Type YCGF 11
Field Failure Relay
YCGF relay
withdrawn from case
Features
l
Application
Loss of field supply to a synchronous
generator can be caused by a fault
in the excitation circuits or by
incorrect opening of the field circuit
breaker. On loss of field, the
machine operates as an induction
generator excited by reactive power
drawn from the system to which it is
connected. This could result in
instability of power in the system
and overheating of the rotor,
especially if the machine is of the
cylindrical rotor type without
damping windings in the
pole faces.
Description
The relay is basically a low inertia,
high speed, four pole induction cup
unit of simple construction having
operating, polarising and restraining
coils.
The relay has circular mho
characteristic with its centre on the
X axis of the RX diagram and is
offset from the origin. This offset is
adjustable so that undesirable
operation of the relay on power
swings or loss of synchronism not
accompanied by loss of field, is
avoided.
The diameter of the circle is also
adjustable to ensure positive
operation during field failure.
Adjustment of circle diameter is
independent of the offset.
Technical data
Ratings
l
Current:
1A or 5A at 50 Hz
Voltage:
110V at 50 Hz
Settings
Circle diameter:
25 to 250 ohms - 1A rating.
5 to 50 ohms - 5A rating.
(adjustable in 5% steps)
Offset
Figure 2:
External connection
diagram for
YCGF 11 relay
Current circuit:
1.7 - 2.8VA per phase
The burden depends on the
relevant ohmic setting and the
magnitude and phase angle of
the load current.
Voltage circuit:
5.0 - 7.7VA
Accuracy
l
Frequency error:
5% over the range 47 to 52 Hz
Temperature error:
10% over the range 20C to
+50C
Contact ratings
A light duty normally open three
point contact is fitted to the induction
cup unit and is rated to make, break
and carry for 30 s, 10W inductive or
20W resistive with maxima of 250V
and 5A dc.
Insulation
The relay meets the requirements of
IS 3231/IEC 255-5 series `C - 2 kV
for 1 minute.
CT requirements
Details furnished on request.
Case
1D, vertical case suitable for flush
mounting and finished twintone and
tropicalised. Suitable trip isolating
switch and CT shorting switches are
provided on the cradle assembly/
case.
ALSTOM Limited Pallavaram Works: 19/1, GST Road, Pallavaram, Chennai-600 043. India.
Tel: 91-044-2368621 Fax: 91-044-2367276 Email: plw.applications@alstom.sprintrpg.eml.vsnl.net.in.
1998 ALSTOM Limited
Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should
only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it.
ALSTOM Limited cannot be held responsible for any reliance on any decision taken on its contents without specific advice
PR:080:0799:A
Printed in India.