1.0
GENERAL
1.1
The intent of this document is to cover the basis and calculations for sizing of
6.6kV (UE), XLPE cables required for 6.6kV Main Switchboard, Distribution
Transformers, & HT Motors in the installations.
2.0
2.1
6.6kV(UE) grade cables shall be Copper conductor with inner semi conducting layer
over conductor, XLPE insulated with semi conducting layer & copper tape over insulation
inner sheath, PVC extruded outer sheath, armoured cables.
2.2
The cables will be laid on cable trays and in single layer which will be shown in cable
layout drawing.
2.3
2.4
6.6kV (UE) Cable from 12.5MVA Power Transformer to 6.6kV Main Switchboard shall be
sized for carrying 26.3kA short circuit current for 1 second duration since numerical type
protective relays are provided in the system to isolate the faulty equipment within less
than 0.4 sec.
2.4
6.6kV (UE) Cable from 6.6kV Main Switchboard to Distribution Transformers shall be
sized for carrying 26.3kA short circuit current for 1 second duration since numerical type
protective relays are provided in the system to isolate the faulty equipment within less
than 0.6 sec
2.5
6.6kV (UE) Cable from 6.6kV Isolator Panel to HT Motor feeder shall be sized for
carrying short circuit current of 26.3kA for 0.2 second duration.
2.6
Starting current for 2200kW SR DOL motor is 3 times greater than rated current.
2.7
Following formula will be used for calculating receiving end terminal voltage during full
load conditions:
Page 1 of 12
PROJECT
CLIENT
CUSTOMER
ELECTRICAL
CONTRACTO
R
DOC NO.
DATE
REV NO.
PREP. BY
CHKD.
BY
APPD.
BY
17/0035-EL-0480
24.09.2010
02
AVS
MND
NCD
Where,
Vr
Vs
I fl
Cos
Length
of
cables
2.8
= Number of Runs
Cable parameters such as resistance, reactance values etc. are taken from
Catalogues of Polycab make cables (Copy attached). These values for the cables
to be supplied actually will meet the values assumed in the calculations subject
to manufacturing tolerances as allowed in respective standards.
2.9
Cables
laid
inside
concrete
0.81
Page 2 of 12
of 5.
Ref. Annexure A; Table No. A
on Page No. 4 of 5.
PROJECT
CLIENT
CUSTOMER
ELECTRICAL
CONTRACTO
R
DOC NO.
DATE
REV NO.
PREP. BY
CHKD.
BY
APPD.
BY
17/0035-EL-0480
24.09.2010
02
AVS
MND
NCD
trays in tier = 3
Overall Derating Factor for 6.6
= 1 x 0.81
= 0.81
2.10
Overhead route;
2.10.
1
0.93
of 5.
Ref. Annexure A; Table No. A
on Page No. 4 of 5.
trays in tier = 6
Overall Derating Factor for 6.6
= 1 x 0.93
trays
on Cable
rack
exposed to air
Page 3 of 12
= 0.93
PROJECT
CLIENT
CUSTOMER
ELECTRICAL
CONTRACTO
R
3.0
DOC NO.
DATE
REV NO.
PREP. BY
CHKD.
BY
APPD.
BY
17/0035-EL-0480
24.09.2010
02
AVS
MND
NCD
3.1 Typical calculation of Cable sizing for 6.6kV (UE) Copper XLPE cable from 12.5MVA
Short circuit rating of selected cable is 34.3 kA for 1 sec. which is more than of possible
short circuit current of 26.3 kA for 1 sec.
Hence selected cable of size 3C X 240 sq. mm. is suitable for Short
Circuit Withstand Capacity.
3.1.2
b)
conductor.
c)
d)
As the Cables laid on cable trays exposed to air, the Derating factor
considered : - 0.81 (Ref 2.9.3 above)
e)
Page 4 of 12
PROJECT
CLIENT
CUSTOMER
ELECTRICAL
CONTRACTO
R
DOC NO.
DATE
REV NO.
PREP. BY
CHKD.
BY
APPD.
BY
17/0035-EL-0480
24.09.2010
02
AVS
MND
NCD
b)
c)
d)
Voltage at receiving end terminals is given by following formula : Vr Vs ( 3 I fl ( R Cos X Sin ) L) (1000 N t )
e)
f)
g)
Vr 6600 (15.20)
Vr 6584.8 V
Now Percentage Voltage Drop, % VD (Vs Vr ) Vs 100
% V D (6600 6584.8) 6600 100
% VD 0.23 which is very negligible.
Hence 6.6kV (UE), 3R x 3C X 240 sq. mm. XLPE Copper conductor Cable is adequate for
Voltage Drop consideration.
Page 5 of 12
PROJECT
CLIENT
CUSTOMER
ELECTRICAL
CONTRACTO
R
3.2
DOC NO.
DATE
REV NO.
PREP. BY
CHKD.
BY
APPD.
BY
17/0035-EL-0480
24.09.2010
02
AVS
MND
NCD
Typical calculation of Cable sizing for 6.6kV (UE) Copper XLPE cable from 6.6kV Main
Switchboard to 2000kVA Transformer.
3.2.1
Maximum possible short circuit current on 6.6kV side : - 26.3kA for 1 sec.
b) Short circuit rating of selected cable (3C X 185 sq. mm) : - 26.4kA for 1 sec.
c) Duration for carrying short circuit current for application: - 0.6 sec.
Selected short circuit current of cable is 26.4 kA for 1 sec. which is more than required
short circuit current of 26.3 kA for 0.6 sec.
Hence selected cable of size 3C X 185 sq. mm. is suitable for Short Circuit
Withstand Capacity.
3.2.2
b)
insulated Copper
conductor.
c)
Current rating of the cable under standard conditions of installation in Air : 430A (Ref. Annexure A; Polycab Cable Catalogue, Table No. 24 on
Page No. 5 of 5)
d)
As the cables shall be laid on cable trays exposed to air, the derating factor
considered : - 0.93 (Ref 2.9.3 above)
e)
Hence selected cable size of 3C x 185 Sq. mm. XLPE is suitable for Continuous
Current Carrying Capacity.
Page 6 of 12
PROJECT
CLIENT
CUSTOMER
ELECTRICAL
CONTRACTO
R
3.2.3
DOC NO.
DATE
REV NO.
PREP. BY
CHKD.
BY
APPD.
BY
17/0035-EL-0480
24.09.2010
02
AVS
MND
NCD
b)
c)
Cable
size considered
insulated Copper
conductor.
d)
Voltage at receiving end terminals is given by following formula : Vr Vs ( 3 I fl ( R Cos X Sin ) L) (1000 N t )
e)
f)
g)
Vr 6600 (1.4)
Vr 6598.6 V
Now Percentage Voltage Drop, % VD (Vs Vr ) Vs 100
% V D (6600 6598.6) 6600 100
% V D 0.021 which is very negligible.
Hence 6.6kV (UE), 3C X 185 sq. mm. XLPE Cable is adequate for Voltage Drop
consideration.
Page 7 of 12
PROJECT
CLIENT
CUSTOMER
ELECTRICAL
CONTRACTO
R
3.3
DOC NO.
DATE
REV NO.
PREP. BY
CHKD.
BY
APPD.
BY
17/0035-EL-0480
24.09.2010
02
AVS
MND
NCD
Typical calculation of Cable sizing for 6.6kV (UE) copper XLPE cable from 6.6kV
Isolator Panel to 6.6kV 2200kW Cement Mill Motor.
3.3.1 Cable size confirmation for Short Circuit Withstands Capacity.
a)
Maximum possible short circuit current on 6.6kV side : - 26.3kA for 1 sec.
b)
Short circuit rating of selected cable (3C X 185 sq. mm): - 26.4kA for 1 sec.
c)
Selected short circuit current of cable is 26.4 kA for 1 sec. which is more than required
short circuit current of 26.3 kA for 0.2 sec.
Hence selected cable of size 3C X 185 sq. mm. is suitable for Short Circuit
Withstand Capacity.
3.3.2
b)
c)
Current rating of the cable under standard conditions of installation in air: 430A (Ref. Annexure A; Polycab Cable Catalogue, Table No. 24 on
Page. No. 5 of 5)
d)
As the cables shall be laid on cable trays exposed to air, the Derating factor
considered : - 0.93 (Ref 2.9.3 above)
e)
Hence selected cable size of 3C x 185 Sq. mm. XLPE is suitable for Continuous
Page 8 of 12
PROJECT
CLIENT
CUSTOMER
ELECTRICAL
CONTRACTO
R
DOC NO.
DATE
REV NO.
PREP. BY
CHKD.
BY
APPD.
BY
17/0035-EL-0480
24.09.2010
02
AVS
MND
NCD
3.3.3
Cable sizing based on steady state Voltage Drop during full load condition.
a)
b)
c)
d)
Voltage at receiving
end
e)
f)
g)
Vr 6600 (0.939)
Vr 6599.061 V
Now Percentage Voltage Drop, % VD (Vs Vr ) Vs 100
% V D (6600 6599.061) 6600 100
% V D 0.014 which is very negligible.
Page 9 of 12
DOC NO.
DATE
REV NO.
PREP. BY
CHKD.
BY
APPD.
BY
17/0035-EL-0480
24.09.2010
02
AVS
MND
NCD
Hence 6.6kV (UE), 3C X 185 sq. mm. XLPE Copper Conductor Cable is adequate for
Steady state Voltage Drop consideration.
3.3.4
Cable sizing based on Starting Voltage Drop during starting of the HT Motor.
a)
b)
c)
d)
Cable
insulated Copper
conductor.
e)
Voltage at receiving
end
f)
g)
h)
Power
Factor
of
system
at
starting
(i.e.
Cos):-
(Sin = 0. 95)
Now we have, Vr Vs ( 3 I fl ( R Cos X Sin ) L) (1000 N t )
Vr 6600 ( 3 704.1 (0.127 0.3 0.087 0.95) 15) (1000 1)
Vr 6600 (2.22)
Vr 6597.78 V
Now Percentage Voltage Drop, % VD (Vs Vr ) Vs 100
Page 10 of 12
0.3
lagging.
DOC NO.
DATE
REV NO.
PREP. BY
CHKD.
BY
APPD.
BY
17/0035-EL-0480
24.09.2010
02
AVS
MND
NCD
4.0 CONCLUSION
4.1 The duration of short circuit withstand capacity of
mm. XLPE cable (34.3 kA for 1 sec) is more than the possible short circuit current
(i.e. 26.3kA for 1 sec.) in the system for HT switchboard.
4.2 The duration of short circuit withstand capacity of
XLPE cable ( 26.4 for 1 sec) is more than the possible short circuit current (i.e.
26.3kA at 0.6 sec.) in the system for Dist. Trafo. Feeder.
4.3 The duration of short circuit withstand capacity of
XLPE cable ( 26.4 kA for 1 sec) is more than the possible short circuit current (i.e.
26.3kA at 0.2 sec.) in the system for HT Motor feeder.
4.4 The
current carrying capacity of selected cables after deration is more than the
Page 11 of 12
DOC NO.
DATE
REV NO.
PREP. BY
CHKD.
BY
APPD.
BY
17/0035-EL-0480
24.09.2010
02
AVS
MND
NCD
The selected cables complies with all the requirements and hence the selection of
6.6kV (UE), 3C X 240 sq. mm. XLPE insulated Copper Cable for 6.6kV Main Switchboard &
6.6kV (UE), 3C X 185 sq. mm XLPE Insulated Copper Cable for Distribution Transformer &
HT Motor are adequate.