Safety Manager Errorcode list

Version
1.0
2.0
3.0
3.1
4.0
5.0
6.0

Version Date
15-Jun-07
01-Aug-07
05-Jan-08
07-Jan-08
23-May-08
24-Jun-11
06-Sep-13

Approval Date
N.A
N.A
N.A
N.A
N.A
N.A
N.A

Author
JvB
JJ
JvB
JvB
JvB
SW
SW

Reference
N.A
N.A
N.A
N.A
N.A
N.A
N.A

Change Description
First Issue
Published
R130 included
QPP-0002 added
R131 included
R140 included (RUSIO)
R151.1

Module type
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2

Module description
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack

EC
0
1
2
3
4
5
6
7
8
9
10

Description in Safety Builder Diagnostics


Error code not defined
Module faulty
Module faulty
Module faulty
Module faulty
Module faulty
Module faulty
Module faulty
Module faulty
Module faulty
Module faulty

Details

Corrective actions

Error detected in IO bus test


Fault detected during 68000 selftest
Fault detected during 68000 selftest
Fault detected during 68000 selftest
Fault detected during 68000 selftest
Fault detected during 68000 selftest
Fault detected during 68000 selftest
Fault detected during 68000 selftest
Fault detected during mem test
Fault detected during mem test

FC-QPP-0001 & 2

Quad Processsor Pack

11

Module faulty

Fault detected during 68000 selftest

FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2

Quad Processsor Pack


Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack

12
13
14
15
16
17
18
19
20
21
22

Module faulty
Module faulty
Error code not defined
Temperature sensor faulty
Module faulty
Module faulty
Module faulty
Module faulty
Module faulty
Module faulty
Module faulty

Fault detected during 68000 selftest


Fault detected during 10 ms interrupt selftest
not used
Temperature sensor inside QPP defect
Hardware comparator test failed
Error detected in IO bus test
Error detected in addressing
Illigal instruction detected
Software error
Hardware error
Spurious interrupt

Replace QPP
Replace QPP
Replace QPP
Replace QPP
Replace QPP
Replace QPP
Replace QPP
Replace QPP
Replace QPP
Replace QPP
1) Upgrade to R131.5 or higher
2) Replace QPP
Replace QPP
Replace QPP

FC-QPP-0001 & 2

Quad Processsor Pack

23

Module faulty

Failed to erase application

FC-QPP-0001 & 2

Quad Processsor Pack

24

Module faulty

Failed to load application

FC-QPP-0001 & 2
FC-QPP-0001 & 2

Quad Processsor Pack


Quad Processsor Pack

25
26

Module faulty
Module faulty

Failed to write to EEPROM


Main-Copy Synchronisation Failed

FC-QPP-0001 & 2

Quad Processsor Pack

27

Module faulty

System program corrupted

FC-QPP-0001 & 2

Quad Processsor Pack

28

Application program corrupted

Application program is corrupted


CP halted

1) Load application again

Configuration and/or application too complex for calculating


cycletime
CP can not be started

1) Check if configuration of IO is set correctly


2) Check if IO chassis are set on correct bus
3) Check if the application can bemade less complex
4) Check if it's possible to split complex logic on sheet on
two or more sheets

FC-QPP-0001 & 2

Quad Processsor Pack

29

Controller too complex to calculate cycle time


within configured DTI

FC-QPP-0001 & 2

Quad Processsor Pack

30

Module faulty

Error detected in share RAM

FC-QPP-0001 & 2

Quad Processsor Pack

31

Incorrect software version

QPP received unsupported request

FC-QPP-0001 & 2

Quad Processsor Pack

32

Key not in Run

Incorrect position keyswitch

FC-QPP-0001 & 2

Quad Processsor Pack

33

Download failed

Incorrect block sequence

FC-QPP-0001 & 2

Quad Processsor Pack

34

Module faulty

USI is not ready

FC-QPP-0001 & 2

Quad Processsor Pack

35

Download failed

File to be loaded is empty

FC-QPP-0001 & 2

Quad Processsor Pack

36

Module faulty

Hardware of flash failed

Replace QPP
Replace QPP
Replace QPP
Replace QPP
Contact TAC
Contact TAC
Replace QPP
Replace QPP and Contact TAC
1) Set system number to '0' and try again
2) replace QPP
1) Set system number to '0' and try again
2) replace QPP
Replace QPP
Replace QPP
1) Load control processor again
2) Replace QPP

Replace QPP
1) If reported during system software upgrade, as
expected
2) If reported during normal operation, Contact TAC
1) Set Keyswitch in correct position
2) Replace QPP
Contact TAC
1) Reset SM
2) replace USI
1) Compile application and load again
2) Contact TAC
Replace QPP

Module type
FC-QPP-0001 & 2

Module description
Quad Processsor Pack

EC
37

Description in Safety Builder Diagnostics


Module faulty

FC-QPP-0001 & 2

Quad Processsor Pack

38

Keyswitch cycled from RUN to IDLE

FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2

Quad Processsor Pack


Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack

39
40
41
42
43
44
45
46

Module faulty
Module faulty
Memory error
Memory error
Wrong QPP type placed
Memory error
Module faulty
Module faulty

Details
EEPROM failed
QPP keyswitch is set from run to Idle
CP halted
Error detected in address test
Error detected in watchdog interrupt test
Error detected in memory USI 1
Error detected in memory USI 2
Error detected in memory application
Error detected in memory internal communication
Error detected in memory internal communication
Error detected in memory internal communication

FC-QPP-0001 & 2

Quad Processsor Pack

47

Startup impossible, modify off-line

Online modification is not possible

FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2

Quad Processsor Pack


Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack

48
49
50
51
52

Module faulty
Module faulty
Module faulty
Module faulty
Module faulty

main-Copy failed to talk


Force disable fail
Memory Synchronisation Failed
Main Copy Not In Sync In Initialisation
Main Copy Not In Sync In Idle

Corrective actions
Replace QPP
Message
Replace QPP
Replace QPP
Replace USI1
Replace USI2
Replace QPP-0001 with a QPP-0002
Replace QPP
Replace QPP
Replace QPP
After load and OLM check, mismatches are detected
between two cp's.
Most likely the option 'online modification' was set to 'no'
during modifications.
Replace QPP
Replace QPP
Replace QPP
Replace QPP
Replace QPP
1) Load QPP or
2) Set QPP to system nr. = 0 and let it load from the
other QPP
The load of the QPP replacement procedure can be
used for this.
The replacement of the QPP itself is not needed.
3) Replace QPP

FC-QPP-0001 & 2

Quad Processsor Pack

53

Embedded software corrupted

QPP detected corrupted embedded software


CP halted

FC-QPP-0001 & 2
FC-QPP-0001 & 2

Quad Processsor Pack


Quad Processsor Pack

54
55

Module faulty
Module faulty

BackUp Failed
EEEPROM Data Corrupted

FC-QPP-0001 & 2

Quad Processsor Pack

56

Check 5 VDC power supply voltage

QPP detected 5VDC almost on minimum level

FC-QPP-0001 & 2

Quad Processsor Pack

57

Check 5 VDC power supply voltage

QPP detected 5VDC almost on maximum level

FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2

Quad Processsor Pack


Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack

58
59
60
61
62
63
64
65
66

Module faulty
Module faulty
Module faulty
Module faulty
Module faulty
Module faulty
Module faulty
Module faulty
Module faulty

Speedy FIFO Buffer Full Error


Speedy FIFO Overflow Int Error
Speedy FIFO Data Incorrect Error
Speedy Comparator Walking bit Error
Speedy Fifo Empty Timeout Error
Speedy Memory Int Error
Speedy Transmitter Error
Speedy FIFO Receiver Error
Speedy Data Send Timeout Error

FC-QPP-0001 & 2

Quad Processsor Pack

67

Temperature pre-alarm

Temperature inside CP reached minimum pre-alarm level

FC-QPP-0001 & 2

Quad Processsor Pack

68

Temperature pre-alarm

Temperature inside CP reached maximum pre-alarm level

FC-QPP-0001 & 2

Quad Processsor Pack

69

Temperature shutdown

Temperature inside CP reached minimum shutdown


Temperature
CP halted

1) Check if fans are running


2) Check room temperature

FC-QPP-0001 & 2

Quad Processsor Pack

70

Temperature shutdown

Temperature inside CP reached maximum shutdown


Temperature
CP halted

1) Check if fans are running


2) Check room temperature

Replace QPP
Replace QPP
1) Replace PSU-240516 of reported controller
2) Replace QPP of reported position
1) Replace PSU-240516 of reported controller
2) Replace QPP of reported position
Replace QPP
Replace QPP
Replace QPP
Replace QPP
Replace QPP
Replace QPP
Replace QPP
Replace QPP
Replace QPP
1) Check if fans are running
2) Check room temperature
1) Check if fans are running
2) Check room temperature

Module type
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2

Module description
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack

EC
71
72
73
74
75
76

Description in Safety Builder Diagnostics


Module faulty
Module faulty
Module faulty
Module faulty
Module faulty
Module faulty

Details
Free Running Counter Error
Fault detected during common IO busdriver selftest
Fault detected in IO BusDriver1
Fault detected in IO BusDriver2
Fault detected in IO BusDriver3
Fault detected in IO BusDriver4
QPP detected 5VDC below minimum level
CP halted
QPP detected 5VDC above maximum level
CP halted

Corrective actions
Replace QPP
Replace QPP
Replace QPP
Replace QPP
Replace QPP
Replace QPP
1) Replace PSU-240516 of reported controller
2) Replace QPP of reported position
1) Replace PSU-240516 of reported controller
2) Replace QPP of reported position
1) Check 24 VDC on busbar
2) Check 24VDC on CP Chassis for reported CP
3) Replace QPP

FC-QPP-0001 & 2

Quad Processsor Pack

77

Check 5 VDC power supply voltage

FC-QPP-0001 & 2

Quad Processsor Pack

78

Check 5 VDC power supply voltage

FC-QPP-0001 & 2

Quad Processsor Pack

79

Check 24 VDC power supply voltage

QPP detected 24VDC below minimum level


CP halted

FC-QPP-0001 & 2

Quad Processsor Pack

80

Check 24 VDC power supply voltage

QPP detected 24VDC above maximum level


CP halted

FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2

Quad Processsor Pack


Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack

81
82
83
84
85
86

Module faulty
Module faulty
Module faulty
Module faulty
Module faulty
Module faulty

Fault detected in WD ESD section


Fault detected in WD section 1002D
Memory error detected in WD section
Fault detected in WD section secondary switch off
Memory error detected in WD section
Fault detected in WD switch off

FC-QPP-0001 & 2

Quad Processsor Pack

87

Module faulty

Fault detected in PowerSupply

FC-QPP-0001 & 2

Quad Processsor Pack

88

Module faulty

Fault detected in PowerSupply

FC-QPP-0001 & 2

Quad Processsor Pack

89

Module faulty

Fault detected in PowerSupply

FC-QPP-0001 & 2

Quad Processsor Pack

90

Module faulty

Fault detected in PowerSupply

FC-QPP-0001 & 2

Quad Processsor Pack

91

Module faulty

Fault detected in PowerSupply

FC-QPP-0001 & 2

Quad Processsor Pack

92

Module faulty

Fault detected in PowerSupply

FC-QPP-0001 & 2

Quad Processsor Pack

93

Module faulty

Fault detected in PowerSupply

FC-QPP-0001 & 2

Quad Processsor Pack

94

Module faulty

Fault detected in PowerSupply

FC-QPP-0001 & 2

Quad Processsor Pack

95

Check battery

Battery value below the limit

FC-QPP-0001 & 2

Quad Processsor Pack

96

Check battery

No Battery voltage

FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2

Quad Processsor Pack


Quad Processsor Pack
Quad Processsor Pack

97
98
99

Module faulty
Module faulty
Module faulty

Fault detcted in RTC during selftest


Fault detected during WD max timer test
Fault detected during WD min timer test

FC-QPP-0001 & 2

Quad Processsor Pack

100

Check 24 VDC power supply voltage

QPP detected 24VDC almost on minimum level

FC-QPP-0001 & 2

Quad Processsor Pack

101

Check 24 VDC power supply voltage

QPP detected 24VDC almost on minimum level

1) Check 24 VDC on busbar


2) Check 24VDC on CP Chassis for reported CP
3) Replace QPP

FC-QPP-0001 & 2

Quad Processsor Pack

102

Module faulty

Correlation detected during level detection. Hardware


circuits for voltage monitoring are faulty

Replace QPP

1) Check 24 VDC on busbar


2) Check 24VDC on CP Chassis for reported CP
3) Replace QPP
Replace QPP
Replace QPP
Replace QPP
Replace QPP
Replace QPP
Replace QPP
1) Replace PSU-240516 of reported controller
2) Replace QPP of reported position
1) Replace PSU-240516 of reported controller
2) Replace QPP of reported position
1) Replace PSU-240516 of reported controller
2) Replace QPP of reported position
1) Replace PSU-240516 of reported controller
2) Replace QPP of reported position
1) Replace PSU-240516 of reported controller
2) Replace QPP of reported position
1) Replace PSU-240516 of reported controller
2) Replace QPP of reported position
1) Replace PSU-240516 of reported controller
2) Replace QPP of reported position
1) Replace PSU-240516 of reported controller
2) Replace QPP of reported position
Replace batteries
1) Check the battery is properly installed in BKM
2) replace batteries in BKM
Replace QPP
Replace QPP
Replace QPP
1) Check 24 VDC on busbar
2) Check 24VDC on CP Chassis for reported CP
3) Replace QPP

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions
1) Reset controller to check if the message re-occurs
2) Check if application is compiled after system software
upgrade
If not, compile and download the application again
3) Check in system info if the software versions of the
USI and QPP match with the current loaded release

Contact TAC

FC-QPP-0001 & 2

Quad Processsor Pack

103

Incorrect software version

Mismatch between QPP, USI and/or Application software


May be reported during upgrade or replacing an USI with
another software version loaded.
As soon as module is equalized, message can be cleared by
giving a reset

FC-QPP-0001 & 2

Quad Processsor Pack

104

Program update failed

Equalizing between CP1 & CP2 not completed within


specified time

Internal communication time out


1) Wait a few minutes till the QPP shows Ready. Then
Can also be reported just after load In this case it's no
reset
hardware defect..
Can also be reported while QPP running, this means the USI 2) replace QPP
module was removed

FC-QPP-0001 & 2

Quad Processsor Pack

105

Program update failed

FC-QPP-0001 & 2
FC-QPP-0001 & 2

Quad Processsor Pack


Quad Processsor Pack

106
107

Safe state initiated by software assertion


Module faulty

FC-QPP-0001 & 2

Quad Processsor Pack

108

Application sheets different (OLM)

FC-QPP-0001 & 2

Quad Processsor Pack

109

Idle state initiated due to on-line modification

CP is halted because of online modification

FC-QPP-0001 & 2

Quad Processsor Pack

110

Module faulty

Hardware fault

FC-QPP-0001 & 2

Quad Processsor Pack

111

Internal communication failure or redundant CP


degraded

Internal communication failure during OLM

FC-QPP-0001 & 2

Quad Processsor Pack

112

Safe state initiated by software assertion

FC-QPP-0001 & 2

Quad Processsor Pack

113

Control Processor halt

FC-QPP-0001 & 2

Quad Processsor Pack

114

Configuration error

FC-QPP-0001 & 2

Quad Processsor Pack

115

Error code not defined

Run Assertion
Fault reset initiated,
while startup is not allowed
(No CP READY on display).
Too many logical connections defined (max 32 per COM
module)
not used

FC-QPP-0001 & 2

Quad Processsor Pack

116

Communication overrun

Force Pending BufferFulll

Message only ; check the number of force and write


commands per second from DCS or Experion

FC-QPP-0001 & 2

Quad Processsor Pack

117

Safe state initiated by software assertion

The calculated and executed number of FLD's does not


match

Contact TAC

Repair timer started

Repair Timer started


CP running

1) Other fault in system ininiated to start the repair timer


- Check Actual diagnostics to detect which fault initiated
the repair timer to start
- Solve the fault in the system which starts the repair
timer

1) Check Actual Diagnostics to see which module(s) in


the non-redudant IO is the cause
This can be DO, AO and IO extender. Not DI and AI.
2) Solve the reported faults in the non redundant IO
Replace USI1
Replace USI2
No signals forced, check force list

FC-QPP-0001 & 2

Quad Processsor Pack

118

Fault in scheduling 10mS test


IO bus driver relay faulty
Sheet differences reported after load
OLM possible

FC-QPP-0001 & 2

Quad Processsor Pack

119

Functionality degraded

Watchdog of non redundant IO is de-actviated.


All outputs in non redundant IO are de-activated Caused by
an output- or IO extender failure in non-redundant IO abd
fault reaction is set to low.
Also the error which is the cause failure will be reported in
the Actual diagnostics.

FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2

Quad Processsor Pack


Quad Processsor Pack
Quad Processsor Pack

120
121
122

Module faulty
Module faulty
All forces cleared

Interrupt USI1 Defect


Interrupt USI 2 Defect
All forces cleared

Contact TAC
Replace QPP
See details to check modified sheets
Other CP1 is loaded with other version after OLM this
CP is stopped because of the OLM.
Replace QPP
1) Set QPP keyswitch to stop and back to run
Check actual diagnostics
If no fault message, Start CP
2) Replace QPP
Contact TAC
Message only
Check/Optimize Logical Connections

Module type
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2

Module description
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack

EC
123
124
125
126
127

Description in Safety Builder Diagnostics


Error code not defined
Error code not defined
Error code not defined
Error code not defined
Error code not defined

Details
Device Flash Difference Main-Copy
Device FPGA1 Difference Main-Copy
Device FPGA2 Difference Main-Copy
Device FPGA3 Difference Main-Copy
Device FPGA4 Difference Main Copy

FC-QPP-0001 & 2

Quad Processsor Pack

128

Calculation overflow

Error en Equatation block

FC-QPP-0001 & 2

Quad Processsor Pack

129

Calculation overflow

Any other overflow in calculating the logic

FC-QPP-0001 & 2

Quad Processsor Pack

130

Divide by zero

Functional Logic Diagram has a divide by 0

FC-QPP-0001 & 2

Quad Processsor Pack

131

Illegal argument e.g. Root of 1

Not valid calculation in FLD


ie srt of negative value

FC-QPP-0001 & 2

Quad Processsor Pack

132

Illegal timer value

Corrective actions
Replace QPP
Replace QPP
Replace QPP
Replace QPP
Replace QPP
1) Check equatation block on correctness
2) reload table in EB
Check logic
Check and correct logic.
FLD number is mentioned in details
FLD number is reported at the bottom in details
Check calculation and and avoid illegal calculations

Timer value out of range

FLD number is reported in details


The timer values must be greater than zero. A zero value
is changed to the nearest
allowed value. The maximum timer value lies in the order
of 2E23, i.e. >100+E6:

FC-QPP-0001 & 2

Quad Processsor Pack

133

Illegal counter value

Input of timer has an illigal value


system halted

In the details, the sheet is mentioned.


Check and correct the application.
Loading a value outside the specified range of 1 to 8191
in the counter causes a system
shutdown!

FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2

Quad Processsor Pack


Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack

134
135
136
137

Module faulty
Module faulty
Safe state initiated by software assertion
Safe state initiated by software assertion

WD section FETs on
Too often drift detected in RTC
Software error
Software error

Replace QPP
Replace QPP
Contact TAC
Contact TAC

FC-QPP-0001 & 2

Quad Processsor Pack

138

I/O extender address incorrect or an additional I/O IO extender detected on IO bus which is not configured
extender placed
CP can not be started

FC-QPP-0001 & 2

Quad Processsor Pack

139

Safe state initiated by software assertion

FC-QPP-0001 & 2

Quad Processsor Pack

140

FC-QPP-0001 & 2

Quad Processsor Pack

141

FC-QPP-0001 & 2

Quad Processsor Pack

142

Module faulty
Internal communication failure or redundant CP
degraded
Internal communication failure or redundant CP
degraded

FC-QPP-0001 & 2

Quad Processsor Pack

143

Divide by zero

FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2

Quad Processsor Pack


Quad Processsor Pack
Quad Processsor Pack

144
145
146

FC-QPP-0001 & 2

Quad Processsor Pack

147

Module faulty
Module faulty
Safe state initiated by software assertion
Internal communication failure or redundant CP
degraded

1) Check if all IO chassis installed in the cabinet are


configured in the hardware configurator
2) Check if the IO bus configuration inside the cabinet
match with the harwdare configurator
3) Verify all IO extender addresses in de cabinet
matches with the addresses in the hardware configurator
On the IO chassis check CA0 thru CA03
In the hardware configurator check the IO bus and IO
chassis address

1) replace reported DO modules


Shutdown on output modules with signals allocated on it with 2) check IO bus
3) check Power 24VDC of IO chassis
fault reaction = Low
4) Check 5VDC/WD cables
RTC SelfTest Error: Real Time Clock does not startup
Replace QPP
Loss of communication between CP's
Message which will appear when 1 cp is halted. As
cp halted
expected
communication overrun between CP1 and cp2
Message which will appear when 1 cp is halted. As
cp halted
expected
Check and correct logic.
Functional Logic Diagrams have a divide by 0
FLD number is reported in details
Instruction error
Trap V Error
Contact TAC, very unlikely to occur
Privelage Violation Error
Contact TAC, very unlikely to occur
Communication overrun between CP1 and cp2
Message which will appear when 1 cp is halted. As
cp halted
expected

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

Start-up not completed


cp halted

1) Set QPP keyswitch to stop and back to run


Check actual diagnostics
If no fault message, Start CP
2) Replace QPP

Error detected in RAM internal communication

FC-QPP-0001 & 2

Quad Processsor Pack

148

Internal communication failure or redundant CP


degraded

FC-QPP-0001 & 2

Quad Processsor Pack

149

Memory error

FC-QPP-0001 & 2

Quad Processsor Pack

150

Communication overrun

Internal Safenet CRC fault

1) Check the number of force and write commands per


second
2) If VP link is connected, decrease number of writes per
second
3) If external devices are connected, reduce number of
writes per second
4) Check configuration of physical and logical network
5) If "run safety builder on device" is enabled at
Experion, disable it and create a separate Safety Builder

FC-QPP-0001 & 2
FC-QPP-0001 & 2

Quad Processsor Pack


Quad Processsor Pack

151
152

Application programs different


Application programs inconsistent

OLM report available


Inconsistency Details

check OLM eport


Contact TAC

FC-QPP-0001 & 2

Quad Processsor Pack

153

Clock source time-out

Clock sysnchronisation clocksource time out expired


No clock synchronisation received witin the specified time

Check in details which clocksource is expired.


Check in the external device if clock synchronisation is
enabled
Check configured time out with recommended time out
If NTP: when NTP device is not synced with GPS, this
message will also be reported
(NTP will set port as Stratum 16: clock not synced)
If a Safety Builder Station connection reports this error,
disable time out for this connection

FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2

Quad Processsor Pack


Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack

154
155
156
157

Safe state initiated by software assertion


Safe state initiated by software assertion
Safe state initiated by software assertion
Safe state initiated by software assertion

Inaccuracy of 1min timers


Inaccuracy of 1s timers
Inaccuracy of 100ms timers
Inaccuracy of 10ms timers

Contact TAC
Contact TAC
Contact TAC
Contact TAC

FC-QPP-0001 & 2

Quad Processsor Pack

158

Repair timer expired

Repair Timer Expired


CP halted

1) Other fault in system ininiated to start the repair timer


and is not solved within the specified time.
- Check Actual diagnostics to detect which fault initiated
the repair timer to start
- Start-up CP by giving a Fault reset
- Check actual diagnostics
- Solve the fault in the system which starts the repair
timer

FC-QPP-0001 & 2
FC-QPP-0001 & 2

Quad Processsor Pack


Quad Processsor Pack

159
160

Module faulty
Safe state initiated by software assertion

Corrupted timers in redundant CP


Timers in FLD's between CP1 and CP2 are not synced

Contact TAC
Contact TAC

Analog output value in apllication out of range with the


analog ouput channel range settings

A calculation overflow occurred in scaling the value from


engineering units to the 12-bit value for the A/D
converter. Check
the calculation of the analog output value in the
functional logic
diagrams.
Be sure the value is within the range setting of the
analog output
Details is mentioning the point

FC-QPP-0001 & 2

Quad Processsor Pack

161

Calculation overflow

Module type
FC-QPP-0001 & 2

Module description
Quad Processsor Pack

EC
162

Description in Safety Builder Diagnostics


Safe state initiated by software assertion

FC-QPP-0001 & 2

Quad Processsor Pack

163

Module faulty

Details
System number out of range
Too often interrupts from time sunc detected
External system is sending to frequent
communication (e.g. a virus attack)
or a hardware fault of the USI

Corrective actions
Contact TAC
1) Check FTE network
2) replace USI

FC-QPP-0001 & 2

Quad Processsor Pack

164

Module faulty

Too often interrupts from time sunc detected


External system is sending to frequent
communication (e.g. a virus attack)
or a hardware fault of the USI

FC-QPP-0001 & 2

Quad Processsor Pack

165

Module faulty

Too often interrupts from speedy detected.


Hardware fault most likely on the redundant QPP

1) Give a wd reset
2) replace other QPP

FC-QPP-0001 & 2

Quad Processsor Pack

166

Module faulty

Hardware fault on the own QPP or the timesync input


contains a high frequency signal, instead of clock pulse

1) replace QPP

FC-QPP-0001 & 2
FC-QPP-0001 & 2

Quad Processsor Pack


Quad Processsor Pack

167
168

FC-QPP-0001 & 2

Quad Processsor Pack

169

Error code not defined


Module faulty
Internal communication failure or redundant CP
degraded

not used
Memory error or internal communication out of sync
Data request inside QPP incorrect

1) Check FTE network


2) replace USI

Replace QPP
1) Replace QPP
2) Contact TAC
Switch QPP key switch of halted cp to stop and then to
Idle
Check status of CPP in 'Load Controller' menu and
Actual Diagnostics
Replace QPP
Replace QPP
Contact TAC
1) Check if correct bus terminator is set on IO bus 1
For non-redundant IO = TERM-0001
For redundant IO = TERM-0002
2) Replace bus terminator on IO bua 1

FC-QPP-0001 & 2

Quad Processsor Pack

170

Internal communication failure or redundant CP


degraded

FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2

Quad Processsor Pack


Quad Processsor Pack
Quad Processsor Pack

171
172
173

Module faulty
Module faulty
Safe state initiated by software assertion

Hardware CRC calculator in QPP-0002 faulty


Fault in Non redudundant watchdog section
Software error

FC-QPP-0001 & 2

Quad Processsor Pack

174

Check I/O bus terminator

No IO Bus termination found on IO bus 1


CP halted/ cannot be started

1) Check if correct bus terminator is set on IO bus 1


For non-redundant IO = TERM-0001
For redundant IO = TERM-0002
2) Replace bus terminator on IO bus 2
1) Check if correct bus terminator is set on IO bus 1
For non-redundant IO = TERM-0001
For redundant IO = TERM-0002
2) Replace bus terminator on IO bus 3

Online modification check not succesfull

FC-QPP-0001 & 2

Quad Processsor Pack

175

Check I/O bus terminator

No IO Bus termination found on IO bus 2


CP halted/ cannot be started

FC-QPP-0001 & 2

Quad Processsor Pack

176

Check I/O bus terminator

No IO Bus termination found on IO bus 3


CP halted/ cannot be started

1) Check if correct bus terminator is set on IO bus 1


For non-redundant IO = TERM-0001
For redundant IO = TERM-0002
2) Replace bus terminator on IO bus 4
Replace QPP

FC-QPP-0001 & 2

Quad Processsor Pack

177

Check I/O bus terminator

No IO Bus termination found on IO bus 4


CP halted/ cannot be started

FC-QPP-0001 & 2
FC-QPP-0001 & 2

Quad Processsor Pack


Quad Processsor Pack

178
179

Module faulty
Error code not defined

Fault detected in IO bus driver


not used

External communication failure

One or more communication links are reported faulty; might


also be reported during OLM from R11x or R12x to R130 or
higher

1) Check which links are faulty in "Link Status"


2) Check configuration as time out etc.
Note: If autorepair is enabled, it may be possible that
communication will be established automatically when
communication is ok.

SafeNet CRC read error

1) Received info is not correct


Check communication loop
2) CRC not correct calculated
Contact TAC

FC-QPP-0001 & 2

FC-QPP-0001 & 2

Quad Processsor Pack

Quad Processsor Pack

180

181

External communication failure

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

1) Check communication loop and Safenet configuration


2) Check details which communication is reported faulty
3) Will also be reported when other systems connected
with Safenet has a CP halted due to OLM.
If links are extablished because a reset was performed
on the other system, another EC182 will be generated
with details "all communication healthy" To clear the
message, perform a reset

FC-QPP-0001 & 2

Quad Processsor Pack

182

External communication failure

SafeNet Timer Expired

FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2

Quad Processsor Pack


Quad Processsor Pack
Quad Processsor Pack

183
184
185

Configuration error
Configuration error
Configuration error

SafeNet Timout TooShort configured


Fault detected SafeNet Configuration
Fault detected SafeNet Configuration

FC-QPP-0001 & 2

Quad Processsor Pack

186

Safenet configuration check failed

SafeNet Timeout during OLM

FC-QPP-0001 & 2

Quad Processsor Pack

187

Safenet incompatible point configuration

Incompatible SafeNet configuration

FC-QPP-0001 & 2

Quad Processsor Pack

188

not used

FC-QPP-0001 & 2

Quad Processsor Pack

189

Error code not defined


Controller too complex to calculate cycle time
within configured DTI

FC-QPP-0001 & 2

Quad Processsor Pack

190

Module faulty

Watchdog startup failure

FC-QPP-0001 & 2

Quad Processsor Pack

191

Secondary switch-off asserted

cp halted initiated by the output "SecSwitchOff"

FC-QPP-0001 & 2

Quad Processsor Pack

192

Module faulty

Watchdog reset enable does not function, hardware fault

Replace QPP

FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2

Quad Processsor Pack


Quad Processsor Pack
Quad Processsor Pack

193
194
195

Module faulty
Module faulty
Module faulty

RTC set failed


RTC accuracy too low
RTC value corrupted

Replace QPP
Replace QPP
Replace QPP

FC-QPP-0001 & 2

Quad Processsor Pack

196

ESD input activated

SD (ShutDown) input activated

At the backside of CP Chassis the SD input is opened.


Normally it's closed by a jumper.
Input can be used for remote ESD

not used

Increase SafeNet Timeout


Check SafeNet configuration
Check SafeNet configuration
1) Check safenet network
2) Turn CP key of CP to IDLE and back to Run on either
the node or peer system to restart the safenet
configuration check
Points between Master and slave do not match.
Must be corrected
Increase DTI
1. Check ESD contact is closed
2. Replace QPP
In the logoc output 'SecSwitchOff' is used and is
activated what initiated the cp's to halt

The other CP detected a fault in of this CP and decided


to halt this CP.
Can be caused by
- Internal communication failures
If it occurs again, replace QPP module

FC-QPP-0001 & 2

Quad Processsor Pack

197

Safe state initiated by redundant control processor

CP is halted by other CP

- Current detected in output loops for FS-SDOL-04xx


modules
Check complete ouput loop(s) and see if it can be
solved.
Note:
In software R102.2 and lower, this fault can also be
caused in demo units with no IO chassis configured.
This ia a system software fault.

Module type
FC-QPP-0001 & 2

Module description
Quad Processsor Pack

EC
198

Description in Safety Builder Diagnostics

Details

Corrective actions

Execution time out of range

The execution cycle time is above the maximum calculated


cycle time
cp halted

Contact TAC and provide them with the complete


application and diagnostics (*.dgn file)
1) Can be caused by too many faults in the system.
In this case solve these items.
If not
2) Contact TAC

FC-QPP-0001 & 2

Quad Processsor Pack

199

Execution time out of range

The execution cycle time is below the minimum calculated


cycle time
CP halted

FC-QPP-0001 & 2

Quad Processsor Pack

200

Memory error

Spurious watchdog interrupt, memory error

FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2

Quad Processsor Pack


Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack

201
202
203
204
205
206

Safe state initiated by software assertion


Safe state initiated by software assertion
Program update failed
Program update failed
Safe state initiated by software assertion
Safe state initiated by software assertion

Software error
Software error
Equalizing between CP1 and CP2 failed
Equalizing between CP1 and CP2 failed
Start-up fail
Inocrrect number of steps

FC-QPP-0001 & 2

Quad Processsor Pack

207

Safe state initiated by software assertion

Tests not ready within DTI

FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2

Quad Processsor Pack


Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack

208
209
210
211
212

Safe state initiated by software assertion


Safe state initiated by software assertion
Safe state initiated by software assertion
Safe state initiated by software assertion
Safe state initiated by software assertion

FC-QPP-0001 & 2

Quad Processsor Pack

213

Measured and calculated FLD execution


difference > 10 %

Inaccuracy of 100ms pulse timers


Inaccuracy of 250ms pulse timers
Inaccuracy of 500ms pulse timer
Inaccuracy of 1s pulse timer
OLM transfer error
Deviation between calculated and measured time for
execution logic sheet deviates more then 10%
CP halted

FC-QPP-0001 & 2

Quad Processsor Pack

214

Controller too complex to calculate cycle time


within configured DTI

Configuration and/or application too complex for calculating


cycletime
CP can not be started

FC-QPP-0001 & 2

Quad Processsor Pack

215

Safe state initiated by software assertion

8 hour test not ready

FC-QPP-0001 & 2

Quad Processsor Pack

216

Communication overrun

Equalize CommandBuffer Full

FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2

Quad Processsor Pack


Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack

217
218
219
220
221
222

Module faulty
Module faulty
Module faulty
Module faulty
Module faulty
Module faulty

Serial Flash Device Faulty


Serial Flash Device Reading Fault
Serial FlashDevice Calc Crc Fault
Serial Flash Device Erase Fault
Serial Flash Device Write Fault
Serial Flash DeviceID Fault

FC-QPP-0001 & 2

Quad Processsor Pack

223

Input compare error

RUSIO Input Compare Error

FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2

Quad Processsor Pack


Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack

224
225
226
227

Module faulty
System program corrupted
Application program corrupted
External communication failure

Imgage Embedded QPP Part2 Incompatible


Serial Flash Embedded Corrupt
Serial Flash Appl Corrupt
RUSIO Configuration Fault

1) Upgrade to R131.5 or higher


2) Contact TAC
Contact TAC
Contact TAC
Contact TAC
Contact TAC
Contact TAC
Contact TAC
1) Can be caused by too many faults in the system.
In this case solve these items.
If not
2) Contact TAC
Contact TAC
Contact TAC
Contact TAC
Contact TAC
Contact TAC
Contact TAC

1) Check if configuration of IO is set correctly


2) Check if IO chassis are set on correct bus
3) Check if the application can bemade less complex
4) Check if it's possible to split complex logic on sheet on
two or more sheets
Contact TAC
1) Reduce number of write commands/second
2) Reduce number of bytes to be written
Toggle key through STOP
Replace QPP
(Re-)Load system
Replace QPP
Replace QPP
(Re-)Load system
CP's detects other status value of the Inputs from RUSIO
3224 module.
Replace module
Replace QPP
Reload system software QPP-0002
Reload system software QPP-0002
Check Configuration of Remote IO module.

Module type

Module description

EC

FC-QPP-0001 & 2

Quad Processsor Pack

228

FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2
FC-QPP-0001 & 2

Quad Processsor Pack


Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack
Quad Processsor Pack

229
230
231
232-250
251

FC-QPP-0001 & 2

Quad Processsor Pack

252

Description in Safety Builder Diagnostics


External communication failure
Functionality degraded
Configuration error
RUSIO module not running
Error code not defined
Module faulty

Input compare error

Details
Report faulty links between Safety Manager and RUSIO
modules (reported by QPP on behalf of the communication
module)
Data transfer between RUSIO at OLM failed
RUSIO Scheduling Fault
RUSIO Not running
not used
Fault reset faulty

FaultReset Compare Error

Corrective actions
- Check link between Safety Manager & RUSIO modules.
E.g. Cables, switches, connections.
Contact TAC
Contact TAC
Contact TAC
Replace QPP
CP's detects other status value of the Fault Reset key
1) Replace BKM
Be-aware that all forces will be cleared when replacing
this module.
2) Replace QPP of CP1
3) Replace QPP of CP2

FC-QPP-0001 & 2

Quad Processsor Pack

253

Input compare error

Force Key Compare Error

CP's detects other status value of the Force key


1) Replace BKM
Be-aware that all forces will be cleared when replacing
this module.
2) Replace QPP of CP1
3) Replace QPP of CP2

FC-QPP-0001 & 2

Quad Processsor Pack

254

Safe state initiated by software assertion

Loop reference

FC-QPP-0001 & 2

Quad Processsor Pack

255

Safe state initiated by software assertion

Software fault

Connect AI input loop or replace transmitter or calibrate


transmitter
Contact TAC

Module type
FC-USI-0001 & 2

Module description
Universal Safety Interface

EC
0

FC-USI-0001 & 2

Universal Safety Interface

Error code not defined

FC-USI-0001 & 2
FC-USI-0001 & 2

Universal Safety Interface


Universal Safety Interface

2
3

Functionality degraded
Safe state initiated by software assertion

FC-USI-0001 & 2

Universal Safety Interface

Configuration error

error detected in communication


configuration

FC-USI-0001 & 2

Universal Safety Interface

Configuration error

error detected in communication


configuration

1) Check plant confguration


2) Check controller configuration
3) Contact TAC

FC-USI-0001 & 2

Universal Safety Interface

Configuration error

error detected in communication


configuration

1) Check plant confguration


2) Check controller configuration
3) Contact TAC

FC-USI-0001 & 2

Universal Safety Interface

Configuration error

error detected in communication


configuration

1) Check plant confguration


2) Check controller configuration
3) Contact TAC

FC-USI-0001 & 2

Universal Safety Interface

Communication program corrupted

Download of Program Image is aborted because the


image is too large or too small. No changes have been
made to the original Program image because the image
size is known right at the beginning of the download.

1) if during system upgrade, re-load cp


2) Contact TAC

FC-USI-0001 & 2

Universal Safety Interface

Communication module faulty

FC-USI-0001 & 2

Universal Safety Interface

10

Communication module faulty

FC-USI-0001 & 2

Universal Safety Interface

11

Functionality degraded

FC-USI-0001 & 2

Universal Safety Interface

12

Communication program corrupted

FC-USI-0001 & 2

Universal Safety Interface

13

Communication module running low on resources

FC-USI-0001 & 2

Universal Safety Interface

14

Error code not defined

FC-USI-0001 & 2

Universal Safety Interface

15

Communication program corrupted

FC-USI-0001 & 2

Universal Safety Interface

16

Communication program corrupted

FC-USI-0001 & 2

Universal Safety Interface

17

Communication program corrupted

Unable to restore backup of Program image

FC-USI-0001 & 2

Universal Safety Interface

18

Communication module faulty

After making backup of Program image, the backup


image appears to be corrupt

FC-USI-0001 & 2

Universal Safety Interface

19

Download failed

FC-USI-0001 & 2

Universal Safety Interface

20

Configuration error

Unable To Make Program Image Backup (Program


Image is too large)
Illegal BOOTP device index detected for channel A

FC-USI-0001 & 2

Universal Safety Interface

21

Configuration error

Illegal BOOTP device index detected for channel B

Configuration error

Channel A:
1) Check plant confguration
Illegal value of last octet of IP-address part (first 3 octets)
2) Check controller configuration
send by BOOTP server. Illegal values are 0 (reserved for
3) Contact TAC
subnet-routers) or 255 (reserved for broadcasts).

FC-USI-0001 & 2

Universal Safety Interface

22

Description in Safety Builder Diagnostics


Error code not defined

Details
Not Used
USI debug details are valid but it is not yet assigned to a
primary error code
Software error
Software error

Module defect
(Unable To Make Program Image Backup, so Download
has been Aborted)
Unable To Make Program Image Backup But Download
Anyway Due To Program Invalid Image
One or more communication protocols
are not started up successfully
The just downloaded and flashed Program Image
appears to be corrupt (automatic restore of backup will be
done)

Corrective actions

Contact TAC
Contact TAC
Contact TAC
1) Check plant confguration
2) Check controller configuration
3) Contact TAC

Replace module
Contact TAC
Contact TAC
1) Load cp
2) Replace module
Contact TAC

Not Used
Restored Program Image appears to be corrupt
Unable to restore Program image backup (no backup is
present)

1) Load cp
2) Replace module
1) Load cp
2) Replace module
1) Load cp
2) Replace module
1) Load cp
2) Replace module
1) Load cp
2) Replace module
Contact TAC
1) Check plant confguration
2) Check controller configuration
3) Contact TAC

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

FC-USI-0001 & 2

Universal Safety Interface

23

Configuration error

Channel B:
1) Check plant confguration
Illegal value of last octet of IP-address part (first 3 octets)
2) Check controller configuration
send by BOOTP server. Illegal values are 0 (reserved for
3) Contact TAC
subnet-routers) or 255 (reserved for broadcasts).

FC-USI-0001 & 2

Universal Safety Interface

24

Configuration error

Channel A:
illegal IPaddress detected (all zeros value used)

1) Check plant confguration


2) Check controller configuration
3) Contact TAC

FC-USI-0001 & 2

Universal Safety Interface

25

Configuration error

Channel B:
illegal IPaddress detected (all zeros value used)

1) Check plant confguration


2) Check controller configuration
3) Contact TAC

FC-USI-0001 & 2

Universal Safety Interface

26

Configuration error

Channel A:
illegal subnetmask address detected (maximum value
used)

1) Check plant confguration


2) Check controller configuration
3) Contact TAC

FC-USI-0001 & 2

Universal Safety Interface

27

Configuration error

FC-USI-0001 & 2
FC-USI-0001 & 2

Universal Safety Interface


Universal Safety Interface

28
29

BootP response time-out


Error code not defined

Channel B:
illegal subnetmask address detected (maximum value
used)
BootP response time out.
Only available in debug version

1) Check plant confguration


2) Check controller configuration
3) Contact TAC
Check if BOOTP server is alive

FC-USI-0001 & 2

Universal Safety Interface

30

BootP response ok

Response from BOOTP Server Succesfully received

FC-USI-0001 & 2

Universal Safety Interface

31

Communication module faulty

FC-USI-0001 & 2
FC-USI-0001 & 2

Universal Safety Interface


Universal Safety Interface

32
33

Error code not defined


Error code not defined

Self-test assertion: module faultly (diagnostic details will


tell which self-test asserted)
Not Used
Not Used

FC-USI-0001 & 2

Universal Safety Interface

34

Functionality degraded

One or more OSE-processes have crashed

FC-USI-0001 & 2

Universal Safety Interface

35

Too many SOE-enabled points configured

Sequence Of Event Generation


Exceeded Actual Application Cycle Time

FC-USI-0001 & 2

Universal Safety Interface

36

Configuration error

Maximum number of DCS addresses exceeded

FC-USI-0001 & 2

Universal Safety Interface

37

Communication program corrupted

Module started up the backup Program image


because the standard Program Image was
corrupted or not present)

FC-USI-0001 & 2

Universal Safety Interface

38

Communication program corrupted

FC-USI-0001 & 2

Universal Safety Interface

39

Communication program corrupted

FC-USI-0001 & 2

Universal Safety Interface

40

FTE Link Loss

FC-USI-0001 & 2
FC-USI-0001 & 2
FC-USI-0001 & 2
FC-USI-0001 & 2

Universal Safety Interface


Universal Safety Interface
Universal Safety Interface
Universal Safety Interface

41
42
43
44

Functionality degraded
Functionality degraded
Functionality degraded
Functionality degraded

1) reset controller
2) If appear again, replace module

1) Check plant and controller confguration


2) Check physical and logical network. Be sure they
are matching
3) Contact TAC
1) Lower number of SOE-enabled points
2) If it appears again, do step 1 again
1) Lower number of DCS addresses
2) Check Logical connection???
3) Contact TAC
1) Re-load cp, if possible
2) Replace module
3) Contact TAC

1) Re-load cp, if possible


Both (standard and backup) Program Images were found
2) Replace module
to be corrupted or not present at powerup
3) Contact TAC
Program image in use that is marked as "not present" but 1) Re-load cp, if possible
its CRC is valid
2) Contact TAC
External Communication failure.
Communication with an external Device on a particular
Physical Link has failed. This could be due to a
disconnected cable.
Internal TTE process failure
Flooding failure in 'receive common layers'
Transmit issues
Flash memory error

1) Check cabling
2) check switches and routing
3) Check time out settings in Physical and logical
view
Contact TAC
Contact TAC
Replace module
Replace module

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

FC-USI-0001 & 2
FC-USI-0001 & 2

Universal Safety Interface


Universal Safety Interface

45
46

Functionality degraded
Configuration error

non fatal error


Com Port For Protocol in Idle

FC-USI-0001 & 2

Universal Safety Interface

47

Configuration error

Secondary comport must be undefined when using


protocol Idle RQ

1) Replace USI
1) Replace USI
1) Check plant confguration
2) Check controller configuration
3) Contact TAC

FC-USI-0001 & 2

Universal Safety Interface

48

Configuration error

Invalid protocol baudrate combination

1) Check plant confguration


2) Check controller configuration
3) Contact TAC

FC-USI-0001 & 2

Universal Safety Interface

49

Configuration error

Invalid primary com port for protocol TcpIp

1) Check plant confguration


2) Check controller configuration
3) Contact TAC

FC-USI-0001 & 2

Universal Safety Interface

50

Configuration error

Invalid secondary comport for protocol TcpIp

FC-USI-0001 & 2

Universal Safety Interface

51

Configuration error

Max. number of protocols exceeded

FC-USI-0001 & 2

Universal Safety Interface

52

Configuration error

FC-USI-0001 & 2

Universal Safety Interface

53

Configuration error

FC-USI-0001 & 2

Universal Safety Interface

54

Configuration error

FC-USI-0001 & 2

Universal Safety Interface

55

Configuration error

FC-USI-0001 & 2

Universal Safety Interface

56

Configuration error

FC-USI-0001 & 2

Universal Safety Interface

57

Configuration error

IP Address of channel A and B are the same


SubnetMask is conflicting with
IP Addressing
Gateway conflicting with
IP addresses channel A & B
Gateway A conflicting with
IP address channel A
Gateway B conflicting with
IP address channel
Error detected in Bootp software

FC-USI-0001 & 2

Universal Safety Interface

58

Configuration error

Error detected during download (see diagnostic details)

FC-USI-0001 & 2

Universal Safety Interface

59

Functionality degraded

Power-up Self-test assertion (e.g.)


(see diagnostic details)

FC-USI-0001 & 2

Universal Safety Interface

60

Memory error

FC-USI-0001 & 2

Universal Safety Interface

61

Memory error

FC-USI-0001 & 2

Universal Safety Interface

62

Too many SOE-enabled points configured

Sequence Of Event Generation


Exceeded Minimum Application Cycle Time Threshold

FC-USI-0001 & 2

Universal Safety Interface

63

Configuration error

USI SafeNet Schedule Overrun error

FC-USI-0001 & 2

Universal Safety Interface

64

Functionality degraded

USI Queue Flooding error

Memory error line assertion by QPP for Communication


module 1 (USI or SMM)
Memory error line assertion by QPP for Communication
module 2 (USI or SMM)

FC-USI-0001 & 2

Universal Safety Interface

65

Configuration error

USI fault

FC-USI-0001 & 2
FC-USI-0001 & 2

Universal Safety Interface


Universal Safety Interface

66
67

Flooding Detected
TT Ethernet Failed

FC-USI-0001 & 2

Universal Safety Interface

68

Communication overrun
Ethernet to Remote modules faulty
Duplicate RUSIO node address detected or RUSIO
replaced

FC-USI-0001 & 2

Universal Safety Interface

69

Ethernet to Remote modules faulty

TT Ethernet Link Down

FC-USI-0001 & 2

Universal Safety Interface

70

RUSIO network topology problem detected

Code RUSIO Network Topology Problem Detected

FC-USI-0001 & 2

Universal Safety Interface

71

Download failed

RUSIO Download Failure

RUSIO MAC Address Change Detected

1) Check plant confguration


2) Check controller configuration
3) Contact TAC
1) Check controller network configuration
2) Contact TAC
Check IP addressing in logical view
Check IP addressing & subnetmask in logical view
Check IP addressing & subnetmask in logical view
Check IP addressing & subnetmask in logical view
Check IP addressing & subnetmask in logical view
Contact TAC
1) Attempt to re-load
1) power cycle module
2) Replace module
1) power cycle USI + QPP
2) Replace Communication module 1
1) power cycle USI + QPP
2) Replace Communication module 2
1) Lower number of SOE-enabled points
2) If it appears again, do step 1 again
1) Increase SafeNet time out
1) Check configuration
2) Check cabling
3) Check jumper settings DCOM Third party
equipment
1) Check configuration
2) Check cabling
3) Check jumper settings DCOM Third party
equipment
Check the network load. Flooding is detected
Contact TAC
Check the Node numbers of the RUSIO that is
placed on the RUSIO link.
- Check link between Safety Manager & RUSIO
modules. E.g. Cables, switches, connections.
Check the Node numbers of the RUSIO that is
placed on the RUSIO link.
Reload Safety manager

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

FC-USI-0001 & 2

Universal Safety Interface

72

HART communication with device lost

HART communication with device lost

Check HART device and field witing for problem

FC-USI-0001 & 2
FC-USI-0001 & 2
FC-USI-0001 & 2

Universal Safety Interface


Universal Safety Interface
Universal Safety Interface

73
74
75-102

Ethernet to Remote modules faulty


Modbus Master link fault
Error code not defined

FC-USI-0001 & 2

Universal Safety Interface

103

FC-USI-0001 & 2
FC-USI-0001 & 2
FC-USI-0001 & 2
FC-USI-0001 & 2
FC-USI-0001 & 2
FC-USI-0001 & 2
FC-USI-0001 & 2
FC-USI-0001 & 2
FC-USI-0001 & 2
FC-USI-0001 & 2

Universal Safety Interface


Universal Safety Interface
Universal Safety Interface
Universal Safety Interface
Universal Safety Interface
Universal Safety Interface
Universal Safety Interface
Universal Safety Interface
Universal Safety Interface
Universal Safety Interface

104-111
112
113
114
115
116-145
146
147-148
149
150

FC-USI-0001 & 2

Universal Safety Interface

151

Memory error

FC-USI-0001 & 2

Universal Safety Interface

152

Memory error

FC-USI-0001 & 2

Universal Safety Interface

153

Memory error

FC-USI-0001 & 2

Universal Safety Interface

154

Memory error

FC-USI-0001 & 2

Universal Safety Interface

FC-USI-0001 & 2

Universal Safety Interface

171

Memory error

FC-USI-0001 & 2

Universal Safety Interface

172

Module faulty

FC-USI-0001 & 2
FC-USI-0001 & 2

Universal Safety Interface


Universal Safety Interface

FC-USI-0001 & 2

Universal Safety Interface

228

FC-USI-0001 & 2
FC-USI-0001 & 2
FC-USI-0001 & 2
FC-USI-0001 & 2

Universal Safety Interface


Universal Safety Interface
Universal Safety Interface
Universal Safety Interface

229
230
231
232-255

TT Ethernet Link Switchover


Modbus Master link fault
Not Used
Com upgrade offLine
Online upgrade not possible
Not Used
Communication module 1 (USI or SMM) removed
Communication module 2 (USI or SMM) removed
Communication module 1 (USI or SMM) inserted
Communication module 2 (USI or SMM) inserted
Not Used
Communication module not responding
Not Used
Shram Communication timeout
Communication overrun
Shram memory Self-test assertion
(Self-test executed by QPP)
Shram memory Self-test assertion
(Self-test executed by QPP)
Shram memory Self-test assertion
(Self-test executed by QPP)
Shram memory Self-test assertion
(Self-test executed by QPP)
Not Used
Shram memory Self-test assertion
(Self-test executed by QPP)
Interrupt COM to QPP Self-test assertion
(Self-test executed by QPP)
Not Used
RUSIO Configuration Fault
Report faulty links between Safety Manager and RUSIO
modules (reported by QPP on behalf of the
communication module)
Not Used
Not Used
RUSIO Not running
Not Used

Incorrect software version


Error code not defined
COM module removed
COM module removed
COM module detected
COM module detected
Error code not defined
Module faulty
Error code not defined
Module faulty
Communication overrun

155-170 Error code not defined

173-226 Error code not defined


227
Software Fault
External communication failure
Error code not defined
Error code not defined
RUSIO module not running
Error code not defined

Contact TAC
no action needed
no action needed
no action needed
no action needed
Replace module
Contact TAC
Contact TAC
1) power cycle module
2) Replace module
1) power cycle module
2) Replace module
1) power cycle module
2) Replace module
1) power cycle module
2) Replace module
1) power cycle module
2) Replace module
1) power cycle module
2) Replace module
Check configuration of Remote IO
- Check link between Safety Manager & RUSIO
modules. E.g. Cables, switches, connections.

Contact TAC

Module type
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

Safe Remote IO module 24 Volt

Error code not defined

Not Used

Safe Remote IO module 24 Volt

Module faulty

Fault detected during 68000 selftest

Replace the module

Safe Remote IO module 24 Volt

Module faulty

Fault detected during 68000 selftest

Replace the module

Safe Remote IO module 24 Volt

Module faulty

Fault detected during 68000 selftest

Replace the module

Safe Remote IO module 24 Volt

Module faulty

Fault detected during 68000 selftest

Replace the module

Safe Remote IO module 24 Volt

Module faulty

Fault detected during 68000 selftest

Replace the module

Safe Remote IO module 24 Volt

Module faulty

Fault detected during 68000 selftest

Replace the module

Safe Remote IO module 24 Volt

Module faulty

Fault detected during 68000 selftest

Replace the module

Safe Remote IO module 24 Volt

Module faulty

Fault detected during 68000 selftest

Replace the module

Safe Remote IO module 24 Volt

Module faulty

Fault detected during mem test

Replace the module

Safe Remote IO module 24 Volt

10

Module faulty

Fault detected during mem test

Replace the module

Safe Remote IO module 24 Volt

11

Module faulty

Fault detected during 68000 selftest

Replace the module

Safe Remote IO module 24 Volt

12

Module faulty

Fault detected during 68000 selftest

Replace the module

Safe Remote IO module 24 Volt

13

Module faulty

Fault detected during accumulator unit

Replace the module

Safe Remote IO module 24 Volt

14

Calculation overflow

Error detected in Equation Block

Safe Remote IO module 24 Volt

15

Calculation overflow

OverFlow detected

Safe Remote IO module 24 Volt

16

Divide by zero

Divide By 0

Safe Remote IO module 24 Volt

17

Illegal argument e.g. Root of 1

Illegal Argument detected

Safe Remote IO module 24 Volt

18

Illegal timer value

Illegal Timer Value

Safe Remote IO module 24 Volt

19

Module faulty

Force Test

Replace the module

Safe Remote IO module 24 Volt

20

Illegal counter value

Illegal Counter Value

In a calculation an illegal counter value is used.


check the calculations in the logic of the specified FLD.

Safe Remote IO module 24 Volt

21

Module faulty

Watchdog or DPRAM faulty

Replace the module

Safe Remote IO module 24 Volt

22

Execution time out of range

Watchdog Minimum Runtime (IRQ4)

The application cycle of the Remote IO module is out of range.


Contact TAC

Safe Remote IO module 24 Volt

23

Execution time out of range

Watchdog Maximum Runtime (IRQ4)

The application cycle of the Remote IO module is out of range.


Contact TAC

Safe Remote IO module 24 Volt

24

Module faulty

Watchdog Startup Failed

Replace the module

Safe Remote IO module 24 Volt

25

Module faulty

WatchDog Max Timer Self Test failed

Replace the module

Safe Remote IO module 24 Volt

26

Module faulty

WatchDog Min Timer Self test failed

Replace the module

Safe Remote IO module 24 Volt

27

Module faulty

Watchdog Voltage Monitor Self Test

Replace the module

Calculation yields a result that is out of a specified range.


check the calculation in the logic of the specified FLD.
Calculation yields a result that is out of a specified range.
check the calculation in the logic of the specified FLD.
In a calculation a divide by zero error occurs.
check the calculations in the logic of the specified FLD.
In a calculation an illegal argument is used.
check the calculations in the logic of the specified FLD.
In a calculation an illegal timer value is used.
check the calculations in the logic of the specified FLD.

Module type
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224

FC-RUSIO-3224 &
FC-RUSLS-3224

FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

Safe Remote IO module 24 Volt

28

Configuration error

Module Type Mismatch

Check node number and module type

Safe Remote IO module 24 Volt

29

Module faulty

Eeprom Faulty

Replace the module

Voltage Reference self test failed


Detail1:
bit 2: Pos3V3
bit 3: Neg8V
bit 4: Neg11V
bit 5: Pos24V
bit 10: Neg2V5
bit 14: Neg5V RedProc

Replace the module

Safe Remote IO module 24 Volt

30

Module faulty

Safe Remote IO module 24 Volt

31

Module faulty

5V Calibration failed

Replace the module

Safe Remote IO module 24 Volt

32

Module faulty

1ms timer Faulty

Replace the module

Safe Remote IO module 24 Volt

33

Module faulty

DPRam Faulty

Replace the module

Spurious Watchdog Interrupt (IRQ4)

FC-RUSIO-3224 &
FC-RUSLS-3224

FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224

Can be:
- Voltage monitors
- Minimum / Maximum runtime
- ESD
- HWC FLASH
- WD test failures

Replace the module

Safe Remote IO module 24 Volt

34

Module faulty

Safe Remote IO module 24 Volt

35

Module faulty

Flash Hardware Comparator Failed

Replace the module

Safe Remote IO module 24 Volt

36

Memory error

Not sufficient memory available in the RUSIO module or the


module is faulty.

replace the module.

Memory Error (IRQ7)


FC-RUSIO-3224 &
FC-RUSLS-3224

FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224

Can be:
- Parity error on reading own DpRam
- HCW error on FLASH access
- Illegal NSR write to DpRam

Replace the module

Safe Remote IO module 24 Volt

37

Module faulty

Safe Remote IO module 24 Volt

38

Module faulty

Illegal Vector

Replace the module

Safe Remote IO module 24 Volt

39

Module faulty

Access Error

Replace the module

Safe Remote IO module 24 Volt

40

Temperature shutdown

Temp Low Low

The temperature is out of range.


check the fans, airflow and environmental conditions.

Safe Remote IO module 24 Volt

41

Temperature shutdown

Temp High High

The temperature is out of range.


check the fans, airflow and environmental conditions.

Safe Remote IO module 24 Volt

42

Module faulty

Address Error

Replace the module

Safe Remote IO module 24 Volt

43

Module faulty

Illegal Instruction

Replace the module

Safe Remote IO module 24 Volt

44

Module faulty

Privilege Violation

Replace the module

Safe Remote IO module 24 Volt

45

Module faulty

Trace Exception

Replace the module

Safe Remote IO module 24 Volt

46

Module faulty

Unimplemented A Line

Replace the module

Module type
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224

FC-RUSIO-3224 &
FC-RUSLS-3224

FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

Safe Remote IO module 24 Volt

47

Module faulty

Unimplemented F Line

Replace the module

Safe Remote IO module 24 Volt

48

Module faulty

Format Error

Replace the module

Safe Remote IO module 24 Volt

49

Module faulty

Unitialized Interrupt

Replace the module

Safe Remote IO module 24 Volt

50

Module faulty

Spurious Interrupt

Replace the module

Safe Remote IO module 24 Volt

51

Module faulty

Parity Redundant Error

Replace the module

Safe Remote IO module 24 Volt

52

Module faulty

Parity Redundant Error

Replace the module

Safe Remote IO module 24 Volt

53

Module faulty

Parity Error DPRam Redundant Proc (IRQ6)

Replace the module

Safe Remote IO module 24 Volt

54

Module faulty

SMOD Control Line Independence Test Failed

Replace the module

Safe Remote IO module 24 Volt

55

Module faulty

DO FET Control Line Independence Test Failed

Replace the module

Safe Remote IO module 24 Volt

56

Module faulty

SMOD Off DO Channel test Failed

Replace the module

Safe Remote IO module 24 Volt

57

Module faulty

Analog Digital Converter Walking Bit Test failed

Replace the module

Safe Remote IO module 24 Volt

58

Module faulty

Digital Analog Converter Walking Bit Test failed

Replace the module

Safe Remote IO module 24 Volt

59

Module faulty

Digital Analog Converter Independence Test failed

Replace the module

Safe Remote IO module 24 Volt

60

Module faulty

Mux Independence Test

Replace the module

Safe Remote IO module 24 Volt

61

Module faulty

Faulty Channel

Replace the module


One or more loop faults have been detected. The field sensor(s) may
(temporarily) have been out of range or there is/was a (number of)
open loop or short circuit(s).
as multiple channels may have loop faults you must check the Loop
Monitoring screen to see which channels have loop faults. To find
possible causes for loop faults:
- check the value of the field sensor
- check the field wiring.

Safe Remote IO module 24 Volt

62

Open loop(s)

Open Loop

Safe Remote IO module 24 Volt

63

Short circuit

Loop Short

Check the loop(s) on short circuit reported in loop monitoring

Safe Remote IO module 24 Volt

64

Device detected on spare channel

Device Detected On Spare Channel

Remove Device that is connected to the spare channel

Safe Remote IO module 24 Volt

65

Module faulty

Leak Current High

Replace the module

Safe Remote IO module 24 Volt

66

Module faulty

AO Actual Value Invalid

Check the loop and the attached device

Safe Remote IO module 24 Volt

67

Safe state initiated by software assertion

AO Compare fault

Contact TAC

Safe Remote IO module 24 Volt

68

Module faulty

Current Read Back Difference

Check the loop and the attached device

Safe Remote IO module 24 Volt

69

Safe state initiated by software assertion

Input Sync fault detected

Contact TAC

Safe Remote IO module 24 Volt

70

Module faulty

AO Over Current detected

Check the loop and the attached device

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

FC-RUSIO-3224 &
FC-RUSLS-3224

Safe Remote IO module 24 Volt

71

Field device value stuck at

DI Too Long In Transit

The value of the input field device is stuck at an undefined value.


check the input signal for slow transients and undefined state. A
signal with an undefined state can have a random value.

Safe Remote IO module 24 Volt

72

Safe state initiated by software assertion

DO Compare detected

Contact TAC

Safe Remote IO module 24 Volt

73

Safe state initiated by software assertion

Test Not Ready In DTI

Contact TAC

Safe Remote IO module 24 Volt

74

Safe state initiated by software assertion

Processor Synchronization Error

Contact TAC

Safe Remote IO module 24 Volt

75

Module faulty

Analog Digital Converter Result Register Corrupt

Replace the module

Safe Remote IO module 24 Volt

76

Module faulty

Internal Ram Error

Replace the module

Safe Remote IO module 24 Volt

77

Temperature sensor faulty

Temperature Single Sensor Failure

Safe Remote IO module 24 Volt

78

Execution time out of range

Execution Time Failure

Safe Remote IO module 24 Volt

79

Module faulty

Redundant Module Not Present

FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224

FC-RUSIO-3224 &
FC-RUSLS-3224

FC-RUSIO-3224 &
FC-RUSLS-3224

Safe Remote IO module 24 Volt

Safe Remote IO module 24 Volt

80

81

Internal communication failure or redundant CP


degraded

Internal communication failure or redundant CP


degraded

DPRam Link Faulty

Serial Link Redundant Processor Faulty

The specified temperature sensor is regarded faulty.


Replace the module
The application cycle of the Remote IO module is out of range.
Contact TAC
Replace the module

Note:
When you manually create shutdowns of one Control Processor such
as during an OLM you can safely ignore this message: An internal
communication failure or CP degraded message is always generated
when losing communication to the other Control Processor.
An internal communication failure is detected if one of the redundant
communication links between the active RUSIO modules has failed.
When detecting an internal communication failure the system halts
one Control Processor.

Note:
When you manually create shutdowns of one Control Processor such
as during an OLM you can safely ignore this message: An internal
communication failure or CP degraded message is always generated
when losing communication to the other Control Processor.
An internal communication failure is detected if one of the redundant
communication links between the active RUSIO modules has failed.
When detecting an internal communication failure the system halts
one Control Processor.

Module type

FC-RUSIO-3224 &
FC-RUSLS-3224

FC-RUSIO-3224 &
FC-RUSLS-3224

FC-RUSIO-3224 &
FC-RUSLS-3224

FC-RUSIO-3224 &
FC-RUSLS-3224

FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224

Module description

Safe Remote IO module 24 Volt

Safe Remote IO module 24 Volt

Safe Remote IO module 24 Volt

EC

82

83

84

Description in Safety Builder Diagnostics

Internal communication failure or redundant CP


degraded

Internal communication failure or redundant CP


degraded

Internal communication failure or redundant CP


degraded

Details

Serial Link Redundant Module Faulty

Ethernet Link Redundant Module Faulty

Status Block Size Invalid

Corrective actions

Note:
When you manually create shutdowns of one Control Processor such
as during an OLM you can safely ignore this message: An internal
communication failure or CP degraded message is always generated
when losing communication to the other Control Processor.
An internal communication failure is detected if one of the redundant
communication links between the active RUSIO modules has failed.
When detecting an internal communication failure the system halts
one Control Processor.

Note:
When you manually create shutdowns of one Control Processor such
as during an OLM you can safely ignore this message: An internal
communication failure or CP degraded message is always generated
when losing communication to the other Control Processor.
An internal communication failure is detected if one of the redundant
communication links between the active RUSIO modules has failed.
When detecting an internal communication failure the system halts
one Control Processor.

Note:
When you manually create shutdowns of one Control Processor such
as during an OLM you can safely ignore this message: An internal
communication failure or CP degraded message is always generated
when losing communication to the other Control Processor.
An internal communication failure is detected if one of the redundant
communication links between the active RUSIO modules has failed.
When detecting an internal communication failure the system halts
one Control Processor.

This shutdown can be caused by:


1. Internal out of range
Replace or Check external power.
2. Memory error
Replace RUSIO modules.
3. Program runtime error
Contact TAC
The watchdog status is displayed automatically.

Safe Remote IO module 24 Volt

85

Spurious watchdog interrupt

Core Watchdog Tripped

Safe Remote IO module 24 Volt

86

Module faulty

AO Calibration error detected

Replace the module

Safe Remote IO module 24 Volt

87

Temperature sensor faulty

Temperature Dual Sensor Failure

The specified temperature sensor is regarded faulty.


Replace the module

Safe Remote IO module 24 Volt

88

Module faulty

Write Violation Detection Channel Failed

Replace the module

Safe Remote IO module 24 Volt

89

Module faulty

Write Violation Detection SMOD Failed

Replace the module

Safe Remote IO module 24 Volt

90

Module faulty

Write Violation Detection DPRam Failed

Replace the module

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

FC-RUSIO-3224 &
FC-RUSLS-3224

Safe Remote IO module 24 Volt

91

Module faulty

Current Too Low Test Failed

Replace the module

FC-RUSIO-3224 &
FC-RUSLS-3224

Safe Remote IO module 24 Volt

92

Embedded software corrupted

System Image CRC Mismatch

A CRC error has been detected in the firmware during the start-up
check.
load the Controller file again. If the fault persists after download,
Replace the module

FC-RUSIO-3224 &
FC-RUSLS-3224

Safe Remote IO module 24 Volt

93

Application program corrupted

Application Image CRC Mismatch

Load application again

FC-RUSIO-3224 &
FC-RUSLS-3224

FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224

FC-RUSIO-3224 &
FC-RUSLS-3224

FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224

Safe Remote IO module 24 Volt

94

Embedded software corrupted

FPGA Hardware CRC Mismatch

A CRC error has been detected in the firmware during the start-up
check.
load the Controller file again. If the fault persists after download,
Replace the module

Safe Remote IO module 24 Volt

95

Module faulty

DO Independence test failed

Replace the module

Safe Remote IO module 24 Volt

96

Module faulty

SMOD On

Replace the module

Safe Remote IO module 24 Volt

97

Module faulty

Boot Image CRC Mismatch

Replace the module

Safe Remote IO module 24 Volt

98

ESD-switch at IOTA in wrong position

ESD circuit Failure Or ESD Switch Differs With ESD


Configuration

Check the RUSIO configuration especially the ESD configuration

Safe Remote IO module 24 Volt

99

Module faulty

ESD Circuit Failure 2

Replace the module


The ESD wiring circuit connected to the Controller backplane has
been
broken because:
- an ESD button has been pushed or
- there is a wiring defect
Check the state of the ESD wiring circuit.

Safe Remote IO module 24 Volt

100

ESD input activated

ESD Input Activated (IRQ4)

Safe Remote IO module 24 Volt

101

Module faulty

Program Counter Test Fail

Replace the module

Safe Remote IO module 24 Volt

102

Shutdown due to RUSIO internal or external


communication link failure

Redundant module Communication Failure

Replace the module

Safe Remote IO module 24 Volt

103

Module faulty

ESD Channel OPAMP Failure

Replace the module

Safe Remote IO module 24 Volt

104

Module faulty

Analog Digital Converter Calibration

Replace the module

Safe Remote IO module 24 Volt

105

Module faulty

Watchdog Startup Failed from Test

Replace the module

Safe Remote IO module 24 Volt

106

Module faulty

Leak Current High

Replace the module

Safe Remote IO module 24 Volt

107

Module faulty

DMA Error

Replace the module

Safe Remote IO module 24 Volt

108

Module faulty

Safe Remote IO module 24 Volt

109

Module faulty

Digital Output Over current

Replace the module

Safe Remote IO module 24 Volt

110

Short circuit in field wiring

Digital Input Short Circuit

Check the channel reported in diagnostics for a short circuit

Safe Remote IO module 24 Volt

111

Safe state initiated by software assertion

Output Diagnostic Failure

Contact TAC

Safe Remote IO module 24 Volt

112

Safe state initiated by software assertion

Input Diagnostic Failure

Contact TAC

Safe Remote IO module 24 Volt

113

Functionality degraded

Start Up Not Allowed

Contact TAC

Replace the module

Module type
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

Safe Remote IO module 24 Volt

114

IOTA faulty (TBD)

Current Sense Resistor Fault

Check the Channel reporting the Short Circuit.

Safe Remote IO module 24 Volt

115

Repair timer expired

Replace the module

Safe Remote IO module 24 Volt

116

Repair timer started

Replace the module

Safe Remote IO module 24 Volt

117

Module faulty

Diode Test failure

Replace the module

Safe Remote IO module 24 Volt

118

Safe state initiated by software assertion

1ms Base Timer Synchronization Fault

Replace the module

Safe Remote IO module 24 Volt

119

RIO SOE buffer full

SOE Buffer Overflow

Check the RIO link availablility to the USI

Safe Remote IO module 24 Volt

120

Safe state initiated by software assertion

Wrong Number of FLDs executed

Contact TAC

Safe Remote IO module 24 Volt

121

Measured and calculated FLD execution


difference > 10 %

FLD execution time out of range

Contact TAC

Safe Remote IO module 24 Volt

122

Program execution assertion (output sync)

Not enough diagnostics spare time

A Warning that diagnostics time is critical.


1. Increase DTI if possible
2. On RUSIO move some points to another module
3. On RUSLS Simplify the FLD or move points to another module

Safe Remote IO module 24 Volt

123

Module faulty

Field Independence Fault

Check Field wiring for shorts between channels

Safe Remote IO module 24 Volt

124

Program execution assertion (output sync)

Modules out of Sync

Contact TAC

Safe Remote IO module 24 Volt

125

AO value out of range

AO value out of range

Check application for values exceding the configured AO range

Safe Remote IO module 24 Volt

126

Module faulty

Device Malfunction

HART field device reports that it has malfunctioned.


Replace the HART device

Safe Remote IO module 24 Volt

127

Range Check

Range Check

Safe Remote IO module 24 Volt

128

Module faulty

HART processor Programming Failed

Replace the module

FC-RUSIO-3224 &
FC-RUSLS-3224

Safe Remote IO module 24 Volt

129

Temperature pre-alarm

Temp Low Alarm

The temperature in RUSIO module is becoming critical.


check the fans, airflow and environmental conditions.

FC-RUSIO-3224 &
FC-RUSLS-3224

Safe Remote IO module 24 Volt

130

Temperature pre-alarm

Temp High Alarm

The temperature in RUSIO module is becoming critical.


check the fans, airflow and environmental conditions.

Safe Remote IO module 24 Volt

131

Module faulty

HART Communcation Failure

Contact TAC

Safe Remote IO module 24 Volt

132

Module faulty

External Ethernet Physical Crash

Contact TAC

Safe Remote IO module 24 Volt

133

External communication failure

TTE Error

Contact TAC

Safe Remote IO module 24 Volt

134

External communication failure

RUSIO Protocol Error

Contact TAC

Safe Remote IO module 24 Volt

135

Functionality degraded

MDO channel currents too far apart

Contact TAC

Safe Remote IO module 24 Volt

136

Program execution assertion (output sync)

Unexpected statistics value

Safe Remote IO module 24 Volt

137

FC-RUSIO-3224 &
FC-RUSLS-3224

FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224

FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224
FC-RUSIO-3224 &
FC-RUSLS-3224

Safe Remote IO module 24 Volt

Module faulty

138-255 Error code not defined

Device EMI
Not used

Contact TAC
Contact TAC

Module type
FC-BKM-0001
FC-BKM-0001
FC-BKM-0001
FC-BKM-0001

Module description
Battery & Keyswitch
Module
Battery & Keyswitch
Module
Battery & Keyswitch
Module
Battery & Keyswitch
Module

EC

Description in Safety Builder Diagnostics

Details

Error code not defined

not used

95

Check battery

Lithium Retention Limit

Replace batteries in BKM

96

Check battery

No Lithium Cell Power

Replace batteries in BKM

0 - 94

97 - 255 Error code not defined

not used

Corrective actions

Module type

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

Module description

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

EC

Description in Safety Builder Diagnostics

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Details

Corrective actions

Fault detected on select line 1

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 2

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 3

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 4

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 5

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 6

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 7

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 8

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Module type

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

Module description

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

EC

10

11

12

13

14

15

Description in Safety Builder Diagnostics

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Details

Corrective actions

Fault detected on select line 9

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 10

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 11

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 12

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 13

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 14

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 15

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 16

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Module type

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

Module description

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

EC

16

17

18

19

20

21

22

23

Description in Safety Builder Diagnostics

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Details

Corrective actions

Fault detected on select line 17

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 18

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

General fault detected on select lines

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Read line 0

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Read line 1

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal test line 0

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal test line 1

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Write line 0

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Module type

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

Module description

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

EC

24

25

26

27

28

29

30

31

Description in Safety Builder Diagnostics

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Details

Corrective actions

Fault detected on Horizontal Write line 1

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Dataline 0

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Dataline 1

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Dataline 2

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Dataline 3

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Dataline 4

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Dataline 5

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Dataline 6

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Module type

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

Module description

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

EC

32

33

34

35

36

37

38

39

Description in Safety Builder Diagnostics

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Details

Corrective actions

Fault detected on Horizontal Dataline 7

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Dataline 0

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Dataline 1

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Dataline 2

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Dataline 3

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Dataline 4

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Dataline 5

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Dataline 6

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Module type

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

FC-IO-0001

Module description

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

EC

40

41

42

43

44

45

46

Description in Safety Builder Diagnostics

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Details

Corrective actions

Fault detected on Horizontal Dataline 7

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Read line 0

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Read line 1

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal test line 0

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal test line 1

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal HWR0

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal HWR1

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Module type

Module description

FC-IO-0001
FC-IO-0001

IO Extender Module
IO Extender Module

FC-IO-0001

IO Extender Module

FC-IO-0001

IO Extender Module

FC-IO-0001

IO Extender Module

FC-IO-0001

IO Extender Module

FC-IO-0001

IO Extender Module

EC

Description in Safety Builder Diagnostics

47
Module faulty
48..137 Error code not defined

138

139

I/O extender address incorrect or an additional I/O


extender placed

Corrective actions

Fault detected during a indepence test


Not used

Replace module

Illigal IO extender IO-0001 detected.


As it is not possible to determine chassis and slot
for an illegal placed HBD, it is reported with the
QPP chassis and slot.

Module faulty

180..255 Error code not defined

1) Check if all IO chassis installed in the cabinet are


configured in the hardware configurator
2) Check if the IO bus configuration inside the
cabinet match with the harwdare configurator
3) Verify all IO extender addresses in de cabinet
matches with the addresses in the hardware
configurator
On the IO chassis check CA0 thru CA03
In the hardware configurator check the IO bus
and IO chassis address
1) Check jumper settings IO extenders on back of
IO chassis
2) Check software and hardware configuration
3) Check 5VDC connection

Module faulty

139..178 Error code not defined


179

Details

Not used
IO Extender quick test
Not used

1) Check 5VDC to this chassis


2) Check front flatcable of this module
3) Replace module
4) Replace other modules in IO chassis

Module type

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

Module description

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

EC

Description in Safety Builder Diagnostics

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Details

Corrective actions

Fault detected on select line 1 of own module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 2 of own module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 3 of own module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 4 of own module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 5 of own module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 6 of own module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 7 of own module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Module type

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

Module description

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

EC

10

11

12

13

14

Description in Safety Builder Diagnostics

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Details

Corrective actions

Fault detected on select line 8 of own module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 9 of own module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 10 of own module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 11 of own module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 12 of own module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 13 of own module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 14 of own module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 15 of own module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Module type

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

Module description

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

EC

15

16

17

18

19

20

21

22

Description in Safety Builder Diagnostics

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Details

Corrective actions

Fault detected on select line 16 of own module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 17 of own module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on select line 18 of own module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

General fault detected on select lines of own


module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Read line 0 of own


module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Read line 1 of own


module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal test line 0 of own


module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal test line 1 of own


module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Module type

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

Module description

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

EC

23

24

25

26

27

28

29

30

Description in Safety Builder Diagnostics

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Details

Corrective actions

Fault detected on Horizontal Write line 0 of own


module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Write line 1 of own


module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Dataline 0 of own


module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Dataline 1 of own


module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Dataline 2 of own


module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Dataline 3 of own


module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Dataline 4 of own


module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Dataline 5 of own


module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Module type

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

Module description

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

EC

31

32

33

34

35

36

37

38

Description in Safety Builder Diagnostics

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Details

Corrective actions

Fault detected on Horizontal Dataline 6 of own


module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Dataline 7 of own


module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Dataline 0 of own


module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Dataline 1 of own


module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Dataline 2 of own


module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Dataline 3 of own


module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Dataline 4 of own


module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Dataline 5 of own


module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Module type

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

Module description

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

EC

39

40

41

42

43

44

45

46

Description in Safety Builder Diagnostics

Details

Corrective actions

Fault detected on Horizontal Dataline 6 of own


module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Dataline 7 of own


module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Read line 0 of own


module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal Read line 1 of own


module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Fault detected on Horizontal test line 0 of own


module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Module faulty

Fault detected on Horizontal test line 1 of own


module

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Module faulty

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
Fault detected on Horizontal HWR0 of own module 3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Module faulty

1) Check if V-bus connections are tighly connected


2) Check jumper settings of IO rack CA0 thru CA3
Fault detected on Horizontal HWR1 of own module 3) Check f flatcable from H-bus to IO extender is
tightly connected
4) replace module

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

FC-IO-0002

IO Extender Module

47

Module faulty

FC-IO-0002
FC-IO-0002

IO Extender Module
IO Extender Module

48
49

Configuration error
Configuration error

Fault detected during a indepence test of own


module
Configuration mismatch
Watchdog cable not connected

FC-IO-0002

IO Extender Module

50

Module faulty

Watchdog signal not present

FC-IO-0002
FC-IO-0002
FC-IO-0002
FC-IO-0002
FC-IO-0002
FC-IO-0002

IO Extender Module
IO Extender Module
IO Extender Module
IO Extender Module
IO Extender Module
IO Extender Module

51
52
53
54
55
56

Error code not defined


Module faulty
Module faulty
Module faulty
Module faulty
Module faulty

FC-IO-0002

IO Extender Module

57

Module faulty

FC-IO-0002
FC-IO-0002

IO Extender Module
IO Extender Module

58
59

Module faulty
Module faulty

FC-IO-0002

IO Extender Module

60

Module faulty

Not used
Watchdog oscillation signal not present
Fault detected on module
Fault detected on module
Watchdog signal section A
Watchdog signal section B
Fault detected on module select lines on own
module
Unable to switch off watchdog
Unable to switch off +5V on own module
Fault detected on module select lines on redundant
module

FC-IO-0002

IO Extender Module

61

Module faulty

Unable to switch off +5V on redundant module

Replace module

FC-IO-0002

IO Extender Module

62

Module faulty

Fault detected on Disable Output of own module

Replace module

FC-IO-0002

IO Extender Module

63-79

Error code not defined

Not used

Module faulty

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
Fault detected on select line 1 of redundant module
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Module faulty

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
Fault detected on select line 2 of redundant module
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Module faulty

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
Fault detected on select line 3 of redundant module
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

FC-IO-0002

FC-IO-0002

FC-IO-0002

IO Extender Module

IO Extender Module

IO Extender Module

80

81

82

Replace module
Check for crossed cables in the cabinet
Check for crossed cables in the cabinet
1) Check if watchdog module is tighly connected
2) replace module

Replace module
Replace module
Replace module
Replace module
Replace module
Replace module
Replace module
Replace module
Replace module

Module type

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

Module description

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

EC

83

84

85

86

87

88

89

Description in Safety Builder Diagnostics

Details

Module faulty

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
Fault detected on select line 4 of redundant module
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Module faulty

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
Fault detected on select line 5 of redundant module
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Module faulty

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
Fault detected on select line 6 of redundant module
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Module faulty

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
Fault detected on select line 7 of redundant module
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Module faulty

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
Fault detected on select line 8 of redundant module
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Module faulty

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
Fault detected on select line 9 of redundant module
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Module faulty

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Fault detected on select line 10 of redundant


module

Corrective actions

Module type

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

Module description

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

EC

90

91

92

93

94

95

96

Description in Safety Builder Diagnostics

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Details

Corrective actions

Fault detected on select line 11 of redundant


module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Fault detected on select line 12 of redundant


module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Fault detected on select line 13 of redundant


module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Fault detected on select line 14 of redundant


module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Fault detected on select line 15 of redundant


module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Fault detected on select line 16 of redundant


module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Fault detected on select line 17 of redundant


module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Module type

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

Module description

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

EC

97

98

99

100

101

102

103

104

Description in Safety Builder Diagnostics

Details

Corrective actions

Fault detected on select line 18 of redundant


module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

General fault detected on select lines of redundant


module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Fault detected on Horizontal Read line 0 of


redundant module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Module faulty

Fault detected on Horizontal Read line 1 of


redundant module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Module faulty

1) Check if V-bus connections are tighly connected


of redundant module
Fault detected on Horizontal test line 0 of redundant 2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
module
tightly connected of redundant module
4) replace redundant module

Module faulty

1) Check if V-bus connections are tighly connected


of redundant module
Fault detected on Horizontal test line 1 of redundant 2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
module
tightly connected of redundant module
4) replace redundant module

Module faulty

Fault detected on Horizontal Write line 0 of


redundant module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Fault detected on Horizontal Write line 1 of


redundant module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Module faulty

Module faulty

Module faulty

Module faulty

Module type

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

Module description

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

EC

105

106

107

108

109

110

111

112

Description in Safety Builder Diagnostics

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Details

Corrective actions

Fault detected on Horizontal Dataline 0 of


redundant module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Fault detected on Horizontal Dataline 1 of


redundant module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Fault detected on Horizontal Dataline 2 of


redundant module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Fault detected on Horizontal Dataline 3 of


redundant module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Fault detected on Horizontal Dataline 4 of


redundant module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Fault detected on Horizontal Dataline 5 of


redundant module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Fault detected on Horizontal Dataline 6 of


redundant module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Fault detected on Horizontal Dataline 7 of


redundant module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Module type

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

Module description

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

EC

113

114

115

116

117

118

119

120

Description in Safety Builder Diagnostics

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Details

Corrective actions

Fault detected on Horizontal Dataline 0 of


redundant module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Fault detected on Horizontal Dataline 1 of


redundant module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Fault detected on Horizontal Dataline 2 of


redundant module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Fault detected on Horizontal Dataline 3 of


redundant module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Fault detected on Horizontal Dataline 4 of


redundant module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Fault detected on Horizontal Dataline 5 of


redundant module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Fault detected on Horizontal Dataline 6 of


redundant module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Fault detected on Horizontal Dataline 7 of


redundant module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Module type

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

FC-IO-0002

Module description

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

IO Extender Module

EC

121

122

123

124

125

Description in Safety Builder Diagnostics

Details

Corrective actions

Fault detected on Horizontal Read line 0 of


redundant module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Module faulty

Fault detected on Horizontal Read line 1 of


redundant module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Module faulty

1) Check if V-bus connections are tighly connected


of redundant module
Fault detected on Horizontal test line 0 of redundant 2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
module
tightly connected of redundant module
4) replace redundant module

Module faulty

1) Check if V-bus connections are tighly connected


of redundant module
Fault detected on Horizontal test line 1 of redundant 2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
module
tightly connected of redundant module
4) replace redundant module

Module faulty

Fault detected on Horizontal HWR0 of redundant


module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module
1) Check if V-bus connections are tighly connected
of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Module faulty

FC-IO-0002

IO Extender Module

126

Module faulty

Fault detected on Horizontal HWR1 of redundant


module

FC-IO-0002

IO Extender Module

127

Module faulty

Fault detected during a indepence test of redundant


Replace redundant module
module

FC-IO-0002

IO Extender Module

128

Module faulty

Fault detected on Disable Output of redundant


module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Module type

Module description

FC-IO-0002

IO Extender Module

FC-IO-0002

IO Extender Module

FC-IO-0002

IO Extender Module

FC-IO-0002

IO Extender Module

FC-IO-0002

IO Extender Module

FC-IO-0002

IO Extender Module

FC-IO-0002

IO Extender Module

EC

129

Description in Safety Builder Diagnostics

Module faulty

130..137 Error code not defined

138

139

I/O extender address incorrect or an additional I/O


extender placed

Corrective actions

Watchdog signal not present of redundant module

1) Check if V-bus connections are tighly connected


of redundant module
2) Check jumper settings of IO rack CA0 thru CA3
3) Check f flatcable from H-bus to IO extender is
tightly connected of redundant module
4) replace redundant module

Not used

Illigal IO extender IO-0001 detected.


As it is not possible to determine chassis and slot
for an illegal placed HBD, it is reported with the
QPP chassis and slot.

Module faulty

180..255 Error code not defined

1) Check if all IO chassis installed in the cabinet are


configured in the hardware configurator
2) Check if the IO bus configuration inside the
cabinet match with the harwdare configurator
3) Verify all IO extender addresses in de cabinet
matches with the addresses in the hardware
configurator
On the IO chassis check CA0 thru CA03
In the hardware configurator check the IO bus
and IO chassis address
1) Check jumper settings IO extenders on back of
IO chassis
2) Check software and hardware configuration
3) Check 5VDC connection

Module faulty

139..178 Error code not defined


179

Details

Not used
IO Extender quick test
Not used

1) Check 5VDC to this chassis


2) Check front flatcable of this module
3) Replace module
4) Replace other modules in IO chassis

Module type

FC-SDI-1624
FC-SDI-1648

FC-SDI-1624
FC-SDI-1648

FC-SDI-1624
FC-SDI-1648

FC-SDI-1624
FC-SDI-1648

Module description

Safe digital input module


(24 Vdc, 16 channels)

Safe digital input module


(24 Vdc, 16 channels)

Safe digital input module


(24 Vdc, 16 channels)

Safe digital input module


(24 Vdc, 16 channels)

EC

Description in Safety Builder Diagnostics

Module faulty

Module faulty

Module faulty

Module faulty

Details

Corrective actions

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus termination on the CP chassis. If nothing
can be found, replace QPP.

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus termination on the CP chassis. If nothing
can be found, replace QPP.

Fault detected on specific address/ data line

1) Check internal power 24VDC & 5VDC


2) Replace module
3) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
4) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus termination on the CP chassis
If nothing can be found, replace QPP.

Fault detected on specific address/ data line

1) Check internal power 24VDC & 5VDC


2) Replace module
3) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
4) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus termination on the CP chassis
If nothing can be found, replace QPP.

Module type

FC-SDI-1624
FC-SDI-1648

FC-SDI-1624
FC-SDI-1648

FC-SDI-1624
FC-SDI-1648

FC-SDI-1624
FC-SDI-1648

Module description

Safe digital input module


(24 Vdc, 16 channels)

Safe digital input module


(24 Vdc, 16 channels)

Safe digital input module


(24 Vdc, 16 channels)

Safe digital input module


(24 Vdc, 16 channels)

EC

Description in Safety Builder Diagnostics

Module faulty

Module faulty

Module faulty

Module faulty

Details

Corrective actions

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus termination on the CP chassis. If nothing
can be found, replace QPP.

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus termination on the CP chassis. If nothing
can be found, replace QPP.

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus termination on the CP chassis. If nothing
can be found, replace QPP.

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus termination on the CP chassis. If nothing
can be found, replace QPP.

Module type

FC-SDI-1624
FC-SDI-1648

FC-SDI-1624
FC-SDI-1648

FC-SDI-1624
FC-SDI-1648

FC-SDI-1624
FC-SDI-1648

Module description

Safe digital input module


(24 Vdc, 16 channels)

Safe digital input module


(24 Vdc, 16 channels)

Safe digital input module


(24 Vdc, 16 channels)

Safe digital input module


(24 Vdc, 16 channels)

EC

10

11

Description in Safety Builder Diagnostics

Module faulty

Module faulty

Module faulty

Module faulty

Details

Corrective actions

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus termination on the CP chassis. If nothing
can be found, replace QPP.

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus termination on the CP chassis. If nothing
can be found, replace QPP.

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus termination on the CP chassis. If nothing
can be found, replace QPP.

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus termination on the CP chassis. If nothing
can be found, replace QPP.

Module type

FC-SDI-1624
FC-SDI-1648

FC-SDI-1624
FC-SDI-1648

FC-SDI-1624
FC-SDI-1648

FC-SDI-1624
FC-SDI-1648

Module description

Safe digital input module


(24 Vdc, 16 channels)

Safe digital input module


(24 Vdc, 16 channels)

Safe digital input module


(24 Vdc, 16 channels)

Safe digital input module


(24 Vdc, 16 channels)

EC

12

13

14

15

Description in Safety Builder Diagnostics

Module faulty

Module faulty

Module faulty

Module faulty

Details

Corrective actions

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus termination on the CP chassis. If nothing
can be found, replace QPP.

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus termination on the CP chassis. If nothing
can be found, replace QPP.

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus termination on the CP chassis. If nothing
can be found, replace QPP.

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus termination on the CP chassis. If nothing
can be found, replace QPP.

Module type

FC-SDI-1624
FC-SDI-1648

FC-SDI-1624
FC-SDI-1648

FC-SDI-1624
FC-SDI-1648

FC-SDI-1624
FC-SDI-1648

Module description

Safe digital input module


(24 Vdc, 16 channels)

Safe digital input module


(24 Vdc, 16 channels)

Safe digital input module


(24 Vdc, 16 channels)

Safe digital input module


(24 Vdc, 16 channels)

EC

16

17

18

19

Description in Safety Builder Diagnostics

Module faulty

Module faulty

Module faulty

Module faulty

Details

Corrective actions

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus termination on the CP chassis. If nothing
can be found, replace QPP.

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus termination on the CP chassis. If nothing
can be found, replace QPP.

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus termination on the CP chassis. If nothing
can be found, replace QPP.

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus termination on the CP chassis. If nothing
can be found, replace QPP.

Module type

FC-SDI-1624
FC-SDI-1648

Module description

Safe digital input module


(24/48 Vdc, 16 channels)

FC-SDI-1624
FC-SDI-1648

Safe digital input module


(24 Vdc, 16 channels)

FC-SDI-1624
FC-SDI-1648

Safe digital input module


(24 Vdc, 16 channels)

FC-SDI-1624
FC-SDI-1648

Safe digital input module


(24 Vdc, 16 channels)

FC-SDI-1624
FC-SDI-1648

Safe digital input module


(24 Vdc, 16 channels)

EC

20

21

Description in Safety Builder Diagnostics

Module faulty

Module faulty

22..252 Error code not defined

253

Input compare error

254..255 Error code not defined

Details

Corrective actions

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus termination on the CP chassis. If nothing
can be found, replace QPP.

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus termination on the CP chassis. If nothing
can be found, replace QPP.

not used

1) Check if signal is toggling with an high frequency


2) check the voltage of the input. Measure between
0VDC of the busbar and the input contact.
If the voltage is in the 'grey' area, the redundant
Mismatch in scan value between CP1 and CP2
Most likely the signals is toggling between high and card can detect this as a zero while the other as a
'1'
low with an high frequently. CP1 scan on another
time as CP2 and if the values differs also after a re- For SDI-1624:
scan, this message will be reported. In this situation, Input HIGH: > 15 Vdc
Input LOW: < 9 Vdc (I < 2 mA)
the configured Fault Reaction will determine the
value be used in the application.
For SDI-1648:
Input HIGH: > 30 Vdc
Input LOW: < 16 Vdc (I < 1.1 mA)

not used

Module type

Module description

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

Module faulty

CP does not receive response of module about


status section B

Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

Module faulty

CP does not receive response of module about


status section A

Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

Module faulty

CP does not receive response of module about


status section B (optional)

Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

Module faulty

CP does not receive response of module about


status of section A and section B (optional)

Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

Module faulty

Both section (A and B) are reporting faults


(Errorcode 5 and 8 can not be reported)

Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

Internal power down

Module does not have 24VDC internal power

1) Check the power loop to the module


2) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

Module faulty

Both section (A and B) are reporting faults


(Errorcode 4 and 5 can not be reported)

Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

Module faulty

iterated code bits not correct in section A (optional) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

Module faulty

iterated code bits not correct in section B (optional) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

Module faulty

Commands not received in section A (optional)

Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

10

Module faulty

Commands not received in section B (optional)

Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

11

Module faulty

Commands not received in section A (optional)

Replace module

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

12

Module faulty

Commands not received in section B (optional)

Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

multiplexer address error channel 1

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

multiplexer address error channel 2

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

15

Module faulty

multiplexer address error channel 3

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

16

Module faulty

multiplexer address error channel 4

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

17

Module faulty

multiplexer address error channel 5

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

multiplexer address error channel 6

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

multiplexer address error channel 7

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

multiplexer address error channel 8

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

multiplexer address error channels 9

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

multiplexer address error channels 10

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

multiplexer address error channels 11

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

13

14

18

19

20

21

22

23

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Module type

Module description

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

EC

Details

Corrective actions

multiplexer address error channels 12

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

multiplexer address error channels 13

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

multiplexer address error channels 14

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

Module faulty

multiplexer address error channels 15

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

27

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

28

Module faulty

multiplexer address error channels 16

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

29

Module faulty

values of section A and B of channel 1 do not


concur (discrepancy error)

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

Module faulty

values of section A and B of channel 2 do not


concur (discrepancy error)

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

Module faulty

values of section A and B of channel 3 do not


concur (discrepancy error)

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

Module faulty

values of section A and B of channel 4 do not


concur (discrepancy error)

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

Module faulty

values of section A and B of channel 5 do not


concur (discrepancy error)

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

Module faulty

values of section A and B of channel 6 do not


concur (discrepancy error)

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

Module faulty

values of section A and B of channel 7 do not


concur (discrepancy error)

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

24

25

26

30

31

32

33

34

35

Description in Safety Builder Diagnostics

Module faulty

Module faulty

Module faulty

Module type

Module description

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

EC

Details

Corrective actions

Module faulty

values of section A and B of channel 8 do not


concur (discrepancy error)

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

Module faulty

values of section A and B of channel 9 do not


concur (discrepancy error)

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

Module faulty

values of section A and B of channel 10 do not


concur (discrepancy error)

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

39

Module faulty

values of section A and B of channel 11 do not


concur (discrepancy error)

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

40

Module faulty

values of section A and B of channel 12 do not


concur (discrepancy error)

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

41

Module faulty

values of section A and B of channel 13 do not


concur (discrepancy error)

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

Module faulty

values of section A and B of channel 14 do not


concur (discrepancy error)

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

Module faulty

values of section A and B of channel 15 do not


concur (discrepancy error)

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

44

Module faulty

values of section A and B of channel 16 do not


concur (discrepancy error)

1) Check complete digital input loop


2) Check if Signals is fluctuating a lot. If yes, check
if this can be avoided
3) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

45

Open loop(s)

Open loop detected on channel 1

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

46

Open loop(s)

Open loop detected on channel 2

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

47

Open loop(s)

Open loop detected on channel 3

Check loop

36

37

38

42

43

Description in Safety Builder Diagnostics

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

48

Open loop(s)

Open loop detected on channel 4

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

49

Open loop(s)

Open loop detected on channel 5

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

50

Open loop(s)

Open loop detected on channel 6

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

51

Open loop(s)

Open loop detected on channel 7

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

52

Open loop(s)

Open loop detected on channel 8

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

53

Open loop(s)

Open loop detected on channel 9

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

54

Open loop(s)

Open loop detected on channel 10

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

55

Open loop(s)

Open loop detected on channel 11

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

56

Open loop(s)

Open loop detected on channel 12

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

57

Open loop(s)

Open loop detected on channel 13

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

58

Open loop(s)

Open loop detected on channel 14

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

59

Open loop(s)

Open loop detected on channel 15

Check loop

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

60

Open loop(s)

Open loop detected on channel 16

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

61

Short circuit

Short circuit detected on channel 1

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

62

Short circuit

Short circuit detected on channel 2

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

63

Short circuit

Short circuit detected on channel 3

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

64

Short circuit

Short circuit detected on channel 4

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

65

Short circuit

Short circuit detected on channel 5

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

66

Short circuit

Short circuit detected on channel 6

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

67

Short circuit

Short circuit detected on channel 7

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

68

Short circuit

Short circuit detected on channel 8

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

69

Short circuit

Short circuit detected on channel 9

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

70

Short circuit

Short circuit detected on channel 10

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

71

Short circuit

Short circuit detected on channel 11

Check loop

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

72

Short circuit

Short circuit detected on channel 12

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

73

Short circuit

Short circuit detected on channel 13

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

74

Short circuit

Short circuit detected on channel 14

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

75

Short circuit

Short circuit detected on channel 15

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

76

Short circuit

Short circuit detected on channel 16

Check loop

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

77..92

Field device value stuck at

Module is faulty

Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

93

Module faulty

Module does not response (optional)

1) Check 24VDC power


2) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

94

Module faulty

Fault detected in section A (optional)

Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

95

Module faulty

Fault detected in section B (optional)

Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

96

Module faulty

Fault detected in section A and B (optional)

Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

97

Internal power down

Module does not have 24VDC internal power


(Optional)

1) Check the power loop to the module


2) Replacde module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

98

Internal power down

Module does not have 24VDC internal power


(optional)

1) Check the power loop to the module


2) Replacde module

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

99

Module faulty

Communication error detected on H-Bus side to


analog side section A (optional)

1) Check the flatcable is tightly connected to the Hbus


2) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

100

Module faulty

Communication error detected on H-Bus side to


analog side section B (optional)

1) Check the flatcable is tightly connected to the Hbus


2) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

101

Module faulty

iterated code bits not OK in section A (optional)

Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

102

Module faulty

iterated code bits not OK in section B (optional)

Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

103

Module faulty

Commands not received in section A (optional)

Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

104

Module faulty

Commands not received in section B (optional)

Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

105

Module faulty

Commands not received in section A (optional)

Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

106

Module faulty

Commands not received in section B (optional)

Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

Channel 1, dependency detected between section


A and/or B
or multiplexer address.

1) Check analog loop


2) Check if value is are fluctuating a lot. If yes, try
verify if this can be avoided
3) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

Channel 2, dependency detected between section


A and/or B
or multiplexer address.

1) Check analog loop


2) Check if value is are fluctuating a lot. If yes, try
verify if this can be avoided
3) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

Channel 3, dependency detected between section


A and/or B
or multiplexer address.

1) Check analog loop


2) Check if value is are fluctuating a lot. If yes, try
verify if this can be avoided
3) Replace module

107

108

109

Module faulty

Module faulty

Module faulty

Module type

Module description

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

EC

110

111

112

113

114

115

116

117

118

119

Description in Safety Builder Diagnostics

Details

Corrective actions

Module faulty

Channel 4, dependency detected between section


A and/or B
or multiplexer address.

1) Check analog loop


2) Check if value is are fluctuating a lot. If yes, try
verify if this can be avoided
3) Replace module

Module faulty

Channel 5, dependency detected between section


A and/or B
or multiplexer address.

1) Check analog loop


2) Check if value is are fluctuating a lot. If yes, try
verify if this can be avoided
3) Replace module

Module faulty

Channel 6, dependency detected between section


A and/or B
or multiplexer address.

1) Check analog loop


2) Check if value is are fluctuating a lot. If yes, try
verify if this can be avoided
3) Replace module

Module faulty

1) Check analog loop


Channel 7, Dependency detected between section 2) Check if value is are fluctuating a lot. If yes, try
A and/or B
verify if this can be avoided
or multiplexer address.
3) Replace module

Module faulty

Channel 8, dependency detected between section


A and/or B
or multiplexer address.

1) Check analog loop


2) Check if value is are fluctuating a lot. If yes, try
verify if this can be avoided
3) Replace module

Module faulty

Channel 9, dependency detected between section


A and/or B
or multiplexer address.

1) Check analog loop


2) Check if value is are fluctuating a lot. If yes, try
verify if this can be avoided
3) Replace module

Module faulty

Module faulty

Module faulty

Module faulty

1) Check analog loop


Channel 10, dependency detected between section 2) Check if value is are fluctuating a lot. If yes, try
A and/or B
verify if this can be avoided
or multiplexer address.
3) Replace module
1) Check analog loop
2) Check if value is are fluctuating a lot. If yes, try
Channel 11, dependency detected between section
verify if this can be avoided
A and/or B or multiplexer address.
3) Replace module
1) Check analog loop
2) Check if value is are fluctuating a lot. If yes, try
Channel 12, dependency detected between section
verify if this can be avoided
A and/or B or multiplexer address.
3) Replace module
1) Check analog loop
2) Check if value is are fluctuating a lot. If yes, try
Channel 13, dependency detected between section
verify if this can be avoided
A and/or B or multiplexer address.
3) Replace module

Module type

Module description

EC

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

122

Module faulty

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

123

Internal power down

Module does not have 24VDC internal power

1) Check the power loop to the module


2) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

124

Module faulty

Fault detected in section A (optional)

Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

125

Module faulty

Fault detected in section B (optional)

Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

126

Module faulty

deliberately corrupted data has not been detected

Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

127

Module faulty

deliberately corrupted data has not been detected

Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

128

Module faulty

deliberately corrupted data has not been detected


in section A

Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

129

Module faulty

deliberately corrupted data has not been detected


in section B

Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

130

Module faulty

Fault detected in section A

Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

131

Module faulty

Fault detected in section B

Replace module

120

121

Description in Safety Builder Diagnostics

Module faulty

Module faulty

Details

Corrective actions

1) Check analog loop


2) Check if value is are fluctuating a lot. If yes, try
Channel 14, dependency detected between section
verify if this can be avoided
A and/or B or multiplexer address.
3) Replace module
1) Check analog loop
2) Check if value is are fluctuating a lot. If yes, try
Channel 15, dependency detected between section
verify if this can be avoided
A and/or B or multiplexer address.
3) Replace module
1) Check analog loop
2) Check if value is are fluctuating a lot. If yes, try
Channel 16, dependency detected between section
verify if this can be avoided
A and/or B or multiplexer address.
3) Replace module

Module type

Module description

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

EC

Description in Safety Builder Diagnostics

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

140

Module faulty

0V value, section A, out of range and/or


multiplexer address error

1) Check if any analog signal connected to the


module is fluctuating a lot. If yes, try to avoid it.
2) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

141

Module faulty

M-0V5 low value, sect. A, out of range and/or


multiplexer address error

1) Check if any analog signal connected to the


module is fluctuating a lot. If yes, try to avoid it.
2) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

142

Module faulty

Vref_B value, section A, out of range and/or


multiplexer address error

1) Check if any analog signal connected to the


module is fluctuating a lot. If yes, try to avoid it.
2) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

143

Module faulty

M_-0V5 high value, sect. A, out of range and/or


multiplexer address error

1) Check if any analog signal connected to the


module is fluctuating a lot. If yes, try to avoid it.
2) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

144

Earth fault detected

Earth fault detected on 1 or more channels

1) Check if any analog signal connected to the


module is fluctuating a lot. If yes, try to avoid it.
2) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

145

Error code not defined

Not used

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

146

Module faulty

M_+12V value, section A, out of range, and/or


multiplexer address error

1) Check if any analog signal connected to the


module is fluctuating a lot. If yes, try to avoid it.
2) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

147

Module faulty

M_+8V2 value, section A, out of range, and/or


multiplexer address error

1) Check if any analog signal connected to the


module is fluctuating a lot. If yes, try to avoid it.
2) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

148

Module faulty

0V value, section A, out of range, and/or


multiplexer address error

1) Check if any analog signal connected to the


module is fluctuating a lot. If yes, try to avoid it.
2) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

149

Module faulty

M_-0V5 low value, sect. A, out of range, and/or


multiplexer address error

1) Check if any analog signal connected to the


module is fluctuating a lot. If yes, try to avoid it.
2) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

150

Module faulty

Vref_B value, section A, out of range, and/or


multiplexer address error

1) Check if any analog signal connected to the


module is fluctuating a lot. If yes, try to avoid it.
2) Replace module

132..139 Error code not defined

Details

Corrective actions

Not used

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

151

Module faulty

M_-0V5 high value, sect. A, out of range, and/or


multiplexer address error

1) Check if any analog signal connected to the


module is fluctuating a lot. If yes, try to avoid it.
2) Replace module
1) Check if a specific channel is reported faulty,
This may the channel with a earth fault
2) It's possible the earth fault is on the +8VDC
side, In that case onon of the channels will be
reported as faulty.
In this case all channels have to be checked in
more detail

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

152

Earth fault detected

Earth fault detected on 1 or more channels

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

153

Error code not defined

Not Used

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

154

Module faulty

M_+12V value, section A, out of range, and/or


multiplexer address error

1) Check if any analog signal connected to the


module is fluctuating a lot. If yes, try to avoid it.
2) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

155

Module faulty

M_+8V2 value, section A, out of range, and/or


multiplexer address error

1) Check if any analog signal connected to the


module is fluctuating a lot. If yes, try to avoid it.
2) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

156

Module faulty

0 V value, section B, out of range, and/or


multiplexer address error

1) Check if any analog signal connected to the


module is fluctuating a lot. If yes, try to avoid it.
2) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

157

Error code not defined

Not Used

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

158

Module faulty

Value +5V, section B, out of range, and/or


multiplexer address error

1) Check if any analog signal connected to the


module is fluctuating a lot. If yes, try to avoid it.
2) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

159

Earth fault detected

Earth fault detected on 1 or more channels

1) Check if a specific channel is reported faulty,


This may the channel with a earth fault
2) It's possible the earth fault is on the +8VDC
side, In that case onon of the channels will be
reported as faulty.
In this case all channels have to be checked in
more detail

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

160

Module faulty

Value +8V5, section B, out of range, and/or


multiplexer address error

1) Check if any analog signal connected to the


module is fluctuating a lot. If yes, try to avoid it.
2) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

161

Module faulty

M_-0V5 low value, section B, out of range, and/or


multiplexer address error

1) Check if any analog signal connected to the


module is fluctuating a lot. If yes, try to avoid it.
2) Replace module

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

162

Module faulty

Vref_A value, section B, out of range, and/or


multiplexer address error

1) Check if any analog signal connected to the


module is fluctuating a lot. If yes, try to avoid it.
2) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

163

Module faulty

M-0V5 high value, section B, out of range, and/or


multiplexer address error

1) Check if any analog signal connected to the


module is fluctuating a lot. If yes, try to avoid it.
2) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

164

Module faulty

0 V value, section B, out of range, and/or


multiplexer address error

1) Check if any analog signal connected to the


module is fluctuating a lot. If yes, try to avoid it.
2) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

165

Error code not defined

Not Used

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

166

Module faulty

Value +5V, section B, out of range, and/or


multiplexer address error

1) Check if any analog signal connected to the


module is fluctuating a lot. If yes, try to avoid it.
2) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

167

Earth fault detected

Earth fault detected on 1 or more channels

1) Check if a specific channel is reported faulty,


This may the channel with a earth fault
2) It's possible the earth fault is on the +8VDC
side, In that case onon of the channels will be
reported as faulty.
In this case all channels have to be checked in
more detail

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

168

Module faulty

Value +8V5, section B, out of range, and/or


multiplexer address error

1) Check if any analog signal connected to the


module is fluctuating a lot. If yes, try to avoid it.
2) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

169

Module faulty

M_-0V5 low value, section B, out of range, and/or


multiplexer address error

1) Check if any analog signal connected to the


module is fluctuating a lot. If yes, try to avoid it.
2) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

170

Module faulty

Vref_A value, section B, out of range, and/or


multiplexer address error

1) Check if any analog signal connected to the


module is fluctuating a lot. If yes, try to avoid it.
2) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

171

Module faulty

M-0V5 high value, section B, out of range, and/or


multiplexer address error

1) Check if any analog signal connected to the


module is fluctuating a lot. If yes, try to avoid it.
2) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

172

Error code not defined

Not Used

Module type

Module description

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

EC

Description in Safety Builder Diagnostics

Details

Module faulty

1) Check the digital input loops are not shorted


invalid V_DA_x: defective A/D-converter section A 2) Check if any analog signal connected to the
and/or multiplexer address error
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

177

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

178

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

173

174

175

176

179

180

181

182

Corrective actions

Module type

Module description

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

187

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

188

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

183

184

185

186

189

190

191

192

Module type

Module description

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

197

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

198

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

193

194

195

196

199

200

201

202

Module type

Module description

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section A


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

207

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

208

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

203

204

205

206

209

210

211

212

Module type

Module description

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

217

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

218

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

213

214

215

216

219

220

221

222

Module type

Module description

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

227

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

228

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

223

224

225

226

229

230

231

232

Module type

Module description

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

236

Module faulty

Fault detected on A/D-converter section B


and/or multiplexer address error

1) Check the digital input loops are not shorted


2) Check if any analog signal connected to the
module is fluctuating a lot. If yes, try to avoid it.
3) Replace module

237

Error code not defined

1) Check if a specific channel is reported faulty,


This may the channel with a earth fault
2) It's possible the earth fault is on the +8VDC
side, In that case onon of the channels will be
reported as faulty.
In this case all channels have to be checked in
more detail

233

234

235

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

238

Earth fault detected

Earth fault detected on 1 or more channels

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

239

Error code not defined

Not used

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

240

Module faulty

Fault detected in the state condition of section A

Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

241

Module faulty

Internal power down error

1) Check Internal power


2) Replace module

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

242..246 Error code not defined

247

Module faulty

Not used

Fault detected in Horizontal bus Datalines at bidirectional Horizontal BUS-driver

1) Replace module
2) replace IO extender
3) Check connections to Horizontal IO bus

Module type

Module description

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

FC-SDIL-1608

Safe loop-monitored
digital input module with
earth fault monitor (16
channels)

EC

Description in Safety Builder Diagnostics

248..252 Error code not defined

253

Input compare error

254..255 Error code not defined

Details

Corrective actions

Not used

Input compare error

Not used

Mismatch in scan value between CP1 and CP2


Most likely the signals is toggling between high and
low with an high frequently. CP1 scan on another
time as CP2 and if the values differs also after a rescan, this message will be reported. In this
situation, the configured Fault Reaction will
determine the value be used in the application.

Module type

Module description

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

Internal power down

Module does not have 24VDC internal power

Check the power loop to the module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

1-2

Error code not defined

Not used

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

Internal power down

Module does not have 24VDC internal power

Check the power loop to the module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

Internal power down

Module does not have 24VDC internal power

Check the power loop to the module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

5-6

Error code not defined

Not used

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

Internal power down

Module does not have 24VDC internal power

Check the power loop to the module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

Module faulty

CP does not receive response from section B

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

9-10

Error code not defined

Not used

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

11

Module faulty

Module faulty

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

12

Internal power down

Module does not have 24VDC internal power

Check the power loop to the module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

13

Module faulty

Internal power down or command error Section A

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

14

Module faulty

Internal power down or command error Section B

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

15

Module faulty

Fault detected on both section (A and B)

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

16-22

Error code not defined

Not used

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

23

Module faulty

multiplexer address error VM channel

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

24

Module faulty

multiplexer address error channel 1

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

25

Module faulty

multiplexer address error channel 2

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

26

Module faulty

multiplexer address error channel 3

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

27

Module faulty

multiplexer address error channel 4

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

28

Module faulty

multiplexer address error channel 5

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

29

Module faulty

multiplexer address error channel 6

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

30

Module faulty

multiplexer address error channel 7

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

31

Module faulty

multiplexer address error channel 8

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

32

Module faulty

multiplexer address error channel 9

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

33

Module faulty

multiplexer address error channel 10

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

34

Module faulty

multiplexer address error channel 11

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

35

Module faulty

multiplexer address error channel 12

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

36

Module faulty

multiplexer address error channel 13

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

37

Module faulty

multiplexer address error channel 14

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

38

Module faulty

multiplexer address error channel 15

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

39

Module faulty

multiplexer address error channel 16

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

40

Module faulty

1) Reset system and check if it appears again


values of section A and B do not concur, channel 1 2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

41

Module faulty

1) Reset system and check if it appears again


values of section A and B do not concur, channel 2 2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

42

Module faulty

1) Reset system and check if it appears again


values of section A and B do not concur, channel 3 2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

43

Module faulty

1) Reset system and check if it appears again


values of section A and B do not concur, channel 4 2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

44

Module faulty

1) Reset system and check if it appears again


values of section A and B do not concur, channel 5 2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

45

Module faulty

1) Reset system and check if it appears again


values of section A and B do not concur, channel 6 2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

46

Module faulty

1) Reset system and check if it appears again


values of section A and B do not concur, channel 7 2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

47

Module faulty

1) Reset system and check if it appears again


values of section A and B do not concur, channel 8 2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

48

Module faulty

1) Reset system and check if it appears again


values of section A and B do not concur, channel 9 2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

49

Module faulty

values of section A and B do not concur, channel


10

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

50

Module faulty

values of section A and B do not concur, channel


11

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

51

Module faulty

values of section A and B do not concur, channel


12

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

52

Module faulty

values of section A and B do not concur, channel


13

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

53

Module faulty

values of section A and B do not concur, channel


14

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

54

Module faulty

values of section A and B do not concur, channel


15

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

55

Module faulty

values of section A and B do not concur, channel


16

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

56

Internal power down

Module does not have 24VDC internal power

Check the power loop to the module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

57-58

Error code not defined

Not used

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

59

Module faulty

Error status byte section A and/or B

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

60

Internal power down

Module does not have 24VDC internal power

Check the power loop to the module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

61

Internal power down

Module does not have 24VDC internal power

Check the power loop to the module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

62-71

Error code not defined

Not used

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

72

Module faulty

It's detected that section A and/or B are dependent 1) Reset system and check if it appears again
2) Check if signal is fluctuating, if yes, try to avoid it
or multiplexer address error
3) Replace module
Channel 1

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

73

Module faulty

It's detected that section A and/or B are dependent 1) Reset system and check if it appears again
or multiplexer address error
2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module
Channel 2

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

74

Module faulty

It's detected that section A and/or B are dependent 1) Reset system and check if it appears again
or multiplexer address error
2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module
Channel 3

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

75

Module faulty

It's detected that section A and/or B are dependent 1) Reset system and check if it appears again
or multiplexer address error
2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module
Channel 4

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

76

Module faulty

It's detected that section A and/or B are dependent 1) Reset system and check if it appears again
or multiplexer address error
2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module
Channel 5

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

77

Module faulty

It's detected that section A and/or B are dependent 1) Reset system and check if it appears again
or multiplexer address error
2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module
Channel 6

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

78

Module faulty

It's detected that section A and/or B are dependent 1) Reset system and check if it appears again
or multiplexer address error
2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module
Channel 7

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

79

Module faulty

It's detected that section A and/or B are dependent 1) Reset system and check if it appears again
or multiplexer address error
2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module
Channel 8

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

80

Module faulty

It's detected that section A and/or B are dependent 1) Reset system and check if it appears again
2) Check if signal is fluctuating, if yes, try to avoid it
or multiplexer address error
3) Replace module
Channel 9

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

81

Module faulty

It's detected that section A and/or B are dependent 1) Reset system and check if it appears again
or multiplexer address error
2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module
Channel 10

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

82

Module faulty

It's detected that section A and/or B are dependent 1) Reset system and check if it appears again
or multiplexer address error
2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module
Channel 11

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

83

Module faulty

It's detected that section A and/or B are dependent 1) Reset system and check if it appears again
or multiplexer address error
2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module
Channel 12

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

84

Module faulty

It's detected that section A and/or B are dependent 1) Reset system and check if it appears again
or multiplexer address error
2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module
Channel 13

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

85

Module faulty

It's detected that section A and/or B are dependent 1) Reset system and check if it appears again
or multiplexer address error
2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module
Channel 14

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

86

Module faulty

It's detected that section A and/or B are dependent 1) Reset system and check if it appears again
or multiplexer address error
2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module
Channel 15

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

87

Module faulty

It's detected that section A and/or B are dependent 1) Reset system and check if it appears again
or multiplexer address error
2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module
Channel 16

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

88

Internal power down

Module does not have 24VDC internal power

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

89-90

Error code not defined

Not used

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

91

Module faulty

Fault detected in section A and/or B

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

92

Internal power down

Module does not have 24VDC internal power

Check the power loop to the module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

93

Internal power down

Module does not have 24VDC internal power

Check the power loop to the module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

94-103

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

104

Module faulty

Fault detected during discharge test in channel 1


section A and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

105

Module faulty

Fault detected during discharge test in channel 2


section A and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

106

Module faulty

Fault detected during discharge test in channel 3


section A and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

107

Module faulty

Fault detected during discharge test in channel 4


section A and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

108

Module faulty

Fault detected during discharge test in channel 5


section A and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

Check the power loop to the module

Not used

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

109

Module faulty

Fault detected during discharge test in channel 6


section A and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

110

Module faulty

Fault detected during discharge test in channel 7


section A and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

111

Module faulty

Fault detected during discharge test in channel 8


section A and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

112

Module faulty

Fault detected during discharge test in channel 9


section A and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

113

Module faulty

Fault detected during discharge test in channel 10


section A and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

114

Module faulty

Fault detected during discharge test in channel 11


section A and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

115

Module faulty

Fault detected during discharge test in channel 12


section A and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

116

Module faulty

Fault detected during discharge test in channel 13


section A and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

117

Module faulty

Fault detected during discharge test in channel 14


section A and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

118

Module faulty

Fault detected during discharge test in channel 15


section A and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

119

Module faulty

Fault detected during discharge test in channel 16


section A and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

120

Module faulty

Fault detected during discharge test in channel 1


section B and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

121

Module faulty

Fault detected during discharge test in channel 2


section B and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

122

Module faulty

Fault detected during discharge test in channel 3


section B and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

123

Module faulty

Fault detected during discharge test in channel 4


section B and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

124

Module faulty

Fault detected during discharge test in channel 5


section B and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

125

Module faulty

Fault detected during discharge test in channel 6


section B and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

126

Module faulty

Fault detected during discharge test in channel 7


section B and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

127

Module faulty

Fault detected during discharge test in channel 8


section B and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

128

Module faulty

Fault detected during discharge test in channel 9


section B and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

129

Module faulty

Fault detected during discharge test in channel 10


section B and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

130

Module faulty

Fault detected during discharge test in channel 11


section B and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

131

Module faulty

Fault detected during discharge test in channel 12


section B and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

132

Module faulty

Fault detected during discharge test in channel 13


section B and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

133

Module faulty

Fault detected during discharge test in channel 14


section B and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

134

Module faulty

Fault detected during discharge test in channel 15


section B and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

135

Module faulty

Fault detected during discharge test in channel 16


section B and/or or multiplexer address error

1) Reset system and check if it appears again


2) Check if signal is fluctuating, if yes, try to avoid it
3) Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

144

Module faulty

Deliberately corrupted iterated code has not been


detected

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

145

Module faulty

Deliberately corrupted iterated code has not been


detected

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

146

Module faulty

Deliberately corrupted iterated code has not been


detected in section A

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

147

Module faulty

Deliberately corrupted iterated code has not been


detected in section B

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

148

Module faulty

Deliberately corrupted frame has not been detected


Replace module
in section A

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

149

Module faulty

Deliberately corrupted frame has not been detected


Replace module
in section B

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

150

Module faulty

Fault detected in section A

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

151

Module faulty

Fault detected in section B

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

164

Module faulty

Fault detected on -7V value, section A.


Out of range and/or multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

165

Module faulty

Fault detected on 4mV value, section A.


Out of range and/or multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

166

Module faulty

Fault detected on M_+5V value, section A .


Out of range and/or multiplexer address error

Replace module

136-143 Error code not defined

152-163 Error code not defined

Not used

Not used

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

Corrective actions

167

Error code not defined

Not used

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

168

Module faulty

Fault detected on M_+9V value, section A.


Out of range and/or multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

169

Module faulty

Fault detected on M_Vext value, section A.


Out of range and/or multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

170

Module faulty

Fault detected on M_-9V value, section A.


Out of range and/or multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

171

Module faulty

Fault detected on xVref_B value, section A.


Out of range and/or multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

172

Module faulty

Fault detected on -7V value section A.


Out of range and/or multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

173

Module faulty

Fault detected on 4mV value, section A.


Out of range and/or multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

174

Module faulty

Fault detected on M_+5V value, section A.


Out of range and/or multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

175

Error code not defined

Not used

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

176

Module faulty

Fault detected on M_+9V value, section A.


Out of range and/or multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

177

Module faulty

Fault detected on M_Vext value, section A.


Out of range and/or multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

178

Module faulty

Fault detected on M_-9V value, section A.


Out of range and/or multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

179

Module faulty

Fault detected on xVref_B value, section A.


Out of range and/or multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

180

Module faulty

Fault detected on -7V value, section B.


Out of range and/or multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

181

Module faulty

Fault detected on 4mV value, section B.


Out of range and/or multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

182

Error code not defined

Not used

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

183

Module faulty

Fault detected on M_+5V value, section B.


Out of range and/or multiplexer address error

Replace module

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

184

Module faulty

Fault detected on M_Vext value, section B.


Out of range and/or multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

185

Module faulty

Fault detected on M_+9V value, section B.


Out of range and/or multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

186

Module faulty

Fault detected on xVref_A value, section B.


Out of range and/or multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

187

Module faulty

Fault detected on M_-9V value, section B.


Out of range and/or multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

188

Module faulty

Fault detected on -7V value, section B.


Out of range and/or multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

189

Module faulty

Fault detected on 4mV value, section B.


Out of range and/or multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

190

Error code not defined

Not used

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

191

Module faulty

Fault detected on M_+5V value, section B.


Out of range and/or multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

192

Module faulty

Fault detected on M_Vext value, section B.


Out of range and/or multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

193

Module faulty

Fault detected on M_+9V value, section B.


Out of range and/or multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

194

Module faulty

Fault detected on xVref_A value, section B.


Out of range and/or multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

195

Module faulty

Fault detected on M_-9V value, section B.


Out of range and/or multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

196

Module faulty

Fault detected on values of section A and B of


voltage monitoring channel 17

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

197

Module faulty

Fault detceted in Horizontal dataline(s) at bidirectional HBUS-driver

1) Replace module
2) replace IO extender
3) Check connections to Horizontal IO bus

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

200

Module faulty

Fault detected on A/D-converter section A and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

201

Module faulty

Fault detected on A/D-converter section A and/or


multiplexer address error

Replace module

198-199 Error code not defined

Not used

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

202

Module faulty

Fault detected on A/D-converter section A and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

203

Module faulty

Fault detected on A/D-converter section A and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

204

Module faulty

Fault detected on A/D-converter section A and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

205

Module faulty

Fault detected on A/D-converter section A and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

206

Module faulty

Fault detected on A/D-converter section A and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

207

Module faulty

Fault detected on A/D-converter section A and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

208

Module faulty

Fault detected on A/D-converter section A and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

209

Module faulty

Fault detected on A/D-converter section A and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

210

Module faulty

Fault detected on A/D-converter section A and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

211

Module faulty

Fault detected on A/D-converter section A and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

212

Module faulty

Fault detected on A/D-converter section A and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

213

Module faulty

Fault detected on A/D-converter section A and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

214

Module faulty

Fault detected on A/D-converter section A and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

215

Module faulty

Fault detected on A/D-converter section A and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

216

Module faulty

Fault detected on A/D-converter section B and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

217

Module faulty

Fault detected on A/D-converter section B and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

218

Module faulty

Fault detected on A/D-converter section B and/or


multiplexer address error

Replace module

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

219

Module faulty

Fault detected on A/D-converter section B and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

220

Module faulty

Fault detected on A/D-converter section B and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

221

Module faulty

Fault detected on A/D-converter section B and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

222

Module faulty

Fault detected on A/D-converter section B and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

223

Module faulty

Fault detected on A/D-converter section B and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

224

Module faulty

Fault detected on A/D-converter section B and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

225

Module faulty

Fault detected on A/D-converter section B and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

226

Module faulty

Fault detected on A/D-converter section B and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

227

Module faulty

Fault detected on A/D-converter section B and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

228

Module faulty

Fault detected on A/D-converter section B and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

229

Module faulty

Fault detected on A/D-converter section B and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

230

Module faulty

Fault detected on A/D-converter section B and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

231

Module faulty

Fault detected on A/D-converter section B and/or


multiplexer address error

Replace module

FC-SAI-1620m

Safe high-density analog


input module
232..251 Error code not defined
(16 channels)

Not Used

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

Loop fault in input circuitry

252

Module Faulty

Check the analog input loop(s) reported in loop


monitoring

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

253

Input compare error

Mismatch in scan value between CP1 and CP2


Most likely the signals is fluctuating fast. CP1 scan
on another time as CP2 and if the values differs
Check the behavior of the analog input and if is
more then 2% of full scale, also after a re-scan, this fluctuating
message will be reported. In this situation, the
configured Fault Reaction will determine the value
be used in the application.

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

254

Analog input loop fault(s)

Analog input open loop

Check the analog input loop(s) reported in loop


monitoring

FC-SAI-1620m

Safe high-density analog


input module
(16 channels)

255

Analog input loop fault(s)

Analog input short circuit

Check the analog input loop(s) on short circuit


reported in Loop monitoring

Module type

FC-SAI-0410

FC-SAI-0410

FC-SAI-0410

Module description

Safe analog input


module (4 channels)

Safe analog input


module (4 channels)

Safe analog input


module (4 channels)

EC

Description in Safety Builder Diagnostics

Module faulty

Module faulty

Module faulty

Details

Corrective actions

Fault detected during capacitor test channel 1


Module test channel on capacitor leakage.
This is needed to quarantee the accuracy of the
input value

1) Replace module
2) check if the external device is active of passive
and verify the correct sub-print is installed on the
backside on the IO Chassis.
BSAI-0420mI = Safe analog input converter
module, 0(4) 20 mA Internal power
BSAI-0420mE = Safe analog input converter
module, 0(4) 20 mA External power
BSAI-0405E = Safe analog input converter module,
0(1) 5 Vdc External power
BSAI-0410E = Safe analog input converter module,
0(2) 10 Vdc External power
BSDIL-0426 = Safe analog input converter module
for loop-monitored digital signals

Fault detected during capacitor test channel 2


Module test channel on capacitor leakage.
This is needed to quarantee the accuracy of the
input value

1) Replace module
2) check if the external device is active of passive
and verify the correct sub-print is installed on the
backside on the IO Chassis.
BSAI-0420mI = Safe analog input converter
module, 0(4) 20 mA Internal power
BSAI-0420mE = Safe analog input converter
module, 0(4) 20 mA External power
BSAI-0405E = Safe analog input converter module,
0(1) 5 Vdc External power
BSAI-0410E = Safe analog input converter module,
0(2) 10 Vdc External power
BSDIL-0426 = Safe analog input converter module
for loop-monitored digital signals

Fault detected during capacitor test channel 3


Modules test module on capacitor test leakage.
Module test channel on capacitor leakage.
This is needed to quarantee the accuracy of the
input value

1) Replace module
2) check if the external device is active of passive
and verify the correct sub-print is installed on the
backside on the IO Chassis.
BSAI-0420mI = Safe analog input converter
module, 0(4) 20 mA Internal power
BSAI-0420mE = Safe analog input converter
module, 0(4) 20 mA External power
BSAI-0405E = Safe analog input converter module,
0(1) 5 Vdc External power
BSAI-0410E = Safe analog input converter module,
0(2) 10 Vdc External power
BSDIL-0426 = Safe analog input converter module
for loop-monitored digital signals

Module type

FC-SAI-0410

FC-SAI-0410

FC-SAI-0410

FC-SAI-0410

Module description

Safe analog input


module (4 channels)

Safe analog input


module (4 channels)

Safe analog input


module (4 channels)

Safe analog input


module (4 channels)

EC

Description in Safety Builder Diagnostics

Module faulty

Module faulty

Module faulty

Module faulty

Details

Corrective actions

Fault detected during capacitor test channel 4


This is needed to quarantee the accuracy of the
input value
Module test channel on capacitor leakage.
This is needed to quarantee the accuracy of the
input value

1) Replace module
2) check if the external device is active of passive
and verify the correct sub-print is installed on the
backside on the IO Chassis.
BSAI-0420mI = Safe analog input converter
module, 0(4) 20 mA Internal power
BSAI-0420mE = Safe analog input converter
module, 0(4) 20 mA External power
BSAI-0405E = Safe analog input converter module,
0(1) 5 Vdc External power
BSAI-0410E = Safe analog input converter module,
0(2) 10 Vdc External power
BSDIL-0426 = Safe analog input converter module
for loop-monitored digital signals

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus twrmination on the CP chasis
If nothing can be found, replace QPP.

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus twrmination on the CP chasis
If nothing can be found, replace QPP.

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus twrmination on the CP chasis
If nothing can be found, replace QPP.

Module type

FC-SAI-0410

FC-SAI-0410

FC-SAI-0410

FC-SAI-0410

Module description

Safe analog input


module (4 channels)

Safe analog input


module (4 channels)

Safe analog input


module (4 channels)

Safe analog input


module (4 channels)

EC

10

Description in Safety Builder Diagnostics

Module faulty

Module faulty

Module faulty

Module faulty

Details

Corrective actions

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus twrmination on the CP chasis
If nothing can be found, replace QPP.

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus twrmination on the CP chasis
If nothing can be found, replace QPP.

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus twrmination on the CP chasis
If nothing can be found, replace QPP.

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus twrmination on the CP chasis
If nothing can be found, replace QPP.

Module type

FC-SAI-0410

FC-SAI-0410

FC-SAI-0410

FC-SAI-0410

Module description

Safe analog input


module (4 channels)

Safe analog input


module (4 channels)

Safe analog input


module (4 channels)

Safe analog input


module (4 channels)

EC

11

12

13

14

Description in Safety Builder Diagnostics

Module faulty

Module faulty

Module faulty

Module faulty

Details

Corrective actions

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus twrmination on the CP chasis
If nothing can be found, replace QPP.

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus twrmination on the CP chasis
If nothing can be found, replace QPP.

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus twrmination on the CP chasis
If nothing can be found, replace QPP.

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus twrmination on the CP chasis
If nothing can be found, replace QPP.

Module type

FC-SAI-0410

FC-SAI-0410

FC-SAI-0410

FC-SAI-0410

Module description

Safe analog input


module (4 channels)

Safe analog input


module (4 channels)

Safe analog input


module (4 channels)

Safe analog input


module (4 channels)

EC

15

16

17

18

Description in Safety Builder Diagnostics

Module faulty

Module faulty

Module faulty

Module faulty

Details

Corrective actions

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus twrmination on the CP chasis
If nothing can be found, replace QPP.

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus twrmination on the CP chasis
If nothing can be found, replace QPP.

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus twrmination on the CP chasis
If nothing can be found, replace QPP.

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus twrmination on the CP chasis
If nothing can be found, replace QPP.

Module type

FC-SAI-0410

FC-SAI-0410
FC-SAI-0410
FC-SAI-0410
FC-SAI-0410
FC-SAI-0410
FC-SAI-0410
FC-SAI-0410
FC-SAI-0410
FC-SAI-0410
FC-SAI-0410
FC-SAI-0410

FC-SAI-0410

FC-SAI-0410
FC-SAI-0410

Module description

Safe analog input


module (4 channels)

Safe analog input


module (4 channels)
Safe analog input
module (4 channels)
Safe analog input
module (4 channels)
Safe analog input
module (4 channels)
Safe analog input
module (4 channels)
Safe analog input
module (4 channels)
Safe analog input
module (4 channels)
Safe analog input
module (4 channels)
Safe analog input
module (4 channels)
Safe analog input
module (4 channels)
Safe analog input
module (4 channels)

Safe analog input


module (4 channels)

Safe analog input


module (4 channels)
Safe analog input
module (4 channels)

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

19

Module faulty

Fault detected on specific address/ data line

1) Replace module
2) If more modules on the same IO chassis are
reporting errors, check IO bus flatcable connection
and if nothing can be found replace IO extender
3) If more modules in more IO chassis reports
errors, most likely there is a fault in the common IO
bus (from CP to IO chassis) or QPP itself. Check If
all IO bus connection are tightly locked. Check also
the bus twrmination on the CP chasis
If nothing can be found, replace QPP.

20

Module faulty

Fault detected during reference check 2,5VDC /


span AD converter

Replace module

21

Module faulty

Fault detected during reference check 12VDC

Replace module

22

Module faulty

Fault detected during reference check 5VDC

Replace module

23

Module faulty

Fault detected during reference check -5,6VDC

Replace module

24

Module faulty

25

Module faulty

26

Module faulty

27

Module faulty

Fault detected during reference check 26VDC


output channel 1
Fault detected during reference check 26VDC
output channel 2
Fault detected during reference check 26VDC
output channel 3
Fault detected during reference check 26VDC
output channel 4

1) Check that the channel has no short circuit


2) Replace module
1) Check that the channel has no short circuit
2) Replace module
1) Check that the channel has no short circuit
2) Replace module
1) Check that the channel has no short circuit
2) Replace module

28

Module faulty

Fault detected during reference check -15VDC

Replace module

29..251 Error code not defined


252

not used
Check the analog input loop(s) reported in loop
monitoring

Analog input loop fault(s)

Loop fault in input circuitry

253

Input compare error

Mismatch in scan value between CP1 and CP2


Most likely the signals is fluctuating fast. CP1 scan
on another time as CP2 and if the values differs
Check the behavior of the analog input and if is
more then 2% of full scale, also after a re-scan, this fluctuating
message will be reported. In this situation, the
configured Fault Reaction will determine the value
be used in the application.

254

Analog input loop fault(s)

Analog input open loop

255

Analog input loop fault(s)

Analog input short circuit

Check the analog input loop(s) reported in loop


monitoring
Check the analog input loop(s) on short circuit
reported in loop monitoring

Module type
FC-SDO-0424

FC-SDO-0424

FC-SDO-0424

FC-SDO-0424

FC-SDO-0424

FC-SDO-0424

FC-SDO-0424

FC-SDO-0424

FC-SDO-0424

FC-SDO-0424

FC-SDO-0424

FC-SDO-0424

FC-SDO-0424

FC-SDO-0424

FC-SDO-0424

Module description

Description in Safety Builder Diagnostics

Details

Corrective actions

Module faulty

Group A (channel 1-2) is de-activated

1) Check other diagnostics. These may give the


reason of the de-activation.
2) Replace module

Safe digital output


module (24 Vdc, 2 A, 4
channels)

Module faulty

Fault detected during step 1 of diode test

Replace module

Safe digital output


module (24 Vdc, 2 A, 4
channels)

Module faulty

Faulte detected during step 2 of diode test

Replace module

Safe digital output


module (24 Vdc, 2 A, 4
channels)

Module faulty

Group B (channel 3-4) is de-activated

1) Check other diagnostics. These may give the


reason of the de-activation.
2) Replace module

Safe digital output


module (24 Vdc, 2 A, 4
channels)

Module faulty

Channel 1 de-activated

1) Check other diagnostics. This may give the


reason on de-activation.
2) Replace module

Safe digital output


module (24 Vdc, 2 A, 4
channels)

Module faulty

Channel 2 de-activated

1) Check other diagnostics. This may give the


reason on de-activation.
2) Replace module

Safe digital output


module (24 Vdc, 2 A, 4
channels)

Module faulty

Channel 3 de-activated

1) Check other diagnostics. This may give the


reason on de-activation.
2) Replace module

Safe digital output


module (24 Vdc, 2 A, 4
channels)

Module faulty

Channel 4 de-activated

1) Check other diagnostics. This may give the


reason on de-activation.
2) Replace module
1) Check internal power
2) Check If the module is set in correct chassis/slot
3) Check the flatcable of module is tightly
connected in the horizontal IO bus.
4) Replace module

Safe digital output


module (24 Vdc, 2 A, 4
channels)

EC

Safe digital output


module (24 Vdc, 2 A, 4
channels)

Actual output status invalid

The actual status of the outputs can be read or is


invalid.
Module is not detected by the CPU

Safe digital output


module (24 Vdc, 2 A, 4
channels)

Short circuit

Short cicruit detected on output channel

Check details, channel will be reported

Safe digital output


module (24 Vdc, 2 A, 4
channels)

10

External power down group A

No external power on group A (chan 1-1)

1) Check external power for this module


2) Check if there is any correlation in the field
2) Replace module

Safe digital output


module (24 Vdc, 2 A, 4
channels)

11

External power down group B

No external power on group A (chan 3-4)

1) Check external power for this module


2) Check if there is any correlation in the field
2) Replace module

Safe digital output


module (24 Vdc, 2 A, 4
channels)

12

External power down complete module

No external power on complate module

1) Check external power for this module.


In redundant configuration, If also the redundant
module reports the same, it's not a module fault.
2) Replace module

Safe digital output


module (24 Vdc, 2 A, 4
channels)
Safe digital output
module (24 Vdc, 2 A, 4
channels)

13..254 Error code not defined

255

Output compare error

Not used

CP1 and CP2 calculates other value for ouput


channel

1) Check application if values are continous


changing.
2) Contact HSMS to define further action.

Module type

Module description

FC-SDO-0824

Safe digital output


module (24 Vdc, 0.55 A,
8 channels)

FC-SDO-0824

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

Module faulty

Group A (channel 1-4) is de-activated

1) Check other diagnostics. These may give the


reason of the de-activation.
2) Replace module

Safe digital output


module (24 Vdc, 0.55 A,
8 channels)

Module faulty

Group B (channel 5-8) is de-activated

1) Check other diagnostics. These may give the


reason of the de-activation.
2) Replace module

FC-SDO-0824

Safe digital output


module (24 Vdc, 0.55 A,
8 channels)

Module faulty

Fault detected during step 1 of diode test

1) Check internal power 24VDC


2) Replace module

FC-SDO-0824

Safe digital output


module (24 Vdc, 0.55 A,
8 channels)

Module faulty

Faulte detected during step 2 of diode test

Replace module

FC-SDO-0824

Safe digital output


module (24 Vdc, 0.55 A,
8 channels)

Error code not defined

Not used

FC-SDO-0824

Safe digital output


module (24 Vdc, 0.55 A,
8 channels)

Module faulty

Channel 1 de-activated

1) Check other diagnostics. This may give the


reason on de-activation.
2) Replace module

FC-SDO-0824

Safe digital output


module (24 Vdc, 0.55 A,
8 channels)

Module faulty

Channel 2 de-activated

1) Check other diagnostics. This may give the


reason on de-activation.
2) Replace module

FC-SDO-0824

Safe digital output


module (24 Vdc, 0.55 A,
8 channels)

Module faulty

Channel 3 de-activated

1) Check other diagnostics. This may give the


reason on de-activation.
2) Replace module

FC-SDO-0824

Safe digital output


module (24 Vdc, 0.55 A,
8 channels)

Module faulty

Channel 4 de-activated

1) Check other diagnostics. This may give the


reason on de-activation.
2) Replace module

FC-SDO-0824

Safe digital output


module (24 Vdc, 0.55 A,
8 channels)

Module faulty

Channel 5 de-activated

1) Check other diagnostics. This may give the


reason on de-activation.
2) Replace module

FC-SDO-0824

Safe digital output


module (24 Vdc, 0.55 A,
8 channels)

10

Module faulty

Channel 6 de-activated

1) Check other diagnostics. This may give the


reason on de-activation.
2) Replace module

FC-SDO-0824

Safe digital output


module (24 Vdc, 0.55 A,
8 channels)

11

Module faulty

Channel 7 de-activated

1) Check other diagnostics. This may give the


reason on de-activation.
2) Replace module

FC-SDO-0824

Safe digital output


module (24 Vdc, 0.55 A,
8 channels)

12

Module faulty

Channel 8 de-activated

1) Check other diagnostics. This may give the


reason on de-activation.
2) Replace module

FC-SDO-0824

Safe digital output


module (24 Vdc, 0.55 A,
8 channels)

13

Actual output status invalid

The actual status of the outputs can be read or is


invalid.
Module is not detected by the CPU

1) Check internal power


2) Check If the module is set in correct chassis/slot
3) Check the flatcable of module is tightly
connected in the horizontal IO bus.
4) Replace module

FC-SDO-0824

Safe digital output


module (24 Vdc, 0.55 A,
8 channels)

14

Short circuit

Short cicruit detected on output channel

Check details, channel will be reported

FC-SDO-0824

Safe digital output


module (24 Vdc, 0.55 A,
8 channels)

15

External power down group A

No external power on group A (chan 1-4)

1) Check external power for this module


2) Check if there is any correlation in the field
2) Replace module

Module type

Module description

FC-SDO-0824

Safe digital output


module (24 Vdc, 0.55 A,
8 channels)

EC
16

FC-SDO-0824

Safe digital output


module (24 Vdc, 0.55 A,
8 channels)

17

FC-SDO-0824

Safe digital output


module (24 Vdc, 0.55 A,
8 channels)

18..99

FC-SDO-0824

Safe digital output


module (24 Vdc, 0.55 A,
8 channels)

FC-SDO-0824

Safe digital output


module (24 Vdc, 0.55 A,
8 channels)

FC-SDO-0824

Safe digital output


module (24 Vdc, 0.55 A,
8 channels)

100

Description in Safety Builder Diagnostics

Details

Corrective actions

External power down group B

No external power on group A (chan 5-8)

1) Check external power for this module


2) Check if there is any correlation in the field
2) Replace module

External power down complete module

No external power on complete module

1) Check external power for this module.


In redundant configuration, If also the redundant
module reports the same, it's not a module fault.
2) Replace module

Error code not defined

Not used

Module faulty

101..254 Error code not defined

255

Output compare error

Module Not accesible

1) Check internal power


2) Check If the module is set in correct chassis/slot
3) Check the flatcable of module is tightly
connected in the horizontal IO bus.
4) Replace module

Not used

CP1 and CP2 calculates other value for ouput


channel

1) Check application if values are continous


changing.
2) Contact HSMS to define further action.

Module type

Module description

Description in Safety Builder Diagnostics

Details

Error code not defined

Not used

Safe digital output


FC-SDO-0448
module 4 channels
FC-SDO-04110
48 Vdc, 0.75 A
110 Vdc, 0.32 A

Module faulty

Fault detected during step 1 of diode test

Replace module

Safe digital output


FC-SDO-0448
module 4 channels
FC-SDO-04110
48 Vdc, 0.75 A
110 Vdc, 0.32 A

Module faulty

Faulte detected during step 2 of diode test

Replace module

Safe digital output


FC-SDO-0448
module 4 channels
FC-SDO-04110
48 Vdc, 0.75 A
110 Vdc, 0.32 A

Module faulty

Channel 1 de-activated

1) Check other diagnostics. This may give the


reason on de-activation.
2) Replace module

Safe digital output


FC-SDO-0448
module 4 channels
FC-SDO-04110
48 Vdc, 0.75 A
110 Vdc, 0.32 A

Module faulty

Channel 2 de-activated

1) Check other diagnostics. This may give the


reason on de-activation.
2) Replace module

Safe digital output


FC-SDO-0448
module 4 channels
FC-SDO-04110
48 Vdc, 0.75 A
110 Vdc, 0.32 A

Module faulty

Channel 3 de-activated

1) Check other diagnostics. This may give the


reason on de-activation.
2) Replace module

Safe digital output


FC-SDO-0448
module 4 channels
FC-SDO-04110
48 Vdc, 0.75 A
110 Vdc, 0.32 A

Module faulty

Channel 4 de-activated

1) Check other diagnostics. This may give the


reason on de-activation.
2) Replace module

Actual output status invalid

The actual status of the outputs can be read or is


invalid.
Module is not detected by the CPU

1) Check internal power


2) Check If the module is set in correct chassis/slot
3) Check the flatcable of module is tightly
connected in the horizontal IO bus.
4) Replace module

Safe digital output


FC-SDO-0448
module 4 channels
FC-SDO-04110
48 Vdc, 0.75 A
110 Vdc, 0.32 A

Safe digital output


FC-SDO-0448
module 4 channels
FC-SDO-04110
48 Vdc, 0.75 A
110 Vdc, 0.32 A

EC

Corrective actions

Safe digital output


FC-SDO-0448
module 4 channels
FC-SDO-04110
48 Vdc, 0.75 A
110 Vdc, 0.32 A

External power down complete module

No external power on complate module

1) Check external power for this module.


In redundant configuration, If also the redundant
module reports the same, it's not a module fault.
2) Replace module

Safe digital output


FC-SDO-0448
module 4 channels
FC-SDO-04110
48 Vdc, 0.75 A
110 Vdc, 0.32 A

Short circuit

Short cicruit detected on output channel

Check details, channel will be reported

Safe digital output


FC-SDO-0448
module 4 channels
FC-SDO-04110
48 Vdc, 0.75 A
110 Vdc, 0.32 A
Safe digital output
FC-SDO-0448
module 4 channels
FC-SDO-04110
48 Vdc, 0.75 A
110 Vdc, 0.32 A

10..254 Error code not defined

255

Output compare error

Not used

CP1 and CP2 calculates other value for ouput


channel

1) Check application if values are continous


changing.
2) Contact HSMS to define further action.

Module type

Module description

FC-SDOL-0424 &
FC-SDOL-0448

Safe loop-monitored
digital output module 4
channels
24 Vdc, 1 A

EC

Description in Safety Builder Diagnostics

Details

Error code not defined

Not used

Corrective actions

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

Module faulty

De-activation of all channels

Replace module

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

Module faulty

Module faulty
Internal power down
The module is not detected by CP

1) Check internal power of module


2) If more modules reporting the same error, check
the common cause as IO bus

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

Output correlation on module

Check output loops. Common cuase is a cross


wiring between different channels.
Another cause may be the behavior of the
connected external device.

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

Module faulty

Output correlation on module

Check output loops. Common cuase is a cross


wiring between different channels.
Another cause may be the behavior of the
connected external device.

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

Current detected in output loop

Check output loops. Common cause is a cross


Output correlation in field. "normal" only, not active wiring between different channels.
if "1oo2D" configured
Another cause may be the behavior of the
connected external device.

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

Current detected in output loop

Check output loops. Common cause is a cross


Output correlation in field.Different reactions 2oo2d wiring between different channels.
/ 1oo2D
Another cause may be the behavior of the
connected external device.

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

Actual output status invalid

Actual output invalid, actual output on

1) Check internal power


2) Check If the module is set in correct chassis/slot
3) Check the flatcable of module is tightly
connected in the horizontal IO bus.
4) Replace module

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

Module faulty

Voltage read back circuit faulty

Replace module

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

Short circuit

Output short or overload

Check details which channel has overload and


correct it.
Check also electrical behavior of external device.
For example a flashlight has a very inrush current

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

10

Module faulty

Output control logic faulty

Replace module

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

11

Module faulty

Output control logic faulty

Replace module

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

12

Module faulty

Flyback diode open

Replace module

Module faulty

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

13

Module faulty

Output deactivation impossible

Replace module

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

14

Module faulty

Output activation impossible

Replace module

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

Output short or overload

Check details which channel has overload and


correct it.
Check also electrical behavior of external device.
For example a flashlight has a very inrush current

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

16

Short circuit

Output short or overload

Check details which channel has overload and


correct it.
Check also electrical behavior of external device.
For example a flashlight has a very inrush current

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

17

Module faulty

Current read back circuit faulty

Replace module

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

18

Module faulty

Current read back circuit faulty

Replace module

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

19

Module faulty

Current read back circuit faulty

Replace module

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

20

Open loop

Output lead breakage

Check in details or loop monitoring which loop(s)


has a breakage

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

21

Open loop

Output lead breakage

Check in details or loop monitoring which loop(s)


has a breakage

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

22

Open loop

Output lead breakage

Check in details or loop monitoring which loop(s)


has a breakage

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

23

External power down complete module

No external power on complete module

1) Check external power for this module.


In redundant configuration, If also the redundant
module reports the same, it's not a module fault.
2) Replace module

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

24

External power down complete module

No external power on complete module

1) Check external power for this module.


In redundant configuration, If also the redundant
module reports the same, it's not a module fault.
2) Replace module

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

25

Module faulty

Module faulty
Internal power down
The module is not detected by CP

1) Check internal power of module


2) If more modules reporting the same error, check
the common cause as IO bus

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

26

Open loop

Output lead breakage

Check in details or loop monitoring which loop(s)


has a breakage

15

Short circuit

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

27

Module faulty

WD input switched off

Check the reason why watchdog signal is switched


off

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

28

Module faulty

WD input switched off

Check the reason why watchdog signal is switched


off

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

29

Current detected in output loop

Check output loops. Common cause is a cross


Output correlation in field. "normal" only, not active wiring between different channels.
if "1oo2D" configured
Another cause may be the behavior of the
connected external device.

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

30

Module faulty

Output correlation on module

Replace module

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

Output correlation in field.

Check output loops. Common cause is a cross


wiring between different channels.
Another cause may be the behavior of the
connected external device.

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

Short circuit

Overload detected in field while output off

Check output loops. Common cause is a cross


wiring between different channels.
Another cause may be the behavior of the
connected external device.

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

Current detected in output loop

Current detected in output loop. Detected during


special 1oo2D test

Check output loops. Common cause is a cross


wiring between different channels.
Another cause may be the behavior of the
connected external device.

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

Current detected in output loop, during scan.

Check output loops. Common cause is a cross


wiring between different channels.
Another cause may be the behavior of the
connected external device.

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

FC-SDOL-0424 &
FC-SDOL-0448

Safe digital output


module (24 Vdc, 2 A, 4
channels)

31

32

33

34

Current detected in output loop

Current detected in output loop

35..254 Error code not defined

255

Output compare error

Not used

CP1 and CP2 calculates other value for ouput


channel

1) Check application if values are continous


changing.
2) Contact HSMS to define further action.

Module type

Module description

FC-DO-1224

Non Safe digital output


module (24 Vdc, 0.55 A,
12 channels)

FC-DO-1224

Non Safe digital output


module (24 Vdc, 0.55 A,
12 channels)

EC

Description in Safety Builder Diagnostics

Details

0..254

Error code not defined

Not used

255

Output compare error

CP1 and CP2 calculates other value for ouput


channel

Corrective actions

1) Check application if values are continous


changing.
2) Contact HSMS to define further action.

Module type

Module description

FC-DO-1624

Non-Safe digital output


module (24 Vdc, 0.1 A,
16 channels)

FC-DO-1624

Non-Safe digital output


module (24 Vdc, 0.1 A,
16 channels)

EC

Description in Safety Builder Diagnostics

Details

0..254

Error code not defined

Not used

255

Output compare error

CP1 and CP2 calculates other value for ouput


channel

Corrective actions

1) Check application if values are continous


changing.
2) Contact HSMS to define further action.

Module type

Module description

FC-RO-1024

Non-Safe relay output


module (contacts, 10
channels)

FC-RO-1024

Non-Safe relay output


module (contacts, 10
channels)

EC

Description in Safety Builder Diagnostics

Details

0..254

Error code not defined

Not used

255

Output compare error

CP1 and CP2 calculates other value for ouput


channel

Corrective actions

1) Check application if values are continous


changing.
2) Contact HSMS to define further action.

Module type

FC-SAO-0220m

FC-SAO-0220m

FC-SAO-0220m

FC-SAO-0220m

FC-SAO-0220m

Module description

Safe analog output


module (0(4) 20 mA, 2
channels)

Safe analog output


module (0(4) 20 mA, 2
channels)

Safe analog output


module (0(4) 20 mA, 2
channels)

Safe analog output


module (0(4) 20 mA, 2
channels)

Safe analog output


module (0(4) 20 mA, 2
channels)

EC

Description in Safety Builder Diagnostics

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Details

Corrective actions

Channel 1 de-activated

1) Check analog output loop channel 1


If no fault can be found, create a short on FTA to
see if loop will become healthy.
If loop becomes healthy, fault must be found in
loop
2) If loop stay faulty, check if channel 2 gives same
error.
In that situation, it's most likely the module.
Check if other modules in same IO chassis are
reported faulty.
If it is, check if this is related to IO extender,
incorrect IO chassis addressing, IO bus...

Channel 2 de-activated

1) Check analog output loop channel 2


If no fault can be found, create a short on FTA to
see if loop will become healthy.
If loop becomes healthy, fault must be found in
loop
2) If loop stay faulty, check if channel 1 gives same
error.
In that situation, it's most likely the module.
Check if other modules in same IO chassis are
reported faulty.
If it is, check if this is related to IO extender,
incorrect IO chassis addressing, IO bus...

95% test value channel 1 failed

If external device is nor conventional equipment


but has electronic, most likely the test pulse are
filtered by the device. In this situation, enable in the
hardware configurator, Io module properties, the
parameter "Test disabled". The loop and card will
be tested but not the percentage tests.

95% test value channel 2 failed

If external device is nor conventional equipment


but has electronic, most likely the test pulse are
filtered by the device. In this situation, enable in the
hardware configurator, Io module properties, the
parameter "Test disabled". The loop and card will
be tested but not the percentage tests.

5% test value channel 1 failed

If external device is nor conventional equipment


but has electronic, most likely the test pulse are
filtered by the device. In this situation, enable in the
hardware configurator, Io module properties, the
parameter "Test disabled". The loop and card will
be tested but not the percentage tests.

Module type

Module description

FC-SAO-0220m

Safe analog output


module (0(4) 20 mA, 2
channels)

FC-SAO-0220m

FC-SAO-0220m

FC-SAO-0220m

FC-SAO-0220m

FC-SAO-0220m

Safe analog output


module (0(4) 20 mA, 2
channels)

Safe analog output


module (0(4) 20 mA, 2
channels)

Safe analog output


module (0(4) 20 mA, 2
channels)

Safe analog output


module (0(4) 20 mA, 2
channels)

Safe analog output


module (0(4) 20 mA, 2
channels)

EC

10

Description in Safety Builder Diagnostics

Module faulty

Module faulty

Module faulty

Module faulty

Module faulty

Actual output status invalid

Details

Corrective actions

5% test value channel 2 failed

If external device is nor conventional equipment


but has electronic, most likely the test pulse are
filtered by the device. In this situation, enable in the
hardware configurator, Io module properties, the
parameter "Test disabled". The loop and card will
be tested but not the percentage tests.

+10% test value channel 1 failed

If external device is nor conventional equipment


but has electronic, most likely the test pulse are
filtered by the device. In this situation, enable in the
hardware configurator, Io module properties, the
parameter "Test disabled". The loop and card will
be tested but not the percentage tests.

+10% test value channel 2 failed

If external device is nor conventional equipment


but has electronic, most likely the test pulse are
filtered by the device. In this situation, enable in the
hardware configurator, Io module properties, the
parameter "Test disabled". The loop and card will
be tested but not the percentage tests.

-10% test value channel 1 failed

If external device is nor conventional equipment


but has electronic, most likely the test pulse are
filtered by the device. In this situation, enable in the
hardware configurator, Io module properties, the
parameter "Test disabled". The loop and card will
be tested but not the percentage tests.

-10% test value channel 2 failed

If external device is nor conventional equipment


but has electronic, most likely the test pulse are
filtered by the device. In this situation, enable in the
hardware configurator, Io module properties, the
parameter "Test disabled". The loop and card will
be tested but not the percentage tests.

Actual value chan. 1 invalid/lead breakage

1) Check analog output loop channel 1


If no fault can be found, create a short on FTA to
see if loop will become healthy.
If loop becomes healthy, fault must be found in
loop
2) If loop stay faulty, check if channel 2 gives same
error.
In that situation, it's most likely the module.
Check if other modules in same IO chassis are
reported faulty.
If it is, check if this is related to IO extender,
incorrect IO chassis addressing, IO bus...

Module type

Module description

EC

Description in Safety Builder Diagnostics

Details

Corrective actions

FC-SAO-0220m

Safe analog output


module (0(4) 20 mA, 2
channels)

11

Actual output status invalid

Actual value chan. 2 invalid/lead breakage

1) Check analog output loop channel 2


If no fault can be found, create a short on FTA to
see if loop will become healthy.
If loop becomes healthy, fault must be found in
loop
2) If loop stay faulty, check if channel 1 gives same
error.
In that situation, it's most likely the module.
Check if other modules in same IO chassis are
reported faulty.
If it is, check if this is related to IO extender,
incorrect IO chassis addressing, IO bus...

FC-SAO-0220m

Safe analog output


module (0(4) 20 mA, 2
channels)

12

Module faulty

AO module faulty
Internal open loop

Replace module

FC-SAO-0220m

Safe analog output


module (0(4) 20 mA, 2
channels)

13

Module faulty

Both channels open loop. This can only happen in


same cycle. Module cannot be accessed.

Check for analog output open loop for both


channels

FC-SAO-0220m

Safe analog output


module (0(4) 20 mA, 2 14..253 Not used
channels)

FC-SAO-0220m

Safe analog output


module (0(4) 20 mA, 2
channels)

254

Open Loop(s)

Loop fault detected in field

1) Check Loop monitoring which loop is faulty


2) Solve the loop fault

FC-SAO-0220m

Safe analog output


module (0(4) 20 mA, 2
channels)

255

Output compare error

CP1 and CP2 calculates other value for ouput


channel

1) Check application if values are continous


changing.
2) Contact HSMS to define further action.