SBI-PDP-ADV80
......
Instruction manual
Before using the product, read the safety instruction section carefully.
Keep the manual in a safe place and available to engineering and installation personnel during the product functioning period.
Gefran S.p.A has the right to modify products, data and dimensions without notice. The data
can only be used for the product description and they can not be understood as legally stated
properties.
Thank you for choosing this Gefran product.
We will be glad to receive any possible information which could help us improvingthis manual.
The e-mail address is the following: techdoc@gefran.com.
All rights reserved.
SBI-PDP-ADV80
Sommario - Contents
Informazioni riguardo a questo manuale.................................. 2
Capitolo 1 - Introduzione............................................................ 5
1.1 Il Manuale....................................................................................................................5
1.2 Profibus-DP in Generale.............................................................................................5
2.1 Dimensioni................................................................................................................. 6
2.2 Montaggio.................................................................................................................. 6
2.3 Alimentazione............................................................................................................ 7
2.4 LED........................................................................................................................... 7
2.5 Configurazione del DIP-Switch.................................................................................. 7
2.6 Specifiche Tecniche................................................................................................... 8
2.7 Interfaccia.................................................................................................................. 8
Capitolo 10 - Altro..................................................................... 31
10.1 Glossario............................................................................................................... 31
10.2 Abbreviazioni......................................................................................................... 31
10.3. Riferimenti............................................................................................................ 31
SBI-PDP-ADV80
Chapter 1 - Introduction........................................................... 32
2.1 Dimensions.............................................................................................................. 33
2.2 Mounting.................................................................................................................. 33
2.3 Power Supply.......................................................................................................... 34
2.4 LEDs........................................................................................................................ 34
2.5 Configurazione del DIP-Switch................................................................................ 34
2.6 Technical Specification............................................................................................ 35
2.7 Interface.................................................................................................................. 35
Chapter 10 - Miscellaneous...................................................... 58
10.1 Glossary................................................................................................................ 58
10.2 Abbreviations......................................................................................................... 58
10.3. References........................................................................................................... 58
SBI-PDP-ADV80
Capitolo 1 - Introduzione
Questo manuale descrive la scheda opzionale SBI-PDP-ADV80 per la connessione degli inverter alle reti Profibus-DP.
Questo manuale indirizzato a progettisti e tecnici responsabili per la manutenzione, messa in servizio e funzionamento dei sistemi Profibus-DP.
Si suppone una conoscenza di base di Profibus-DP mentre ulteriori informazioni
sono disponibili nel manuale Draft Standard DIN 19245 Parte 3.
1.1 Il Manuale
Capitolo 2 Montaggio meccanico della scheda e connessioni elettriche.
Capitolo 3 Trasmissione dati Master - Slave
Capitolo 4 Questa sezione descrive come gestire il drive tramite la control word
e la status word e come accedere ai parametri del drive.
Capitolo 5 Gestione diagnostica Profibus-DP
Capitolo 6 Assegnazione dei parametri del drive agli I/O virtuali digitali
Capitolo 7 Questa sezione descrive come agire senza Profidrive Profile.
Capitolo 8 Men tastierino del drive
Capitolo 9 Numero di identificazione e codici per la connessione del Bus
Capitolo 10 Altro: glossario, abbreviazioni e riferimenti
1.2 Profibus-DP in Generale
Profibus-DP un Bus di campo progettato per un veloce scambio di dati a livello
sensore/attuatori; la comunicazione viene stabilita tra lunit centrale del Master
(PLC oppure PC) e le unit dello Slave, vale a dire sensori, attuatori, drive ecc.
La durata totale del ciclo dipende dal numero di Slave collegati; il Baud Rate da
1,5-Mbit/s permette di interrogare 8 drive Gefran in un periodo di 6 millisecondi. Il
supporto fisico dato dalla linea seriale RS485; al Bus pu essere collegato un
numero massimo di 125 Slave.
Esempio di sistema Profibus-DP Mono-Master.
Italiano
Lo scambio di dati ciclico; lunit Master legge i dati in ingresso dello Slave e
scrive i dati in uscita dello Slave. La durata del ciclo del Bus inferiore a quella
dellunit centrale; i Baud Rate della scheda SBI possono essere inclusi tra 9,6
kbit/s e 12 Mbit/s in base agli standard di Profibus-DP, sezione 3.
MASTER
SLAVE
SLAVE
English
SLAVE
34.75 mm
(1.38 in)
Italiano
25 mm
2.2 Montaggio
English
La scheda SBI deve essere fissata su una guida DIN da 35 mm. tramite lapposita molla di fissaggio; si raccomanda di tenere la scheda SBI-PDP-ADV80 il pi
possibile vicino al drive.
Non posizionare il cavo di connessione SBI-Drive vicino ai cavi di potenza.
EXP-SEL
Dip-switch che seleziona lindirizzo dellopzione
DEA, AL, PWR
Leds di segnalazione
PDP-ADD
display a 2 cifre che visualizza lindirizzo Profibus dellazionamento
XS
connettore per il collegamento del Bus
PE
connettori per la messa a terra, devono essere collegati entrambi per aumentare
limmunit ai disturbi.
XOPT
connettori in parallelo per il collegamento a drive e a un altro eventuale dispositivo.
1.
Spegnere il drive.
2.
3.
4.
Accendere il drive.
5.
6.
7.
Sul display verr visualizzato lindirizzo del nodo Profibus, impostato con il
parametro I.750 - SBI Address.
2.4 LED
PWR (Verde)
Alimentazione a +5V.
AL (Rosso)
Allarme attivo.
DEA (Giallo)
English
Lalimentazione viene fornita al connettore XOPT che viene utilizzato anche per il
trasferimento dei dati tra la scheda SBI e la scheda di regolazione del drive.
Italiano
2.3 Alimentazione
ON
OFF
1
2
ON
Queste temperature sono adeguate a quelle del drive al quale le schede vengono
connesse.
2.7 Interfaccia
Per la connessione al Bus utilizzare un doppino schermato come indicato dalla
specifica Profibus.
I pinout dei connettori del Bus (XS) sono i seguenti:
XS
5
9
Italiano
PIN
RIFERIMENTO
Schermo
Non collegato
RX / TX - B
Non collegato
0V - GND
+5V
Non collegato
RX / TX - A
Non collegato
SIGNIFICATO
Schermo / massa a terra
Ricezione / trasmissione dato P
Potenziale trasmissione dato (terra a 5V)
Alimentazione della resistenza -P di terminazione (P 5V)
Ricezione / trasmissione dato P
English
SBI-PDP-ADV80
XS1
XS1
XS1
English
Italiano
SBI-PDP-ADV80
Italiano
Offset
Sub
Offset
10
11
12
13
14
15
16
17
18
10
19
11
20
12
Custom
PPO-1
PPO-2
PPO-3
PPO-4
PCV
PCV
PCV
Nu
Nu
PDC-W0
CTW/STW
CTW/STW
CTW/STW
CTW/STW
PDC-W1
SP/AF
SP/AF
SP/AF
SP/AF
PDC-W2
Nu
PDC-W0
Nu
PDC-W0
PDC-W3
Nu
PDC-W1
Nu
PDC-W1
PDC-W4
Nu
PDC-W2
Nu
PDC-W2
PDC-W5
Nu
PDC-W3
Nu
PDC-W3
English
Nu Non utilizzato
CTW
STW
10
Larea PCV costituita da 7 byte e serve per leggere e scrivere i parametri dellazionamento uno alla volta.
PCV
1
3-4
PCA LOW
PCA HIGH
PCA
WL-BL
WL-BH
WH-BL
WH-BH
SIND
PCA
PVA
16 bits
PCA (16 bits)
15
14
13
RC
12
11
10
TB
Index
RC
Richiesta
0
Nessuna richiesta
Lettura parametro
3..15
Non utilizzato
Nessuna risposta
Lettura parametro
Scrittura parametro
Non utilizzato
Non utilizzato
Non utilizzato
Non utilizzato
Richiesta rifiutata
8..15
Non utilizzato
TB
Index
I dati provenienti da Profibus-DP e letti dallo Slave vengono indicati come dati
in ingresso; i dati scritti in Profibus-DP dallo Slave vengono indicati come dati in
11
English
Italiano
Risposta
uscita.
I parametri dello Slave vengono letti ciclicamente dal Master assegnando i parametri del drive ai parametri di configurazione delluscita PDC.
Il Master trasmette ciclicamente i parametri del drive allo Slave assegnando i
parametri del drive ai parametri di configurazione dellingresso PDC.
Lassegnazione dei parametri del drive alla Word del Process Data Channel viene
eseguita utilizzando lindice del parametro stesso (I.760 e seguenti).
Al Process Data Channel possono essere assegnati solo parametri del drive con
unampiezza di 16 bit (1 Word). I parametri I.760 ... I.775 con indice uguale a 0000
indicano che la word non stata assegnata a nessun parametro dellazionamento.
Per la configurazione dei Process Data Channel (PDC) vedere il manuale di
istruzione dellazionamento (paragrafo 7.4, Menu I - INTERFACE, parametri I.760
e successivi).
Nota!
A seconda della configurazione selezionata si dovranno configurare un numero di Word differenti; esempi:
Italiano
English
Per abilitare la scrittura del Riferimento di frequenza bisogna selezionare il parametro F.050 Ref 1 channel = [8] Profidrive.
12
Word
PDC
PCA
IND
PVA
CTW MRV
STW MAV
PDC
1
PDC
2
PDC
3
PDC
4
10
10
PDC
5
PDC
6
PDC
7
PDC
8
Italiano
PCV
PPO1
Word
Word
English
PPO2
PPO3
Word
PPO4
13
Italiano
Bit # della
control word
Bit = 0
Bit =1
ON1
ON2
ON3
Operazione disabilitata
Operazione disabilitata
Condizione di attivazione
Nessuna funzione
Riconoscimento errore
Non utilizzato
Non utilizzato
Non utilizzato
Non utilizzato
10
Dati validi
11
Nessuna funzione
Inversione
Non utilizzato
Non utilizzato
12-15
English
Bit 0, OFF1/ON1:
Bit = 0 :
Bit = 1 :
Bit 1, OFF2/ON2:
14
Bit = 0 :
Bit = 1 :
soddisfatte.
Bit 2, OFF3/ON3:
Bit = 0 :
Bit = 1 :
Bit = 1 :
Bit = 1 :
Bit =1 :
Bit = 0 :
Bit =1 :
Bit =1 :
lerrore viene identificato sul fronte positivo, vale a dire bit = 0 poi 1..
Italiano
Bit = 0 :
Bit =1 :
Bit = 0 :
Bit =1 :
15
English
Bit = 0
Bit =1
Operazione inibita
Operazione abilitata
Nessun errore
Operazione disabilitata
OFF2
ON2
OFF3
ON3
Intervento allarme
Nessun allarme
Allarme
Frequenza uguale al
valore di riferimento
valore di riferimento
Controllo locale
Controllo Bus
10
11-15
Non utilizzato
Non utilizzato
Bit =1 :
Italiano
Bit =1 :
il bit 0,1,2 o 3 della control word (OFF1, OFF2, OFF3 oppure operazione disabilitata) impostato a 0 oppure il drive in condizione
dallarme.
Bit =1 :
English
Bit =1 :
16
Bit =1 :
Bit =1 :
Bit =1 :
Bit 8, Frequenza diversa dal valore di riferimento / Frequenza uguale al valore di riferimento:
Bit = 0 :
Bit =1 :
Nota! Lampiezza di tolleranza della frequenza viene configurata nel parametro P.460.
Bit =1 :
P.000 - Cmd source sel = [4] Control word and F.050 - Ref 1 channel
= [8] Profidrive.
Bit = 0 :
Bit =1 :
Italiano
English
17
18
Bit 2
Coast stop
Italiano
Bit 6=1
Bit 0=1
Ready
Bit 1=1
ON1 (bit 0 = 1)
Ready to
switch-on
Fault
Stop drive
Bit 3=1
OFF2 (bit 1 = 0)
Fault acknowledge
(bit 7: 0 to 1)
OFF3 (bit 2 = 0)
OFF1 (bit 0 = 0)
Switch-on
inhibit
Enable operation
OFF3 active
Quick stop
Coast stop
OFF2 active
stage 1
(bit 3 = 1)
Bit 5=0
Bit 4=0
RFG output
Enable
Drive stopped
disabled
Bit 2=1
operation
(bit 4 = 0)
A
RFG output enabled Open load
OFF3 active
From every state
C
D
stage 2
contactor
(bit 4 = 1)
OFF1 (bit 0 = 0)
Ramp function
Stop RFG
generator
Load
Load
(bit 5 = 0)
Normal
OFF1 active
Enabled output
contactor
contactor
stop
stage 1
B
RFG acceleration enabled
open
open
D
(bit
5
=
1)
Drive stopped
Inhibit
Ramp function
Bit 1=0
setpoint
OFF1 active
generator
Open load
(bit 6 = 0)
stage
2
Accel. Enabled
contactor
Enable setpoint
C
(bit 6 = 1)
Load contactor open
Operation
D
state
Drive stopped
Inhibit
operationactive
Inhibit operation
(bit 3 = 0)
A B C D
Voltage ON
Voltage
switched-off
English
3-4
PCA LOW
PCA HIGH
PCA
WL-BL
WL-BH
WH-BL
WH-BH
SIND
PVA
14
13
RC
12
11
10
TB
Index
TB
Index
SIND
PVA
2 Word
High Word
Low Byte
High Byte
Low Byte
High Byte
Byte 4 di PCV
Byte 5 di PCV
Byte 6 di PCV
Byte 7 di PCV
19
English
RC
Italiano
Gestione PCA:
Gestione richiesta/risposta
La sezione RC della word PCA definisce quale richiesta/risposta pu essere
emessa.
Richiesta Funzione
0
Nessuna richiesta
Italiano
Risposta Funzione
0
Nessuna risposta
9-15
Non utilizzato
Se il drive rifiuta una richiesta del master, la word RC nel PPO di lettura indicher
tale condizione assumendo il valore 7.
Il numero di descrizione dellerrore (vedere sotto) disponibile nella parte PVA.
English
Numero errore
20
Descrizione
Sottoindice sbagliato
Nessun insieme
11
17
101
102
103
104
105
106
00 00
non utilizzato
02 00
00 00
06 4F
control word
00 40
Italiano
38 21
38 11
00 00
non utilizzato
02 00
00 00
37 03
status word
00 40
velocit reale
English
21
English
Italiano
La comunicazione tra il Master e lo Slave pu avvenire solo se sono state terminate con successo linizializzazione del drive e della scheda SBI; in caso contrario
non possibile determinare la causa dellerrata inizializzazione utilizzando il Bus.
22
Maschera Bit i
Sorgente DI i
Sorgente DO i
Morsetto
Funzione Drive
Virtuale
Controllo virtuale
Fare anche riferimento al paragrafo 7.4, Menu I Interface, sezione Abilitazione I/O
virtuali del manuale distruzioni del drive.
Per ulteriori informazioni riguardo la configurazione degli I/O digitali virtuali, fare
riferimento al paragrafo 7.9 HIDDEN, sezione Comandi I/O virtuali del manuale
distruzioni del drive:
Italiano
I parametri maschera devono essere gestiti in base ai bit. Ad ogni bit corrisponde
uno switch in base alla logica seguente.
23
English
Il possibile utilizzo delle impostazioni virtuali determinato dal parametro maschera I.450.
I parametri maschera devono essere gestiti in base ai bit. Ad ogni bit corrisponde
uno switch in base alla logica seguente.
Maschera Bit i
Sorgente An Out
Funzione Drive
Controllo virtuale
Fare anche riferimento al paragrafo 7.4, Menu I Interface, sezione Abilitazione I/O
virtuali del manuale distruzioni del drive.
Per ulteriori informazioni riguardo la configurazione degli I/O digitali virtuali, fare
riferimento al paragrafo 7.9 HIDDEN, sezione Comandi I/O virtuali del manuale
distruzioni del drive:
English
Italiano
24
Esempio:
Comandi Run e Reverse dal Bus (parte PDC).
Comando Ext fault dallIngresso digitale 5 del morsetto.
Italiano
English
25
English
Italiano
26
Prg
DISPLAY
d000
--------------
Prg
STARTUP
S000
--------------
Prg
INTERFACE
I000
--------------
Prg
Prg
Prg
PARAMETER P000
--------------
Prg
APPLICATION A000
--------------
COMMAND
C000
--------------
Allaccensione del drive il display del tastierino mostra il parametro Output frequency (d.000) del men DISPLAY.
Italiano
Prg
Entrare nel men d.000 (Display); tale men viene utilizzato per visualizzare
diverse informazioni relative alla scheda SBI (parametri d.350 ... d.354); tutti gli
elementi relativi ai dati sono di sola lettura.
Per muoversi tra i vari elementi del men utilizzare i tasti o .
Cod.
d.350
d.351
d.352
Display LCD
[Cod.] & Selez. LCD
Option 1 state
Option 2 state
Par port state
SBI-PDP-ADV80 Manuale istruzione
IPA
038
039
040
27
English
d.353
SBI State
d.354
SBI Baude rate
0
1
2
3
0
1
2
3
4
5
6
7
8
15
Wait parametrization
059
Wait configuration
Data exchange
Error
12 Mbit / s
060
6 Mbit / s
3 Mbit / s
1.5 Mbit / s
500 Mbit / s
187.5 kbit / s
93.75 kbit / s
45.45 kbit / s
19.2 kbit / s
unknowk
Italiano
configurazione opzionale.
I.750:
I.752:
C.000:
English
Cod.
I.700
I.701
28
Nome
Default
MIN
MAX
IPA
Option 1 type
0
0
4
161
[0] Board Off
[1] Board master
[2] IO Board
[3] Board free
[4] SBI Board
Option 2 type
0
0
4
162
[0] Board Off
[1] Board master
[2] IO Board
[3] Board free
[4] SBI Board
I.750
I.752
C.000
I.760
I.761
I.762
I.763
I.764
I.765
I.770
I.771
I.772
I.773
I.774
I.775
SBI address
3
0
255
163
SBI Profibus mod
2
0
4
165
[0] Custom
[1] PPO1
[2] PPO2
[3] PPO3
[4] PPO4
Bus Flt Holdoff
0.0
0.1
60
179
SBI to Drv W 0
0
0
1999
167
SBI to Drv W 1
0
0
1999
168
SBI to Drv W 2
0
0
1999
169
SBI to Drv W 3
0
0
1999
170
SBI to Drv W 4
0
0
1999
171
SBI to Drv W 5
0
0
1999
172
Drv to SBI W 0
1
0
1999
173
Drv to SBI W 1
2
0
1999
174
Drv to SBI W 2
3
0
1999
175
Drv to SBI W 3
4
0
1999
176
Drv to SBI W 4
5
0
1999
177
Drv to SBI W 5
6
0
1999
178
Al
Rev
Op
Fwd
Limit
Alarm
0U
Prg
Display a 7 segmenti
Il tastierino del drive indica sul display a 7 segmenti un messaggio lampeggiante
con il codice dellallarme intervenuto.
Riconoscimento allarme
Italiano
Enter
Per ulteriori informazioni vedere il Capitolo 9, Ricerca Guasti, del manuale distruzioni del drive.
29
English
Lallarme attivo pu essere riconosciuto premendo il tasto Prg sul tastierino. Questa operazione permette di navigare allinterno del men e di editare il parametro
mentre il drive in condizione dallarme (i LED rossi lampeggiano). Per far riprendere lattivit del drive necessario utilizzare il comando di reset dellAllarme.
Nota:
07FD
Byte 1
Byte 2
Module=Custom defined
0xF3
0xF5
Module=PPO Typ 1
0xF3
0xF1
Module=PPO Typ 2
0xF3
0xF5
Module=PPO Typ 3
0xF1
Module=PPO Typ 4
0xF5
Italiano
Per il significato di questi byte fare riferimento al paragrafo 8.3.5 del manuale
Draft Standard PROFIBUS -DP DIN 19245 Parte 3.
English
Il file GSD adatto per la configurazione della rete Profibus-DP disponibile per il
download sul sito web www.gefran.com, sezione download di ADV80.
30
Capitolo 10 - Altro
10.1 Glossario
Master
Slave
Process Channel Canale per un trasferimento dati veloce, ciclico e ad alta priorit di parametri configurati precedentemente.
Configuration Channel
10.2 Abbreviazioni
PDC
DP
Decentralized Peripherals.
PDU
PPO
PCV
CTW
STV
SP
AF
10.3. Riferimenti
1 - Draft Standard PROFIBUS-DP DIN 19245 Parte 3.
English
Italiano
31
Chapter 1 - Introduction
This manual describes the SBI-PDP-ADV80 optional cards for connecting of
inverters to Profibus-DP networks:
This manual is intended for design engineeres and technicians responsible for
the maintenance, commissioning and operation of Profibus-DP systems. A basic
knowledge of Profibus-DP is assumed and may be found in the Draft Standard
DIN 19245 Part 3 manual.
1.1 About this manual
Chapter 2 Mechanical Card mounting and electrical connections.
Chapter 3 Master - Slave transmission data
Chapter 4 This section describes how to control drive via control word/status
word and how to access drive parameters.
Chapter 5 Profibus-DP diagnostic handling
Chapter 6 Assignment of the drive parameter to the virtual digital I/O
Chapter 7 This section describes how to operate without Profidrive Profile.
Chapter 8 Keypad drive menu
Chapter 9 Identification number and codes for Bus connection
Chapter 10 Miscellaneous: glossary, abbreviations and references
1.2 Overview of Profibus-DP
Profibus-DP is a field Bus designed for a fast data exchange relating to sensors /
actuators level; the communication is established between a Master central unit
(PLC or PC) and Slave units, i.e. sensors, actuators, drives, etc.
The data exchange is cyclic; the Master unit reads the Slaves input data and
writes the Slaves output data. The Bus cycle time is shorter than the cycle time of
the central unit; the Baud Rates for the SBI cards are from 9.6 kbit/s to 12 Mbit/s
according to Profibus-DP standard part. 3.
Italiano
The total cycle time depends on the number of Slaves connected; the 1.5-Mbit/s
Baud Rate allows 8 Gefran drives to be polled in 6 milliseconds.
The physical support is the RS485 serial line; the max. number of Slaves connected to the Bus is 125.
Example of Mono-Master Profibus-DP system.
MASTER
English
SLAVE
SLAVE
SLAVE
32
34.75 mm
(1.38 in)
2.2 Mounting
The SBI card has to be fastened to a 35 mm DIN rail by using the spring on the
back side; it is recommended to keep the SBI-PDP-ADV80 card as close as possible to the drive.
Do not put the SBI-Drive link cable near power cables.
33
English
Italiano
25 mm
EXP-SEL
Dip-switch selecting the option address
DEA, AL, PWR
Signaling LEDs
PDP-ADD
2-digit display showing the Profibus address of the drive
XS
connector for the Bus connection
PE
grounding connectors; they must be both connected to increase the noise
immunity.
XOPT
parallel connectors for the connection to the drive and to another possible device.
1.
2.
The SBI-Drive link cable (cod. S7QAE0 - 8 poles Shielded cable, L=400
mm, standard) must be connected between XOPT on drive Regulation
card and one of two XOPT connectors on SBI-PDP-ADV80 card.
3.
4.
5.
6.
The LED DEA lights up when the communication enters in the Data Exchange Phase.
7.
The display shows the address of the Profibus node; it is set via the I.750
- SBI Address parameter.
Italiano
The power supply is provided by the XOPT connector which is also used to transfer data between the SBI card and the drive regulation card.
English
2.4 LEDs
PWR (Green)
AL (Red)
Alarm active.
DEA (Yellow)
34
ON
OFF
1
2
ON
These temperatures are adequate to those of the drive, to which the cards are
connected.
2.7 Interface
For the connection to the Bus please use a shielded twisted cable recommended
by Profibus specification.
The pinout of the Bus (XS) connectors are the following:
5
9
6
1
PIN
REFERENCE
Shield
Not connected
MEANING
Shield / grounding
RX / TX - B
Not connected
0V - GND
+5V
Not connected
RX / TX - A
Not connected
P datum reception/transmission
P datum reception/transmission
The terminating resistances of the first and last network components must be
active. Pins 5 (GND) and 6 (+5V) provide the connection of the terminating resistances.
Italiano
XS
English
35
The Bus connection is provided via a shielded twisted cable which should be
placed as far as possible from the power cables, with a minimum distance of 20
cm. The cable shielding must be connected to ground at both ends of the cable.
It is recommended that straight metal connectors be used and that the cable
shielding is connected to the connector housing or to pin 1 (shield / protective
ground). If the cable shielding from a number of drives is connected to ground at
different points of the system, use equipotential connection cables to reduce the
current flow between the drives and the Profibus DP master. The following figure
shows a connection between the single cards.
SBI-PDP-ADV80
SBI-PDP-ADV80
XS1
XS1
XS1
English
Italiano
SBI-PDP-ADV80
36
Sub
Offset
10
11
12
13
14
15
16
17
18
10
19
11
20
12
Custom
PPO-1
PPO-2
PPO-3
PPO-4
PCV
PCV
PCV
Nu
Nu
PDC-W0
CTW/STW
CTW/STW
CTW/STW
CTW/STW
PDC-W1
SP/AF
SP/AF
SP/AF
SP/AF
PDC-W2
Nu
PDC-W0
Nu
PDC-W0
PDC-W3
Nu
PDC-W1
Nu
PDC-W1
PDC-W4
Nu
PDC-W2
Nu
PDC-W2
PDC-W5
Nu
PDC-W3
Nu
PDC-W3
Italiano
Nu
Not Used
CTW
STW
SP
AF
PDC-W0..W5
37
English
3-4
PCA LOW
PCA HIGH
PCA
WL-BL
WL-BH
WH-BL
WH-BH
SIND
PCA
PVA
16 bits
PCA (16 bits)
15
14
13
12
11
RC
10
TB
Index
RC
Request
0
No request
Parameter reading
3..15
Not Used
Italiano
Response
0
No response
Parameter reading
Parameter writing
Not Used
Not Used
Not Used
Not Used
Refused request
8..15
Not Used
TB
Index
English
The data read from Profibus-DP by the Slave are referred to as input data; the
data written in Profibus-DP by the Slave are referred to as output data.
The Slave parameters are cyclically read by the Master by assignign drive parameters to the PDC output configuration parameters.
The Master cyclically transmits drive parameters to the Slave by assigning drive
parameters to the PDC input configuration parameters.
The drive parameters assignment to the Process Data Channel Word is carried
38
out by means of the index of the parameter itself (I.760 and following).
Only drive parameters with a 16-Bit width (1 Word) may be assigned to the Process Data Channel.
The I.760 ... I.775 parameters with an index equal to 0000 show that the word has
not been assigned to any parameter of the drive.
As for the configuration of the Process Data Channel (PDC) see the drive instruction manual (paragraph 7.4, Menu I - INTERFACE, parameters I.760 and following).
Note!
A number of different Words has to be configured according to the selected configuration; examples:
English
The use of Frequency Setpoint can be enabled by selecting the parameter F.050
Ref 1 channel = [8] Profidrive.
Italiano
Length 2 bytes
39
Italiano
Word
PDC
PCA
IND
PVA
CTW MRV
STW MAV
PDC
1
PDC
2
PDC
3
PDC
4
10
10
PPO1
Word
PPO2
English
Word
PPO3
Word
PPO4
40
PDC
5
PDC
6
PDC
7
PDC
8
4.2 PDC-part
In this chapter the process data part (PDC) of a PPO is discussed.
The PDC part consist of a fixed part (all PPOs) and a parametrable part (only
PPO 2 & 4).
In the fixed part, control word and speed reference are transferred to the drive
while status word and actual output frequency are transferred from the drive.
In the parametrable part, PDC word 1-4, the user can configure what parameters
that should be transferred to/from the drive every bus-cycle.
4.2.1 Control / Status word
This section describes how to operate the drive with the control / status word.
Profidrive Control Word
The control word is used to send control commands to the inverter
Bit # of control
word
Bit = 0
Bit =1
ON1
ON2
ON3
Operation disabled
Operation disabled
Setpoint disabled
Setpoint enabled
No function
Fault acknowledge
Not used
Not used
Not used
Not used
10
Data valid
11
No function
Reversing
12-15
Not used
Not used
Italiano
(PLC -> Drive). P.000 - Cmd source sel = [4] Control word.
Bit 0, OFF1/ON1:
Bit = 0 :
Bit = 1 :
Bit = 0 :
Bit = 1 :
Bit 2, OFF3/ON3:
Bit = 0 : fast stop that uses deceleration time specified in F.206. When output
frequency = 0 the drive output is disabled.
41
English
Bit 1, OFF2/ON2:
Bit = 1 : drive can be started if all other start conditions are fulfilled.
Bit 3, Operation disabled / enabled:
Bit = 0 :
Bit = 1 :
Bit = 1 :
Bit =1 :
Bit =1 :
Bit =1 :
the control word and frequency setpoint (from Profibus) are not activated.
Bit =1 :
the control word and frequency setpoint (from Profibus) are activated.
Bit = 0 :
Bit =1 :
drive is reversing.
English
Italiano
42
Bit = 0
Bit =1
Ready to switch-on
Operation inhibited
Operation enabled
No fault
Operation disabled
OFF2
ON2
OFF3
ON3
Trip
No alarm
Alarm
Frequency equal to
setpoint
setpoint
Local control
Bus control
10
11-15
Not used
Not used
control word bit 0,1 or 2 (OFF1, OFF2, OFF3) is set to 0, or the drive
has tripped.
Bit =1 :
Bit = 0 :
control word bit 0,1 or 2 (OFF1, OFF2, OFF3) is set to 0, or the drive
has tripped.
Bit =1 :
control word bit 0,1 and 2 are set to 1, and the drive has not tripped.
Bit =1 :
control word bit 0,1,2 and 3 are set to 1, and the drive has not tripped.
Italiano
Bit =1 :
English
Bit = 0 :
Bit = 0 :
Bit =1 :
43
Bit =1 :
Bit =1 :
control word bit 1 or 2 (OFF2, OFF3) is set to 0 or fault trip has been
acknowledged.
actual output frequency does not equal frequency setpoint (i.e. motor
is accelerating / decelerating).
Bit =1 :
Bit =1 :
P.000 - Cmd source sel = [4] Control word and F.050 - Ref 1 channel
= [8] Profidrive.
Bit = 0 :
Bit =1 :
English
Italiano
44
45
Bit 2
Coast stop
Bit 6=1
Bit 0=1
Ready
Bit 1=1
ON1 (bit 0 = 1)
Ready to
switch-on
Fault
Stop drive
Bit 3=1
OFF2 (bit 1 = 0)
Fault acknowledge
(bit 7: 0 to 1)
OFF3 (bit 2 = 0)
OFF1 (bit 0 = 0)
Switch-on
inhibit
English
Italiano
Enable operation
OFF3 active
Quick stop
Coast stop
OFF2 active
stage 1
(bit 3 = 1)
Bit 5=0
Bit 4=0
RFG output
Enable
Drive stopped
disabled
Bit 2=1
operation
(bit 4 = 0)
A
RFG output enabled Open load
OFF3 active
From every state
C
D
stage 2
contactor
(bit 4 = 1)
OFF1 (bit 0 = 0)
Ramp function
Stop RFG
generator
Load
Load
(bit 5 = 0)
Normal
OFF1 active
Enabled output
contactor
contactor
stop
stage 1
B
RFG acceleration enabled
open
open
D
(bit
5
=
1)
Drive stopped
Inhibit
Ramp function
Bit 1=0
setpoint
OFF1 active
generator
Open load
(bit 6 = 0)
stage
2
Accel. Enabled
contactor
Enable setpoint
C
(bit 6 = 1)
Load contactor open
Operation
D
state
Drive stopped
Inhibit
operationactive
Inhibit operation
(bit 3 = 0)
A B C D
Voltage ON
Voltage
switched-off
3-4
PCA LOW
PCA HIGH
PCA
WL-BL
WL-BH
WH-BL
WH-BH
SIND
PVA
14
13
RC
12
11
10
TB
Index
English
Italiano
PCA handling:
RC
TB
Index
SIND
PVA
2 Word
46
High Word
Low Byte
High Byte
Low Byte
High Byte
Byte 4 di PCV
Byte 5 di PCV
Byte 6 di PCV
Byte 7 di PCV
Functione
No request
10-15
Not used
No response
9-15
Not used
If the drive rejects a request from the master, the RC word in the PPO-read will
indicate this by assuming value 7.
The describing fault number (see below) will be found in the PVA part.
Interpretation
Erroneous sub-index
No array
11
English
Fault number
Italiano
Response Function
47
17
101
102
103
104
105
106
Italiano
identify the Change parameter value function equal to 2 and the IPA
138 hex (312 dec)
00 00
not used
02 00
00 00
06 4F
control word
00 40
00 00
not used
02 00
00 00
37 03
word status
00 40
actual speed
English
38 11
48
English
Italiano
The communication between Master and Slave can only be carried out if the initialization of the drive and of the SBI card is successfully terminated; if not, it is not
possible to determine the cause of the erroneous initialization using the Bus.
49
DI i source
DO i source
Terminal
Drive function
Virtual
Virtual control
Italiano
See also paragraph 7.4, Menu I Interface, Enabling Virtual I/O section of the
drive instruction manual.
For more info on virtual digital I/O configuration, please refer to the paragraph 7.9
HIDDEN, Virtual I/O Commands section of the drive instruction manual:
- for virtual digital inputs, writing the H.000 and H.001 parameters,
English
50
An Out source
Drive function
Virtual control
See also paragraph 7.4, Menu I Interface, Enabling Virtual I/O section of the
drive instruction manual.
For more info on virtual digital I/O configuration, please refer to the paragraph 7.9
HIDDEN, Virtual I/O Commands section of the drive instruction manual:
English
Italiano
51
Example:
Run and Reverse commands from Bus (PDC part).
Ext fault command from terminal Digital input 5.
Frequency reference from Bus.
Italiano
English
52
English
Italiano
53
Prg
DISPLAY
d000
--------------
Prg
STARTUP
S000
--------------
Prg
INTERFACE
I000
--------------
Prg
Prg
Prg
PARAMETER P000
--------------
Prg
APPLICATION A000
--------------
Italiano
Prg
COMMAND
C000
--------------
At the drive power up the keypad display will show d.000 Output frequency
parameter of DISPLAY menu.
English
Enter the d.000 Display menu, it is used to display various information about the
SBI card (d.350 ... d.354 parameters); all data items are strictly read-only.
Move between the Menu items by pressing the or keys.
Cod.
d.350
d.351
d.352
d.353
54
LCD display
[Code] & LCD select.
Option 1 state
Option 2 state
Par port state
SBI State
0 Wait parametrization
SBI-PDP-ADV80 Instruction manual
IPA
038
039
040
059
d.354
SBI Baude rate
1
2
3
0
1
2
3
4
5
6
7
8
15
Wait configuration
Data exchange
Error
12 Mbit / s
060
6 Mbit / s
3 Mbit / s
1.5 Mbit / s
500 Mbit / s
187.5 kbit / s
93.75 kbit / s
45.45 kbit / s
19.2 kbit / s
unknowk
option configuration.
I.750
I.752
I.754
This parameter allows the setting of a delay for the intervention of the BUS FAULT alarm.
In each word the parameters reading or writing, has to be addressed setting the
relative number of IPA.
Name
Default
MIN
MAX
IPA
Option 1 type
0
0
4
161
[0] Board Off
[1] Board master
[2] IO Board
[3] Board free
[4] SBI Board
Option 2 type
0
0
4
162
[0] Board Off
[1] Board master
[2] IO Board
[3] Board free
[4] SBI Board
SBI address
3
0
255
163
SBI Profibus mod
2
0
4
165
[0] Custom
[1] PPO1
SBI-PDP-ADV80 Instruction manual
English
Cod.
I.700
I.701
I.750
I.752
Italiano
55
C.000
I.760
I.761
I.762
I.763
I.764
I.765
I.770
I.771
I.772
I.773
I.774
I.775
[2] PPO2
[3] PPO3
[4] PPO4
Bus Flt Holdoff
0.0
0.1
60
179
SBI to Drv W 0
0
0
1999
167
SBI to Drv W 1
0
0
1999
168
SBI to Drv W 2
0
0
1999
169
SBI to Drv W 3
0
0
1999
170
SBI to Drv W 4
0
0
1999
171
SBI to Drv W 5
0
0
1999
172
Drv to SBI W 0
1
0
1999
173
Drv to SBI W 1
2
0
1999
174
Drv to SBI W 2
3
0
1999
175
Drv to SBI W 3
4
0
1999
176
Drv to SBI W 4
5
0
1999
177
Drv to SBI W 5
6
0
1999
178
Al
Rev
Op
Fwd
Limit
0U
Alarm
Prg
Enter
7 segments display
Italiano
The drive keypad will show on the 7th segment display a blinking message with
code of the alarm occurred.
Alarm acknowledge
The active alarm can be acknowledged by pressing the Prg button on the keypad.
This operation will allow menu navigation and parameter editing while the drive is
in alarm state (red LEDs blinking). In order to resume drive operation, an Alarm
reset command is necessary.
English
For more info see Chapter 9, Troubleshooting of the drive instruction manual.
56
Note:
07FD
Byte 1
Byte 2
Module=Custom defined
0xF3
0xF5
Module=PPO Typ 1
0xF3
0xF1
Module=PPO Typ 2
0xF3
0xF5
Module=PPO Typ 3
0xF1
Module=PPO Typ 4
0xF5
English
The GSD file suitable for the Profibus-DP network configure is available on web
site www.gefran.com, download section on ADV80.
Italiano
For the meaning of these bytes please refer to the paragraph 8.3.5 of the Draft
Standard PROFIBUS -DP DIN 19245 Part 3 manual.
57
Chapter 10 - Miscellaneous
10.1 Glossary
Master
Slave
Process Channel Channel for the fast, cyclic and high-priority data transfer of
parameters previously configured.
Configuration Channel
10.2 Abbreviations
PDC
DP
Decentralized Peripherals.
PDU
PPO
PCV
CTW
STV
SP
AF
10.3. References
1 - Draft Standard PROFIBUS-DP DIN 19245 Part 3.
Italiano
English
58
Gefran worldwide
GEFRAN FRANCE
4, rue Jean Desparmet - BP
8237
69355 LYON Cedex 08
Ph. +33 (0) 478770300
Fax +33 (0) 478770320
commercial@gefran.fr
GEFRAN DEUTSCHLAND
Philipp-Reis-Strae 9a
63500 SELIGENSTADT
Ph. +49 (0) 61828090
Fax +49 (0) 6182809222
vertrieb@gefran.de
SIEI AREG - GERMANY
Gottlieb-Daimler-Strasse 17/3
D-74385 Pleidelsheim
Ph. +49 7144 89 736 0
Fax +49 7144 89 736 97
info@sieiareg.de
GEFRAN S.p.A.
Via Sebina 74
25050 Provaglio dIseo (BS)
ITALY
Ph. +39 030 98881
Fax +39 030 9839063
info@gefran.com
www.gefran.com
GEFRAN SUISSE SA
Rue Fritz Courvoisier 40
2302 La Chaux-de-Fonds
Ph. +41 (0) 329684955
Fax +41 (0) 329683574
office@gefran.ch
GEFRAN - UK Ltd.
7 Pearson Road, Central Park
TELFORD, TF2 9TX
Ph. +44 (0) 845 2604555
Fax +44 (0) 845 2604556
sales@gefran.co.uk
Technical Assistance :
technohelp@gefran.com
Customer Service :
motioncustomer@gefran.com
Ph. +39 02 96760500
Fax +39 02 96760278
1S5F31
GEFRAN BRASIL
ELETROELETRNICA
Avenida Dr. Altino Arantes,
377/379 Vila Clementino
04042-032 SO PAULO - SP
Ph. +55 (0) 1155851133
Fax +55 (0) 1132974012
gefran@gefran.com.br
GEFRAN Inc.
8 Lowell Avenue
WINCHESTER - MA 01890
Toll Free 1-888-888-4474
Ph. +1 (781) 7295249
Fax +1 (781) 7291468
info@gefraninc.com
0.0 - 28-10-2011
Gefran Espaa
Josep Pla, 163 2-6
08020 BARCELONA
Ph. +34 934982643
Fax +34 932662713
comercial.espana@gefran.es
GEFRAN BENELUX
Lammerdries-Zuid, 14A
B-2250 OLEN
Ph. +32 (0) 14248181
Fax. +32 (0) 14248180
info@gefran.be