GENERAL PROVISIONS
R 408.14001. Scope.
Rule 4001. (1) The provisions of these rules
regulate electrical safety-related work practices for
both qualified persons, that is, those who have training
in avoiding the electrical hazards of working on or near
exposed energized parts, and unqualified persons, that
is, those who have little or no such training, who work
on, near, or with any of the following installations:
(a) Installations of electric conductors and
equipment within or on buildings or other structures
and on other premises such as yards; carnival,
parking, and other lots, and industrial substations.
(b) Installations of conductors that connect to the
supply of electricity.
(c) Installations of other outside conductors on
the premises.
(d) Installations of optical fiber cable where such
installations are made together with electric
conductors. See R 408.14002 for training requirements
that apply to qualified and unqualified persons.
(2) The provisions of these rules also regulate
work that is performed by unqualified persons on, near,
or with the installations listed in subrule (3) (a) to (d) of
this rule.
(7)
(3) If the exposed live parts are not deenergized, for example, for reasons of increased or
additional hazards or infeasibility, other safety-related
work practices shall be used to protect employees who
may be exposed to the electrical hazards involved.
Such work practices shall protect an employee from
direct contact between energized circuit parts and any
part of his or her body and from indirect contact
through some other conductive object. The work
practices that are used shall be suitable for the
conditions under which the work is to be performed
and for the voltage level of the exposed electric
conductors or circuit parts. Specific work practice
requirements are detailed in R 408.14005.
R 408.14004 Working on or near exposed deenergized parts.
Rule 4004. (1) This rule applies to work on exposed
deenergized parts and to work that is near enough to
exposed de-energized parts to expose an employee to
any electrical hazard the parts present. Conductors
and parts of electric equipment that have been deenergized, but have not been locked out in accordance
with the provisions of subrule (2) of this rule, shall be
treated as energized parts and the provisions of
R 408.14005 apply to work on or near such parts.
(2) While any employee is exposed to contact
with parts of fixed electrical equipment or circuits which
have been deenergized, the circuits energizing the
parts shall be locked out in accordance with the
requirements of this rule. The requirements shall be
followed in the order in which they are presented.
TABLE 2
APPROACH DISTANCE FOR QUALIFIED EMPLOYEES
ALTERNATING CURRENT
Voltage Range (Phase to Phase) Distance
Minimum Approach
Avoid contact
1 ft. 0 in. (30.5 cm)
1 ft. 6 in. (46 cm)
2 ft. 0 in. (61 cm)