Vous êtes sur la page 1sur 12

COMPACT HCFB / HCFT

PLATE MOUNTED AXIAL FLOW FANS

COMPACT Series type HCFB / HCFT


(Plastic impellers)

Range of low profile plate mounted axial fans


fitted with plastic impellers (250 to 630) or aluminium hub and plastic blades (710 to 1000).
Available, depending upon the model, with single or three phase motors in 2, 4, 6 or 8 poles.
Motors
All the motors are IP65 (1), Class F insulation (2),
equipped with thermal protection.
All motors are speed controllable by autotransformer except 2 pole and /4-630, /4-710, 800,
900, 1000 models.

Plate mounted axial flow fans

Models 800 to 1000 are speed controllable by


inverter.
Electrical supplies:
Single phase 230V-50Hz. (Capacitor located
inside the wiring terminal box).
Three phase 230/400V-50Hz or 400V-50Hz.
(See characteristic chart).
(1) 2 pole motor and 800, 900 & 1000 models are IP55.
(2) Working temperatures from -40C up to 70C. Except models

800 to 1000 suitable for usage in environments from -20 C

to 40C.

Additional Information
Standard air direction: form (A) configuration

Compact design

Corrosion
resistance

Terminal
box

(Motor over Impeller).


On request
Air direction: form (B) configuration (Impeller
over Motor).
Inlet finger proof guard for models 800 to
1000.
A

Compact design created by the

Mounting plate, motor support

Wiring terminal box with cable

combination of the motor with

and finger proof guard protected

gland PG-11

the factory matched direct drive

by cataforesis primer and black

wrap around impeller hub

polyester paint finish. Stainless


steel screws

Impeller dynamically
balanced

Impellers are dynamically


balanced, according to
ISO 1940 standard, giving

Warehouses

Workshops

Commercial
premises

Car parks

Agricultural extract
or supply
applications

Greenhouses

Painting
Installations

Air conditioning
equipment

Configuration for
models 800 to 1000

vibration free operation

COMPACT Series type HCBB / HCBT


(Aluminium impellers)

Range of low profile plate mounted axial fans


fitted with aluminium impellers.
Available, depending upon the model, with single or three phase motors in 2, 4, 6 or 8 poles.
Motors
All the motors are IP65(1), Class F insulation(2),
equipped with thermal protection. All motors are
speed controllable except 2/315/H, 2/355/H

COMPACT HCBB / HCBT

PLATE MOUNTED AXIAL FLOW FANS

and B/4-630, B/6-710, B/8-710 models (see


characteristics chart).
Electrical supplies:

Three phase 230/400V-50Hz or 400V-50Hz


(See characteristic chart).
(1) 2/315/H,2/355/H and 800, 900 & 1000 models are IP55.
(2) Working temperatures from -40C up to 70C (except
/2-315/H,/2-355/H, 800, 900 and 1000 models: suitable

for usage in environments -20C to 40 C ).

Additional Information
Standard air direction: form (A) configuration
(Motor over Impeller).
On request
Air direction: form (B) configuration (Impeller

Compact design

Corrosion
resistance

Terminal
box

over Motor).
Three phase motors suitable for inverter control
(E22 version).
Inlet finger proof guard for models 800 to 1000.
Explosion proof versions in accordance to
ATEX Directive for three phase models:
Ex II2G EExe IIT3
- Increased safety
(except 250 models).
- Flame proof only for models 800 to 1000,
Ex II2G EExd IIBT5 or EExd IICT4.

Working temperatures from -20C to 55C

Compact design created by the

Mounting plate, motor support

Wiring terminal box with cable

combination of the motor with

and finger proof guard protected

gland PG-11

the factory matched direct drive

by cataforesis primer and black

wrap around impeller hub

polyester paint finish. Stainless

steel screws

Impeller dynamically
balanced

Configuration for
models 800 to 1000

Warehouses

Workshops

Commercial
premises

Car parks

Agricultural extract
or supply
applications

Greenhouses

Painting
Installations

Air conditioning
equipment

Impellers are dynamically


balanced, according to
ISO 1940 standard, giving
vibration free operation

Plate mounted axial flow fans

Single phase 230V-50Hz. (Capacitor located


inside the wiring terminal box).

Reference
H C F T

COMPACT

1 - H: Compact Plate Axial Fan

5 -

2 - C: Series designation

3 -

Impeller Type:

F: 250- 630 Fixed blade plastic


impeller


Plate mounted axial flow fans

710 - 1000 Aluminium impeller


hub and adjustable plastic blade impellers

G: Adjustable plastic blade impellers

B: 250- 400 Fixed blade aluminium


impeller

L: Weatherproof Protected

2: (approx. 2900 r.p.m. - 50 Hz)

C: Condensation drain holes on motor

EX: Explosion proof versions in accordance


to ATEX Directive, for three phase
models:

Number of poles:

4: (approx. 1400 r.p.m. - 50 Hz)

6: (approx. 900 r.p.m. - 50 Hz)

8: (approx. 700 r.p.m. - 50 Hz)

6 - : Nominal Diameter of impeller. (mm)


7 - : Pitch Angle

H: high

L: low
Direction of Air:

450 - 1000 Adjustable blade aluminium impeller

8 -

A: Motor over Impeller

4 -

Electrical supply:

B: Impeller over Motor

B: Single phase

T: Three phase

9 -

-EXE: Increased safety

-EXD: Flame proof, only for models 800


and 1000 II2G EExdIIBT5 or
EExdIICT4

II2G EExeIIT3

G: Special corrosion treatment for


agricultural applications

TF: With anticorrosive Teflon paint finish

Special Construction

X: Motor support without inlet finger guard

Supply Voltages and Frequencies


Mains supply
voltage

Motor type

Connection

Speed

SINGLE PHASE
220V 50Hz, 240V 50Hz

230V 50Hz

See wiring
diagram

High

THREE PHASE
220V 50Hz
240V 50Hz

230/400V 50Hz

High
Low*

230/400V 50Hz

THREE PHASE
380V 50Hz
415V 50Hz

High
High

400V 50Hz

Low*

* From sizes 450 up to 630 mm diameter.

Acoustic characteristics
The sound levels shown in the technical characteristic chart, correspond to the value of sound pressure dB(A), measured in free field
conditions at a distance equivalent to three times the diameter of the impeller with a minimum of 1.5 meters.
Sound power level spectrum in dB(A) at the corresponding frequency band in Hz.
LwA ASP QMAX
2-250
2-315
2-355

63
50
51
58

125
61
62
63

250
68
82
87

500
73
77
83

1000
74
85
89

2000
74
85
92

4000 8000
67
58
79
71
86
79

LwA ASP QMAX


4-250
4-315
4-355
4-400
4-450
4-500
4-560
4-630
4-710
4-800/L
4-800/H
4-900/L
4-900/H
4-1000/L
4-1000/H

63
44
37
39
41
40
50
47
52
56
61
64
66
70
68
71

125
50
47
59
62
65
68
72
75
78
83
86
88
92
90
93

250
57
57
56
58
62
67
70
73
76
81
84
86
90
88
91

500
58
61
65
67
68
73
82
81
84
89
92
95
97
96
99

1000
60
66
70
74
77
79
82
86
89
95
98
100
104
102
105

2000
59
63
66
70
71
77
79
83
86
91
94
96
100
98
101

4000 8000
53
42
57
48
61
52
66
43
67
58
72
61
74
65
77
68
81
71
86
77
89
80
91
82
95
87
93
84
96
87

LwA ASP QMAX


6-315
6-355
6-400
6-450
6-500
6-560
6-630
6-710
6-800/L
6-800/H
6-900/L
6-900/H
6-1000/L
6-1000/H

63
27
39
34
35
39
41
43
51
56
58
61
65
63
66

125
37
45
46
50
52
55
59
65
70
72
75
79
77
80

250
45
46
49
52
55
60
62
68
73
75
79
83
80
83

500
51
52
59
61
63
67
70
77
82
84
87
91
89
92

1000
52
53
60
64
67
71
71
80
85
87
90
94
92
95

2000
53
54
60
62
65
70
69
79
84
86
89
93
91
94

4000 8000
47
36
48
37
53
41
56
45
59
49
64
53
67
56
73
62
78
67
80
69
83
72
87
76
85
74
88
77

LwA ASP QMAX


8-450
8-500
8-560
8-630
8-710
8-800/L
8-800/H
8-900/L
8-900/H
8-1000/L
8-1000/H

63
42
42
46
45
57
61
63
67
71
68
72

125
42
42
46
48
57
61
63
67
71
68
72

250
47
51
55
57
64
69
71
75
79
76
80

500
55
56
60
63
71
75
77
81
85
82
86

1000
57
59
62
63
73
77
79
83
87
84
88

2000
58
59
62
64
73
77
79
83
87
84
88

4000 8000
49
39
52
42
55
45
58
46
65
55
70
60
72
62
76
76
80
70
77
67
81
71

Technical characteristics with PLASTIC impellers (HCGB, HCFB, HCGT & HCFT)
Model

Speed

(r.p.m.)

Maximum
absorbed
power
(W)

HCFB/2-250/H
HCGB/2-315/L
HCGB/2-355/J

2500
2500
2000

250
380
460

HCFB/4-250/H
HCFB/4-315/H
HCFB/4-355/H
HCFB/4-400/H
HCFB/4-450/H
HCFB/4-500/H
HCFB/4-560/H
HCFB/4-630/H

1330
1300
1225
1200
1290
1290
1250
1200

60
100
200
340
480
650
980
1700

HCFB/6-315/H
HCFB/6-355/H
HCFB/6-400/H
HCFB/6-450/H
HCFB/6-500/H
HCFB/6-560/H
HCFB/6-630/H
HCFB/6-710/H

825
800
750
835
840
900
800
900

80
90
110
220
290
420
510
1300

HCFB/8-450/H
HCFB/8-500/H
HCFB/8-560/H
HCFB/8-630/H
HCFB/8-710/H

625
605
610
585
625

130
160
240
320
480

HCFT/2-250/H
HCGT/2-315/G
HCGT/2-355/I

2500
2650
2380

250
410
520

HCFT/4-250/H
HCFT/4-315/H
HCFT/4-355/H
HCFT/4-400/H
HCFT/4-450/H
HCFT/4-500/H
HCFT/4-560/H
HCFT/4-630/H
HCFT/4-710/H
HCFT/4-800/L-X (1,5 kW)
HCFT/4-800/H-X (3 kW)
HCFT/4-900/L-X (3 kW)
HCFT/4-900/H-X (5,5 kW)
HCFT/4-1000/L-X (4 kW)
HCFT/4-1000/H-X (5,5 kW)

1330
1300
1260
1350
1230
1350
1320
1420
1350
1420
1430
1400
1400
1400
1460

60
150
200
300
500
660
1210
1550
2200
2300
4200
4400
7200
4400
7200

Maximum current
(A)
at 230 V

at 400 V

Weight

(dB(A))

Maximum
air
volume
(m3/h)

65
70
71

2160
3260
4000

5
7
8

52
54
58
60
65
68
71
72

1215
2350
3490
5070
6760
9200
12480
17060

5
7
8
9
13
16
22
25

REB-1
REB-1
REB-2,5
REB-2,5
REB-2,5
REB-5
REB-5

45
50
52
53
56
59
60
66

1560
2210
3400
4550
5820
7870
10750
17570

7
8
9
13
16
22
25
27

REB-1
REB-1
REB-1
REB-2,5
REB-2,5
REB-2,5
REB-5

46
49
52
53
59

3500
4660
5990
8340
11960

13
16
22
25
27

REB-1
REB-1
REB-2,5
REB-2,5

65
70
71

2160
3400
4400

5
7
8

52
54
58
60
65
68
71
72
75
79
82
83
87
84
87

1220
2350
3490
5070
6760
9200
12480
17060
22150
24960
32600
35000
45000
42000
54000

5
7
8
9
13
16
22
25
27
37
52
94
110
67
95

RMT-1,5
RMT-1,5
RMT-1,5
RMT-1,5
RMT-1,5
RMT-2,5
RMT-2,5
VFKB-45
VFKB-45
VFKB-45
VFKB-48
VFKB-48
VFTM-TRI 5,5
VFKB-48
VFTM-TRI 5,5

Sound
pressure
level

Speed*
controller

(kg)

SINGLE PHASE 2 POLES

1,2
1,7
2,2

COMPACT

Before making any electrical connection ensure that the voltage and frequency of the mains electrical supply matches that of the fan data plate label.

0,3
0,6
1,0
1,6
2,3
3,0
4,9
7,6
SINGLE PHASE 6 POLES

0,4
0,5
0,6
1,2
1,6
2,4
2,6
5,7
SINGLE PHASE 8 POLES

0,7
0,9
1,3
1,7
2,4
THREE PHASE 2 POLES

0,9
1,4
1,6

0,5
0,8
0,9

THREE PHASE 4 POLES

0,3
0,6
0,8
1,4
1,7
2,7
3,9
5,2
7,0
6,6
12,6
11,3
12,3

* Three phase speed controllers (RMT) or inverter control (VFKB/VFTM) are suitable for 400V.

0,2
0,3
0,5
0,8
1,0
1,6
2,3
3,0
4,0
3,8
7,3
6,5
12,0
7,1
12,0

Plate mounted axial flow fans

SINGLE PHASE 4 POLES

Technical characteristics with PLASTIC impellers

Plate mounted axial flow fans

COMPACT

Model

Speed

(r.p.m.)

Maximum
absorbed
power
(W)

Maximum current
(A)
at 230 V

at 400 V

Sound
pressure
level

Maximum
air
volume

Weight

(dB(A))

(m3/h)

(kg)

50
52
53
56
59
60
66
70
72
74
78
75
78

2210
3400
4550
5820
8260
11000
16500
19370
22000
23500
30000
28000
36400

8
9
13
16
22
25
27
31
36
86
93
54
62

RMT-1,5
RMT-1,5
RMT-1,5
RMT-1,5
RMT-1,5
RMT-1,5
VFKB-45
VFKB-45
VFKB-45
VFKB-45
VFKB-45
VFKB-45
VFKB-45

46
49
52
53
59
63
65
69
72
68
72

3500
4660
5990
8340
11960
14000
17160
17500
22500
20490
27040

13
16
22
25
27
63
64
90
90
68
71

RMT-1,5
RMT-1,5
RMT-1,5
RMT-1,5
VFKB-45
VFKB-45
VFKB-45
VFKB-45
VFKB-45
VFKB-45
VFKB-45

Speed*
controller

THREE PHASE 6 POLES

HCFT/6-355/H
HCFT/6-400/H
HCFT/6-450/H
HCFT/6-500/H
HCFT/6-560/H
HCFT/6-630/H
HCFT/6-710/H
HCFT/6-800/L-X (0,55 kW)
HCFT/6-800/H-X (0,75 kW)
HCFT/6-900/L-X (1,1 kW)
HCFT/6-900/H-X (1,5 kW)
HCFT/6-1000/L-X (1,1 kW)
HCFT/6-1000/H-X (1,5 kW)

875
830
835
840
900
905
920
900
940
950
950
940
950

90
110
190
250
410
530
1100
1180
1220
1400
2330
1400
2330

HCFT/8-450/H
HCFT/8-500/H
HCFT/8-560/H
HCFT/8-630/H
HCFT/8-710/H
HCFT/8-800/L-X (0,25 kW)
HCFT/8-800/H-X (0,37 kW)
HCFT/8-900/L-X (0,37 kW)
HCFT/8-900/H-X (0,75 kW)
HCFT/8-1000/L-X (0,37 kW)
HCFT/8-1000/H-X (0,75 kW)

660
625
610
635
670
710
690
700
700
700
725

130
150
230
310
450
580
700
720
1100
720
1100

0,5
0,5
0,8
0,9
1,6
2,2
4,9
3,9
4,3
5,7
7,0
5,6
7,6

0,3
0,3
0,5
0,5
0,9
1,26
3,3
2,2
2,5
3,3
4
3,2
4,4

THREE PHASE 8 POLES

0,7
0,7
1,0
1,3
2,0
2,2
3,0
2,8
4,5
3,0
4,6

* Three phase speed controllers (RMT) or inverter control (VFKB/VFTM) are suitable for 400V.

0,4
0,4
0,6
0,8
1,2
1,3
1,7
1,6
2,6
1,7
2,7

Technical characteristics with ALUMINIUM impellers (HCBB, HCBT)


Model

Speed

(r.p.m.)

Maximum
absorbed
power
(W)

HCBB/2-250/H
HCBB/2-315/H
HCBB/2-315/L
HCBB/2-355/H
HCBB/2-355/J

2500
2550
2500
2500
2000

250
730
380
1200
460

HCBB/4-250/H
HCBB/4-315/H
HCBB/4-355/H
HCBB/4-400/H
HCBB/4-450/H
HCBB/4-500/H
HCBB/4-560/H
HCBB/4-630/H

1330
1300
1225
1200
1290
1290
1250
1200

60
100
200
340
480
650
980
1700

HCBB/6-355/H
HCBB/6-400/H
HCBB/6-450/H
HCBB/6-500/H
HCBB/6-560/H
HCBB/6-630/H
HCBB/6-710/H

800
750
835
840
900
800
900

90
110
220
290
420
510
1300

HCBB/8-450/H
HCBB/8-500/H
HCBB/8-560/H
HCBB/8-630/H
HCBB/8-710/H

625
605
610
585
625

130
160
240
320
480

HCBT/2-250/H
HCBT/2-315/H
HCBT/2-315/G
HCBT/2-355/H
HCBT/2-355/I

2500
2750
2650
2700
2380

250
750
410
1200
520

HCBT/4-250/H
HCBT/4-315/H
HCBT/4-355/H
HCBT/4-400/H
HCBT/4-450/H
HCBT/4-500/H
HCBT/4-560/H
HCBT/4-630/H
HCBT/4-710/H
HCBT/4-800/L-X (1,5 kW)
HCBT/4-800/H-X (3 kW)
HCBT/4-900/L-X (3 kW)
HCBT/4-900/H-X (5,5 kW)
HCBT/4-1000/L-X (4 kW)
HCBT/4-1000/H-X (5,5 kW)

1330
1300
1260
1350
1230
1350
1320
1420
1350
1420
1430
1400
1400
1400
1460

60
150
200
300
500
660
1210
1550
2200
2300
4200
4400
7200
4400
7200

Maximum current
(A)
at 230 V

at 400 V

Sound
pressure
level

Maximum
air
volume

Weight

(dB(A))

(m3/h)

(kg)

65
75
70
81
71

2160
4800
3260
7000
4000

5
8
7
9
8

52
54
58
60
65
68
71
72

1215
2350
3490
5070
6760
9200
12480
17060

5
7
8
9
13
16
22
25

REB-1
REB-1
REB-2,5
REB-2,5
REB-2,5
REB-5
REB-10

50
52
53
56
59
60
66

2210
3400
4550
5820
7870
10750
17570

8
9
13
16
22
25
27

REB-1
REB-1
REB-2,5
REB-2,5
REB-2,5
REB-5

46
49
52
53
59

3500
4660
5990
8340
11960

13
16
22
25
27

REB-1
REB-1
REB-2,5
REB-2,5

65
75
70
81
71

2160
4800
3800
7000
4400

5
8
7
9
8

52
54
58
60
65
68
71
72
75
79
82
83
87
84
87

1220
2350
3490
5070
6760
9200
12480
17060
22150
24960
32600
35000
45000
42000
54000

5
7
8
9
13
16
22
25
27
37
52
96
112
67
95

RMT-1,5
RMT-1,5
RMT-1,5
RMT-1,5
RMT-1,5
RMT-2,5
RMT-2,5
VFKB-45
VFKB-45
VFKB-45
VFKB-48
VFKB-48
VFTM TRI-5,5
VFKB-48
VFTM TRI-5,5

Speed*
controller

SINGLE PHASE 2 POLES

1,2
3,5
1,7
5,0
2,2

COMPACT

Explosion proof types only work at an environmental temperature between -30C and +40C.

0,3
0,6
1,0
1,6
2,3
3,0
5,9
7,6
SINGLE PHASE 6 POLES

0,5
0,6
1,2
1,6
2,4
2,6
5,7
SINGLE PHASE 8 POLES

0,7
0,9
1,3
1,7
2,4
THREE PHASE 2 POLES

0,9
2,1
1,4
3,3
1,6

0,5
1,2
0,8
1,9
0,9

THREE PHASE 4 POLES

0,3
0,6
0,8
1,4
1,7
2,7
3,9
5,2
7,0
6,6
12,6
11,3
12,3

0,2
0,3
0,5
0,8
1,0
1,6
2,3
3,0
4,0
3,8
7,3
6,5
12,0
7,1
12,0

* Three phase speed controllers (RMT) or inverter control (VFKB/VFTM) are suitable for 400V.

Plate mounted axial flow fans

SINGLE PHASE 4 POLES

Technical characteristics with ALUMINIUM impellers

Plate mounted axial flow fans

COMPACT

Model

Speed

(r.p.m.)

Maximum
absorbed
power
(W)

Maximum current
(A)
at 230 V

at 400 V

Sound
pressure
level

Maximum
air
volume

Weight

(dB(A))

(m3/h)

(kg)

50
52
53
56
59
60
66
70
72
74
78
75
78

2210
3400
4550
5820
8260
11000
16500
19370
22000
23500
30000
28000
36400

8
9
13
16
22
25
27
31
36
88
95
54
62

RMT-1,5
RMT-1,5
RMT-1,5
RMT-1,5
RMT-1,5
RMT-1,5
VFKB-45
VFKB-45
VFKB-45
VFKB-45
VFKB-45
VFKB-45
VFKB-45

46
49
52
53
59
63
65
69
72
68
72

3500
4660
5990
8340
11960
14000
17160
17500
22500
20490
27040

13
16
22
25
27
63
64
85
92
68
71

RMT-1,5
RMT-1,5
RMT-1,5
RMT-1,5
VFKB-45
VFKB-45
VFKB-45
VFKB-45
VFKB-45
VFKB-45
VFKB-45

Speed*
controller

THREE PHASE 6 POLES

HCBT/6-355/H
HCBT/6-400/H
HCBT/6-450/H
HCBT/6-500/H
HCBT/6-560/H
HCBT/6-630/H
HCBT/6-710/H
HCBT/6-800/L-X (0,55 kW)
HCBT/6-800/H-X (0,75 kW)
HCBT/6-900/L-X (1,1 kW)
HCBT/6-900/H-X (1,5 kW)
HCBT/6-1000/L-X (1,1 kW)
HCBT/6-1000/H-X (1,5 kW)

875
830
835
840
900
905
920
900
940
950
950
940
950

90
110
190
250
410
530
1100
1180
1220
1400
2330
1400
2330

HCBT/8-450/H
HCBT/8-500/H
HCBT/8-560/H
HCBT/8-630/H
HCBT/8-710/H
HCBT/8-800/L-X (0,25 kW)
HCBT/8-800/H-X (0,37 kW)
HCBT/8-900/L-X (0,37 kW)
HCBT/8-900/H-X (0,75 kW)
HCBT/8-1000/L-X (0,37 kW)
HCBT/8-1000/H-X (0,75 kW)

660
625
610
635
670
710
690
750
750
700
725

130
150
230
310
450
580
700
720
1100
720
1100

0,5
0,5
0,8
0,9
1,6
2,20
4,9
3,9
4,3
5,7
7,0
5,6
7,6

0,3
0,3
0,5
0,5
0,9
0,53
3,3
2,2
2,5
3,3
4
3,2
4,4

THREE PHASE 8 POLES

0,7
0,7
1,0
1,3
2,0
2,2
3,0
2,8
4,5
3,0
4,6

* Three phase speed controllers (RMT) or inverter control (VFKB/VFTM) are suitable for 400V.

0,4
0,4
0,6
0,8
1,2
1,3
1,7
1,6
2,6
1,7
2,7

Dimensions (mm)

/2

/4

250

315

260

220

254

10

122

122

315

400

330

280

315

10

129

122

355

450

380

315

355

10

129

129

400

500

420

355

400

10

129

129

450

560

480

400

450

10

150

150

150

500

630

560

450

500

10

150

150

150

560

710

630

510

560

10

218,5

150

150

630

800

710

580

630

12

218,5

150

150

710

900

800

636

710

12

218,5 218,5 218,5

Number of Poles
/6

/8

Number of Poles

/2

/4

/6

/8

294

59

59

122

329

45

32

129

371

45

45

422

40,5

40,5

476

48

48

48

536

44,5

44,5

596

110,5

42

674

110,5

733

134

Tri- Singlephase phase

53

12

40

65

32

68

12

40

65

45

75

12

40

65

78

12

40

65

91

12

40

65

44,5

97

12

40

65

42

98,5

12

40

65

41

41

103

12

40

65

134

134

91,5

16,5

40

65

HCBT-B/2-315/H

400

330

280

315

10

298

329

220,5

77,5

68

12

135

HCBT-B/2-355/H

450

380

315

355

10

298

371

219

79

75

12

135

Model

Model

/4

L
345

800

1000

800

800

92

926

900

1120

900

900

120

1060

1000

1250

1000

1000

110

1154

/6

/8

/4

380

310

345

310

345

181

439
380

485

/6

/8

203

162

181

162

181

181

203

181

203

306
345

380

345

380

203

280

Plate mounted axial flow fans

G
D

C
B

Model

COMPACT

Models HCBT-B/2-315/H

HCBT-B/2-355/H

Installation accessories

Plate mounted axial flow fans

COMPACT

DEF-D

Model HCFB/HCFT
HCBB/HCBT
250

PER-CN
PER-W
PER-EX

DEF-AN

(for models 800


and 1000)

PER-CN
PER-W

Wire Protection Guards

DEF-D

DEF-1001A

HCFT/4-1000/H

Exhaust Side Louvre Shutters

Outlet

Inlet

Plastic

Aluminium

ATEX version*

DEF-250 D

PER-250 W

PER-250 CN

PER-315 Ex

315

DEF-325 D

PER-355 W

PER-355 CN

PER-315 Ex

355

DEF-375 D

PER-355 W

PER-355 CN

PER-355 Ex

400

DEF-450 D

PER-400 W

PER-400 CN

PER-400 Ex

450

DEF-450 D

PER-450 W

PER-450 CN

PER-450 Ex

500

DEF-525 D

PER-500 W

PER-500 CN

PER-500 Ex

560

DEF-630 D

PER-560 W

PER-630 CN

PER-560 Ex

630

DEF-630 D

PER-630 W

PER-630 CN

PER-630 Ex
PER-710 Ex

710

DEF-800 D

PER-710 W

PER-710 CN

800

DEF-800 D

DEF- 800 AN

PER-800 W

PER-800 CN

900

DEF-1000 D

DEF- 900 AN

PER-1000 W

PER-1000 CN

1000

DEF-1000 D

DEF-1000 AN

PER-1000 W

PER-1000 CN

HCFT / 4-1000 / H

DEF-1000 D

DEF-1001 AN

PER-1000 W

PER-1000 CN

* Only can be mounted with HCBT explosion proof versions. For more information see mounting accessories.

Electrical accessories
REB-1N / REB-2,5N
Single phase
electronic
speed controllers

REB-5 / REB-10
Single phase
electronic speed
controllers

RMB/RMT
Single and three
phase auto
transformer speed
controllers

REB-4 Auto
Electronic single phase
speed controllers with
temperature sensor. For
agricultural applications

VFKB
Adjustable frequency
drives for three phase
motors from 0,37 to 4
kW. 230 V or 400 V

Three phase fan


To connect three
phase fans with 400 V
motor.
For three phase
models

VFTM IP54
Adjustable frequency
drive for three phase
motors from 0,37 to
15 kW. 230 V or 400 V

Performance curves HCFB/HCFT HCBB/HCBT TCFB/TCFT Series

COMPACT

Q = Air volume in, m3/hr and m3/s.


Pst = Static pressure in mmWG and Pa.
Dry air at 20C and 760 mmHg.
Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
mm
WG

Typical fan selection:

System
Resistance
Curve

Do not select the working point in the coloured area. To find the
working point it is first necessary to plot the system resistance
curve. The working point lies at the intersection between that curve
and the fan performance curve.

Working Point of Fan

Required Air Volume

m3/h

Example: Required air volume 10.000


at 3 mmWG.

Fan working point 11.300 m3/h at 4 mmWG.

Pst
mmWG

Pst
mmWG

4 pole - 250 - 315 - 355

Pst
mmWG

2 pole - 250 - 315 - 355

4 pole - 400 - 450 - 500

Plate mounted axial flow fans

Do Not Select a Fan


with a Working Point
in this Area

Plate mounted axial flow fans

COMPACT

Performance curves HCFB/HCFT HCBB/HCBT TCFB/TCFT Series


Q = Air volume in, m3/hr and m3/s.
Pst = Static pressure in mmWG and Pa.
Dry air at 20C and 760 mmHg.
Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.
Pst

mmWG

4 pole - 560 - 630 - 710

Pst

mmWG

mmWG

Pst

Pst

mmWG

Pst

6 pole - 315-355-400-450-500

4 pole - 800 - 900 - 1000

mmWG

6 pole - 560 - 630 - 710

mmWG

8 pole - 450 - 500

Pst

6 pole - 800 - 900 - 1000

Pst

mmWG

8 pole - 560 - 630 - 710

Pst

mmWG

8 pole - 800 - 900 - 1000

Plate mounted axial flow fans

Q = Air volume in, m3/hr and m3/s.


Pst = Static pressure in mmWG and Pa.
Dry air at 20C and 760 mmHg.
Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

COMPACT

Performance curves HCFB/HCFT HCBB/HCBT TCFB/TCFT Series

Vous aimerez peut-être aussi