Conventional

Fire Alarm Systems

Contents

Introduction
Premier SX Conventional
Fire Alarm Panel
Premier Elite Conventional
Fire Alarm Panel

Zeta UV/IR Optical Flame Detectors

26-27

Zeta Conventional Manual Call Points

28

Zeta Conventional
Weatherproof Call Point

29

30

Premier Conventional Repeater Panel

10

Zeta Conventional Explosion Proof


Manual Call Point

Premier M Plus 8-24 Zone


Conventional Fire Alarm Panel

11

Miditone Conventional
Electronic Sounder

31

Premier M Plus Repeater Panel

12

Miditone Conventional Combined


Electronic Sounder & Flasher

32

Premier 48 M Plus 24-48 Zone


Conventional Fire Alarm Panel

13

Securetone Conventional
Electronic Sounder

33

Premier 48 M Plus Repeater Panel

14

Secure Light Xenon Flasher

34

Premier MX Conventional
Fire Alarm Panel

15

Maxitone Conventional Sounder and


Combined Sounder & Flasher

35

Fyreye Extra Conventional


Optical Smoke Detector

16

Zeta Conventional Fire Alarm Bells

36

Zeta Flame Proof Siren

37

Zeta Flame Proof Gong Bell

38

Zeta Magnetic Door Holders

39

Zeta Duct Unit

40

Fyreye Extra Conventional Rate of


Rise and Fixed Heat Detectors

3-7

17

Fyreye Extra Conventional


Opto-Heat Detector

18

Fyreye Conventional
Ultra-Violet Flame Detector

19

Fyreye Conventional Detector Bases

20

Premier Power Pack EN 54-4 Power


Supply with LCD Screen

41

Zeta Remote LED Indicator

21

Batteries

42

Fyreye 50 & 100m Reflective Beam


Smoke Detector

22-23

Fyreye 50 & 100m Auto-aligning Beam


Smoke Detector Systems 50 & 100m

24-25

Introduction
Zeta Alarm Systems, a trading name of GLT Exports Ltd, was founded
in 1985 and is a privately held UK manufacturer of Fire Alarm, Gas
Detection and Emergency Systems.
Our brand name is well known throughout the industry and is acclaimed in over forty
countries worldwide. We are currently represented in the UK, Europe, Africa, the
Middle East, Southern Asia & South America and this list continues to grow.

Complete System Supplier

Research & Development

To meet the requirements of our ever-changing market,


we pride ourselves on being a complete system
supplier. This means our customers can rely on us for
their entire system requirements.

As with all electronic equipment there is an ever


present drive to manufacture products that are
increasingly effective whilst becoming more cost
sensitive. To meet this objective we spend a significant
percentage of our profits on the continued development
of products, whether it be introducing new items, or
improving existing ones. We have a team of engineers &
designers all of whom have vast industry knowledge &
experience.

One of the main advantages of using a complete system


supplier, compared with a component supplier, is that
system wide compatibility is assured and there is one
point of contact.
Marketing our products as systems has played a vital
role in our worldwide success.

The Future
Our continued inward investment and constant
endeavour to offer the very best products is recognised
by our increased turnover and profit margin year-onyear. Our mission is to support our existing & future
customers by providing them with the highest quality
products, at the most competitive prices.

Customer Support & Product Warranty

As a manufacturer we always follow the market needs


closely to evaluate how we should adapt our product
range. This, combined with welcomed customer
feedback, has proved to be a successful formula for
meeting the current and future industry needs.

Statement Of Quality Policy


We maintain a Quality System, which conforms to BS EN
ISO9001:2008. We are committed, where applicable,
to manufacture in compliance with all appropriate
legislation & regulatory requirements.

We value our customers greatly and to ensure they have


the best experience we have a dedicated support team
who are able to assist with sales, technical or logistical
queries.
Our products carry a full 24 month manufacturers
guarantee from the date of purchase. Our network
of authorised agents is fully trained on the use of our
products and will provide a helpful & friendly service.

Introduction to Fire
Alarm Systems

Fire Detection &


Alarm Systems BS5839

Fire alarm systems are used to detect a


fire, and to signal a warning alarm to the
appropriate source.

Risk Assessment

In general, there are 3 types of system;


1. Manual Fire Alarm Systems which rely on manual
call points to signal an alarm
2. Life Protection Fire Alarm Systems these are
designed to protect the occupants of a building
3. Property Protection Fire Alarm Systems these
are designed to protect buildings

The warning may be simply ringing fire alarm sirens,


however if a building is likely to be unoccupied, it may
be more appropriate to signal to a monitoring station,
or at least send a message to the building owner via
telephone.

The Fire precautions (Workplace) Regulations require


any business employing five or more persons to hold a
written Fire Risk Assessment and Emergency Plan.
This must be periodically reviewed.
The local fire brigade can enforce compliance, and
close any building that does not meet this act.
In the event of a fire in a building without a written
Fire Risk Assessment, those responsible may face fines
and imprisonment, and/or private litigation.
What the law requires you to do:
Complete a fire risk assessment for your work
place (considering all employees, the public,
disabled people and people with special needs).
Identify and record any significant findings or
persons at risk.
Provide and maintain fire precautions.
Provide information, instruction and training.
Nominate persons responsible to implement
your emergency plan.
Consult employees about the above nominations
and your proposals to improve fire precautions.
Inform other employees who may have work
places in the building about any significant risks
which may affect their safety and co-operate with
them to reduce/control these risks.
If you are not an employer, but control premises
which contain more than one workplace, you are
responsible for complying with fire regulations.
You must establish a suitable means of
contacting the emergency services.
Your employees must co-operate to ensure the
workplace is safe from fire and its effects.

System Zoning
Information
In order to aid identification of the source of a possible
fire, the protected building should be divided into
zones. When deciding on a suitable zoning scheme
for a building, consideration should be given to the
size, any existing fire routines, escape routes, zone
accessibility, and structural fire compartmentation.

The following guide lines should be observed:


If the total floor area of the building is less
than 300m2 then the building needs only one zone,
regardless of the number of storeys.

Manual Call Points


A Manual Call Point is a device which enables
personnel to raise an alarm in the event of a fire
incident by pressing a frangible element to activate the
alarm system.
Manual Call Points should be installed at a height of
1.2m above floor level at easily accessible, conspicuous
positions, on exit routes, at the entry floor landings of
staircases and at all exits to the open air.

If the total floor area is greater than


300m2:
The maximum area for a zone is 2000m2
If a stairwell (or similar) extends beyond one floor it
should be a separate zone.
If a zone covers more than one fire compartment
then the zone boundaries should follow the
compartment boundaries.
The search distance within the zone in order to
ascertain the position of the fire should not exceed
60m. Remember that the use of Remote Indicator
lamps may help to reduce the distance travelled.

1.2m - 1.4m

Manual Call Points should be spaced so that one may


always be found within a maximum distance of 45m
apart or 25m for disabled person.

45m Max. or
25m Max. for disabled person

60m Max.

If a building is divided between occupiers, zones


must not be shared between them.

Detector Information
Automatic Detectors
When deciding on the type of detector to be used in any area it is important to remember that the detector has to
discriminate between a genuine fire and the normal conditions existing therein.

Smoke Detectors

Heat Detectors General

In open spaces under flat horizontal ceilings, every


point should lie within 7.5m of a smoke detector.

In open spaces under flat horizontal ceilings, every


point should lie within 5.3m of a heat detector.

10.6m

7.5m

112m
(10.6m x
10.6m)

56.3m
(7.5m x
7.5m)

Room
boundary

7.5m

5.3m

5.3m

Smoke detection should be generally avoided in the


following areas to avoid unwanted alarms. They should
be protected by means of other detectors such as heat
detectors.
Contamination in dusty areas may cause unwanted
alarms and reduce the life of the detector.
Damp or humid conditions such as showers, bathrooms
and external areas should be avoided as the water
vapour may cause unwanted alarms and reduce the life
of the detector.
Detectors should not be mounted where gases, vapours
or fumes are present.
Detectors should never be used at low temperature
where ice or condensation can affect detector
sensitivity.
Kitchens, garages, welding shops and boiler houses
should generally be avoided.

Room
boundary

3.8m

Heat detectors are designed to either detect a


rapid rise in temperature or to operate at a fixed
temperature. Although they provide a slower response
time than smoke detectors they do provide a method of
protection for areas where smoke detectors cannot be
used.
Heat detectors should not be used for the protection of
life or where extensive property loss may be expected.

Rate of Rise Heat Detectors


Rate of Rise heat detectors respond to both rapid
increases of temperature and to fixed top temperature.

Fixed Temperature Heat Detectors


Fixed temperature heat detectors are available with
different temperature settings, and are normally
installed in kitchens, boiler rooms, etc.

Detection In Apex Roofs

Fire Alarm Sounders

If the ceiling is pitched or sloping, smoke will tend


to rise towards the highest point (apex) of the roof,
therefore detection should be placed in the apex. As
the slope tends to reduce the delay before smoke or
heat reaches the detectors, it is permissible to use a
greater spacing between the detectors mounted there.

Fire Alarm Sounders should be installed throughout the


building with an even distribution, to generally provide
a minimum sound level of 65dB(A) or 5dB(A) above any
background noise which is likely to persist for more
than 30 seconds.

Limits of Ceiling Height

65dB(A)
@ 500Hz - 1000Hz

+5dB(A)
@ 500Hz - 1000Hz
Background noise

Heat
Detector

Smoke
Detector

Heat
Detector

Smoke
Detector

Apex
<150mm

Apex
<600mm

Apex
>150mm

Apex
>600mm

Small Apex
= Standard Spacing

Large Apex
= Extended Spacing

Cabling

Where the alarm may have to arouse sleeping persons


e.g. Hotel bedrooms, nursing homes, etc, a minimum
sound level of 75dB(A) is required, at the bed head with
all the doors shut.

The operation of a Fire Alarm and Detection


System depends on the cabling and connections
between the components. It is essential that
connection between Manual Call Points and
Detectors function correctly when they are
operated.
Cables within the system are required to function
correctly for significant periods after being
attacked by fire. These include the power supply
cables to the control panel, the detection circuits
and the fire alarm sounder circuits. Thus the
cables chosen must be correctly rated to withstand
these conditions.

75dB(A)

All fire alarm sounders in a building should produce the


same sound, distinct from any other audible warning
devices in the building.
Where fire alarm sounders are required in extremely
noisy areas e.g. Machine shops, it may be necessary to
install additional Visual Indication Beacons.

Conventional Fire Alarm Systems /

Premier SX Conventional Fire Alarm Panel


(NPSX1, NPSX2, NPSX4, NPSX6, NPSX8)

The Premier SX control panel range is available


in 1, 2, 4, 6 and 8 zones, housed in a light grey
flame retardant ULV0 enclosure, designed to
meet modern architectural surroundings, with
a removable hinged door.
The Premier SX has been designed with ease of
installation in mind, in addition to the robust electronic
design expected from Zeta Alarm Systems.

73mm

Features

100mm

LPCB Approved to EN54 parts 2 & 4


One man test facility
Disablement facility for zones & sounders
Space for up to 7Ahr batteries
Sounder delay option (0 9 min)
Panel can be flush mounted

Flush Mount

Wall Mount

Model

NPSX1

NPSX2

NPSX4

NPSX6

NPSX8

Part No.

37-050

37-051

37-052

37-053

37-054

Mains Voltage

230V AC +10% / -15% @ 50/60Hz

System Voltage

24V DC (nominal)

Zone Voltage

21V DC (nominal)

Sounder Alarm Output

2 x 400mA @ 24V DC (nominal)

Fault Relay Output

1 x relay SELV @ 1A maximum

Fire Relay Output

1 x relay SELV @ 1A maximum

Zone Capacity

32 devices per zone

Remote Sounder Activation

Via N/O contact (class change)

Sounder Activation Delay

0-9 minutes in 1 minute increments

Zone End Of Line

IN4002 Diode (cathode stripe to +)

Sounder End Of Line

10K resistor

Charger Voltage

28.4V @ 20C (with battery disconnected)

Zone Short Circuit Protection

100mA

Charger Short Circuit Protection

Battery voltage less than 20V

Enclosure Size

355 (l) x 275 (h) x 100 (d) mm

Weight

3.25kg (excluding batteries)

Conventional Fire Alarm Systems /

Premier Elite Conventional Fire Alarm Panel


(PE1, PE2, PE4, PE6, PE8)

The Premier Elite 1-8 zone fire alarm


panels are ideal for small to medium sized
installations. They meet all the requirements
of EN54 parts 2 & 4, and come in an
attractively styled enclosure.
The zonal output card gives a drive voltage to operate
zonal alarm relays, or a hardwired repeater panel.

Features
73mm

Fault relay (4, 6 & 8 zone only)

100mm

Alarm relay
Current limited charger to prevent flat batteries
drawing too much current (4, 6 & 8 zone only)
Built in diode base compatibility (4, 6 & 8 zone
only)
Sounder delay facility (4, 6 & 8 zone only)
Connection to optional add on zonal output card
(4, 6 & 8 zone only)
Zone disablement facility (4, 6 & 8 zone only)

Flush Mount

One man test facility (4, 6 & 8 zone only)

Wall Mount

Model

PE1

PE2

PE4

PE6

PE8

Part No.

37-040

37-041

37-042

37-043

37-044

Detection Zones

Mains Voltage

230V AC +10%/-15% @ 50/60Hz

System Voltage

24V DC (nominal)

Zone Voltage

22V DC (nominal)

Sounder Alarm Output

2 x 400mA @ 24V DC (nominal)

Fault Relay Output

N/A

Fire Relay Output

1 x relay SELV @ 1A maximum

Zone Capacity

20 Devices

32 Devices

Remote Sounder Activation

N/A

Via N/O Contacts

Sounder Activation Delay

N/A

0-9 minutes in 1 minute increments

Zone End Of Line

10K resistor

IN4002 Diode (cathode stripe to +)

Sounder End Of Line

10K resistor

10K resistor

Charger Voltage

27.6V DC (No Batt Connected)

28.4V @ 25C (No Battery Connected)

Zone Short Circuit Protection

N/A

100mA

Charger Short Circuit Protection

N/A

Batteries less than 21V

Operating Temperature

0C to 50C

Enclosure Size

355 x 275 x 100mm

Weight

2.5kg (excluding batteries)

29V DC (nominal)

1 x relay SELV @ 1A maximum

3.25kg (excluding batteries)

Conventional Fire Alarm Systems /

Premier Conventional Repeater Panel


(PRE-REP)

The Premier Repeater panel is a hard-wired


repeater panel for use with the Premier SX (all
sizes), and the Premier Elite (4-8 zone) panels.
It is display only (no controls) and indicates power,
general fault, general fire & the zone in alarm. It also
has an internal buzzer to indicate that it requires
attention.
It comes supplied with an interface card to connect to
the Premier SX and Premier Elite (4-8 zone) panels.

73mm

100mm

Features
Zonal indication for fire
Common fault indication
Surface or semi flush fixing

Flush Mount

Model

PRE-REP

Part No.

37-045

Supply Voltage

2035V DC

Supply Voltage

29V DC (nominal)

Connections

10

Wall Mount

A+

Supply +VE

0V

Supply VE

GA

General Alarm

CF-

Common Fault

TN-

Tone (Buzzer Active)

Z1- to Z8-

Zonal Alarm

Operating Temperature

-0C to 50C

Enclosure Size

355 x 275 x 100mm

Weight

1kg

Conventional Fire Alarm Systems /

Premier M Plus 8-24 Zone Conventional Fire


Alarm Panel (PMP8, PMP16, PMP24)
The Premier M Plus control panels are designed
to fulfil the requirements of EN54 parts 2 & 4
as well as being easy to install, operate and
maintain.
Being of modular construction, the basic M Plus panel
has 8 zone capacity, expandable to 16, 20 and 24 zones.
The Premier M Plus is suitable for surface mounting or
semi-flush fitting (with just the door protruding).

Features
4 Common sounder circuits (150mA each)
Optional add-on zonal sounder circuits (50mA
Max.)
Serial repeater output
Auxiliary supply (29 Volts, 250mA)
Zone & sounder disablement facility
Sounder delay facility
Zonal to common timer (when fitted with zonal
sounder boards)
One man test mode

Model

PMP8

PMP16

PMP24

Part No.

37-020

37-022

37-024

Detection Zones

16

24

Mains Voltage

230V AC +10% / -15% @ 50/60 Hz

System Voltage

24V DC (nominal)

Zone Voltage

21V DC

Sounder Alarm Output

4 x 150mA @ 24V DC

Fault Relay Output

1 x relay SELV @ 1A maximum

Fire Relay Output

1 x relay SELV @ 1A maximum

Zone Capacity

32 Devices

Remote Sounder Activation

N/A

Sounder Activation Delay

0 9 minutes in 1 minute increments

Zone End Of Line

IN4002 Diode

Sounder End Of Line

10K Resistor

Charger Voltage

28.4V DC (batteries disconnected)

Zone Short Circuit Protection

100mA

Charger Short Circuit Protection

Batteries less than 20V

Charger Size

3.0 Amp

Operating Temperature

0C - 50C

Enclosure Size

485 x 477.5 x 125mm

11

Conventional Fire Alarm Systems /

Premier M Plus Repeater Panel


(PMP-REP, PMP-REP/M)

The Premier M Plus repeater is available in 2


versions standard & multiple.
The standard repeater offers display & control
functions, however it is limited to one per system.
The second version allows multiple repeaters on the
same system however they do not have any control
functions (i.e. they cannot be used to silence or reset
the system).
A single repeater can be powered from the panels
auxiliary 24V supply. If more than one repeater is to be
used, a separate 24V is required.

Model

PMP-REP

PMP-REP/M

Part No.

37-026

37-027

Functions

Display & control

Control only

Supply Voltage

20-30V DC

Max. Quantity Per System

1
Serial Repeater A

Connections

Serial Repeater B
+24V DC
0V

12

Operating Temperature

0C to 50C

Enclosure Size

375 x 335 x 125mm

Weight

TBC

Conventional Fire Alarm Systems /

Premier 48 M Plus 24-48 Zone Conventional


Fire Alarm Panel (PMP48/24, PMP48/32, PMP48/40, PMP48/48)
The Premier 48 M Plus control panels are designed to
fulfil the requirements of EN54 parts 2 & 4 as well as
being easy to install, operate & maintain.
Being of modular design, the basic panel has 24 zones
built in and it can be expanded to 32, 40 & 48 zones.
The construction of the panel is epoxy painted steel
enclosure, with top & rear cable entries.

Features
4 common sounder circuits (400mA each)
Optional add-on zonal sounder circuits (50mA
Max)
Serial repeater output
Auxiliary supply (29 Volts, 250mA)
Zone & sounder disablement facility
Sounder delay facility
Zonal to common timer (when fitted with zonal
sounder boards)
One man test mode
Model

PMP48/24

PMP48/32

PMP48/40

PMP48/48

Part No.

37-030

37-032

37-034

37-036

32

40

48

Detection Zones

24

Supply Voltage

230V AC +10%/-15% @ 50/60 Hz

System Voltage

29V DC (nominal)

Zone Voltage

21V DC

Sounder Alarm Output

4 X 400mA @ 24V DC

Fault Relay Output

1 relay SELV @ 1A (normally energised)

Fire Relay Output

1 relay SELV @ 1A maximum

Other Connections

Class Change Input (N/O Contact) / F.A.R.E. Output / Serial Repeater Output (4 Wire)

Zone Capacity

Up to 32 devices

Remote Sounder Activation

N/A

Sounder Activation Delay

0 to 9 minutes

Zone End Of Line

100F capacitor

Sounder End Of Line

10K resistor

Charger Voltage

28.4V DC (Batteries disconnected)

Zone Short Circuit Protection

100mA

Charger Short Circuit Protection

Batteries less than 20V

Charger Size

3 Amp

IP Rating

IP43

Operating Temperature

0C to 50C

Enclosure Size

675 x 480 x 135mm

Weight

13kg

13

Conventional Fire Alarm Systems /

Premier 48 M Plus Repeater Panel


(PMP48-REP, PMP48-REP/M)

The Premier 48 M Plus repeater is available in


2 versions standard & multiple.
The standard repeater offers display & control
functions, however is limited to one per system.
The second version allows multiple repeaters on the
same system however they do not have any control
functions (i.e. they cannot be used to silence or reset
the system).
A single repeater can be powered from the panels
auxiliary 24V supply. If more than one repeater is to be
used, a separate 24V is required.

Model

PMP48-REP

PMP48-REP/M

Part No.

37-037

37-038

Functions

Display & control

Control only

Supply Voltage

2030V DC

Maximum Quantity Per System

1
Serial Repeater A

Connections

Serial Repeater A
+24V DC
0V

14

Operating Temperature

0C to 50C

Enclosure Size

480 x 330 x 60mm

Weight

4.8kg

Conventional Fire Alarm Systems /

Premier MX Conventional Fire Alarm Panel


(MX-16 & MX-32)

The Premier MX ranges of panels are available


in either 16 or 32 zone versions and have been
approved by LPCB to EN54 parts 2 & 4.
The panels offer an extensive range of configuration
options whilst remaining easy to install and configure.

Model

MX-16

MX-32

Part No.

37-140

37-142

Detection Zones

16

32

Supply Voltage

230V AC +/- 10%

Zonal one-man test facility

System Voltage

24V DC (Nominal)

Zone Voltage

24V DC (Nominal) Relay, SELV @ 1A

Latching or non-latching zones

Zone End of Line

22uF, 35V Axial Capacitor

Sounder Output

4 X 1.0A @ 24V DC

Sounder EOL

3K9 Resistor

Aux DC Output

24V DC (Nominal) 1A

Repeater option

Yes
Remote
Evacuation
Remote Silence
Alarms

Panel Inputs

Remote Reset
Class Change
Panel Outputs
Fault Routing
Relay, SELV @ 1A
Fire Routing
Relay, SELV @ 1A

Features
LPCB Approved to EN54 parts 2 & 4

Delayed or non delayed zone operation


Standard or intrinsically safe zone mode
Short circuit to fire mode for compatibility with
old detectors

Fire Protection Relay,


SELV @ 1A
Disablement Active
(Open Collector
Output)
Evacuation Active
(Open Collector
Output)
Buzzer Active (Open
Collector Output)

Zonal or common alarm operation (requires


output expansion PCBs)
Latching or non-latching fault modes
Fault routing, fire routing & fire protection
relays can be programmed as 24V output
(monitored) or volt free
Fault routing, fire routing & fire protection
relays can have delayed operation in any
configuration
The panel is available as flush mount on request
Repeater panel option (up to 5 maximum per
panel)

RS 485 Repeater
Connection

Operating
Temperature

-5C to 40C

Size

325 x 370 x 126mm 400 x 441 x 131mm

Weight

7.05kg

9.35kg

15

Conventional Fire Alarm Systems /

Fyreye Extra Conventional


Optical Smoke Detector (FEOE2000)
The Fyreye Extra optical smoke detector uses
a pulsing IR LED & photodiode to detect IR
scatter caused by smoke entering the chamber.
The detector is particularly suitable for detecting
optically dense smoke, involving materials such as soft
furnishings, PVC, plastic, foam and all similar materials
which produce small visible particles (0.5 to 10m).
The detector will work with most modern fire alarm
control panels and comes supplied with a locking grub
screw to prevent unauthorised head removal.
The Fyreye Extra range of detectors has an extra LED to
improve detector identification in an alarm condition.

100mm

37mm

Features
Designed to meet EN54 requirements
Attractive design
Dual LEDs for 360 visibility
Lockable base to stop unauthorised removal
Compatible with all Fyreye bases

16

Model

FEOE2000

Part No.

80-022

Detector Class

Optical Smoke

Design Standard

EN54 part 7

Approval

DIFT

Operating Voltage

9-33V DC

Quiescent Current

65A

Alarm Current @ 24V DC

53mA MAX

Operating Temperature

-10C to +50C

Minimum Continuous Temperature

0C

Maximum Humidity

95% RH non-condensing

Alarm Condition

2.4% obscuration per metre

Coverage

100m2

IP Rating

IP43

Start-up Time

10 Seconds

Size (with Base)

100 x 37mm (101 x 53mm)

Weight (with Base)

95g (153g)

Conventional Fire Alarm Systems /

Fyreye Extra Conventional Rate of Rise and


Fixed Heat Detectors (FEHE2000 & FEFHE2000)
The Fyreye Rate of Rise heat detector
(FEHE2000) uses a thermistor arrangement
to sense a quick rise in temperature and also
a final threshold temperature of 57C. The
Fyreye fixed heat detector (FEFHE2000) has a
single thermistor arrangement that gives an
alarm at a temperature of 90C.
The detectors will work with most modern fire alarm
control panels and comes supplied with a locking grub
screw to prevent unauthorised head removal.
The Fyreye Extra range of detectors has an extra LED to
improve detector identification in an alarm condition.

100mm

48mm

Features
Designed to meet EN54 requirement
Lockable to base to stop unauthorised removal
Remote LED output
Dual LEDs for 360 visibility
Compatible with all Fyreye bases

Model

FEHE2000

FEFHE2000

Part No.

80-038

80-039

Detector Class

Rate of Rise & Fixed Heat Detector

Fixed Heat Only

Design Standard

EN54 part 5

Approval

DIFT

Operating Voltage

9-33V DC

Quiescent Current

40A

Alarm Current @ 24V DC

34mA

Operating Temperature

-10C to +50C

Minimum Continuous Temperature

0C

Maximum Humidity

95% RH non-condensing

Alarm Condition

Rate of rise or fixed heat trigger @ 57C

Coverage

50m

IP Rating

IP43

Start-up Time

10 Seconds

Size (with Base)

100 x 48 mm (101 x 64 mm)

Weight (with Base)

75g (133g)

Fixed heat trigger @90C

17

Conventional Fire Alarm Systems /

Fyreye Extra Conventional


Opto-Heat Detector (FEOH2000)
The Fyreye Extra opto-heat detector
incorporates both an optical chamber and
heat sensing element with advanced detection
technology & discrimination algorithms. This
multisensor is the perfect replacement for
ionisation detectors.
The detector will work with most modern fire alarm
control panels and comes supplied with a locking grub
screw to prevent unauthorised head removal.
The Fyreye Extra range of detectors has an extra LED to
improve detector identification in an alarm condition.

Features
100mm

50mm

Advanced electronic technology used to


minimise false alarms
Designed to meet EN54 requirement
Built-in 10 seconds alarm verification
Lockable to base to stop unauthorised removal
Remote LED output
Dual LEDs for 360 visibility
Compatible with all Fyreye bases

18

Model

FEOH2000

Part No.

80-025

Detector Class

Optical / Heat

Design Standard

EN54

Approval

DIFT

Operating Voltage

17-20V DC

Quiescent Current

100A

Alarm Current @ 24V DC

70mA MAX

Operating Temperature

-20C to +60C

Minimum Continuous Temperature

0C

Maximum Humidity

95% RH non-condensing

Alarm Condition

3% obscuration per metre

Coverage

100m

IP Rating

IP43

Start-up Time

10 Seconds

Size (with Base)

100 x 50mm (100 x 66mm)

Weight (with Base)

95g (153g)

Conventional Fire Alarm Systems /

Fyreye Conventional
Ultra-Violet Flame Detector

(FEUV2000)

The Fyreye ultra-violet flam detector is


particularly suited to applications where
flames can be expected to develop initially
rather than smoke. This is typically due to the
nature of the materials being protected for
instance camera film, computer, audio & video
tapes or disks.
The detector is for indoor use only and should not
be exposed to spurious sources of UV, such as sparks,
uncovered halogen lights, lightening, etc. as these may
trigger a false alarm.
Due to the operational nature of flame detectors it is
generally recommended to fit just one detector per
zone.

Features

0
30

30

60

60

90

90
ANODE
CATHODE

UV EMISSION
POINT

0
30

Low profile shape

VERTICAL VIEWING
(top fig.)

The detector is solar blind and incorporates an


electronic filter to eliminate unwanted alarms
from naturally occurring phenomena

HORIZONTAL
VIEWING
(bottom fig.)

Fast response time

30

60

High immunity to electrical noise & RF


interference

60

90

90
ANODE
CATHODE

Horizontal & Vertical Detector Field Of View

Model

FEUV2000

Part No.

80-045

Detector Class

Ultra Violet Flame Detector

Operating Voltage

12-28V DC

Quiescent Current

320A

Alarm Current @ 24V DC

45-50mA

Operating Temperature

0C to 45C

Minimum Continuous Temperature

0C

Maximum Humidity

95% RH non-condensing

Alarm Condition

10 seconds for 30mm flame @ 4 metres

Detection Angle

120

UV Sensitivity

185-260nm

Size (with Base)

98 x 36mm (98 x 52mm)

Weight (with Base)

85g (143g)

19

Conventional Fire Alarm Systems /

Fyreye Conventional Detector Bases


(FE-CB, FE-DB, FE-RB)

FE-CB

FE-CB/S

There are 3 types of base available


for the Fyreye conventional range
of detectors namely common base,
diode base and relay base.
The Fyreye common base and diode
base are available in standard,
shallow or deep versions.
The common base is used on systems
that do not need to keep line
integrity on head removal and also
on addressable systems.

Model

20

FE-CB/D

The diode base is used on systems


that do need line integrity on
head removal. This would include
all conventional systems that mix
detectors & call points on the same
line (please note that the Premier M
Plus panels will need an active end
of line to work with diode bases).
The relay base is mainly used on 12V
security systems to signal detector
operation to the panel. They can

FE-CB

FE-CB/S

FE-CB/D

80-050S

80-050D

FE-RB

FE-DB

also be used on 24V fire systems


where the activation of a particular
detector requires a signal to nearby
equipment (for instance door
holders).
Please note that a remote led
indicator cannot be used with a relay
base as the detector cannot sink
enough current to operate both.

FE-DB

FE-DB/S

FE-DB/D

FE-RB

80-052

80-052S

80-052D

80-054

Part No.

80-050

Type

Common base

Supply Voltage

9-33V DC

Quiescent Current @ 24V

0A

Alarm Current @ 24V

0mA

15mA

Relay Max Switching Power

N/A

30W, 50VA

Relay Max Switching Power

N/A

30W, 50VA

Diode base

Relay base
24V DC

Relay Max Switching Current N/A

1A resistive

Relay Max Switching Voltage N/A

50V AC

Relay Minimum Capability

N/A

10A, 10mV

Relay Dropout Voltage

N/A

<6V

Operating Temperature

-20C to 90C (non-condensing or icing)

Max. Wind Speed

Not affected

Connections

L1in, L1out, L2, -R & Earth

Size

100 x 15mm 100 x 8mm

100 x 25mm 100 x 15mm 100 x 8mm

100 x 25mm 100 x 15mm

Weight

48g

61g

61.2g

42g

48.2g

42.2g

171.4g

Conventional Fire Alarm Systems /

Zeta Remote LED Indicator


(ZT-RL)

Remote LEDs indicators are used in


installations where a detector going to alarm is
likely to occur out of sight (for instance behind
a locked door or in a ceiling void). In these
instances the indicator will then show the
location of the alarm.

Features
Twin LEDs
Surface or flush mounting

Model

ZT-RL

Part No.

48-023

Input Voltage

5 30vdc

Quiescent Current

0mA

Alarm Current

12mA

Operating Temperature

0C - 50C

Max Humidity

95% Relative Humidity Non-condensing

IP Rating

IP41

Size

85 x 85 x 70mm

Weight

113g

21

Conventional Fire Alarm Systems /

Fyreye 50 & 100m Reflective Beam


Smoke Detector (ZT-50RZ, ZT-100RZ, ZT-50RV & ZT-100RV)

The Fyreye reflective beam detectors comprise


of a single unit incorporating an infrared
transmitter & receiver. The signal is reflected
by a prism and analysed for smoke presence.
Should a predetermined level be reached then
the detector will signal an alarm.
The system is designed to be mounted so that the beam
will project between 0.3 and 0.6 metres below the
ceiling and parallel to it. Lateral detection may be up to
7.5 metres either side of the beam.

Features

70mm
126mm

120mm

50 or 100 metre reflective beam smoke detector


VdS approved
BS 5839 part 5

100mm
100mm

140mm
210mm

Complies fully to;


EN54 part 12
Single compact housing
Horizontal or vertical mounting
12-24V DC operation
9.5mm

Low current consumption


Latching or non latching alarm
Reflector targeting mode to ease set-up
Microprocessor controlled
Automatic contamination compensation
Selectable sensitivity
Robust construction

22

The Fyreye beam detectors are available with ranges of up to 50 or 100 metres and either 2 or 4
wire connections.

The 2 wire models (ZT-50RZ & ZT-100RZ)


are zone powered (please note these will
only work on Premier SX & M Plus panels).

The 4 wire models (ZT-50RV & ZT-100RV)


require an external 24V power supply and
have a fire & fault relay output for wide
compatibility.

Typical Applications
Beam detectors are generally used for two purposes; either to cover a wide-open space and/or in places where
several regular smoke detectors would be aesthetically unacceptable.
Such places include;
Shopping centres

Open Plan offices

Heritage sites

Warehouses

Churches or mosques

Factories

Museums

Power stations

Leisure centres

and more

Model

ZT-50RZ

ZT-100RZ

ZT-50RV

ZT-100RV

Part No.

47-050

47-051

47-050A

47-051A

50-100m

5-50m

50-100m

Range

5-50m

Number of Wires

Supply Voltage

10.2V to 30V DC

Quiescent Current

<4mA

Operating Temperature

-30C to 55C

Max Humidity

95% RH non-condensing

Max Wind Speed

Not affected

Alarm Current

35mA (typical)

<15mA

Fire Output

470 OHM resistor placed across zone internally

Fire relay closing (relay contact is normally


open)

Fault Output

Schottky diode introduced between VE in &


-VE out

Fault relay opening (relay contact is normally


closed)

Power Down Reset

<2 seconds

>5 seconds

Beam Misalignment Tolerance Detector 0.8


at 35%
Prism 5.0
Alarm Thresholds

2.50dB (25%), 3.74dB (35%), 6.02dB (50%)

Optical Wavelength

880nm

Construction

Flame Retardant ABS (Grey /Black)

IP Rating

IP50

Size

130 x 210 x 120mm

Weight

0.75kg

0.7kg

23

Conventional Fire Alarm Systems /

Fyreye 50 & 100m Auto-aligning Beam Smoke


Detector Systems 50 & 100m (ZT-5000R & ZT-5000R/100)

Based on the proven technology of the


standard Fyreye reflective beam detectors, the
Fyreye auto-aligning beam detector has been
designed to help improve ease of installation.
The system is ideally suited for the protection of
large areas where the use of traditional detection
technologies would prove to be too difficult and/or
costly to install.
The system combines an infrared transmitter and
receiver in the same discrete unit and operates by
projecting a well-defined beam to a reflective prism,
which returns the beam to the receiver for analysis.
Smoke in the beam path causes a drop in power, which,
if below a pre-determined level, results in an alarm
signal.

The system consists of 2 parts; the beam detector itself


and a low level control unit.
The system can be fully customised, according to local
conditions and installation guidelines; alarm thresholds
(sensitivity) and time to alarm/fault can be set from the
low level system controller.
Each detector head is independently configurable from
8m through to 100m and has its own individual fire
threshold. The system controller retains one set of fire
and fault relays that is common to all detectors that are
installed.
The system is supplied as either a 50 or 100 metre
version with a single detector head. Additional heads
and a long range kit (additional prisms to allow the
detector head to reach 100m) are available separately.

Additional System Components


ZT-5000R/DH - 47-072 - Fyreye Auto-aligning Single
Beam Detector Head 50m
ZT-5000R/100/DH - 47-073 - Fyreye Auto-aligning
Single Beam Detector Head 100m
ZT-5000R/LRK - 47-074 - Fyreye Auto-aligning Beam
Detector Long Range Kit

24

Features
Worldwide approvals including EN54:12 and
UL268
Up to 4 detectors per system controller
Each detector configurable from 8m to 100m
Integral LASER
Auto-align fast automatic beam alignment
Auto-optimise building movement and
contamination compensation
Low level system controller
20mm cable gland knockouts on system
controller
2-wire interface from system controller to
detector

202mm
135mm

81mm

135mm

230mm

135mm

Model

ZT-5000R

ZT-5000R/100

Part No.

47-070

47-071

Range

50m

100m

Number of Wires

Supply Voltage

14-28V DC

Operating Current

8-12mA (low current mode with 1 detector)


48-52mA (high current mode with 1-4 detectors)

Operating Temperature

-20C to 55C

Storage Temperature

-40C to 85C

Max Humidity

85% RH non-condensing

Max Wind Speed

Not affected

Alarm Current

35mA (typical)

Fire Output

Volt free relay contact

Fault Output

Volt free relay contact

Beam Misalignment Tolerance @ 35%

Detector 0.8, Prism 5.0

Alarm Thresholds

2.50dB (25%), 3.74dB (35%) & 6.02dB (50%)

Optical Wavelengths

850nm

Construction

Flame Retardant ABS (Grey / Black)

IP Rating

IP54

Detector Size

135 x 135 x 135mm

Detector Weight

0.5kg

Controller Size

202 x 230 x 81mm

Controller Weight

0.9kg

25

Conventional Fire Alarm Systems /

Zeta UV/IR Optical Flame Detectors


(VS-200P & VS-200EX)

VS-200P

VS-200EX

The VS-200P & VS-200EX UV/IR flame detectors


detect fuel & gas fires at long distances with
the highest immunity to false alarms. The
detectors can detect a 0.1m gasoline pan fire
at 30m in less than 5 seconds.

Typical
Applications
Non-hazardous (VS-200P)
Parking buildings
Warehouse
Waste disposal facilities
Culture centres

Hazardous (VS-200EX)
Offshore oil & gas
installations
Onshore oil & gas
installations and
pipelines
Petrochemical plants
Chemical plants
Shipbuilding facility
Automotive industry
Storage tank farms
Power generation
facility
Petrochemical plants
Painting industry
Warehouse
Waste disposal facility
Explosive & munitions

26

Features
UV/IR spectrum for medium distance detection
and high false alarm immunity
Compact & lighter design
User selectable sensitivity & functions
Multiple output options (relays for alarm & fault,
0-20mA (stepped) and RS-485/RS-232 spectrum
monitoring)
ATEX approved by DNV for explosion-proof (VS200EX UV/IR only)
CE certified

Model

VS-200P

VS-200EX

Part No.

47-150

47-151

Spectrum Response

UV /IR (Dual Bands)

Spectrum Response
(at highest sensitivity setting
for 0.1m pan fire)

Fuel
n-Heptane
Gasoline
Diesel
LPG*

Distance
30m
30m
20m
20m

Fuel
Ethanol
IPA
Methanol

Distance
20m
25m
20m

*0.5m high / 0.2m width plume fire


Response Time

Typically 5 seconds

Adjustable Time Delay

Up to 20 seconds

Sensitivity Range

4 sensitivity ranges for 0.1m n-Heptane pan fire from 15m to 65m

Field of View

Horizontal 90, Vertical 90

Built-in-Test

Manual (optionally Automatic)

Temperature Range

Operating/Storage: -40C to 75C

Humidity

Up to 95% non-condensing

Operating Voltage

24VDC norminal (17-31VDC)

Power Consumption

Standby: max. 35mA, Alarm: max. 75mA

Cable Entry

1 x M20 (ISO)

Wiring

AWG 16-26 (Str 1.5mm to 0.13mm)

Electromagnetic Compatibility

EMI/RFI protected to EN61000 series

Electrical Interface

The detector includes twelve(12) terminals with four(4) wiring options

Relays

Alarm, Fault. SPST volt-free contacts rated 5A at 30VDC or 250VAC


Non-isolated Source configuration

0-20mA (stepped)

Fault:
Normal:
Alarm:

Materials

Polycarbonate Enclosure

0 +1mA
4mA10%
20mA10%

Bit Fault:
Warning:
Resistance
Loop:

2mA10%
16mA10%
Max. 800

Heavy duty copper free aluminium (less than 1%) with bright grey
anodizing finish
Enclosure options - Stainless Steel 316L with electro polish finish

Mounting (Tilt Mount)

Stainless Steel

Heavy duty copper free aluminium (less than 1%) with grey epoxy
enamel finish
Options - Stainless Steel 316L with electro polish finish

Dimensions

Detector: 80 x 82 X 86
mm

Weight

Detector : 0.3kg (1.0kg


with cable gland /
1m-length cable / Tilt
Mount)

Water and Dust

IP66 per EN60529

EMI/RFI

CE Marking

Performance

EN54-10 (designed to
meet)

Detector: 83(d) x 126(l) mm


Detector (aluminium): 1.1 kg (1.4 kg with Ex cable gland /
1m-length
Detector (St. SUS316L): 2.0 kg
Tilt mount (aluminium/ St.): 0.3kg / 0.7kg
IP66 and IP67 per EN60529
ATEX Ex II 2 G
Exd IIC T6, -40C to +75C (DNV 09 ATEX 0000)
KFI (Korea)
EN54-10 (designed to meet)

27

Conventional Fire Alarm Systems /

Zeta Conventional Manual Call Points


(ZT-CP2, ZT-CP2/W, ZT-CP1 & ZT-CP1/W)

The Zeta conventional manual call point has


a modern design and has been approved by
BSI to EN54 part 11. It is a resettable call
point that signals an alarm with a yellow flag
entering the window area and a red alarm LED.
There are two versions available; the ZT-CP2 call points
comes complete with a protective Perspex cover as
well as a snaplatch catch that needs to be broken off
before the call point cover can be lifted (this acts as a
deterrent to malicious activations and forms a Type B
call point). Alternatively the ZT-CP1 is supplied without
the Perspex cover & snaplatch and is single action or
Type A call point.
The recommended colour for these call points is red
however white is also available to meet architectural
requirements.

Features
BSI approved to EN54 part 11
Attractive design

28

Model

ZT-CP2

ZT-CP2/W

ZT-CP1

ZT-CP1/W

Part No.

43-300

43-314

43-301

43-317

Type

Type B

Element Type

Resettable

Alarm Activation

Break snaplatch, lift Perspex cover, press


element

Press element
Red

Type A

Colour

Red

Input Voltage

9-33V DC

White

Quiescent Current

0mA

Alarm Current

Typical 35mA (maximum 51mA)

Alarm Load

470 resistor

Operating Temperature

-20C to 50C

Max Humidity

95% RH non-condensing

IP Rating

IP43

Size

111 x 100 x 67mm

105 x 100 x 58mm

Weight

198g

175g

White

Conventional Fire Alarm Systems /

Zeta Conventional Weatherproof Call Point


(ZT-CP2/WP)

The Zeta conventional weatherproof manual


call point is an IP65 rated call point which
complies with EN54 part 11. It is resettable
and signals an alarm with a yellow flag
entering the window area and a red alarm LED.
The call point comes complete with a protective Perspex
cover as well as a snaplatch catch that needs to be
broken off before the call point cover can be lifted (this
acts as a deterrent to malicious activations and forms a
Type B call point).

Features
Complies with EN54 part 11
Attractive design
Resettable element
Protective cover

Model

ZT-CP2/WP

Part No.

43-350

Type

Type B

Element Type

Resettable

Alarm Activation

Break snaplatch, lift Perspex cover, press element

Colour

Red

Input Voltage

9-33V DC

Quiescent Current

0mA

Alarm Current

Typical 35mA (maximum 51mA)

Alarm Load

470 resistor

Operating Temperature

-20C to 50C

Max Humidity

95% RH non-condensing

IP Rating

IP65

Size

87 x 87 x 70mm

Weight

198g

29

Conventional Fire Alarm Systems /

Zeta Conventional Explosion Proof


Manual Call Point (ZT-BGU/WP/R & ZT-BGU/WP)

The Zeta conventional explosion proof manual


call point is manufactured from aluminium
with a built-in push button activator. The call
point is finished with red anti-corrosive epoxy
powder coating with 2 x 20mm cable entries.
This unit is equipped with a stainless steel
hammer and chain.
Two models are available; the ZT-BGU/WP/R with 470
built-in resistor for connection to a standard fire alarm
system or the ZTBGU/WP for mains connection.

4 Holes - 7

CASE O
FIRE
S

BR

AK

GL

105mm

2 Nos.0.75ET

30

Hammer
S

185mm

Chain

Model

ZT-BGU/WP/R

ZT-BGU/WP

Part No.

43-300/WP

43-305/WP

Contact Rating

10 Amp

Voltage Rating

500V AV

Build-in Resistor

470

IP Rating

IP65

Earthling

2No M6 eternal & 1No M5 internal

Size

TBC

Weight

1.5kg

N/A

Conventional Fire Alarm Systems /

Miditone Conventional Electronic Sounder


(ZMDD/8R & ZMDD/8W)

The Miditone sounder is a small, high output


conventional sounder which designed to meet
the requirements of EN54 part 3 and is CE
marked.
The sounder is a compact unit that fits a standard
European back box and can be either surface or flush
mounted. It has a choice of 8 tone patterns, selectable
by an internal dip switch and a sound output of 95dB @
1m with volume control.
It is available in red or white to meet architectural
requirements.

Features
Complies to EN54 part 3
95dB @ 1m sound output
8 Tone patterns
Flush or surface fixing

Model

ZMDD/8R

ZMDD/8W

Part No.

42-040

42-040A

Sound Output

See current consumption table

Colour

Red

Operating Voltage

9-30V DC

Quiescent Current

0mA

Alarm Current @ 24V

See current consumption table

Operating Temperature

-10C to 50C

Minimum Continuous Temperature

0C

Maximum Humidity

95% RH Non Condensing

IP Rating

IP43

Size (with Back Box)

85 x 85 x 35mm (85 x 85 x 67mm)

Weight (with Back Box)

100g (150g)

White

DIL Switch Settings (SW4 N/A)


1

Tone Description

dB Level

Current (mA)

Off

Off

Off

Sweep Negative 1200- 500 Hz In 1 Second

97 (+/- 2dB)

21

On

Off

Off

Alternating 554 and 440Hz 0.5s Each

95 (+/- 2dB)

17

Off

On

Off

Continuous 660Hz

96 (+/- 2dB)

22

On

On

Off

Alternating 554Hz @ 0.1s/440Hz @ 0.4s

94 (+/- 2dB)

17

Off

Off

On

Intermittent 970Hz @ 0.5s On/Off

93 (+/- 2dB)

8-24

On

Off

On

Continuous 970Hz

95 (+/- 2dB)

25.5

Off

On

On

Sweep Positive 800-970Hz

99 (+/- 2dB)

25

On

On

On

Alternating 800 and 970Hz @ 0.25s Each

100 (+/- 2dB)

25

31

Conventional Fire Alarm Systems /

Miditone Conventional Combined Electronic


Sounder & Flasher (ZMDF/8R, ZMDF/8A, ZMDF/8B, ZMDF/8C & ZMDF/8G)
The Miditone combined sounder & flasher is a small, high
output conventional sounder & flasher which is designed
to meet the requirements of EN54 part 3 and is CE
marked.
The device is a compact unit that fits a standard
European back box and can be either surface or flush
mounted. It has a choice of 8 tone patterns, selectable
by an internal dip switch and a sound output of 95dB
@ 1m with volume control. This is an ideal solution to
upgrade an existing sounder to a combined sounder &
flasher.
It is available with either a red, amber, blue, clear or
green lens to meet architectural requirements.

Features
Complies to EN54 part 3
95dB @ 1m sound output
8 tone patterns
Flush or surface fixing
Model

ZMDF/8R

ZMDF/8A

ZMDF/8B

ZMDF/8C

ZMDF/8G

Part No.

42-024

42-024A

42-024B

42-02C

42-024G

Sound Output

See current consumption table

Lens Colour

Red

Blue

Clear

Green

Operating Voltage

17-30V DC

Quiescent Current

0mA

Alarm Current @ 24V

See current consumption table

Operating Temperature

-10C to 50C

Minimum Continuous Temperature

0C

Maximum Humidity

95% RH non condensing

IP Rating

IP43

Size (with Back Box)

85 x 85 x 35mm (85 x 85 x 67mm)

Weight (with Back Box)

112g (162g)

Amber

DIL Switch Settings (SW4 N/A)

32

Tone Description

dB LEVEL

CURRENT (mA)

Off

Off

Off

Sweep Negative 1200- 500 Hz In 1 Second

102 (+/- 2dB)

35

On

Off

Off

Alternating 554 and 440Hz 0.5s Each

100 (+/- 2dB)

27

Off

On

Off

Continuous 660Hz

100 (+/- 2dB)

33

On

On

Off

Alternating 554Hz @ 0.1s/440Hz @ 0.4s

98 (+/- 2dB)

26

Off

Off

On

Intermittent 970Hz @ 0.5s On/Off

93 (+/- 2dB)

13 - 35

On

Off

On

Continuous 970Hz

103 (+/- 2dB)

37

Off

On

On

Sweep Positive 800-970Hz

103 (+/- 2dB)

45

On

On

On

Alternating 800 and 970Hz @ 0.25s Each

103 (+/- 2dB)

42

Conventional Fire Alarm Systems /

Securetone Conventional Electronic Sounder


(ZST/8R & ZST/8W)

The Securetone sounder is designed to be


aesthetically pleasing and unobtrusive. It has
an elegant round design and fits to its supplied
mounting plate with a bayonet action to avoid
unsightly screws.
It has 8 selectable tones with a volume adjust screw to
set the required sound level.
This product is designed to meet the requirements of
EN54 part 3 and is CE marked.

Features
85mm

8 selectable tones
Volume control

100mm

Model

ZST/8R

ZST/8W

Part No.

42-004

42-004A

Sound Output

100dBA @ 1 metre

Colour

Red

Operating Voltage

10-30V DC

Quiescent Current

0mA

Alarm Current @ 24V

35mA MAX

Operating Temperature

-0C to 50C

Minimum Continuous Temperature

0C

Maximum Humidity

95% RH Non Condensing

IP Rating

IP43

Size (including Plate)

100 x 100 x 75mm (100 x 100 x 85mm)

Weight (including Plate)

230g (260g)

White

33

Conventional Fire Alarm Systems /

Secure Light Xenon Flasher


(ZTSL6/R & ZTSL6/A)

The Secure Light Xenon Flasher range is


designed to provide a visual warning at alarm
condition.
Both red and amber versions are available with the
lenses constructed of high-Impact and heat resistant
ACRYREX. The case is made of high-impact resistant ABS
plastic.

Features

97mm

Available in Red & Amber


Fits onto a standard outlet box
100mm

34

Model

ZST/8R

ZST/8W

Part No.

42-035

42-038

Colour

Red

Amber

Flash Energy

3 Watt

Flash Frequency

60 times per minute

Operating Voltage

20-30V DC

Quiescent Current

0mA

Alarm Current @ 24V

100mA MAX

Operating Temperature

-30C to 60C

Minimum Continuous Temperature

0C

Maximum Humidity

95% RH Non Condensing

IP Rating

IP54

Size

97 x 100mm

Weight (including Plate)

231g

Conventional Fire Alarm Systems /

Maxitone Conventional Sounder and


Combined Sounder & Flasher (ZMT/8R, ZMT/8W & ZMTF/8R)
The Maxitone sounder is an ideal alternative
to fire bells and for external use. It is housed
in an attractive horn comprises of flame
retardant ABS. Eight selectable tones and
volume control are featured to meet most
requirements.
The Maxitone is also available with transparent
polycarbonate front which will provide both visual and
audible alarm.

Features

120mm

High output
8 selectable tones
Volume control
126mm

107mm

Model

ZMT/8R

ZMT/8W

ZMTF/8R

Part No.

42-001

42-001A

42-032

Sound Output

See current consumption table

Colour

Red

Operating Voltage

17-30V DC

Quiescent Current

DIL SWITCH SETTINGS (SW4 N/A)


1

Tone Description

dB Level

Current
(mA)

Off

Off

Off

Sweep Negative 1200500 Hz In 1 Second

101 (+/2dB)

27

0mA

On

Off

Off

Alternating 554 and


440Hz 0.5s Each

98 (+/2dB)

20

Alarm Current @
24V

See current consumption table

Off

On

Off

Continuous 660Hz

101 (+/2dB)

27

Operating
Temperature

-20C to 60C

On

On

Off

Alternating 554Hz @
0.1s/440Hz @ 0.4s

98 (+/2dB)

19

Minimum
Continuous
Temperature

0C

Off

Off

On

Intermittent 970Hz @
0.5s On/Off

98 (+/2dB)

20

On

Off

On

Continuous 970Hz

103 (+/2dB)

29.3

Off

On

On

Sweep Positive 800970Hz

103 (+/2dB)

38

On

On

On

Alternating 800 and


970Hz @ 0.25s Each

102 (+/2dB)

35

White

Maximum Humidity 95% RH non condensing


IP Rating

IP65

Size

124 x 130 x 100mm

Weight

357g

Red

35

Conventional Fire Alarm Systems /

Zeta Conventional Fire Alarm Bells


(ZTB6B, ZTB8B/230, ZTB8B & ZTB8B/WP)

ZTB8B

ZTB6B

55mm

152mm

152mm

The Zeta motorised fire alarm bells combine


styling and functional efficiency. They
incorporate a low power rotary centrifugal
mechanism, which gives a high sound output
with low current consumption at 24V dc.
The bells are available in 2 sizes; 6 (152mm) and 8
(203mm). These sizes suit a wide variety of installations.

55mm

203mm

203mm

There is a 230V ac version of the 6 bell, and a 24V dc


Weatherproof version of the 8 bell.

Features
Low current
Universally accepted fire evacuation signal

36

Model

ZTB6B

ZTB8B/230

ZTB8B

ZTB8B/WP

Part No.

41-003

41-004

41-005

41-006

Supply Voltage

18-30V dc

200-250V AC

Diameter

6 (152mm)

8 (203mm)

Quiescent Current

25mA

28mA

Nominal Output @ 1M

95dB(A)

97dB(A)

Dimensions

152 x 152 x 55mm

203 x 203 x 55mm

Weight

860g

960g

18-30V dc

1700g

1800g

Conventional Fire Alarm Systems /

Zeta Flame Proof Siren


(ZTSR/EXD24 & ZTSR/EXD230)

The Zeta flame proof siren is an explosion


proof siren available in either 24V or 230V
versions.
An intrinsically safe circuit is housed in the main
chamber and it is duly wired up to terminal chamber
through sealed bushes. The horn unit is placed on the
main chamber cover and the output signals are taken
through sealed coils. Neoprene 0 rings are provided for
the weather proof protection.

170mm

240mm

390mm

Model

ZTSR/EXD24

ZTSR EXD230

Part No.

42-100/24

42-105/230

Type Of Protection

Flame proof Exd T6 IP 65

Area Classification

Zone 1 & 2

Gas Groups

Group I, II A, II B, II C

Apparatus
Standard

IS - 2148

CMRI Certificate

CMRI / TC / S / H388

Approvals

CCE, DGFAS

Materials

Cast Aluminium LM 6

Weight

5 Kg (approx.)

Size

170 (w) x 390 (h) x 240 (d) mm

IP Protection

IP 65 to IS 13947 / 93

Finish

Anti corrosive Epoxy Powder Coated

Cable Entry

2 x ET

Gasket

Neoprene

Hardware

Stainless Steel

Terminals

4 x 2.5 sq. mm (standard) 6 x 2.5 sq.


mm (for looping)

Voltage

24 V DC

Output Current

600mA Peak. Galvanically Isolated

Power Rating

18 Watts

Sound Output

106 db 900 Hz On & Off alternatively


at 1C/s

Earthing

External: 2 Nos.
- M6

230 V AC 50 Hz

Internal: 1 No. M5

37

Conventional Fire Alarm Systems /

Zeta Flame Proof Gong Bell


(ZTB8B/EXD/24)

The Zeta flame proof gong bell is an explosion


proof gong bell with a terminal chamber.
A highly reliable electric circuit is housed inside to
control the frequency of the gong operating spindle.
The operating spindle and dish are made out of stainless
steel thereby ensuring a long life.
The electric circuits are connected to terminals in
the terminal chamber through nipple. The covers are
provided with neoprene gaskets for weatherproof
protection.

225mm

160mm

285mm

38

Model

ZTB8B/EXD

Part No.

41-075

Type Of Protection

Flame proof Exd T6 IP 65

Area Classification

Zone 1 & 2

Apparatus Standard

IS - 2148

Material

Cast Aluminium LM 6

Weight

3 Kg (approx.)

Size

225(w) x 285(h) x 160(d) mm

IP Protection

IP 65 to IS 13947 / 93

Finish

Anti Corrosive Epoxy


Powder coated

Cable Entry

1 X 3/4 ET

Gasket

Neoprene

Hardware

Stainless steel

Voltage

24V DC or 110V / 230V AC


50 Hz

Power Rating

12 Watt

Sound Output

112db

Terminals

4 x 4 mm

Earthing

External: 2 Nos M6 Internal:


1 No. - M5

Conventional Fire Alarm Systems /

Zeta Magnetic Door Holders


(ZT-DR24 & ZT-DR240)

ZT-BR

The Zeta magnetic door holders are designed


to retain a fire door open against the force of
its own closing device. In the event of a fire,
the door holder magnet can be turned off by
the fire alarm, allowing the door to shut.
The manual release button is changeable from the base
side to left or right. Cable entry is possible from rear
side by means of enclosed exits from the base side, left
or right.
An optional bracket is also available for floor or wall
mounting (ZT-BR).

Features
Tested according to EN1155

Model

ZT-DR24

ZT-DR240

Part No.

50-001

50-002

Rated Voltage

24V DC

230V AC

Rated Current

65mA

6mA

Switch Through Aux

Yes

No

Needs Back EMF Diode

Yes

No

Holding Force

400 N

Size (Main Unit)

110 x 85 x 38mm

Dimensions (Keeper Plate)

55 x 55 x 50mm

Weight (Main Unit)

404g

Weight (Keeper Plate)

153g

39

Conventional Fire Alarm Systems /

Zeta Duct Unit


(ZT-DU, ZT-DU/12 & ZT-DU/230)

The Zeta duct unit allows air in a ventilation


duct to be monitored for smoke via a smoke
detector mounted externally in a sealed
chamber. The unit comes supplied with 2
sampling probes (one in & one out) which are
mounted through the duct in the centre of the
air flow.

There are 3 versions of the unit


available which are as follows;
ZT-DU enclosure supplied with a Fyreye common base
(FE-CB) allowing either a conventional or addressable
Fyreye detector to be connected and wired as part a
system.
ZT-DU/12 enclosure c/w Fyeye base and relay board
with form C relay outputs for alarm and for fault which
requires 12V power supply.

Test Point

ZT-DU/230 - enclosure c/w Fyeye base and relay board


with form C relay outputs for alarm and for fault which
requires 230V power supply.
Duct Wall

Please note for reliable smoke detection the air speed in


the duct must be at least 2.5m/s.

Features
Direction of Airflow

Fire and Fault relays


Option for latching or non-latching
Manual reset (latching option)

Model

40

ZT-DU

ZT-DU/12

ZT-DU/230

Part No.

48-011A

48-011B

48-011C

Supply Voltage

N/A

12V

230V

Stand by current

N/A

46mA (From 12v supply)

Alarm current

N/A

86mA (From 12v supply)

Fault current

N/A

26mA (From 12v supply)

Indications

N/A

Power, fault & alarm


1 x fault relay & 1 x alarm relay

Outputs

N/A

Size

190 x 227 x 70mm

Weight

728g

989g

Conventional Fire Alarm Systems /

Premier Power Pack EN 54-4 Power Supply


with LCD Screen (PP-2/12, PP-5/17)
The Premier Power Pack Power supply uses an
innovative design that allows the engineer to
view system status through the on board LCD
screen. The screen can display several power
supply parameters, including output voltage,
and output current.
The power supply itself uses a 3 state charger which
uses BOOST, FLOAT, and PULSE modes, depending on the
state of the battery.
The PSU will disconnect the batteries under mains fail
condition, when the batteries are fully discharged to
prevent damage to the batteries.
The PSU will also monitor the battery for high internal
resistance, and signal a fault if that condition is
detected.

Screen Information

Model

System Normal Screen

Part No.

46-300

Input Voltage

170-264V AC 47-63 Hz

2 . 0 A

Output Voltage

28V DC Nominal

E R

R A T I N G

3 0 V

S Y S T E M

N O R M A L

D C

Screen 1 - Main Information


M A I N S

O K

B A T T S

O K

V ( A ) = 2 9 . 5
C U R R E N T

46-305

S Y S T E M S

A L A R M

P R E M I

PP-5/17

P O W E R - P A C K

Z E T A

PP-2/12

V ( B ) = 2 9 . 5

0 . 1 2

A M P S

28V DC Nominal

Power Rating

75W

150W

Efficiency

79%

86%

Total Power
Output

2.0 Amp

5.0 Amp

Power Supply
Outputs

2 Fused Outputs

2 Fused Outputs

Maximum Current
Per Output

0.625mA

2.0 Amps

B A T T E R Y

I M P : 0 . 0 0 3 7

Battery Charging
Current

750mA

920mA

C H A R G E R

V O L T : 2 5 . 4 5

Fault Relay Rating

SELV 1A

SELV 1A

B O O S T

IP Rating

IP30

IP30

S T A T E : G O O D

Size

375 x 335 x 128mm 375 x 403 x 128mm

Screen 2 - Battery Info

C H A R G E

T Y P E :

B A T T E R Y
Screen 3 - Misc.

E A R T H : 2 . 4 4 7 V
C H A R G E R
B A D

C I R C U I

B A T T E R Y

L V L

G O O D

T :

O K

X . X R

Screen 4 - Software Information

S o f

t w a r e

P S U :

2 V 0 0

S o f

t w a r e

L C D :

2 V 0 0

41

Conventional Fire Alarm Systems /

Batteries
(Z20201, Z20301, Z20651, Z21251 & Z21751)

As fire alarm systems are life safety systems,


they must have a battery backup to ensure full
functionality is maintained in the event of a
mains failure. All parts of the system (including
auxiliary power supplies) must have a battery
backup.
All the batteries stocked are 12V meaning that 2
batteries are required for a 24V systems. The standard
capacities available are 2.2Ah, 3.2Ah, 7Ah, 12Ah and
17Ah.
It is important to choose the correct battery size for the
system load to give the required standby time (usually
24 or 48 hours).

Battery Calculation
To calculate the required battery backup, we use the equation:Battery Size (Standby time in Amp Hours) = 1.25 x [(TALM x IALM) + (TSBY x ISBY)]
Where:
TALM = Maximum time in hours required for the alarm [ hour is most common time]
IALM = Total Alarm Current in amps for all alarm devices connected to the alarm
circuits
TSBY = Standby time in hours for the system after mains failure [normally 24, 48 or 72
hr]
ISBY = Quiescent current in amps of control panel in fault condition [because of mains
failure] PLUS all loop devices

42

Model

Z20201

Z20301

Z20651

Z21251

Z21751

Part No.

46-002

46-100

46-003

46-105

46-004

Type

Sealed lead acid

Voltage

12V DC

Capacity

2.2 Ah

3.2 Ah

7.2 Ah

12 Ah

17 Ah

Size

178 x 34 x 65mm

132 x 59 x 65mm

151 x 65 x 98mm

150 x 98 x 103mm

178 x 75 x 168mm

Weight

1.0kg

1.25kg

2.5kg

3.5kg

5.8kg

Available now from:

Tel: +44 (0) 1792 455 175


Fax: +44 (0) 1792 455 176
E-mail: info@zetaalarmsystems.com
Web: www.zetaalarmsystems.com

Detection House
72-78 Morfa Road
Swansea
SA1 2EN
United Kingdom