CONTROL SYSTEM FUNCTIONAL DESCRIPTION

LPG TRAIN-4 PROJECT


AT MINA AL-AHMADI REFINERY

AS SHIPPED
REVISION DESCRIPTION:
REVISED SH.: 1,68,1217,22,23,26,29,36,75,83,84,86,87,9193

REVISION

DOCUMENT CODE

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION

SOM6629548
Stoppa L.

APPROVED

DATE

0202-AugAug-12

SECURITY CODE
CHECKED

EXECUTED

Chakraborty A.

SIME

SCALE

REPLACES/DERIVED FROM

1st ISSUE

ORIGINAL JOB

SIZE

N/A

N/A

2828-SepSep-11

18000571800057-58

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

1 of 94

Electronically approved draw. GE NuovoPignone DT-'N'

SOM6629548

INDEX

TABLE OF CONTENTS
1

START/STOP SEQUENCING
1.1
READY TO START

6
6

1.2

AUXILIARIES STARTING

1.3

CRANK

1.4

SEAL GAS HEATER AND BOOSTER STARTING LOGIC

1.5

IGNITION AND WARM-UP

10

1.6

ACCELERATION TO OPERATIVE SPEED

11

1.7

COMPLETE SEQUENCE

12

1.8

TURBINE SPEED CONTROL BY DCS

13

1.9

SHUTDOWN REQUEST

14

1.10

SHUTDOWN SEQUENCE

15

1.11

TRIP REQUEST

16

1.12

TRIP SEQUENCE

17

1.13

COOLDOWN SEQUENCE

18

1.14

ONLINE WATER-WASH

19

1.15

OFFLINE WATER-WASH

20

STATUS DEFINITION
2.1
AUXILIARIES START READY

22
22

2.2

AUXILIARIES START PASSED

25

2.3

AUXILIARIES CRANK READY

26

2.4

AUXILIARIES FIRE READY

27

2.5

AUXILIARIES LOAD READY

28

2.6

SHUTDOWN

29

2.7

TRIP

30

2.8

MAINTENANCE OVERRIDE IMPLEMENTATION DESCRIPTION

33

OPERATION MODES SELECTION


OFF mode

34
34

CRANK mode

34

FIRE mode

34

AUTO mode

34

REMOTE mode

34

AUXILIARIES SEQUENCING
4.1
MINERAL LUBE OIL

35
35

4.1.1
DEVICE SUMMARY
4.1.2
SOFTWARE DESCRIPTION
4.2
OIL VAPOUR SEPARATOR

35
35
38

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

2 of 94

4.2.1
DEVICE SUMMARY
4.2.2
SOFTWARE DESCRIPTION
4.3
LUBE OIL HEATER

38
38
39

4.3.1
DEVICE SUMMARY
4.3.2
SOFTWARE DESCRIPTION
4.4
LUBE OIL WATER COOLER

39
39
40

4.4.1
DEVICE SUMMARY
4.4.2
SOFTWARE DESCRIPTION
4.5
CONTROL OIL

40
40
41

4.5.1
DEVICE SUMMARY
4.5.2
SOFTWARE DESCRIPTION
4.6
HYDRAULIC OIL

41
41
42

4.6.1
DEVICE SUMMARY
4.6.2
SOFTWARE DESCRIPTION
4.7
STARTING

42
42
44

4.7.1
DEVICE SUMMARY
4.7.2
SOFTWARE DESCRIPTION
4.8
HYDRAULIC RATCHETING

44
44
45

4.8.1
DEVICE SUMMARY
4.8.2
SOFTWARE DESCRIPTION
4.9
BEARING METAL TEMPERATURE

45
45
47

4.9.1
DEVICE SUMMARY
4.9.2
SOFTWARE DESCRIPTION
4.9.3
DEVICE SUMMARY
4.9.4
SOFTWARE DESCRIPTION
4.10 WHEELSPACES

47
47
48
48
49

4.10.1 DEVICE SUMMARY


4.10.2 SOFTWARE DESCRIPTION
4.11 SEISMIC VIBRATION

49
49
50

4.11.1 DEVICE SUMMARY


4.11.2 SOFTWARE DESCRIPTION
4.12 MAGNETIC SPEED PICK-UP

50
50
51

4.12.1 DEVICE SUMMARY


4.12.2 SOFTWARE DESCRIPTION
4.13 COMBUSTION CHAMBER FLAME DETECTOR

51
51
52

4.13.1 DEVICE SUMMARY


4.13.2 SOFTWARE DESCRIPTION
4.14 INTERFACES WITH BENTLY NEVADA VIBRATION MONITORING SYSTEM

52
52
53

4.14.1 DEVICE SUMMARY


4.14.2 SOFTWARE DESCRIPTION
4.14.3 DEVICE SUMMARY
4.14.4 SOFTWARE DESCRIPTION
4.15 EXHAUST TEMPERATURE

53
53
54
54
55

4.15.1 DEVICE SUMMARY


4.15.2 SOFTWARE DESCRIPTION
4.16 EXHAUST DUCT BACK PRESSURE

55
55
56

4.16.1
4.16.2

DEVICE SUMMARY
SOFTWARE DESCRIPTION
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION

REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

56
56
DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

3 of 94

4.17

WATER WASH

57

4.17.1 DEVICE SUMMARY


4.17.2 SOFTWARE DESCRIPTION
4.18 VENTILATION

57
57
59

4.18.1 DEVICE SUMMARY


4.18.2 SOFTWARE DESCRIPTION
4.19 INLET AIR FILTRATION

59
59
62

4.19.1 DEVICE SUMMARY


4.19.2 SOFTWARE DESCRIPTION
4.20 FUEL GAS

62
62
63

4.20.1 DEVICE SUMMARY


4.20.2 SOFTWARE DESCRIPTION
4.21 LIQUID FUEL

63
64
66

4.21.1 DEVICE SUMMARY


4.21.2 SOFTWARE DESCRIPTION
4.22 FUEL TRANSFER

66
66
68

4.22.1 Fuel Splitter


4.22.2 Fuel Transfer (Liquid to Gas)
4.22.3 Fuel transfer (Gas to Liquid)
4.23 FUEL GAS BLOCK / FUEL GAS VENT VALVES

68
68
68
69

4.24

70

ATOMIZING AIR SYSTEM

4.24.1 DEVICE SUMMARY


4.24.2 SOFTWARE DESCRIPTION
4.25 SEAL GAS, SEAL GAS HEATER & SEAL GAS BOOSTER SYSTEM

70
70
72

4.25.1 DEVICE SUMMARY


4.25.2 SOFTWARE DESCRIPTION
4.26 STEAM INJECTION

72
72
75

4.26.1 DEVICE SUMMARY


4.26.2 SOFTWARE DESCRIPTION
5 ANTISURGE AND LOAD SHARING
6 FIRE FIGHTING MONITORING
6.1
ENCLOSURE FIRE DETECTION / FIGHTING:

75
75
78
79
79

6.1.1
DEVICE SUMMARY
6.1.2
SOFTWARE DESCRIPTION
6.2
FIRE FIGHTING DEDICATED PLC INTERFACE:
7
8

79
80
81

MARKVIE INTERFACES WITH OTHER SYSTEMS


CONTROL INTERFACE WITH WASTE HEAT RECOVERY UNIT CONTROL SYSTEM
8.1.1
INTERLOCK SIGNALS
8.1.2
SOFTWARE DESCRIPTION

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

82
92
92
92

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

4 of 94

LEGEND:
L14HSX:
L4:
14HR:
L62CD:
L2TVX:
L28FDX:
L1X:
SIS:
FSR:
DCP:

MINIMUM OPERATING SPEED


MASTER PROTECTIVE RELAY
SHAFT ZERO SPEED
COOLDOWN END
IGNITION TRANSFORMER ACTIVATION
FLAME DETECTED
MASTER CONTROL START-UP.
SAFETY INSTRUMENTED SYSTEM (MK VIeS)
FUEL STROKE REFERENCE
DIRECT CURRENT PANEL

GENERAL NOTE:
1. Contacts for limit switches are closed when valve is actuated to corresponding switch position.
2. For signal philosophy to MCC or DCP see UNIT CONTROL SYSTEM HARDWIRED I/O LIST
(SOM6628418/3).
3. The software macro performs a position check on each valve command output transition, after a
max positioning time if the relevant limit switch input is not verified a position mismatch Alarm is
generated. Moreover the position mismatch Alarm becomes active immediately if both limit switch
inputs are closed.
4. The scope of this specification is to give a functional description of its auxiliary sequences. This
document does not cover the description of CORE ENGINE LOGIC FUNCTIONS. The CORE
ENGINE LOGIC FUNCTIONS software section contains algorithms for combustion chambers flame
detection, firing temperature calculation, speed/load regulator/protection, acceleration regulators,
exhaust temperature averaging regulator and protection, inter stage pressure regulator. These
algorithms shall be considered GE proprietary information and are excluded from this specification.

REFERENCE DOCUMENTS:
GE-NP DOCUMENTS
Piping & Instruments Diagram
Cause & Effect Diagram
UCS IO List
Control System & Power Supply Schematic
CCC Control System Description
Field Instrument List
Communication List
CCC Modbus List

SOM5081820/1
SOM6629813/3
SOM6628418/3
SOM5464708/3
SOM6629507/4
SOM6628002/3
SOM6629523/3
SOM6629508/4

NOTE:
~ Symbol indicate NOT signal operation
Median function is used in Mark Vie logic where 2oo3 function is required
Spread alarm for 2oo3 signals will be active as follow: if the difference between the maximum and
the minimum values of the three variable becomes greater than or equal to the specified constant.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

5 of 94

1 START/STOP SEQUENCING
1.1

READY TO START

Figure 1 - Ready to start

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
REVISED
WHERE
SHOWN <4>
NO REVISION
INTRODUCED
IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

6 of 94

1.2

AUXILIARIES STARTING

Figure 2 - Auxiliaries starting


TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
REVISED
WHERE
SHOWN <4>
NO REVISION
INTRODUCED
IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

7 of 94

1.3

CRANK
External
Sequences

Turbine and Auxiliaries


Sequences

Sequences

From Sh. 07

Customer valve
sequencing start

4VALV
(231-XS-0256)
<4>

Start process valve


positioning

Off-line water
wash selection on
HMI

Yes

No

Water wash
system start (1)

No
Hot Bypass valve open command for purge
Hot Bypass valve open / close feedback (1= Open; 0 = close)

Aux. Ready to
crank?
Open Hot Gas
Bypass Valve

End of Sequence

Yes

Close Anti-surge valve for Purge

AND

Anti-surge valve open / close feedback (1= Closed; 0 = Open)

Close Anti-surge
Valve command to
CCC

See TABLE 5
Auxiliary ready
to Crank
-Ratchet system activation
-Starting system activation

Close Anti-surge
valve

Valve sequence
ended; Customer
Permissive to Crank

No
TNH Above
zero speed?

3CRC

(231-XS-0258 RS) <4>


Yes
14HMX

PESD

-Ratchet system de-activation


-Solenoid valve 20HD-1 closed

(231-XS-253C)

Unit in Crank

No
TNH Above
Crank speed?

Notes:(1) Note that if water wash is


selected ready to start and start
passed conditions changes
from the above described

Yes
CRANK

WHRU CTRL
GT Purge Done

231-XS-0955

<4>

Yes

WHRU dampers
in By-Pass
position?
No
Purge Timer Reset

WHRU CTRL
WHRU Purge Sequence
GT Purge Time
elapsed?
Yes
L2TV=1

WHRU CTRL
WHRU Purge Timer Elapsed

No

231-XS-960

No

WHRU Purge
Done?
Yes

WHRU CTRL
Damper Status

231-XS-554
or
231-XS-654

WHRU dampers
in By-Pass
position?

No

Yes

To Sh. 09

Figure 3 Crank

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
REVISED
WHERE
SHOWN <4>
NO REVISION
INTRODUCED
IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

8 of 94

1.4

SEAL GAS HEATER AND BOOSTER STARTING LOGIC

Figure 4 Seal Gas Heater and Booster Starting Logic

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

9 of 94

1.5

IGNITION AND WARM-UP

Figure 5 - Ignition and warm-up

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

10 of 94

1.6

ACCELERATION TO OPERATIVE SPEED

Figure 6 - Acceleration to operative speed


TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

11 of 94

1.7

COMPLETE SEQUENCE

Figure 7 - Complete sequence


TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
REVISED
WHERE
SHOWN <4>
NO REVISION
INTRODUCED
IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

12 of 94

1.8

TURBINE SPEED CONTROL BY DCS

Figure 8 Turbine Speed Control by DCS


TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
REVISED
WHERE
SHOWN <4>
NO REVISION
INTRODUCED
IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

13 of 94

1.9

SHUTDOWN REQUEST

Figure 9 - Shutdown request

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
REVISED
WHERE
SHOWN <4>
NO REVISION
INTRODUCED
IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

14 of 94

1.10 SHUTDOWN SEQUENCE

Figure 10 - Shutdown sequence


TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
REVISED
WHERE
SHOWN <4>
NO REVISION
INTRODUCED
IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

15 of 94

1.11 TRIP REQUEST


External
Sequences

Turbine and Auxiliaries


Sequences

Trip
sequence

- Crank
- Fire
- Manual
- Auto
Master
Selector

- Remote

PESD
CESD-1, CESD-2

Customer ESD
signal

Customer
Trip?

(231-XS-700A)
(231-XS-700B)

YES

No

Trip from
HMI?

L
To Sh.6, 17

YES
L
To Sh. 6, 17

No

DCS
4CT

Process Remote
Trip

(231-XS-0257T)

See Table 9
Trip from Auxiliaries

<4>

No
YES

Aux Trip?

No

Yes

Core Engine Trip?

To sh. 06, 17
No

End sequence

Figure 11 - Trip request

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
REVISED
WHERE
SHOWN <4>
NO REVISION
INTRODUCED
IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

16 of 94

1.12 TRIP SEQUENCE

Figure 12 - Trip sequence


TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
REVISED
WHERE
SHOWN <4>
NO REVISION
INTRODUCED
IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

17 of 94

1.13 COOLDOWN SEQUENCE

Figure 13 - Cooldown sequence

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

18 of 94

1.14 ONLINE WATER-WASH

Figure 14 Online Water-wash

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

19 of 94

1.15 OFFLINE WATER-WASH

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

20 of 94

Figure 15 Offline Water-wash

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

21 of 94

2 STATUS DEFINITION
2.1

AUXILIARIES START READY

Table1 Ready to start from Other Systems


LOGIC

SOFTWARE
TAG
L33as_o

NOT
NOT

l86asc
L86as1

NOT

l86ls
L3COMM_IO

NOT
NOT
NOT

l86ps1
l86ps2
l86psfg

NOT
NOT
NOT

l86psf
l86ps3
l80x

NOT

l30ra

JOB TAG(GE TAG)


231-ZSH-5001A
231-XS-807A (86AS)
(31-XS-808B (86LS)
231-XS-601A (86PS-1)
231-XS-601B (86PS-2)
231-XS-602 (86PS-FG)
231-XS-603 (86PS-FIELD)
231-XS-610 (86PS-3)
231-XS-207 (DCP-80X)
231-XS-206A (DCP-30RA)

NOT

ldcp_bad
231-XS-208A (DCP-BD)
231-XS-863 (-) <4>
231-XS-864 (-) <4>

NOT
NOT
NOT

l86vmn

NOT

l86tm

NOT

l86cr

NOT

l33cp_c

231-XS-515L (86CR)
231-XS-144 (33CP-1)

NOT

l86fg

231-XS-652 SF (86FF-1)

NOT

L71GFH_W

NOT

L86PS_110V
AC_TRVIEW
L86PS_24VD
C_TRVIEW
FF_NSD

231-LIT-5039A/B/C (71GF2/3/4A)
OR,
231-LIT-5043A/B/C (71GF2/3/4B)
231-XS-612 A

231-YS-402F (86VM)
231-YS-451F (86TM)

NOT
NOT

L3crs

231-XS-613 A
231-XS-652 IF (86FF_SD)
231-XS-0250 RS (3CRS)
<4>

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
REVISED
WHERE
SHOWN <4>
NO REVISION
INTRODUCED
IN THIS PAGE

DESCRIPTION

SYSTEM

Anti-surge control valve


open position-ASV 1
Anti-surge controller fault
Anti-surge control valve 1
position failure
Master controller fault
MKVIe IO pack
communication OK
24Vdc Bus 1 failure
24Vdc Bus 2 failure
Fire Fighting 24Vdc Bus
failure
Field 24Vdc Bus failure
110Vdc Bus failure
Minimum battery voltage
alarm
DCP rectifier A common
alarm
DCP-battery
A
discharging
GROUND FAULT +
GROUND FAULT Vibration monitor common
fault alarm
Temperature monitoring
fault
Cranking motor protective
lock-out
Fire fighting Inergen
discharge valve closed
FF system fault alarm

Process (ASC)

Fuel gas scrubber level


high alarm

110 Vac Bus Failure at TV


server panel
24 Vdc Bus Failure at TV
server panel
FF Input fault- Normal
shutdown
Customer ready to start

Process (ASC)
Process (ASC)
Process (MCP)
Misc-MarkVIe
Misc-PS
Misc-PS
Misc-PS
Misc-PS
Misc-PS
Misc-DCP
Misc-DCP
Misc-DCP
Misc-DCP
Misc-DCP
Misc- BN3500 VIB
Monitor
Misc- BN3500
TEMP Monitor
Misc- Starting
Motor
Fire Fighting
monitor
Fire Fighting
monitor
Customer ESD

MISC-PS
MISC-PS
FF
DCS

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

22 of 94

LOGIC

JOB TAG(GE TAG)

DESCRIPTION

SYSTEM

NOT

SOFTWARE
TAG
L86FTL

231-XA 5015 (-)

LF thyristor Panel

NOT
NOT

L27mc1n
L49x

231-XS-134 (27MC)
231-XS-135 (49X)

NOT
NOT

L74x_mcc
L45hsa_o

231-XS-136 (74X-MCC)
231-XS-736 (45HSA)

Liquid fuel thyristor panel


fault
Undervoltage from MCC
Common overload from
MCC
Drawer Common Alarm
Acc compt H2S detected
alarm
Hot Gas Bypass Valve
Close Limit Switch
Diverter System Close
Seal Gas thyristor Panel
fault

231-ZSL-2055 (-)

NOT

231-XS-554 (-)
231-UA-5209A (TH1_F)

L86thy

MCC
MCC
MCC
MarkVIe
MarkVIe
MarkVIe
Thy Panel

Table2 Ready to start from Auxiliaries


LOGIC
NOT
NOT

SOFTWARE
TAG
L71QL_W
l27qel

JOB TAG(GE TAG)

DESCRIPTION

SYSTEM

231-LIT-5086A (96QL1)

Lube oil tank level low alarm


Lube oil emergency pump
fault
Lube oil tank temperature
normal
Hydraulic protective trouble
Hydraulic ratchet pump
overload alarm
Hydraulic ratchet pump
under-voltage alarm
Turbine compartment outlet
temp high alarm
Turbine enclosure ventilation
inlet damper open
Turbine enclosure ventilation
outlet damper#1 open
Turbine enclosure ventilation
outlet damper#2 open
Turbine enclosure ventilation
outlet damper#3 open
Coupling compartment outlet
temperature high alarm
Fuel gas warm-up vent valve
closed
Fuel gas pressure high alarm

Lube oil
Lube oil

Inter-valve fuel gas pressure


high
Fire fighting Inergen
discharge valve open

Fuel gas system

NOT
NOT

SIS1.L86HD
l49hr1a

231-XS-851B (49QE) <4>


231-TE 5088AA
(LT-OT-1)
231-XS-200O (49HR-1)

NOT

L27hr1a

231-XS-200U (27HR-1)

NOT

L26BA

231-TE-5241A1/A2/A3
(TT-BA-2A/B/C)
231-ZSH-5242A (33ID-1)

L26qn_W

l33ido

NOT

Note1

l33odo1

Note1

l33odo2

Note1

l33odo3

Note1

L26BA_1
l33vg2_c

NOT

L63FGH_W

NOT

L63FGH1_W
l33cp

NOT

L33PV3_o

231-ZSH-5243A (330D1)
231-ZSH-5244A (330D2)
231-ZSH-5245A (330D3)
231-TE-5242A1/A2/A3
(TT-BA-3A/B/C)
231-ZSL-5009A
(33VG-2)
231-PIT-5003A (96FG-1)
231-PIT-5005A1/A2/A3
(96FG-2A/B/C)
231-ZSH-5265A (33CP1A);
231-ZSH-5266A (33CP1D)
231-ZSH 5007 A (33PV2)

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
REVISED
NO REVISION
WHERE
INTRODUCED
SHOWN <4>
IN THIS PAGE

Nozzle Purge Air Vent valve


open

Lube oil
Control oil
Hydraulic ratchet
Hydraulic ratchet
Enclosure
ventilation
Enclosure
ventilation
Enclosure
ventilation
Enclosure
ventilation
Enclosure
ventilation
Enclosure
ventilation
Fuel gas system
Fuel gas system

Fire Fighting skid


system

Fuel gas system

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

23 of 94

LOGIC

JOB TAG(GE TAG)

DESCRIPTION

SYSTEM

NOT

SOFTWARE
TAG
L33cb1o

231-ZSH 5050A (33CB-1)

Cooling & Sealing

NOT

L33cb2o

231-ZSH 5049A (33CB-2)

NOT

L33ac_c

231-ZSL-5157A (33AC-1)

VAB-1 Axial Compressor


Bleed valve status Open
VAB-2 Axial Compressor
Bleed valve status Open
Atomizing air cooler valve
closed

Cooling & Sealing


Oil water cooler

Note1: This permissive to start is enabled if Water Wash On function is not selected on the HMI (L43BW is false).
Table3 Ready to start from SIS
LOGIC
NOT

SOFTWARE
TAG
l45hta2

NOT

l45hta1

NOT

l45hfa
l33dtc

NOT
NOT
NOT
NOT
NOT
NOT
NOT

NOT

NOT

JOB TAG(GE TAG)

DESCRIPTION

SYSTEM

231-AE-5242A1/2/3 (45HD2A/B/C)
231-AE-5241A1/2/3 (45HD1A/B/C)
231-AE-5229A1/2/3 (45HF1/2/3)

Turbine enclosure gas


detected alarm
Accessory comp. gas
detected alarm
Turbine inlet air filter gas
detected alarm
Enclosure
access
door
closed
Master protective lockout
Inter-valve gas unit rate
mismatch
Fuel Gas Stop valve control
signal on safety
GT-2 shaft selected
Flame detected without fuel
on
Off-skid shutoff valve position
mismatch
Off-skid bleed valve position
mismatch

SIS

Note1

L86MP

231-ZSL-5241(33DT)
-

(L86VG-1)

L20HDX

GT_2SHAFT

L28FD_FLT

(L86FB)

(L86FV)

L30FORCED
_SIS
L86BT1_ALM
L86BT2_ALM
L86BT3_ALM
L30LOCKED
_SIS
l33af1c

NOT

SIS forced signal detected

Turbine compart. /ambient.


Diff. Press. TX-1/2/3 fault

SIS CPU locked active

231-ZSL-5229A (33AF-1)
231-ZSL-5219A (33ED-1)

NOT
NOT

L86splc
L4_sis

NOT

L33ED4

NOT

L33ED5

231-ZSL-5277A1 (33ED-4)
231-ZSL-5277A2 (33ED-5)

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

Turbine inlet air filter


inspection. door closed
Combustion Wrapper Drain
valve closed
Safety system fault signal
Master Protective Signal
(1=Fuel ON)
Exhaust Plenum Drain Valve
VA17-6 Closed
Exhaust Plenum Drain Valve
VA17-6 Closed

SIS
SIS
SIS
SIS
SIS
SIS
SIS
SIS
SIS
SIS
SIS
SIS

SIS
SIS
SIS
SIS
SIS
Water wash
Water wash

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

24 of 94

Note1: This permissive to start is enabled if Water Wash On function is not selected on the HMI (L43BW is false).

2.2

AUXILIARIES START PASSED

Table 4 Start Passed


LOGIC

SOFTWARE
TAG
L3PSP
l52qa

NOT

L63QA2L_W

NOT

L63QAL_W
L3QE_TEST

NOT

L63HQ1L_W
l52hq
l52bt1
OR
Note2
l52bt2

NOT

NOT

L63BT_W

Note2

L63SGLA

JOB
TAG)

TAG(GE

231-XS-100I
(52QA-1)
231-PIT-5133
A1/2/3
231-PIT-5091A
(96QA-1)
231-PIT-5114A
(96HQ-1)
231-XS-104I
(52HQ-1)
231-XS-108I
(52BA-1)
OR,
231-XS-109I
(52BA-2)
231-PDIT5241A1/2/3 (96SV1A/B/C)
231-PDIT-5201 A

DESCRIPTION

SYSTEM

Process start passed


Lube oil auxiliary pump
running
Lube oil header pressure
low alarm
Lube oil pump discharge
pressure low alarm
Lube oil emergency pump
test passed
Hydraulic oil pressure low
alarm
Hydraulic oil aux pump
running
Turbine-enclosure
ventilation fan #1 running
OR,
Turbine-enclosure
ventilation fan #2 running

Lube oil
Lube oil
Lube oil
Lube oil
Hydraulic oil
Hydraulic oil

Enclosure ventilation

Turbine compartment diff.


press low alarm

Enclosure ventilation

Seal Gas Inlet Balancing


Line Differential Pressure

Seal Gas

Note2: This permissive to start is bypassed if Compressor/turbine Water Wash Control function is selected (L83BW is
true).

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

25 of 94

2.3

AUXILIARIES CRANK READY

Table 5 Ready to Crank from auxiliaries


LOGIC

NOT

SOFTWAR
E TAG
L3PRC
L71QL_W
l52qa

NOT
NOT

L63QA2L_
W
L63QAL_W
L26QN_W

NOT

NOT

L63HQ1L_
W
l52hq
L26FGL_W

l33vg2_c

Note3

NOT

L63FGL_W

Note3

JOB TAG(GE TAG)

DESCRIPTION

SYSTEM

Process ready to crank


Lube oil tank level low
alarm
Lube oil auxiliary pump
running
Lube oil header pressure
low alarm
Lube oil pump discharge
pressure low alarm

Process

Lube oil tank temp normal

Lube oil

231-LIT-5086A (96QL1)
231-XS-100I (52QA-1)
231-PIT-5133 A1/2/3
231-PIT-5091A (96QA1)
231-TE-5088AA (LTOT-1)
231-PIT-5114A (96HQ1)
231-XS-104I (52HQ-1)
231-TE-5006AA
(TG-FG-1)
231-ZSL-5009A (33VG2)
231-PIT-5003A (96FG1)

Hydraulic oil pressure low


alarm
Hydraulic oil aux pump
running
Fuel gas temp low alarm
Master selector in crank
position
Fuel gas vent valve closed
Fuel gas
alarm

pressure

low

Off-skid gas
shut-off
valve open

Note3

NOT

AND
Off-skid gas
vent valve
Note3
closed
L63NCP_W
L3crc
L33prc

Lube oil

Lube oil
Lube oil

Hydraulic oil
Hydraulic oil
Fuel gas
Fuel gas
Fuel gas

Fuel gas

(33FB-O)
AND
(33FV-1)

Process valve
crank position

ready

231-PIT 5063 (96NCP1)


231-XS-0258
RS
(3CRC) <4>
SIS1.L33FB_O
&
SIS1.L33FV_C

Bearing
cooling
Pressure Low

to

Air

Customer ready to crank


Process valve
crank Position

Ready to

Process
Process

Note3: This permissive to start is bypassed if Compressor/turbine Water Wash Control function is selected (L83BW is
true).

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
REVISED
WHERE
SHOWN <4>
NO REVISION
INTRODUCED
IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

26 of 94

2.4

AUXILIARIES FIRE READY

Table 6 Ready to Fire from auxiliaries


LOGIC

NOT

SOFTWARE
TAG
L3PRF
L63HQ1L_W

NOT
NOT

L43BW
L83BW

NOT

L63FGL_W

NOT

L26FGL_W
l33vg2_c

NOT

L63NCP_W

JOB
TAG(GE
TAG)
231-PIT-5114A
(96HQ-1)
231-PIT-5003A
(96FG-1)
231-TE-5006AA
(TG-FG-1)
231-ZSL-5009A
(33VG-2)
231-PIT
5063
(96NCP-1)

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DESCRIPTION

SYSTEM

Process ready to fire


Hydraulic oil pressure low
alarm
Water-wash on selected
Turbine/compressor
water
wash control

Process
Hydraulic oil

Fuel gas pressure low alarm

Fuel gas

Fuel gas
alarm

Fuel gas

temperature

low

Fuel gas vent valve closed

Water-wash
Water-wash

Fuel gas

Bearing Cooling Air Pressure


Low

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

27 of 94

2.5

AUXILIARIES LOAD READY

Table 7 Ready to load from auxiliaries


LOGIC
SOFTWAR
JOB
TAG(GE
E TAG
TAG)
L3PRL
NOT
l52qa
231-XS-100I
(52QA-1)
l72qez
231-XS-851-A
(52QE-1)
NOT
L52hq
231-XS-104I
(52HQ-1)

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DESCRIPTION

SYSTEM

Process ready to load

Process

Lube oil aux pump running

Lube oil

Lube oil emergency pump


stopped
Hydraulic oil aux pump
running

Lube oil
Hydraulic oil

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

28 of 94

2.6

SHUTDOWN

Table 8 Shutdown from auxiliaries


LOGIC
SOFTWAR
JOB
TAG(GE
E TAG
TAG)
L94PSHD
L63TF
231-PDIT5231A1/2/3
(96TF-1A/B/C)
L30WSA4_
231-TE-5082/A1
ALM
(TT-WS1AI-1)
OR
231-TE-5082/A2
(TT-WS1AI-2)
OR
231-TE-5079/A1
(TT-WS1FI-1)
OR
231-TE-5079/A2
(TT-WS1FI-2)
OR
231-TE-5080/A1
(TT-WS2FI-1)
OR
231-TE-5080/A2
(TT-WS2FI-2)
OR
231-TE-5081/A1
(TT-WS2AI-1)
OR
231-TE-5081/A2
(TT-WS2AI-2)

S1STPSEL

TAH-208
TAH-211
TAH-212
TAH-213
231-TE5158/A1A/2A/3A
(AAT-1A/B/C)
231-TIT5013A1/A2/A3
231-XS-652-IF
(86FF_SD)
231-XS-0257 S
(1STOP) <4>

DESCRIPTION

SYSTEM

Process shut-down command

Process

Turb inlet filter diff. press. High


vot. Shutdown logic

Inlet and Filtration


Wheel-space

Wheel-space shutdown logic

Wheel-space
Wheel-space temperature high
Note4
alarm
Atomizing air temperature high
high shutdown
Liquid Fuel Temperature low
low
Fire Fighting Input fault normal
shutdown

Atomizing air

Liquid Fuel System


Fire Fighting System
DCS

Process remote Stop

gthrsgds_sd

GT shutdown for HRSG


Shutdown & Diverter System
Failure to Close
Note4: Shutdown is started if wheel-space temperature is high for 24 hours

PESD

231-XS-354

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
REVISED
WHERE
SHOWN <4>
NO REVISION
INTRODUCED
IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

29 of 94

2.7

TRIP

Table 9 Trip from auxiliaries


LOGIC

SOFTWARE
TAG

JOB TAG(GE TAG)

DESCRIPTION

SYSTEM

231-TE-5210A1/2/3

Compressor primary vent


pressure (depressurized trip)
Nitrogen gas header pressure
low low
Primary vent pressure
(depressurized trip)
Buffer gas Temp low low.
(depressurized trip)

Surge trip

ASC

L26QT

231-TE-5159A1/2/3
(LT-TH-1A/B/C)

Lube oil header temperature


high voting trip logic

Lube Oil

L63QTX

231-PIT-5133 A1/2/3

Lube oil pressure low voting trip


aux. logic

Lube Oil

L63QVT

231-PDIT-5087A1/2/3
(96QV-1A/B/C)

Lube oil tank pressure high


voting trip logic

Lube Oil

231-PDIT-5204A1/2/3
231-PIT-5195A1/2/3
231-PDIT-5205A1/2/3
(L26TSGLL)
L4surge_1

L4QE_TRP
L3SMTX

231-TE-5241A1/2/3
(TT-BA-2A/B/C)

L26BT

L4CETRIP
L4T_S
L4T_FGS
(L4T)

231-TE-5242A1/2/3
(TT-BA-3A/B/C)
-

231-ZT-5133A1/2/3

231-XT-5133A1/A2

231-XT-5134A1/A2

231-TE5139A1A/2A//3A
231-TE5140A1A/2A/3A
231-SE-5061A1/2/3
(77NH-13)
231-SE-5063A1/2/3
(77NL-13)
231-TE-5076A1 to
231-TE-5076A13
(TT-XD-1 to TT-XD13)

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

Lube oil emergency pump trip


logic
Starting motor trip logic
GT compartment internal
temperature high trip
Core Trip
Cumulative safety trip to MKVIe
Fuel Gas Scrubber Trip Signal
Trip Notification from MKVIe
Axial Displacement of
Compressor bearings High High
Radial Vibration on Compressor
bearings High High
Radial Vibration on Compressor
bearings High High
Thrust bearing temperature
high high
Thrust bearing temperature
high high
HP Shaft Speed Safety
System
LP Shaft Speed Safety
System
Exhaust Thermocouple

Seal Gas System


Seal Gas System
Seal Gas System
Seal Gas System

Lube Oil
Hydraulic

Ventilation System

UCS
SIS
DCS
SIS
BN 3500 (Vib)
BN 3500 (Vib)
BN 3500 (Vib)
BN 3500 (Temp)
BN 3500 (Temp)
Control &
Protection
Control &
Protection
Control &
Protection

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

30 of 94

LOGIC

SOFTWARE
TAG
L28FDT
L3SFLT
L4ATOMPU
R
L45FTT

JOB TAG(GE TAG)


231-BE5061A1/A2/A3/A4
(28FD-2/3/10/11)
231-TE5158A1A/2A/3A
231-XS-657 T
231-PDIT-5217A
231-VE-5061A1/A2
(39V-1A/B)
231-VE-5062A1/A2
(39V-2A/B)

DESCRIPTION

SYSTEM

Loss of flame detected

Control &
Protection

Control system fault


Atomizing Air Cooler Discharge
Temp low low
Fire detected trip
CE/CO Inlet Filter high high

UCS (Mark Vie)


Atomizing Air
Cooler
FF System
UCS (Mark VIe)

HP Shaft Vibration high high

BN 3500 (Vib)

HP Shaft Vibration high high

BN 3500 (Vib)

DESCRIPTION

SYSTEM

Table 10 Trip from Safety system


LOGIC

SOFTWARE
TAG

JOB TAG(GE TAG)


(5ESD-R1)
(5ESD-R2)

L5LESD1

231-HS-5254A
(5ESD-1)

L5LESD2

231-HS-5253A
(5ESD-2)

L63CO_TRP
L4BTLOSS

231-PIT-5121A1/2/3
(96HG-1A/B/C)
231-PDIT-5241A1/2/3
(96SV-1A/B/C)

(L4PV)

(L4T)

L6FGEX

L63ETH

L28FDT
L5cesd1
L5cesd2

231-SE-5061A1/2/3
(77NH-13)
231-SE-5063A1/2/3
(77NL-13)
231-PDIT5067A1/A2/A3
(96EA-1A/B/C)
231-BE5061A1/A2/A3/A4
(28FD-2/3/10/11)
231-XS-700 A
(CESD-1)
231-XS-700 B
(CESD-2)

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

Front panel ESD push button


(pressurized trip)
Front panel ESD push button
(depressurized trip)
Turbo unit emergency
shutdown button (depressurized
trip)
Turbo unit emergency
shutdown button (depressurized
trip)
Control oil header pressure low
voting trip logic
Enclosure loss of ventilation trip
Depress. trip Notification from
MKVIe
Trip Notification from MKVIe
SIS fuel gas flow excessive trip
(only during start-up)
HP Shaft Speed Safety
System
LP Shaft Speed Safety
System

UCS
UCS
Enclosure Turbine

Enclosure Turbine
Control Oil
Ventilation System
SIS
SIS
Fuel Gas
Control &
Protection
Control &
Protection

Exhaust Duct Back Pressure

Control &
Protection

Loss of flame detected

Control &
Protection

Customer ESD Signal

PESD

Customer ESD Signal

PESD

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

31 of 94

LOGIC

SOFTWARE
TAG

JOB TAG(GE TAG)


231-AE
5241\A1/A2/A3
(45HD-1A/B/C)
231-AE
5242\A1/A2/A3
(45HD-2A/B/C)

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DESCRIPTION

SYSTEM

Acc. Compart. Vent. Outlet Gas


Detector high high
Acc. Compart. Vent. Outlet Gas
Detector high high

UCS (Mark VIeS)

UCS (Mark VIeS)

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

32 of 94

2.8

MAINTENANCE OVERRIDE IMPLEMENTATION DESCRIPTION

Following is a functional description of the implementation for maintenance overrides required for single
(1oo1) trip input devices to the MKVIe system.
Maintenance override shall be enabled by operator from HMI.
When the MKVIe receives the MOS enable signal from HMI, the MKVIe logic enables this function. The
number of instruments under MOS will be transmitted to DCS via the DCS - MK VIe serial link.
The MKVIe HMI is configured with a Maintenance Override selection screen which shows all of the field
devices capable of being put on override. When the MKVIe receives the MOS enable signal from HMI, a
transmitter selected to be overridden can be selected on the MKVIe screen through password protection.
Once the transmitter input is selected, the trip from this input will be overridden in the logic and the MKVIe
shown on HMI GT MOS ON indication shown on the MKVIe HMI
This GT MOS ON indication should be maintained for the duration of the override.
The MKVIe logic includes an interlock such that only one trip input for voting function may be overridden at a
time (i.e. selection of a transmitter to override when another transmitter of the same voting function is already
on override shall not be possible).
While an input signal is on override, the trip function from that input will be temporarily inhibited for the
duration of the maintenance activity. However, the logic should be configured to allow the alarm functionality
to remain active during this time in order to allow testing of the device after maintenance and before
removing the override (i.e. before return to normal service).
A MOS repeating alarm is sent from the MKVIe to DCS via the serial link once every hour, to warn the plant
operations personnel that a transmitter is on override.
After confirmation that the individual device/signal is ready to be restored to normal operation, the MOS is
cancelled (override is removed) by removing the MOS from the individual instrument (not by resetting the
MOS switch). When the selector switch is moved to cancel the DCS will send a momentary MOS Cancel
signal to MKVIe via the serial link.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

33 of 94

3 OPERATION MODES SELECTION


Unit Operational Mode selection shall be performed by means of a software selector on UCS HMI called
MASTER SELECTOR. The following operational modes are defined:
OFF
CRANK
FIRE
AUTO
REMOTE
MANUAL
Only one mode can be selected or set at any time. Mode selection is possible only if the relevant permissive
conditions are met as indicated below.
Switching to AUTO and REMOTE is always possible; the only exception is the Off-Line Water Wash
condition that locks the selector in CRANK.
Switching from/to different modes is allowed only under specific conditions (see below paragraphs for
details).

OFF mode
OFF mode is automatically set upon system initialization (i.e. UCS power-up). Off Mode can only be selected
by the operator when the GT has come to a complete stop.
If the master selector is in OFF mode no kind of starting sequence can be run, because the machine is not
ready to start and any kind of start command is ignored.

CRANK mode
In CRANK mode the engine is allowed to complete crank phase only, reaching purge/firing speed: all other
following sequencing phases can be then completed changing the Master Selector position. Switching to
OFF is possible before start up is initiated.
This Master Selector position also enables OFF LINE WATER WASH selection until start up is initiated
(pushing START button). In case of Off-Line Water Wash sequence activation no other following sequence
can be completed: Master Selector remains locked to Crank position until Water Wash sequence ends as a
consequence of a normal stop or trip command.

FIRE mode
In FIRE mode the ignition phase is allowed, the turbine can reach the flame-on status and the sequence
stops to warm-up.
It is possible to switch back to CRANK only before firing and to OFF before start up is initiated.

AUTO mode
In AUTO mode the complete start-up procedure can be executed, bringing centrifugal compressor at
minimum operating speed; after that load control are managed by external load set-point.
It is possible to switch back to FIRE only if warm up is not ended yet, to CRANK before firing, to OFF
before start up is initiated.

REMOTE mode
REMOTE mode is equivalent to AUTO, but the start command is given by a remote system (i.e. the CMS)
while the stop command can be generated both remotely and locally.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

34 of 94

4 AUXILIARIES SEQUENCING
4.1

MINERAL LUBE OIL

4.1.1 DEVICE SUMMARY


DEVICE NAME
TL-1
PL-1
PL-2
PL-3
88QA-1
88QE-1
FL-1A/B
96QL1
LT-TH-1A
LT-TH-1B
LT-TH-1C
LT-BT1D
LT-BID
LT-B2D
LT-B3D
LT-B4D
------96QQ-1
96QA-1
LT-OT-1
96QV-1A/B/C

CUSTOMER TAG
C-231-001A-TK2
C-231-001A-P5
C-231-001A-P6
C-231-001A-P7
C-231-001A-P6-M
C-231-001A-P7-M
C-231-001A-F13A/B
231-LIT-5086A
231-TE-5159A1A
231-TE-5159A2A
231-TE-5159A3A
231-TE-5097A
231-TE-5098A
231-TE-5099A
231-TE-5100A
231-TE-5101A
231-PIT-5133A1
231-PIT-5133A2
231-PIT-5133A3
231-PDIT-5094A
231-PIT-5091A
231-TE-5088AA
231-PDIT-5087A1/A2/A3

DESCRIPTION
LUBE OIL TANK (ACCESSORY BASE)
MAIN LUBE OIL PUMP
AUXILIARY LUBE OIL PUMP
EMERGENCY LUBE OIL PUMP
AUXILIARY LUBE OIL PUMP MOTOR
EMERGENCY LUBE OIL PUMP MOTOR
LUBE OIL DUPLEX FILTERS
LUBE OIL TANK LEVEL
LUBE OIL HEADER TEMPERATURE
LUBE OIL HEADER TEMPERATURE
LUBE OIL HEADER TEMPERATURE
THRUST BRG. #1 DRAIN OIL TEMPERATURE
JOURNAL BRG. #1 DRAIN OIL TEMPERATURE
JOURNAL BRG. #2 DRAIN OIL TEMPERATURE
JOURNAL BRG. #3 DRAIN OIL TEMPERATURE
JOURNAL/THRUST BRG.#4 DRAIN OIL TEMP.
LUBE OIL HEADER PRESSURE
LUBE OIL HEADER PRESSURE
LUBE OIL HEADER PRESSURE
LUBE OIL FILTER DIFF. PRESSURE
LUBE OIL PUMP DISCHARGE PRESSURE
LUBE OIL TANK TEMPERATURE
LUBE OIL TANK PRESSURE

4.1.2 SOFTWARE DESCRIPTION


Auxiliary pump logic
Request during unit startup
During startup, if permissive from process is detected (tertiary seal header pressure not low), the auxiliary pump
starts when the turbine start sequence is activated. It continues to operate until the HP shaft reaches minimum
operating speed (L14HSX). From this point, the main mechanical lube oil pump will provide the necessary oil
pressure.
The pump can also be started if one of the following conditions is verified:
Process hydraulic oil request
Request during normal operation
When HP shaft is above minimum operating speed, the auxiliary pump starts if one of the following conditions is
verified for more than 2.5 s:
The lube oil header pressure is detected low by 231-PIT-5133A1, 231-PIT-5133A2, 231-PIT-5133A3
The lube oil pumps discharge pressure is detected low. (96QA-1 (231-PIT-5091A) ).
During normal operation, when auxiliary pump start is detected by 52QA-1 (231- XS-100I), alarm is generated.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

35 of 94

Stop during normal operation


If, during normal operation, the pump has been started, detected by 52QA-1 (231- XS-100I), the pump remains
running also if starting conditions are reset. Operator from HMI or from MCC can stop it manually.
Request during shutdown
After a unit shutdown, the auxiliary pump is started when the HP shaft decreases below the minimum operating
speed. The pump remains running till the cool down is completed (L62CD).
Manual control
If lube oil tank level is not detected low by 96QL1 (231-LIT-5086A), auxiliary pump can be manually started.
If manual operation is de-selected, the pump return to automatic control and can be stopped as described
above.
Emergency pump logic
The emergency pump provides lube oil pressure in case of failure of auxiliary pump. It is requested to run
each time the lube oil pressure is detected low by median value of 231-PIT-5133A1, 231-PIT-5133A2 and
231-PIT-5133A3. The emergency pump actually runs if one of the following enabled conditions is detected:
During normal operation: after start passed (L4) or if GT shaft is detected moving.
During cool down: the first time slice (15 min) of cool down, the emergency pump is always enabled.
Then it is periodically enabled starting with ON period of length 30s and an OFF period of length 3 min.
This mode ends when cool down is ended (L62CD).
Once emergency pump has started, it stops when the pressure is detected normal by median value of 231PIT-5133A1, 231-PIT-5133A2 and 231-PIT-5133A3.
Alarms and trips
If emergency pump is detected running by feedback (52QE-1), alarm is generated.
<4>
If lube oil emergency pump overload is detected (49QE), alarm is generated
Lube oil alarm and trips
If lube oil header temperature LT-TH-1A (231-TE-5159A1A), LT-TH-1B (231-TE-5159A2A), LT-TH-1C
(231-TE-5159A3A) is detected higher than High Alarm threshold, alarm is generated.
If lube oil header temperature LT-TH-1A (231-TE-5159A1A), LT-TH-1B (231-TE-5159A2A), LT-TH-1C
(231-TE-5159A3A) is detected very high by voting trip logic, trip and alarm are generated.
If lube oil header pressure which is median of 231-PIT-5133A1, 231-PIT-5133A2 and 231-PIT-5133A3, is
lower than the low threshold alarm is generated. Also alarm is generated after start-passed (L4) till cool
down end.
If lube oil header pressure is detected low low by 231-PIT-5133A1, 231-PIT-5133A2 and 231-PIT5133A3 voting trip logic trip is generated. Also trip and alarm are generated if unit is running (L4).
If lube oil pumps discharge pressure is detected low 96QA-1 (231-PIT-5091A), output is generated. Also
alarm is generated after start-passed (L4) till cool down end.
If lube oil filter differential pressure is detected high (96QQ-1 (231-PDIT-5094A) ) for more than 1 s,
alarm is generated
If lube oil tank level is detected high by 96QL1 (231-LIT-5086A), alarm is generated.
If lube oil tank level is detected low by 96QL1 (231-LIT-5086A), alarm is generated
If at least one bearing drain oil temperature is detected higher than its threshold, summarized alarm is
generated.
Cooldown
After the coast down, cooldown indicate the time period in which the lube oil is provided by using the
auxiliary or the emergency pumps.
Cooldown is enabled each time the flame is detected in combustion chamber (28FDX signal from MKVIe)
resetting cooldown timer.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
REVISED
WHERE
SHOWN <4>
NO REVISION
INTRODUCED
IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

36 of 94

Cooldown timer starts counting after a coast down as soon as the GT shaft is detected at zero speed
(L14HR) (signal from MKVIe). Cooldown will be completed after 10 hours. Cooldown end is detected by
signal L62CD signal.
The VTR-1 valve is actuated on the base LT-TH-1A (231-TE-5159A1A), LT-TH-1B (231-TE-5159A2A), LTTH-1C (231-TE-5159A3A) signal; inside the software an internal PI controller is activated.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

37 of 94

4.2

OIL VAPOUR SEPARATOR

4.2.1 DEVICE SUMMARY


DEVICE NAME
PDS-1
QV-1
QV-2

CUSTOMER TAG
C-231-001A-F18
C-231-001A-BL2A
C-231-001A-BL2B

88QV-1

C-231-001A-BL2A-M

88QV-2

C-231-001A-BL2B-M

DESCRIPTION
MINERAL OIL VAPOUR SEPARATOR
MAIN VAPOUR EXTRACTOR
AUXILIARY VAPOUR EXTRACTOR
MAIN MINERAL OIL VAPOUR
SEPARATOR FAN MOTOR
AUXILIARY MINERAL OIL VAPOUR
SEPARATOR FAN MOTOR

4.2.2 SOFTWARE DESCRIPTION


Oil vapor separator fan sequence
Two vapor separator fan motors are provided: Fan selection (main, auxiliary) is done by HMI dedicated
pushbuttons, normally when both fans are stopped. Selection can be changed, also if main fan is running. At
changeover, the new selected main fan starts immediately; the deselected fan continues to run for 10
seconds, then it is stopped.
This changeover sequence doesn't activate auxiliary fan running alarm.
If changeover is done when both fans are running or both are stopped, nothing changes except the
selection.
Manual fans command
If all start permissive conditions are verified and all cutoffs conditions are not verified, each fan can be
manually started and stopped.
The main lube oil vapor separator fan motor is started when the flame is detected in the combustion
chambers. The fan continues to run until the cooldown sequence is completed (L62CD).
The fan is also started if the following conditions are all verified:
Lube oil heater ON command
Normal temperature in oil tank.
Oil vapor separator fan manual operation
When fan extractor is not required running, the lube oil vapor separator fan motor 88QV-1 can be manually
started and stopped.
Lube oil tank pressure alarms and trips
If lube oil tank pressure is detected high 96QV-1A/B/C (231-PDIT-5087A1/A2/A3), alarm is generated and
the auxiliary vapor separator fan motor is started.
If lube oil tank pressure is detected very high (trip level) by voting logic 96QV-1A/B/C (231-PDIT5087A1/A2/A3), trip and alarm are generated.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

38 of 94

4.3

LUBE OIL HEATER

4.3.1 DEVICE SUMMARY


DEVICE NAME
23QT-1
23QT-2
23QT-3

CUSTOMER TAG
C-231-001A-H5A
C-231-001A-H5B
C-231-001A-H5C

49QT-1

231-TSHH-5085A

49QT-2

231-TSHH-5086A

49QT-3

231-TSHH-5087A

DESCRIPTION
LUBE OIL ELECTRIC HEATER
LUBE OIL ELECTRIC HEATER
LUBE OIL ELECTRIC HEATER
LUBE OIL HEATER CUT-OUT SIGNAL TO
MARKVIE
LUBE OIL HEATER CUT-OUT SIGNAL TO
MARKVIE
LUBE OIL HEATER CUT-OUT SIGNAL TO
MARKVIE

4.3.2 SOFTWARE DESCRIPTION


The unit its also equipped with 23QT1/2/3 lube oil heaters. The purpose of lube oil heater system is to
provide a correct viscosity of mineral lube oil acting on its temperature.
To provide heater start/stop commands, the system is equipped with the temperature element LT-OT-1 (231TE-5088AA).
Heater cutout logic
Cutout conditions for lube oil heater on command auxiliary signal are listed below:
Lube oil tank level low 96QL1 (231-LIT-5086A)
Flame detected (L28FDX)
Over-temperature detected by all lube oil tank heaters temperature switches 49QT-1/2/3 (231-TSHH5085A/5086A/5087A)
Each heater is then singularly cutout if the relative switch 49QT-1/2/3 (231-TSHH-5085A/5086A/5087A)
detects over-temperature. Also, cutout signal is repeated to MCC namely 4QT1_C (231-XS-720), 4QT2_C
(231-XS-722), 4QT3_C (231-XS-723) if one of the following conditions is detected:
Lube oil tank level low 96QL1 (231-LIT-5086A)
Over-temperature detected by the lube oil tank heater temperature switches 49QT-1/2/3 (231-TSHH5085A/5086A/5087A)
If over-temperature is detected by at least one lube oil tank heater temperature switches 49QT-1/2/3 (231TSHH-5085A/5086A/5087A) alarm is generated.
Heater control logic
If no cutout condition is active for the heater on, 23QT1/2/3 are started when the oil temperature is detected low
by the low threshold on LT-OT-1 (231-TE-5088AA) temperature value. They are stopped when the oil
temperature is detected moderate by the high threshold on LT-OT-1 (231-TE-5088AA). Between the two
thresholds, 23QT-1/2/3 can be manually stopped down also by HMI pushbutton.
If manual command is active, 23QT-1/2/3 can be started and stopped manually by HMI pushbutton. Also, if
manual operation is active an alarm is generated.
If oil temperature is below a low low threshold, an alarm is generated. It inhibits the turbine start and crank.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

39 of 94

4.4

LUBE OIL WATER COOLER

4.4.1 DEVICE SUMMARY


---

DEVICE NAME

CUSTOMER TAG
231-TY-5159A

VTR-1

231-TCV-5159A

DESCRIPTION
VTR-1 THERMOSTATIC VALVE
CONTROL I TO P CONVERTOR
LUBE OIL THERMOSTATIC VALVE

4.4.2 SOFTWARE DESCRIPTION


Start-Up and Normal Operation
The Lube Oil Temperature Regulator Valve VTR-1 (231-TCV-5159A) is enabled to control (set point=55C)
the lube oil header temperature LT-TH-1A (231-TE-5159A1A), LT-TH-1B (231-TE-5159A2A), LT-TH-1C
(231-TE-5159A3A) at the beginning of the Start-up sequence, just after the Emergency Auxiliaries Check,
and it is disabled and close at the end of the cool-down subsequently to the stoppage of the Lube Oil
Auxiliary Pump 88QA-1(C-231-001A-P6-M).
231-TCV-5159A (VTR-1) valve will be controlled by MKVIE through 4-20mA command to I/P converter 231TY-5159A.
Manual Operation
This is a One State Auxiliary, manual mode is not permitted at all.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

40 of 94

4.5

CONTROL OIL

4.5.1 DEVICE SUMMARY


DEVICE NAME
65NV-1
90TV-1
96TV-1
96TV-2
96NC-1
96NC-2
20HD-1
20HD-2
96HG-1A
96HG-1B
96HG-1C

CUSTOMER TAG
231-FCV-5124A
231-FCV-5125A
231-ZT-5125A1
231-ZT-5125A2
231-ZT-5124A1
231-ZT-5124A2
231-XX-5122A
231-XX-5123A
231-PIT-5121A1
231-PIT-5121A2
231-PIT-5121A3

DESCRIPTION
NOZZLE CONTROL SERVO VALVE
TURBINE IGV ACTUATION
TURBINE IGV POSITION
TURBINE IGV POSITION
ND
TURBINE 2 STAGE NOZZLES POSITION
ND
TURBINE 2 STAGE NOZZLES POSITION
CONTROL OIL TRIP
CONTROL OIL TRIP
CONTROL OIL HEADER PRESS.
CONTROL OIL HEADER PRESS.
CONTROL OIL HEADER PRESS.

4.5.2 SOFTWARE DESCRIPTION


Control oil pressure triple redundant transmitters validation (TMR)
Because of this is a critical loop, TMR architecture requires triple redundancy of measurements. The three
signals are median selected so that a single measurement failure is distinguished from system fails.
The selected value, A63HG_W, is used for succeeding elaborations.
If measurements spread is higher than maximum spread allowed K63HG_FLT for more than
K63HGL_SENSR (typically 2 s), alarm L63HGL_SENSR is generated.
Control oil pressure triple redundant switches (mixt) validation (TMR)
Starting at ignition phase during normal operation (L4=TRUE), if one of the three switches detects trip, but
trip is not detected for more than K63HGL_SENSR (typically 2 s), alarm L63HGL_SENSR is generated. In
case of mixt instrumentation, same logic apply with one switch reading substituted by condition L63HG1_L,
corresponding to the transmitter signal below trip level (K63HGT).
Control oil excessively low pressure (critical)
Excessively low pressure is detected:
Transmitters: 2oo3 voting of (L63HGL1_W, l26hg2l, l26hg3l).
If control oil pressure is detected excessively low, signal L63HGL is generated.
Also, trip L63CO_TRP is generated after ignition phase during normal operation (L4=TRUE) and alarm
L63HGL_ALM is generated starting at ignition (L2TVX).
The transmitters 231-PIT-5121A1/A2/A3 (96HG-1A/B/C) are wired to MarkVIeS and when 2oo3 sensors
detect a low-low condition, a trip condition is generated.
Trip system healthy monitoring
Fuel valves and variable geometries are driven to safe position by de-energizing 20HD-1 valve. This
happens immediately when a trip is detected or at flameout in case of shutdown.
The de-energizing of 20HD-1 must assure a rapid decrease of control oil pressure. If, elapsed one second
from a trip, control oil pressure is not below trip level K63HGT, alarm L86HD_ALM is generated and the unit
becomes not ready to start through L86HD latched signal resettable by master reset (L86MR1).
The actuation of the 20HD-1 and 20HD-2 is done from MarkVIeS

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

41 of 94

4.6

HYDRAULIC OIL

4.6.1 DEVICE SUMMARY

DEVICE NAME
PH-1
PH-2
88HQ
FH1-1/2
96HQ-1
96HF-1
33HR-1
20CS-1

CUSTOMER TAG
C-231-001A-P2
C-231-001A-P3
C-231-001A-P3-M
C-231-001A-F8A/B
231-PIT-5114A
231-PDIT-5113A
231-ZSL-5119A
231-FV-5114A

DESCRIPTION
HYDRAULIC OIL MAIN PUMP
HYDRAULIC OIL AUXILIARY PUMP
HYDRAULIC OIL AUXILIARY PUMP MOTOR
HYDRAULIC OIL DUPLEX FILTERS
HYDRAULIC OIL HEADER LOW PRESSURE
HYDRAULIC OIL FILTERS HIGH DIFF. PRESS.
HYD. RATCHET VALVE POSITION CLOSED
HYD. RATCHET SELF-SEQUENCING VALVE

4.6.2 SOFTWARE DESCRIPTION


Auxiliary pump logic
Cutout condition
If lube oil header pressure is not detected normal by 231-PIT-5133A1, 231-PIT-5133A2 and 231-PIT-5133A3,
the hydraulic pump requests described below is cutout.
When unit is stopped (L14HR), if the cutout condition is active for more than 10s from hydraulic pump start
request, alarm is generated.
When unit is running, if the cutout condition is active, alarm is generated.
In case of lube oil pressure low voting trip by 231-PIT-5133A1, 231-PIT-5133A2 and 231-PIT-5133A3, cutout
to MCC is generated.
Request during unit startup
If cutout condition is not active, during startup the auxiliary pump starts when the turbine start sequence is
activated. It continues to operate until the HP shaft reaches minimum operating speed. From this point, the main
mechanical hydraulic oil pump will provide the necessary oil pressure.
Request during normal operation
When HP shaft is above minimum operating speed, if cutout condition is not active, the auxiliary pump starts if
Hydraulic oil pressure detected low by pressure transmitter 96HQ-1 (231-PIT-5114A).
During normal operation when hydraulic pump start detected by 52HQ, alarm is generated.
Stop during normal operation
If during normal operation the pump gets started, detected by 52HQ, the pump remains running, also when the
starting condition is reset. Operator from HMI or MCC can stop it manually.
Request during shutdown
If cutout condition is not active, when a normal shutdown occurs, the auxiliary pump is started when the HP
shaft decreases below the minimum operating speed. The pump will keep running till the master relay (L4) is
de-energized.
If emergency shutdown (trip) is detected, L4 drop down and consequently the hydraulic pump is not started.
Manual control
If cutout condition is not active, auxiliary pump can be manually started. If manual operation is deselected, the
pump return to automatic control and can be stopped as described above.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

42 of 94

Alarms logic
If hydraulic oil pressure is detected low by 96HQ-1 (231-PIT-5114A), for more than 3s, alarm is generated.
Alarm is generated if all the following conditions are verified:
Above crank speed (L14HM)
After start passed and before shutdown (L4)
If hydraulic oil filter differential pressure is detected high by 96HF-1 (231-PDIT-5113A) for more than 1s, alarm
is generated.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

43 of 94

4.7

STARTING

4.7.1 DEVICE SUMMARY


DEVICE NAME
33CS-1
20TU-1
88CR-1
PS-1

CUSTOMER TAG
231-ZSL-5181A
231-XX-5181A
C-231-001A-P8-M
C-231-001A-P8

DESCRIPTION
STARTING CLUTCH POSITION ENGAGED
TORQUE CONVERTER OIL DRAIN
STARTING MOTOR
CHARGE PUMP FOR TORQUE CONVERTER

4.7.2 SOFTWARE DESCRIPTION


Hydraulic ratchet interface logic
When the unit is ready to crank, hydraulic ratchet system energizes the starting clutch solenoid 20CS-1 (231FV-5114A). If the starting clutch is not detected engaged within 10 seconds, alarm is generated.
The turbine shaft breakaway is helped by hydraulic ratchet system that is stopped as soon as shaft moves.
88CR-1 command permissive
Auxiliaries ready to crank
Loss of feedback event (~l52cr) elapsed from more than 20s, detected by 52CR-1 (231-XS-515I) signal.
88CR-1 turn-on command logic
When starting clutch is detected engaged by 33CS-1 (231-ZSL-5181A) , cranking motor 88CR-1 is started
through 4CR_1A (231-XS-515R) signal.
If motor feedback from MCC 52CR-1 (231-XS-515I) is not detected within 2 seconds, trip and alarm are
generated (sequence aborted).
If motor feedback is detected but HP shaft doesn't break away (L14HR) within 30 seconds, trip and alarm are
generated (sequence aborted).
Cranking speed logic
After shaft break away, when the minimum cranking speed is achieved, the torque converter oil drain valve
20TU-1 (231-XX-5181A) is opened, in order to reduce the torque and to maintain the specified speed to
accomplish purge, ignition and warm-up steps. Signal OPENING is enabled by L4 to avoid the opening of the
valve during coast down. The valve will be closed again after warm-up step completes, in order to have the
maximum torque for accelerating phase.
If motor feedback 52CR-1 (231-XS-515I) or clutch engaged limit switch 33CS-1 (231-ZSL-5181A) signals
are lost, trip and alarm are generated. Alarm and trip are enabled below accelerating speed and are disabled
above the operative speed and in case of trip.
88CR-1 turn-off logic
After warm-up sequence, unit accelerates to full speed. At approx. 5060% of rating speed, the inversion of
the torque on starting clutch causes its mechanical disengagement (the turbine can sustain itself). This
condition is detected by 33CS-1 (231-ZSL-5181A) limit switch signal and the cranking motor is turned off.
The motor is anyway turned off if HP shaft speed is above self-sustaining speed (60%). and above operative
speed. If starting clutch doesn't disengage when the HP shaft speed is above the minimum operating speed,
trip and alarm are generated.
Motor turn-off is also achieved if one of the following conditions is verified:
system trip
unit trip
unit shutdown

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

44 of 94

4.8

HYDRAULIC RATCHETING

4.8.1 DEVICE SUMMARY


DEVICE NAME
PH-3
88HR
FH-2
43HR

CUSTOMER TAG
C-231-001A-P4
C-231-001A-P4-M
C-231-001A-F9
231-HS-5109A

33HR-1

231-ZSL-5119A

20CS-1

231-FV-5114A

33CS-1

231-ZSL-5181A

DESCRIPTION
RATCHET PUMP
HYDRAULIC RATCHET MOTOR
HYDRAULIC RATCHET OIL FILTER
HYDRAULIC RATCHET PUMP MOTOR TEST
HYDR. RATCHET VALVE POSITION
CLOSED
HYDRAULIC RATCHET SELF SEQUENCING
VALVES
STARTING CLUTCH POSITION ENGAGED

4.8.2 SOFTWARE DESCRIPTION


The sequence described is used to describe ratchet pump motor (88HR) start command (4HR1) and starting
clutch engaging command 20CS-1 (231-FV-5114A). The two ratcheting commands are generated at the
same time by the same logic. The clutch engaged is detected by limit switch 33CS-1 (231-ZSL-5181A) signal
that cause the cranking motor to start.
Push button 43HR (231-HS-5109A) is installed to provide manual start of motor 88HR.
Ratcheting commands cutout
Lube oil pressure low voting trip logic
HP shaft control speed signal loss
HP shaft above crank speed
Unit start-up ratcheting sequence
During the unit starting sequence, if no cutout and all permissive conditions verified, the ratcheting begin as soon
as the ready to crank is detected. It continues to operate until the HP shaft speed is detected.
Ratcheting cycles during cooldown
During a stop sequence, the ratchet pump is started 60 seconds after the HP shaft is detected at zero speed by
L14HR; independently from the state of, the pump remains running and rotating the shaft until the 33HR-1 (231ZSL-5119A) limit switch drop down delayed of 2s is detected. At this point the pump is kept stopped for 180 s,
and then the cycle is repeated. Cooldown ratcheting cycles are stopped when cooldown sequence is completed.
Manual ratcheting (Jogging)
When GT is stopped, a ratcheting cycle can be started manually (jogging) acting on the local push-button
mounted on the ratchet pump skid 43HR (231-HS -5109A) or by HMI push button. Note that the local push
button has to be closed for more than 2 s to activate the jogging command.
Usually jogging is required after cooldown: as lube oil header pressure low cutout condition (L63QT) is detected,
jogging command causes first the lube oil emergency pump starting, and then, when the cutout condition is
reset, a jogging cycle.
As for cooldown ratcheting, a jogging cycle stops 2s after the drop down of hydraulic ratchet limit switch (33HR-1
(231-ZSL-5119A) )
Alarms, trips and monitoring
If, during cooldown ratcheting, limit switch (33HR-1 (231-ZSL-5119A) )
generated. The alarm is disabled at the end of cooldown.
If ratcheting cycle is longer than 30s, alarm is generated.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

is not detected for 6 minutes, alarm is

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

45 of 94

If hydraulic ratchet motor overload is detected (49HR), alarm is generated.


Hydraulic ratchet pump running is detected (72HR) for monitoring purposes.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

46 of 94

4.9

BEARING METAL TEMPERATURE

TURBINE BEARINGS

4.9.1 DEVICE SUMMARY


DEVICE NAME
BT-TA1-1A
BT-TI1-1A
BT-J1-1A
BT-J1-2A
BT-TA1-2A
BT-TI1-2A
BT-J2-1A
BT-J2-2A
BT-J3-1A
BT-J3-2A
BT-TA4-1A
BT-TI4-1A
BT-J4-1A
BT-J4-2A
BT-TA4-2A
BT-TI4-2A

CUSTOMER TAG
231-TE-5061AA
231-TE-5062AA
231-TE-5063AA
231-TE-5064AA
231-TE-5066AA
231-TE-5065AA
231-TE-5067AA
231-TE-5068AA
231-TE-5069AA
231-TE-5070AA
231-TE-5073AA
231-TE-5072AA
231-TE-5071AA
231-TE-5083AA
231-TE-5074AA
231-TE-5075AA

DESCRIPTION
CASE BEARING 1 TEMP (THRUST ACTIVE)
CASE BEARING 1 TEMP (THRUST INACTIVE)
CASE BEARING 1 TEMP (JOURNAL)
CASE BEARING 1 TEMP (JOURNAL)
CASE BEARING 1 TEMP (THRUST ACTIVE)
CASE BEARING 1 TEMP (THRUST INACTIVE)
CASE BEARING 2 TEMP (JOURNAL)
CASE BEARING 2 TEMP (JOURNAL)
CASE BEARING 3 TEMP (JOURNAL)
CASE BEARING 3 TEMP (JOURNAL)
CASE BEARING 4 TEMP (THRUST ACTIVE)
CASE BEARING 4 TEMP (THRUST INACTIVE)
CASE BEARING 4 TEMP (JOURNAL)
CASE BEARING 4 TEMP (JOURNAL)
CASE BEARING 4 TEMP (THRUST ACTIVE)
CASE BEARING 4 TEMP (THRUST INACTIVE)

4.9.2 SOFTWARE DESCRIPTION


One element of each bearing metal RTD is wired to the Bently Nevada Temperature Monitoring System and
the temperature reading is compared to the alarm set-point. If measured temperature of individual elements
exceeds its set-point, individual alarm is generated.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

47 of 94

COMPRESSOR BEARINGS

4.9.3 DEVICE SUMMARY


DEVICE NAME

CUSTOMER TAG

---

231-TE-5133AA

---

231-TE-5134AA

---

231-TE-5135AA

---

231-TE-5136AA

---

231-TE-5139A1A

---

231-TE-5139A2A

---

231-TE-5139A3A

---

231-TE-5140A1A

---

231-TE-5140A2A

---

231-TE-5140A3A

DESCRIPTION
THERMOELEMENT ON COMPRESSOR
JOURNAL BEARING
THERMOELEMENT ON COMPRESSOR
JOURNAL BEARING
THERMOELEMENT ON COMPRESSOR
JOURNAL BEARING
THERMOELEMENT ON COMPRESSOR
JOURNAL BEARING
THERMOELEMENT ON COMPRESSOR
THRUST BEARING (ACTIVE)
THERMOELEMENT ON COMPRESSOR
THRUST BEARING (ACTIVE)
THERMOELEMENT ON COMPRESSOR
THRUST BEARING (ACTIVE)
THERMOELEMENT ON COMPRESSOR
THRUST BEARING (INACTIVE)
THERMOELEMENT ON COMPRESSOR
THRUST BEARING (INACTIVE)
THERMOELEMENT ON COMPRESSOR
THRUST BEARING (INACTIVE)

4.9.4 SOFTWARE DESCRIPTION


Alarm and Trip logic:
One element of each bearing metal RTD on the Compressor Journal Bearing (231-TE-5133AA, 231TE-5134AA, 231-TE-5135AA and 231-TE-5136AA) is wired to the Bently Nevada Temperature
Monitoring System and the temperature reading is compared to the alarm set-point. If measured
temperature of individual elements exceeds its set-point, individual alarm is generated.
For thermo elements on CC Thrust bearings Active side (231-TE-5139A1A, 231-TE-5139A2A and
231-TE-5139A3A) as well as for CC Thrust bearings Inactive side (231-TE-5140A1A, 231-TE5140A2A and 231-TE-5140A3A) for HH temperature, Trip condition is initiated. The trip notification
is sent to MarkVIe for time stamping.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

48 of 94

4.10 WHEELSPACES
4.10.1 DEVICE SUMMARY
DEVICE NAME
TT-WS1FI-1
TT-WS1FI-2
TT-WS1AI-1
TT-WS1AI-2

CUSTOMER TAG
231-TE-5079A1
231-TE-5079A2
231-TE-5082A1
231-TE-5082A2

TT-WS2FI-1

231-TE-5080A1

TT-WS2FI-2

231-TE-5080A2

TT-WS2AI-1
TT-WS2AI-2

231-TE-5081A1
231-TE-5081A2

DESCRIPTION
st
WHEEL SPACE TEMP. 1 STAGE FWD INNER #1
st
WHEEL SPACE TEMP. 1 STAGE FWD INNER #2
st
WHEEL SPACE TEMP. 1 STAGE AFT INNER #1
st
WHEEL SPACE TEMP. 1 STAGE AFT INNER #2
nd
WHEEL SPACE TEMP. 2 STAGE FWD INNER
#1
nd
WHEEL SPACE TEMP. 2 STAGE FWD INNER
#2
nd
WHEEL SPACE TEMP. 2 STAGE AFT INNER #1
nd
WHEEL SPACE TEMP. 2 STAGE AFT INNER #2

4.10.2 SOFTWARE DESCRIPTION


Alarms and Shutdown logic
There are single element thermocouples (TC) in each measurement location to monitor the wheel space
temperature. For each measurement section, the average temperature is calculated by the two TC.
If the average temperature exceeds the alarm level for more than 10s, a common alarm is generated.
If alarm level is reached continuously for more than 24 hours, alarm signal is generated and shutdown
sequence starts.
If the average temperature exceeds the shutdown level for more than 10s, a common alarm is generated that
cause shutdown sequence to start.
Water Wash Permissive
All of the average wheel space temperature values are compared against each other and the highest value
is selected. This value is then compared to a started threshold, to provide water wash permissive signal.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

49 of 94

4.11 SEISMIC VIBRATION


4.11.1 DEVICE SUMMARY

DEVICE NAME

CUSTOMER TAG

DESCRIPTION

39V-1A
39V-1B
39V-2A
39V-2B

231-VE-5061A1
231-VE-5061A2
231-VE-5062A1
231-VE-5062A2

HP SHAFT VIBRATION
HP SHAFT VIBRATION
LP SHAFT VIBRATION
LP SHAFT VIBRATION

4.11.2 SOFTWARE DESCRIPTION


The Seismic Vibration signals are wired to the BN3500 vibration monitoring system.
Alarm and trip logic
If one of sensor (39V-1A (231-VE-5061A1) 39V-1B (231-VE-5061A2), 39V-2A (231-VE-5062A1), 39V-2B
(231-VE-5062A2) ) reaches alarm level for more than 5s, alarm is generated.
If a sensor reaches trip level for more than 0.5s while a second sensor value is above alarm level, trip and
alarm are generated.
Inside each pair of sensors 39V-1A (231-VE-5061A1) 39V-1B (231-VE-5061A2) and 39V-2A (231-VE5062A1), 39V-2B (231-VE-5062A2) ), vibration differential calculation is done. If the differential is higher than
a threshold for more than 0.5s, alarm is generated.
In case of unhealthy or disabled sensors, the relative signals are discarded and alarm/trip logic is modified as
follows to maintain the reliability of operation (lowering availability):
One sensor faulty or disabled: nothing changes except that only the enabled and healthy signals are
taken into account. This is because of transmissibility of vibration between the two pairs: it assures
that trip level on the first pair is sensed at least at alarm level on the second pair.
Two sensors faulty or disabled: trip logic is based on only one sensor. If the two faulty or disabled
sensors belong to the same pair, shutdown signal L39VD2 and L39VD2_ALM alarm are generated
Trip notification is hardwired from BN to MarkVIeS.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

50 of 94

4.12 MAGNETIC SPEED PICK-UP


4.12.1 DEVICE SUMMARY

DEVICE NAME

DESCRIPTION

77NH-1

CUSTOMER
TAG
231-SE-5061A1

77NH-2

231-SE-5061A2

HP SHAFT MAGNETIC SPEED PICKUP WIRED (TO MARKVIES)

77NH-3

231-SE-5061A3

HP SHAFT MAGNETIC SPEED PICKUP WIRED (TO MARKVIES)

77NL-1

231-SE-5063A1

LP SHAFT MAGNETIC SPEED PICKUP WIRED (TO MARKVIES)

77NL-2

231-SE-5063A2

LP SHAFT MAGNETIC SPEED PICKUP WIRED (TO MARKVIES)

77NL-3

231-SE-5063A3

LP SHAFT MAGNETIC SPEED PICKUP WIRED (TO MARKVIES)

77HT-1
77HT-2
77HT-3
77LT-1

231-SE-5062A1
231-SE-5062A2
231-SE-5062A3
231-SE-5064A1

HP SHAFT MAGNETIC SPEED PICKUP WIRED (TO MARKVIES)


HP SHAFT MAGNETIC SPEED PICKUP WIRED (TO MARKVIES)
HP SHAFT MAGNETIC SPEED PICKUP WIRED (TO MARKVIES)
LP SHAFT MAGNETIC SPEED PICKUP WIRED (TO MARKVIES)

77LT-2

231-SE-5064A2

LP SHAFT MAGNETIC SPEED PICKUP WIRED (TO MARKVIES)

77LT-3

231-SE-5064A3

LP SHAFT MAGNETIC SPEED PICKUP WIRED (TO MARKVIES)

HP SHAFT MAGNETIC SPEED PICKUP WIRED (TO MARKVIES)

4.12.2 SOFTWARE DESCRIPTION


The median value of the magnetic pick-up signals for HP shaft 77NH-1(231-SE-5061A1), 77NH-2(231-SE5061A2) and 77NH-3(231-SE-5061A3) as well as the median value of the magnetic pick-up signals for LP
shaft 77NL-1(231-SE-5063A1), 77NL-2(231-SE-5063A2) and 77NL-3(231-SE-5063A3) are sent to Mark Vie
for Turbine Control.
The median value of the magnetic pick-up signals for HP shaft 77HT-1(231-SE-5062A1), 77HT-2(231-SE5062A2) and 77HT-3(231-SE-5062A3) as well as the median value of the magnetic pick-up signals for LP
shaft 77LT-1(231-SE-5064A1), 77LT-2(231-SE-5064A2) and 77LT-3(231-SE-5064A3) are sent to MarkVIeS
and upon detection of High-high condition the gas turbine is tripped.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

51 of 94

4.13 COMBUSTION CHAMBER FLAME DETECTOR

4.13.1 DEVICE SUMMARY

DEVICE NAME

DESCRIPTION

28FD-2

CUSTOMER
TAG
231-BE-5061A1

28FD-3

231-BE-5061A2

COMBUSTION CHAMBER FLAME DETECTOR

28FD-10

231-BE-5061A3

COMBUSTION CHAMBER FLAME DETECTOR

28FD-11

231-BE-5061A4

COMBUSTION CHAMBER FLAME DETECTOR

COMBUSTION CHAMBER FLAME DETECTOR

4.13.2 SOFTWARE DESCRIPTION


All 4 detectors 28FD-2 (231-BE-5061A1), 28FD-3 (231-BE-5061A2), 28FD-10 (231-BE-5061A3), 28FD-11
(231-BE-5061A4), are hardwired to MarkVIeS. If 3oo4 detectors do not detect flame inside the combustion
chamber, the Gas Turbine is tripped.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

52 of 94

4.14 INTERFACES WITH BENTLY NEVADA VIBRATION MONITORING SYSTEM


TURBINE BEARINGS

4.14.1 DEVICE SUMMARY


DEVICE NAME
XT-1X
XT-1Y
ZT-1
ZT-2
XPH
XT-2X
XT-2Y
XT-3X
XT-3Y
XT-4X
XT-4Y
ZT-3
ZT-4
XPL

CUSTOMER TAG
231-XT-5063A1
231-XT-5063A2
231-ZT-5061A1
231-ZT-5061A2
231-KT-5061A
231-XT-5064A1
231-XT-5064A2
231-XT-5065A1
231-XT-5065A2
231-XT-5066A1
231-XT-5066A2
231-ZT-5062A1
231-ZT-5062A2
231-KT-5062A

DESCRIPTION
NO CONTACT RADIAL VIBRATION (CASE BRG 1)
NO CONTACT RADIAL VIBRATION (CASE BRG 1)
NO CONTACT AXIAL DISPLACEMENT (CASE BRG 1)
NO CONTACT AXIAL DISPLACEMENT (CASE BRG 1)
KEY PHASOR (CASE BRG 1)
NO CONTACT RADIAL VIBRATION (CASE BRG 2)
NO CONTACT RADIAL VIBRATION (CASE BRG 2)
NO CONTACT RADIAL VIBRATION (CASE BRG 3)
NO CONTACT RADIAL VIBRATION (CASE BRG 3)
NO CONTACT RADIAL VIBRATION (CASE BRG 4)
NO CONTACT RADIAL VIBRATION (CASE BRG 4)
NO CONTACT AXIAL DISPLACEMENT (CASE BRG 4)
NO CONTACT AXIAL DISPLACEMENT (CASE BRG 4)
KEY PHASOR (CASE BRG 4)

4.14.2 SOFTWARE DESCRIPTION


The NO Contact Radial Vibration, NO Contact Axial Displacement and Key-phasor signals are all wired
to BN3500 Vibration Monitoring System.
Alarm Logic:
For high value of NO Contact Radial Vibration signals detected by any one of the sensors, a High
alarm is generated.
For high value of NO Contact Axial Displacement signal detected by any one of the sensors, a High
alarm is generated.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

53 of 94

COMPRESSOR BEARINGS

4.14.3 DEVICE SUMMARY


DEVICE NAME

CUSTOMER TAG

---

231-XT-5133A1

---

231-XT-5133A2

---

231-XT-5134A1

---

231-XT-5134A2

---

231-ZT-5133A1

---

231-ZT-5133A2

---

231-ZT-5133A3

DESCRIPTION
RADIAL VIBRATION PROBE ON
COMPRESSOR JOURNAL BEARING
RADIAL VIBRATION PROBE ON
COMPRESSOR JOURNAL BEARING
RADIAL VIBRATION PROBE ON
COMPRESSOR JOURNAL BEARING
RADIAL VIBRATION PROBE ON
COMPRESSOR JOURNAL BEARING
AXIAL DISPLACEMENT PROBE ON
COMPRESSOR THRUST BEARING
AXIAL DISPLACEMENT PROBE ON
COMPRESSOR THRUST BEARING
AXIAL DISPLACEMENT PROBE ON
COMPRESSOR THRUST BEARING

4.14.4 SOFTWARE DESCRIPTION


The NO Contact Radial Vibration and NO Contact Axial Displacement signals are all wired to BN3500
Vibration Monitoring System.
Alarm and Trip logic:
Radial Vibration:
If 1oo2 probes [231-XT-5133A1 and 231-XT-5133A2] or [231-XT-5134A1 and 231-XT-5134A2]
detects vibration corresponding H set-point, an alarm is generated. If vibration is HH then a Trip
is initiated and a notification is sent to Mark Vie for Time stamping.
If 2oo3 probes [231-ZT-5133A1, 231-ZT-5133A2 and 231-ZT-5133A3] detect axial displacement
corresponding HH set-point, then a Trip is initiated and a notification is sent to Mark Vie for Time
stamping.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

54 of 94

4.15 EXHAUST TEMPERATURE


4.15.1 DEVICE SUMMARY

DEVICE NAME

CUSTOMER TAG

DESCRIPTION

TT-XD-1
TT-XD-2
TT-XD-3
TT-XD-4
TT-XD-5
TT-XD-6
TT-XD-7
TT-XD-8
TT-XD-9
TT-XD-10
TT-XD-11
TT-XD-12
TT-XD-13

231-TE-5176A1
231-TE-5176A2
231-TE-5176A3
231-TE-5176A4
231-TE-5176A5
231-TE-5176A6
231-TE-5176A7
231-TE-5176A8
231-TE-5176A9
231-TE-5176A10
231-TE-5176A11
231-TE-5176A12
231-TE-5176A13

EXHAUST TEMPERATURE
EXHAUST TEMPERATURE
EXHAUST TEMPERATURE
EXHAUST TEMPERATURE
EXHAUST TEMPERATURE
EXHAUST TEMPERATURE
EXHAUST TEMPERATURE
EXHAUST TEMPERATURE
EXHAUST TEMPERATURE
EXHAUST TEMPERATURE
EXHAUST TEMPERATURE
EXHAUST TEMPERATURE
EXHAUST TEMPERATURE

4.15.2 SOFTWARE DESCRIPTION


Alarm and trip logic
When the mean value of the Exhaust Thermocouples is greater than or equal to High value, a
cumulative alarm is generated.
When the mean value of the Exhaust Thermocouples is greater than or equal to High High value, a
Trip is initiated.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

55 of 94

4.16 EXHAUST DUCT BACK PRESSURE


4.16.1 DEVICE SUMMARY

DEVICE NAME

CUSTOMER TAG

DESCRIPTION

96EA-1A
96EA-1B
96EA-1C

231-PDIT-5067A1
231-PDIT-5067A2
231-PDIT-5067A3

EXHAUST DUCT BACK PRESSURE


EXHAUST DUCT BACK PRESSURE
EXHAUST DUCT BACK PRESSURE

4.16.2 SOFTWARE DESCRIPTION


Alarm and trip logic
When the median value of the three transmitters 96EA-1A (231-PDIT-5067A), 96EA-1B (231-PDIT5067B) and 96EA-1C (231-PDIT-5067C) reaches High threshold value an alarm is generated.
When the median value reaches High High threshold value a Trip of the GT is started.
This logic is implemented in MarkVIeS

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

56 of 94

4.17 WATER WASH


4.17.1 DEVICE SUMMARY
DEVICE NAME

CUSTOMER TAG

33ED-4

231-ZSL-5277A

20TW-1
20TW-2

231-XX-5278A
231-XX-5277A

DESCRIPTION
EXHAUST PLENUM DRAIN VALVE VA17-6
CLOSED
ON LINE WASHING WATER SUPPLY
OFF LINE WASHING WATER SUPPLY

4.17.2 SOFTWARE DESCRIPTION


On line water wash sequence
Cutout conditions
Turbine start sequence not ended
Compressor inlet temperature lower than the threshold 50F.
Selection logic
If all cut-out condition are not verified, on-line water wash is selected by HMI pushbutton.
Then, 3 seconds after the selection, the solenoid valve 20TW-1 (231-XX-5278A) is energized.
Water wash is de-activated (and solenoid valve 20TW-1 (231-XX-5278A) is de-energized) whenever on line
water wash is de-selected by pushbutton or a cut-out condition is verified.
Alarms
When the turbine start sequence is ended (L3), if the on line water wash pushbutton is selected while
temperature cut-out condition is verified, alarm is generated.

Off line water wash sequence


Cut-out conditions
Master selector not in CRANK mode
Selection logic:
If cut-out condition is not active, off-line water wash is selected by HMI pushbutton. If sequence is not
already active, off-line water wash is de-selected by HMI pushbutton.
Activation enabling conditions:
Master selector in CRANK mode
HP shaft zero speed detected
Off line water wash selected
Activation logic:
If activation-enabling conditions are all verified, the water wash sequence is activated when the unit is
started.
Water wash cut-out:
Wheel spaces temperature high;
Master protective signal dropped down
Flame detected
HP shaft below crank speed.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

57 of 94

Water wash start:


If all cutout conditions are not verified and water wash sequence is activated, IGV open command is
generated and the cleaning solution intercept valve 20TW-2 (231-XX-5277A) is opened.
Water wash stop:
Once the water wash is started, it is stopped when the unit normal stop is detected.
Alarms:
When the water wash is selected, if wheel spaces temperature permissive is dropped down, alarm is
generated.
Start permissive condition:
If limit switch 33ED-4 (231-ZSL-5277A) closed during starting sequence, alarm is generated and start
permissive inhibited. This logic is implemented in MarkVIeS.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

58 of 94

4.18 VENTILATION
4.18.1 DEVICE SUMMARY
DEVICE NAME
FNVF1/2

CUSTOMER TAG
C-231-001A-BL1A/B

88BA-1/2

C-231-001A-BL1A/B-M

33ID-1
33OD-1
33OD-2
33OD-3
TT-BA-2A
TT-BA-2B
TT-BA-2C

231-ZSH-5242A
231-ZSH-5243A
231-ZSH-5244A
231-ZSH-5245A
231-TE-5241A1
231-TE-5241A2
231-TE-5241A3

96SV-1A

231-PDIT-5241A1

96SV-1B

231-PDIT-5241A2

96SV-1C

231-PDIT-5241A3

TT-BA-3A/B/C

231-TE-5242A1/A2/A3

45HD-1A/B/C

231-AE-5241A1/2/3

45HD-2A/B/C

231-AE-5242A1/2/3

DESCRIPTION
VENTILATION FANS
MAIN & STAND-BY VENTILATION AIR FAN
MOTOR
VENTILATION INLET DAMPER OPEN
ACCESS. COMP. VENTILATION OUTLET OPEN
TURBINE COMP. VENTILATION OUTLET OPEN
COUPL. COMP. VENTILATION OUTLET OPEN
GT COMPART. INTERNAL TEMP
GT COMPART. INTERNAL TEMP
GT COMPART. INTERNAL TEMP
ENCLOSURE PRESSURE WITH RESPECT TO
ATMOSPHERIC PRESSURE
ENCLOSURE PRESSURE WITH RESPECT TO
ATMOSPHERIC PRESSURE
ENCLOSURE PRESSURE WITH RESPECT TO
ATMOSPHERIC PRESSURE
COUPL. COMP. INTERNAL TEMP.
CATALYTIC GAS DETECTORS AT VENTILATION
OUTLET
CATALYTIC GAS DETECTORS AT VENTILATION
OUTLET

4.18.2 SOFTWARE DESCRIPTION


The ventilation system has a dual fan configuration driven by motors 88BA-12. Under normal condition, only
one fan, chosen by the operator as main, is operating, while the other, the auxiliary, is off.
Limit switches are provided to monitor the compartments access doors fully close condition and also to
monitor the fire dampers fully open condition. Median value of 96SV-1A/B/C (231-PDIT-5241A1/2/3) detects
low differential pressure between inside and outside of Accessory-Turbine enclosure. These transmitters
send the signal to SIS. If low differential pressure is detected, ventilation fan switch-over takes place; if
already switched, shutdown of the GT occurs.
Temperature elements are utilized to control turbine compartment outlet temperature (TT-BA-2A (231-TE5241 A1) / TT-BA-2B (231-TE-5241 A2) / TT-BA-2C (231-TE-5241 A3)) and (TT-BA-3A (231-TE-5242 A1) /
TT-BA-3B (231-TE-5242 A2) / TT-BA-3C (231-TE-5242 A3))
Ventilation Start permissive conditions:
Fire dampers fully open.
Ventilation cutout conditions:
Turbine enclosure fire detected trip, detected by fire-fighting system interface signal 45FTT ;
Turbine enclosure Inergen discharged trip, detected by fire-fighting system interface signal 63CPD
(generated inside FF.
In addition ventilation cut out signals are sent from SIS directly to MCC (4BA1_C, 4BA2_C). This redundancy
ensures that the fans do not operate during fire or extinguishing action of Inergen.
Main/Auxiliary selection and changeover
Fan selection is done by HMI dedicated pushbuttons, normally when both fans are stopped. Selection can be
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

59 of 94

changed, also if main fan is running. At changeover, the new selected main fan starts immediately; the
deselected fan continues to run for 10 seconds, then it is stopped.
This changeover sequence doesn't activate auxiliary fan running alarm.
If changeover is done when both fans are running or both are stopped, nothing changes except the
selection.
If turbine compartment pressure detected by (96SV-1A/B/C (231-PDIT-5241A1/A2/A3)) is lower than the
alarm threshold, then alarm is generated and ventilation fan is switched over from one to another. If already
switched then shutdown occurs.
This loop is wired to the SIS which generates command for the changeover.
Auxiliary fan start requests:
Turbine enclosure temperature high alarm;
Turbine enclosure gas detected alarm, detected by gas detection system interface signal 45HTA ;
(Gas Detection loop is in SIS).
Also, in operative condition, from L4 pick-up to two hours after flameout, the following start condition is
active: Accessory-Turbine compartment differential pressure low alarm, detected by median value of (96SV1A/B/C (231-PDIT-5241A1/A2/A3))
Main fan command:
Main fan starts as soon as turbine starting sequence is initiated if all conditions below are verified:
all start permissive conditions are verified
all cutoff conditions are not verified
Offline water wash not selected
Main fan stops if at least one of the following conditions is verified:
After ventilation operative period (120 min) after flameout.
After L4 drop down, can be manually stopped by HMI dedicated pushbutton.
Auxiliary fan command
Auxiliary fan starts if the conditions below are all verified:
at least one of auxiliary fan start request is verified
all cutoffs conditions are not verified
If no auxiliary fan start request is active, it stops when one of the following conditions is verified:
together with the main, after ventilation operative period
manually by HMI pushbutton
from MCC
Manual fans command
If all start permissive conditions are verified and all cutoffs conditions are not verified, each fan can be
manually started and stopped.
Alarms and trips logic
If high temperature is detected by voting logic of sensors in turbine (TT-BA-2A (231-TE-5241 A1) /
TT-BA-2B (231-TE-5241 A2) / TT-BA-2C (231-TE-5241 A3)) and coupling compartment (TT-BA-3A
(231-TE-5242 A1) / TT-BA-3B (231-TE-5242 A2) / TT-BA-3C (231-TE-5242 A3)) alarm is
generated.
If high high temperature is detected by voting logic of sensors in turbine (TT-BA-2A (231-TE-5241
A1) / TT-BA-2B (231-TE-5241 A2) / TT-BA-2C (231-TE-5241 A3)) and coupling compartment (TTBA-3A (231-TE-5242 A1) / TT-BA-3B (231-TE-5242 A2) / TT-BA-3C (231-TE-5242 A3)) trip is
generated.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

60 of 94

The gas detectors in the accessory and turbine compartment ventilation outlet are wired to
MarkVIeS. If 1oo3 detectors detect an LEL level of 5% an alarm is generated. During start-up, this
results in an Inhibit to Start condition. If 2oo3 detectors detect an LEL level of 10% a trip of the GT
is activated.
There are 3 H2S detectors in the Accessory compartment that are hardwired to MarkVIeS. Upon
detection of High value of H2S, an alarm is generated.
If at least one enclosure door is not closed alarm is generated. This signal is hardwired to the MarkVIeS.
If dampers are not fully open, detected by 33ID-1 (231-ZSH-5242A), 33OD-1 (231-ZSH-5243), 33OD-2
(231-ZSH-5244) and 33OD-3 (231ZSH-5245), alarms are generated.
If both 88BA-1 and 88BA-2 feedback signals are off for more than 30 seconds, alarm and normal
shutdown are generated
Start permissive condition
Ventilation inlet damper open.
Turbine, coupling and accessory compartment ventilation outlet dampers are open.
If high temperature is detected by voting logic of sensors in turbine and coupling compartment in
turbine compartment inhibit to start condition is generated.
If high level of gas is detected by voting logic of gas detectors in turbine and accessory compartment
in turbine compartment inhibit to start condition is generated.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

61 of 94

4.19 INLET AIR FILTRATION


4.19.1 DEVICE SUMMARY
DEVICE NAME
88TA-1
88TA-2
88TA-3
TA-1
TA-2
TA-3
96TF-1A
96TF-1B
96TF-1C
33AF-1
45HF-1
45HF-2
45HF-3

CUSTOMER TAG
C-231-001A-BL3A-M
C-231-001A-BL3B-M
C-231-001A-BL3C-M
C-231-001A-BL3A
C-231-001A-BL3B
C-231-001A-BL3C
231-PDIT-5231A1
231-PDIT-5231A2
231-PDIT-5231A3
231-ZSL-5229A
231-AE-5229A1
231-AE-5229A2
231-AE-5229A3

DESCRIPTION
DUST EXTRACTOR FAN MOTOR
DUST EXTRACTOR FAN MOTOR
DUST EXTRACTOR FAN MOTOR
DUST EXTRACTOR FAN
DUST EXTRACTOR FAN
DUST EXTRACTOR FAN
TURBINE AIR INLET FILTER PRESS. CTRL
TURBINE AIR INLET FILTER PRESS. CTRL
TURBINE AIR INLET FILTER PRESS. CTRL
INLET FILTER INSPECTION DOOR CLOSED
INFRA RED GAS DETECTORS
INFRA RED GAS DETECTORS
INFRA RED GAS DETECTORS

4.19.2 SOFTWARE DESCRIPTION


Alarms and trips logic :
If inlet air filter differential pressure is detected high by median value of 96TF-1A (231-PDIT-5231/A1) , 96TF1B (231-PDIT-5231/A2) and 96TF-1C (231-PDIT-5231/A3) for more than 2 s, alarm L63TF1_ALM is
generated
If inlet air filter differential pressure is detected high high by voting shutdown median value of 96TF-1A (231PDIT-5231/A1) , 96TF-1B (231-PDIT-5231/A2) and 96TF-1C (231-PDIT-5231/A3) , shutdown signal and
alarm signals are generated.
In case of filter house inspection door closed detected by 33AF-1A (231-ZSL-5229A) , alarm is generated
and permissive to start is given. This logic is implemented by SIS.
If only one of the shutdown transmitter 96TF-1A (231-PDIT-5231/A1) , 96TF-1B (231-PDIT-5231/A2) and
96TF-1C (231-PDIT-5231/A3) detect high pressure for more than 60 s but the other two transmitters do not
detect trip condition, alarm is generated.
In case of pulse jet local panel failure detected 86PJ, alarm is generated.
There are 3 Infra-Red Gas Detectors at the Air Inlet. These detectors are wired to the MarkVIeS. If 1oo3
detectors detect an LEL level of 5% an alarm is generated. If 2oo3 detectors detect an LEL level of 10% a
trip of the GT is activated along with cut-out of the ventilation fans.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

62 of 94

4.20 FUEL GAS


4.20.1 DEVICE SUMMARY
DEVICE
NAME
96FG-2A
96FG-2B
96FG-2C
90SR
TG-FG-1
96FG-1
96SR-1
96SR-2
65GC
96GC-1
96GC-2
33VG-2
20VG-2
--96FG
FG-1
--FG-2
--96FG-1A
96FG-1B
20PG-1
20PG-2
20PG-3
33PG-1
33PG-2
33PG-3
33PG-4
96PG-1

CUSTOMER TAG

DESCRIPTION

231-PT-5005A1
231-PT-5005A2
231-PT-5005A3
231-FCV-5003A2
231-TE-5006AA
231-PIT-5003A
231-ZT-5003A1
231-ZT-5003A2
231-FCV-5004A2
231-ZT-5004A1
231-ZT-5004A2
231-ZSL-5009A
231-XX-5009A
231-PDT-5006A
231-PT-5005A
231-TE-5005A1B
231-TE-5005A1A
231-TE-5005A2B
231-TE-5005A2A
231-FIT-5005A1
231-FIT-5005A2
23-XX-5006A
23-XX-5008A
23-XX-5007A
231-ZSH-5006A
231-ZSL-5006A
231-ZSH-5008A
231-ZSL-5008A
231-PIT-5007A

33PV-2

231-ZSH- 5007A

FTG-1A
FTG-1B
96FTG
96FG-B

231-TIT-5039
231-TIT-5040
231-TIT-5041
231-PT-5002A

---

231-FT-5002A

20VG-1

231-XX-5010A

INTER-STAGE FUEL GAS PRESSURE


INTER-STAGE FUEL GAS PRESSURE
INTER-STAGE FUEL GAS PRESSURE
FUEL GAS STOP/SPEED RATIO VALVE ACTUATION
FUEL GAS SUPPLY TEMPERATURE
FUEL GAS PRESSURE UPSTREAM VALVE
FUEL GAS STOP/SPEED RATIO VALVE POSITION
FUEL GAS STOP/SPEED RATIO VALVE POSITION
FUEL GAS CONTROL VALVE ACTUATION
FUEL GAS CONTROL VALVE POSITION
FUEL GAS CONTROL VALVE POSITION
WARM-UP LINE VENT VALVE STATUS (CLOSED)
WARM-UP LINE VENT VALVE
DIFFERENTIAL PRESSURE ACROSS FUEL GAS Y-STRAINER
FUEL GAS PRESSURE FOR INLET FLOW CALCULATION
FUEL GAS TEMPERATURE FOR INLET FLOW CALCULATION
FUEL GAS TEMPERATURE FOR INLET FLOW CALCULATION
FUEL GAS TEMPERATURE FOR INLET FLOW CALCULATION
FUEL GAS TEMPERATURE FOR INLET FLOW CALCULATION
FUEL GAS INLET FLOW TRANSMITTER
FUEL GAS INLET FLOW TRANSMITTER
PURGE VALVE 1 ACTUATION SOLENOID
PURGE VALVE 2 ACTUATION SOLENOID
PURGE LINE VENT ACTUATION SOLENOID
PURGE VALVE 1 OPEN CONDITION
PURGE VALVE 1 CLOSE CONDITION
PURGE VALVE 2 OPEN CONDITION
PURGE VALVE 2 CLOSE CONDITION
FUEL GAS PURGE LINE PRESSURE TRANSMITTER
LIMIT SWITCH TO INTER STAGE VENT VALVE OF FUEL GAS
NOZZLE PURGE LINE
FUEL GAS TEMPERATURE UPSTREAM OF HEATER
FUEL GAS TEMPERATURE UPSTREAM OF HEATER
FUEL GAS TEMPERATURE DOWNSTREAM OF HEATER
FUEL GAS PRESSURE FOR FLOW CLACULATION
FUEL GAS FLOW TRANSMITTER FOR EXCESSIVE FUEL AT
START-UP
FUEL GAS VENT SOLENOID VALVE

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

63 of 94

4.20.2 SOFTWARE DESCRIPTION


Following description is aplicable if Fuel-Gas mode is activated.
Vent valve control sequence:
Vent valve opening is enabled if the following conditions are all verified:
Water wash off-line not active (~L83BW)
Flame not detected (~L28FDX)
Ignition command not detected (~L2TVX)
After start passed (L4)
Conditions above select an enabling window between start passed and igniting events (see figure 1). Also,
venting is disabled in case of off -line water wash sequence.
L4

L2TVX
L28FDX

Opening enabling window

Alarm enabling

Figure 1 - Vent valve enabling


If vent valve opening is enabled, open command (l20vg2) is generated if fuel gas temperature is less than
K26FGL_VG2 (typically 4F) above alarm threshold K2 6FGL. Then it closes again with a hysteresis of
K26FGL_VG2_H (typically 8F).
After an opening command (l20vg2), if valve is not open, detected by ~l33vg2_c, within 3s, alarm
L86VG2_ALM is generated.
After a closing command (~l20vg2), if valve is not completely closed, detected by l33vg2_c, within
K20VG2_C (typically 30s), alarm L86VG2_ALM is generated.
If valve is not completely closed, detected by ~l33vg2_c, alarm L33VG2_ALM is generated if at least one of
the following conditions is true:
Water wash off-line active (L83BW)
Ignition active (L2TVX)
Before start passed and after K20VG2_C seconds from loss of L4.
After flame detection and before 1.1 * K20VG2_C seconds after loss of flame (~L28FDX).
Conditions above select the complementary to the enabling opening window (see figure 1). Note that in case
of trip event before ignition, the alarm is also disabled during maximum closing time (K20VG2_C) to allow
vent valve to close.
Alarms logic
If the fuel gas pressure is low, detected by l63fgl, during ignition L2TVX or with flame detected
L28FDX, alarm L63FGL_ALM is generated.
If the fuel gas temperature ftg2 is lower than K26FGL (typically 86F) during ignition L2TVX or with
flame detected L28FDX, then alarm L26FGL_ALM is generated.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

64 of 94

If the fuel gas temperature ftg2 is higher than K26FGH (typically 284F), alarm L26FGH_ALM is
generated.
If Differential Pressure across Fuel Gas Y- Strainer is found high detected by 231-PDT-5306A, then
a High alarm is generated.
Fuel Gas Heater Control Logic:
Fuel Gas heater control will not be performed by Thyristor panels. The logic that would be followed to
perform the ON / OFF command for the heaters and the logic that must be considered during GT starting is:
Logic to be managed by DCS and MCC:
IF FE-5005A (unit 1) + FE-5005A (unit 2) > or = 3000 kg/h
AND
IF TIT5041 (96FTG) < + 4C
THEN: heater ON.

IF TIT- 5039 (FTG-1A) or TIT0340 (FTG-1B) > or = + 7C


OR
IF TIT- 5041 (96FTG) > + 90C
THEN: heater OFF.
Logic to be managed by MKVIe:
The interlock to the opening of SRV/GCV during GT starting procedure:
IF TIT5039 (FTG-1A) or TIT5040 (FTG-1B) > or = + 8C
AND
TG-FG-1 (231-TE-5006AA) is not low

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

65 of 94

4.21 LIQUID FUEL


4.21.1 DEVICE SUMMARY
DEVICE NAME
F-001A/B
F-002
F-003
PF-1
88PF-1
23FL
PF-2
88PF-2
77FD-1
77FD-2
77FD-3
------96HF-2
96FL-1

CUSTOMER TAG
C-231-001A-F-10A/B
C-231-001A-F-11
C-231-001A-F-12
C-231-001A-P1
C-231-001A-P1-M
C-231-001A-H4
C-231-001A-P12
C-231-001A-P12-M
231-SE-5013A
231-SE-5014A
231-SE-5015A
231-TIT-5013A1
231-TIT-5013A2
231-TIT-5013A3
231-PDIT-5014A
231-PIT-5018A

65FP-1

231-FCV-5015A1

20LF-2

231-XX-5016A

---

231-LIT-5013A

---

231-TIT-5014A

20LF-1
33FL-1
33FL-2

231-XX-5014AA
231-ZSH-5014A
231-ZSL-5014B

DESCRIPTION
LIQUID FUEL DUPLEX FILTER
LIQUID FUEL FILTER DOWNSTREAM PUMP
LIQUID FUEL HYD OIL FILTER
LIQUID FUEL PUMP
LIQUID FUEL PUMP MOTOR
LIQUID FUEL HEATER
LIQUID FUEL DRAIN PUMP
LIQUID FUEL DRAIN PUMP MOTOR
LIQUID FUEL FLOW DIVIDER SPEED PICK-UP
LIQUID FUEL FLOW DIVIDER SPEED PICK-UP
LIQUID FUEL FLOW DIVIDER SPEED PICK-UP
LIQUID FUEL TEMP
LIQUID FUEL TEMP
LIQUID FUEL TEMP
LIQUID FUEL FILTER DIFF. PRESSURE
LIQUID FUEL PRESSURE
LIQUID FUEL SYSTEM CONTROL VALVE
REGULATING SERVO VALVE
LIQUID FUEL BYPASS VALVE ACTUATING
SOLENOID VALVE
LIQUID FUEL TANK LEVEL
LIQUID FUEL TEMPERATURE FEEDBACK TO
THYRISTOR CONTROL PANEL
LIQUID FUEL VALVE ACTUATING SOLENOID
LIQUID FUEL VALVE OPEN LIMIT SWITCH
LIQUID FUEL VALVE CLOSE LIMIT SWITCH

4.21.2 SOFTWARE DESCRIPTION


In Liquid Fuel System the main pump PF-1 delivers the 100% liquid fuel to the skid.
The fuel valve 231-XV-5316A has two operating positions:
By pass position: It provides the liquid by-pass through the recycle piping.
Liquid fuel temperature is monitored by RTDs and transmitted to MarkVIe v.i.a. Temperature
transmitters 231-TIT-5013A1, 231-TIT-5013A2 and 231-TIT-5013A3.
If liquid fuel temperature low condition is detected (231-TAL-5013) an alarm is generated and liquid
fuel heater is turned on and the fuel valve is set in the by-pass position. An inhibit signal for liquid
system starting and running is generated.
For liquid fuel temperature low-low condition (231-TALL-5013), GT Normal Stop condition is
activated.
Fuel supply position:
Liquid fuel temperature detected by 231-TIT-5014A is sent to MarkVIe, which generates a control
signal and sends to the Thyristor control panel to switch on/off the heater based on the feedback.
Upon attaining the correct temperature the fuel is allowed to flow to the combustor by actuation of
the SOV 231-XX-5016A.
If low pressure is detected by 231-PIT-5018A (96FL-1), an alarm is generated and Inhibit Liquid
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

66 of 94

Fuel Starting and running condition is generated.


If differential pressure across Liquid Fuel Filters detected by 231-PDIT-5014A (96HF-2) is detected
high, an alarm is generated.
The Liquid Fuel Heater control is performed by Thyristor Control Panel. Following feedback signals
are transmitted to MarkVIe from Thyristor Control Panel:
Liquid Fuel Temperature
Liquid Fuel Heater Cut-out status
Liquid Fuel Heater working/ ok condition
Fault Condition
In case of Thyristor Control Panel failure, electric heater will remain turned on until its own cut-off.
The liquid fuel flow is sensed by each individual speed sensors 77FD-1 (231-SE-5013A) , 77FD-2
(231-SE-5014A) and 77FD-3 (231-SE-5015A) and transmitted to MarkVIe which perform Liquid
Fuel Bypass valve 65FP-1 (231-FCV-5015A1) control to recirculate the liquid fuel back to Liquid
Fuel Tank (C-231-001A-TK1)
If the liquid fuel tank (TK-1) level is detected high (231-LAH-5013A) by the level transmitter 231-LIT5013A then the pump PF-2 is started to pump the liquid fuel to liquid fuel storage tank. If the level
transmitter senses the level to be low (231-LAL-5013A) the pump PF-2 is stopped.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

67 of 94

4.22 FUEL TRANSFER


4.22.1 Fuel Splitter
In dual fuel Gas Turbine the FSR (Fuel Stroke Reference) is divided into two signals to provide
dual fuel operation. The two signals are FSR1 and FSR2. Typically FSR1 is for liquid and FSR2
is for gas.
Fuel transfer sequence can be activated only when the START-UP COMPLETE SEQUENCE
flag is satisfied.

4.22.2 Fuel Transfer (Liquid to Gas)


If the unit is running on liquid operator interface GAS target is selected, the following sequence
of events will take place:
1. FSR1 will remain at initial value but FSR2 will step to a value slightly greater than zero. This
will open the gas control valve slightly to bleed down the inter valve volume, P2. This is done in
case a high pressure has been entrapped. The presence of a pressure higher than that
required by the speed ratio controller would cause slow response in initiating gas flow.
2. After a time delay to bleed down P2 and fill the gas supply line, the software program ramp
the fuel commands at a rate programmed to a complete transfer.
3. As transfer progress, FSR1 will be reduced and FSR2 will increase at the programmed ramp
rate.
When the transfer is complete, 231-XX-5016A solenoid valve switches 231-XV-5016A to recycle
position.

4.22.3 Fuel transfer (Gas to Liquid)


When transfer from gas to liquid is initiated, the liquid fuel pump clutch is engaged, energizing
the liquid fuel trip valve opens the liquid fuel stop valve, and the liquid purge is shut off.
Transfer from gas to liquid is essentially the same sequence as previously described except
that gas and liquid fuel command voltages are interchanged. For instance, at the beginning of a
transfer FSR2 remains at its initial value, but FSR1 steps to a value slightly greater than zero.
This will command a small liquid fuel flow. If there has been any fuel leakage past the check
valves, this will fill the liquid fuel piping and avoid any delay in delivery at the beginning of the
FSR1 increase.
When transfer to total liquid is completed, a logic signal will close the gas fuel stop valve by deenergizing the gas fuel trip valve 231-XX-2052 (20FB-1) and initiating the gas fuel purge
sequence.
During normal running condition, the automatic Fuel gas to liquid fuel transfer is activated by
the Fuel gas low-pressure transmitter 96FG-1.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

68 of 94

4.23 FUEL GAS BLOCK / FUEL GAS VENT VALVES


Fuel Block (20FB-1) valve logic
During starting sequence, fuel block valve is opened when L4 is detected. The opening is disabled if off line
water wash is selected.
When a trip (pressurized or depressurized) is detected the valve is closed.
Fuel Vent (20FV-1) valve logic
During starting sequence, fuel vent valve is closed after fuel line purge sequence. When a trip (pressurized
or depressurized) is detected the valve is opened. The opening is enabled when fuel block valve is
completely closed.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

69 of 94

4.24 ATOMIZING AIR SYSTEM


4.24.1 DEVICE SUMMARY
DEVICE NAME
CA-1
CA-2
FA2-1
FA1-1
FA3-1
20PL-1
20AA-1
AAT-1A
AAT-1B
AAT-1C
20AB-1
33AA-1
33AA-2
96AA
96AA-2
33AC-1

CUSTOMER TAG
C-231-001A-C1
C-231-001A-C2
C-231-001A-F6
C-231-001A-F5
C-231-001A-F7
231-XX-5076A
231-XX-5074A
231-TE-5158A1A
231-TE-5158A2A
231-TE-5158A3A
231-XX-5073A
231-ZSL-5073A
231-ZSH-5073A
231-PIT-5078A
231-PIT-5077A
231-ZSL-5157A

DESCRIPTION
MAIN ATOMIZING AIR COMPRESSOR
AUXILIARY ATOMIZING AIR COMPRESSOR
STARTING COMPRESSOR AIR FILTER
AIR FILTER
AIR FILTER
LIQUID FUEL SYSTEM PURGE SOLENOID VALVE
VA18-1 CONTROL AIR ON/OFF VALVE
ATOMIZING AIR COOLER DISCHARGE TEMPERATURE
ATOMIZING AIR COOLER DISCHARGE TEMPERATURE
ATOMIZING AIR COOLER DISCHARGE TEMPERATURE
AUX. ATOMIZING AIR COMPRESSOR VALVE CONTROL
AUX. ATOMIZING AIR COMPRESSOR VALVE POSITION
AUX. ATOMIZING AIR COMPRESSOR VALVE POSITION
ATOMIZING AIR MANIFOLD PRESSURE
PURGE AIR MANIFOLD PRESSURE
ATOMIZING AIR COOLER VALVE CLOSE LIMIT SWITCH

4.24.2 SOFTWARE DESCRIPTION

The purpose of atomizing air is, during liquid fuel operation, to break up the liquid fuel into a fine mist, so that
the fuel can ignite, and burn completely. In order to reach this requirement, the nominal pressure ratio of
atomizing air relative to combustion chamber (Pcc) air is 1.35. This pressure ratio is needed for proper
atomization of the liquid fuel. Improper liquid fuel atomization may result in incomplete combustion, and/or
carryover of liquid fuel droplets into the turbine. The main atomizing air compressor (CA-1) pressurizes
compressor discharge (Pcd) air to meet this requirement. During a liquid fuel startup, the nominal pressure
ratio of atomizing air relative to Pcd air is 1.5. This pressure ratio is needed to ignite the liquid fuel. In order to
meet this requirement a booster compressor driven by starting motor (CA-2) is required, because the main
atomizing air compressor is shaft driven, and does not develop enough pressure until the turbine reaches
90% speed.
Atomizing air is required during gas fuel operation. During gas fuel operation, atomizing air purges the
atomizing air circuits and the liquid fuel circuits. These circuits must be purged in order to cool the nozzle tips
and prevent backflow of combustion gases. During gas fuel operation, the nominal pressure ratio of
atomizing air relative to Pcc air is 1.05. The air flow is driven to Purge Air Manifold by the valve VA19-1,
actuated by solenoid 231-FX-5076 (20PL-1). During a gas fuel startup, the atomizing air circuits do not
require purge.
Three thermocouples (231-TE-5158A1A (AAT-1A) , 231-TE-5158A2A (AAT-1B) , 231-TE-5158A3A (AAT1C) monitor the inlet temperature of the main atomizing air compressor in order to protect the compressor.
Alarms are generated for high and low level. Shutdown is generated for HH level. Trip is generated for LL
condition.
The pressure in the manifold is monitored by 231-PIT-5078A (96AA) . Shutdown is generated if relative
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

70 of 94

pressure is below a threshold that is different for start-up, liquid fuel running, fuel gas running, shut-down.
During start-up the valve VA18 -1, actuated by solenoid 231-FV-5074A (20AA-1) , is open. The valve VA221, actuated by solenoid 231-XX-5073A (20AB-1) is open to give air supply to booster compressor.
At end of start sequence (L3) VA22-1 receives the close command and the atomizing air system is driven by
atomizing air compressor.
During fuel gas operation the nominal pressure ratio of atomizing air relative to Pcc (1.05) is guaranteed by
atomizing air compressor with VA18-1 closed. The correct suction pressure is guaranteed through the
bypass line orifice (231-FO-5075A).

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

71 of 94

4.25 SEAL GAS, SEAL GAS HEATER & SEAL GAS BOOSTER SYSTEM
4.25.1 DEVICE SUMMARY
DEVICE NAME
F-701/A/B
-----------------------------------------------------------------

CUSTOMER TAG
C-231-001A-F3A/B
231-FIT-5206A
231-FIT-5207A
231-PDIT-5193A
231-PDIT-5201A1
231-PIT-5204A1
231-PIT-5204A2
231-PIT-5204A3
231-PIT-5205A1
231-PIT-5205A2
231-PIT-5205A3
231-PIT-5195A1
231-PIT-5195A2
231-PIT-5195A3
231-PIT-5199A
231-PIT-5200A
231-PIT-5208A
231-XX-5210A
231-ZSH-5208A
231-ZSH-5210A
231-ZSL-5208A
231-ZSL-5210A
231-PDIT-5209A
231-PDY-5201A
231-ZSH-5211A
231-ZSL-5211A
231-XX-5211A
231-TE-5210A1A
231-TE-5210A2A
231-TE-5210A3A
231-XX-5209A
231-ZSL-5209A
231-XX-5212A

---

231-PDIT-5210A

-----

231-PIT-5197A1/A2/A3
231-PIT-5198A1/A2/A3

DESCRIPTION
N2 FILTER
COMPRESSOR DISCHARGE END PRIMARY VENT
COMPRESSOR SUCTION END PRIMARY VENT
NITROGEN FILTER PRESSURE
BUFFER SEAL GAS INLET
COMPRESSOR PRIMARY VENT PRESSURE
COMPRESSOR PRIMARY VENT PRESSURE
COMPRESSOR PRIMARY VENT PRESSURE
COMPRESSOR PRIMARY VENT PRESSURE
COMPRESSOR PRIMARY VENT PRESSURE
COMPRESSOR PRIMARY VENT PRESSURE
NITROGEN HEADER PRESSURE
NITROGEN HEADER PRESSURE
NITROGEN HEADER PRESSURE
SEAL GAS OUTLET BALANCING LINE PRESSURE
SEAL GAS INLET BALANCING LINE PRESSURE
PRIMARY VENT CONTROL PRESSURE
NITROGEN INTERMEDIATE INJECTION VALVE
FLARE PRESSURE CONTROL VALVE POSITION
NITROGEN INTERMEDIATE INJECTION VALVE
FLARE PRESSURE CONTROL VALVE POSITION
NITROGEN INTERMEDIATE INJECTION VALVE
SEAL GAS FILTERS
BUFFER GAS PRESSURE CONVERTER
GAS AMPLIFIER INLET VALVE OPEN LIMIT SWITCH
GAS AMPLIFIER INLET VALVE CLOSE LIMIT SWITCH
GAS AMPLIFIER INLET VALVE ACTUATING SOV
GAS AMPLIFIER- SEALS PROTECTION
GAS AMPLIFIER- SEALS PROTECTION
GAS AMPLIFIER- SEALS PROTECTION
EXTERNAL SEAL GAS INLET SOLENOID VALVE
EXTERNAL SEAL GAS INLET LIMIT SWITCH
BOOSTER SKID BUFFER GAS INLET ACTUATING SOV
DIFFERENTIAL PRESSURE ACROSS SEAL GAS
BOOSTER
CC SEALING CHAMBER VENT DISCHARGE SIDE
CC SEALING CHAMBER VENT SUCTION SIDE

4.25.2 SOFTWARE DESCRIPTION


The purpose of buffer gas is to maintain a constant volumetric flow of dry filtered gas between primary seal
and internal labyrinth avoiding unfiltered gas to reach seals. This is achieved actuating valve (231-PDCV5201A) through signal 231-PDY-5201A to maintain differential pressures 231-PDIT-5201A1 to the set point
value. A PI control is used.
Buffer gas alarm and fault logic
If the differential pressures 231-PDIT-5201A1 lowers below threshold value when starting sequence is ended
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

72 of 94

(L3), an alarm is generated.


If differential pressure between buffer-gas filter (231-PDIT-5209A) is above threshold level an alarm is
generated.
Buffer gas manual operation
Manual operation can be enabled by command L43SG_CMD. If enabled, 231-PDCV-5201A valve is
managed by seven pushbuttons:
L5SG_SR_CPB Set-point raise step
L5SG_SL_CPB Set-point lower step
L5SG_C_CPB - Valve close command (fine tuning)
L5SG_O_CPB - Valve open command (fine tuning)
L5SG_FC_CPB - Valve close command (latched till completely close or stop is detected)
L5SG_FO_CPB - Valve open command (latched till completely open or stop is detected)
L5SG_S_CPB - Stop
Primary vent flow alarm logic
Primary vent low flow alarms are enabled if pressurized state is detected (L4PV) and, during startup, after
the shaft has moved (~L14LR).
If enable condition is verified and if flow through primary vent line suction side, measured by 231-FIT5206A, 231-FIT-5207A, lowers below threshold an alarm is generated.
If flow through primary vent line suction side, measured by 231-FIT-5206A, 231-FIT-5207A, rises above
threshold an alarm is generated.
Primary vent pressure alarm and fault logic
If primary vent suction side pressure 231-PDIT-5504 A1 / 231-PDIT-5504 A2 / 231-PDIT-5504 A3 rises
above the trip threshold value, an alarm and depressurized trip are generated. The same alarm and trip
are generated in case of transmitter fault detected.
If primary vent discharge side pressure 231-PIT-5205 A1 / 231-PIT-5205 A2 / 231-PIT-5205 A3 rises
above the trip threshold value, an alarm and depressurized trip are generated. The same alarm and trip
are generated in case of transmitter fault detected.
Primary vent control pressure
The primary vent line pressure is monitored by 231-PIT-5208A and transmitted to MarkVIe which in controls
the opening and closing of the valve 231-XV-5208A by actuating the solenoid valve 231-XX-5208A. The
open/close position of 231-XV-5208A is detected by 231-ZSH-5208A and 231-ZSL-5508A.
Seal purge gas injection logic
If seal purge gas pressure 231-PIT-5195 A1 / 231-PIT-5195 A2 / 231-PIT-5195 A3 lowers below low
threshold an alarm is generated.
If seal purge gas pressure 231-PIT-5195 A1 / 231-PIT-5195 A2 / 231-PIT-5195 A3 becomes higher than
high threshold an alarm is generated.
If seal purge gas pressure 231-PIT-5195 A1 / 231-PIT-5195 A2 / 231-PIT-5195 A3 lowers below low low
threshold an alarm and pressurized trip is generated.
If the differential pressure 231-PDIT-5193A across the separation gas (Nitrogen) inlet filter is greater
than a threshold value an alarm is generated.
Start-up sequence
During the start-up sequence, if valve open condition is not detected, when L1X is active, the valve 231XV-5209 is opened through the command 231-XX5209A. The valve is closed when LP shaft reaches
70% of full speed.

Stop sequence
During the shutdown or pressurized trip sequence, if valve open condition is not detected, the valve 231XV-5209A is opened through the command 231-XX5209A when low pressure shaft speed goes below
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

73 of 94

the value of 60% of full speed.


Intermediate Buffer Gas isolation
In order to prevent the risk of reverse pressurization of the primary seal, the buffer gas injection shall be
isolated maintaining however the injection to barrier seals.
A remote controlled isolation valve (solenoid type) on the buffer gas downstream filter line dedicated to
intermediate injection shall be provided. The valve shall be closed by the control logic in the following cases:

LP and Double Control Sealing System


The valve shall be closed when the differential pressure between seal gas and primary vent is below
0.3 bar.
HP Sealing System
The valve shall be closed when the suction pressure or balancing drum chamber pressure is below 3
barg.

Seal Gas Booster Logic


At the compressor start-up sequence, the seal gas booster is started. In the first 1 minute the transmitter
(231-PDIT-5210A) is bypassed since initially there is no differential pressure developed across the booster.
After 1 minute of starting the booster, if the transmitter detects a Low condition (231-PDSL-5210A), an alarm
is generated. For a LL condition, the Booster trips and compressor running sequence is aborted.
The temperature at the seal gas booster outlet is measured by the RTDs 231-TE-5210A1A, 231-TE5210A2A and 231-TE-5210A3A. If 2oo3 RTDs sense:
- Low temperature, an alarm is generated and heater-on signal is transmitted by the MarkVIe to the
Thyristor Control Panel which turns on the heater.
- Low Low temperature, a trip with vent is initiated.
- High temperature, an alarm is generated and heater-off signal is transmitted by the MarkVIe to the
Thyristor Control Panel which turns off the heater.
- High High temperature, a heater cut-off signal is generated.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

74 of 94

4.26 STEAM INJECTION


4.26.1 DEVICE SUMMARY
DEVICE
NAME

CUSTOMER TAG

96PJ-1

231-PIT-5025A

ST-SJ-1/2/3

231-TE-5025A1A/A2A/A3A

20SJ-2
33SJ-1
33SJ-2
33CJ-1
20BS-1
33BS-1
20BS-2
33BS-2
20BS-3
33BS-3
20BS-4
33BS-4

231-XX-5029A
231-ZSH-5029A
231-ZSL-5029A
231-ZSL-5026A
231-XX-5030A
231-ZSL-5030A
231-XX-5031A
231-ZSL-5031A
231-XX-5032A
231-ZSL-5032A
231-XX-5027A
231-ZSL-5027A

---

231-PY-5025A

96SJ-1
96SJ-2
60WQL
60WQR

231-FIT-5025A1
231-FIT-5025A2
231-XS-561 <4>
231-XS-562 <4>

DESCRIPTION
STEAM INLET FLOW CALCULATION PRESSURE
TRANSMITTER
STEAM INLET FLOW CALCULATION TEMPERATURE
INPUTS (RTD)
STEAM INJECTION STOP VALVE ACTUATION
STEAM INJECTION STOP VALVE OPEN
STEAM INJECTION STOP VALVE CLOSED
STEAM INJECTION CONTROL VALVE CLOSED
DRAIN VALVE NUMBER 1 ACTUATION
STEAM INJECTION DRAIN VALVE N.1 CLOSED
DRAIN VALVE NUMBER 2 ACTUATION
STEAM INJECTION DRAIN VALVE N.2 CLOSED
DRAIN VALVE NUMBER 3 ACTUATION
STEAM INJECTION DRAIN VALVE N.3 CLOSED
STEAM DISCHARGE (AFTER VA-4)
STEAM INJECTION MANIFOLD DRAIN VDI-4
STEAM INLET PRESSURE REGULATING I TO P
CONVERTOR
STEAM FLOW
STEAM FLOW
STEAM VALVES COMMAND
STEAM VALVES COMMAND

4.26.2 SOFTWARE DESCRIPTION


Steam injection skid function is NOx reduction.
The 96PJ-1 (231-PIT-5025A) transmitter and ST-SJ-1 (231-TE-5025A1A) / ST-SJ-2 (231-TE-5025A2A) /
ST-SJ-3 (231-TE-5025A3A) RTDs purpose is to calculate the steam mass flow in order to grant the
necessary steam/gas mass ratio inside combustion chambers.
Steam injection reference function is:
WQR2 = [WQKn_K * [(FQMT - WQKn_B)] + WQKn_N
Note the equation is of the form Y= mX + B
Y = WQR2

(function)

m = WQKn_K

(Diluent/Fuel slope)

x = (FQMT - WQKn_B)
(variable)
FQMT = Total Fuel Mass Flow Reference
WQKn_B = Fuel Flow Offset
b = WQKn_N

(offset)
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION

REVISION DESCRIPTION:
NO REVISION
INTRODUCED
IN THIS PAGE
REVISED
WHERE
SHOWN <4>

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

75 of 94

STEAM INJECTION FLOW VS. FUEL FLOW

MAX limit
WQKn_M
slope
WQKn_K
n=1

STEAM
FLOW

slope
WQKn_K
n=0

WQKn_N

WQKn_B
n=0
WQKn_E

WQKn_B
n=1
LK83WKn
n=1

FUEL FLOW

Note: The table is applicable for both fuel gas and liquid fuel with following parameters
Fuel Gas:
WQK0_N
0.00859739 Kg/sec
WQK0_M
1.47681
Kg/sec
Liquid Fuel:
WQK2_N
0.705118 Kg/sec
WQK2_M
2.19891
Kg/sec
The WQKn_E is the minimum fuel flow set point to start steam injection.
The WQKn_M is the steam injection maximum flow limit.
The ramp consists of multiple steps; the logic is used to select the n constant set to change the curve with
fuel flow.
The steam injection skid in order to be operative during turbine running requires a purging line heating
procedures in steps. With steam injection disabled the position of the valves is the following: VDI-1 closed,
VS-3 closed, VDI-2 open, VA-4 closed, VDI-3 closed, and VDI-4 closed.
The VDI-1, VDI-3, VDI-4 valves are opened by the 20BS-1 (231-XX-5030A) , 20BS-3 (231-XX-5032A) ,
20BS-4 (231-XX-5027A) commands, the control system will monitor the limit switch 33BS-1 (231-ZSL5030A) ,33BS-3 (231-ZSL-5032A) , 33BS-4 (231-ZSL-5027A) in not closed position, if after 3 seconds from
the drain valve opening command the limit switches are still in closed position an alarm will be generated.
The first step permits to heat and drain from condensate vapor the stop valve and at the same time to heat.
This step permits also to drain and heat (with Pcd air) the piping from control valve to manifold and the
manifold itself. The opening command 20BS-1 (231-XX-5030A) will start a timer set at 120 seconds, when
this timer is expired the second step starts with the 20SJ-2 (231-XX-5029A) command in order to open the
VS-3 stop valve.
The control system will monitor the limit switch 33SJ-1 (231-ZSH-5029A) in not closed position, if after 3
seconds from the drain valve opening command the limit switch is still in closed position an alarm will be
generated.
The 20BS-1 (231-XX-5030A) command is de-energized 1 second after the 33SJ-1 (231-ZSH-5029A) limit
switch not in closed position and the 20SJ-2 (231-XX-5029A) command active.
The opening command 20SJ-2 will start a timer set at 120 seconds, when this timer is expired the third step
starts with the 20BS-3 (231-XX-5032A) , 20BS-4 (231-XX-5027A) commands in order to close the VDI-3,
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

76 of 94

VDI-4 drain valves.


The control system will monitor the limit switch 33BS-3 (231-ZSL-5032A) , 33BS-4 (231-ZSL-5027A) in
closed position, if after 3 seconds from the drain valve opening command, the limit switch is not in closed
position an alarm will be generated.
VA-4 valve can now be opened and regulated by
4CJ-RUN
MOT. STEAM VALVE RUN
4CJ-DIR
MOT. STEAM VALVE DIRECTION
And the steam injection system can be operative. The control system will monitor the limit switch 33CJ-1
(231-ZSL-5026A) in not closed position, if after 3 seconds from the drain valve regulating command the limit
switch is still in closed position an alarm will be generated.
The missing opening command to VS-3, VDI-1, VDI-2, VDI-3, VDI-4, VA-4 and not closed position feedback
from limit switch will also generate an alarm, delay time will be set on site.
During skid operation:

If the ST-SJ-1 (231-TE-5025/A1A) / ST-SJ-2 (231-TE-5025/A2A) / ST-SJ-3 (231-TE-5025/A3A)


RTD temperature is below a low low superheated steam threshold an alarm is generated.
If the ST-SJ-1 (231-TE-5025/A1A) / ST-SJ-2 (231-TE-5025/A2A) / ST-SJ-3 (231-TE-5025/A3A)
RTDs temperature is below a low superheated steam threshold an alarm is generated.
If the ST-SJ-1 (231-TE-5025/A1A) / ST-SJ-2 (231-TE-5025/A2A) / ST-SJ-3 (231-TE-5025/A3A)
RTDs temperature is over a high threshold an alarm is generated.
If the ST-SJ-1 (231-TE-5025/A1A) / ST-SJ-2 (231-TE-5025/A2A) / ST-SJ-3 (231-TE-5025/A3A)
RTDs temperature is over a high threshold an alarm is generated.
If the 96PJ-1 (231-PIT-5025A) pressure is below a low low threshold an alarm is generated.
If the 96PJ-1 (231-PIT-5025A) pressure is below a low threshold an alarm is generated.
If the 96PJ-1 (231-PIT-5025A) pressures is over a high threshold an alarm is generated.
If the96PJ-1 (231-PIT-5025A) pressure is over a high high threshold an alarm is generated.

To re-initialize steam injection after a system shutdown a MASTER reset is needed.

Press. L

Press. LL

Temp. H

Press. HH

Temp. HH
Press. H

Steam temp.

WORKING
AREA

Tem

p. L

p
Tem

. LL

Steam
saturation

Steam
pressure

Pressure (Barg)
Temperature (C)

LL
16
260

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

L
18
280

H
23
390

HH
24
400

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

77 of 94

5 ANTISURGE AND LOAD SHARING


The compressor surge control panel contains redundant CCC series 5 surge controllers for each
compressor stage.
The output of the surge controllers operates Antisurge valves for each stage to prevent compressor surge.
Antisurge supplier (C.C.C.) will show details on relevant Functional Description.
The interface signals between MarkVIe and CCC Controller is listed down Unit Control System Hardwired IO
List (SOM6628418).
Each Antisurge valve is equipped with a solenoid which is activated when the trip sequence is requested. For
further information see section 1.10 (Trip sequence).

Logic Description of Fast Opening Antisurge Valve:


l20as=0 means Fast Open Antisurge SOV is commanded to open.
This happens when the following condition occurs:
Condition:
1. The Shutdown condition is active
Or
2. Turbine is tripped and shaft is not stopped
(Considering Water-wash is not selected).
Reset Logic of the Fast opening SOV:
The SOV open condition is reset:
- The Fast Opening command is reset if LP shaft is stopped or Reset pulse is obtained
(K4PULS_RES = 60secs), whichever is earlier.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

78 of 94

6 FIRE FIGHTING MONITORING


6.1

ENCLOSURE FIRE DETECTION / FIGHTING:

6.1.1 DEVICE SUMMARY


DEVICE NAME
CBVF-1/2
CBVF-3 to
CBVF-10

CUSTOMER TAG
C-231-001A-V4A/B

DESCRIPTION
FIRE FIGHTING NITROGEN CYLINDER

C-231-001A-V5A to H

FIRE FIGHTING INERGEN CYLINDER

33CP-1A

231-ZSH-5265A

33CP-1D

231-ZSH-5266A

33CP-2A

231-ZSL-5265A

33CP-2D

231-ZSL-5266A

96CP-1A
96CP-1B
96CP-1C
45CR-1
45-CR-2
45FA-1
45FA-2
45FA-3
45FA-4
45FT-1
45FT-2
45FT-3
45FT-4
45FT-5
45FT-6
45UV/IR-1
45UV/IR-2
XL-3A
XL-3B
XL-3C
------XL-4A
XL-4B
XL-4C
------XL-2
XA-2
EDS-2
XL-1
XA-1

231-PT-5289A1
231-PT-52891B
231-PT-52891C
231-XX-5265A
231-FX-5266A
231-TSHH-5253A1
231-TSHH-5253A2
231-TSHH-5253A3
231-TSHH-5253A4
231-TSHH-5253A5
231-TSHH-5253A6
231-TSHH-5253A7
231-TSHH-5253A8
231-TSHH-5253A9
231-TSHH-5253A10
231-BE-5253A1
231-BE-5253A2
231-XL-5258A1
231-XL-5258A2
231-XL-5258A3
231-HS-5258A
231-HS-5258I
231-HS-5258M
231-XL-5255A1
231-XL-5255A2
231-XL-5255A3
231-HS-5255A
231-HS-5255I
231-HS-5255M
231-XL-5256A1
231-XA-5256A2
231-HS-5256A3
231-XL-5257A1
231-XA-5257A2
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION

REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

EXTINGUISHER HEADER ISOLATION VALVE OPEN


FEEDBACK TO MARKVIE
EXTINGUISHER HEADER ISOLATION VALVE OPEN
FEEDBACK TO MARKVIE
EXTINGUISHER HEADER ISOLATION VALVE CLOSE
FEEDBACK TO FF SYSTEM
EXTINGUISHER HEADER ISOLATION VALVE CLOSE
FEEDBACK TO FF SYSTEM
EXTINGUISHER DISCHARGE HEADER PRESSURE
EXTINGUISHER DISCHARGE HEADER PRESSURE
EXTINGUISHER DISCHARGE HEADER PRESSURE
FIRE DISCHARGE SOLENOIDS
FIRE DISCHARGE SOLENOIDS
HEAT RISE FIRE DETECTOR
HEAT RISE FIRE DETECTOR
HEAT RISE FIRE DETECTOR
HEAT RISE FIRE DETECTOR
HEAT RISE FIRE DETECTOR
HEAT RISE FIRE DETECTOR
HEAT RISE FIRE DETECTOR
HEAT RISE FIRE DETECTOR
HEAT RISE FIRE DETECTOR
HEAT RISE FIRE DETECTOR
UV/IR FIRE DETECTOR
UV/IR FIRE DETECTOR
GREEN LAMP- AUTO
FLASHING RED LAMP- DISCHARGED
WHITE LAMP INHIBITED
3 POSITION SELECTOR- AUTO POSITION
3 POSITION SELECTOR- INHIBIT POSITION
3 POSITION SELECTOR- MANUAL POSITION
GREEN LAMP- AUTO
FLASHING RED LAMP- DISCHARGED
WHITE LAMP INHIBITED
3 POSITION SELECTOR- AUTO POSITION
3 POSITION SELECTOR- INHIBIT POSITION
3 POSITION SELECTOR- MANUAL POSITION
FIRE DISCHARGE LAMP
FIRE DISCHARGE HORN
DISCHARGE PUSH BUTTON
FIRE DISCHARGE LAMP
FIRE DISCHARGE HORN
DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

79 of 94

DEVICE NAME
EDS-1

CUSTOMER TAG
231-HS-5257A3

DESCRIPTION
DISCHARGE PUSH BUTTON

6.1.2 SOFTWARE DESCRIPTION


Inergen is discharged energizing two solenoid valves, 45CR-1 (231-XX-5265A) and 45CR-2 (231-XX5266A) .In normal conditions these valves are de-energized. Inergen header isolation valves closure is
detected by two limit switches, 33CP-2A (231-ZSL-5265A) and 33CP-2B (231-ZSL-5266A) , cabled to FF
panel. Inergen header pressure is detected by median value of three pressure transmitters: 96CP-1A/B/C.
When the system is in Automatic Mode, extinguisher discharge procedure is activated in case of automatic
fire trip detection or extinguisher discharge push-button action, that activate the 45CR-1 (231-XX-5265A)
and 45CR-2 (231-XX-5266A) solenoid valves.
These steps will be then executed:
1. UCS is notified through a contact, 45FTT open on trip.
2. Enclosure ventilation fans cut-out is available through 2 contacts, 4BA1_C1 ,4BA2_C, open on trip.
3. the following alarm means are activated:
horns close to the enclosure
red flashing lights by the turbine enclosure
Red flashing light or led mounted in the front of the F&G system.
4. After a 30 seconds delay, the Inergen is released in the turbine enclosure.
5. The UCS is notified through a free of voltage contact 63CPD open when extinguisher is discharging.
6. Once discharge is complete, the UCS is notified through a free of voltage open contact 33CPX.

The extinguisher discharge header pressure is checked by pressure switches in case an high pressure is
detected the following steps are executed:
1. the UCS is notified through a free of voltage contact, 63CPD ,open on high pressure
2. Enclosure ventilation fans cut-out is available through 2 contacts, 4BA_C1, 4BA_C2 that open on
trip.
3. the following alarm means are activated:
horns close to the enclosure
red flashing lights by the turbine enclosure
Red flashing light mounted in the front of the F&G system.
The selector switches 231-HS5255A and 231-HS5258A have 3 positions and follow the logic below:
- When AUTO mode is selected, upon detection of Fire by any one of the Fire Detectors, the
discharge procedure is activated.
- When INHIBIT/OFF mode is selected, even if there is Fire in the enclosure, the system does not
send command to Inergen discharge solenoid valves,
- When MANUAL mode is selected at Field, the operator can press the 231-HS-5256X3 (EDS-2) or
231-HS-5257X3 (EDS-1) push buttons at field to enable discharging of extinguisher at field.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

80 of 94

6.2

FIRE FIGHTING DEDICATED PLC INTERFACE:

Following signals are elaborated from F&G dedicated PLC and affect turbine start/stop sequence:
If enclosure fire is detected, unit trips signal is generated (45FTT)
If Inergen is discharged, (33CPX (231- XS -144C) ESTINGUISHANT DISCHARGED and 63CPDX (231XS-656C) EXTINGUISHANT RELEASE IN PROGRESS) unit trip and alarm are generated.
If fire-fighting discharge is inhibited alarm (43CP-IX
ESTINGUISHANT NOT AVAILABLE /
INHIBITED) is generated.
If FF system fault is detected, alarm (86FG-1 FIRE/GAS SYSTEM FAULT) is generated.
Field Interface:
If fire-fighting Inergen discharge valves is detected closed by limit switch (33CP-1A, 33CP-1D), alarm is
generated.
If fire-fighting bottles are empty, alarm (by 33CR) is generated.
For details refer to Fire Fighting Logic Diagram (SOM6628499).

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

81 of 94

7 MARKVIE INTERFACES WITH OTHER SYSTEMS


Here is given a brief explanation of all signals that are interfaced between MarkVIe and other systems external to MarkVIe.
Fire Fighting System vs. Unit Control System:
1. 231-XL 145 A (XL-A) (RED FRONT PANEL LAMP): It Is a Contact 24Vdc signal (lamp) in the UCS front panel that indicates
Fire condition.
2.

231-XL 145 B (XL-B) (GREEN FRONT PANEL LAMP): It Is a Contact 24Vdc signal (lamp) in the UCS front panel that
indicates Armed condition.

3.

231-XL 145 C (XL-C) (WHITE FRONT PANEL LAMP): It Is a Contact 24Vdc signal (lamp) in the UCS front panel that
indicates Inhibited condition.

4.

231-XS -146 (43AUTO) (3 POSITION AUTO/INHIBIT/MANUAL SELECTOR): It is 3 Position Auto / Inhibit Manual Mode
Selector in the UCS Front Panel.

5.

231-XS-610 (86PS-3) (110VDC BUS FAILURE): It is a contact signal (Open=Failure) from Fire Fighting Panel to MarkVIe
indicating failure condition of 110VDC Bus 3 located at Fire Fighting Panel.

Fire Fighting System vs. Customer Fire Fighting System:


1. 231-XS -144 C (33CPX) (EXTING. UNAVAILABLE/INHIBITED (VALVES CLOSED) (TO CUSTOMER FF): It is a contact
signal (NO, Close= valves closed) that indicate the open/ close condition of the extinguisher discharge header valves to
Customer FF System.
2.

231-XS -655 C (43CP_IX) (ELECTRICAL DISCHARGE DIASABLED ALM (TO CUSTOMER FF) It is a contact signal (NO,
Close= electric discharge disabled) that indicate the electric discharge disabled condition to Customer FF System.

3.

231-XS -656 C (63CPDX) (EXTINGUISHANT DISCH. IN PROGRESS (TO CUSTOMER FF): It is a contact signal (NO,
Close= discharge in progress) that indicate the extinguisher discharge in progress condition to Customer FF System.

4.

231-XS -657 TC (45FTX) (FIRE DETECTED TRIP (TO CUSTOMER FF): It is a contact signal (NC, Open= Trip) that indicate
the fire detected Trip condition to Customer FF System.

MarkVIe vs. Fire Fighting System:


1.

231-XS-140 (43CP_ARST) (FF SYSTEM REMOTE RESET): It is a contact signal (NO, Close= reset) that provide remote
reset from MarkVIe to FF detection system.

2.

231-xs-141 (43CP_ASIL) (FF SYSTEM REMOTE SILENCE): It is a contact signal (NO, Close= silence) that provide remote
silence from MarkVIe to FF detection system.

3.

231-XS-144 (33CP-1) (EXTINGUISHER UNAVAILABLE/ INHIBITED (VALVES CLOSED)): It is a contact signal (NO, Close=
valves closed) that indicate the open/ close condition of the extinguisher discharge header valves from FF detection system to
MarkVIe.

4.

231-XS-652 IF (86FF_SD) (FF INPUT FAULT (NORMAL SHUTDOWN): It is a contact signal (NC, Open= Fault), transmitted
from FF detection system to MarkVIe that indicate the fault condition of the FF detection inputs.

5.

231-XS-652 SF (86FF-1) (FF SYSTEM FAULT): It is a contact signal (NC, Open= Fault), transmitted from FF detection
system to MarkVIe that indicate the fault condition of the FF PLC.

6.

231-XS-655 (43CP_I) (ELECTRICAL DISCHARGE DISABLED ALARM): It is a contact signal (NO, Close= electric discharge
disabled) that indicate the electric discharge disabled condition from FF detection system to MarkVIe.

7.

231-XS-656 A (63CPD) (EXTINGUISHER DISCHARGE IN PROGRESS): It is a contact signal (NO, Close= discharge in
progress) that indicate the extinguisher discharge in progress condition from FF detection system to MarkVIe.

8.

231-XS-657 T (45FTT) (FIRE DETECTED TRIP): It is a contact signal (NC, Open= Trip) that indicate the fire detected Trip
condition from FF detection system to MarkVIe.

MarkVIe vs. HRSG Burner Management System:


1. 231-XS-960 (DUCT BURNER PURGE COMPLETED): It is a contact signal from BMS to MarkVIe that indicate that the Duct
Burner Purge is completed.
2.

231-XS-961 (GT LOAD > 60%): It is a Contact signal (NO, Close = GT Load > 60%) from MarkVIe to the BMS indicating that
GT Load is greater than 60%.
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION

REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

82 of 94

MarkVIe vs. CCC:


1. 231-XA-804 (TNL_O) (TURBINE SPEED TO LOAD SHARING CONTROL SYSTEM): It is a (4-20) mA signal transmitted from
MarkVIe to CCC Load Sharing Controller indicating the Turbine Speed.
2.

231-XA-808A (TNR_EXT) (SPEED SET-POINT FROM COMPRESSOR LOAD SHARING SYSTEM): It is a (4-20) mA signal
transmitted from CCC Load Sharing Controller to MarkVIe that gives speed set-point to MarkVIe.

3.

231-XS-800B (4SURGE-1) (ANTISURGE CONTROLLER SURGE DETECTED): It is a contact signal (NO, Close = Surge
Detected) transmitted from CCC Anti-surge Controller to MarkVIe indicating detection of Surge.

4.

231-XS-800C (3AS_ENA-1) (ANTISURGE CONTROLLER ENABLE): It is a contact signal (NO, Close = Enable) transmitted
from MarkVIe to CCC Anti-surge Controller indicating Turbine Start sequence has ended (L3=1) and CCC Anti-surge
Controller is enabled to perform Anti-surge Control.

5.

231-XS-800D (4TXT_O-1) (TURBINE TRIP STATUS REPETITION): It is a contact signal (NC, Open= Trip) transmitted from
MarkVIe to CCC Controllers indicating Unit Summary Trip (L4=0).

6.

231-XS-800F (EXCESSIVE SURGE SHUTDOWN): It is a Contact Signal (Close= Shutdown) transmitted from CCC Antisurge Controller to MarkVIe initiating Shutdown due to excessive surge.

7.

231-XS-800L (LOAD SHARING RUN / STOP): It is a Contact Signal (NO, Close= Load Sharing Enabled) transmitted from
MarkVIe to CCC Load Sharing Controller indicating that Turbine Start sequence has ended (L3=1) and CCC Load Sharing
Controller is enabled to perform Load Sharing Control.

8.

231-XS-806 (4TRACK) (TRACKING REQUEST TO LOAD SHARING SYSTEM): It is a Contact Signal (NO, Close = Tracking
Request enabled) transmitted from MarkVIe to CCC Controller to indicate CCC controller to remain in Tracking Mode.

9.

231-XS-807A (86AS) (ANTI-SURGE CONTROLLER FAULT): It is a contact signal (NC, Open=Fault) transmitted from CCC
Anti-surge / Load Sharing Controller to MarkVIe indicating Fault condition of CCC Anti-surge controller.

10. 231-XS-808B (86LS) (MASTER CONTROLLER FAULT): It is a contact signal (NC, Open=Fault) transmitted from CCC
Master Controller to MarkVIe indicating Fault condition of CCC Master Controller.
MarkVIe vs. DCP:
1. 231-XS-200 I (42HR-1) (HYDRAULIC RATCHET MOTOR RUNNING): It is a contact signal (Close= Running) transmitted
from DCP to MarkVIe indicating the running status of Hydraulic Ratchet pump motor.
2.

231-XS-200 O (49HR-1) (HYDRAULIC RATCHET PUMP MOTOR OVERVOLTAGE): It is a contact signal (Open=Alarm)
transmitted from DCP to MarkVIe indicating the overvoltage status of Hydraulic Ratchet pump motor.

3.

231-XS-200 R (4HR-1) (HYDRAULIC RATCHET RUN/STOP COMMAND): It is a contact signal (NO, Close = Running)
transmitted from MarkVIe to DCP commanding Hydraulic Ratchet pump motor to Start. The inverted condition of the signal
commands Stop condition of the motor.

4.

231-XS-200 U (27HR-1) (HYDRAULIC RATCHET PUMP MOTOR UNDERVOLTAGE): It is a contact signal (Open=Alarm)
transmitted from DCP to MarkVIe indicating the under-voltage status of Hydraulic Ratchet pump motor.

5.

231-XS-206 A (DCP-30RA) (DCP- RECTIFIER A COMMON ALARM): It is a contact signal (Open=Alarm) transmitted from
DCP to MarkVIe indicating the common alarm condition of the DCP Rectifier A.

6.

231-XS-207 (DCP-80X) (DCP BATTERY MINIMUM VOLTAGE): It is a contact signal (Open=Alarm) transmitted from DCP to
MarkVIe indicating the minimum voltage condition of the DCP Battery.

7.

231-XS-208 (DCP-BD) (DCP BATTERY DISCHARGING): It is a contact signal (Open=Alarm) transmitted from DCP to
MarkVIe indicating that the DCP Battery is discharging.

8.

231-XS-851-A (52QE-1) (MINERAL LUBE OIL EMERGENCY DC PUMP RUNNING): It is a contact signal (Close= Running)
transmitted from DCP to MarkVIe indicating the running status of Mineral Lube Oil Emergency DC Pump.

9.

231-XS-851-B (49QE) (MINERAL LUBE OIL EMERGENCY DC PUMP FAULT): It is a contact signal (Open= Fault)
transmitted from DCP to MarkVIe indicating the fault status of Mineral Lube Oil Emergency DC Pump. <4>

10. 231-XS-852 (14HLR) (TURBINE SHAFT ZERO SPEED): It is a wet contact (110Vdc, Closed= Zero speed) signal transmitted
from MarkVIe to DCP indicating the Turbine Shaft Zero Speed Condition.
11. 231-XS-853 (28FD) (TURBINE FLAME NOT DETECTED): It is a wet contact (110Vdc, Closed = Flame not detected) signal
transmitted from MarkVIe to DCP indicating the turbine flame not detected condition.
12. 231-XS-854 (4E) (UCP SYSTEM FULLY OPERATIVE): It is a wet contact (110Vdc, Closed = Fully Operative) signal
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
REVISED
WHERE
SHOWN <4>
NO REVISION
INTRODUCED
IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

83 of 94

transmitted from MarkVIe to DCP indicating the UCP System Fully Operative condition.
13. 231-XS-855 (4-TEST) (PUMP TEST): It is a wet contact (110Vdc, Closed = Test) signal transmitted from MarkVIe to DCP
commanding the Emergency Lube Oil Pump test.
14. 231-XS-857 (63QL) (LUBE OIL PRESSURE NOT LOW): It is a wet contact (110Vdc, Closed = Pressure not low) signal
transmitted from MarkVIe to DCP indicating the Lube Oil header pressure not low condition.
15. 231-XS-858 (63QN) (LUBE OIL PRESSURE NORMAL): It is a wet contact (110Vdc, Closed = Pressure normal) signal
transmitted from MarkVIe to DCP indicating the Lube Oil header pressure normal condition.
16. 231-XS-859 (62CD) (COOLDOWN SEQUENCE ENDED): It is a contact signal (Close= sequence ended) transmitted from
DCP to MarkVIe indicating the end of Cooldown sequence and expiration of Cooldown Timer. <4>
MarkVIe vs. MCC:
1. 231-XS-100 I (52QA-1) (LUBE OIL AUXILIARY PUMP FEEDBACK): It is a Contact Signal (NO, Close= Running) from MCC
to MarkVIe indicating running feedback of Lube Oil Auxiliary Pump Motor).
2.

231-XS-100-R (4QA-1A) (LUBE OIL AUXILIARY PUMP START COMMAND): It is a Pulse Signal (Pulse= Start) from MarkVIe
to MCC indicating Start command to Lube Oil Auxiliary Pump Motor).

3.

231-XS-100-S (4QA-1B) (LUBE OIL AUXILIARY PUMP STOP COMMAND) It is a Pulse Signal (Pulse= Stop) from MarkVIe
to MCC indicating Stop command to Lube Oil Auxiliary Pump Motor).

4.

231-XS-102 I (52QV-1) (LUBE OIL VAPOUR EXTRACTOR 1 FEEDBACK): It is a Contact Signal (NO, Close= Running) from
MCC to MarkVIe indicating running feedback of Lube Oil Vapor Extractor Motor 1).

5.

231-XS-102-R (4QV-1A) (LUBE OIL VAPOUR EXTRACTOR 1 START COMMAND): It is a Pulse Signal (Pulse= Start) from
MarkVIe to MCC indicating Start command to Lube Oil Vapor Extractor 1 Motor).

6.

231-XS-102-S (4QV-1B) (LUBE VAPOUR EXTRACTOR 1 STOP COMMAND): It is a Pulse Signal (Pulse= Stop) from
MarkVIe to MCC indicating Stop command to Lube Oil Vapor Extractor 1 Motor).

7.

231-XS-103 I (52QV-2) (LUBE OIL VAPOUR EXTRACTOR 2 FEEDBACK): It is a Contact Signal (NO, Close= Running) from
MCC to MarkVIe indicating running feedback of Lube Oil Vapor Extractor Motor 2).

8.

231-XS-115-R (4QV-2A) (LUBE OIL VAPOUR EXTRACTOR 2 START COMMAND): It is a Pulse Signal (Pulse= Start) from
MarkVIe to MCC indicating Start command to Lube Oil Vapor Extractor 2 Motor).

9.

231-XS-115-S (4QV-2B) (LUBE VAPOUR EXTRACTOR 2 STOP COMMAND): It is a Pulse Signal (Pulse= Stop) from
MarkVIe to MCC indicating Stop command to Lube Oil Vapor Extractor 2 Motor).

10. 231-XS-104I (52HQ) (AUX HYDRAULIC OIL PUMP FEEDBACK): It is a Contact Signal (NO, Close= Running) from MCC to
MarkVIe indicating running feedback of Auxiliary Hydraulic Oil Pump Motor).
11. 231-XS-104-R (4HQ-1A) (AUX HYDRAULIC OIL PUMP START COMMAND): It is a Pulse Signal (Pulse= Start) from MarkVIe
to MCC indicating Start command to Auxiliary Hydraulic Oil Pump Motor).
12. 231-XS-104-S (4HQ-1B) (AUX HYDRAULIC OIL PUMP STOP COMMAND): It is a Pulse Signal (Pulse= Stop) from MarkVIe
to MCC indicating Stop command to Auxiliary Hydraulic Oil Pump Motor).
13. 231-XS-108I (52BA-1) (VENTILATION FAN #1 FEEDBACK): It is a Contact Signal (NO, Close= Running) from MCC to
MarkVIe indicating running feedback of Ventilation Fan 1 Motor).
14. 231-XS-113-R (4BA-1A) (VENTILATION FAN #1 START COMMAND): It is a Pulse Signal (Pulse= Start) from MarkVIe to
MCC indicating Start command to Lube Oil Ventilation Fan 1 Motor).
15. 231-XS-113-S (4BA-1B) (VENTILATION FAN #1 STOP COMMAND): It is a Pulse Signal (Pulse= Stop) from MarkVIe to MCC
indicating Stop command to Lube Oil Ventilation Fan 1 Motor).
16. 231-XS-109I (52BA-2) (VENTILATION FAN #2 FEEDBACK): It is a Contact Signal (NO, Close= Running) from MCC to
MarkVIe indicating running feedback of Ventilation Fan 2 Motor).
17. 231-XS-114-R (4BA-2A) (VENTILATION FAN #2 START COMMAND): It is a Pulse Signal (Pulse= Start) from MarkVIe to
MCC indicating Start command to Ventilation Fan 2 Pump Motor).
18. 231-XS-114-S (4BA-2B) (VENTILATION FAN #2 STOP COMMAND): It is a Pulse Signal (Pulse= Stop) from MarkVIe to MCC
indicating Stop command to Ventilation Fan 2 Pump Motor).
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
REVISED
WHERE
SHOWN <4>
NO REVISION
INTRODUCED
IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

84 of 94

19. 231-XS-121I (52PF-1) (LIQUID FUEL FORWARDING MOTOR 1 FEEDBACK): It is a Contact Signal (NO, Close= Running)
from MCC to MarkVIe indicating running feedback of Liquid Fuel Forwarding Pump Motor 1).
20. 231-XS-129-R (4PF-1A) (LIQUID FUEL FORWARDING MOTOR 1 START COMMAND): It is a Pulse Signal (Pulse= Start)
from MarkVIe to MCC indicating Start command to Liquid Fuel Forwarding Pump 1 Motor).
21. 231-XS-129-S (4PF-1B) (LIQUID FUEL FORWARDING MOTOR 1 STOP COMMAND): It is a Pulse Signal (Pulse= Stop)
from MarkVIe to MCC indicating Stop command to Liquid Fuel Forwarding Pump 1 Motor).
22. 231-XS-711 (4PF1_C) (LIQUID FUEL FORWARDING MOTOR 1 CUT OUT): It is a contact Signal (Open= Cut-Out) from
MarkVIe to MCC indicating cut-out condition of Liquid Fuel forwarding pump Motor 1).
23. 231-XS-122I (52PF-2) (LIQUID FUEL FORWARDING MOTOR 2 FEEDBACK): It is a Contact Signal (NO, Close= Running)
from MCC to MarkVIe indicating running feedback of Liquid Fuel Forwarding Pump Motor 2).
24. 231-XS-120-R (4PF-2A) (LIQUID FUEL FORWARDING MOTOR 2 START COMMAND): It is a Pulse Signal (Pulse= Start)
from MarkVIe to MCC indicating Start command to Liquid Fuel forwarding Pump 2 Motor).
25. 231-XS-120-S (4PF-2B) (LIQUID FUEL FORWARDING MOTOR 2 STOP COMMAND): It is a Pulse Signal (Pulse= Stop)
from MarkVIe to MCC indicating Stop command to Liquid Fuel forwarding Pump 2 Motor).
26. 231-XS-714 (4PF2_C) (LIQUID FUEL FORWARDING MOTOR 2 CUT OUT): It is a contact Signal (Open= Cut-Out) from
MarkVIe to MCC indicating cut-out condition of Liquid Fuel forwarding pump Motor 2).
27. 231-XS-126 I (52QT-1) (LUBE OIL HEATER #1 FEEDBACK): It is a Contact Signal (NO, Close= Running) from MCC to
MarkVIe indicating running feedback of Lube Oil Heater 1).
28. 231-XS-126-R (4QT1_1A) (LUBE HEATER#1 START COMMAND): It is a Pulse Signal (Pulse= Start) from MarkVIe to MCC
indicating Start command to Lube Oil Heater 1).
29. 231-XS-126-S (4QT1_1B) (LUBE HEATER#1 STOP COMMAND): It is a Pulse Signal (Pulse= Stop) from MarkVIe to MCC
indicating Stop command to Lube Oil Heater 1).
30. 231-XS-720 (4QT1_C) (LUBE OIL HEATER 1 CUT OUT): It is a contact Signal (Open= Cut-Out) from MarkVIe to MCC
indicating cut-out condition of Lube Oil Heater 1).
31. 231-XS-127 I (52QT-2) (LUBE OIL HEATER #2 FEEDBACK): It is a Contact Signal (NO, Close= Running) from MCC to
MarkVIe indicating running feedback of Lube Oil Heater 2).
32. 231-XS-127-R (4QT2_1A) (LUBE HEATER#2 START COMMAND): It is a Pulse Signal (Pulse= Start) from MarkVIe to MCC
indicating Start command to Lube Oil Heater 2).
33. 231-XS-127-S (4QT2_1B) (LUBE HEATER#2 STOP COMMAND): It is a Pulse Signal (Pulse= Stop) from MarkVIe to MCC
indicating Stop command to Lube Oil Heater 2).
34. 231-XS-722 (4QT2_C) (LUBE OIL HEATER 2 CUT OUT): It is a contact Signal (Open= Cut-Out) from MarkVIe to MCC
indicating cut-out condition of Lube Oil Heater 2).
35. 231-XS-128 I (52QT-3) (LUBE OIL HEATER #3 FEEDBACK): It is a Contact Signal (NO, Close= Running) from MCC to
MarkVIe indicating running feedback of Lube Heater 3).
36. 231-XS-128-R (4QT3_1A) (LUBE HEATER#3 START COMMAND): It is a Pulse Signal (Pulse= Start) from MarkVIe to MCC
indicating Start command to Lube Oil Heater 3).
37. 231-XS-128-S (4QT3_1B) (LUBE HEATER#3 STOP COMMAND): It is a Pulse Signal (Pulse= Stop) from MarkVIe to MCC
indicating Stop command to Lube Oil Heater 3).
38. 231-XS-723 (4QT3_C) (LUBE OIL HEATER 3 CUT OUT): It is a contact Signal (Open= Cut-Out) from MarkVIe to MCC
indicating cut-out condition of Lube Oil Heater 3).
39. 231-XS-134 (27MC) (UNDERVOLTAGE FROM MCC): It is a Contact Signal (Open = Under-voltage) from MCC to MarkVIe
indicating under-voltage condition from MCC).
40. 231-XS-135 (49X) (COMMON OVERLOAD FROM MCC): It is a Contact Signal (Open = Overload) from MCC to MarkVIe
indicating Overload condition from MCC).
41. 231-XS-136 (74X-MCC) (DRAWERS COMMON ALARM): It is a Contact Signal (Open = Alarm) from MCC to MarkVIe
indicating Common alarm from MCC drawers).
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

85 of 94

42. 231-XS-139 (2TVX) (IGNITION COMMAND TO MCC): It is a Contact Signal (Close = Ignite) from MarkVIe to MCC
commanding the igniter to ignite).
43. 231-XS-515 I (52CR-1) (GT CRANKING MOTOR STATUS): It is a Contact Signal (NO, Close= Running) from MCC to
MarkVIe indicating running feedback of Cranking Motor).
44. 231-XS-515 L (86CR) (GT CRANKING MOTOR LOCKOUT): It is a Contact Signal (NO, Close= Lockout) from MCC to
MarkVIe indicating lockout condition of Cranking Motor).
45. 231-XS-515-R (4CR-1A) (GT CRANKING MOTOR START COMMAND): It is a Pulse Signal (Pulse= Start) from MarkVIe to
MCC indicating Start command to Cranking Motor).
46. 231-XS-515-S (4CR-1B) (GT CRANKING MOTOR STOP COMMAND): It is a Pulse Signal (Pulse= Stop) from MarkVIe to
MCC indicating Stop command to Cranking Motor).
47. 231-XS-558 (52TG) (FEED BACK TURNING GEAR): It is a Contact Signal (Cls=Running) from MCC to MarkVIe indicating
running feedback of turning gear. <4>
48. 231-XS-559 (4TG1_R) (TURNING GEAR COMMAND-RESET): It is a Contact Signal (Cls=Reset) from MarkVIe to MCC
commanding the reset of turning gear. <4>
49. 231-XS-560 (4TG1_S) (TURNING GEAR COMMAND-SET): It is a Contact Signal (Cls=Set) from MarkVIe to MCC
commanding the set of turning gear. <4>
MarkVIe vs. DCS:
1. 231-XS-0250 RS (3CRS) (CUSTOMER READY TO START): It is a Contact Signal (NO, Close= Ready to Start) transmitted
from DCS to MarkVIe as a permissive to start the Gas Turbine. <4>
2.

231-XS-0253 C (14HMX) (GT CRANKING STATUS): It is a Contact Signal (NO, Close= Cranking status) transmitted from
MarkVIe to DCS indicating the GT cranking status. <4>

3.

231-XS-0253 R (3X) (GT RUNNING STATUS): It is a Contact Signal (NO, Close= Running status) transmitted from MarkVIe
to DCS indicating the GT running status (L3=1). <4>

4.

231-XS-0253 RS (3RS) (GT READY TO START STATUS): It is a Contact Signal (NO, Close= Ready to Start) transmitted
from MarkVIe to DCS indicating the GT Ready to Start status. <4>

5.

231-XS-0253 S (GT STARTING STATUS): It is a Contact Signal (NO, Close= Starting) transmitted from MarkVIe to DCS
indicating the GT start sequence initiated and the internal command Start Auxiliaries is true (L1X=1). <4>

6.

231-XS-0253SD (94X_C) (GT NORMAL STOP STATUS): It is a Contact Signal (NO, Close= Stop) transmitted from MarkVIe
to DCS indicating the GT Normal stop status and that the Shutdown is in progress (L94X=1). <4>

7.

231-XS-0253 TD (4T_C2) (GT TRIP STATUS DEPRESSURIZED): It is a Contact Signal (NC, Open= Trip) transmitted from
MarkVIe to DCS indicating the GT Depressurized Trip status. <4>

8.

231-XS-0253 TP (4T_C1) (GT TRIP STATUS PRESSURIZED): It is a Contact Signal (NC, Open= Trip) transmitted from
MarkVIe to DCS indicating the GT Pressurized Trip status. <4>

9.

231-XS-0254 (30ALM) (CUMULATIVE ALARM REPETITION): It is a Contact Signal (NC, Open= Trip) transmitted from
MarkVIe to DCS indicating the Cumulative alarm condition. <4>

10. 231-XS-0255 (43R_C) (GT IN REMOTE CONTROL MODE): It is a Contact Signal (NO, Close= Remote Control Mode)
transmitted from MarkVIe to DCS indicating that Remote Control Mode is selected and the DCS can control the sequence.
<4>
11. 231-XS-0256 (4VALV) (PROCESS VALVE POSITIONING): It is a Contact Signal (NO, Close= Process valve positioning
signal) transmitted from MarkVIe to DCS indicating that Auxiliaries are started and Master Protective signal is enabled (L4=1).
Now the DCS must start the Purging sequence of the Process valves. <4>
12. 231-XS-0257 R (1START) (PROCESS REMOTE START): It is a Contact Signal (NO, Close= Remote Start) transmitted from
DCS to MarkVIe commanding the GT to start after L3RS=1 is reached and from Master Selector in HMI Remote mode is
selected. <4>
13. 231-XS-0257 S (1STOP) (PROCESS REMOTE STOP): It is a Contact Signal (NO, Close= Remote Stop) transmitted from
DCS to MarkVIe commanding the GT to stop and if in HMI Remote mode is selected. <4>
14. 231-XS-0257 T (4CT) (PROCESS REMOTE TRIP): It is a Contact Signal (NC, Open= Remote Trip) transmitted from DCS to
MarkVIe commanding the GT to Trip. <4>
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION
INTRODUCED
IN THIS PAGE
REVISED
WHERE
SHOWN <4>

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

86 of 94

15. 231-XS-0258 RS (3CRC) (CUSTOMER READY TO CRANK): It is a Contact Signal (NO, Close= Ready to Crank) transmitted
from DCS to MarkVIe giving the permissive to MarkVIe to Crank. It indicates that the Process valve purging sequence is
completed by the DCS and the valve position is ok for a pressurized or a depressurized start and that the cranking can be
started. <4>
16. 231-XS-0260 (FUEL GAS SCRUBBER SYSTEM TRIP): It is a Contact Signal (NC, Open= Trip) transmitted from DCS to
MarkVIe indicating the Trip condition from Fuel Gas Scrubber system (in customers scope). <4>
17. 231-XS-0261 (TNR) (SPEED SETPOINT FEEDBACK): It is a (4-20) mA signal transmitted from MarkVIe to DCS indicating
the speed set-point feedback. <4>
18. 231-XS-0261 AL (60LC) (LOAD SETPOINT): It is a (4-20) mA signal transmitted from DCS to MarkVIe indicating the load setpoint from DCS. It is when the LP Shaft speed is controlled by Raise / Lower command from DCS. <4>
19. 231-XS-0954 (DUCT BURNER PURGE CHANGEOVER SEQUENCE INITIATED): It is a Contact Signal (Close= Sequence
Initiated) from DCS to MarkVIe indicating that Duct Burner Purge Changeover sequence is initiated. <4>
20. 231-XS-0955 (PURGE PHASE 1 COMPLETED- BYPASS STACK): It is a Contact Signal (NO, Close= Bypass Stack Purge
completed) from MarkVIe to DCS indicating that Purge Phase-1 (Bypass Stack) is completed. <4>
21. 231-XS-0958 (GT LOAD > 60%): It is a Contact signal (NO, Close = GT Load > 60%) from MarkVIe to the DCS indicating that
GT Load is greater than 60%. <4>
22. 231-XS-2056 (HOT GAS BYPASS VALVE OPEN COMMAND FOR PURGE): It is a Contact signal (Cls=Purge) from DCS to
MarkVIe commanding the hot gas bypass valve for purging sequence. <4>
23. 231-XS-2057 (HOT GAS BYPASS VALVE OPEN/CLOSE FEEDBACK): It is a Contact signal (1=Open; 0=Close) from
MarkVIe to the DCS indicating a feedback position of hot gas bypass valve. <4>
24. 231-XS-2059 (ANTISURGE VALVE OPEN/CLOSE FEEDBACK): It is a Contact signal (1=Close; 0=Open) from MarkVIe to
the DCS indicating a feedback position of 1st stage antisurge valve. <4>
MarkVIe vs. MarkVIeS:
1. 231-XS-703A (4FCV) (OFF SKID VALVE OPEN REQUEST FROM MARKVIE): It is a Contact Signal (Close= Valve Open)
from MarkVIe to MarkVIeS indicating that Auxiliaries are started (L4=1) and Off-skid valves need to be positioned (Fuel Gas
Block valve to open and Bleed valve to close).
2.

231-XS-703B (4FUEL) (ON SKID VALVE OPEN REQUEST FROM MARKVIE): It is a Contact Signal (NO, Close= Open
valve) from MarkVIe to MarkVIeS for On-Skid Gas Fuel valve Open request).

3.

231-XS-703C (4FUEL_LIQ) (ON SKID LIQUID VALVE OPEN REQUEST FROM MARKVIE): It is a Contact Signal (NO,
Close= Open valve) from MarkVIe to MarkVIeS for On-Skid Liquid Fuel valve Open request).

4.

231-XS-705 (4TM-REQ) (TRIP MULTIPLIER ON REQUEST FROM MARKVIE): It is a Contact Signal (NO, Close= Trip
Multiplier on) from MarkVIe to MarkVIeS to activate Trip Multiplier function).

5.

231-XS-712 (4T_S) (CUMULATIVE SAFETY TRIP TO MARKVIE): It is a Contact Signal (NC, Open= Trip) from MarkVIeS to
MarkVIe indicating Cumulative Trip condition).

6.

231-XS-721 (63BT) (VENTILATION SYSTEM RUNNING): It is a contact signal (NO, Close= Running) from MarkVIeS to
MarkVIe indicating that the ventilation system is running.

7.

231-XS-726 P (28FDX_S) (COMBUSTION CHAMBER FLAME ON (PRIMARY)): It is a contact signal (NO, Close= Flame on)
from MarkVIeS to MarkVIe indicating that the combustion chamber flame is ON.

8.

231-XS-730 (45HFA) (FILTER HOUSE GAS DETECTED ALARM TO MARKVIE): It is a contact signal (NC, Open= Alarm)
from MarkVIeS to MarkVIe indicating Filter House Gas Detected Alarm condition (for any gas detector detecting a gas level of
5% LEL at filter house).

9.

231-XS-731 (45HFT) (FILTER HOUSE GAS DETECTED TRIP TO MARKVIE): It is a contact signal (NC, Open= Trip) from
MarkVIeS to MarkVIe indicating Filter House Gas Detected Trip condition (for 2oo3 gas detector detecting a gas level of 10%
LEL at filter house).

10. 231-XS-732 (45HDA-1) (ACC. COMPARTMENT GAS DETECTED ALARM TO MARKVIE): It is a contact signal (NC, Open=
Alarm) from MarkVIeS to MarkVIe indicating Enclosure Ventilation outlet (Accessory compartment) Gas Detected Alarm
condition (for 1oo3 gas detector detecting a gas level of 5% LEL at enclosure ventilation outlet).
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
REVISED
NO REVISION
WHERE
INTRODUCED
SHOWN <4>
IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

87 of 94

11. 231-XS-733 (45HDT-1) (ACC. COMPARTMENT GAS DETECTED TRIP TO MARKVIE): It is a contact signal (NC, Open=
Trip) from MarkVIeS to MarkVIe indicating Enclosure Ventilation outlet (Accessory compartment) Gas Detected Trip condition
(for 2oo3 gas detector detecting a gas level of 10% LEL at enclosure ventilation outlet).
12. 231-XS-734 (45HDA-2) (TURBINE COMPARTMENT GAS DETECTED ALARM TO MARKVIE): It is a contact signal (NC,
Open= Alarm) from MarkVIeS to MarkVIe indicating Enclosure Ventilation outlet (Turbine compartment) Gas Detected Alarm
condition (for 1oo3 gas detector detecting a gas level of 5% LEL at enclosure ventilation outlet).
13. 231-XS-735 (45HDT-2) (TURBINE COMPARTMENT GAS DETECTED TRIP TO MARKVIE): It is a contact signal (NC,
Open= Trip) from MarkVIeS to MarkVIe indicating Enclosure Ventilation outlet (Turbine compartment) Gas Detected Trip
condition (for 2oo3 gas detector detecting a gas level of 10% LEL at enclosure ventilation outlet).
14. 231-XS-736 (45HSA) (ACC. COMPARTMENT H2S DETECTED ALARM TO MARKVIE): It is a contact signal (NC, Open=
Alarm) from MarkVIeS to MarkVIe indicating Accessory compartment H2S concentration High Alarm condition.
Mark Vie vs. Plant Emergency Shutdown System:
1. 231-XS-254 R (GT RUNNING STATUS): It is a contact signal (NO, Close= Running) from MarkVIe to PESD indicating the
running status of GT (L3=1).
2.

231-XS-354 (GT SHUTDOWN FOR HRSG SHUTDOWN AND DIVERTER SYSTEM FAILURE TO CLOSE): It is a contact
signal (Open= Shutdown) from PESD to MarkVIe commanding the Gas Turbine shutdown due to HRSG shutdown and
diverter system failure to close.

3.

231-XS-454 (HRSG SHUTDOWN CONDITION RESET): It is a contact signal (Close=Reset) from PESD to MarkVIe
indicating HRSG Shutdown condition Reset.

4.

231-XS-554 (DIVERTER SYSTEM CLOSE): It is a contact signal (Close=Diverter close) from PESD to MarkVIe indicating
Diverter System close i.e. HRSG damper closed and Bypass stack damper Open.

5.

231-XS-654 (DIVERTER SYSTEM OPEN): It is a contact signal (Close=Diverter open) from PESD to MarkVIe indicating
Diverter System open i.e. HRSG damper open and Bypass stack damper closed.

6.

231-XS-754 (TEG TEMPERATURE 56 DEG C LOWER THAN FUEL AUTO IGNITION TEMPERATURE): It is a contact signal
(Close=Lower) from MarkVIe to PESD indicating Turbine exhaust Gas Temperature 56 deg. C Lower than Fuel Auto Ignition
temperature.

MarkVIe vs. Bently Nevada 3500 Temperature Monitoring System:


1. 231-XS-450 (43TM_ARST) (TEMPERATURE MONITOR RESET): It is a contact signal (Close= Reset) from MarkVIe to BN
Temp Monitor commanding Reset of the BN Temperature Monitor.
2.

231-XS-451 A (26TMA) (TEMPERATURE MONITOR CUMULATIVE ALARM): It is a contact signal (Open=Alarm) from BN
Temp Monitor to MarkVIe indicating cumulative alarm condition of Bearing metal temperature measurement.

3.

231-YS-430 (CENTRIFUGAL COMPRESSOR THRUST BEARING TEMPERATURE TRIP): It is a contact signal (Open=Trip)
from BN Temp Monitor to MarkVIe indicating trip condition of Thrust Bearing metal temperature.

4.

231-YS-451 F (86TM) (TEMPERATURE MONITOR FAULT): It is a contact signal (Open=Fault) from BN Temp Monitor to
MarkVIe indicating fault condition of the BN Temperature Monitor.

MarkVIe vs. Bently Nevada 3500 Vibration Monitoring System:


1. 231-XS-400 (43VM_ARST) (VIBRATION MONITOR RESET): It is a contact signal (Close= Reset) from MarkVIe to BN
Vibration Monitor commanding Reset of the BN Vibration Monitor
2.

231-XS-402 A (39VMA) (VIBRATION MONITOR CUMULATIVE ALARM): It is a contact signal (Open=Alarm) from BN
Vibration Monitor to MarkVIe indicating cumulative alarm condition of Bearing vibration measurement.

3.

231-YS-402 F (86VM) (VIBRATION MONITOR FAULT): It is a contact signal (Open=Fault) from BN Vibration Monitor to
MarkVIe indicating fault condition of the BN Vibration Monitor.

4.

231-YS-402 T (39VMT) (VIBRATION MONITOR CUMULATIVE TRIP): It is a contact signal (Open=Trip) from BN Vibration
Monitor to MarkVIe indicating cumulative trip condition of Bearing vibration measurement.

5.

231-YS-415 (39VC-1T) (CENTRIFUGAL COMPRESSOR RADIAL TRIP): It is a contact signal (Open=Trip) from BN Vibration
Monitor to MarkVIe indicating trip condition from Radial Vibration of bearings.

6.

231-YS-416 (39PC-1T) (CENTRIFUGAL COMPRESSOR AXIAL TRIP): It is a contact signal (Open=Trip) from BN Vibration
Monitor to MarkVIe indicating trip condition from Axial Displacement of bearings.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

88 of 94

MarkVIe vs. Unit Control System:


1. 231-XS-601A (86PS-1) (24VDC BUS 1 FAILURE): It is a contact signal (Open=Failure) from UCS to MarkVIe indicating
failure condition of 24VDC Bus 1.
2.

231-XS-601B (86PS-2) (24VDC BUS 2 FAILURE): It is a contact signal (Open=Failure) from UCS to MarkVIe indicating
failure condition of 24VDC Bus 2.

3.

231-XS-602 (86PS-FG) (FIRE FIGHTING 24VDC BUS FAILURE): It is a contact signal (Open=Failure) from UCS to MarkVIe
indicating failure condition of 24VDC Bus in Fire Fighting Panel.

4.

231-XS-603 (86PS-FIELD) (FIELD 24VDC POWER BUS FAILURE): It is a contact signal (Open=Failure) from UCS to
MarkVIe indicating failure condition of 24VDC Bus to power field instruments.

5.

231-XS-605 (XA-1) (UCS ALARM BUZZER): It is a wet voltage contact from MarkVIe to UCS (Open= Buzzer on) indicating
alarm or trip condition.

6.

231-XS-607 (49UCS) (UCS HIGH TEMPERATURE ALARM): It is a contact signal (Open=Alarm) from UCS to MarkVIe
indicating high temperature inside UCS.

7.

231-XS-612 A (110V AC BUS FAILURE AT TRAINVIEW SERVER PANEL): It is a contact signal (Open=Failure) from
Trainview Server Panel to MarkVIe indicating failure condition of 110VDC Bus at Trainview Server Panel.

8.

231-XS-613 A (24VDC BUS FAILURE AT TRAINVIEW SERVER PANEL): It is a contact signal (Open=Failure) from
Trainview Server Panel to MarkVIe indicating failure condition of 24VDC Bus at Trainview Server Panel.

MarkVIe vs. Local Control Panel:


1. 231-XS-614 (24VDC BUS FAILURE AT LOCAL CONTROL PANEL): It is a Contact signal (Open = Bus Failure) from LCP to
MarkVIe indicating 24VDC Bus failure at LCP.
2.

231-XS-615 (INVERTER FAILURE AT LOCAL CONTROL PANEL): It is a Contact signal (Open = Inverter Failure) from LCP
to MarkVIe indicating Inverter failure at LCP.

3.

231-XS-616 (LCP ALARM BUZZER SIGNAL): It is a wet contact (110Vdc, Closed = Alarm buzzer on) signal transmitted from
MarkVIe to DCP indicating the alarm or trip condition.

MarkVIe vs. Liquid Fuel Thyristor Panel:


1. 231-XA-5015A (LIQUID FUEL THYRISTOR PANEL FAULT): It is a Contact Signal (Open= Fault) from Liquid Fuel Thyristor
Panel to MarkVIe indicating the Fault status of the Liquid Fuel Thyristor Panel.
2.

231-XL-5015A (LIQUID FUEL HEATER RUNNING STATUS): It is a Contact Signal (Close= Running) from Liquid Fuel
Thyristor Panel to MarkVIe indicating the Running status of the Liquid Fuel Heater.

3.

231-XS-5015A (LIQUID FUEL HEATER CUT-OFF STATUS): It is a Contact Signal (Open= Cut-off) from Liquid Fuel Thyristor
Panel to MarkVIe indicating the Cut-off status of the Liquid Fuel Heater.

4.

TIT-5014 (LIQUID FUEL HEATER TEMPERATURE): It is a (4-20) mA signal from MarkVIe to Liquid Fuel Thyristor Panel that
gives analog set-point to the Liquid Fuel Thyristor Panel to turn-on or turn-off the heater based on temperature feedback of
liquid fuel received from field.

MarkVIe vs. Seal Gas Heater Thyristor Panel:


1. 231-TSHH-5210A (SEAL GAS HEATER CUT-OUT STATUS): It is a contact signal (Open= Cut-Out) from Thyristor Panel to
MarkVIe indicating cut-out condition of the Seal gas Heater.
2.

231-UA-5209A (TH1_F) (THYRISTOR PANEL FAULT STATUS): It is a contact signal (Open= Fault) from Thyristor Panel to
MarkVIe indicating fault condition of the Thyristor Panel.

3.

231-XA-809 (SEAL GAS HEATER SET POINT TO THYRISTOR PANEL): It is a (4-20) mA signal transmitted from MarkVIe to
Thyristor Panel providing Seal Gas Heater Set-point.

4.

231-XI-5209A (TH1_ON) (THYRISTOR PANEL ON STATUS): It is a contact signal (Close=ON) from Thyristor Panel to
MarkVIe indicating ON condition of the Thyristor Panel.

5.

231-XI-5210A (H1_ON) (SEAL GAS HEATER ON/OFF COMMAND): It is a contact signal (Close=ON, Open = OFF) from
MarkVIe to Thyristor Panel commanding ON condition of the Seal Gas Heater.

6.

231-XS-5209A (TH1_CUT) (SEAL GAS HEATER CUT OUT): It is a contact signal (Close=Cut out) from MarkVIe to Thyristor
Panel commanding Cut out of the Seal Gas Heater.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

89 of 94

MarkVIe vs. Pulse Jet Panel:


1. 231-XS-522 (86PJ) (PULSE JET PANEL FAULT): It is a contact signal (Open= Fault) from Pulse Jet Panel to MarkVIe
indicating Fault status of the Pulse Jet Panel.
2.

231-XS-523 (52PJ) (PULSE JET CLEANING CYCLE IN PROGRESS): It is a contact signal (Close= in progress) from Pulse
Jet Panel to MarkVIe indicating Pulse Jet Cleaning in Progress.

MarkVIeS vs. Fire Fighting System:


1. 231-XS-657 TS (45FTT_S) (FIRE DETECTED TRIP TO SAFETY SYSTEM): It is a contact signal (NC, Open=trip) from Fire
Fighting System to MarkVIeS indicating GT Trip due to Fire detection.
MarkVIeS vs. MCC:
1. 231-XS-709 A (4BA1_C) (VENTILATION MAIN FAN CUT-OUT): It is a Contact signal (NC, Open= Cut-out) from MarkVIeS to
MCC commanding the cut out of the ventilation main fan.
2.

231-XS-709 B (4BA2_C) (VENTILATION STAND-BY FAN CUT-OUT): It is a Contact signal (NC, Open= Cut-out) from
MarkVIeS to MCC commanding the cut out of the ventilation stand-by fan.

MarkVIeS vs. Plant Emergency Shutdown System:


1. 231-XS-700 A (CESD-1) (CUSTOMER ESD SIGNAL 1): It is a Contact signal (Open= ESD) from PESD to MarkVIeS
commanding the Emergency Shutdown (Pressurized).
2.

231-XS-700 B (CESD-2) (CUSTOMER ESD SIGNAL-2): It is a Contact signal (Open= ESD) from PESD to MarkVIeS
commanding the Emergency Shutdown (Depressurized).

3.

231-XS-700 C (CESD_OP) (SAFETY TRIP REPETITION TO CUSTOMER ESD- PRESSURIZED): It is a Contact signal (NC,
Open= Trip) from MarkVIeS to PESD indicating the Emergency Shutdown (Pressurized).

4.

231-XS-700 D (CESD_ODP) (SAFETY TRIP REPETITION TO CUSTOMER ESD- DEPRESSURIZED): It is a Contact signal
(NC, Open= Trip) from MarkVIeS to PESD indicating the Emergency Shutdown (Depressurized).

MarkVIeS vs. Unit Control System:


1. 231-XS-717 (5ESD-R1) (ESD PUSH BUTTON FROM SAFETY RELAY- PRESSURIZED): It is a Contact signal (NC, Open=
Trip) from UCS to MarkVIeS indicating the Emergency Shutdown (Pressurized).
2.

231-YZ-575 T2 (5ESD-R2) (ESD PUSH BUTTON FROM SAFETY RELAY- DEPRESSURIZED): It is a Contact signal (NC,
Open= Trip) from UCS to MarkVIeS indicating the Emergency Shutdown (Depressurized).

MarkVIeS vs. Bently Nevada 3500 Vibration Monitoring System:


1. 231-XS-713 (4TM) (TRIP MULTIPLIER ON REQUEST TO VIBRATION MONITOR): It is a contact signal (Close= Trip
Multiplier ON) from MarkVIeS to BN Vibration Monitor commanding the Trip Multiplier function to be ON.
2.

231-YS-426 A (39BNVT-1) (CUMULATIVE VIBRATION TRIP 1 TO ESD SYSTEM): It is a contact signal (NC, Open=Trip)
from BN Vibration Monitoring System to MarkVIeS indicating cumulative vibration trip 1.

3.

231-YS-426 B (39BNVT-2) (CUMULATIVE VIBRATION TRIP 2 TO ESD SYSTEM): It is a contact signal (NC, Open=Trip)
from BN Vibration Monitoring System to MarkVIeS indicating cumulative vibration trip 2.

4.

231-YS-429 (39VT) (TURBINE SEISMIC TRIP): It is a contact signal (NC, Open=Trip) from BN Vibration Monitoring System
to MarkVIeS indicating Turbine Seismic Trip.

CCC vs. Unit Control System:


1. 231-XS-306 (COMMUNICATION DEVICE FAULT FOR MASTER CONTROLLER): It is a contact signal (NC, Open=Fault)
from CCC Master Controller chassis to CCC Master Controller indicating communication device fault to Master Controller.
2.

231-XS-601 C (COMMUNICATION DEVICE FAULT): It is a contact signal (NC, Open=Fault) from CCC Anti-surge Controller
chassis to CCC Anti-surge Controller indicating communication device fault to Anti-surge Controller.

3.

231-XS-601D (HVAC SYSTEM FAULT): It is a contact signal (NC, Open=Fault) from CCC Controller chassis to CCC
Controller indicating HVAC System fault to CCC Controller.

4.

231-XS-601 E (ANTISURGE CONTROLLER POWER / FAN FAULT): It is a contact signal (NC, Open=Fault) from CCC Antisurge Controller chassis to CCC Anti-surge Controller indicating Power/ Fan fault to Anti-surge Controller.

5.

231-XS-701 E (MASTER CONTROLLER POWER/FAN FAULT): It is a contact signal (NC, Open=Fault) from CCC Master
Controller chassis to CCC Master Controller indicating power/ fan fault to Master Controller.

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

90 of 94

Customer DCS vs. CCC:


1. 231-XA-0997 PROCESS REMOTE SET-POINT (CTRL OF DISCHARGE HEADER PRESSURE): It is a 4-20mA signal from
Customer DCS to CCC (Master Controller) to perform Load Sharing by Controlling the Compressor Discharge Header
Pressure. <4>
2.

231-XS -0305 (DISCHARGE PRESSURE CONTROL ENABLE): It is a contact signal (NO, Closed = Enable) from Customer
DCS to CCC to switch over from Suction Header Control Mode to Discharge Header Control Mode. <4>

3.

231-XS-0999 (MCP_SP) (PROCESS REMOTE SET-POINT (CTRL OF SUCTION HEADER PRESSURE): It is a 4-20mA
signal from Customer DCS to CCC (Master Controller) to perform Load Sharing by Controlling the Compressor Suction
Header Pressure. <4>

4.

231-XS-2058 (CLOSE ANTISURGE VALVE FOR PURGE): It is a contact signal (Cls=Purge) from Customer DCS to CCC
commanding the antisurge valve for purging sequence. <4>

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
REVISED
WHERE
SHOWN <4>
NO REVISION
INTRODUCED
IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

91 of 94

8 CONTROL INTERFACE WITH WASTE HEAT RECOVERY UNIT


CONTROL SYSTEM
8.1.1 INTERLOCK SIGNALS <4>
JOB TAG
231-XS-0958
231-XS-0955
231-XS-0954
231-XS-254 R
231-XS-354
231-XS-454
231-XS-554
231-XS-654
231-XS-754
231-XS-960
231-XS-961

DESCRIPTION
GT Load Greater than 60%
Purge Phase 1 completed (Bypass stack)
Duct Burner Purge Changeover Sequence initiated
GT Running Status
GT Shutdown for HRSG Shutdown and Diverter
System failure to close
HRSG Shutdown condition Reset
Diverter System Close
Diverter System Open
Teg temperature 56 deg. C lower than Fuel Auto
Ignition temperature
Duct Burner Purge Completed
GT Load Greater than 60%

FROM
MarkVIe
MarkVIe
DCS
MarkVIe
PESD

TO
DCS
DCS
MarkVIe
PESD
MarkVIe

TYPE
HW
HW
HW
HW
HW

PESD
PESD
PESD
MarkVIe

MarkVIe
MarkVIe
MarkVIe
PESD

HW
HW
HW
HW

BMS
MarkVIe

MarkVIe
BMS

HW
HW

8.1.2 SOFTWARE DESCRIPTION


GT + HRSG PURGE & START UP (GT/BMS SYSTEMS LOGIC DCS LOGIC)
A purge of both the HRSG enclosure and by-pass system shall be completed prior to the light-off of the GT
and prior to the admission of combustion turbine exhaust gas into the HRSG. The purge sequence
(GT+HRSG) shall be managed by MarkVIe.
Purge shall be accomplished by at least five volume changes and for duration of not less than 5 minutes.
During the purge, the flow rate shall be not less than 8% of GT full-load mass air-flow.
Depending on the availability of the HRSG, the followings two cases have to be considered:
First case - HRSG available
When the HRSG is available, the GT can operate in combined cycle mode. In this case both the by-pass
stack and the HRSG must be purged. With all the following purge permissives MarkVIe can start the
GT/HRSG purge sequence:
HRSG shutdown not present (231-XS-454)
No GT shutdown causes present and GT trip condition reset (231-XS-254 R)
Diverter damper system close (231-XS-554) that indicates the condition HRSG damper closed &
bypass stack Damper open from PESD)
GT not firing
GT flow rate not less than 8% of GT full-load mass air-flow
The GT+HRSG purge sequence will purge first the By-pass stack (phase 1) and then the HRSG duct (phase
2).
At the end of the phase 1, the MarkVIe will send to DCS the hardwire signal 231-XS-0955 (Purge phase 1
completed by GTS) in order to open the diverter system dampers allowing the purge sequence to proceed
with the phase 2. The phase 2 is allowed to proceed when the Diverter System Open (231-XS-654) signal is
obtained from PESD. The Diverter system Open condition is equivalent to HRSG damper open and by pass
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION
REVISED
WHERE
INTRODUCED
SHOWN <4>
IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

92 of 94

damper in closed condition.<4>


The purge rate, volume changes and duration will be provided by MarkVIe for both phases. At the purge end
(i.e. both the phase 1 and the phase 2 are completed), the GTS will have the permissive to put the GT in
service in combined cycle mode through the HRSG.
The following signals shall be available from MarkVIe to DCS, by serial link:
GT+HRSG Purge requested
GT+HRSG Purge in progress (phase 1, phase 2)
GT+HRSG Purge completed (phase 1, phase 2)
GT+HRSG Purge interrupted (phase 1, phase 2)
HRSG purge in Fresh Air (FA) mode
The Phase 2 (HRSG duct purge by GTS) could be replaced, as alternative, by the duct burner purge
performed in FA mode (FA duct burner purge sequence managed by BMS logic).
In this case, after the HRSG duct purging in FA mode the DCS logic, with all the following permissives:
NOT GT Running (~231-XS-254 R)
HRSG in FA mode
HRSG isolation provided and maintained
Duct burner purge completed by BMS (after HRSG isolation provided and maintained) (231-XS-960)
HRSG duct purging in FA mode enabled by DCS (selection by operator) shall transfer the system to
Combined Cycle mode by the following way: when GTS sends the hardwire signal (231-XS-0955) to DCS
(purge phase 1 completed by GTS) then the DCS will execute the following sequence: <4>
Diverter damper system open command
Set the signal: Duct Burner Purge change-over sequence initiated (231-XS-0954) <4>
With the signal, Diverter damper system NOT in close position (~231-XS-554) the DCS shall carry out:
FA duct damper close command (hardwired signal sent to the Diverter Damper System)
With the resulting signals:
Diverter damper system in open position & FA duct damper in close position (xx seconds delayed)
The DCS shall carry out:
FA fan stop command (FA fan damper will close)
Reset the signal: Duct Burner Purge change-over sequence initiated (231-XS-0954) <4>
The signal: Duct Burner Purge change-over sequence initiated is reset also if at least one of the following
conditions is detected:
HRSG Shutdown
GT running (231-XS-254 R)
GT trip (from PESD to DCS)
Purge phase 1 completed (231-XS-0955) NOT present <4>
This signal is reset, in any case, after a prefixed time (about xx seconds, to allow the complete execution of
the transfer sequence to CC mode).
MarkVIe will set the condition purge phase 2 completed and will have the permissive to put the GT in service
in combined cycle mode, through the HRSG, when MarkVIe verifies the following condition:
Purge phase 1 completed (231-XS-0955) & <4>
Duct Burner Purge Completed (231-XS-960) from BMS (10 sec Off-Delay in order to allow the
diverter opening) &
Duct Burner Purge change-over sequence initiated (231-XS-0954) & <4>
Diverter Dampers system in open position (231-XS-654).
TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
REVISED
WHERE
SHOWN <4>
NO REVISION
INTRODUCED
IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
N/A
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

93 of 94

Second Case - HRSG not available


If HRSG shutdown is present (HSRG not available), the GT can operate only in open cycle mode. In this
case, MarkVIe can start the GT purge sequence through the by-pass stack (phase 1) if all the following
purge permissives are fulfilled:
No GT shutdown causes present and GT trip condition reset from MarkVIe
Diverter damper system close (231-XS-554)
GT not firing
GT flow rate not less than 8% of GT full-load mass air-flow
The purge rate, volume changes and duration shall be decided by MarkVIe.
At the end of the phase 1 (GT+ By-pass stack purge completed), MarkVIe will have the permissive to put the
GT in service in open cycle mode (through the by-pass stack).
During combined cycle operation and following the GT+HRSG purge as above indicated, the combustion
turbine shall be permitted to switch in open cycle mode (by closing the diverter system dampers by DCS)
and to purge and operate in open cycle through the by-pass stack.
When GT has operated in open cycle through the by-pass stack, then the HRSG purged condition shall be
reset. In this case the TEG shall not be permitted to re-enter the HRSG at a later time without HRSG repurging (the opening of the diverter system dampers shall not been allowed by DCS and PESD).
With GT running in open cycle mode through the by-pass stack, then the following two scenarios can be
considered:

HRSG duct shall be purged in FA mode (FA duct burner purge sequence managed by BMS logic. In
FA mode it shall be possible to light-off the auxiliary fire burner and start up the HRSG; then the TEG
shall be permitted to re-enter the HRSG at a later time (by activating the manual change over
sequence from FA mode to CC mode, without lowering the GT load. TEG shall not be permitted to
re-enter the HRSG if the HRSG is not in service, pressurized and in hot state.

The GT is operated with an exhaust gas temperature at least 56C lower the auto-ignition
temperature of fuels (231-XS-754) designed for use in the GT and in the Duct burner (TEG temp. <=
xxx C, to be defined - 231-XS-957).In this case th e TEG, at this lower temperature, shall be
permitted to re-enter the HRSG (by opening the diverter system dampers by DCS) and shall be used
to perform the duct burner purge (monitored by BMS). After the duct burner purge (hardwired signal
from BMS to MarkVIe 231-XS-960), MarkVIe will have the permissive to increase the load. Further
limitations in TEG temperature are foreseen according to the actual status of HRSG.

NOTE
1) HRSG isolation shall be considered maintained when all the following conditions are satisfied:
HRSG damper close (hardwired signal from PESD to DCS)
Sealing air pressure > min (xx sec maintained in order to allow sealing fans change over) (hardwired
signal from PESD to DCS)

TITLE:
CONTROL SYSTEM FUNCTIONAL DESCRIPTION
REVISION DESCRIPTION:
NO REVISION INTRODUCED IN THIS PAGE

DOCUMENT CODE

REVISION

SOM6629548
PAGE MARKER
Undef.
ORIGINAL JOB

18000571800057-58

4
SECURITY CODE

N
SIZE

THIS DOCUMENT IS AND CONTAINS CONFIDENTIAL AND PROPRIETARY INFORMATION OF Nuovo Pignone S.r.l. WHICH SHALL NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE
WRITTEN PERMISSION OF Nuovo Pignone S.r.l. . UNPUBLISHED WORK 2012
2012 Nuovo Pignone S.r.l..
S.r.l.. ALL RIGHTS RESERVED.

LANGUAGE

A
SHEET

94 of 94