosen to contract out all operational work and maintenance of
their switchgear. As a result, there may be no one within the organisation who
understands the equipment, its safe operation or the need for maintenance. This
should be treated as unacceptable and steps should be taken to remedy the
situation.
20 Staff responsible for care, operation and maintenance of switchgear should
receive training (or refresher courses) relevant to the duties that are required of
them. This is particularly relevant to staff called upon to operate switchgear and
such staff should have competency at the authorised person level. Even where
all operational and maintenance work is contracted out, it is preferable that there
is sufficient technical knowledge within the company to audit the practices of
the contractors and to handle abnormal (including emergency) situations that will
inevitably arise on the premises. If this is not the case, this role should be given to
an independent organisation.
21 A number of organisations (eg electricity distribution companies or specialist
training organisations) provide training courses to the varying levels of competency
that may be required.
Page 8 of 60
Overstressing
22 Switchgear is described as being overstressed when the potential fault
energy of the electrical system (eg from a short-circuit) at the switchgear location
exceeds the fault energy rating of the switchgear. When it is operated under fault
conditions it is unable to cope with the resulting electrical and thermal stress that
can sometimes lead to catastrophic failure, ie total destruction of the switchgear.
Such failures are accompanied by arc discharge products, burning gas clouds and
oil mist (if oil switchgear). These envelop anyone near the switchgear, resulting in
serious burn injuries and often death.
23 While the original installation design may have been adequate, modifications
and extensions to the network that feeds the switchgear, or of the network
controlled by it, can lead to situations where the switchgear is overstressed. An
example is where the infeed capacity has been increased. Also some configurations
of the network (eg by paralleling of transformers onto the switchgear busbars) can
lead to an overstressing situation. Such situations should be documented and
clear operating instructions provided to prevent such a configuration being created.
They can result from a response to an abnormal operational situation whereby an
incorrect network configuration is inadvertently set up.
Modifications
24 Over the years, manufacturers have issued details of modifications to existing
equipment that should be carried out on switchgear to improve its safety. However,
the procedures for circulating such information are not perfect and in many cases
users are unaware of the need to carry out these modifications. As a result, the
equipment may be incapable of performing satisfactorily. It would be wise to carry
out an audit, if one has not already been undertaken, of the switchgear for which
the user is responsible and liaise with the manufacturers (or other appropriate
expert) to identify any outstanding modifications.
25 It is also good practice to catalogue any circulars or instructions that are
received relating to modifications and make them readily available to all staff whose
duties involve the operation and maintenance of switchgear.
Page 9 of 60
27 With DMO switchgear, the operator closes or opens the switchgear solely
by manual effort. Therefore movement of the contacts is totally dependent upon
the speed and actions of the person operating the levers/handles. Any hesitancy
on the part of the operator is likely to lead to a serious and potentially fatal failure
of the switchgear, eg operators may not realise that they have failed to close the
circuit-breaker completely and release the operating lever/handle, thus drawing
an arc within the oil tank which can result in catastrophic failure. It is essential
that these levers/handles are operated in a decisive and positive manner without
any hesitation and as rapidly as possible, particularly over the latter portion of the
closing operation. In addition, should a lever/handle be closed onto a system fault,
the force needed is significantly greater than when closed onto normal system load
current. In some cases it may be physically impossible to close (or open) the device
under fault conditions, again this may result in failure. See paragraphs 54-58 for
guidance on actions to take in these situations.
Lack of maintenance
28 This is usually the result of oversight, lack of knowledge of the equipment, or
pressures to avoid plant shutdowns. Whatever the cause, it will lead to a situation
where switchgear has been neglected (this is particularly true of low-voltage
devices). The result is that routine servicing such as oil changing, lubrication,
contact refurbishment, and verification of contact engagement may not have
been carried out for many years and deterioration due to corrosion may also have
occurred. In some cases the expertise in maintenance techniques and for handling
insulating oil is lacking.
29 Where oil-filled switchgear has been neglected, it is difficult to assess the
actual fault capability of the switchgear in the state in which it is found. An audit of
maintenance records should be carried out to establish whether or not there is a
problem and, if necessary, a detailed condition assessment should be made.
Anti-reflex handles
30 At one time, a common cause of accidents/incidents with high-voltage
switches was when an operator carried out an incorrect operation when moving
the operating handle (eg switching from OFF to EARTH instead of from OFF to ON)
and then immediately attempted to reverse that incorrect operation. As oil switches
are not rated for the interruption of fault current, any attempt to open them when
fault current is flowing is likely to lead to disruptive failure, with the possibility of the
operator(s) being killed.
31 To address this problem, many manufacturers have produced anti-reflex
operating handles for their equipment. These handles are one-way operating
devices and have to be removed and relocated before carrying out a further
operation, thus imposing a time delay between operations. This built-in time delay
means that when the incorrect operation is reversed, no fault current is flowing (as
the circuit protection will have operated to interrupt the current flow), and there is
no likely failure of the switch. The built-in time delay is also important when closing
from OFF to ON onto a known fault.
32 A review of the oil switches and oil switch fuses should be undertaken to
determine whether an anti-reflex facility exists. Where no such facility exists, action
should be taken to retrofit an appropriate modification.
Page 10 of 60
Management of switchgear
33 It is the duty of all users of switchgear to provide management systems that will
ensure safe operation and minimise the risk of injury. Such management systems
should include the following:
(a) policies and procedures covering the installation, commissioning, operation,
maintenance and removal of the equipment;
(b) an appropriate system of records;
(c) definition of responsibilities and training requirements;
(d) auditing of the effectiveness of procedures.
34 An important pre-requisite is to identify all switchgear in service and to
ensure that up-to-date records of network diagrams and configurations (including
prospective fault level values at every relevant point on the system) are available.
From this basic information, any potential risks, eg overstressing or dependent
manual operation, should be assessed so that any necessary remedial action can
be identified to ensure that the equipment and systems are being operated safely,
and that work is put in hand to eliminate or reduce the risks. The basic records for
an LV installation may also contain electrical installation certificates and periodic
inspection reports. Further information is in BS 7671 (see Appendix B Further
reading).
35 Sufficient technical expertise may not be available in-house to carry out a risk
assessment and decide on the appropriate precautions. In such cases switchgear
users should take advice from suitably competent organisations, including:
(a) electricity distribution companies;
(b) switchgear manufacturers;
(c) switchgear maintenance companies with particular expertise in older types of
switchgear;
(d) consulting organisations specialising in switchgear.
36 The British Electrotechnical and Allied Manufacturers Association (BEAMA)
can provide up-to-date details of manufacturers and the Institution of Electrical
Engineers (Presidents list of experts) may also be able to provide help and
guidance as to other sources of information and expertise (see Appendix D for their
addresses).
Page 11 of 60
Records
37 All switchgear users should have a record of their switchgear available. Where
there are doubts about the accuracy or validity of records then a new inventory
should be prepared as a matter of urgency. The basic records that are suggested
are discussed below.
Network diagrams
38 The diagram is a schematic representation of the network and it is ideal to
display the interconnection of the plant items, including the switchgear. This allows
the normal and any alternative arrangements of the network to be displayed
in a way that is readily understood, bearing in mind that there may be several
switchrooms or substations on any one site. In addition, the diagrams can be
annotated with the status of the switchgear in a particular network arrangement to
avoid any confusion, particularly where overstressing may be an issue.
Asset register
39 An asset register forms the basis of management information providing both
basic identification information (location, type etc) and performance/maintenance
records. Although some items may not be scheduled to receive any routine
maintenance, all items that are likely to receive some kind of attention during their
life should be included. A hierarchical structure is essential to ensure a logical
approach to establishing information for asset management purposes. It is possible
to develop complex hierarchies, but most asset owners find that a two- or threelevel hierarchy is sufficient. A typical structure might involve:
Level 1: Location/cost centre/process or production grouping
Equipment associated with an activity, eg production department.
Level 2: Unit
Collection of plant items that are interdependent and adjacent to each other in
Level 1.
Level 3: Item
Distinct item of plant within the unit, usually the smallest discrete piece of
equipment from an operational point of view, eg item of switchgear, tripping battery
etc.
40 Use of a hierarchical structure allows the straightforward development of an
asset numbering system, eg an item can be coded as a combination of the cost
centre code, the unit code and its own code to provide a unique code.
41 Along with the structure, the level of information to be recorded against
each item needs to be decided. Collecting plant data can be a time-consuming
and costly exercise, particularly basic data that does not directly contribute to
improvements in performance and safety. Care should be taken not to collect too
much basic data and typical information that is required for an item of switchgear at
each location includes:
(a)
(b)
(c)
(d)
Page 12 of 60
(e)
(f)
(g)
(h)
voltage rating;
current rating;
fault rating and whether it is a certified or assessed and assigned rating;
type of operating mechanism (dependent manual, independent manual,
dependent power, independent power and stored energy);
(i) details of any modifications, eg fitted anti-reflex handles;
(j) if the equipment is an oil circuit-breaker, whether it is plain break equipment
(ie equipment without arc control devices) or not;
(k) type of electrical protection fitted and details of the settings.
Maintenance records
42 A minimum requirement would be to record:
(a) the date of the last maintenance/oil change (where applicable);
(b) in the case of a circuit-breaker, the number of fault operations since it was last
maintained (if known).
43 This provides a record that maintenance schedules are being adhered to and
also provides planning for the next maintenance. As will be seen in later sections,
some measurements are taken during the maintenance and it is valuable to record
such data in order to determine trends in performance and what problems are
emerging. Such records should be retained as a history and the information should
not overwrite the previous record.
Operational issues
Page 13 of 60
46 Other than for the simplest of system configurations, the calculation of fault
levels is a specialist topic requiring support from people experienced in undertaking
and interpreting such calculations.
Page 14 of 60
(d) Reduce the fault energy levels, if possible. In some cases changing system
operating conditions will achieve this, for example operating transformers as
single feeders to switchboards and not in parallel with other transformers.
These changes should be made as soon as possible to reduce the fault energy
level to as low as practicable.
(e) Longer-term measures that can be taken to reduce fault energy levels include
fitting reactors or network reconfiguration. These measures may be used to
reduce fault energy levels to values less than the fault energy ratings of
switchgear. Such actions are normally only a solution for high-voltage
installations. It should be noted these measures will not overcome the problems
associated with switchgear that has no fault energy rating.
50 Where the actions (d) and (e) above reduce the fault energy levels below
the rating of the switchgear, then electrical protection and live operation can be
restored, after necessary measures (eg interlocks) have been provided to prevent
the rating being exceeded at any time.
51 If the actions (d) and (e) in paragraph 49 do not reduce the fault energy levels
below the ratings of the switchgear, and it is sited in open workshop areas, the
provision of blast protection should be considered. This may take the form of
suitable walls or enclosures, the purpose of which is to contain any failure of the
switchgear while it is energised. However, this is a complex matter and it is often
more practicable to make the switchgear dead and provide alternative electrical
supplies.
52 Where high-voltage and low-voltage switchgear share the same switchroom
and only one set of switchgear is overstressed, it will be necessary to either:
(a) keep personnel out until the overstressed switchgear is made dead; or
(b) where space permits, erect a suitable blast wall around that switchgear, thus
permitting personnel access to the other switchgear.
53 In addition to these immediate actions, arrangements should be made to
replace the overstressed switchgear as soon as possible.
Dependent manually operated (DMO) switchgear
54 Dependent manually operated (DMO) mechanisms are generally only found on
older types of oil and air circuit-breakers.
55 All operation and maintenance of DMO switchgear should be restricted to those
personnel trained in the operation of the switchgear concerned. They should also
be aware of the dangers of operating the equipment incorrectly, the construction of
the switchgear and the manufacturers maintenance requirements. The personnel
will need to be familiar with the safe system of work outlined in paragraph 56. It
is essential that the actions listed to allow continued use of DMO switchgear be
treated as short-term measures only.
56 Where the switchgear is not overstressed (ie ratings are greater than the actual
fault energy levels), the following precautions are needed to reduce the risks that
result from the fact that it has dependent manual operation:
(a) All DMO switchgear should be maintained in accordance with the
manufacturers advice. This should include, where applicable, the checking
of seals and gaskets, which should be properly installed and in good condition.
An annual maintenance schedule for this equipment should be prepared and
be implemented.
Page 15 of 60
(b) Power closing mechanisms should be fitted as a matter of urgency to all high
voltage DMO switchgear (ie 3.3 kV and above). However, this should only be
carried out in accordance with the manufacturers advice. It may not be
possible to obtain the necessary guidance and advice where the original
manufacturer no longer exists and there are no agents. In these cases it is
not advisable to fit power closing mechanisms.
(c) A phased replacement programme should be prepared and implemented for all
DMO switchgear manufactured prior to 1960 and for those high-voltage
systems manufactured and installed after 1960 that cannot be fitted with
power closing mechanisms. In some cases it is possible to obtain replacement
circuit-breakers of modern design (often called cassettes), which can be used
to replace old high- and low-voltage units and can use the existing switchgear
busbar housings and support arrangements. This approach can mitigate the
cost of replacement. Advice should be sought from the manufacturer regarding
this approach see also the section on Selection of new, replacement or
refurbished switchgear (paragraphs 163-175).
(d) When DMO switchgear is to be closed, the preferred method of operation is as
follows (in order to achieve this preferred method of operation it may be
necessary to change system running conditions and adjust the electrical
protection accordingly):
make the system dead upstream using a suitably rated independent
operated switch or circuit-breaker;
check, where practicable, the system beyond the DMO switchgear to
ensure that it is fault-free. This will mean applying various electrical
tests to the system;
if the system is healthy, close the DMO switchgear to ON; and
energise the system from the remote point, ensuring that no personnel are
in the vicinity of the DMO switchgear.
Page 16 of 60
63 Various actions can be taken to minimise these risks of catastrophic failure and
these are set out below, together with the problem areas they address:
(a) Inspection (non-intrusive)
An external inspection will address obvious signs of abnormal condition that are
detectable by sight, smell and sound.
(b) Maintenance (intrusive)
Maintenance under outage conditions will address problems due to mechanism
defects, insulating oil contamination and deterioration, erosion of contacts and
arc control devices.
(c) Condition monitoring/assessment by partial discharge techniques
These techniques can be used to detect and locate deterioration of solid insulation.
(d) Refurbishment/replacement
This approach can be taken to address problems caused by inadequate rating,
inadequate operating mechanism or arc interruption system, or deteriorated or
defective insulation.
64 The sections below look at the inspection and maintenance actions in detail.
There is information on condition monitoring and assessment techniques in
paragraphs 146-152 and on refurbishment and replacement options in paragraphs
163-175.
Page 17 of 60
Inspection
65 A regular substation inspection is recommended. At the time of the inspection
any remedial work should be prioritised, so that it is carried out:
(a) immediately (this should always be the case when security of the substation
enclosure has been interfered with);
(b) at the earliest possible opportunity; or
(c) at the next scheduled maintenance.
66 An inspection schedule would be expected to include the following items.
Switchgear environment
67 An inspection sequence for the switchgear environment should include the
following aspects:
(a) switchroom access and surrounds (including fence and external walls, if
outdoors);
(b) signs of trespass and/or interference;
(c) presence and legibility of warning notices;
(d) switchroom internal fabric;
(e) firefighting equipment;
(f) general housekeeping;
(g) signs of water ingress/dampness in switchroom.
Signs of abnormal condition
68 A check for any abnormal conditions should be carried out immediately on
entering the substation and if any danger is suspected then the inspection should
be aborted. Typical warning signs are:
(a)
(b)
(c)
(d)
(e)
(f)
(g)
(h)
Page 18 of 60
Maintenance
72 Detailed guidance on the maintenance of electrical switchgear can be found in
BS 6423: 1983 and BS 6626: 1985 (see Appendix B Further reading).
Time-based preventive maintenance
73 Oil-filled switchgear was designed and introduced at a time when the
predominant maintenance philosophy consisted mainly of equipment overhauls at
fixed intervals. Time-based maintenance has been and continues to be applied to
such switchgear. Manufacturers recommendations are available to determine the
maintenance programme and advice can be sought from specialist organisations.
74 Rigorous application of such schedules has provided high levels of reliability,
whereas neglecting maintenance can lead to a switchgear condition where its
ability to perform all its duties safely and satisfactorily is not easy to ascertain. So it
is essential that oil-filled switchgear is properly maintained and the application of a
correctly implemented time-based maintenance programme is a well-proven route.
Condition-based maintenance
75 In recent years attention has focused on condition-based maintenance
where maintenance is dictated by need as revealed by inspections and condition
monitoring techniques or predictive maintenance methods. Some users have
moved to this approach but only after careful assessment of the parameters to be
monitored, techniques for acquiring the condition data and, most importantly, an
understanding of the degradation mechanisms affecting the switchgear and the
criteria on which the decisions to take action are based.
76 When considering moving to a condition-based maintenance approach, the
options available need to be carefully assessed. This should be done preferably
with the assistance of organisations with experience in this area, since the
performance of switchgear is influenced by the electrical and environmental
conditions under which it operates. Simply applying techniques and criteria from
another industry section may not be appropriate.
Reliability-centred maintenance (RCM)
77 RCM can assist in the process of determining the maintenance policy because
it analyses maintenance tasks in a structured way to determine the maintenance
requirements of any item of equipment in its operating context. It does so by taking
account of plant usage and condition, the causes and consequences of failure, and
the required performance standards of the organisation. See Appendix B Further
reading for details of publications which provide more background information on
RCM.
Maintenance procedures
78 Whatever the approach used to determine when maintenance is required, it
is important that the intrusive maintenance work is undertaken in a structured
manner in accordance with a documented procedure/checklist.
Page 19 of 60
Frequency of maintenance
81 Switchgear should be maintained at a frequency appropriate to the equipment.
The manufacturer, or others, may be able to give advice on this but difficulties
exist in defining the frequency. These are affected by operating policies, types
of switchgear and the reliability requirements. An industrial user whose activities
depend on the reliability of power supply may institute more frequent maintenance
as a means of guarding against power failures than (say) a distribution company
where the duplication built into the network allowing alternative supplies means that
a higher risk of malfunction may be acceptable.
82 Overstressed and/or DMO switchgear needs special attention. If any such
switchgear has not been maintained within the past three years, then maintenance
should be carried out immediately and thereafter on a frequent basis.
83 Trip-testing of oil circuit-breakers provides an operational test and exercises
the mechanism. It can be carried out more frequently than the internal
maintenance, within operational constraints. Annual trip-testing is considered a
suitable frequency by many users and, if combined with tripping via the protection
scheme, also confirms that satisfactory (or otherwise) operation of the complete
tripping system will occur under fault conditions.
Keeping electrical switchgear safe
Page 20 of 60
Insulating oil
89 The reliable performance of oil-filled switchgear depends on the maintenance
of certain basic characteristics of the mineral insulating oil. It is essential that any
new, reclaimed or reconditioned insulating oil is tested prior to being introduced into
equipment to ensure that it meets the required level of performance.
90 Sampling of oil in service can provide valuable information on the deterioration
of the oil and of the switchgear itself and the materials contained within it.
Laboratories with long experience of testing oil samples can provide assessments
of the state of a users switchgear and of the validity of the maintenance
programme. Guidance on the monitoring and maintenance for mineral insulating
oils in electrical equipment is provided in BS 5730 (see Appendix B Further
reading). This includes values and significance of standardised oil tests and uniform
criteria for the evaluation of test data, along with practical details on:
(a) sampling techniques;
(b) testing procedures and assessment criteria;
(c) handling and storage of oil samples.
Page 21 of 60
Page 22 of 60
98 Fungal growth can occur in insulating oil that contains free water. The growth
occurs at the interface between water from below and the carbon compounds from
above. The most common fungal growth identified in insulating oil is Cladosporium
Resinae. While it is rare to find fungal growth in insulating oil, any occurrence
needs to be dealt with because as the fungus grows the oil is degraded, producing
more water and various volatiles and acidic conditions that can cause corrosion of
materials. The production of water and resultant corrosion of materials in contact with
the oil will also reduce the insulating properties of the oil.
99 The spores of Cladosporium Resinae are airborne. They can lay dormant for
periods of time and germinate when adequate moisture becomes available. Growth
of the fungus from germinated spores can occur in a temperature range of -25C to
40C. Biocides can be used to kill the spores and it is important to eradicate them
because if they are not destroyed the fungal growth is likely to reoccur.
Page 23 of 60
inspection;
maintenance;
condition monitoring/assessment;
refurbishment/replacement (more likely to be relevant for air-insulated
switchgear as sulphur hexafluoride and vacuum types are modern designs).
Page 24 of 60
Inspection
109 A regular substation inspection is recommended, as discussed for the oil-filled
switchgear in paragraphs 65-71. This should cover:
(a) switchgear environment;
(b) signs of abnormal condition;
(c) switchgear general condition (for sulphur hexafluoride equipment the gas
pressure gauge should be checked, a pungent smell indicates gas leakage);
(d) checks on all the plant items in the substation.
Maintenance
110 Detailed guidance on the maintenance of electrical switchgear can be found in
BS 6423: 1983 and BS 6626: 1985 (see Appendix B Further reading).
111 Sulphur hexafluoride and vacuum switchgear is designed to be low
maintenance but that does not mean that maintenance can be ignored.
Maintenance using a time-interval approach, based on manufacturers
recommendations, may be applied to such switchgear. Rigorous application of
such schedules should provide high levels of reliability.
112 Condition-based maintenance is an option where maintenance is dictated by
need as revealed by inspections and condition monitoring techniques or predictive
maintenance methods. As with oil-filled switchgear, this requires careful assessment
of the parameters to be monitored, techniques for acquiring the condition data
and, most importantly, an understanding of the degradation mechanisms affecting
the switchgear and the criteria on which the decisions to take action are based.
Before a user considers moving to a condition-based maintenance approach,
the available options should be carefully assessed, preferably with the assistance
of organisations with experience in this area. The performance of switchgear is
influenced by the electrical and environmental conditions under which it operates
and simply applying techniques and criteria from another industry sector may not
be appropriate.
113 Reliability-centred maintenance (see paragraph 77) can assist in the process
of determining the maintenance policy because it analyses maintenance tasks
in a structured way to determine the maintenance requirements of any item of
equipment in its operating context. It does so by taking account of plant usage
and condition, the causes and consequences of failure, together with the required
performance standards of the organisation.
Maintenance procedures
Sulphur hexafluoride switchgear
114 The maintenance work should essentially include:
(a) inspection of the external condition;
(b) checking of gas pressure;
(c) if topping up of the gas is necessary, then refer to precautions in paragraph
130;
(d) inspection, adjustment and lubrication of mechanisms (including shutters where
appropriate);
Page 25 of 60
Page 26 of 60
Page 27 of 60
Page 28 of 60
128 Where there is any work on equipment which involves contact with sulphur
hexafluoride or its decomposition products, then the staff should observe the
following precautions:
(a)
(b)
(c)
(d)
(e)
(f)
(g)
Sampling
129 The majority of modern switchgear up to 33 kV uses sealed containment
with the sulphur hexafluoride gas at a small, positive gauge pressure (typically 0-1
bar gauge). This type of equipment is completely assembled, filled with sulphur
hexafluoride and tested in the factory and no further handling of the gas is required
during its expected operating life. However, there may be occasions where
sampling and testing of the gas is required. As indicated above, care must be
taken not to release gas into the atmosphere and also to treat it as contaminated
gas. Guidelines for assessing the quality of the gas are available in BS 5207 and
BS 5209. These also provide guidance on quality of new gas and gas to be used
for topping-up switchgear.
Topping-up
130 It may be necessary to top-up the quantity of sulphur hexafluoride within
switchgear if the pressure is found to be below the optimum pressure for that type
of equipment. It is essential that the additional sulphur hexafluoride used be of a
known and satisfactory quality and tested for quality before it is introduced. Where
recycled gas is to be used then specialist equipment is available.
Page 29 of 60
Earthing equipment
133 The earthing equipment for switchgear can be categorised as:
(a) integral part of the permanent operating mechanism of the switchgear;
(b) extensible a system of probes that are attached to a circuit-breaker truck
which can then be racked into an earth position;
(c) portable a system of probes for insertion into the switchgear spouts and
leads for connection to a suitable earth point.
134 This section is concerned with the care and maintenance of the latter two
types (extensible and portable) since these are separate, removable items unlike
the integral types, which will be dealt with as part of the maintenance regime of the
switchgear itself.
135 Portable and extensible types of earthing equipment are vital pieces of safety
equipment and so it is essential that these should be inspected on a regular basis.
Including them in an asset register (see paragraph 39) will allow a regular inspection
instruction to be generated and ensure that this is not overlooked. Use of, for
example, a safety colour-coding procedure to indicate the current period for use will
ensure that equipment that is outside that period is not inadvertently used.
Page 30 of 60
Testing
Tests to be undertaken during commissioning
137 The commissioning of new (or refurbished) switchgear requires detailed testing
to confirm the functionality of the switch or circuit-breaker, secondary wiring,
protection, indications etc. This requires a detailed checklist of all relevant items
and is beyond the scope of this document. Commissioning should normally be
carried out by the manufacturer or main contractor installing the switchgear, who
will have the necessary experience and expertise to cover all the necessary actions.
Page 31 of 60
145 The risk of catastrophic failure (particularly in the case of oil switchgear)
increases with age and so a process of assessment is needed in order to decide
on the appropriate action for dealing with aged switchgear in service. Such an
approach should incorporate condition assessment where appropriate. Application
of this process will enable rational decisions to be made on whether to retain,
refurbish or replace each switchboard and allow investment to be directed to best
effect. The decisions are made on the basis of condition and on the potential risk of
leaving individual switchboards in service. The decision-making process follows the
assessment actions displayed in the following flowcharts.
Phase 2
Condition assessment
Phase 1
Phase 4
Initial considerations
Phase 3
Information assessment
Page 32 of 60
Phases
2 and 3
YES
REPLACE SWITCHGEAR
Notes:
(a) If the switchgear has either a dependent manual operating mechanism or, in
the case of oil circuit-breakers, plain break contacts (ie no arc control system),
then it is strongly recommended that it be scheduled for early replacement (or
upgrading if practicable).
(b) If the calculated fault level at the switchboard exceeds the switchgear fault
rating and there is no possibility of reconfiguring the network to reduce the
fault level, then usually the only viable option will be to replace the switchgear
with modern equipment of an adequate rating.
Page 33 of 60
Visual inspection
of switchgear and its environment
+
Sample internal examinations
+
Assessment of condition of insulation by partial
discharge detection/ monitoring (and/or other
appropriate diagnostics)
Notes:
(a) If the switchgear is not to be replaced as a result of the Phase 1
considerations, it will be necessary to carry out condition assessment in order
to establish the suitability of the switchgear for continuing service.
The condition assessment should embrace a mixture of external and internal
examination, together with appropriate diagnostic tests to ascertain the
condition of HV insulation.
(b) Information on diagnostics for assessing insulation condition is provided in the
Conditioning monitoring section (paragraphs 146-152).
Consideration of:
Q Fault and defect history
Q Maintenance records/policy/costs
QCondition of enclosure
QSpares availability
Q Operational and network planning issues
additional capacity requirements
redundant circuits
remote control requirements
presence of other plant
Note:
The above information needs to be acquired from the appropriate sources and
assessed.
Page 34 of 60
REPLACE
SWITCHGEAR
Decide on
prioritisation
REFURBISH
SWITCHGEAR
PARTS
Where technically and
economically viable
(eg retrofit CB trucks)
RETAIN
SWITCHGEAR
and REVIEW
MAINTENANCE
Q frequency
Q procedure
Q condition monitoring
Note:
If it is decided to retain the switchgear in service, an estimate of remaining life
should be made and the maintenance regime modified to include regular condition
monitoring.
Condition Monitoring
Available techniques
Partial discharge detection
146 Partial discharge (PD) measurements provide a powerful technique to diagnose
the condition of insulation in high-voltage plant. A number of specialist service
companies are able to undertake PD measurements and provide interpretative
guidance on the significance of specific measurements. The following non-intrusive
techniques are available using portable instruments:
(a) measurement of transient earth voltages (TEVs);
(b) ultrasonic detection;
(c) radio frequency interference (RFI) detection.
147 Some surface discharges are best detected using ultrasonic detection
equipment and in practice a combination of TEV and ultrasonics is generally
used on indoor, metal-clad switchgear. RFI can also be used to detect some
advanced partial discharge activity but the technique is limited in application. Where
necessary, the partial discharge measurements are supplemented with intrusive
tests (PD, loss angle and capacitance) and visual inspection to pinpoint the precise
nature of a problem.
148 On strategically important switchboards, permanent partial discharge
monitoring can be considered based on the TEV principle.
Page 35 of 60
Thermographic surveys
149 Infra-red techniques use either thermal imaging equipment or non-contact
thermometers. The techniques are useful for detecting overheated conductors,
connections and fuses on open-fronted, low-voltage distribution boards or on
other low-voltage switchgear where live parts can be safely exposed and remotely
scanned. These techniques are not particularly useful for indoor high-voltage,
metal-clad switchboards but can detect overheating bushings and connections on
open terminal switchgear.
Mechanism timing tests
150 Many problems in circuit-breakers are attributable to distortion or damage of
the metal parts or stiction in the mechanism causing failure to open or close, or
slow opening of the circuit-breaker. Detection of a problem in a mechanism may
not be fully dealt with by invasive maintenance and in fact may be more effectively
dealt with by incorporating timing tests into the periodic trip-tests which can be
carried out at the time of, or independently of, maintenance activities. As well as
straightforward timing, the use of trip-profile instruments provides a more detailed
appreciation of the mechanism performance and is potentially a valuable additional
test that can be incorporated into the routine trip-testing procedure. A number of
instruments are available on the market and specialist organisations can provide a
testing and assessment service.
Page 36 of 60
Protection
Protection relay schemes
153 The protection relays and associated systems should be subjected to regular
inspection and diagnostic testing in addition to routine maintenance actions.
Diagnostic testing will give an indication of the condition and comparison of test
results with records of previous results will provide a guide to possible deterioration
and assist in determining the appropriate testing/maintenance interval. This
procedure is valuable for estimation of trends.
154 Insulation resistance testing should be carried out on the secondary wiring
associated with the protection, including any pilot wires if they form part of the
protection circuitry. This is important since current leakage across the wiring will
affect the characteristics of the protection scheme and may have a detrimental
effect on the operation and discrimination of the protection scheme.
155 The checks and actions carried out for protection relay schemes should
include:
(a) ensuring relay settings are correct;
(b) inspection for condition, damage and deterioration. For an electromechanicaltype relay this should include checks that:
relay movement runs freely;
magnet gaps and induction disc are clean;
contacts are not burnt or pitted (refurbish as necessary);
induction disc resetting time (electromechanical IDMT relays);
flag mechanisms and reset knobs operate correctly;
front cover glass and seals are satisfactory;
current transformer shorting contacts operate satisfactorily;
(c) secondary injection tests to check operating characteristics. These tests will be
dependent on the protection type (instantaneous and IDMT overcurrent/earth
fault, directional, auto-reclose, unit, distance, motor protection etc) and whether
time-limit fuses are used. Guidance on the test procedure can be obtained from
manufacturers or specialist testing companies;
(d) checking the correct operation of load ammeters and any other instruments;
(e) insulation resistance testing.
(f) trip-testing of the circuit-breaker from the protection;
(g) inspection of the associated current and voltage transformers where
appropriate.
Fuse protection
156 For switchgear where the protection is dependent on fuse operation (eg switch
fuses and fuse switches) then the operation tests involve carrying out fuse trip-testing
(a test-trip fuse can be used if available) to ensure that:
(a) single fuse operation causes all other phases to operate;
(b) the manual ON/OFF trip mechanism operates correctly.
Page 37 of 60
157 Batteries for circuit-breaker tripping and closing supplies play a vital role in
the overall performance of the switchgear. The batteries and associated chargers
need an appropriate maintenance regime in order to ensure consistent and reliable
performance.
158 The battery/charger installation should be regularly inspected, tested and
maintained. The level of maintenance attention will depend on the type of battery
and type of charger system in use. The battery manufacturers operation and
maintenance instructions should be followed, and in particular, the recommended
charging rates should be adhered to.
159 All work on substation batteries needs to be carried out in accordance with the
safety rules applicable to the work and only insulating tools complying with BS EN
60900 (see Appendix B Further reading) and other suitable equipment are to be
used.
160 Care needs to be taken to ensure that removal of connections does not
inadvertently immobilise the switchgear or associated equipment.
161 Smoking or the use of naked flames should not be allowed in the proximity
of battery installations and the production of sparks should be avoided due to
inadvertent short-circuiting of cells.
162 When batteries are replaced it is important that the existing battery charger is
compatible with the new batteries and old batteries are disposed of, observing the
relevant environmental legislation.
Page 38 of 60
164 A major factor in such a decision is to obtain some technical confidence that
the high-voltage insulation components of the busbar system, current transformer
chambers, cables and terminations etc have adequate remaining life to justify any
proposed expenditure on partial replacement, refurbishment or retrofitting. For this
reason it is essential that an overall assessment of the switchgear is carried out
before evaluating the economics of refurbishment/retrofit against replacement. This
should include condition assessment of the high-voltage insulation using partial
discharge measurement techniques. Included in this process is the evaluation
of available test data and relevant standards. Where circuit-breakers are under
consideration, it is also important to consider:
(a)
(b)
(c)
(d)
165 The availability of spares plays a role in the decision process. Consideration
should be given to the availability of both strategic items (eg bushings, current
transformer chambers, cable boxes, mechanisms) and routine maintenance
items (eg arcing contacts, turbulator inserts, gaskets, tripping and closing coils).
Confirmation should be sought as to whether spares are available from the original
equipment manufacturer (OEM), or the OEMs successor companies, or from small
specialist engineering companies.
Ratings
166 The load rating and the short-circuit rating of any new/refurbished/retrofit
switchgear should be assessed relative to that of any of the fixed portion and
ancillary equipment such as the current transformers that are to be retained. It
is not unknown for users to overlook the fact that where there is a mismatch
between the replaced/refurbished equipment and the existing equipment then the
lowest load and short-circuit rating apply. Consequently, they may install uprated
switchgear that cannot be utilised to its full rating.
Page 39 of 60
Replacement installations
167 Where a complete new switchboard is to be installed, the opportunity exists
to consider whether direct replacement is necessary or whether the switchboard
arrangement can be simplified. You also need to take account of the possible
additional capacity benefits and the reduced maintenance costs associated with the
new switchgear. Also, less space will generally be required and the opportunity given
to modernise the protection and control schemes.
168 Where only individual switchgear panels are to be replaced, then the decision is
one of a like-for-like replacement, if it is still available, or of a modern equivalent (see
also circuit-breaker retrofit option described in paragraphs 172-174).
169 It should be noted that old paper/lead cables can be internally damaged by
significant disturbance and appropriate measures need to be taken to avoid this.
Refurbished/retrofitted switchgear
170 Users should only embark on the refurbishment and/or retrofit route after an
overall assessment of those parts of the switchgear to be retained has been carried
out. This is necessary to confirm that the retained parts have adequate rating and
sufficient remaining life to justify the expenditure on refurbishment/retrofitting. The
options available are refurbishment of switchgear or retrofitting of circuit-breakers.
Refurbishment of switchgear
171 This can be viewed as a major overhaul of the switchgear with replacement
of parts deemed to be time-expired, eg operating mechanisms, insulation
components etc.
Retrofit circuit-breakers for withdrawable switchgear
172 Retrofitting involves updating the existing moving portions of switchgear,
generally to incorporate vacuum or sulphur hexafluoride technology, for use with
the existing fixed portions. Two options can be considered:
(a) replacing the complete circuit-breaker truck; or
(b) modifying the existing truck to incorporate a vacuum or sulphur hexafluoride
circuit-breaker.
173 Retrofit systems can be obtained either from switchgear manufacturers or
specialist retrofit suppliers. When selecting a system, particular attention should be
paid to the mechanical compatibility between the fixed portion and the new moving
portion. Problems can be experienced due to mechanical mismatch between the
mating portions, shutter actuation, racking mechanisms and physical clearances.
These are better addressed at the planning stage rather than attempting to cure
them at the installation stage. Such problems can be minimised by close liaison
between the user and supplier at all stages of a retrofit operation.
174 It is good practice to carry out a partial discharge survey of the switchboard,
prior to installation of the retrofit units, to establish the integrity of the existing
equipment and repeat the survey after installation to ensure that problems have not
been exacerbated or introduced.
Page 40 of 60
Second-hand equipment
175 It is possible to purchase second-hand switchgear from companies
specialising in the recovery of redundant switchgear and in its refurbishment for
re-sale. If second-hand switchgear is being considered, it is important to only deal
with reputable and experienced organisations. Such organisations are required
to provide documentation on the use and maintenance of the equipment. This
would include information originating from the OEM. An audit of the contract
by an independent consultant can be a worthwhile safeguard against purchase
of equipment that might not be fit for purpose. The companies supplying the
refurbished equipment though should ensure all relevant items are dealt with during
overhaul, upgrades, modifications etc.
176 Failure of switchgear can lead to fires and where oil-filled equipment is involved
the incident can be a major one. A serious incident not only poses potential fire and
smoke risks to people in the vicinity and to the building fabric but may also affect
other plant, thus escalating the primary event. There are a number of techniques
that can be used singularly or in combination to mitigate the effects of a fire and
limit smoke spread.
Compartmentation
177 Substation plant items can be separated by fire-resisting barriers to limit
the extent of any fire to the item of fire origin. If automatic extinction or control is
required (see paragraphs 178-180), then compartmentation is useful. However,
there may be contradictory requirements between fire safety and explosion safety,
for example where venting may be required to safeguard against explosion.
Compartmentation needs to be carefully designed so that it can contain a fire but
not inhibit any venting required for explosion control.
Page 41 of 60
Prevention
181 The most appropriate control measure is that of prevention. The following
strategies can be considered:
(a) good management of the plant items, eg careful control of workmanship,
as there is a greater likelihood of an incident occurring after replacement or
maintenance of equipment;
(b) careful monitoring of any degradation of oil and dielectric insulation;
(c) reduction of possible ignition sources;
(d) good housekeeping.
Detection
182 The use of an appropriate automatic fire detection system could provide the
electrical plant room or area with early fire detection and alarm features which
could also be linked with a control/extinction system to provide fast response fire
suppression or control.
Safety issues
183 Where automatic fire protection systems are installed there are risks to people
in the protected area when the system operates. These include:
(a) asphyxiation by the gases or chemical extinguishants used;
(b) poisoning if extinguishants are toxic;
(c) physical injury (falling, striking objects etc) due to poor visibility after release of
the gases or chemical extinguishants;
(d) effect of low temperature due to release of the gases or chemical
extinguishants.
184 Precautions should therefore be taken if people are to enter an area fitted with
automatic fire protection equipment. These include:
(a) the automatic control to be rendered inoperative before entry;
(b) caution notices indicating that the control is on non-automatic to be fitted to
the automatic/non-automatic selector;
(c) precautions taken to render the automatic control inoperative to be noted in
any safety documents issued for work in the protected area;
(d) instructions issued to staff to ensure that the system is restored to automatic
control as soon as all staff have withdrawn from the area.
185 Notices requiring the above actions should be prominently displayed at the
point(s) of access to the area.
Page 42 of 60
Training
General advice
186 It is the duty of all users of switchgear to provide necessary training in order
that staff involved in the operation and maintenance of switchgear are able to
carry out their duties in safety and without risk to health. Many organisations
offer a full range of training courses, from general appreciation of site access and
responsibilities through to detailed courses on operations, safety, maintenance
practice etc. Such organisations include:
(a)
(b)
(c)
(d)
187 The use of a set of safety rules and a system of safety documents (see
paragraph 188 for definitions) that clearly and unambiguously state what actions
are required to ensure safe working is essential, particularly at high voltage. To
ensure that the different levels of activity associated with switchgear are performed
competently and the safety rules are strictly adhered to, it is also important to
define different categories of staff. This means you can clearly define the duties that
are expected of them and, just as important, those they are not authorised to carry
out. Typical categories are as follows (training courses can be prepared to meet the
requirements of these categories):
(a) competent person a person recognised as having sufficient technical
knowledge and/or experience to enable them to avoid danger when carrying
out their duties and who may be nominated to receive and clear specified
safety documents;
(b) authorised person a competent person who has been appointed in writing
to carry out specified duties, including the issue and cancellation of safety
documents, eg a permit-to-work or sanction for test.
Page 43 of 60
189 Operational safety documents are not intended (and should not be used) for
work control purposes.
Disposal issues
191 Anyone who produces, treats, keeps, stores, transports or disposes of waste
is subject to a duty of care under section 34 of the Environmental Protection Act
1990. This makes holders of waste responsible for its fate even after it has left their
hands.
Insulating oil
192 Much of the used oil from switchgear is returned to oil companies and is
subject to a process to generate reclaimed oil (which is sold back to the users
for reuse). Within the reclaiming and refining processes, the oil companies have
their own quality assurance/quality control procedures, which should ensure that
the quality and performance of the reclaimed oil being supplied back to users is
satisfactory. It is standard practice within the oil companies to check the quality of
batches of oil returned for reclaiming and reject those that are severely degraded.
Users with known batches of badly degraded oil should keep it as separate waste
oil for disposal by the oil companies in an appropriate manner.
193 Switchgear oil may contain polychlorinated biphenyls (PCBs), so the
procedures for handling used oil should take account of the approved handling
procedures for PCB-contaminated materials or substances as laid down by:
(a) EU Directive 96/59/EC The Disposal of Polychlorinated Biphenyls and
Polychlorinated Triphenyls;
(b) Statutory Instrument SI 2000 No 1034 The Disposal of Polychlorinated Biphenyls
and Other Dangerous Substances Regulations (England and Wales) May 2000.
194 As discussed in paragraphs 91-99, used switchgear oil may contain cadmium
or cadmium sludge. Where this situation arises, the oil, cadmium sludge and all
material containing it needs to be treated as special waste and the disposal
needs to be carried out as laid down by The Special Waste Regulations 1996. This
includes all oil containing the cadmium and any new oil or solvents used to clean
and rinse the components within the tank. Any wipes, gloves or clothing that have
come into contact with the cadmium should be collected and sealed in boxes. All
of this should then be appropriately labelled as special waste.
Capacitors
195 Some capacitors contain PCBs and therefore the procedures for disposal of
capacitors should take account of approved handling procedures for PCBcontaminated materials or substances see the documents referred to in
paragraph 193.
Keeping electrical switchgear safe
Page 44 of 60
Page 45 of 60
Low voltage
Normally exceeding 50 V ac or 120 Vdc but not exceeding 1000 V ac or 1500 V dc
between conductors, or 600 V ac or 900 V dc between conductors and earth.
High voltage
Normally exceeding 1000 V ac or 1500 V dc between conductors, or 600 V ac or
900 V dc between conductors and earth.
Medium voltage
Some companies and persons use the term medium voltage to describe
distribution voltages in range 3.3 kV to 72.5 kV to distinguish these from the higher
values of voltage associated with transmission systems. There is no International
Electrotechnical Vocabulary (IEV) meaning which specifies values; all that is stated
is that the upper value lies between 30 kV and 100 kV. The term has not been used
in the UK to prevent confusion with the widely understood use of the term for 415
V three-phase systems.
Switchgear
A combination of one or more switching devices together with associated control,
measuring, signal, protective, regulating equipment etc completely assembled
under the responsibility of the manufacturer with all the internal electrical and
mechanical interconnections and structural parts.
Switching devices
It is possible to separate switching devices into the following groups and to define
the type of switching device. It should be noted that they are all electromechanical
devices.
Isolator
A switching device which is used to open (or close) a circuit either when negligible
current is interrupted (or established) or when no significant change in the voltage
across the terminals of each pole or phase of the isolator will result from the
operation.
Switch
A switching device suitable for making or closing a circuit under normal and
abnormal conditions, such as those of short-circuit, and capable of breaking or
opening a circuit under normal conditions.
Circuit-breaker
A switching device capable of making and breaking, or closing and opening, a
circuit under normal conditions and under abnormal conditions such as those of
short-circuit.
Page 46 of 60
Switch fuse
A switching device that is an integral assembly of switch and fuses in which a fuse
is connected in series with the switch.
Fuse switch
A switching device in which a fuse link or fuse carrier constitutes the moving
contact.
Operating duties
The operating duties of the above switching devices may be summarised as
follows:
Q An isolator has no rated making or breaking capability, ie these devices can
only be used for OFF-LOAD or DEAD switching.
Q A switch is a FAULT MAKE/LOAD BREAK device.
Q A circuit-breaker is a FAULT MAKE/FAULT BREAK device.
Operating mechanisms
The types of operating mechanisms used for these switching devices are defined
as follows:
Q Dependent manual operation (of a mechanical switching device) (IEV
Definition 441-16-13)
An operation solely by means of directly applied manual energy such that the
speed and force of the operation are dependent upon the action of the
operator.
Q Independent manual operation (of a mechanical switching device) (IEV
Definition 441-16-16)
A stored energy operation where the energy originates from manual power,
stored and released in one continuous operation, such that the speed and
force of the operation are independent of the action of the operator.
Q Dependent power operation (of a mechanical switching device) (IEV
Definition 441-16-14)
An operation by means of energy other than manual, where the completion of
the operation is dependent upon the continuity of the power supply
(to solenoids, electric or pneumatic motors etc).
Q Independent power operation (of a mechanical switching device) (IEV
Definition 441-16-6)
A stored energy operation where the stored energy originates from an external
power source and is released in one continuous operation, such that the speed
and force of the operation are independent of the action of the operator.
Q Stored energy operation (of a mechanical switching device) (IEV Definition
441-16-15)
An operation by means of energy stored in the mechanism itself prior to the
completion of the operation and sufficient to complete it under predetermined
conditions. This kind of operation may be subdivided according to:
(a) the manner of storing the energy (spring, weight etc);
(b) the origin of the energy (manual, electric etc);
(c) the manner of releasing the energy (manual, electric etc).
Page 47 of 60
Switchgear general
CH Flurscheim Power circuit-breaker theory and design Peter Peregrinus Ltd 1985
ISBN 0906048702
R T Lythall The J and P Switchgear Book: An outline of modern switchgear practice
for the non-specialist user 1972 edition Newnes/Butterworth-Heinemann
ISBN 0408000694
BS 3078: 1959 Isolators (including selectors) for alternating current systems
BS 4752: 1977: Part 1 Switchgear and control gear for voltage up to and including
1000 V ac and 1200 V in dc circuit-breakers
BS 5311: 1976: Parts 1 to 5 AC circuit-breakers of rated voltage above 1 kV
BS 5311: 1996 High-voltage alternating-current circuit-breakers
BS 5463: 1977 AC switches of rated voltage above 1 kV
BS 60947: Specification for low-voltage switchgear and controlgear general
requirements and circuit-breakers
BS 6423: 1983 Code of Practice for main-tenance of electrical switchgear and
controlgear for voltages up to and including 1 kV
BS 6626: 1985 Code of Practice for maintenance of electrical switchgear and
controlgear for voltages above 1 kV and up to and including 36 kV
Page 48 of 60
BS 936: 1940 Oil circuit-breakers for medium voltage ac systems (up to 660 V)
BS 936: 1960 Oil circuit-breakers for medium voltage ac systems (up to 660 V)
BS 5730: 1979 Monitoring and maintenance guide for mineral insulating oil
LV installations
BS 7671: 2001 Requirement for Electrical Installations (IEE Wiring Regulations)
Seventeenth edition
Page 49 of 60
RCM background
Smith A M Reliability-centred maintenance Wiley New York 1992
Moubray J Reliability-centred maintenance Butterworth-Heinemann Oxford 1991
Insulating tools
BS EN 60900 1994 Hand tools for live working up to 1000 V ac and 1500 V dc
Page 50 of 60
Appendix C: Examples of
switchgear configurations
MAIN ISOLATING
CONTACTS
OPERATING
MECHANISM
BUSBARS
CURRENT
TRANSFORMERS
CIRCUIT-BREAKER
OIL TANKER
CABLE BOX
VOLTAGE
TRANSFORMER
Page 51 of 60
OIL-FILLED VOLTAGE
TRANSFORMER
CURRENT
TRANSFORMERS
EARTHING
CONTACTS
MAIN ISOLATING
CONTACTS
CIRCUIT-BREAKER
TANK
CIRCUIT-BREAKER
CARRIAGE
Page 52 of 60
VOLTAGE
TRANSFORMER
RELAY PANEL
TEST ACCESS
AND COVER
CABLE BOX
VACUUM
INTERRUPTERS
CLOSING AND
SELECTOR
MECHANISMS
Page 53 of 60
COMPOUND FILLED
BUSBAR CHAMBER
TEST ACCESS
OPERATING
HANDLE
CABLE BOX
Page 54 of 60
TEE OFF
BUSHING
HV FUSE
MOVING
CONTACT
EARTH
SWITCH
FIXED
CONTACT
CABLE
BOX
Page 55 of 60
FUSE ACCESS
COVER
HV FUSES
RING SWITCH
MAIN CONTACTS
RING SWITCH
BLADES
SWITCH
BLADES
RING SWITCH
EARTH CONTACTS
Page 56 of 60
CONTACTS AND
ARC CHUTES
ISOLATOR
CLOSED POSITION
REMOVABLE
HANDLE
CIRCUIT-BREAKER
CLOSED POSITION
Page 57 of 60
CIRCUIT-BREAKER
MECHANISM
VACUUM
INTERRUPTERS
VOLTAGE
TRANSFORMER
SELECTOR
MECHANISM
RESIN
ENCAPSULATED
BUSBARS
SELECTOR SWITCH
IN SF6 GAS
Page 58 of 60
Page 59 of 60
Further information
HSE priced and free publications can be viewed online or ordered from
www.hse.gov.uk or contact HSE Books, PO Box 1999, Sudbury, Suffolk
CO10 2WA Tel: 01787 881165 Fax: 01787 313995. HSE priced publications
are also available from bookshops.
For information about health and safety ring HSEs Infoline Tel: 0845 345 0055
Fax: 0845 408 9566 Textphone: 0845 408 9577 e-mail: hse.infoline@natbrit.com or
write to HSE Information Services, Caerphilly Business Park, Caerphilly CF83 3GG.
British Standards can be obtained in PDF or hard copy formats from BSI:
http://shop.bsigroup.com or by contacting BSI Customer Services for hard
copies only Tel: 020 8996 9001 e-mail: cservices@bsigroup.com.
The Stationery Office publications are available from The Stationery Office, PO
Box 29, Norwich NR3 1GN Tel: 0870 600 5522 Fax: 0870 600 5533 e-mail:
customer.services@tso.co.uk Website: www.tso.co.uk (They are also available from
bookshops.) Statutory Instruments can be viewed free of charge at
www.opsi.gov.uk.
Published by HSE
02/10
Page 60 of 60