FDKN-C

11. WALL MOUNTED TYPE


PACKAGED AIR CONDITIONER
Split system, Air cooled
cooling only type

FDKN208CEN-S, FDKN208CEP-S, FDKN208CEN


FDKN208CEP, FDKN258CEN-S, FDKN258CEP-S
FDKN258CEN, FDKN258CEP, FDKN308CEN
FDKN308CEP, FDKN308CES

469

FDKN-C
CONTENTS
11.1

GENERAL INFORMATION...................................................................... 471

11.1.1

Specific features ............................................................................... 471

11.1.2

How to read the model name ........................................................... 471

11.2

SELECTION DATA .................................................................................. 472

11.2.1

Specifications ................................................................................... 472

11.2.2

Range of usage & limitations .......................................................... 483

11.2.3

Exterior dimensions ......................................................................... 484

11.2.4

Exterior appearance ......................................................................... 492

11.2.5

Piping system ................................................................................... 493

11.2.6

Selection chart .................................................................................. 494

11.2.7

Noise level ......................................................................................... 497

11.3

ELECTRICAL DATA ................................................................................ 499

11.3.1

Electrical wiring ................................................................................ 499

11.4

OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER ........... 504

11.5

APPLICATION DATA ............................................................................... 504

11.6

MAINTENANCE DATA ............................................................................ 504

470

FDKN-C
11.1 GENERAL INFORMATION
11.1.1 Specific features
(1)

Less refrigerant charge amount due to use of double phase refrigerant flow system. The total refrigerant charge amount has
been reduced by more than 50%.

(2)

The indoor outdoor interconnection signal wiring has been done away with. The microcomputer chip is installed in the
indoor unit. There is no need for the unit to communicate between the outdoor and indoor units so the unit is more resistant
to electromagnetic noise thus the incidence of microcomputer malfunction has been reduced. The compressor in the outdoor
unit has its own self protection function, that reacts according to abnormal high pressure and excessive high temperature.

(3)

There are only four power line between the outdoor and indoor unit. As no signal wire is used there is no need to separate the
power line from the signal line. One cab tyre cable with 4 wires encased in one sheath is enough for conducting the wiring
work between the outdoor unit and the indoor unit. This contributes to simpler wiring work in the field.

(4)

The operation modes are only cooling and fan operation for easier control.

(5)

All air supply ports have auto swing louvers. The indoor fan motor has two speeds of high and low.

(6)

The controls are wireless residential split air conditioner type remote controller with 4 malfunction modes.

(7)

All models have service valves protruding from the outdoor unit for faster flare connection work in the field.

(8) Aero trap louver


(a)

Pleasantness will be enhanced with the employment of aero trap louver. It has an excellent wind orientation and a
homogeneous air conditioning feeling is ensured at every corner in a room with the auto swing blasting which can be
adjusted the maximum 70 downward.

(b)

Louver angle can be adjusted to 4 fixed positions with the remote control. It can be adjusted at any optional angle
during the manual operation. Sidewise blast is adjustable by 40 in each direction.

(9) Low noise


Specially developed silent fan is employed. A very gentle operation sound is assured because the noise like wind slashing
sound are suppressed effectively.
(10) Thin and compact design
The unit measures 17.9 cm (208 type) or 19.6 cm (258, 308 type) in thickness and its size is so compact as a room air
conditioner. Body of the unit is dinished in the ivory white color and a pleasant and simple design produces a very pleasant
harmony for the interior design.

11.1.2 How to read the model name


Example: FDKN

20 8 C

EN

Applicable power source ... See the specifications


Cooling only type
Series No.
Product capacity
Model name

FDKN: Wall mounted type unit with


wireless remote controller.
FDC: Outdoor unit

471

FDKN-C
11.2 SELECTION DATA
11.2.1 Specifications
Model FDKN208CEN-S
FDKN208CEN-S

Model
Item

FDKN208C

Nominal cooling capacity(1)

FDC208CEN3
4850

Power source
Operation data(3)

Cooling input

1 Phase, 220/240V, 50Hz


kW

1.76/1.85

Running current (Cooling)

8.2/8.0

Power factor (Cooling)

98/96

Inrush current (L.R.A)

44

Noise level(4)
Exterior dimensions
Height Width Depth

dB(A)

Hi:45 Lo:38

52

mm

275 790 179

690 880 290

Net weight
Refrigerant equipment
Compressor type & Qty

kg

10

49

RM5523GNE4 1

1.6

Line starting

Heat exchanger

Louver fins & inner grooved tubing

Slitted fines & bare tubing

Refrigerant control

Capillary tube

Motor

kW

Starting method

Capillary tube

Refrigerant

R22

Quantity
Refrigerant oil

kg

Holding charged

0.9 [Pre-charged up to the piping length of 5m]


0.7 (BARREL FREEZE 32 SAM)

High pressure control

Air handling equipment

Tangential fan 1

Fan type & Qty


Motor

Starting method
Air flow (Standard)

CMM

Fresh air intake


Air filter, Qty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Safety equipment
Installation data
Refrigerant piping size

26 1

55 1

Line starting

Line starting

Hi:16 Lo:10

56

Unavailable

Long life filter 2 (washable)

Rubber sleeve (for fan motor)

Rubber mount (for compressor)

20 (Crank case heater)

Wireless remote control switch

(Indoor unit side)

Room temperature control

Propeller fan 1

Thermostat by electronics

Internal thermostat for fan motor.


Frost protection thermostat.

Internal thermostat for fan motor.


Thermostat for discharge temperature.

mm
(in)

Liquid line: 6.35 (1/4) Gas line: 15.88 (5/8)

Connecting method
Drain hose

Flare piping
(Connectable with VP16)

Insulation for piping


Accessories

Necessary (both Liquid & Gas lines)


Mounting kit. Wireless remote controller. Drain hose

Optional parts
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Operation
DB
WB
Cooling
27C
19C

Outdoor air temperature


DB
WB
35C
24C

(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 UNITARY AIR CONDITIONERS
(3) The operation data indicate when the air conditioner is operated at 220V and 240V respectively.
(4) Indicates the value at mild mode.

472

Standards
ISO-T1, JIS B8616

FDKN-C
Model FDKN208CEP-S
FDKN208CEP-S

Model
Item

FDKN208C

Nominal cooling capacity(1)

FDC208CEP3
5200

Operation data(3)

Power source
Cooling input

1 Phase, 220V, 60Hz


kW

1.76

Running current (Cooling)

8.3

Power factor (Cooling)

96

Inrush current (L.R.A)

52

Noise level(4)
Exterior dimensions
Height Width Depth

dB(A)

Hi:45 Lo:38

52

mm

275 790 179

690 880 290

Net weight
Refrigerant equipment
Compressor type & Qty

kg

10

49

RM5520GP4 1

1.6

Line starting

Heat exchanger

Louver fins & inner grooved tubing

Slitted fines & bare tubing

Refrigerant control

Capillary tube

Motor

kW

Starting method

Capillary tube

Refrigerant

R22

Quantity
Refrigerant oil

kg

Holding charged

0.9 [Pre-charged up to the piping length of 5m]


0.7 (BARREL FREEZE 32 SAM)

High pressure control

Air handling equipment

Tangential fan 1

Fan type & Qty


Motor

Starting method
Air flow (Standard)

CMM

Fresh air intake


Air filter, Qty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Safety equipment
Installation data
Refrigerant piping size

26 1

55 1

Line starting

Line starting

Hi:16 Lo:10

56

Unavailable

Long life filter 2 (washable)

Rubber sleeve (for fan motor)

Rubber mount (for compressor)

20 (Crank case heater)

Wireless remote control switch

(Indoor unit side)

Room temperature control

Propeller fan 1

Thermostat by electronics

Internal thermostat for fan motor.


Frost protection thermostat.

Internal thermostat for fan motor.


Thermostat for discharge temperature.

mm
(in)

Liquid line: 6.35 (1/4) Gas line: 15.88 (5/8)

Connecting method
Drain hose

Flare piping
(Connectable with VP16)

Insulation for piping


Accessories

Necessary (both Liquid & Gas lines)


Mounting kit. Wireless remote controller. Drain hose

Optional parts
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Operation
DB
WB
Cooling
27C
19C

Outdoor air temperature


DB
WB
35C
24C

Standards
ISO-T1, JIS B8616

(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 UNITARY AIR CONDITIONERS
(3) The operation data indicate when the air conditioner is operated at 220V.
(4) Indicates the value at mild mode.

473

FDKN-C
Model FDKN258CEN-S
FDKN258CEN-S

Model
Item

FDKN258C

Nominal cooling capacity(1)

FDC258CEN3
5700

Power source
Operation data(3)

Cooling input

1 Phase, 220/240V, 50Hz


kW

2.03/2.14

Running current (Cooling)

9.3/9.3

Power factor (Cooling)

99/96

Inrush current (L.R.A)

51

Noise level(4)
Exterior dimensions
Height Width Depth

dB(A)

Hi:45 Lo:38

52

mm

298 940 196

845 880 340

Net weight
Refrigerant equipment
Compressor type & Qty

kg

11

55

RM5526GNE4 1

1.9

Line starting

Heat exchanger

Louver fins & inner grooved tubing

Slitted fines & bare tubing

Refrigerant control

Capillary tube

Motor

kW

Starting method

Capillary tube

Refrigerant

R22

Quantity
Refrigerant oil

kg

Holding charged

1.05 [Pre-charged up to the piping length of 5m]


0.7 (BARREL FREEZE 32 SAM)

High pressure control

Air handling equipment

Tangential fan 1

Fan type & Qty


Motor

Starting method
Air flow (Standard)

CMM

Fresh air intake


Air filter, Qty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Safety equipment(4)
Installation data
Refrigerant piping size

40 1

55 1

Line starting

Line starting

Hi:17 Lo:10

56

Unavailable

Long life filter 2 (washable)

Rubber sleeve (for fan motor)

Rubber mount (for compressor)

20 (Cank case heater)

Wireless remote control switch

(Indoor unit side)

Room temperature control

Propeller fan 1

Thermostat by electronics

Internal thermostat for fan motor.


Frost protection thermostat.

Internal thermostat for fan motor.


Thermostat for discharge temperature.

mm
(in)

Liquid line: 9.52 (3/8) Gas line: 15.88 (5/8)

Connecting method
Drain hose

Flare piping
(Connectable with VP16)

Insulation for piping


Accessories

Necessary (both Liquid & Gas lines)


Mounting kit. Wireless remote controller. Drain hose

Optional parts
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Operation
DB
WB
Cooling
27C
19C

Outdoor air temperature


DB
WB
35C
24C

(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 UNITARY AIR CONDITIONERS
(3) The operation data indicate when the air conditioner is operated at 220V and 240V respectively.
(4) Indicates the value at mild mode.

474

Standards
ISO-T1, JIS B8616

FDKN-C
Model FDKN258CEP-S
FDKN258CEP-S

Model
Item

FDKN258C

Nominal cooling capacity(1)

FDC258CEP3
6200

Operation data(3)

Power source
Cooling input

1 Phase, 220V, 60Hz


kW

2.75

Running current (Cooling)

12.7

Power factor (Cooling)

98

Inrush current (L.R.A)

71

Noise level(4)
Exterior dimensions
Height Width Depth

dB(A)

Hi:45 Lo:38

52

mm

298 940 196

845 880 340

Net weight
Refrigerant equipment
Compressor type & Qty

kg

11

55

RM5526GP4 1

1.9

Line starting

Heat exchanger

Louver fins & inner grooved tubing

Slitted fines & bare tubing

Refrigerant control

Capillary tube

Motor

kW

Starting method

Capillary tube

Refrigerant

R22

Quantity
Refrigerant oil

kg

Holding charged

1.13 [Pre-charged up to the piping length of 5m]


0.7 (BARREL FREEZE 32 SAM)

High pressure control

Air handling equipment

Tangential fan 1

Fan type & Qty


Motor

Starting method
Air flow (Standard)

CMM

Fresh air intake


Air filter, Qty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Safety equipment
Installation data
Refrigerant piping size

40 1

55 1

Line starting

Line starting

Hi:17 Lo:10

56

Unavailable

Long life filter 2 (washable)

Rubber sleeve (for fan motor)

Rubber mount (for compressor)

20 (Cank case heater)

Wireless remote control switch

(Indoor unit side)

Room temperature control

Propeller fan 1

Thermostat by electronics

Internal thermostat for fan motor.


Frost protection thermostat.

Internal thermostat for fan motor.


Thermostat for discharge temperature.

mm
(in)

Liquid line: 9.52 (3/8) Gas line: 15.88 (5/8)

Connecting method
Drain hose

Flare piping
(Connectable with VP16)

Insulation for piping


Accessories

Necessary (both Liquid & Gas lines)


Mounting kit. Wireless remote controller. Drain hose

Optional parts
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Operation
DB
WB
Cooling
27C
19C

Outdoor air temperature


DB
WB
35C
24C

Standards
ISO-T1, JIS B8616

(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 UNITARY AIR CONDITIONERS
(3) The operation data indicate when the air conditioner is operated at 220V.
(4) Indicates the value at mild mode.

475

FDKN-C
Model FDKN208CEN
FDKN208CEN

Model
Item

FDKN208C

Nominal cooling capacity(1)

ISO-T1
ISO-T3

ISO-T1
ISO-T3

Operation data(3)

Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height Width Depth
Net weight
Refrigerant equipment
Compressor type & Qty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Qty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Qty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment

FDC206CEN3
5000
4100
1 Phase, 220/240V, 50Hz
2.07/2.10
9.9/9.7
95/90
2.33/2.35
11.0/10.8
96/91
47

kW
A
%
kW
A
%
A
dB(A)

Hi:45 Lo:38

59

mm

275 790 179

615 850 290 + 30

kg

10

55

RC5520ENE1 1

kW

Louver fins & inner grooved tubing


Capillary tube

1.49
Line starting
Slitted fines & bare tubing
Capillary tube

kg
r

Holding charged

R22

W
CMM

0.9 [Pre-charged up to the piping length of 10m]


1.63 (SUNISO 3GS)
High pressure regulator valve

Tangential fan 1

Propeller fan 1

26 1
Line starting
Hi:16 Lo:10
Unavailable
Long life filter 2 (washable)
Rubber sleeve (for fan motor)

55 1
Line starting
42

Rubber mount (for compressor)

Wireless remote control switch


Thermostat by electronics

(Indoor unit side)

Internal protector for compressor.


Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.

Internal thermostat for fan motor.


Frost protection thermostat.

Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories

mm
(in)

Liquid line: 6.35 (1/4) Gas line: 15.88 (5/8)


Flare piping
(Connectable with VP16)

Necessary (both Liquid & Gas lines)


Mounting kit. Wireless remote controller. Drain hose

Optional parts

Notes (1) The data are measured at the following conditions.


Item
Operation
Cooling

Indoor air temperature

Outdoor air temperature

WB
19C

DB
35C

WB
24C

ISO-T1, JIS B8616

29C

19C

46C

24C

ISO-T3, SASO

(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 UNITARY AIR CONDITIONERS
(3) The operation data indicate when the air conditioner is operated at 220V and 240V respectively.
(4) Indicates the value at mild mode.

476

Standards

DB
27C

FDKN-C
Model FDKN208CEP
FDKN208CEP

Model
Item

FDKN208C

Nominal cooling capacity(1)

ISO-T1
ISO-T3

ISO-T1
ISO-T3

Operation data(3)

Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height Width Depth
Net weight
Refrigerant equipment
Compressor type & Qty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Qty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Qty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment

FDC206CEP3
5200
4500
1 Phase, 220V, 60Hz
2.06
9.6
98
2.32
10.9
97
50

kW
A
%
kW
A
%
A
dB(A)

Hi:45 Lo:38

59

mm

275 790 179

615 850 290 + 30

kg

10

55

RC5520EPE1 1

kW

Louver fins & inner grooved tubing


Capillary tube

1.31
Line starting
Slitted fines & bare tubing
Capillary tube

kg
r

Holding charged

R22

W
CMM

1.15 [Pre-charged up to the piping length of 10m]


1.63 (SUNISO 3GS)
High pressure regulator valve

Tangential fan 1

Propeller fan 1

26 1
Line starting
Hi:16 Lo:10
Unavailable
Long life filter 2 (washable)
Rubber sleeve (for fan motor)

55 1
Line starting
44

Rubber mount (for compressor)

Wireless remote control switch


Thermostat by electronics

(Indoor unit side)

Internal protector for compressor.


Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.

Internal thermostat for fan motor.


Frost protection thermostat.

Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories

mm
(in)

Liquid line: 6.35 (1/4) Gas line: 15.88 (5/8)


Flare piping
(Connectable with VP16)

Necessary (both Liquid & Gas lines)


Mounting kit. Wireless remote controller. Drain hose

Optional parts

Notes (1) The data are measured at the following conditions.


Item
Operation
Cooling

Indoor air temperature

Outdoor air temperature

Standards

DB
27C

WB
19C

DB
35C

WB
24C

ISO-T1, JIS B8616

29C

19C

46C

24C

ISO-T3, SASO

(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 UNITARY AIR CONDITIONERS
(3) The operation data indicate when the air conditioner is operated at 220V.
(4) Indicates the value at mild mode.

477

FDKN-C
Model FDKN258CEN
FDKN258CEN

Model
Item

FDKN258C

Nominal cooling capacity(1)

ISO-T1
ISO-T3

ISO-T1
ISO-T3

Operation data(3)

Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height Width Depth
Net weight
Refrigerant equipment
Compressor type & Qty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Qty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Qty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment

FDC256CEN3
5700
4900
1 Phase, 220/240V, 50Hz
2.57/2.61
12.5/13.1
93/83
2.75/2.79
13.3/13.9
94/84
64

kW
A
%
kW
A
%
A
dB(A)

Hi:45 Lo:38

59

mm

298 940 196

615 850 290 + 30

kg

11

56

RC5527ENE1 1

kW

Louver fins & inner grooved tubing


Capillary tube

1.87
Line starting
Slitted fines & bare tubing
Capillary tube

kg
r

Holding charged

R22

W
CMM

1.35 [Pre-charged up to the piping length of 5m]


1.63 (SUNISO 3GS)
High pressure regulator valve

Tangential fan 1

Propeller fan 1

40 1
Line starting
Hi:17 Lo:10
Unavailable
Long life filter 2 (washable)
Rubber sleeve (for fan motor)

55 1
Line starting
42

Rubber mount (for compressor)

Wireless remote control switch


Thermostat by electronics

(Indoor unit side)

Internal protector for compressor.


Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.

Internal thermostat for fan motor.


Frost protection thermostat.

Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories

mm
(in)

Liquid line: 9.52 (3/8) Gas line: 15.88 (5/8)


Flare piping
(Connectable with VP16)

Necessary (both Liquid & Gas lines)


Mounting kit. Wireless remote controller. Drain hose

Optional parts

Notes (1) The data are measured at the following conditions.


Item
Operation
Cooling

Indoor air temperature

Outdoor air temperature

WB
19C

DB
35C

WB
24C

ISO-T1, JIS B8616

29C

19C

46C

24C

ISO-T3, SASO

(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 UNITARY AIR CONDITIONERS
(3) The operation data indicate when the air conditioner is operated at 220V and 240V respectively.
(4) Indicates the value at mild mode.

478

Standards

DB
27C

FDKN-C
Model FDKN258CEP
FDKN258CEP

Model
Item

FDKN258C

Nominal cooling capacity(1)

ISO-T1
ISO-T3

ISO-T1
ISO-T3

Operation data(3)

Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height Width Depth
Net weight
Refrigerant equipment
Compressor type & Qty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Qty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Qty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment

FDC256CEP3
6200
5200
1 Phase, 220V, 60Hz
2.66
12.3
98
3.04
14.3
97
66

kW
A
%
kW
A
%
A
dB(A)

Hi:45 Lo:38

59

mm

298 940 196

615 850 290 + 30

kg

11

56

RC5528EPE1 1

kW

Louver fins & inner grooved tubing


Capillary tube

1.68
Line starting
Slitted fines & bare tubing
Capillary tube

kg
r

Holding charged

R22

W
CMM

1.35 [Pre-charged up to the piping length of 5m]


1.63 (SUNISO 3GS)
High pressure regulator valve

Tangential fan 1

Propeller fan 1

40 1
Line starting
Hi:17 Lo:10
Unavailable
Long life filter 2 (washable)
Rubber sleeve (for fan motor)

55 1
Line starting
44

Rubber mount (for compressor)

Wireless remote control switch


Thermostat by electronics

(Indoor unit side)

Internal protector for compressor.


Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.

Internal thermostat for fan motor.


Frost protection thermostat.

Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories

mm
(in)

Liquid line: 9.52 (3/8) Gas line: 15.88 (5/8)


Flare piping
(Connectable with VP16)

Necessary (both Liquid & Gas lines)


Mounting kit. Wireless remote controller. Drain hose

Optional parts

Notes (1) The data are measured at the following conditions.


Item
Operation
Cooling

Indoor air temperature

Outdoor air temperature

Standards

DB
27C

WB
19C

DB
35C

WB
24C

ISO-T1, JIS B8616

29C

19C

46C

24C

ISO-T3, SASO

(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 UNITARY AIR CONDITIONERS
(3) The operation data indicate when the air conditioner is operated at 220V.
(4) Indicates the value at mild mode.

479

FDKN-C
Model FDKN308CEN
FDKN308CEN

Model
Item

FDKN308C

Nominal cooling capacity(1)

ISO-T1
ISO-T3

ISO-T1
ISO-T3

Operation data(3)

Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height Width Depth
Net weight
Refrigerant equipment
Compressor type & Qty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Qty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Qty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment

FDC306CEN3
7100
5700
1 Phase, 220/240V, 50Hz
3.04/3.08
15.5/16.2
89/79
3.23/3.27
16.5/17.2
89/79
89

kW
A
%
kW
A
%
A
dB(A)

Hi:46 Lo:40

56

mm

298 1155 196

844 950 340

kg

13.5

67

RC5532ENE1 1

kW

Louver fins & inner grooved tubing


Capillary tube

2.24
Line starting
Slitted fines & bare tubing
Capillary tube

kg
r

Holding charged

R22

W
CMM

1.3 [Pre-charged up to the piping length of 10m]


1.63 (SUNISO 3GS)
High pressure regulator valve

Tangential fan 1

Propeller fan 1

40 1
Line starting
Hi:21 Lo:15
Unavailable
Long life filter 3 (washable)
Rubber sleeve (for fan motor)

60 1
Line starting
54

Rubber mount (for compressor)

Wireless remote control switch


Thermostat by electronics

(Indoor unit side)

Internal protector for compressor.


Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.

Internal thermostat for fan motor.


Frost protection thermostat.

Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories

mm
(in)

Liquid line: 9.52 (3/8) Gas line: 15.88 (5/8)


Flare piping
(Connectable with VP16)

Necessary (both Liquid & Gas lines)


Mounting kit. Wireless remote controller. Drain hose

Optional parts

Notes (1) The data are measured at the following conditions.


Item
Operation
Cooling

Indoor air temperature

Outdoor air temperature

WB
19C

DB
35C

WB
24C

ISO-T1, JIS B8616

29C

19C

46C

24C

ISO-T3, SASO

(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 UNITARY AIR CONDITIONERS
(3) The operation data indicate when the air conditioner is operated at 220V and 240V respectively.
(4) Indicates the value at mild mode.

480

Standards

DB
27C

FDKN-C
Model FDKN308CEP
FDKN308CEP

Model
Item

FDKN308C

Nominal cooling capacity(1)

ISO-T1
ISO-T3

ISO-T1
ISO-T3

Operation data(3)

Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height Width Depth
Net weight
Refrigerant equipment
Compressor type & Qty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Qty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Qty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment

FDC306CEP3
7100
5700
1 Phase, 220V, 60Hz
3.00
13.9
98
3.23
15.1
97
78

kW
A
%
kW
A
%
A
dB(A)

Hi:46 Lo:40

59

mm

298 1155 196

844 950 340

kg

13.5

67

RC5533EPE1 1

kW

Louver fins & inner grooved tubing


Capillary tube

1.87
Line starting
Slitted fines & bare tubing
Capillary tube

kg
r

Holding charged

R22

W
CMM

1.3 [Pre-charged up to the piping length of 10m]


1.63 (SUNISO 3GS)
High pressure regulator valve

Tangential fan 1

Propeller fan 1

40 1
Line starting
Hi:21 Lo:15
Unavailable
Long life filter 3 (washable)
Rubber sleeve (for fan motor)

60 1
Line starting
56

Rubber mount (for compressor)

Wireless remote control switch


Thermostat by electronics

(Indoor unit side)

Internal protector for compressor.


Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.

Internal thermostat for fan motor.


Frost protection thermostat.

Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories

mm
(in)

Liquid line: 9.52 (3/8) Gas line: 15.88 (5/8)


Flare piping
(Connectable with VP16)

Necessary (both Liquid & Gas lines)


Mounting kit. Wireless remote controller. Drain hose

Optional parts

Notes (1) The data are measured at the following conditions.


Item
Operation
Cooling

Indoor air temperature

Outdoor air temperature

Standards

DB
27C

WB
19C

DB
35C

WB
24C

ISO-T1, JIS B8616

29C

19C

46C

24C

ISO-T3, SASO

(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 UNITARY AIR CONDITIONERS
(3) The operation data indicate when the air conditioner is operated at 220V.
(4) Indicates the value at mild mode.

481

FDKN-C
Model FDKN308CES
FDKN308CES

Model
Item

FDKN308C

Nominal cooling capacity(1)

ISO-T1
ISO-T3

ISO-T1

kW
A
%
kW
A
%
A
dB(A)

ISO-T3

Operation data(3)

Power source
Cooling input
Running current (Cooling)
Power factor (Cooling)
Cooling input
Running current (Cooling)
Power factor (Cooling)
Inrush current (L.R.A)
Noise level(4)
Exterior dimensions
Height Width Depth
Net weight
Refrigerant equipment
Compressor type & Qty
Motor
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
High pressure control
Air handling equipment
Fan type & Qty
Motor
Starting method
Air flow (Standard)
Fresh air intake
Air filter, Qty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment

FDC306CES3
7100/7700
5700/6000
3 Phase, 380-415V 50Hz or 380V 50Hz/415V 50Hz, 380V 60Hz
2.80/2.81/3.32
5.2/5.2/5.9
82/75/85
2.99/3.00/3.55
5.6/5.6/6.4
81/75/84
43
Hi:46 Lo:40
59

mm

298 1155 196

844 950 340

kg

13.5

67

RC5538ESE1 1

kW

Louver fins & inner grooved tubing


Capillary tube

2.24
Line starting
Slitted fines & bare tubing
Capillary tube

kg
r

Holding charged

R22

W
CMM

1.3 [Pre-charged up to the piping length of 10m]


1.63 (SUNISO 3GS)
High pressure regulator valve

Tangential fan 1

Propeller fan 1

40 1
Line starting
Hi:21 Lo:15
Unavailable
Long life filter 3 (washable)
Rubber sleeve (for fan motor)

60 1
Line starting
54/56

Rubber mount (for compressor)

Wireless remote control switch


Thermostat by electronics

(Indoor unit side)

Internal protector for compressor.


Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.

Internal thermostat for fan motor.


Frost protection thermostat.

Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories

mm
(in)

Liquid line: 9.52 (3/8) Gas line: 15.88 (5/8)


Flare piping
(Connectable with VP16)

Necessary (both Liquid & Gas lines)


Mounting kit. Wireless remote controller. Drain hose

Optional parts

Notes (1) The data are measured at the following conditions.


Item
Operation
Cooling

Indoor air temperature

Outdoor air temperature

DB

WB

DB

WB

27C
29C

19C
19C

35C
46C

24C
24C

(2) This packaged air conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 UNITARY AIR CONDITIONERS
(3) The operation data indicate when the air conditioner is operated at 380/415V 50Hz and 380V 60Hz respectively.
(4) Indicates the value at mild mode.

482

Standards
ISO-T1, JIS B8616
ISO-T3, SASO

FDKN-C
11.2.2 Renge of usage & limitations
Models

FDKN208, 258 (FDC208, 258 type)

FDKN208, 258, 308 (FDC206, 256, 306 type)

Item
Indoor return air temperature
(Upper, lower limits)
Refer to the selection chart

Outdoor air temperature


(Upper, lower limits)
Refrigerant line (one way) length
Vertical height difference between
outdoor unit and indoor unit
Power source voltage

30 m
Max. 20 m (Outdoor unit is higher)

15 m

Max. 15 m (Outdoor unit is lower)


Rating 10%

Voltage at starting

Min. 85% of rating

Frequency of ON-OFF cycle

Max. 10 times/h

ON and OFF interval

Min. 3 minutes

483

FDKN-C
11.2.3 Exterior dimensions
(1) Indoor unit
Model FDKN208C

Unit: mm
784
68

40

26

179

790

3
Mounting plate

56

275

Remote controller
signal receives

Lower piping outlet


(Refer to the top view.)

Indoor unit
15

Outlet for piping (On both side)

Mounting plate
15

760
450

170

170
50 50

4.5

36

187.5

261.5

61

46

50 50

Gas piping
15. 88(5/8)

67
Hole on wall for
rear connection
(65)
Drain hose (VP16)

82
390

440
600

Liquid piping
6.35(1/4)

VIEW A (Rear side)

65 or
more

Space for installation and service

120 or
more

484

120 or
more

Hole on wall for


rear connection
(65)

49

Outer for electric wiring

FDKN-C
Model FDKN258C
Unit: mm
930
75

51

45

940

196

Mounting plate

55

298

Remote controller
signal receives

Lower piping outlet


(Refer to the top view.)

Outer for
electric wiring

51
Outlet for piping (On both side)

Indoor unit
Mounting plate
55

53

832
245

450
50

50

50

Hole on wall for


rear connecting
(65)

72

Drain hose
(VP16)

65
463

Liquid piping
9.52(3/8)

518
600

Gas piping

Hole on wall for


rear connection
(65)

15.88(5/8)

VIEW A (Rear side)

Space for installation and service

90 or
more

37

283

209

60

55

50

245

120 or
more

120 or
more

485

FDKN-C
Model FDKN308C
Unit : mm
1145
75

45

75

51

51

35

196

1155

55

298
Lower piping outlet
(Refer to the top view)

Mounting
plate

Remote controller
signal receives

51
Outlet for piping
(On both side)

Indoor unit
54

Mounting plate
54

1047
220

245

690
50

450
50

50

450
45

60

50

Hole on wall for


rear connecting
(65)

Drain hose
(VP16)
Liquid piping
9.52 (3/8'')

72
245

282.5

8 - 12 18
(Long hole)

65
465
515

Gas piping
15.88 (5/8'')

600

VIEW A (Rear side)

90 or
more

Space for installation and service

120 or
more

486

120 or
more

6.5

37

209

4 - 5.5 15
(Long hole)

Hole on wall for


rear connecting
(65)

Outlet for
electric
wiring

FDKN-C
(2) Wireless remote controller

COOL DRY FAN


FAN HI LO

FILTER

Unit : mm

C
ON AM
PM

TEMP

ON/OFF

161.5

MODE

OFF AM
PM

60

20.5

(3) Inication board of indoor unit

487

FDKN-C
(4) Outdoor unit
Models FDC208CEN3, 208CEP3

Unit: mm
Liquid piping: 6.35 (1/4)
(Flare connecting)

40

53

Gas piping: 15.88 (5/8)


(Flare connecting)

40
95

Liquid piping: 6.35 (1/4)


(Flare connecting)

Terminal block

Gas piping: 15.88 (5/8)


(Flare connecting)

690

Opening for electric wiring

195

351

Opening for piping and


electric wiring

50

331

50

Opening for piping


and electric wiring

195

10

110

110

50

40
50

50

27

15

880
Electric wiring
Opening for
electric wiring

150

70

15

Opening for piping


and electric wiring

103

150

580

150

40

50

55

290
35

35

330
15

15

Holes for anchor bolt


(M10 4 pcs. )

15
50

55
335

260

15

Holes for drain


(20 3 pcs. )

50

VIEW A

40

Minimum allowable space to the obstacles


Unit: mm
Installation type
1

L1

Open

Open

500

L2

300

Open

L3

100

150

100

L4

Mark
Required space for maintenance and air flow

L3
L2

Air inlet
L4

Air
inlet

488

L1

Maintenance
space

Air outlet

Notes
(1) Avoid the location where four sides are entirely surrounded by
walls.
(2) Fix the unit by anchor bolts without fail. Restrict the protrusion
length of anchor bolt to 15 mm and under.
(3) When strong wind blows against the unit, direct the discharge
port at a right angle to the wind direction.
(4) Secure the space of 1 m and over at the top of unit.
(5) Make the height of obstruction wall in front of discharge port
lower than the height of unit.

FDKN-C
Models FDC258CEN3, 258CEP3
Unit: mm
Liquid piping: 9.52 (3/8")
(Flare connecting)

53

40

Gas piping: 15.88 (5/8")


(Flare connecting)

40
95

Terminal block

Liquid piping: 9.52 (3/8")


(Flare connecting)

Opening for piping


and electric wiring

110

195
50

50

10

195

460

110

845

Gas piping: 15.88 (5/8")


(Flare connecting)
Opening for
electric wiring
Opening for
electric wiring

50

40
50

27

15

Opening for piping


and electric wiring

50

880

15

35

103

70

Opening for piping


and electric wiring

40

50
222

50

47

340
35

55

380
15

Electric wiring

150

15

150

Holes for anchor bolt


(M10 4 pcs.)
580
150

15

50
15

50

Holes for drain


(9.52 3pcs.)

310

VIEW A
Required space for maintenance and air flow

Minimum allowable space to the obstacles


Unit:mm

L3
L2

Installation
type

Air inlet
L4

Air
inlet

L1

Maintenance
space

Air outlet

L1

Open

Open

500

L2

300

Open

L3

100

150

100

L4

Mark

Notes
(1) Avoid the location where four sides are entirely
surrounded by walls.
(2) Fix the unit by anchor bolts without fail. Restrict
the protrusion length of anchor bolt to 15 mm
and under.
(3) When strong wind blows against the unit, direct the discharge port at a right angle to the
wind direction.
(4) Secure the space of 1 m and over at the top of
unit.
(5) Make the height of obstruction wall in front of
discharge port lower than the height of unit.

489

FDKN-C
Models FDC206CEN3, 206CEP3, 256CEN3, 256CEP3
Unit: mm

30

Anchor bolts
(M10 4 pcs.)

19

30

307

19

170

345

510

25

170

33

30

850

290

615

Terminal block

Gas piping: 15.88(5/8")


(Flare connecting)
206 type, 6.35(1/4")
Liquid piping: 256 type, 9.52(3/8")
(Flare connecting)
206 type: 125
256 type: 145

25

128

Opening for
electric wiring

65 105

15
87

Required space for maintenance and air flow

Minimum allowable space to the obstacles


Unit:mm

L3
L2

Air inlet
500 mm

Air
inlet

L1

Maintenance
space

Installation
type

Air outlet

Obstacles

L1

Open

100

L2

100

Open

L3

100

500

Mark

Notes
(1) Fix the unit with anchor bolts.
(2) Strong wind must not be directed to the air
outlet.
(3) Free space over the unit must be larger than
1 m.
(4) The unit should not be surrounded by
obstructions in all direction.
At least one direction around the unit must
be free.

490

FDKN-C
Models FDC306CEN3, 306CEP3, 306CES3
Unit: mm
580

185

30

340

35

70

38

18

380

15

185

33

Anchor bolts
(M10 4 pcs.)

950

Terminal block

844

Gas piping: 15.88(5/8")


(Flare connecting)
Opening for
electric wiring

65
30

Required space for maintenance and air flow

128

85

145

25

30

Liquid piping: 9.52(3/8")


(Flare connecting)

102
255

Minimum allowable space to the obstacles


Unit:mm

L3
L2

Air inlet
500 mm

Air
inlet

L1

Maintenance
space

Installation
type

Air outlet

L1

Open

Open

500

L2

300

Open

L3

100

150

100

Mark
Obstacles

Notes
(1) Fix the unit with anchor bolts.
(2) Strong wind must not be directed to the air
outlet.
(3) Free space over the unit must be larger than
1 m.
(4) The unit should not be surrounded by obstructions in all direction.
At least one direction around the unit must be
free.

491

FDKN-C
11.2.4 Exterior appearance
(1) Indoor unit
Models All models
Ivory white
(Front panel)
Ivory white
(Air inlet grill)
Ivory white
(Base)

Ivory white
(Louver)

(2) Outdoor unit


Models FDC208CEN3, 208CEP3

Models FDC258CEN3, 258CEP3


Polar white

Polar white

Models FDC206CEN3, 206CEP3, 256CEN3


256CEP3

Models FDC306CEN3, 306CEP3, 306CES3


Polar white

Polar white

492

FDKN-C
11.2.5 Piping system
Models FDKN208CEN-S, 208CEP-S, 258CEN-S, 258CEP-S
Check joint

Service valve
(Flare connecting)

Indoor unit

Outdoor unit

Gas line
15.88
Thermistor
(ThI-A)
Capillary tube

Heat
exchanger

Heat exchanger
Thermostat
(23Td)
Thermistor
(ThI-R)

Solenoid
SV
valve
Compressor
Accumulator

Liquid line
208:6.35
258: 9.52

Check joint

Capillary tube

Strainer

Service valve
(Flare connecting)

Models FDKN208CEN, 208CEP, 258CEN, 258CEP,


308CEN, 308CEP, 308CES
Check joint

Indoor Unit

Service valve
(Flare connecting)

Outdoor Unit

Strainer
Gas line
(15.88)

Check joint

Thermistor
(ThI-A)
Heat exchanger

Heat exchanger
Compressor

High Pressure
regulator valve

Thermistor
(ThI-R)

Liquid line
208: 6.35
258,308: 9.52

Strainer

Service valve
Capillary tube
(Flare connecting)

Preset point of the protective devices


Part name
Thermistor
(for frost prevention)

Mark

Equipped
unit

All models

ThI-R

Indoor unit

OFF 2.5C
ON 10C

493

FDKN-C
11.2.6 Selection chart
Correct the cooling capacity in accordance with the conditions as follows. The net cooling capacity can be obtained in the
following way.
Net capacity = Capacity shown on specifications Correction factors as follows.
(1) Coefficient of cooling capacity in relation to temperatures
(a) Only case of ISO-T1 models
Coefficient of cooling capacity in relation
to temperatures

1.3
1.2

Cooling

1.1
1.0
0.9
0.8
0.7
0.6

Cooling operation

Outdoor air D.B.


temperature (CD.B.)

Applicable range
43
40
35
30
25

27
26

20

24

15
10
14

16

18

20

22

ISO-T1 Standard condition

Indoor air W.B. temperature (CW.B.)

494

24

FDKN-C

Coefficient of cooling capacity in relation


to temperatures

(b) Only case of ISO-T3 and SASO models


1.3
1.2

Cooling

1.1
1.0
0.9
0.8
0.7
0.6

Outdoor air D.B.


temperature (CD.B.)

Cooling operation

Applicable range
60
55
50
43
40
35
30
25
20
15
10

27
26
24
10
14

16

18

20
22
ISO-T1 Standard condition
Indoor air W.B. temperature (CW.B.)

24

Table of bypass factor


Item
Air flow

Model

FDKN208 type

FDKN258 type

0.03

0.03

Hi

FDKN308 type
0.04

(2) Correction of cooling capacity in relation to air flow rate control (fan speed)
Coefficient: 1.00 at High, 0.95 at Low

(3) Correction of cooling capacity in relation to one way length of refrigerant piping
It is necessary to correct the cooling capacity in relation to the one way equivalent piping length between the indoor and outdoor
units.

(50/60Hz)
(1)

10

15

20

25

30

35

FDKN208type

1.0

0.995

0.995/0.99

0.99/0.985

0.985/0.98

0.985/0.975

0.98/0.97

FDKN258type

1.0

0.995

0.99

0.985

0.98

0.975

0.97

FDKN308type

1.0

0.99

0.98/0.975

0.97/0.965

0.96/0.95

0.95/0.94

0.94/0.925

Cooling

Equivalent piping length

Note (1)Equivalent piping length can be obtained by calculating as follows.


Equivalent piping length = Real piping length + (0.10 Number of bends in piping)
[Equivalent piping length Limitation length of piping + 5 m]

(4) When the outdoor unit is located at a lower height than the indoor unit in cooling operation, the following values
should be subtracted from the values in the above table.
Height difference between the indoor unit and
outdoor unit in the vertical height difference

5m

10 m

15 m

Adjustment coefficient

0.01

0.02

0.03

495

FDKN-C
Piping length limitations
Model
FDKN208, 258 (FDC208, 258 type)

FDKN208, 258, 308 (FDC206, 256, 306 type)

Item
Max. one way piping length

30 m
20m (Outdoor unit is higher)

Max. vertical height difference

15m

15m (Outdoor unit is lower)

Note (1)Values in the table indicate the one way piping length between the indoor and outdoor units.

How to obtain the cooling capacity


Example: The net cooling capacity of the model FDKN258CEN-S with the air flow High, the piping length of 15 m, the
outdoor unit located 5 m above the indoor unit, indoor wet-bulb temperature at 19.0C and outdoor dry-bulb
temperature 35C is
Net cooling capacity = 5700

FDKN258CEN-S

496

1.00

Air flow High

(0.99-0.01)

1.0

= 5586 W

Length 15 m.
Factor by air temperatures
Height difference 5 m

FDKN-C
11.2.7 Noise level
Notes (1) The data are based on the following conditions.
Ambient air temperature:
Indoor unit 27C DB, 19C WB
Outdoor unit 35C DB,

1m

Indoor unit
Measured based on JIS B 8616
Mike position as below
Unit
1m

Outdoor unit
Measured based on JIS B 8616
Mike position: at highest noise level
in position as below
Distance from front side
1m
Height
1m

Mike
(Center & Low points)

(2) The data in the chart are measured in an unechonic room.


(3) The noise levels measured in the field are usually higher than the data because of reflection.

(1) Indoor unit


Model FDKN208C
Noise level 45dB (A) at HIGH
38dB (A) at LOW

70

70

50

N50
40

N40
30

30

N30

N2

20
63

125

250

500

1000

2000

Sound pressure level


(Standard 0.0002 bar) dB

Sound pressure level


(Standard 0.0002 bar) dB

60

40

60

60

60
N60

50

50
N50

40

40
N40

30

30

63

125

Mid octave band frequency (Hz)

250

500

60
N60

50

50
N50

40

40
N40

30

30

N30

N2
0
20

20
8000

4000

70
N70

N70

N60
50

70

70

N70
60

Model FDKN308C
Noise level 46dB (A) at HIGH
40dB (A) at LOW

Souud pressure level


(standard 0.0002bar)

70

Model FDKN258C
Noise level 45dB (A) at HIGH
38dB (A) at LOW

1000

2000

4000

N30

N2
0
20

20
8000

63

125

Mid octave band frequency (Hz)

250

500

1000

2000

4000

20
8000

Mid octave band frequency (Hz)

(2) Outdoor unit


Model FDC208CEN3

Model FDC208CEP3

Noise level 52 dB (A)

Model FDC206CEN3

Noise level 52 dB (A)

70

50

N50
40

40

N40
30

30

N30

20
125

250

500

1000

2000

4000

60

60
N60

50

50
N50

40

40
N40

30

30
N30

N2

20

20
8000

63

125

Mid octave band frequency (Hz)

250

500

1000

2000

Model FDC206CEP3
Noise level 59 dB (A)

50

50
N50

40

40
N40

30

30
N30

20
500

1000

2000

4000

20
8000

Sound pressure level


(Standard 0.0002 bar) dB

Sound pressure level


(Standard 0.0002 bar) dB

60

250

40
N40

30

30
N30

N2
0

63

125

250

500

1000

2000

60

60

50

50
N50

40

40
N40

30

30
N30

N2
0

20
125

250

500

1000

20
8000

70

70
N70

N60

63

4000

Noise level 52 dB (A)


70
N70

N60

Mid octave band frequency (Hz)

40

Noise level 52 dB (A)

60

125

50
N50

Mid octave band frequency (Hz)

70

70

50

Model FDC258CEP3

N70

N2

60
N60

20

20
8000

Model FDC258CEN3

70

63

4000

60

Mid octave band frequency (Hz)

2000

Mid octave band frequency (Hz)

4000

20
8000

Sound pressure level


(Standard 0.0002 bar) dB

63

70
N70

Sound pressure level


(Standard 0.0002 bar) dB

50

Sound pressure level


(Standard 0.0002 bar) dB

Sound pressure level


(Standard 0.0002 bar) dB

60

N60

70

70
N70

60

N2

Noise level 59 dB (A)

70

70

N70

60

60
N60

50

50
N50

40

40
N40

30

30
N30

N2
0
20
63

125

250

500

1000

2000

4000

20
8000

Mid octave band frequency (Hz)

497

FDKN-C
Model FDC256CEN3

Model FDC256CEP3

Noise level 59 dB (A)

Model FDC306CEN3

Noise level 59 dB (A)


60
N60

50

50
N50

40

40
N40

30

30
N30

N2
0

20
63

125

250

500

1000

2000

4000

60

60

50

50
N50

40

40
N40

30

30
N30

N2

20

20
8000

63

125

250

500

1000

2000

Model FDC306CEP3

Noise level 59 dB (A)


70
N70

50

50
N50

40

40
N40

30

30
N30

N2
0

20
250

500

1000

2000

Mid octave band frequency (Hz)

498

4000

Sound pressure level


(Standard 0.0002 bar) dB

Sound pressure level


(Standard 0.0002 bar) dB

60
N60

60

60
N60

50

50
N50

40

40
N40

30

30
N30

N2

20
8000

20
63

125

250

500

1000

2000

Mid octave band frequency (Hz)

60

60
N60

50

50
N50

40

40
N40

30

30
N30

N2
0

20
63

125

250

500

1000

2000

Mid octave band frequency (Hz)

70

70
N70

125

20
8000

Model FDC306CES3

Noise level 59 dB (A)

63

4000

Mid octave band frequency (Hz)

60

70
N70

N60

Mid octave band frequency (Hz)

70

70

70
N70

Sound pressure level


(Standard 0.0002 bar) dB

Sound pressure level


(Standard 0.0002 bar) dB

60

Noise level 56 dB (A)

70

70
N70

Sound pressure level


(Standard 0.0002 bar) dB

70

4000

20
8000

4000

20
8000

WH

RD

Y/GN

BK

WH

BL

SV

CnM

OR

Cc
CFO
CH
CM
CnA~W
F
FMI
FMO
LED1
LED2
LM
NR
SV
SW
SW3
TB

Mark

BR

Parts name

CFO

CnP

CH

CnP

52C

RD

WH

Capacitor for CM
Capacitor for FMO
Crankcase heater
Compressor motor
Connector
Fuse
Fan motor (Indoor unit)
Fan motor (Outdoor unit)
Indication lamp (Green-Run)
Indication lamp (Yellow-Timer/Check)
Louver motor
Surge suppressor
Solenoid coil (for control)
Back up switch (ON/OFF)
Change over switch
Terminal block ( mark)

OR

CnM
CnM
OR OR
FMO
(49FO)

BK

52C

23Td

Meaning of marks

CM

CC

RD

5IC

WH

BK

BL BK

RD

F (3.15A)

NR

52C

ThI-A
ThI-R
Trl
Val
49FI
49FO
23Td
51C
52C
52X5
v

Mark

2
3

2
3

Y/GN

BK

WH

RD

Parts name

TB
1

TB
1

Thermistor
Thermistor
Transformer
Varistor
Internal thermostat for FMI
Internal thermostat for FMO
Thermostat
Overcurrent relay for CM
Magnetic contactor for CM
Auxiliary relay
Terminal (F)
Connector

BK

WH

RD

Y/GN

RD

Mark
BK
BL
BR
GR
OR
PK
RD
WH
Y
Y/GN

CnF
BL

Black
Blue
Brown
Gray
Orange
Pink
Red
White
Yellow
Yellow/Green

Color

52X5

FMI
(49FI)

Color mark

52X5

Indoor Unit

BK

Outdoor Unit

RD
Y/GN

WH

BL

WH

BL

WH
Y
BL

TB
RD
L

BK

WH

WH

WH
BK

CnJ

LM

BR
OR
RD

VaI

TrI
220/240V

14V

16V

ON 1 2 3 4
OFF

SW3

CnQ Test

CnW1 CnW2

BK BR

BK RD

CnT
CnN CnH
CnC
CnL
CnA

Power source
FDKN208CEN-S
1 Phase 220/240V 50Hz
FDKN208CEP-S
1 Phase 220V 60Hz

BK

BK

BK

BK

LED2

LED1

Option

Wireless
remote
cotroller

ThI-R

ThI-A

XR5

XR3

XR1

Receiver
amp.

SW

BK

BK

BK

BK

BK

BK

XR4

XR2

FDKN-C

11.3 ELECTRICAL DATA

11.3.1 Electrical wiring


Models FDKN208CEN-S, 208CEP-S

499

PK

WH

Y/GN

CC

WH
4

CM

BK

WH

BL

Cc
CFO
CH
CM
CnA~W
F
FMI
FMO
LED1
LED2
LM
NR
SV
SW
SW3
TB

Mark

SV

CnM

OR

BR

Parts name

CFO

CnP

CH

CnP

52C

RD

WH

Capacitor for CM
Capacitor for FMO
Crankcase heater
Compressor motor
Connector
Fuse
Fan motor (Indoor unit)
Fan motor (Outdoor unit)
Indication lamp (Green-Run)
Indication lamp (Yellow-Timer/Check)
Louver motor
Surge suppressor
Solenoid coil (for control)
Back up switch (ON/OFF)
Change over switch
Terminal block ( mark)

OR

CnM
CnM
OR OR
FMO
(49FO)

BK

52C

23Td

Meaning of marks

5IC

WH

RD

RD

RD

ThI-A
ThI-R
Val
49FI
49FO
23Td
51C
52C
52X5
v

Mark

NR

2
3

2
3

Parts name

BK

TB
1

TB
1
RD

Y/GN

BK

WH

Thermistor
Thermistor
Varistor
Internal thermostat for FMI
Internal thermostat for FMO
Thermostat
Overcurrent relay for CM
Magnetic contactor for CM
Auxiliary relay
Terminal (F)
Connector

52C

RD
WH

Y/GN

F (3.15A)
52X5

BK
BL
BR
GR
OR
PK
RD
WH
Y
Y/GN

Mark

Color mark

CnF

Indoor Unit

Color

52X5

FMI
(49FI)

Black
Blue
Brown
Gray
Orange
Pink
Red
White
Yellow
Yellow/Green

RD

Outdoor Unit

Y
BL
WH

RD

BK

BL BK

WH

BL

WH

BL

CnJ

LM

BR
OR
RD

TB
RD
L

BK

WH

WH

WH
BK

IC10

ON 1 2 3 4
OFF

SW3

SW

CnQ Test

220/240V

Printed wiring board

VaI
CnT
CnH
CnN
CnC

500
CnA

Power source
FDKN258CEN-S
1 Phase 220/240V 50Hz
FDKN258CEP-S
1 Phase 220V 60Hz

BK

BK

BK

BK

BK

BK

BK

BK

BK

BK

Option

Wireless
remote
cotroller

LED2

LED1

ThI-R

ThI-A

XR5

XR3

XR1

Receiver
amp.

XR4

XR2

FDKN-C

Models FDKN258CEN-S, 258CEP-S

PK

BL

Y/GN

CC

BL

CM
(49C)

BK

52C

Cc
CFO
CM
CnA~W
F
FMI
FMO
LED1
LED2
LM
NR
SW
SW3
TB

Mark

OR

OR

CF0

Capacitor for CM
Capacitor for FMO
Compressor motor
Connector
Fuse
Fan motor (Indoor unit)
Fan motor (Outdoor unit)
Indication lamp (Green-Run)
Indication lamp (Yellow-Timer/Check)
Louver motor
Surge suppressor
Back up switch (ON/OFF)
Change over switch
Terminal block ( mark)

Parts name

CnM

OR

OR

CnM

CnM

NR

FM0
(49F0)

Meaning of marks

WH

WH

WH

WH

RD

RD

RD

ThI-A
ThI-R
Trl
Val
49FI
49FO
49C
52C
52X5
v

Mark

2
3

TB2 TB
1
1

Parts name

Y/GN

BK

WH

RD

Y/GN

BK

WH

RD

Thermistor
Thermistor
Transformer
Varistor
Internal thermostat for FMI
Internal thermostat for FMO
Internal thermostat for CM
Magnetic contactor for CM
Auxiliary relay
Terminal (F)
Connector

F(3.15A)

52C

WH
BK

BK

BK

BK
BL
BR
GR
OR
PK
RD
WH
Y
Y/GN

Mark

Color mark

52X5

CnF

Indoor Unit

Black
Blue
Brown
Gray
Orange
Pink
Red
White
Yellow
Yellow/Green

Color

52X5

FMI
(49FI)

BK

WH

Outdoor Unit

RD
Y/GN

RD

Y/GN

WH
Y
BL

BL

Y/GN

WH

WH

CnJ

LM

BR
OR
RD

VaI

TrI
220/240V

14V

16V

ON 1 2 3 4
OFF

SW3

CnQ Test

CnW1 CnW2

BK BR

BK RD

CnT
CnN CnH
CnC
CnL
CnA

Power source
FDKN208CEN
1 Phase 220/240V 50Hz
FDKN208CEP
1 Phase 220V 60Hz

BK

BK

BK

BK

LED2

LED1

Option

Wireless
remote
cotroller

ThI-R

ThI-A

XR5

XR3

XR1

Receiver
amp.

SW

BK

BK

BK

BK

BK

BK

XR4

XR2

FDKN-C

Models FDKN208CEN, 208CEP

501

PK

BL

Y/GN

CC

BL

CM
(49C)

BK

52C

Cc
CFO
CM
CnA~W
F
FMI
FMO
LED1
LED2
LM
NR
SW
SW3
TB

Mark

FM0
(49F0)

OR

OR

CF0

Parts name

CnM

OR

OR

CnM

CnM

NR

Capacitor for CM
Capacitor for FMO
Compressor motor
Connector
Fuse
Fan motor (Indoor unit)
Fan motor (Outdoor unit)
Indication lamp (Green-Run)
Indication lamp (Yellow-Timer/Check)
Louver motor
Surge suppressor
Back up switch (ON/OFF)
Change over switch
Terminal block ( mark)

Meaning of marks

WH

WH

WH

WH

RD

RD

RD

52C

ThI-A
ThI-R
Val
49FI
49FO
49C
52C
52X5
v

Mark

2
3

TB2 TB
1
1

Parts name

Y/GN

BK

WH

RD

RD

Y/GN

BK

WH

Thermistor
Thermistor
Varistor
Internal thermostat for FMI
Internal thermostat for FMO
Internal thermostat for CM
Magnetic contactor for CM
Auxiliary relay
Terminal (F)
Connector

F(3.15A)

52X5

BK
BL
BR
GR
OR
PK
RD
WH
Y
Y/GN

Mark

Color mark

Indoor Unit

CnF

Black
Blue
Brown
Gray
Orange
Pink
Red
White
Yellow
Yellow/Green

52X5

FMI
(49FI)

Color

RD

WH

Outdoor Unit

WH
BK

BK

BK

Y
BL
WH

RD

Y/GN

CnJ

LM

BR
OR
RD

BL

Y/GN

WH

WH

IC10

ON 1 2 3 4
OFF

SW3

SW

CnQ Test

220/240V

Printed wiring board

VaI

CnT
CnH
CnN
CnC

502
CnA

Power source
FDKN258CEN, 308CEN
1 Phase 220/240V 50Hz
FDKN258CEP, 308CEP
1 Phase 220V 60Hz

BK

BK

BK

BK

BK

BK

BK

BK

BK

BK

Option

Wireless
remote
cotroller

LED2

LED1

ThI-R

ThI-A

XR5

XR3

XR1

Receiver
amp.

XR4

XR2

FDKN-C

Models FDKN258CEN, 258CEP, 308CEN, 308CEP

PK

BL

L3

T3

T1

CM
(49C)

T2

52C

NR

CFO
CM
CnA~W
F
FMI
FMO
LED1
LED2
LM
NR
SW
SW3
TB

Mark

OR

OR

CF0

Capacitor for FMO


Compressor motor
Connector
Fuse
Fan motor (Indoor unit)
Fan motor (Outdoor unit)
Indication lamp (Green-Run)
Indication lamp (Yellow-Timer/Check)
Louver motor
Surge suppressor
Back up switch (ON/OFF)
Change over switch
Terminal block ( mark)

Parts name

CnM

OR

OR

CnM

CnM

FM0
(49F0)

Meaning of marks

BK

BL

WH

RD

Y/GN

L2

Y/GN

BL

BL

BL

52C

ThI-A
ThI-R
Val
49FI
49FO
49C
52C
52X5
v

Mark

2
3

TB2 TB
1
1

Parts name

Y/GN

BK

WH

RD
RD

Y/GN

BK

WH

Thermistor
Thermistor
Varistor
Internal thermostat for FMI
Internal thermostat for FMO
Internal thermostat for CM
Magnetic contactor for CM
Auxiliary relay
Terminal (F)
Connector

F(3.15A)
52X5

BK
BL
BR
GR
OR
PK
RD
WH
Y
Y/GN

Mark

Color mark

CnF

Indoor Unit

Black
Blue
Brown
Gray
Orange
Pink
Red
White
Yellow
Yellow/Green

52X5

FMI
(49FI)

Color

RD

WH

Outdoor Unit

WH
BK

RD

RD

Y
BL
WH

WH

RD

WH

WH

Y/GN

BK

BK

CnJ

LM

BR
OR
RD

L1

WH

IC10

ON 1 2 3 4
OFF

SW3

SW

CnQ Test

220/240V

Printed wiring board

VaI
CnT
CnH
CnN
CnC

BK

BK

BK

BK

BK

BK

BK

BK

BK

BK

Option

Wireless
remote
cotroller

LED2

LED1

ThI-R

ThI-A

XR5

XR3

XR1

Receiver
amp.

XR4

XR2

Model

CnA

Power source
3 Phase 380-415V 50Hz / 380V 60Hz

FDKN-C

FDKN308CES

503

PK

BL

FDKN-C
11.4 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER
Except for function relating to heating, same as the unit for FDT(N) heat pump type. See page 241.

11.5 APPLICATION DATA


The application data for the cooling only models are similar to those for the heat pump models. (See page 464.)

11.6 MAINTENANCE DATA


Same as the cooling/heating equipment for FDT(N) heat pump type. Refer to page 271.

504