Vous êtes sur la page 1sur 10

achrnews.

com
served by

Google - view original

Enter The NEWS Dealer Design Awards Competition


The Dealer Design Awards recognize contractor-oriented products that aid in installation and service. Enter here.
MOST POPULAR
SUBSCRIBE NOW!

Most Popular Stories


Regional Standards Take Effect; DOE Considers Enforcement
Jan. 16, 2015: Bosch Acquires Climatec, Strengthening Its Energy and Building Technology Business
Jan. 8, 2015: Daikin Announces Expansion, Consolidation of Goodman Operations in Houston
Jan. 5, 2015: Home Automation and Control Market Worth $12.81 Billion by 2020
Jan. 19, 2015: The Number of Homes with Smart Thermostats Doubled in 2014
Most Emailed Stories
What's Your HVAC/Plumbing Business Worth?
Nov. 18, 2014: Price Increase Announced for Carrier, Bryant, Payne, and ICP Brands
Nov. 10, 2014: Lennox Industries Increases Prices
Illustrious AHR Expo Returns to the Midwest
Diagnosing A Restricted Liquid Line Can Be Tricky
Nov. 25, 2014: Rees Foundation Presents HVACR and Water Heating Scholarships
The Case Of The Water-Filled Ducts
More Delta Vs. Wye Transformers
A cure for the dreaded 'Dirty Sock Syndrome'?
EPA Finalizes R-22 Phaseout Plan
Recent Discussions
- HVAC Contractors Crack Down on Distracted Driving
- Sumner Manufacturing Co. Inc.: Gantry Lift
- Attaining a Green Building with Good Indoor Air Quality
- Attaining a Green Building with Good Indoor Air Quality
- Sumner Manufacturing Co. Inc.: Gantry Lift

Recent Searches
r22 units 2015 / coil cleanings / schwartz regional / compring motor technologies / price increase

Search Term(s)
FIND
ADVANCED

Submit

Understanding Superheat
June 3, 2004
2 Comments
Email / Print / Reprints /

More

/ Text Size+

Larger Smaller

[X]

Related Articles
A Better Understanding Of Superheat
Troubleshooting With Superheat, Subcooling
Tips for preventing superheat hunting in TXVs
Using the Superheat Method to Charge A/C Systems
Related Products
Understanding TXV Refrigeration Systems: Superheat and Subcooling DVD

Refrigeration and Air Conditioning Technology, 7th Edition


Related Events
Motors, Variable Speed Drives and Energy Efciency
Related Directories
Acme Engineering Products Ltd.
Sussman Electric Boilers

Superheat is probably the most talked about, yet misunderstood, technical term used by technicians.
Superheat is a measured value. It is the difference between two temperatures. Superheat is measured
as the difference between the actual temperature of the refrigerant vapor and the saturation
temperature of the refrigerant at that same point. Superheat on the system's low side can be divided
into two types: evaporator superheat and total (or compressor) superheat.

Evaporator Superheat

Evaporator superheat starts at the 100-percent saturated vapor point in the evaporator and ends at the
outlet of the evaporator. The 100-percent saturated vapor point is the point where all the liquid has just
turned to vapor. The temperature at this point can be obtained from a pressure-temperature chart.

Figure 1. A diagram of a basic refrigeration system.

The evaporator outlet is where the remote bulb of the thermostatic expansion valve (TXV) is located.
(See Figure 1.) Technicians usually put a thermistor or thermocouple at the evaporator outlet to get the
evaporator outlet temperature. A pressure gauge at the same point as the temperature reading will give
a technician the saturated vapor temperature. Most manufacturers of larger evaporators supply a
Schrader tting at the evaporator outlet pretty close to the remote bulb of the TXV for measuring
pressure. (See Figure 2.)

Figure 2. A Schrader tting at the evaporator outlet or the beginning of the suction line can be used for measuring pressure.

Example No. 1

Let's look at an R-134a refrigeration system. The low-side gauge reading at the evaporator outlet equals
20 psig or 23 degrees F. (See Table 1.) The evaporator outlet temperature (thermistor reading) equals
30 degrees.
The evaporator superheat calculation would be as follows: The evaporator outlet temperature (30
degrees) minus the saturation temperature at the evaporator (23 degrees) equals the evaporator
superheat (7 degrees).

Errors To Avoid

If a technician were to measure the pressure at the compressor instead of the evaporator outlet, a
higher and ctitious superheat value would be read. As the refrigerant travels the length of the suction
line, there would be associated pressure drop from friction and/or restrictions. This would cause the
pressure at the compressor to be lower than the pressure at the evaporator outlet.
This higher, ctitious superheat reading may lead the technician to adjust the TXV stem clockwise
(open) to compensate for the erroneously high superheat reading. This could cause compressor
damage from liquid flooding or slugging from too low of a superheat setting.

Example No. 2

Assume a 5-psi pressure drop from the evaporator outlet to the compressor in an R-134a system. The
low-side gauge reading at the compressor inlet equals 15 psig or 15 degrees. The evaporator outlet
temperature (thermistor reading) equals 30 degrees.
In this case, the evaporator superheat calculation would be: Evaporator outlet temperature (30 degrees)
minus saturation temperature at compressor inlet (15 degrees) equals degrees superheat (15 degrees).
The superheat changed from 7 degrees to 15 degrees simply by reading the pressure at the
compressor inlet instead of the evaporator outlet. This correct evaporator superheat would be 7
degrees. It is best to measure the pressure at the same location as you measured the temperature to
exclude any system pressure drops.

Superheat Amounts

The amount of evaporator superheat that is required for a certain application will vary. Commercial
icemakers call for 3 degrees to 5 degrees of evaporator superheat to ll out their ice sheets.
However, suction line accumulators are often employed on these systems for added protection. This
will help ensure the entire refrigerant entering the compressor is free of liquid. This will also help keep a
fully active evaporator. Lower temperature applications generally utilize lower evaporator superheat.
Please consult the case manufacturer if in doubt. In the absence of manufacturer's data, a chart such
as the one shown in Table 2 shows guidelines for superheat settings.
There will always be a time when the evaporator sees a light load and the TXV may lose control of its
evaporator superheat due to limitations of the valve and to system instability. This is where total
superheat comes into play.

Total Superheat

Total superheat is all the superheat in the low side of the refrigeration system. It starts at the 100percent saturated vapor point in the evaporator and ends at the compressor inlet. (See Figure 1.)
Sometimes referred to as compressor superheat, total superheat consists of evaporator superheat plus
suction line superheat. A technician can measure total superheat by placing a thermistor or
thermocouple at the compressor's inlet and taking the temperature. A pressure reading will also be
needed at this same location.
Table 1. A pressure-temperature chart for R-134a.

Example No. 3

Let's take another look at an R-134a system. Low-side pressure at the compressor is 20 psig or 23
degrees F. (See Table 1.) The compressor inlet temperature equals 50 degrees.
The total superheat calculation is as follows: Degrees compressor in temperature (50 degrees) minus
saturation temperature (23 degrees) equals total superheat (27 degrees).
In the above example, the total superheat was calculated to be 27 degrees. It is possible to have a TXV
that is adjusted to control superheat at the coil (evaporator superheat) and still return liquid refrigerant
to the compressor at certain low load conditions.
If so, the conditions causing the floodback should be found and corrected. It is recommended that all
TXV-controlled refrigeration systems have at least 20 degrees of compressor superheat to ensure that
the compressor will not see liquid refrigerant (flood or slug) at low evaporator loads. Total superheats
from 20 degrees to 30 degrees are recommended to ensure adequate compressor cooling and
preventive liquid control to the compressor. The TXV, however, should be set to maintain proper
superheat for the evaporator.
Air-cooled compressors are more vulnerable to slugging and valve damage because the suction gases
are not heated by the motor windings. The gases enter the sidewall of the compressor and go directly
to the valves. The 20 degrees of compressor superheat will be a buffer in case the TXV loses control of
superheat at these low loads.
However, the evaporator superheat must still be maintained by the guidelines in the chart shown. A
buffer of 20 degrees to 30 degrees of compressor superheat will also make sure that the refrigerant
vapor entering the compressor is not too dense. Vapors at too high of a density entering the
compressor will cause the compressor to have a higher-than-normal amp draw.
This will overload the compressor in many instances and open thermal overloads.
On the other hand, excess suction gas superheat and/or long periods of low mass flow rate (e.g., an
unloaded compressor), can result in insufcient cooling of the stator and open the internal protectors.

Increasing Total Superheat

Remember, the TXV controls evaporator superheat. To obtain more total superheat, one may add a
liquid/suction heat exchanger, or even run a bit longer suction line to allow heat gains from the

surrounding temperature to heat the suction line.


It is not recommended to take the insulation off of the suction line to increase total superheat. This will
cause the suction line to sweat from water vapor in the air reaching its dew point on the suction line.
Freezing at this condensation may also occur if suction line temperatures are below 32 degrees. Water
damage can occur.

Table 2. A sample chart showing recommended superheat settings for evaporators.

If at all possible, do not sacrice (raise) evaporator superheat to get the amount of total superheat
needed. This will not maintain an active evaporator and system capacity will suffer.
TXVs often lose control of evaporator superheat at evaporator loads. Low evaporator loads can be
caused by many different situations.
Causes for low load conditions on evaporator coils include:
Inoperable evaporator fan motor.
Iced-up or dirty coil.
Defrost circuit malfunction causing coil icing.
End of the refrigeration cycle.
Low airflow across evaporator coil.
Low refrigerant charge.

TXV Hunting

Anytime the evaporator coil sees a reduced heat load than that it is designed to see, a TXV can lose
control and hunt. Hunting is nothing but the valve overfeeding and then underfeeding, trying to nd
itself.
Hunting occurs during periods of system unbalance (e.g., low loads), when temperatures and pressures
become unstable. The TXV tends to overfeed and underfeed in response to these rapidly changing
values until the system conditions settle out, and the TXV can stabilize.
It is this overfeeding condition that hurts compressors. Too low evaporator superheat setting also
causes the TXV to hunt.
In conclusion, a total superheat of at least 20 degrees can prevent the compressor from seeing any
liquid refrigerant.
Tomczyk is a professor of HVACR at Ferris State University, Big Rapids, Mich. He can be reached by e-mail at
tomczykj@tucker-usa.com.
Publication date: 06/07/2004
Did you enjoy this article? Click here to subscribe to The NEWS Magazine
You must login or register in order to post a comment.

Report Abusive Comment

Thank you for helping us to improve our forums. Is this comment offensive? Please tell us why.
Submit Report

Multimedia
Videos

Photos
Podcasts

2014 World Energy Engineering Congress


Scenes from the 2014 World Energy Engineering Congress in Washington,
D.C.

Kari Arfstrom, executive director of the HVACR Workforce Development Foundation, talks about the upcoming
HVACR & Mechanical Conference. Posted on Jan. 23.

Listen
More Podcasts

ACHRNEWS

2015 January 19

Check out the weekly edition of The NEWS today!


Table Of Contents Subscribe

Regional Standards
With regional standards for a/c equipment going into effect in 2015, how do you think it will impact the industry?
Regional standards will cause confusion and the industry will be negatively impacted.
The industry will be prepared and regional standards will not cause any major disruption.
Not sure.
Submit
View Results
Poll Archive

HVACR INDUSTRY STORE

2015 National Plumbing & HVAC Estimator


Every plumbing and HVAC estimator can use the cost estimates in this practical manual!

More Products
Clear Seas Research
With access to over one million
professionals and more than 60
industry-specic publications, Clear
Seas Research offers relevant insights
from those who know your industry best. Let us customize
a market research solution that exceeds your marketing
goals.
DON'T MISS A THING

Register today for complete access to ACHRNews.com. Get full access to the latest features, Extra Edition, and more.
Click here.
STAY CONNECTED

The Magazine

Current Issue
Digital Edition
Archives
Subscribe
About Us
Contact
Advertise
Submit a Press Release
Submit a Letter
Topics

Residential Market

Light Commercial Market


Commercial Market
Refrigeration
Indoor Air Quality
Ventilation
Components & Accessories
Residential Controls
Commercial Controls
Testing, Monitoring, Tools
Services, Apps & Software
Standards & Legislation
Resources
HVACR Directory
eNewsletter
Classieds
Market Research
HVACR Industry Store
List Rental
Reprints
eProduct Info
Custom Content & Marketing Services
Sister Publications
Multimedia

Videos
Podcasts
Photo Gallery
NEWS Apps
Extra Edition

News
Products
Columns
Exclusives
Energy Management
Events
Manufacturer Reports
Regional Reports
Learning Center
Dot Comment
Webinars
HVACR Cartoon
Copyright 2015. All Rights Reserved BNP Media.
Design, CMS, Hosting & Web Development :: ePublishing

Vous aimerez peut-être aussi