Vous êtes sur la page 1sur 282

Palestine

Polytechnic
University
Collage of Engineering and Technology
Department of Civil and Architectural Engineering

Reinforced
Concrete
II
Dr. Nasr Younis Abboushi

2013-2014

Reinforced Concrete II

Dr. Nasr Abboushi

CONTENTS
CHAPTER 8

CHAPTER 9

ONE-WAY SLABS

185

8.1

Types of slabs

185

8.2

Analysis of continuous beams and frames

187

8.3

Analysis and design of one-way solid slabs. ACI code limitations.

191

8.4

Minimum reinforcement ratio

195

8.5

Temperature and shrinkage reinforcement

196

8.6

Reinforcement details

197

8.7

One-way joist floors and one-way ribbed slabs

212

8.8

Design of one-way ribbed slab

216

TWO-WAY SLABS

234

9.1

Introduction

234

9.2

Types of two-way slabs

234

9.3

Economical choice of concrete floor systems

237

9.4

Minimum thickness of two-way slabs

238

9.5

Slab reinforcement requirements

241

9.6

Shear strength of two-way slabs

243

9.6.1

Two-Way Slabs Supported on Beams

244

9.6.2

Two-Way Slabs Without Beams

244

9.6.3

Tributary Areas for Shear in Two-Way Slabs

247

9.6.4

Shear Reinforcement in Two-Way Slabs Without Beams

247

9.7

Analysis and design of two-way slabs

249

9.8

Slab analysis by the coefficient method

250

9.9

Slab analysis by the direct design method (DDM).

294

9.9.1

Limitations on the Use of the Direct-Design Method

294

9.9.2

Column and middle strips

295

9.9.3

Total Static Moment at Factored Loads

296

9.9.4

Assignment of positive and negative moments

296

9.9.5

Lateral Distribution of Moments (between Column Strips


and Middle Strips)

298

II - ii

Reinforced Concrete II

CHAPTER 10

CHAPTER 11

Dr. Nasr Abboushi

9.10

Slab analysis by the equivalent frame method (EFM)

302

9.11

Shear design in flat plates

305

STAIRS

317

10.1

Introduction

317

10.2

Types of stairs

318

10.3

Slab type stairs. Structural system

327

FOOTINGS AND FOUNDATIONS

341

11.1

Introduction

341

11.2

Types of footings

342

11.3

Distribution of soil pressure. Gross and net soil pressures

343

11.4

Design considerations

346

11.4.1

Size of footings

346

11.4.2

One-way shear (Beam shear)

346

11.4.3

Two-way shear (Punching shear)

347

11.4.4

Flexural strength and footing reinforcement

348

11.4.5

Transfer of Load from Column to Footing

350

11.4.6

Bearing Strength

351

11.5

Spread (isolated) footings

353

11.6

Strip (wall) footings

360

11.7

Footings under eccentric column loads

363

11.8

Combined footings

372

11.9

Continuous footings

380

11.10 Mat foundations

386

CHAPTER 12 DEVELOPMENT, ANCHORAGE, AND SPLICING OF REINFORCEMENT

393

12.1

Introduction

393

12.2

Flexural bond

393

12.3

Mechanism of bond transfer

394

II - iii

Reinforced Concrete II

Dr. Nasr Abboushi

12.4

Development length

396

12.5

Hooked anchorages

405

12.6

Bar cutoffs and development of bars in flexural members

412

12.7

Development of positive moment reinforcement

417

12.8

Development of negative moment reinforcement

421

12.9

Reinforcement continuity and structural integrity requirements

425

12.10 Splices of reinforcement

II - iv

446

Reinforced Concrete II

CHAPTER 8

Dr. Nasr Abboushi

ONE-WAY SLABS

8.1 TYPES OF SLABS


Structural concrete slabs are constructed to provide flat surfaces, usually horizontal, in
building floors, roofs, bridges, and other types of structures. The slab may be supported by
walls, by reinforced concrete beams usually cast monolithically with the slab, by structural
steel beams, by columns, or by the ground. The depth of a slab is usually very small
compared to its span.

Structural concrete slabs in buildings may be classified as follows:


1. One-way stabs: If a slab is supported on two opposite sides only, it will bend or
deflect in a direction perpendicular to the supported edges. The structural action is one way,
and the loads are carried by the slab in the deflected short direction. This type of slab is
called a one-way slab.
185

Reinforced Concrete II

Dr. Nasr Abboushi

If the slab is supported on four sides and the ratio


of the long side to the short side is equal to or
greater than (
), most of
the load (about
or more) is carried in the
short direction, and one-way action is considered
for all practical purposes. If the slab is made of
reinforced concrete with no voids, then it is called
a one-way solid slab.
2. One-way joist floor system: This type of
slab is also called a ribbed slab. It consists of a
floor slab, usually
thick, supported
by reinforced concrete ribs (or joists). The ribs are usually tapered and are uniformly spaced
at distances that do not exceed
. The ribs are supported on girders that rest on
columns. The spaces between the ribs may be formed using removable steel or fiberglass
186

Reinforced Concrete II

Dr. Nasr Abboushi

form fillers (pans), which may be used many times. In some ribbed slabs, the spaces
between ribs may be filled with permanent fillers to provide a horizontal slab.

3. Two-way floor systems: When the slab is supported on four sides and the ratio of
the long side to the short side is less than (
), the slab will deflect in
double curvature in both directions. The floor load is carried in two directions to the four
beams surrounding the slab. Other types of two-way floor systems are flat plate floors, flat
slabs, and waffle slabs. This chapter deals only with one-way floor systems.

8.2 ANALYSIS OF CONTINUOUS BEAMS AND FRAMES.


In reinforced concrete structures, as much of the concrete as is practical is placed in one
single operation. Reinforcing steel is not terminated at the ends of a member but is
extended through the joints into adjacent members. At construction joints, special care is
taken to bond the new concrete to the old by carefully cleaning the latter, by extending the
reinforcement through the joint, and by other means. As a result, reinforced concrete
structures usually represent monolithic, or continuous, units. A load applied at one location
causes deformation and stress at all other locations. Even in precast concrete construction,
which resembles steel construction in that individual members are brought to the job site
and joined in the field, connections are often designed to provide for the transfer of moment
as well as shear and axial load, producing at least partial continuity.

187

Reinforced Concrete II

Dr. Nasr Abboushi

In statically determinate structures, such as simple-span beams, the deflected shape and
the moments and shears depend only on the type and magnitude of the loads and the
dimensions of the member. In contrast, inspection of the statically indeterminate structures
shows that the deflection curve of any member depends not only on the loads but also on
the joint rotations, whose magnitudes in turn depend on the distortion of adjacent, rigidly
connected members.
Continuous beams and frames can be analyzed using approximate methods or computer
programs, which are available commercially. Other methods, such as the displacement and
force methods of analysis based on the calculation of the stiffness and flexibility matrices,
may also be adopted. Slope deflection and moment-distribution methods may also be used.
These methods are explained in books dealing with the structural analysis of beams and
frames. However, the ACI Code, Section 8.3, gives approximate coefficients for calculating
the bending moments and shear forces in continuous beams and slabs. These coefficients
were given in Section 8.3 of this Chapter. The moments obtained using the ACI coefficients
will be somewhat larger than those arrived at by exact analysis. The limitations stated in the
use of these coefficients must be met.
In the structural analysis of continuous beams, the span length is taken from center to
center of the supports, which are treated as knife-edge supports. In practice, the supports
are always made wide enough to take the loads transmitted by the beam, usually the
moments acting at the face of supports. To calculate the design moment at the face of the
support, it is quite reasonable to deduct a moment equal to
from the factored
moment at the centerline of the support, where is the factored shear and is the column
width.
According to ACI Code Section 8.9 Span Length:
8.9.1 Span length of members not built integrally with supports shall be considered as the
clear span plus the depth of the member, but need not exceed distance between
centers of supports.
8.9.2 In analysis of frames or continuous construction for determination of moments,
span length shall be taken as the distance center-to-center of supports.
8.9.3 For beams built integrally with supports, design on the basis of moments at faces of
support shall be permitted.
8.9.4 It shall be permitted to analyze solid or ribbed slabs built integrally with supports,
with clear spans not more than 3 m, as continuous slabs on knife edge supports
with spans equal to the clear spans of the slab and width of beams otherwise
neglected.
The individual members of a structural frame must be designed for the worst combination of
loads that can reasonably be expected to occur during its useful life. Internal moments,
shears, and thrusts are brought about by the combined effect of dead and live loads, plus
other loads, such as wind and earthquake. While dead loads are constant, live loads such as
floor loads from human occupancy can be placed in various ways, some of which will result
in larger effects than others.
188

Reinforced Concrete II

Dr. Nasr Abboushi

For structural analysis of continuous beam or rib to obtain the shear and moment diagrams,
it shall be permitted according to ACI code, 8.11.2, to assume that the arrangement of live
load is limited to combinations of:
a. Factored dead load on all spans with full factored live load on two adjacent
spans; and
b. Factored dead load on all spans with full factored live load on alternate spans.

Span 1

Span2

Span 3

Load Case 1: ACI-8.11.2-a

LL
DL

Load Case 2: ACI-8.11.2-a

LL
DL

Load Case 3: ACI-8.11.2-b

LL

LL

DL

Load Case 4: ACI-8.11.2-b

LL
DL
189

Reinforced Concrete II

Dr. Nasr Abboushi

From each case we get the Maximum moment:


Maximum negative moment from load cases 1+2 (ACI-8.11.2-a)
Maximum positive moment from load cases 3+4 (ACI-8.11.2-b)
Envelope moment diagram from all possible load cases.

Moment Diagram from

Load Case 1

Moment Diagram from

Load Case 2

Moment Diagram from

Load Case 3

Moment Diagram from

Load Case 4

190

Reinforced Concrete II

Dr. Nasr Abboushi

Moment Diagrams of all Load cases

Envelope Moment Diagram from all Load cases

8.3 ANALYSIS AND DESIGN OF ONE-WAY SOLID SLABS. ACI CODE LIMITATIONS.
If the concrete slab is cast in one uniform thickness without any type of voids, it can be
referred to as a solid slab. In a one-way stab nearly all the loading is transferred in the short
direction, and the slab may be treated as a beam. A unit strip of slab, usually 1 m at right
angles to the supporting girders, is considered a rectangular beam. The beam has a unit
width with a depth equal to the thickness of the slab and a span length equal to the distance
between the supports. A one-way slab thus consists of a series of rectangular beams placed
side by side.
If the slab is one span only and rests freely on its supports, the maximum positive moment
for a uniformly distributed load of
is
, where is the span length
between the supports. If the same slab is built monolithically with the supporting beams or
is continuous over several supports, the positive and negative moments are calculated by
structural analysis or by moment coefficients as for continuous beams. The ACI Code,
Section 8.3, permits the use of moment and shear coefficients in the case of two or more
approximately equal spans.
The maximum positive and negative moments and shears are computed from the following
expressions:
191

Reinforced Concrete II

where
193).

and

Dr. Nasr Abboushi

are moment and shear coefficients given in table below and figure (page

For all positive midspan moments, all shears and the negative moment at exterior
supports, , is for the span under consideration. For the negative moment at interior
supports, , shall be taken as ( ) as defined in the figure above.

192

Reinforced Concrete II

Dr. Nasr Abboushi

193

Reinforced Concrete II

Dr. Nasr Abboushi

The conditions under which the moment coefficients for continuous beams and slabs should
be used can be summarized as follows:
1. Spans are approximately equal: Longer span
(shorter span).
2. Loads are uniformly distributed.
3. The ratio (live load/dead load) is less than or equal to .
4. For slabs with spans less than or equal to
, negative bending moment at
face of all supports is ( )
5. For an unrestrained discontinuous end, the coefficient is
(

at end support and

) at midspan.

6. Shear force at C is

and at the face of all other support is ( )

7. The members are prismatic.


When these conditions are not satisfied, structural analysis is required. In structural analysis,
the negative bending moments at the centers of the supports are calculated. The value that
may be considered in the design is the negative moment at the face of the support, ACI
8.9.2, 8.9.3.
The following limitations are specified by the ACI code:
Atypical imaginary strip 1m wide is assumed.
The minimum thickness of one-way slabs using grade 420 steel can be defined
according to the ACI Code, 9.5.2.1, Table 9.5a, for solid slabs and for beams or ribbed
one-way slabs .
ACI 9.5.2.1 Minimum thickness stipulated in Table 9.5(a) shall apply for one-way
construction not supporting or attached to partitions or other construction likely to be
damaged by large deflections, unless computation of deflection indicates a lesser thickness
can be used without adverse effects.

194

Reinforced Concrete II

Dr. Nasr Abboushi

Deflection is to be checked when the slab supports are attached to construction


likely to be damaged by large deflections. Deflection limits are set by the ACI Code,
Table 9.5b.
ACI 9.5.2.2 Where deflections are to be computed, deflections that occur immediately on
application of load shall be computed by usual methods or formulas for elastic deflections,
considering effects of cracking and reinforcement on member stiffness.

It is preferable to choose slab depth to the nearest


.
Shear should be checked, although it does not usually control.
Concrete cover in slabs shall not be less than
at surfaces not exposed to
weather or ground. In this case,

In structural slabs of uniform thickness, the minimum amount of reinforcement in


the direction of the span shall not be less than that required for shrinkage and
temperature reinforcement (ACI Code, Section 7.12).
The principal reinforcement shall be spaced not farther apart than three times the
slab thickness nor more than
(ACI Code, Section 7.6.5).
Straight-bar systems may be used in both tops and bottoms of continuous slabs. An
alternative bar system of straight and bent (trussed) bars placed alternately may also
be used.
In addition to main reinforcement, steel bars at right angles to the main must be provided. This additional steel is called secondary, distribution, shrinkage, or
temperature reinforcement.
8.4 MINIMUM REINFORCEMENT RATIO.

For structural slabs and of uniform thickness,


in the direction of the span shall be the
same as that required by 7.12.2.1 for temperature and shrinkage reinforcement (see section
8.5).

195

Reinforced Concrete II

Dr. Nasr Abboushi

Maximum spacing of this reinforcement shall not exceed three times the thickness, nor
.
To limit the widths of flexural cracks in beams and slabs, ACI Code Section 10.6.4 defines
upper limit on the center-to-center spacing between bars in the layer of reinforcement
closest to the tension face of a member. The spacing limit is:
(

but
(

where
is the least distance from
surface of reinforcement to the tension
face. It shall be permitted to take as
.

8.5 TEMPERATURE AND SHRINKAGE REINFORCEMENT.


Concrete shrinks as the cement paste hardens, and a certain amount of shrinkage is usually
anticipated. If a slab is left to move freely on its supports, it can contract to accommodate
the shrinkage. However, slabs and other members are joined rigidly to other parts of the
structure, causing a certain degree of restraint at the ends. This results in tension stresses
known as shrinkage stresses. A decrease in temperature and shrinkage stresses is likely to
cause hairline cracks. Reinforcement is placed in the slab to counteract contraction and
distribute the cracks uniformly. As the concrete shrinks, the steel bars are subjected to
compression.
Reinforcement for shrinkage and temperature stresses normal to the principal
reinforcement should be provided in a structural slab in which the principal reinforcement
extends in one direction only.
The ACI Code, Section 7.12.2, specifies that: area of shrinkage and temperature
reinforcement shall provide at least the following ratios of reinforcement area to gross
concrete area, but not less than
:
For slabs in which grade 280 (
) or 350 (
) deformed bars
are used,
.
For slabs in which grade 420 (
) deformed bars or welded bars or
welded wire fabric are used,
.
For Slabs where reinforcement with yield stress exceeding
measured at a

yield strain of
percent is used,

Shrinkage and temperature reinforcement shall be spaced not farther apart than five times
the slab thickness, nor farther apart than
.
196

Reinforced Concrete II

Dr. Nasr Abboushi

For temperature and shrinkage reinforcement, the whole concrete depth


shrinkage shall be used to calculate the steel area.

exposed to

8.6 REINFORCEMENT DETAILS.


In continuous one-way slabs, the steel area of the main reinforcement is calculated for all
critical sections, at midspans, and at supports. The choice of bar diameter and detailing
depends mainly on the steel areas, spacing requirements, and development length. Two bar
systems may be adopted.
In the straight-bar system: straight bars are used for top and bottom reinforcement
in all spans. The time and cost to produce straight bars is less than that required to
produce bent bars; thus, the straight-bar system is widely used in construction.
In the bent-bar, or trussed, system: straight and bent bars are placed alternately in
the floor slab. The location of bent points should be checked for flexural, shear, and
development length requirements. For normal loading in buildings, the bar details at
the end and interior spans of one-way solid slabs may be adopted as shown in
figures.

197

Reinforced Concrete II

Dr. Nasr Abboushi

198

Reinforced Concrete II

Dr. Nasr Abboushi

199

Reinforced Concrete II

Dr. Nasr Abboushi

Example:
Design a simply supported one-way solid slab, span of
(
). Dead Load own weight only.

, subjected to service live load


and
.

Solution:
Minimum thickness (deflection requirements). For simply supported one-way solid
slab:

for main reinforcement.

Cover

Loads calculation:

Assume bar diameter

Provide
Use

then
200

Reinforced Concrete II

Dr. Nasr Abboushi

Take

Step ( ) is the smallest of:


1.

2.
(

Take

Step (
1.

) is the smallest of:

2.

Example:
The cross-section of a continuous one-way solid slab in a building is shown below. The slabs
are supported by beams that span
between simple supports. The dead load on the
slabs is that due to self-weight plus
; the live load is
. Design the
continuous slab and draw a detailed section. Given:
and
.
201

Reinforced Concrete II

Dr. Nasr Abboushi

Solution:
Minimum thickness (deflection requirements).
(

Take slab thickness


Assume bar diameter

for main reinforcement.

Loads calculation:

202

Reinforced Concrete II

Dr. Nasr Abboushi

Check whether thickness is adequate for shear:

- for shear.

The thickness of the slab is adequate enough.


Even, if

for solid slabs, the thickness of the slab will be enough.

Factored moments at sections A, B, C, D, E:


For the negative moment at interior supports,
Here
(
)

, shall be taken as

Location

A
B
C

Slab Design for the positive moments:


Midspan section B:

).

)
203

Reinforced Concrete II

Use

Dr. Nasr Abboushi

then

Take

Step ( ) is the smallest of:


1.
2.

Midspan section E:

Use

then

Take

Slab Design for the negative moments:


Note that the second support has two values of moments by analysis, at section C and
section D. In construction, the provided reinforcement will be the same bar diameters on
opposite sides of the support, so the design may be done for the maximum moment of the
two moments at C and D (Only one design for Support section C).
204

Reinforced Concrete II

Dr. Nasr Abboushi

Support section C:

Assume bar diameter

Use

for main reinforcement.

then

Take

Support section D (interior D supports):

Assume bar diameter

Use

for main reinforcement.

then

Take

205

Reinforced Concrete II

Dr. Nasr Abboushi

Support section A:

Assume bar diameter

for main reinforcement.

Provide
Use

then

Take

Temperature and shrinkage reinforcement.


(

Take

Step (

) is the smallest of:

1.
2.

Required

Location

3.3

3.3

C and first
interior D

3.3

Interior D

3.3

3.3

Temperature and shrinkage


reinforcement

206

Provided

Reinforcement

Reinforced Concrete II

Dr. Nasr Abboushi

Example:
Design the one-way solid slab, which plan is shown below. The dead load on the slabs is that
due to self-weight plus weight of:
Tiles,
.
Mortar,
.
Sand,
.
Plaster,
.
Partitions,
.
The live load is
.
Given:
and
.

Solution:

Minimum

thickness

(deflection requirements).
From the maximum span
length

for

one-end

continuous, we get

Take slab thickness


Assume bar diameter

for main reinforcement.

Loads calculation:
207

Reinforced Concrete II

Material

Dr. Nasr Abboushi

Quality Density

Tiles
mortar
Sand
Reinforced Concrete solid slab
Plaster
Partitions
Total Dead Load

Dead Load for 1 m strip of slab


Live Load for 1 m strip of slab

208

Reinforced Concrete II

Dr. Nasr Abboushi

According to ACI 8.9.2 In analysis of frames or continuous construction for determination


of moments, span length shall be taken as the distance center-to-center of supports.
According to ACI 8.9.3 For beams built integrally with supports, design on the basis of
moments at faces of support shall be permitted.
Check whether thickness is adequate for shear:

- for shear.

The thickness of the slab is adequate enough.


209

Reinforced Concrete II

Dr. Nasr Abboushi

Slab Design for the negative moment:

Assume bar diameter

for main reinforcement.

Use

then

Take

Step ( ) is the smallest of:

1.
2.

Check for strain (tension-controlled section -

210

):

Reinforced Concrete II

Dr. Nasr Abboushi

Slab Design for the positive moments:

Assume bar diameter

Use

for main reinforcement.

then

Take

Assume bar diameter

Use

for main reinforcement.

then

Take

For both positive moment designs

211

Reinforced Concrete II

Dr. Nasr Abboushi

Temperature and shrinkage reinforcement.


(

Take

Step (

) is the smallest of:

1.
2.

8.7

ONE-WAY JOIST FLOORS AND ONE-WAY RIBBED SLABS.

A one-way joist floor system consists of hollow slabs with a total depth greater than that of
solid slabs. The system is most economical for buildings where superimposed loads are small
and spans are relatively large, such as schools, hospitals, and hotels. The concrete in the
tension zone is ineffective; therefore, this area is left open between ribs or filled with
lightweight material to reduce the self-weight of the slab.
212

Reinforced Concrete II

Dr. Nasr Abboushi

The design procedure and requirements of ribbed slabs follow the same steps as those for
rectangular and T-sections explained in Chapter 4. The following points apply to design of
one-way ribbed slabs:
1. Ribs are usually tapered and uniformly spaced at about
. Voids are
usually formed by using pans (molds)
wide and
deep,
depending on the design requirement. The standard increment in depth is 50 mm.
2. The ribs shall not be less than
wide and must have a depth of not more than
times the width. Clear spacing between ribs shall not exceed
(ACI Code,
Section 8.13).
213

Reinforced Concrete II

Dr. Nasr Abboushi

3. Shear strength, , provided by concrete for the ribs may be taken


greater than
that for beams. This is mainly due to the interaction between the slab and the closely
spaced ribs (ACI Code, Section 8.13.8).
4. The thickness of the slab on top of the ribs is usually
and contains
minimum reinforcement (shrinkage reinforcement). This thickness over permanent
fillers shall not be less than ( ) of the clear span between ribs or

(ACI Code,

Section 8.13.5.2). When removable forms or fillers are used slab thickness shall be
not less than ( ) of the clear distance between ribs, nor less than

. (ACI

Code, Section 8.13.6.1)


5. The ACI coefficients for calculating moments in continuous slabs can be used for
continuous ribbed slab design.
If the live load on the ribbed slab is less than
and the span of ribs exceeds
,
a secondary transverse rib (distribution rib) should be provided at midspan (its direction is
perpendicular to the direction of main ribs) and reinforced with the same amount of steel as
the main ribs. Its top reinforcement shall not be less than half of the main reinforcement in
the tension zone. These transverse ribs act as floor stiffeners. If the live load exceeds
and the span of ribs varies between and
, one traverse rib must be provided,
as indicated before. If the span exceeds
, at least two transverse ribs at one-third span
must be provided with reinforcement, as explained before.

214

Reinforced Concrete II

Dr. Nasr Abboushi

215

Reinforced Concrete II

Dr. Nasr Abboushi

Reinforcement for the joists usually consists of two bar in the positive bending region, with
one bar discontinued where no longer needed or bent up to provide a part of the negative
steel requirement over supporting girder. According to ACI Code section 7.13.2 at least one
bottom bar must be continuous over the support, or at non continuous supports, terminated
in a standard hook, as a measure to improve structural integrity in the event of major
structural damage.
The minimum thickness of beams or ribbed one way slabs depending on the support
conditions can be determined according to ACI Code 9.5.2. (see table 9.5(a), page 194).
8.8 DESIGN OF ONE-WAY RIBBED SLAB.
For the ribbed slab plan with section as shown below:
Determine the total slab thickness.
Design the topping slab.
Design the rib for flexure and shear, the envelope moment and shear diagrams are
shown.
Design the beams B1, B2 for flexure and shear, the envelope moment and shear
diagrams are shown.
Take the material's density from the table below.

216

Reinforced Concrete II

Dr. Nasr Abboushi

Quality Density

Material
Tiles
mortar
Sand
Reinforced Concrete
Hollow Block
Plaster
Partitions

Compressive strength of concrete


Yield strength of steel,
Live Load,

.
217

Reinforced Concrete II

Dr. Nasr Abboushi

Solution:

800 mm

Rib 2

Beam 1

Beam 2

Beam 3

Beam 4

Beam 5

Beam 6

800 mm

Rib 1

800 mm

800 mm

800 mm

218

800 mm

Reinforced Concrete II

Dr. Nasr Abboushi

Minimum thickness (deflection requirements).


There are two groups of ribs and beams (Rib 1; Rib 2; Beam 1, 2, 3, 4; Beam 5, 6).
The thickness of the one-way ribbed slab without drop beams can be obtained according to
ACI code, table 9.5 (a).
The maximum span length for one-end continuous (for ribs):
then

The maximum span length for both-ends continuous (for ribs):

then

The maximum span length for one-end continuous (for Beams):

then

The maximum span length for both-ends continuous (for Beams):

then

The minimum ribbed slab thickness will be


Take slab thickness
(

Topping Design.

Topping in One way ribbed slab can be


considered as a strip of 1 meter width and
span of hollow block length with both end
fixed in the ribs.
Dead Load calculations:

Dead Load from:

Tiles
Mortar
Coarse Sand
Topping
Interior Partitions

Live Load calculations:

Total Factored Load:

219

Reinforced Concrete II

Dr. Nasr Abboushi

Strength condition, where

where

for plain concrete.

(ACI 22.5.1, Equation 22-2)

for rectangular section of the slab:

NO Reinforcement is required by analysis. According to ACI 10.5.4., provide

for slabs

as shrinkage and temperature reinforcement.


According to ACI 7.12.2.1,

Try bars

8 with

Take

in both directions.

Step ( ) is the smallest of:


1.
2.

(
Take

in both directions.

From the Geometry of T-section:

220

h= 250 mm

Load Calculations for Rib 1:

t = 80 mm

From practical concederation, the secondary reinforcement parallel to the ribs shall be
placed in the slab and spaced at distances not more than half of the spacings between ribs
(usually two bars upon each
width block).

Reinforced Concrete II

Dead Load calculations:

Live Load calculations:

Dr. Nasr Abboushi

Tiles

Mortar

Coarse Sand

Topping

RC Rib

Hollow Block

Plaster

Interior Partitions

Dead Load / rib:


Live Load /rib:

Dead Load from:

The Effective Flange width (


is the smallest of:

) According to ACI 8.12.2 (see page 220):

( )

( )
( )
Take

Structural Analysis of Rib 1. The envelope shear and moment diagrams (for all load
combinations).
Using the structural analysis and design programs, we obtain the Envelope Moment diagram
for Rib1.

221

Reinforced Concrete II

Dr. Nasr Abboushi

222

Reinforced Concrete II

Dr. Nasr Abboushi

Design of Rib 1 for positive moments.


Assume bar diameter
for main positive reinforcement.

The maximum positive moment in all spans of Rib 1


Check if

The section will be designed as rectangular section with

Check for

Use

with

Check for strain:

Usually, no reinforcement less than

can be used. So, for all spans with positive

moments equal or less than

, use
223

for each rib span.

Reinforced Concrete II

Dr. Nasr Abboushi

Design of Rib 1 for negative moments.


Assume bar diameter
for main positive reinforcement.

According to ACI 8.9.3 for beams built integrally with supports, design on the basis of
moments at faces of support shall be permitted.
The maximum negative moment at the face of support

Check for

Use

with

Check for strain:

Usually, no reinforcement less than


moments equal or less than

)
can be used. So, for all supports with negative
, use

for each rib support.

Design of Rib 1 for shear.


The maximum shear force at the distance

from the face of support

Shear strength, , provided by concrete for the ribs may be taken


greater than that for
beams. This is mainly due to the interaction between the slab and the closely spaced ribs
(ACI Code, Section 8.13.8).
224

Reinforced Concrete II

Dr. Nasr Abboushi

Minimum shear reinforcement is required except for concrete joist construction. So, No
shear reinforcement is provided.

Load calculations for Beam 4:


The distributed Dead and Live loads acting upon the Beam 4 can be defined from the
support reactions of the rib 1 and rib 2.

Beam 4

Dead Load calculations:


The maximum support reaction (factored) from Dead Loads for rib1 upon beam 4 is
. The distributed Dead Load from the Rib 1 on Beam 4:

225

Reinforced Concrete II

Dr. Nasr Abboushi

Assume the width of the beam


, then the own weight of the beam and the weight
of the floor layers within the beam width can be calculated:
Dead Load from:

Tiles
Mortar
Coarse Sand
RC Beam
Plaster
Interior Partitions

The total factored Dead Load:


Live Load calculations:
The maximum support reaction (factored) from Live Loads for rib1 upon beam 4 is

The distributed Live Load from the Rib 1 on Beam 4:

The Live Load within the beam width (

) can be calculated:

The total factored Live Load:


Important NOTE:
The dead and live loads acting within the beam width have been calculated twice actually.
That because the support reactions of ribs from the dead and live loads acting over the ribs
were calculated for full span of the ribs, measured center to center, which include the whole
beam width.
More accurately calculations to determine the loads on the beam could be done by taking
the loads that transfer from the rib to the beam which could be calculated as the sum of
shear values of the ribs at the face of support (beam) from each side and then adding the
dead and live loads acting directly on the beam within the beam width.
From the next envelope shear diagrams, the shear values at the face of beam 4 are:

From dead load:


from the left, and
from the right) which means
that the total dead load that transfers to the beam 4 is
The uniformly distributed dead load over the beam from the ribs only is

226

Reinforced Concrete II

Dr. Nasr Abboushi

From live load:


from the left, and
from the right) which means
that the total live load that transfers to the beam 4 is
The uniformly distributed live load over the beam from the ribs only is

Shear diagram from Dead load only.

Beam 4

Envelope shear diagram from Live load only.

Beam 4

The total factored Dead Load:


The total factored Live Load:

227

Reinforced Concrete II

Dr. Nasr Abboushi

I
v
h h
f
h
h
f l l
.I
f
l
to calculate the loads more accurate specially when the beam section is wide and the spans
are large. We can use the first method for simplicity, especially in this stage of calculations,
when the dimensions of the beam are not known yet.

Structural Analysis of Beam 4. The envelope shear and moment diagrams (for all load
combinations).
The Beam 4 is loaded from the ribs 1 (first two spans) and ribs 2 (last span). The load
transferred from ribs 1 to Beam 4 is calculated before. The load transferred from rib 2 to
Beam 4 will be obtained by analyzing the rib 2 as continuous beam as follows:

Beam 4

228

Reinforced Concrete II

Dr. Nasr Abboushi

Dead Load calculations:


The maximum support reaction (factored) from Dead Loads for rib2 upon beam 4 is
. The distributed Dead Load from the Rib 1 on Beam 4:

The total factored Dead Load:


Live Load calculations:
The maximum support reaction (factored) from Live Loads for rib 2 upon beam 4 is

The distributed Live Load from the Rib 2 on Beam 4:

The total factored Live Load:


Using the structural analysis and design programs, we obtain the Envelope Moment diagram
for Beam 4.

229

Reinforced Concrete II

Dr. Nasr Abboushi

Design of Beam 4 for flexure.


Assume bar diameter

for main positive reinforcement.

The width of the Beam 4 can be defined from the maximum factored moment.
The maximum factored moment in Beam 4
Note that according to ACI 8.9.3 for beams built integrally with supports, design on the
basis of moments at faces of support shall be permitted. Here the design will be done for the
moments at the center of supports.
Take
Assume

fl

ll

.
230

Reinforced Concrete II

Take

Dr. Nasr Abboushi

Usually in construction the maximum width of the beams is

. Here, take

and no need to recalculate the loads acting on the beam.


Note that the factored moments of other supports and spans may be satisfied by the section
width of

as a singly reinforced beam sections, but the support section with

may be designed as doubly reinforced section.

Check whether the section will be act as singly or


doubly reinforced section:
Maximum nominal moment strength from strain

condition

Design the section as singly reinforced concrete section.

)
231

Reinforced Concrete II

Dr. Nasr Abboushi

Take

in one layer with

Check for strain:

Check for bar placement:

Design of Beam 4 for shear.


Critical section at distance

from the face of support.

Check for section dimensions:

Find the maximum stirrups spacing:

232

Reinforced Concrete II

Dr. Nasr Abboushi

Check for

)
(

Or
Compute the stirrups spacing required to resist the shear forces:
Use stirrups 2U-shape (4 legs stirrups)

with

Take 2U-shape (4 legs stirrups)

25 cm

100 cm

233

Reinforced Concrete II

Dr. Nasr Abboushi

Design the other beam sections for flexure (for positive and negative moments and caculate
the area of steel for each section).

Note that for shear design, it is obvious that, the stirrups cannot be less than two U-shape
stirrups

and the step

for all sections where stirrups are reqired.

So, for all sections the design for shear will be as the previous section ( 2 U-shape
).

An alternative design for the Beam 4 can be done on the basis of drop beam section, not as a
hidden beam as in the previous design.

234

Reinforced Concrete II

CHAPTER 9

Dr. Nasr Abboushi

TWO-WAY SLABS

9.1 INTRODUCTION
When the slab is supported on all four sides and the length, , is less than twice the width,
, the slab will deflect in two directions, and the loads on the slab are transferred to all four
supports. This slab is referred to as a two-way slab. The bending moments and deflections in
such slabs are less than those in one-way slabs; thus, the same slab can carry more load
when supported on four sides. The load in this case is carried in two directions, and the
bending moment in each direction is much less than the bending moment in the slab if the
load were carried in one direction only.

9.2 TYPES OF TWO-WAY SLABS


Structural two-way concrete slabs may be classified as follows:
1. Two-Way Slabs on Beams: This case occurs when the two-way slab is supported by
beams on all four sides. The loads from the slab are transferred to all four supporting
beams, which, in turn, transfer the loads to the columns.
2. Flat Slabs: A flat slab is a two-way slab reinforced in two directions that usually does
not have beams or girders, and the loads are transferred directly to the supporting
columns. The column lends to punch through the slab, which can be treated by three
methods:
234

Reinforced Concrete II

Dr. Nasr Abboushi

a. Using a drop panel and a column capital.


b. Using a drop panel without a column capital. The concrete panel around the column
capital should be thick enough to withstand the diagonal tensile stresses arising from
the punching shear.
c. Using a column capital without drop panel, which is not common.
3. Flat-Plate Floors: A flat-plate floor is a two-way slab system consisting of a uniform
slab that rests directly on columns and does not have beams or column capitals
(Fig. a). In this case the column tends to punch through the slab, producing diagonal
tensile stresses. Therefore, a general increase in the slab thickness is required or
special reinforcement is used.
235

Reinforced Concrete II

Dr. Nasr Abboushi

4. Two-Way Ribbed Slabs and the Waffle Slab System: This type of slab consists of a
floor slab with a length-to-width ratio less than 2. The thickness of the slab is usually
5 to 10 cm and is supported by ribs (or joists) in two directions. The ribs are arranged
in each direction at spacings of about
, producing square or
rectangular shapes. The ribs can also be arranged at
or
from the centerline
of slabs, producing architectural shapes at the soffit of the slab. In two-way ribbed
slabs, different systems can be adopted:
a.

b.

c.

A two-way rib system with voids between the ribs, obtained by using special
removable and usable forms (pans) that are normally square in shape. The ribs are
supported on four sides by girders that rest on columns. This type is called a twoway ribbed (joist) slab system.
A two-way rib system with permanent fillers between ribs that produce horizontal
slab soffits. The fillers may be of hollow, lightweight or normal-weight concrete or
any other lightweight material. The ribs are supported by girders on four sides,
which in turn are supported by columns. This type is also called a two-way ribbed
(joist) slab system or a hollow-block two-way ribbed system.
A two-way rib system with voids between the ribs with the ribs continuing in both
directions without supporting beams and resting directly on columns through solid
panels above the columns. This type is called a waffle slab system.

236

Reinforced Concrete II

Dr. Nasr Abboushi

9.3 ECONOMICAL CHOICE OF CONCRETE FLOOR SYSTEMS


Various types of floor systems can be used for general buildings, such as residential, office,
and institutional buildings. The choice of an adequate and economic floor system depends
on the type of building, architectural layout, aesthetic features, and the span length
between columns. In general, the superimposed live load on buildings varies between 4 and
. A general guide for the economical use of floor systems can be summarized as
follows:
1. Flat Plates: Flat plates are most suitable for spans of
and live loads
between and
. The advantages of adopting flat plates include lowcost formwork, exposed flat ceilings, and fast construction. Flat plates have low
shear capacity and relatively low stiffness, which may cause noticeable
deflection. Flat plates are widely used in buildings either as reinforced or
prestressed concrete slabs.
237

Reinforced Concrete II

Dr. Nasr Abboushi

2. Flat Slabs: Flat slabs are most suitable for spans of


and for live loads of
. They need more formwork than flat plates, especially for column
capitals. In most cases, only drop panels without column capitals are used.
3. Waffle Slabs: Waffle slabs are suitable for spans of
and live loads of
. They carry heavier loads than flat plates and have attractive
exposed ceilings. Formwork, including the use of pans, is quite expensive.
4. Slabs on Beams: Slabs on beams are suitable for spans beiween and
and
live loads of
. The beams increase the stiffness of the slabs,
producing relatively low deflection. Additional formwork for the beams is
needed.
5. One-Way Slabs on Beams: One-way slabs on beams are most suitable for spans
of
and a live load of
. They can be used for larger spans
with relatively higher cost and higher slab deflection. Additional formwork for
the beams is needed.
6. One-Way Joist Floor System: A one-way joist floor system is most suitable for
spans of
and live loads of
. Because of the deep ribs, the
concrete and steel quantities are relatively low, but expensive formwork is
expected. The exposed ceiling of the slabs may look attractive.
9.4 MINIMUM THICKNESS OF TWO-WAY SLABS.
The ACI Code, Section 9.5.3, specifies a minimum slab thickness in two-way slabs to control
deflection. The magnitude of a slab's deflection depends on many variables, including the
flexural stiffness of the slab, which in turn is a function of the slab thickness, . By increasing
the slab thickness, the flexural stiffness of the slab is increased, and consequently the slab
deflection is reduced. Because the calculation of deflections in two-way slabs is complicated
and to avoid excessive deflections, the ACI Code limits the thickness of these slabs by
adopting the following three empirical limitations, which are based on experimental
research. If these limitations are not met, it will be necessary to compute deflections.
1. For
(

)
(

but not less than

2. For
(
but not less than

3. For
238

Reinforced Concrete II

Dr. Nasr Abboushi

where
clear span in the long direction measured face to face of columns (or face to face of
beams for slabs with beams).
the ratio of the long to the short clear spans.
the average value of
for all beams on the sides of a panel.
the ratio of flexural stiffness of a beam section
to the flexural stiffness of the slab
, bounded laterally by the centerlines of the panels on each side of the beam.

where

, and
are the moduli of elasticity of concrete in the beam and the slab,
respectively, and
the gross moment of inertia of the beam section about the centroidal axis (the beam
section includes a slab length on each side of the beam equal to the projection of the
beam above or below the slab, whichever is greater, but not more than four times the
slab thickness)
the moment of inertia of the gross section of the slab.

However, the thickness of any slab shall not be less than the following:
1. For slabs with
then thickness
2. For slabs with
then thickness

If no beams are used, as in the case of flat plates, then


and
. The ACI Code
equations for calculating slab thickness, , take into account the effect of the span length,
the panel shape, the steel
reinforcement yield stress,
, and the flexural stiffness
of beams. When very stiff
beams are used, Eq. ( )
may give a small slab
thickness, and Eq. ( ) may
control. For flat plates and
flat slabs, when no interior
beams are used, the
minimum slab thickness
may be determined directly
from Table 9.5(c) of the ACI
Code, which is shown here.

239

Reinforced Concrete II

Dr. Nasr Abboushi

Other ACI Code limitations are summarized as follows:


1. For panels with discontinuous edges, end beams with a minimum
equal to
must
be used; otherwise, the minimum slab thickness calculated by Eqs. ( ) and ( ) must be
increased by at least
(ACI Code, Section 9.5.3).
2. When drop panels are used without beams, the minimum slab thickness may be
reduced by
. The drop panels should extend in each direction from the centerline of
support a distance not less than one-sixth of the span length in that direction between
center to center of supports and also project below the slab at least
. This reduction
is included in Table 9.5(c).
3. Regardless of the values obtained by Eqs. ( ) and ( ), the thickness of two-way slabs
shall not be less than the following:
(1) for slabs without beams or drop panels,
;
(2) for slabs without beams but with drop panels,
;
(3) for slabs with beams on all four sides with
,
, and
for
,
(ACI Code, Section 9.5.3.).
The thickness of a slab also may be governed by shear. This is particularly likely if large
moments are transferred to edge columns and for interior columns between two spans that
are greatly different in length. The selection of slab thicknesses to satisfy shear requirements
will be discussed later. Briefly, it is suggested that the trial slab thickness be chosen such that
at edge columns and
at interior columns.
240

Reinforced Concrete II

Dr. Nasr Abboushi

9.5 SLAB REINFORCEMENT REQUIREMENTS.


Placement Sequence.
In a flat plate or flat slab, the moments are larger in the slab strips spanning the long
direction of the panels. As a result, the reinforcement for the long span generally is placed
closer to the top and bottom of the slab than is the short-span reinforcement. This gives the
larger effective depth for the larger moment. For slabs supported on beams having
greater than about
, the opposite is true, and the reinforcing pattern should be reversed.
If a particular placing sequence has been assumed in the reinforcement design, it should be
shown or noted on the drawings. It also is important to maintain the same arrangements of
layers throughout the entire floor, to avoid confusion in the field. Thus, if the eastwest
reinforcement is nearer the top and bottom surfaces in one area, this arrangement should
be maintained over the entire slab, if at all possible.
Concrete Cover.
ACI Code Section 7.7.1 specifies the minimum clear cover to the surface of the
reinforcement in slabs as
for
and smaller bars, provided that the slab is not
exposed to earth or to weather.
Spacing Requirements, Minimum Reinforcement, and Minimum Bar Size.
ACI Code Section 13.3.1 requires that the minimum area of reinforcement provided for
flexure should not be less than (see page 195):
For slabs in which grade 280 (
) or 350 (
) deformed bars
are used,
.
For slabs in which grade 420 (
) deformed bars or welded bars or
welded wire fabric are used,
.
The maximum spacing of reinforcement at critical design sections for positive and negative
moments in both the middle and column strips shall not exceed two times the slab thickness
(ACI Code Section 13.3.2), and the bar spacing shall not exceed
at any location (ACI
Code Section 7.12.2.2).
Although there is no code limit on bar size, the top steel bars abd steps in slab should be
enough to give adequate rigidity to prevent displacement of the bars under ordinary foot
traffic before the concrete is placed.
Bar Cutoffs and Anchorages
For slabs without beams, ACI Code Section 13.3.8.1 allows the bars to be cut off as shown in
the figure below (ACI Code Fig. 13.3.8). Where adjacent spans have unequal lengths, the
extension of the negative-moment bars past the face of the support is based on the length
of the longer span.
ACI Code Section 13.3.3 requires that the Positive moment reinforcement perpendicular to a
discontinuous edge shall extend to the edge of slab and have embedment, straight or
hooked, at least
in spandrel beams, columns, or walls.
241

Reinforced Concrete II

Dr. Nasr Abboushi

ACI Code Section 13.3.4 requires that all negative-moment steel perpendicular to an edge be
bent, hooked, or otherwise anchored in spandrel beams, columns, and walls along the edge
to develop in tension. If there is no edge beam, this steel still should be hooked to act as
torsional reinforcement and should extend to the minimum cover thickness from the edge of
the slab.

ACI 318 - Fig. 13.3.8 Minimum extensions for reinforcement in slabs without beams. (See 12.11.1 for
reinforcement extension into supports).

ACI Code Section 13.3.6 requires that at exterior corners of slabs supported by edge walls or
where one or more edge beams have a value of greater than
, top and bottom slab
reinforcement shall be provided at exterior corners in accordance with 13.3.6.1 through
13.3.6.4.
13.3.6.1 Corner reinforcement in both top and bottom of slab shall be sufficient to
resist a moment per unit of width equal to the maximum positive moment per unit width in
the slab panel.
13.3.6.2 The moment shall be assumed to be about an axis perpendicular to the
diagonal from the corner in the top of the slab and about an axis parallel to the diagonal
from the corner in the bottom of the slab.
13.3.6.3 Corner reinforcement shall be provided for a distance in each direction
from the corner equal to one-fifth the longer span.
242

Reinforced Concrete II

Dr. Nasr Abboushi

13.3.6.4 Corner reinforcement shall be placed parallel to the diagonal in the top of
the slab and perpendicular to the diagonal in the bottom of the slab. Alternatively,
reinforcement shall be placed in two layers parallel to the sides of the slab in both the top
and bottom of the slab.

9.6 SHEAR STRENGTH OF TWO-WAY SLABS.


In a two-way floor system, the slab must have adequate thickness to resist both bending
moments and shear forces at the critical sections. To investigate the shear capacity of twoway slabs, the following cases should be considered.
243

Reinforced Concrete II

Dr. Nasr Abboushi

9.6.1 Two-Way Slabs Supported on Beams


In two-way slabs supported on beams, the critical sections are at a distance from the face
of the supporting beams, and the shear capacity of each section is

. When the supporting beams are stiff and are capable of transmitting

floor loads to the columns, they are assumed to carry loads acting on floor areas bounded by
lines drawn from the corners, as shown in the figure below. The loads on the trapezoidal
areas will be carried by the long beams
and
, whereas the loads on the triangular
areas will be carried by the short beams
and
. The shear per unit width of slab is
highest between and in both directions, and
, where
is the uniform
factored load per unit area.

If no shear reinforcement is provided, the shearing force at a distance


beam,
, must be equal to

from the face of the

where
(

9.6.2 Two-Way Slabs Without Beams


In flat plates and flat slabs, beams are not provided, and the slabs are directly supported by
columns. In such slabs, two types of shear stresses must be investigated; the first is one-way
shear, or beam shear. The critical sections are taken at a distance from the face of the
244

Reinforced Concrete II

Dr. Nasr Abboushi

column, and the slab is considered as a wide beam spanning between supports, as in the
case of one-way beams. The shear capacity of the concrete section is

The second type of shear to be studied is twoway, or punching, shear, as in the design of
footings. Shear failure occurs along a truncated
cone or pyramid around the column. The critical
section is located at a distance
from the
face of the column, column capital, or drop
panel. The ACI Code, Section 11.11.2 allows a
shear strength, , in slabs and footings without
shear reinforcement for two-way shear action,
the smallest of
(

where
Ratio of long side to short side of the rectangular column.
For shapes other than rectangular, is taken to be the ratio of the longest dimension of the
effective loaded area in the long direction to the largest width in the short direction
(perpendicular to the long direction).
perimeter of the critical section taken at
from the loaded area.
effective depth of slab.
for normal-weight concrete.
is assumed to be:

for interior columns,

for edge columns, and

for corner columns.


245

Dr. Nasr Abboushi

Edge of the slab

When openings are located at


less than
times the slab
thickness from a column, ACI
Code Section 11.11.6 requires
that the critical perimeter be
reduced, as shown below.
ACI Commentary suggested
that the side faces of the
critical perimeter would extend
to the edge of the slab if the
distance from the face of the
column to the edge of the slab
does not exceed the larger of:
(i) four slab thicknesses, , or
(ii) twice the development
length,
, of the flexural
reinforcement perpendicular
to the edge, shown by the
distances labeled A and B in
the Figures (b) and (c).
246

Edge of the slab

Reinforced Concrete II

Edge of the slab

Reinforced Concrete II

Dr. Nasr Abboushi

9.6.3 Tributary Areas for Shear in Two-Way Slabs.


For uniformly loaded two-way slabs, the tributary areas used to calculate are bounded by
lines of zero shear. For interior panels, these lines can be assumed to pass through the
center of the panel. For edge panels, lines of zero shear are approximately at
to
from the center of the exterior column, where is the span measured from center-tocenter of the columns. However, to be conservative in design, ACI Code Section 8.3.3
requires that the exterior supports must resist a shear force due to loads acting on half of
the span
. Also, to account for the larger tributary area for the first interior support, ACI
Code Section 8.3.3 requires that the shear force from loads acting on half of the span must
be increased by
. This essentially results in a tributary length of
.

Critical sections and tributary areas for shear in a flat plate.


9.6.4 Shear Reinforcement in Two-Way Slabs Without Beams.
In flat-slab and flat-plate floor systems, the thickness of the slab selected may not be
adequate to resist the applied shear stresses. In this case, either the slab thickness must be
increased or shear reinforcement must be provided. The ACI Code allows the use of shear
reinforcement by shearheads and anchored bars or wires (see next figures).
The design for shear (punching) reinforcement in flat plates will be discussed later in details
(see section 9.11).
247

Reinforced Concrete II

Dr. Nasr Abboushi

248

Reinforced Concrete II

Dr. Nasr Abboushi

9.7 ANALYSIS AND DESIGN OF TWO-WAY SLABS.


An exact analysis of forces and displacements in a two-way slab is complex, due to its highly
indeterminate nature; this is true even when the effects of creep and nonlinear behavior of
the concrete are neglected. Numerical methods such as finite elements can be used, but
249

Reinforced Concrete II

Dr. Nasr Abboushi

simplified methods such as those presented by the ACI Code are more suitable for practical
design. The ACI Code, Chapter 13, assumes that the slabs behave as wide, shallow beams
that form, with the columns above and below them, a rigid frame. The validity of this
assumption of dividing the structure into equivalent frames has been verified by analytical
and experimental research. It is also established that factored load capacity of two-way slabs
with restrained boundaries is about twice that calculated by theoretical analysis, because a
great deal of moment redistribution occurs in the slab before failure. At high loads, large
deformations and deflections are expected; thus, a minimum slab thickness is required to
maintain adequate deflection and cracking conditions under service loads.
The ACI Code specifies two methods for the design of two-way slabs:
1. The direct design method. DDM (ACI Code, Section 13.6), is an approximate
procedure for the analysis and design of two-way slabs. It is limited to slab systems
subjected to uniformly distributed loads and supported on equally or nearly equally
spaced columns. The method uses a set of coefficients to determine the design
moments at critical sections. Two-way slab systems that do not meet the limitations
of the ACI Code, Section 13.6.1, must be analyzed by more accurate procedures.
2. The equivalent frame method, EFM (ACI Code, Section 13.7), is one in which a threedimensional building is divided into a series of two-dimensional equivalent frames by
cutting the building along lines midway between columns. The resulting frames are
considered separately in the longitudinal and transverse directions of the building
and treated floor by floor, as will be shown later.
The systems that do not meet the requirements permitting analysis by the "direct design
method" of the present code, has led many engineers to continue to use the design method
of the 1963 ACI Code (The coefficient method) for the special case of two-way slabs supported on four sides of each slab panel by relatively deep, stiff, edge beams. It has been
used extensively here since 1963 for slabs supported at the edges by walls, steel beams, or
monolithic concrete beams having a total depth not less than about 3 times the slab
thickness. While it was not a part of the 1977 or later ACI Codes, its continued use is
permissible under the current code provision (ACI Code 13.5.1) that a slab system may be
designed by any procedure satisfying conditions of equilibrium and geometric compatibility,
if it is shown that the design strength at every section is at least equal to the required
strength, and that serviceability requirements are met.
9.8 SLAB ANALYSIS BY THE COEFFICIENT METHOD.
The coefficient method makes use of tables of moment coefficients for a variety of
conditions. These coefficients are based on elastic analysis but also account for inelastic
redistribution. In consequence, the design moment in either direction is smaller by an
appropriate amount than the elastic maximum moment in that direction. The moments in
the middle strips in the two directions are computed from
250

Reinforced Concrete II

Dr. Nasr Abboushi

and

where

tabulated moment coefficients.


uniform load,
length of clear span in short and long directions respectively.

The method provides that each panel be divided in both directions into a middle strip whose
width is one-half that of the panel and two edge or column strips of one-quarter of the panel
width (see figure below). The moments in both directions are larger in the center portion of
the slab than in regions close to the edges. Correspondingly, it is provided that the entire
middle strip be designed for the full, tabulated design moment. In the edge strips this
moment is assumed to decrease from its full value at the edge of the middle strip to onethird of this value at the edge of the panel. This distribution is shown for the moments
in
the short span direction in figure below. The lateral variation of the long span moments
is similiar.

The discussion so far has been restricted to a single panel simply supported at all four edges.
An actual situation is shown in next figure, in which a system of beams supports a two-way
slab. It is seen that some panels, such as , have two discontinuous exterior edges, while the
other edges are continuous with their neighbors. Panel has one edge discontinuous and
three continuous edges, the interior panel has all edges continuous, and so on. At a
continuous edge in a slab, moments are negative, just as at interior supports of continuous
beams. Also, the magnitude of the positive moments depends on the conditions of
continuity at kall four edges.
251

Reinforced Concrete II

Dr. Nasr Abboushi

Correspondingly, Table 1 gives moment coefficients , for negative moments at continuous


edges. The details of the tables are self-explanatory. Maximum negative edge moments are
obtained when both panels adjacent to the particular edge carry full dead and live load.
Hence the moment is computed for this total load. Negative moments at discontinuous
edges are assumed equal to one-third of the positive moments for the same direction. One
must provide for such moments because some degree of restraint is generally provided at
discontinuous edges by the torsional rigidity of the edge beam or by the supporting wall.
For positive moments there will be little, if any, rotation at the continuous edges if dead load
alone is acting, because the loads on both adjacent panels tend to produce opposite
rotations which cancel, or nearly so. For this condition, the continuous edges can be
regarded as fixed, and the appropriate coefficients for the dead load positive moments are
given in Table 2. On the other hand, the maximum live load positive moments are obtained
when live load is placed only on the particular panel and not on any of the adjacent panels.
In this case, some rotation will occur at all continuous edges. As an approximation it is
assumed that there is
restraint for calculating these live load moments. The
corresponding coefficients are given in Table 3. Finally, for computing shear in the slab and
loads on the supporting beams, Table 4 gives the fractions of the total load that are
transmitted in the two directions.

252

Reinforced Concrete II

Dr. Nasr Abboushi

253

Reinforced Concrete II

Dr. Nasr Abboushi

254

Reinforced Concrete II

Dr. Nasr Abboushi

255

Reinforced Concrete II

Dr. Nasr Abboushi

256

Reinforced Concrete II

Dr. Nasr Abboushi

Find the required slab thickness and


reinforcement for the corner panel shown.

Corner
Panel

Example (Design of two-way edge-supported solid slab):


A monolithic reinforced concrete floor is to be composed of rectangular bays
measuring
, as shown. Beams of width
and depth
are provided on
all column lines; thus the clear-span dimensions for the two-way slab panels are
. The floor is to be designed to carry a service live load
and a dead load
on the slab due to self-weight plus weight of:
Tiles,
.

Mortar,
.
Sand,
.
Plaster,
.
Partitions,
.
Given:
and
.

Solution:

1. Minimum thickness (deflection


requirements):
For slabs of this type the first trial
thickness is often taken equal to

Check for the minimum thickness of the slab:

Exterior beam:

257

Reinforced Concrete II

Dr. Nasr Abboushi

Interior beam:

Slab section for Exterior beam:

Short direction
(

Long direction

Slab section for Interior beam:

Short direction

Long direction

258

Reinforced Concrete II

Dr. Nasr Abboushi

Corner
Panel

the minimum slab thickness will be:


(

First trial thickness

. Take slab thickness

2. Loads calculation:
Quality Density

Material
Tiles
mortar
Sand
Reinforced Concrete solid slab
Plaster
Partitions
Total Dead Load
Dead Load of slab
Live Load of slab

,
,
259

Reinforced Concrete II

Dr. Nasr Abboushi

3. Moments calculations:

Discontinuous Edge

middle strip - short

Case 4

Continuous Edge

Discontinuous Edge

Column strip - short

Continuous Edge

and

The moment calculations will be done for the slab middle strip.

Negative moments at continuous edges (Table 1):


(

and

and

Positive moments (Table 2 and Table 3):


(

(
(

and
)

and
)

)
)

)
)

260

Column strip - long

Column strip - long

Middle strip - long

Column strip - short

Reinforced Concrete II

and
)

)
)

)
)

Negative moments at Discontinuous edges (

short direction

long direction

Moments

and
)

Dr. Nasr Abboushi

261

):

Reinforced Concrete II

Dr. Nasr Abboushi

4. Slab reinforcement:
Short direction:
Assume bar diameter

for main reinforcement.

Midspan:

Provide
Use

then

Take

Note that in the edge strips the positive moment, and the corresponding steel reinforcement
area, is assumed to decrease from its full value at the edge of the middle strip to one-third of
this value at the edge of the panel, which will not be provided.
Continuous edge:
Assume bar diameter

for main reinforcement.

262

Reinforced Concrete II

Dr. Nasr Abboushi

Provide
Use

then

Take

Discontinuous edge.
The negative moment at the discontinuous edge is one-third the positive moment in the
span.

Provide

Take

Long direction.
Design for positive and negative moment as in the short direction.
Note that the effective depth for the long direction will be

5. Check for shear:


(

and
(

)
and

)
(

)
(

The reactions of the slab are calculated from Table 4, which indicates that
of the load is
transmitted in the short direction and
in the long direction.
The total load on the panel being
The load per meter on the long beam is
, and
The load per meter on the short beam is
.
The shear to be transmitted by the slab to these beams is numerically equal to these beam
loads, reduced to a critical section a distance from the beam face. The shear strength of
the slab is
263

Reinforced Concrete II

Dr. Nasr Abboushi

- for shear.

The thickness of the slab is adequate enough.


at the face of support, at distance
smaller.
Even, if

from the face of support will be

for solid slabs, the thickness of the slab will be enough.

Example:
A monolithic reinforced concrete solid slab is to be composed of rectangular bays as shown.
Beams of width
and depth
are provided on all column lines. The floor is to be
designed to carry a service live load
and a dead load on the slab due to selfweight plus weight of:
Tiles,
.
Mortar,
.
Sand,
.
Plaster,
.
Partitions,
.
Given:
and
.
Find the required slab thickness and reinforcement for the solid slab shown.
Solution:
1. Minimum thickness (deflection requirements):
For slabs of this type the first trial thickness is often taken equal to

Take

As was required in the previous example.

Check for the minimum thickness of the slab (for


shaded panel):

Exterior beam:
(

264

Reinforced Concrete II

Dr. Nasr Abboushi

6.0 m

B 11 (60 x 60 cm)

B 1 (60 x 60 cm)

6.6 m

B 5 (60 x 60 cm)

B 6 (60 x 60 cm)

B 2 (60 x 60 cm)

6.6 m

265

B 16 (60 x 60 cm)

B 19 (60 x 60 cm)

B 3 (60 x 60 cm)

6.6 m

7.5 m
7.5 m

8.0 m

B 9 (60 x 60 cm)

B 24 (60 x 60 cm)

B 21 (60 x 60 cm)

B 8 (60 x 60 cm)

B 20 (60 x 60 cm)

B 7 (60 x 60 cm)

B 17 (60 x 60 cm)

B 13 (60 x 60 cm)

B 4 (60 x 60 cm)

8.6 m

B 18 (60 x 60 cm)

B 15 (60 x 60 cm)
B 14 (60 x 60 cm)

8.1 m

8.1 m

B 12 (60 x 60 cm)

B 23 (60 x 60 cm)

B 10 (60 x 60 cm)

6.0 m

B 22 (60 x 60 cm)

6.0 m

Reinforced Concrete II

Dr. Nasr Abboushi

Interior beam:

Slab section for Exterior beam:

Short direction
(

Long direction

Slab section for Interior beam:

Short direction

Long direction
(

)
266

Reinforced Concrete II

Dr. Nasr Abboushi

Corner
Panel

the minimum slab thickness will be:


(

First trial thickness

. Take slab thickness

2. Loads calculation:
Quality Density

Material
Tiles
mortar
Sand
Reinforced Concrete solid slab
Plaster
Partitions
Total Dead Load
Dead Load of slab
Live Load of slab

,
,

267

Reinforced Concrete II

Dr. Nasr Abboushi

3. Moments calculations:
and
All negative and positive coefficients are shown on the slab plane (page 265).
Negative moments at Discontinuous edges (
6.0 m

25.2

+27.5

+21.5

B 1 (60 x 60 cm)

B 2 (60 x 60 cm)

B 3 (60 x 60 cm)

6.6 m

6.6 m

Moments,
268

6.6 m

9.2

7.5 m
7.5 m
8.0 m

45.4
+14.9

+9.6

46.6

B 19 (60 x 60 cm)

46.6

3.2

B 16 (60 x 60 cm)

+14.9

25.5

B 6 (60 x 60 cm)

+27.5

B 23 (60 x 60 cm)

+21.5

14.9

25.5
9.2

7.2

38.3

+18.6

32.9
+15.3

+12.2

38.8

B 5 (60 x 60 cm)

45.4

B 24 (60 x 60 cm)

27.1
38.3

38.8

B 20 (60 x 60 cm)

+21.5

B 4 (60 x 60 cm)

B 13 (60 x 60 cm)

B 9 (60 x 60 cm)

25.2

7.2

B 17 (60 x 60 cm)

+15.3

32.9

8.4

+25.1

15.9
B 8 (60 x 60 cm)

38.3

B 14 (60 x 60 cm)

8.1 m

42.4
+16.2

+11.5
+19.9

38.3

B 7 (60 x 60 cm)

8.6 m

44.5

B 21 (60 x 60 cm)

3.8
B 18 (60 x 60 cm)

+16.2
+25.1

44.5

27.1

B 15 (60 x 60 cm)

8.1 m

42.4
8.4

B 12 (60 x 60 cm)

5.4

B 11 (60 x 60 cm)

5.4

B 10 (60 x 60 cm)

6.0 m

B 22 (60 x 60 cm)

6.0 m

):

Reinforced Concrete II

Dr. Nasr Abboushi

4. Slab reinforcement:
Assume bar diameter

Find

corresponding to

(
Check for strain

:
(

Take

Assume bar diameter

(
Check for strain

:
(

Take

Assume bar diameter

(
Check for strain

:
269

Reinforced Concrete II

Dr. Nasr Abboushi

Take

10@15 cm c/c
L=300 cm

7.5 m

10@15 cm c/c
L=900 cm

10@15 cm c/c
L=300 cm

12@15 cm c/c
L=600 cm
T

10@15 cm c/c
L=900 cm

7.5 m

10@15 cm c/c
L=750 cm

10@15 cm c/c
L=900 cm
B

10@15 cm c/c
L=600 cm

14@15 cm c/c
L=500 cm
B

10@15 cm c/c
L=300 cm

10@15 cm c/c
L=750 cm

10@15 cm c/c
L=950 cm

10@15 cm c/c
L=950 cm

10@15 cm c/c
L=300 cm

10@15 cm c/c
L=750 cm

10@15 cm c/c
L=300 cm

8.0 m

T
14@15 cm c/c
L=500 cm
B

12@15 cm c/c
L=600 cm

10@15 cm c/c
L=900 cm
B

10@15 cm c/c
L=950 cm

6.6 m

6.6 m

200

6.6 m

10@15 cm c/c
L=300 cm

10@15 cm c/c
L=750 cm

8.6 m

10@15 cm c/c
L=300 cm

10@15 cm c/c
L=750 cm

12@15 cm c/c
L=500 cm

10@15 cm c/c
L=750 cm

10@15 cm c/c
L=900 cm
B

12@15 cm c/c
L=600 cm
T
10@15 cm c/c
L=300 cm
B

10@15 cm c/c
L=300 cm

12@15 cm c/c
L=500 cm

10@15 cm c/c
L=750 cm

8.1 m

12@15 cm c/c
L=500 cm

10@15 cm c/c
L=300 cm
B

10@15 cm c/c
L=750 cm

10@15 cm c/c
L=600 cm

10@15 cm c/c
L=900 cm

T
T

6.0 m

12@15 cm c/c
L=500 cm

10@15 cm c/c
L=750 cm

12@15 cm c/c
L=600 cm

8.1 m

T 10@15 cm c/c
L=300 cm

6.0 m

10@15 cm c/c
L=300 cm

6.0 m

Typical section in solid slab


270

Reinforced Concrete II

Dr. Nasr Abboushi

5. Check for shear:


The maximum shear coefficient is

, from case 9.

The reactions of the slab are calculated from Table 4, which indicates that
of the load is
transmitted in the short direction.
The total load on the panel being
The load per meter on the long beam is
,
The shear to be transmitted by the slab to these beams is numerically equal to these beam
loads, reduced to a critical section a distance from the beam face. The shear strength of
the slab is

- for shear.

The thickness of the slab is adequate enough.


at the face of support, at distance
smaller and can be calculated from
Another way (simply supported
of support
(
Even, if

from the face of support will be

strip) to calculate the shear at distance


)

from the face

for solid slabs, the thickness of the slab will be enough.

For the two methods of calculating

the thickness of the slab is adequate enough.

6. Design of Beams 16-17-18 (


):
The tributary load area for beams 16, 17, 18 from the solid slab is as shown (shaded area). In
addition to factored load acting on the beam from the solid slab, the own weight of the
beam must be added.
Load calculation for the beams 16-17-18:

No additional loads applied directly on the beams.

B 16
8.6 m

B 17
8.1 m

271

B 18
8.1 m

45

6.6 m

3.0 m

45

6.6 m

272

45

45

6.6 m

Using software programs such as BEAMD to analyze the beam and to get shear and moment
envelopes, and then design it.
8.0 m

2.0 m

45

3.0 m

3.0 m

3.0 m

7.5 m

1.5 m

1.5 m

3.0 m

3.0 m

3.0 m

3.0 m

3.0 m

7.5 m

1.5 m

1.5 m

3.0 m

3.0 m

B 18 (60x60 cm)

3.0 m

6.0 m

3.0 m

2.0 m

3.0 m

3.0 m

1.5 m

1.5 m

B 17 (60x60 cm)

3.0 m

8.1 m

8.1 m

6.0 m

3.0 m

B 16 (60x60 cm)

3.0 m

2.0 m

8.6 m

Reinforced Concrete II
Dr. Nasr Abboushi

6.0 m

45

Reinforced Concrete II

Dr. Nasr Abboushi

273

Reinforced Concrete II

Dr. Nasr Abboushi

Example (Design of two-way edge-supported ribbed slab):


A monolithic reinforced concrete ribbed slab is to be composed of rectangular bays as
shown. Beams of width
and depth
are provided on all column lines. The floor
is to be designed to carry a service live load
and a dead load on the slab due to
self-weight plus weight of:
Tiles,
.
Mortar,
.
Sand,
.
Plaster,
.
Partitions,
.
Given:
and
.
Find the required slab thickness and reinforcement for the ribbed slab shown.

Solution:
1. Minimum thickness (deflection requirements): Assume the thickness for the shown
ribbed slab
Check for the minimum thickness of the slab (for the shaded corner slab):

All Exterior and Interior beams have rectangular section of 60 cm width and 52 cm
depth:

Slab section for Exterior beam:

The moment of inertia for the ribbed slab is the sum of moment of inertia of T-section ribs
within a distance (
)
was defined as in one-way ribbed
slab design (
)

274

Reinforced Concrete II

Dr. Nasr Abboushi

6.0 m

B2 (60x52 cm)

6.6 m

Typical section in ribbed slab


275

7.5 m

B 24 (60x52 cm)

7.5 m

B 23 (60x52 cm)
B3 (60x52 cm)

6.6 m

7.5 m

B 16 (60x52 cm)

B 13 (60x52 cm)

B6 (60x52 cm)

B 19 (60x52 cm)

B 14 (60x52 cm)

8.1 m

B 17 (60x52 cm)

B5 (60x52 cm)

B4 (60x52 cm)

8.1 m

B9 (60x52 cm)

B 20 (60x52 cm)

B 15 (60x52 cm)

8.1 m

B 18 (60x52 cm)

B8 (60x52 cm)

B7 (60x52 cm)

6.6 m

B12 (60x52 cm)

B 21 (60x52 cm)

B11 (60x52 cm)

B10 (60x52 cm)

B1 (60x52 cm)

6.0 m

B 22 (60x52 cm)

6.0 m

Reinforced Concrete II

Dr. Nasr Abboushi

Short direction

Long direction

Slab section for Interior beam:

Short direction
(

Long direction

7.5 m

6m
Corner
Panel

the minimum slab thickness will be:


(

)
(

)
276

Reinforced Concrete II

Dr. Nasr Abboushi

First trial thickness


Take slab thickness

2. Loads calculation:
Material

Quality Density

Tiles
mortar
Sand
Reinforced Concrete Topping
Reinforced Concrete Rib
Concrete Block
Plaster
Partitions
Total Dead Load,
Dead Load of slab:

Live Load of slab:

3. Moments calculations:
and
All negative and positive coefficients are shown on the slab plane (page 278).
Negative moments at Discontinuous edges (

):
277

Reinforced Concrete II

Dr. Nasr Abboushi

6.0 m

6.6 m

Note that all moments

6.6 m

and

are for

7.5 m

7.5 m

8.1 m

8.1 m

8.1 m

6.0 m

strip. For one rib (


278

7.5 m

6.0 m

6.6 m

Reinforced Concrete II

Dr. Nasr Abboushi

6.0 m

7.5 m

B 23 (60 x 60 cm)

+8.32
+11.72

13.8

B 6 (60 x 60 cm)

2.95

+13.71

2.09

+10.85

23.23

B 2 (60 x 60 cm)

B 3 (60 x 60 cm)

6.6 m

Moments,
279

6.6 m

4.57

7.5 m

+6.26

24.54

+8.84

24.54

B 19 (60 x 60 cm)

14.82

8.69
+8.84

3.91

20.96

+18.09

18

B 1 (60 x 60 cm)

6.6 m

7.5 m

14.82
20.96
+6.61

21.27

B 20 (60 x 60 cm)

21.27

2.95

+13.71

B 16 (60 x 60 cm)

14.82
4.57

B 24 (60 x 60 cm)

+8.84

+6.26

B 9 (60 x 60 cm)

B 5 (60 x 60 cm)

23.23

4.57

+13.71

8.69
+11.72

B 4 (60 x 60 cm)

B 13 (60 x 60 cm)

+10.85

23.23

13.8

3.91

B 17 (60 x 60 cm)

+8.32

18

20.96

B 14 (60 x 60 cm)

8.1 m

24.54

B 8 (60 x 60 cm)

20.96

B 7 (60 x 60 cm)

8.1 m

24.54

B 21 (60 x 60 cm)

2.09
B 18 (60 x 60 cm)

+8.84
+13.71

14.82

B 15 (60 x 60 cm)

8.1 m

23.23
4.57

B 12 (60 x 60 cm)

2.95

B 11 (60 x 60 cm)

2.95

B 10 (60 x 60 cm)

6.0 m

B 22 (60 x 60 cm)

6.0 m

Reinforced Concrete II

Dr. Nasr Abboushi

4. Slab reinforcement:
The design can be done directly for the negative moment or through section analysis with
assumed bar diameter and step.
Design for negative moment

Assume bar diameter

for main reinforcement.

Check for

Use

with

Check for strain:

Analysis the T-section rib for different two bars (

Assume

bottom bars (+ve moment).

280

Reinforced Concrete II

Dr. Nasr Abboushi

(
Check for strain

:
(

Take

All panels will be reinforced with


bottom bars in both directions except for the middle
panel in the short direction where will be used
bottom bars as shown in the next
figure.

Assume

top bars (ve moment).

(
Check for strain

:
(

Take

Assume

top bars (ve moment).

(
Check for strain

:
(

Take
281

Reinforced Concrete II

Dr. Nasr Abboushi

T 2 12
L=500 cm

B 2 10
L=900 cm
T 2 12
L=600 cm

B 2 10
L=900 cm

T 2 14
L=500 cm
B 2 10
L=750 cm

T 2 10
L=300 cm

B 2 10
L=900 cm

T 2 10
L=300 cm

T 2 10
L=300 cm

B 2 10
L=900 cm

B 2 10
L=750 cm

6.6 m

T 2 10
L=300 cm

6.6 m

6.6 m
8 @20 cm

10 or 12 or 14

24 cm

32 cm

8 cm

10

40 cm

12 cm

Typical section in ribbed slab


282

7.5 m

T 2 12
L=600 cm

T 2 12
L=600 cm

B 2 10
L=900 cm

8.1 m

T 2 14
L=500 cm
B 2 10
L=750 cm

7.5 m

B 2 10
L=750 cm

B 2 12
L=750 cm

T 2 10
L=300 cm

8.1 m

T 2 10
L=300 cm

B 2 10
L=900 cm

B 2 10
L=750 cm

7.5 m

B 2 10
L=900 cm

B 2 10
L=900 cm
T 2 12
L=600 cm

T 2 12
L=600 cm

T 2 12
L=500 cm

T 2 10
L=300 cm

T 2 10
L=300 cm

B 2 10
L=750 cm

B 2 10
L=750 cm
B 2 10
L=900 cm

8.1 m

B 2 10
L=750 cm

T 2 14
L=500 cm

T 2 10
L=300 cm

T 2 14
L=500 cm

T 2 12
L=600 cm

T 2 10
L=300 cm

6.0 m

T 2 10
L=300 cm

6.0 m

T 2 10
L=300 cm

6.0 m

Reinforced Concrete II

Dr. Nasr Abboushi

Assume

top bars (ve moment).

(
Check for strain

:
(

Take

5. Design for shear:


Maximum shear coefficient will be in the short direction for the slab with boundary
conditions as in case 9.
The total load on the panel being
The load per rib at face of the long beam is
.
The shear critical section is at distance from the beam face:
The shear strength of one rib in the slab is

- for shear.

The shear in the slab can be calculated using tributary


area for shear (as simply supported
strip):
)

Design the rib for shear assuming that the critical shear
in the rib is
.

3m

1.5 m

3m

No need for shear reinforcement (exception for joist constructions)

3m
283

3m

Reinforced Concrete II

Dr. Nasr Abboushi

Provide minimum shear reinforcement.


Use
(

for stirrups
)

Use

for the distance of 1 m from the face of support, and


in the middle space. Note that the shear force at distance

face of support is

from the
, so no

shear reinforcement is required for the middle space.

6. Design of Beams 16-17-18 (

):

The tributary load area for beams 16, 17, 18 from ribbed slab is as shown (shaded area). In
addition to factored load acting on the beam from the ribbed slab, the own weight of the
beam must be added.
Load calculation for the beams 16-17-18:

Weight of the floor materials acting directly on the beam


Material
Tiles
mortar
Sand
Plaster
Partitions
Total Dead Load,

No additional loads applied directly on the beams (such as walls).


284

45

6.6 m

1.5 m

3.0 m

B1 (60x52 cm)

B2 (60x52 cm)

6.6 m

285

B3 (60x52 cm)

6.6 m

7.5 m

3.0 m

7.5 m

B 23 (60x52 cm)

3.0 m

3.0 m

7.5 m

B 24 (60x52 cm)

3.0 m

1.5 m

B 21 (60x52 cm)

1.5 m

3.0 m

6.0 m

B 22 (60x52 cm)

3.0 m

B5 (60x52 cm)

3.0 m

B8 (60x52 cm)

1.5 m

B 20 (60x52 cm)

1.5 m

3.0 m

B11 (60x52 cm)

1.5 m

B 19 (60x52 cm)

1.5 m

B4 (60x52 cm)

3.0 m

B7 (60x52 cm)

3.0 m

3.0 m

B 18 (60x52 cm)

3.0 m

1.5 m

B 15 (60x52 cm)

8.1 m

B10 (60x52 cm)

3.0 m

3.0 m

B 17 (60x52 cm)

3.0 m

1.5 m

B 14 (60x52 cm)

8.1 m

6.0 m

3.0 m

45

B 16 (60x52 cm)

3.0 m

B 13 (60x52 cm)

8.1 m

Reinforced Concrete II
Dr. Nasr Abboushi

6.0 m

B12 (60x52 cm)

B9 (60x52 cm)

B6 (60x52 cm)

Reinforced Concrete II

Total service
Total service

Dr. Nasr Abboushi

on the beam
on the beam

and
and

Using software programs such as BEAMD to analyze and design the beams and to get
reinforcement details.

7. Design of Beams 7-8-9 (

):

The tributary load area for beams 7, 8, 9 from ribbed slab is as shown (shaded area). In
addition to factored load acting on the beam from the ribbed slab, the own weight of the
beam must be added.
Load calculation for the beams 7-8-9:

No additional loads applied directly on the beams (such as walls).


Total service
Total service

on the beam
on the beam

and

and

6.6 m

6.6 m

6.6 m

Using software programs such as BEAMD to analyze and design the beams and to get
reinforcement details.
286

Reinforced Concrete II

Dr. Nasr Abboushi

8. Design of Beams 22-23-24 (

):

The tributary load area beams 22, 23, 24 from ribbed slab is as shown (shaded area). In
addition to factored load acting on the beam from the ribbed slab, the own weight of the
beam must be added and the load of the RC wall (
thick,
height).
Load calculation for the beams 22-23-24:

Note here that the width of the beam for the floor materials and live load on the beam will
be smaller because of the thickness of the exterior wall (
)
Weight of the floor materials acting directly on the beam
Material
Tiles
mortar
Sand
Plaster
Partitions
Total Dead Load,

Total service
Total service

on the beam
on the beam

and
and

Using software programs such as BEAMD to analyze and design the beams and to get
reinforcement details.
287

Reinforced Concrete II

Dr. Nasr Abboushi

288

Reinforced Concrete II

Dr. Nasr Abboushi

289

Reinforced Concrete II

Dr. Nasr Abboushi

290

Reinforced Concrete II

Dr. Nasr Abboushi

291

Reinforced Concrete II

Dr. Nasr Abboushi

292

Reinforced Concrete II

Dr. Nasr Abboushi

293

Reinforced Concrete II

9.9

Dr. Nasr Abboushi

SLAB ANALYSIS BY THE DIRECT DESIGN METHOD (DDM).

The direct-design method also could have been called the direct-analysis method, because
this method essentially prescribes values for moments in various parts of the slab panel
without the need for a structural analysis. The reader should be aware that this design
method was introduced in an era when most engineering calculations were made with a
slide rule and computer software was not available to do the repetitive calculations required
to analyze a continuous-floor slab system. Thus, for continuous slab panels with relatively
uniform lengths and subjected to distributed loading, a series of moment coefficients were
developed that would lead to safe flexural designs of two-way floor systems.

9.9.1 Limitations on the Use of the Direct-Design Method.


The direct-design method is easier to use than the equivalent-frame method, but can be
applied only to fairly regular multipanel slabs. The limitations, given in ACI Code Section
13.6.1, include the following:
1. There must be a minimum of three continuous spans in each direction. Thus, a
ninepanel structure (
) is the smallest that can be considered. If there are fewer
than three panels, the interior negative moments from the direct-design method
tend to be too small.
2. Rectangular panels must have a long-span/short-span ratio that is not greater than .
One-way action predominates as the span ratio reaches and exceeds .
3. Successive span lengths in each direction shall not differ by more than one third of
the longer span. This limit is imposed so that certain standard reinforcement cutoff
details can be used.
4. Columns may be offset from the basic rectangular grid of the building by up to 0.1
times the span parallel to the offset. In a building laid out in this way, the actual
column locations are used in determining the spans of the slab to be used in
calculating the design moments.
5. All loads must be due to gravity only and uniformly distributed over an entire panel.
The direct-design method cannot be used for unbraced, laterally loaded frames,
foundation mats, or prestressed slabs.
6. The service (unfactored) live load shall not exceed two times the service dead load.
Strip or checkerboard loadings with large ratios of live load to dead load may lead to
moments larger than those assumed in this method of analysis.
7. For a panel with beams between supports on all sides, the relative stiffness of the
beams in the two perpendicular directions given by (
) (
) shall not be less
than
or greater than . The term was defined in the prior section, and and
are the spans in the two directions.
Limitations and do not allow use of the direct-design method for slab panels that
transmit load as one-way slabs.
294

Reinforced Concrete II

Dr. Nasr Abboushi

9.9.2 Column and middle strips.


In both direct design and equivalent frame methods, a typical panel is divided, for purposes
of design, into column strips and middle strips. A column strip is defined as a strip of slab
having a width on each side of the column centerline equal to one-fourth the smaller of the
panel dimensions and . Such a strip includes column-line beams, if present. A middle
strip is a design strip bounded by two column strips. In all cases, , is defined as the span in
the direction of the moment analysis and as the span in the lateral direction measured
center to center of the support. In the case of monolithic construction, beams are defined to
include that part of the slab on each side of the beam extending a distance equal to the
projection of the beam above or below the slab
(whichever is greater) but not greater
than 4 times the slab thickness (see Section 9.4).

295

Reinforced Concrete II

Dr. Nasr Abboushi

9.9.3 Total Static Moment at Factored Loads.


For purposes of calculating the total static moment
in a panel, the clear span in the
direction of moments is used. The clear span is defined to extend from face to face of the
columns, capitals, brackets, or walls but is not to be less than
. The total factored
moment in a span, for a strip bounded laterally by the centerline of the panel on each side of
the centerline of supports, is

The face of the support where the


negative moments should be
calculated is illustrated in the figure
below. The length is measured in a
direction perpendicular to
and
equals the direction between center
to center of supports (width of slab).
The total moment
calculated in
the long direction will be referred to
here as
and that in the short
direction, as
.
Once the total moment,
, is
calculated in one direction, it is
divided into a positive moment,
, and a negative moment,
,
such that
. Then
each moment,
and
, is
distributed across the width of the slab between the column and middle strips.
9.9.4 Assignment of positive and negative moments.
For interior spans, the total static moment is apportioned between the critical positive and
negative bending sections according to the following ratios:
Negative factored moment:
Positive factored moment:
The critical section for negative bending is taken at the face of rectangular supports, or at
the face of an equivalent square support having the same cross-sectional area as a round
support.
In the case of end spans, the apportionment of the total static moment among the three
critical moment sections (interior negative, positive, and exterior negative, as illustrated by
the figure below) depends upon the flexural restraint provided for the slab by the exterior
column or the exterior wall, as the case may be, and depends also upon the presence or
absence of beams on the column lines. ACI Code 13.6.3 specifies five alternative sets of
moment distribution coefficients for end spans, as shown in the next table and figure.

296

Reinforced Concrete II

Dr. Nasr Abboushi

297

Reinforced Concrete II

Dr. Nasr Abboushi

9.9.5 Lateral Distribution of Moments (between Column Strips and Middle Strips)
Having distributed the moment
to the positive and negative-moment sections as just
described, the designer still must distribute these design moments across the width of the
critical sections. For design purposes, it is convenient to consider the moments constant
within the bounds of a middle strip or column strip unless there is a beam present on the
column line. In the latter case, because of its greater stiffness, the beam will tend to take a
larger share of the column-strip moment than the adjacent slab. The distribution of total
negative or positive moment between slab middle strips, slab column strips, and beams
depends upon the ratio
, the relative stiffness of the beam and the slab, and the degree
of torsional restraint provided by the edge beam.
A convenient parameter defining the relative stiffness of the beam and slab spanning in
either direction is

in which
and
are the moduli of elasticity of the beam and slab concrete (usually the
same) and and are the moments of inertia of the effective beam and the slab.
Subscripted parameters
and
are used to identify computed for the directions of
, and , respectively.
The flexural stiffnesses of the beam and slab may be based on the gross concrete section,
neglecting reinforcement and possible cracking, and variations due to column capitals and
drop panels may be neglected. For the beam, if present, and for the slab,
are
defined as in Section 9.4.
The relative restraint provided by the torsional resistance of the effective transverse edge
beam is reflected by the parameter , defined as

where , as before, is calculated for the slab spanning in direction , and having width
bounded by panel centerlines in the direction. The constant
pertains to the torsional
rigidity of the effective transverse beam, which is defined according to ACI Code 13.7.5 as
the largest of the following:
1. A portion of the slab having a width equal to that of the column, bracket, or capital in
the direction in which moments are taken,
2. The portion of the slab specified in 1 plus that part of any transverse beam above and
below the slab,
3. The transverse beam defined as in Section 9.4.
The constant is calculated by dividing the section into its component rectangles, each
having smaller dimension
and larger dimension , and summing the contributions of all
the parts by means of the equation
(

The subdivision can be done in such a way as to maximize .


298

Reinforced Concrete II

Dr. Nasr Abboushi

With these parameters defined, ACI Code 13.6.4 distributes the negative and positive
moments between column strips and middle strips, assigning to the column strips the
percentages of positive and negative moments shown in the next table. Linear interpolations
are to be made between the values shown.

Example (Calculation of Moments in an Interior Panel of a Flat Plate).


An interior panel of a flat-plate floor in an apartment building shown below. The slab
thickness is
. The slab supports a design live load of
and a superimposed
dead load of
for partitions. The columns and slab have the same strength of
concrete. The story height is
. Compute the column-strip and middle-strip moments
in the short direction of the panel.
Solution:
1. Compute the factored loads.

2. Compute the moments in the short span of the slab.


(a)

Compute

and

and divide the slab into column and middle strips.

The column strip extends the smaller of


or
on each side of the column
centerline (ACI Code Section 13.2.1). Thus, the column strip extends
on each
side of column centerline. The total width of the column strip is
. Each half-middle strip
extends from the edge of the column strip to the centerline of the panel. The total width of
two half-middle strips is
.
299

Reinforced Concrete II

(b)

Compute

(c)

Divide

Dr. Nasr Abboushi

into negative and positive moments. From ACI Code Section 13.6.3.2,

Negative moment
Positive moment
This process is illustrated in the figure (a) below, and the resulting distribution of total
moments is shown in figure (b).
300

Reinforced Concrete II
(d)

Dr. Nasr Abboushi

Divide the moments between the column and middle strips.

Negative moments: From Table (page 299) for


are no beams between columns and in this panel),

Half of this

because there

goes to each adjacent half-middle strip. Because the

adjacent bays have the same width, , a similar moment will be assigned to the other half of
each middle strip so that the total middle-strip negative moment is
.
Positive moments: From Table (page 299), where

These calculations are illustrated in figure (a) below. The resulting distributions of moments
in the column strip and middle strip are summarized in figure (c).

301

Reinforced Concrete II

Dr. Nasr Abboushi

In the next figure, the moments in each strip have been divided by the width of that strip.

3. Compute the moments in the long span of the slab. Although it was not asked for in
this example, in a slab design, it now would be necessary to repeat steps 2(a) to 2(d)
for the long span.
4. Design the middle and the column strips for these moments and find the
reinforcement area for each strip.

9.10

SLAB ANALYSIS BY THE EQUIVALENT FRAME METHOD (EFM).

The ACI Code presents two general methods for calculating the longitudinal distribution of
moments in two-way slab systems. These are the direct-design method (presented in the
previous section) and equivalent-frame methods, which are presented in this section.
Equivalent-frame methods are intended for use in analyzing moments in any practical slab
column frame. Their scope is thus wider than the direct-design method, which is subject to
the limitations presented in Section 9.9.1 (ACI Code Section 13.6.1). In the direct-design
method, the statical moment, is calculated for each slab span. This moment is then divided
between positive- and negative-moment regions using arbitrary moment coefficients, which
are adjusted to reflect pattern loadings. For equivalent-frame methods, a stiffness analyses
of a slabcolumn frame is used to determine the longitudinal distribution of bending
moments, including possible pattern loadings. The transverse distribution of moments to
column and middle strips, as defined in the prior section, is the same for both methods.
The design requirements can be explained as follows.
1. Description of the equivalent frame: An equivalent frame is a two-dimensional
building frame obtained by cutting the three-dimensional building along lines
midway between columns (see the figure below). The resulting equivalent frames are
considered separately in the longitudinal and transverse directions of the building.
302

Reinforced Concrete II

Dr. Nasr Abboushi

For vertical loads, each floor is analyzed separately, with the far ends of the upper
and lower columns assumed to be fixed. The slab-beam may be assumed to be fixed
at any support two panels away from the support considered, because the vertical
loads contribute very little to the moment at that support. For lateral loads, the
equivalent frame consists of all the floors and extends for the full height of the
building, because the forces at each floor are a function of the lateral forces on all
floors above the considered level. Analysis of frames can also be made using
computer programs.

2. Load assumptions: When the ratio of the service live load to the service dead load is
less than or equal to
, the structural analysis of the frame can be made with the
factored dead and live loads acting on all spans instead of a pattern loading. When
the ratio of the service live load to the service dead load is greater than
, pattern
loading must be used, considering the following conditions:
303

Reinforced Concrete II

Dr. Nasr Abboushi

a. Only
of the full-factored live load may be used for the pattern loading
analysis.
b. The maximum negative bending moment in the slab at the support is
obtained by loading only the two adjacent spans.
c. The maximum positive moment near a midspan is obtained by loading only
alternate spans.
d. The design moments must not be less than those occurring with a fullfactored live load on all panels (ACI Code, Section 13.7.6).
e. The critical negative moments are considered to be acting at the face of a
rectangular column or at the face of the equivalent square column having
the same area for nonrectangular sections.
3. Slab-beam moment of inertia: The ACI Code specifies that the variation in moment
of inertia along the longitudinal axes of the columns and slab beams must be taken
into account in the analysis of frames. The critical region is located between the
centerline of the column and the face of the column, bracket, or capital. This region
may be considered as a thickened section of the floor slab. To account for the large
depth of the column and its reduced effective width in contact with the slab beam,
the ACI Code, Section 13.7.3.3, specifies that the moment of inertia of the slab beam
between the center of the column and the face of the support is to be assumed equal
to that of the slab beam at the face of the column divided by the quantity

, where is the column width in the transverse direction and is the


width of the slab beam. The area of the gross section can be used to calculate the
moment of inertia of the slab beam.
4. Column moment of inertia: The ACI Code, Section 13.7.4, states that the moment of
inertia of the column is to be assumed infinite from the top of the slab to the bottom
of the column capital or slab beams.

304

Reinforced Concrete II

5. Column stiffness,

where

Dr. Nasr Abboushi

, is defined by

is the sum of the stiffness of the upper and lower columns at their ends,

)
)

6. Column moments: In frame analysis, moments determined for the equivalent


columns at the upper end of the column below the slab and at the lower end of the
column above the slab must be used in the design of a column.
7. Negative moments at the supports: The ACI Code, Section 13.7.7, states that for an
interior column, the factored negative moment is to be taken at the face of the
column or capital but at a distance not greater than
from the center of the
column. For an exterior column, the factored negative moment is to be taken at a
section located at half the distance between the face of the column and the edge of
the support. Circular section columns must be treated as square columns with the
same area.
8. Sum of moments: A two-way slab floor system that satisfied the limitations of the
direct design method can also be analyzed by the equivalent frame method. To
ensure that both methods will produce similar results, the ACI Code, Section 13.7.7,
states that the computed moments determined by the equivalent frame method may
be reduced in such proportion that the numerical sum of the positive and average
negative moments used in the design must not exceed the total statical moment,
.

9.11

SHEAR DESIGN IN FLAT PLATES.

Shear strength of two-way slabs was discussed in section 9.6.


Shear Reinforcement for Two-Way Slabs, two types of shear reinforcement will be discussed
only:
Stirrups:
ACI Code Section 11.11.3 allows the use of single-leg, multiple-leg and closed stirrups,
provided there are longitudinal bars in all corners of the stirrups.
Stirrups are allowed in slabs with effective depths, , that exceed the larger of
or
16 times the stirrup diameter. The precision required to bend and place either the closed
stirrups or the multiple-leg stirrups makes these types of shear reinforcement laborintensive and expensive. As a result, shear reinforcement consisting of stirrups or bent
reinforcement is not used widely.
305

Reinforced Concrete II

Dr. Nasr Abboushi

According to ACI Code Sections:


11.11.3.1 shall be computed by Eq. (11-2) (
greater than
In Eq. (11-15) (

, and
),

), where

shall not be taken

shall be calculated in accordance with 11.4.


shall be taken as the cross-sectional area of all legs

of reinforcement on one peripheral line that is geometrically similar to the


perimeter of the column section.
11.11.3.2

shall not be taken greater than

11.11.3.3 The distance between the column face and the first line of stirrup legs that
surround the column shall not exceed
. The spacing between adjacent stirrup legs in the
first line of shear reinforcement shall not exceed
measured in a direction parallel to the
column face. The spacing between successive lines of shear reinforcement that surround the
column shall not exceed
measured in a direction perpendicular to the column face
Headed Shear Studs:
The headed shear studs shown in the figure below are permitted by the ACI Code Section
11.11.5. They act in the same mechanical manner as a stirrup leg, but the head of the shear
stud is assumed to provide better anchorage than a bar hook.
Headed shear-stud reinforcement at a slab-column connection consists of rows of vertical
rods, each with a circular head or plate welded or forged on the top end, as shown. These
rows are placed to extend out from the corners of the column. To aid in the handling and
306

Reinforced Concrete II

Dr. Nasr Abboushi

placement of the shear studs and to anchor the lower ends of the studs, they generally are
shop-welded to flat steel bars at the desired spacing. The vertical rods are referred to as
headed shear reinforcement or headed shear studs. The assembly of studs plus the bar is
called a stud rail.
ACI Section 11.11.5 Headed shear stud reinforcement, placed perpendicular to the plane
of a slab or footing, shall be permitted in slabs and footings in accordance with 11.11.5.1
through 11.11.5.4. The overall height of the shear stud assembly shall not be less than the
thickness of the member less the sum of:
(1) the concrete cover on the top flexural reinforcement;
(2) the concrete cover on the base rail; and
(3) one-half the bar diameter of the tension flexural reinforcement.
Where flexural tension reinforcement is at the bottom of the section, as in a footing, the
overall height of the shear stud assembly shall not be less than the thickness of the member
less the sum of:
(1) the concrete cover on the bottom flexural reinforcement;
(2) the concrete cover on the head of the stud; and
(3) one-half the bar diameter of the bottom flexural reinforcement.
11.11.5.1 For the critical section defined in 11.11.1.2, shall be computed using
Eq. (11-2) (
respectively.

), with

and

not exceeding

shall be calculated using Eq. (11-15) (

) with

and

equal to the cross-

sectional area of all the shear reinforcement on one peripheral line that is approximately
parallel to the perimeter of the column section, where
is the spacing of the peripheral
shall not be less than .

lines of headed shear stud reinforcement.

11.11.5.2 The spacing between the column face and the first peripheral line of
shear reinforcement shall not exceed
. The spacing between peripheral lines of shear
reinforcement, measured in a direction perpendicular to any face of the column, shall be
constant. For prestressed slabs or footings satisfying 11.11.2.2, this spacing shall not exceed
; for all other slabs and footings, the spacing shall be based on the value of the shear
stress due to factored shear force and unbalanced moment at the critical section defined in
11.11.1.2, and shall not exceed:
(a)
where maximum shear stresses due to factored loads are less than or
equal to
;
(b)
where maximum shear stresses due to factored loads are greater than
.
11.11.5.3 The spacing between adjacent shear reinforcement elements, measured
on the perimeter of the first peripheral line of shear reinforcement, shall not exceed .
11.11.5.4 Shear stress due to factored shear force and moment shall not exceed

at the critical section located

outside the outermost peripheral line of shear

reinforcement.

307

Reinforced Concrete II

Dr. Nasr Abboushi

Example (Checking One-Way and Two-Way Shear at an Interior Column in a Flat Plate):
The figure below shows an interior column in a large uniform flat-plate slab. The slab is
thick. An average effective depth, , as shown, normally is used in shear strength
calculations for two-way slabs. Both one-way and two-way punching shear usually is checked
near columns where top reinforcement is used in both principal directions to resist negativebending moments. ACI Code Section 7.7.2(c) states that the minimum clear cover for slab
reinforcement is
. Thus, assuming
bars are used as flexural reinforcement, the
average value for determining shear strength
of the slab is
The slab supports a uniform, superimposed dead load of
and a uniform,
superimposed live load of
. The normal-weight concrete has a compressive
strength of
. Check whether the shear capacity is adequate.
308

Reinforced Concrete II

Dr. Nasr Abboushi

Solution:
1. Determine the factored uniform load.

2. Check the one-way shear. One-way shear is critical at a distance from the face of
the column. Thus, the critical sections for one-way shear are AA and BB.
The loaded areas causing shear on these sections are cross hatched. Their outer boundaries
are lines of symmetry on which
Because the tributary area for section AA is larger,
this section will be more critical.
(c) Compute
at section AA.
(d)

Compute
we have

for one-way shear. Because there is no shear reinforcement,

309

Reinforced Concrete II

where

Dr. Nasr Abboushi

for one-way shear is

the slab is OK in one-way shear.


3. Check the two-way punching shear. Punching shear is critical on a rectangular section
located at
away from the face of the column. The load on the cross-hatched area
causes shear on the critical perimeter. Once again, the outer boundaries of this area
are lines of symmetry, where
is assumed to be zero.

Now,

(a)

Compute

(b)

Compute

on the critical perimeter for two-way shear.


for the critical section. The length of the critical perimeter is

is to be taken as the smallest of the following:


(

)
(

(
)

310

(
)

)
(

Reinforced Concrete II

Dr. Nasr Abboushi

Therefore, the smallest value is


(

So
Because

exceeds

the slab is OK in two-way shear.

Example (Design of an integral beam with vertical stirrups):


The flat plate slab with
total thickness and
effective depth is carried by
square columns
on centers in each direction. A factored load of
must be
transmitted from the slab to a typical interior column. Concrete and steel strengths used are,
respectively,
and
. Determine if shear reinforcement is required
for the slab; and if so, design integral beams with stirrups to carry the excess shear.
Solution:
The design shear strength of the concrete alone at the critical section
the column, is the smallest of the following:
(

)
(

(
)

(
)

from the face of

)
(

where

Therefore, the smallest value is

This is less than


, indicating that shear reinforcement is required. The effective
depth
just satisfies the minimum allowed to use stirrup reinforcement, as
described in the beginning of this Section.
In this case, the maximum design strength allowed by the ACI Code is

satisfactorily above the actual . When shear is resisted by combined action of concrete and
bar reinforcement, the concrete contribution is reduced to

311

Reinforced Concrete II

The

Dr. Nasr Abboushi

vertical closed hoop stirrups will be used since

diameter (

must be

times the stirrup

) and arranged along four integral beams as shown below.

Thus, the
provided is
at the first critical section, a distance
from the column face, and the required spacing can be found from:

The spacing

less than the maximum spacing of

, and

stirrups

at a constant spacing of
will be used. In other cases, stirrup spacing might be
increased with distance from the column, as excess shear is less, although this would
complicate placement of the reinforcement and generally save little steel.
The required perimeter of the second critical section, at which the concrete alone can carry
the shear, is found from the controlling equation (

from which the minimum perimeter


equations for :
)
(

(
)

. Using this value of

in the other

)
)

The first equation governs. It is easily confirmed that


projection of the critical section past the face of
the column of
.
(

) as follows:

requires a minimum

Five stirrups at a constant


spacing will be
sufficient, the first placed at
from
the column face, as indicated in the figure below.
This provides a perimeter
at the second
critical section:
(
)
which exceeds the requirement.
Note: the projection distance
can be
calculated from the face of the column and assuming that
(

)
312

is the column width.

Reinforced Concrete II

Dr. Nasr Abboushi

Four longitudinal
bars will be provided inside the corners of each closed hoop stirrup,
as shown, to provide for proper anchorage of the shear reinforcement.
Note that the approach taken here is somewhat conservative because the portion of the slab
load applied inside the perimeter of the critical section does not act on that section and can
thus be subtracted from the factored load of
.

Example (Design of an Interior SlabColumn Connection with Headed Shear Reinforcement


Studs):
A 20-cm-thick flat-plate slab with
flexural reinforcement is supported by
square columns spaced at
on centers N-S and
on centers E-W. The
service loads on the slab are dead load
(including self-weight) and live
load
.The normalweight concrete has a compressive strength of
. Check the capacity of an interior slab-column connection. If necessary, design
shear reinforcement using headed-shear studs.
Solution:
1. Select the critical section for two-way shear around the column. At this stage in the
calculations, the designer does not know whether shear reinforcement will be
required.
We will assume it is not and will redo the calculations if we are wrong. Assuming
flexural reinforcement, the average effective depth of the slab is
The inner critical shear section for two-way shear in a flat plate extends around the column
at
from the face of the column, as shown in the figure below.
The length of one side of the critical shear section around the column is
giving a shear perimeter
The area enclosed within the critical shear section is
313

Reinforced Concrete II

Dr. Nasr Abboushi

2. Compute the shear acting on the critical shear section. The load combinations from
ACI Code Section 9.2 will be used to compute the total factored dead and live loads.
The basic combination for gravity load is
The factored shear force on the critical shear section is
Compute
Now,

for the critical section:

is to be taken as the smallest of the following:


(

)
(

(
)

(
)

)
(

Therefore, the last equation governs

So
Because
less than
, shear reinforcement is required at
the critical shear section. Using shear studs as shear reinforcement results in

This gives

The maximum value of

allowed with headed-shear studs is

3. Lay out the punching shear reinforcement. Rows of shear studs welded to bars will
be placed parallel and perpendicular to the main slab reinforcement to cause the
least disruption in the placement of the main slab steel. Using a trial and error
process:
Try eight stud rails, each with seven
-diameter studs (
) with
-diameter heads, and
(typical for shear studs).
The spacing to the first set of shear studs, , is to be taken less than or equal to
. Thus,
select
(see figure). Before proceeding to layout the subsequent rows of shear
studs, the shear strength should be checked at the inner critical section. In Equation
, the area provided by the inner row of shear studs is

314

Reinforced Concrete II

Dr. Nasr Abboushi

Then, assuming only one line of shear studs are


crossed by the potential critical shear crack
nearest the column
,
This exceeds the required value of
.

Try eight stud rails with the first stud located at


from the column face.
Subsequent studs are at a spacing of
with seven
-diameter headed shear
studs per rail.
The outermost studs are at
from the face of the column, and the
outer critical section is
from the face of the column.
315

Reinforced Concrete II

Dr. Nasr Abboushi

The outer critical-shear section is a series of straight line segments passing through points
located
outside the outer shear studs, as shown in the figure. The perimeter of this
peripheral line is
(

4. Check the shear stresses on the outer critical section. The factored shear force on the
concrete at the outer critical section is
and

The shear stress on the outer critical section is limited to

Because this is larger than

, the design is OK.

316

Reinforced Concrete II

CHAPTER 10

Dr. Nasr Abboushi

STAIRS

10.1 INTRODUCTION
Stairs must be provided in almost all buildings, either low-rise or high-rise, even if adequate
numbers of elevators are provided. Stairs consist of rises, runs (or treads), and landings. The
total steps and landings are called a staircase. The rise is defined as the vertical distance
between two steps, and the run is the depth of the step. The landing is the horizontal part of
the staircase without rises.

317

Reinforced Concrete II

Dr. Nasr Abboushi

10.2 TYPES OF STAIRS


There are different types of stairs, which depend mainly on the type and function of the
building and on the architectural requirements. The most common types are as follows.
1. Single-flight stairs: The structural behavior of a flight of stairs is similar to that of a
one-way slab supported at both ends. The thickness of the slab is referred to as the
waist. When the flight of stairs contains landings, it may be more economical to
provide beams at and between landings (see next figure). If such supports are
not provided, which is quite common, the span of the staircase will increase by the
width of two landings and will extend between and . In residential buildings, the
landing width is in the range of
, and the total distance between and
is about 6 m.

318

Reinforced Concrete II

Dr. Nasr Abboushi

An alternative method of supporting a single flight of


stairs is to use stringers, or edge beams, at the two sides
of the stairs; the steps are then supported between the
beams.
2. Double-flight stairs: It is more
convenient in most buildings to build
the staircase in double flights between
floors. The types commonly used are
quarter-turn and closed-or open-well

stairs, as shown in figure. For the


structural analysis of the stairs, each
flight is treated as a single flight and is
considered supported on two or more
beams, as shown in the previous
figure (page 318). The landing extends
in the transverse direction between
two supports and is designed as a oneway slab. In the case of open-well
stairs, the middle part of the landing
carries a full load, whereas the two
end parts carry half-loading only, as
shown in figure (d). The other halfloading is carried in the longitudinal
direction by the stair flights, sections
A-A and B-B.
3. Three or more flights of stairs: In some
cases, where the overall dimensions of
the staircase are limited, three or four
flights may be adopted. Each flight will
be treated separately, as in the case of
double-flight staircases.
319

Reinforced Concrete II

Dr. Nasr Abboushi

4. Cantilever stairs: Cantilever stairs are used mostly in fire-escape stairs, and they are
supported by concrete walls or beams. The stairsteps may be of the full-flight type,
projecting from one side of the wall, the half-flight type, projecting from both sides of
the supporting wall, or of the semispiral type. In this type of stairs, each step acts as a
cantilever, and the main reinforcement is placed in the tension side of the run and
the bars are anchored within the concrete wall. Shrinkage and temperature
reinforcement is provided in the transverse direction.

320

Reinforced Concrete II

Dr. Nasr Abboushi

Another form of a cantilever stair is that using open-riser steps supported by a central beam,
as shown below. The beam has a slope similar to the flight of stairs and receives the steps on
its horizontally prepared portions. In most cases, precast concrete steps are used, with
special provisions for anchor bolts that fix the steps into the beam.
5. Precast flights of stairs: The speed of construction in some projects requires the use
of precast flights of stairs. The flights may be cast separately and then fixed to castin-place landings. In other cases, the flights, including the landings, are cast and then
placed in position on their supporting walls or beams. They are designed as simply
supported one-way slabs with the main reinforcement at the bottom of the stair
waist. Adequate reinforcement must be provided at the joints.

Provisions must be made for lifting and handling the precast stair units by providing lifting
holes or inserting special lifting hooks into the concrete. Special reinforcement must be
provided at critical locations to account for tensile stresses that will occur in the stairs from
the lifting and handling process.
321

Reinforced Concrete II

Dr. Nasr Abboushi

6. Free-standing staircase: In this type of stairs, the landing projects into the air without
any support at its end. The stairs behave in a springboard manner, causing torsional
stresses in the slab.

322

Reinforced Concrete II

Dr. Nasr Abboushi

Three systems of loading must be considered in the design of this type of stairs, taking into
consideration that torsional moments will develop in the slab in all cases:
a. When the live load acts on the upper flight and half the landing only (Case 1), the
upper flight slab will be subjected to tensile forces in addition to bending moments,
whereas the lower flight will be subjected to compression forces, which may cause
buckling of the slab.
b. When the live load acts on the lower flight and half the landing only (Case 2), the
upper flight slab will be subjected to tensile forces, whereas the lower flight will be
subjected to bending moment and compression forces.
c. When the live load acts on both upper and lower flights, the loading of one flight will
cause the twisting of the other. The torsional stresses developed in the stairs require
adequate reinforcement in both faces of the stair slabs and the landing. Transverse
reinforcement in the slab and the landing must be provided in both faces of the
concrete in the shape of closed U-bars lapping at midwidth of the stairs. Typical
reinforcement details are shown in the figure below.

323

Reinforced Concrete II

Dr. Nasr Abboushi

This type of stairs is favored by architects and sometimes called a pliers-shaped staircase or
jackknife staircase.
For practical design, the parameters may be chosen as follows: flight width between
and
, horizontal span between
and
, total (light height between
and
, and slab thickness between
and
.
The above information is a guide to help the designer to choose the right parameters for an
economical design.
7. Run-riser stairs: Run-riser stairs are stepped underside stairs that consist of a number
of runs and risers rigidly connected without the provision of the normal waist slab.
This type of stairs has an elegant appearance and is sometimes favored by architects.

The structural analysis of run-riser stairs can be simplified by assuming that the effect of
axial forces is negligible and that the load on each run is concentrated at the end of the run
324

Reinforced Concrete II

Dr. Nasr Abboushi

(see next figure). For the analysis of a simply supported flight of stairs, consider a simple
flight of two runs,
, subjected to a concentrated load at . Because joints and
are rigid, the moment at joint is equal to the moment at , or

where is the width of the run. The moment in rise,


, is constant and is equal to
.
When the rise is absent, the stairs,
, act as a simply supported beam, and the maximum
bending moment occurs at midspan with value

For a flight of stairs that consists of a number of runs and risers, the same approach can be
used; the bending moment diagram is shown below. The moment in
is constant and is
equal to the moment at joint , or
. Similarly,
, and

325

Reinforced Concrete II

Dr. Nasr Abboushi

8. Helical stairs (open-spiral stairs): A helical staircase is a three-dimensional structure,


which usually has a circular shape in plan. It is a distinctive type of stairs used mainly
in entrance halls, theater foyers, and special low-rise office buildings. The cost of a
helical stair is much higher than that of a normal staircase.

The stairs may be supported at some edges within adjacent walls or may be designed as a
free-standing helical staircase, which is most popular. The structural analysis of helical
staircases is complicated. Design charts for helical stairs are also prepared. Under load, the
flight slab will be subjected to torsional stresses throughout. The upper landing will be
subjected to tensile stresses, whereas compressive stresses occur at the bottom of the flight.
The forces acting at any section may consist of vertical moment, lateral moment, torsional
moment, axial force, shearing force across the waist of the stairs, and radial horizontal
shearing force. The main longitudinal reinforcement consists of helical bars placed in the
concrete waist of the stairs and runs from the top landing to the bottom support. The
transverse reinforcement must be in a closed stirrup form to resist torsional stresses or in a
U-shape lapped at about the midwidth of the stairs.
Based on many studies, the possible practical dimensions may be chosen as follows: Total
subtended arc between
and
, stair width between
and
, stairs slab
thickness between
and
and stair height between and
.
The above information can be used as a guide to achieve a proper and economical design of
helical staircase.
326

Reinforced Concrete II

Dr. Nasr Abboushi

An alternative method of providing a helical stair is to use a central helical girder located at
the midwidth of the stairs and have the steps project equally on both sides of the girder.
Each step is analyzed as a cantilever, and the reinforcement bars extend all along the top of
the run. Precast concrete steps may be used and can be fixed to specially prepared
horizontal faces at the top surfaces of the girder.
10.3

SLAB TYPE STAIRS. STRUCTURAL SYSTEM.

In the second and third types (slab type stairs), the main supporting element could be the
slab itself. The flight could be supported on the landing, which is in turn supported on the
supporting beams. From the structural point of view, it is better that the main supporting
element is spanning in the short direction. However, this depends on the surrounding
beams. If the beams exist around the perimeter of the stair well or at least along the long
sides, solution A in the figure below is more economical. If the supporting beams are only at
the short side, solution B is the only valid structural system.

Since the landing and the stairs are not straight, internal forces are generated in these
sloped elements. The two tensile forces and generated at the kink, producing a third
outward force as shown in the next figure. This force tends to cause splitting cracks if the
produced stresses exceed concrete tensile strength. Thus, tension reinforcement should be
extended from each side so that no outward force is generated.
327

Reinforced Concrete II

Dr. Nasr Abboushi

328

Reinforced Concrete II

Dr. Nasr Abboushi

Example
Design the staircase shown below, which carries a uniform live load of
rise of
and a run of
. Use
and

. Assume a
.

Solution
1. Structural system: If no stringer beam is used, one of the four possible solutions
shown in figure (page 318) may be adopted. When no intermediate supports are
used, the flight of stairs will be supported at the ends of the upper and lower
landings. This structural system will be adopted in this example.
2. Minimum slab thickness for deflection is (for a simply supported one-way solid slab)

In the case presented here, where the slab ends are cast with the supporting beams and
additional negative reinforcement is provided, minimum thickness can be assumed to be

Take

3. Loads: The applied live loads are based on the plan area (horizontal projection), while
the dead load is based on the sloped length. To transform the dead load into
horizontal projection the figure below explains how.
Flight Dead Load computation:
(

329

cos

Reinforced Concrete II

Dr. Nasr Abboushi

Quality Density

Material
Tiles

mortar

Stair steps

Reinforced Concrete
solid slab
Plaster

cos
cos

Total Dead Load,


Landing Dead Load computation:
Material

Quality Density

Tiles
mortar
Reinforced Concrete solid slab
Plaster
Total Dead Load

8.01

Live Load:
Total factored Load:

Because the load on the landing is carried into two directions, only half the load will be
considered in each direction
.

330

Reinforced Concrete II

Dr. Nasr Abboushi

4. Check for shear strenght:


Assume bar diameter
for main reinforcement.

Assume beam width


(

- for shear.

The thickness of the slab is adequate enough.


5. Calculate the maximum bending moment and steel reinforcement:
(

Assume bar diameter

for main reinforcement.

Use

then

Take

Step ( ) is the smallest of:


1.
2.

331

Reinforced Concrete II

Dr. Nasr Abboushi

(
s

6. Temperature and shrinkage reinforcement.


(
)

Take

Step (

) is the smallest of:

1.
2.
s

If the slab will be cast monolithically with its supporting beams, additional reinforcement
must be provided at the top of the upper and lower landings. Details of stair reinforcement
are shown in the figure (page 333).
7. Design of landings: Considering a 1-m length of the landing, the load on the landing is
shown in the next figure. The middle
will carry a full load, whereas the two
1.5-m lengths on each side will carry half the ultimate load.

332

Reinforced Concrete II

Dr. Nasr Abboushi

333

Reinforced Concrete II

Dr. Nasr Abboushi

Assume bar diameter


for main reinforcement. Because the bars in the landing will be
placed on top of the main stair reinforcement

then provide

Use

then

Take

Step ( ) is the smallest of:


1.
2.
(

(
s

8. The transverse beams at the landing levels must be designed to carry loads from
stairs (
) in addition to their own weight and the weight of the wall
above.

334

Reinforced Concrete II

Dr. Nasr Abboushi

Example
Design the staircase shown below, which carries a uniform live load of
rise of
and a run of
. Use
and

. Assume a
.

Solution
1. Minimum slab thickness for deflection is (for a simply supported one-way solid slab)

Take

2. Loads:
Flight Dead Load computation:
(

Material

Quality Density

Tiles

mortar

Stair steps

Reinforced Concrete
solid slab
Plaster

cos
cos

Total Dead Load,


335

Reinforced Concrete II

Dr. Nasr Abboushi

Landing Dead Load computation:

Quality Density

Material
Tiles
mortar
Reinforced Concrete solid slab
Plaster
Total Dead Load

8.01

Live Load:
Total factored Load:

3. Design of slab S1:


Slab S1 is supported at the centerline of slabs S2 and S3.

The reaction at each end

Check for shear strenght:


Assume bar diameter
for main reinforcement.

Take the maximum shear as the support reaction

- for shear.

336

Reinforced Concrete II

Dr. Nasr Abboushi

The thickness of the slab is adequate enough.


Calculate the maximum bending moment and steel reinforcement:
(

Assume bar diameter

for main reinforcement.

Use

then

Take

Step ( ) is the smallest of:


1.
2.
(

(
s

Temperature and shrinkage reinforcement.


)

337

Reinforced Concrete II

Dr. Nasr Abboushi

Take

Step (

) is the smallest of:

1.
2.
s

4. Design of slab S2:


Slab S2 is supported on the beams located on axis 1,2 at the floor level. The reaction of the
slab S1 is applied at the centerline of the slab S2. Since the width of S2 is
, the reaction
will be distributed along this width. Thus the load per meter
equals
(

or
(

of the slab S1 is applied at the middle of the slab.

338

Reinforced Concrete II

Dr. Nasr Abboushi

The reaction at each end

Check for shear strenght:


Assume bar diameter
for main reinforcement.

Take the maximum shear as the support reaction

- for shear.

The thickness of the slab is adequate enough.


Calculate the maximum bending moment at midspan and the steel
reinforcement:
(

Assume bar diameter

for main reinforcement.

Use

then

Take

Step ( ) is the smallest of:


1.
339

Reinforced Concrete II

Dr. Nasr Abboushi

2.
(

(
s

Temperature and shrinkage reinforcement.


)

Take

Step (

) is the smallest of:

1.
2.
s

5. Design of slab S3:


Slab S3 is supported on the beams, the reaction of the slab S1 is applied at the middle of the
slab:

Design the slab S3 for flexure and shear as for slabs S1 and S2.
340

Reinforced Concrete II

CHAPTER 11

11.1

Dr. Nasr Abboushi

FOOTINGS AND FOUNDATIONS

INTRODUCTION.

Reinforced concrete footings are structural members used to support columns and walls and
to transmit and distribute their loads to the soil. The design is based on the assumption that
the footing is rigid, so that the variation of the soil pressure under the footing is linear.
Uniform soil pressure is achieved when the column load coincides with the centroid of the
footing. Although this assumption is acceptable for rigid footings, such an assumption
becomes less accurate as the footing becomes relatively more flexible. The proper design of
footings requires that
1. The load capacity of the soil is not exceeded.
2. Excessive settlement, differential settlement, or rotations are avoided.
3. Adequate safety against sliding and/or overturning is maintained.
The most common types of footings used in buildings are the single footings and wall
footings. When a column load is transmitted to the soil by the footing, the soil becomes
compressed. The amount of settlement depends on many factors, such as the type of soil,
the load intensity, the depth below ground level, and the type of footing. If different footings
of the same structure have different settlements, new stresses develop in the structure.
Excessive differential settlement may lead to the damage of nonstructural members in the
buildings or even failure of the affected parts.
Vertical loads are usually applied at the centroid of the footing. If the resultant of the applied
loads does not coincide with the centroid of the bearing area, a bending moment develops.
In this case, the pressure on one side of the footing will be greater than the pressure on the
other side.

341

Reinforced Concrete II

Dr. Nasr Abboushi

If the bearing soil capacity is different under different footingsfor example, if the footings
of a building are partly on soil and partly on rocka differential settlement will occur. It is
usual in such cases to provide a joint between the two parts to separate them, allowing for
independent settlement.
The depth of the footing below the ground level is an important factor in the design of
footings. This depth should be determined from soil tests, which should provide reliable
information on safe bearing capacity at different layers below ground level. Soil test reports
specify the allowable bearing capacity to be used in the design. In cold areas where freezing
occurs, frost action may cause heaving or subsidence. It is necessary to place footings below
freezing depth to avoid movements.
11.2

TYPES OF FOOTINGS.

Different types of footings may be used to support building columns or walls. The most
common types are as follows:
1. Wall footings are used to support structural walls that carry loads from other floors
or to support nonstructural walls. They have a limited width and a continuous length
under the wall. Wall footings may have one thickness, be stepped, or have a sloped
top.
2. Isolated, or single, footings are used to support single columns. They may be square,
rectangular, or circular. Again, the footing may be of uniform thickness, stepped, or
have a sloped top. This is one of the most economical types of footings, and it is used
when columns are spaced at relatively long distances. The most commonly used are
square or rectangular footings with uniform thickness.

342

Reinforced Concrete II

Dr. Nasr Abboushi

3. Combined footings usually support two columns or three columns not in a row. The
shape of the footing in plan may be rectangular or trapezoidal, depending on column
loads. Combined footings are used when two columns are so close that single
footings cannot be used or when one column is located at or near a property line.
4. Cantilever, or strap, footings consist of two single footings connected with a beam or
a strap and support two single columns. They are used when one footing supports an
eccentric column and the nearest adjacent footing lies at quite a distance from it.
This type replaces a combined footing and is sometimes more economical.
5. Continuous footings support a row of three or more columns. They have limited
width and continue under all columns.
6. Raft, or mat, foundations consist of one footing, usually placed under the entire
building area, and support the columns of the building. They are used when:
a. The soil-bearing capacity is low.
b. Column loads are heavy.
c. Single footings cannot be used.
d. Piles are not used.
e. Differential settlement must be reduced through the entire footing system.
2. Pile caps are thick slabs used to tie a group of piles together and to support and
transmit column loads to the piles.

11.3

DISTRIBUTION OF SOIL PRESSURE. GROSS AND NET SOIL PRESSURES.

The figure below shows a footing supporting a single column. When the column load, P, is
applied on the centroid of the footing, a uniform pressure is assumed to develop on the soil
surface below the footing area. However, the actual distribution of soil pressure is not
uniform but depends on many factors, especially the composition of the soil and the degree
of flexibility of the footing. For example, the distribution of pressure on cohesionless soil
(sand) under a rigid footing is shown. The pressure is maximum under the center of the
footing and decreases toward the ends of the footing. The cohesionless soil tends to move
from the edges of the footing, causing a reduction in pressure, whereas the pressure

343

Reinforced Concrete II

Dr. Nasr Abboushi

increases around the center to satisfy equilibrium conditions. If the footing is resting on a
cohesive soil such as clay, the pressure under the edges is greater than at the center of the
footing. The clay near the edges has a strong cohesion with the adjacent clay surrounding
the footing, causing the nonuniform pressure distribution.
The allowable bearing soil pressure, , is usually determined from soil tests. The allowable
values vary with the type of soil, from extremely high in rocky beds to low in silty soils.
Maximum allowable
soil pressure [
]

Class of Material

of ultimate
crushing strength

Rock
Compact coarse sand, compact fine sand,
hard clay, or sand clay
Medium stiff clay or sandy clay
Compact inorganic sand and silt mixtures
Loose sand
Soft sand clay or clay
Loose inorganic sand-silt mixtures
Loose organic sand-silt mixtures, muck, or
bay mud

The figure below shows a


-thick spread footing with a column at its center and with its
top surface located
below the ground surface. There is no column load at this stage.
The total downward load from the weights of the soil and the footing is
. This is
balanced by an equal, but opposite, upward pressure. As a result, the net effect on the
concrete footing is zero. There are no moments or shears in the footing due to this loading.
When the column load

is added, the pressure under the footing increases by

. The

total soil pressure is


. This is referred to as the gross soil pressure and must
not exceed the allowable soil pressure, . When moments and shears in the concrete
footing are calculated, the upward and downward pressures of
cancel out,
leaving only the net soil pressure, , to cause internal forces in the footing.
In design, the area of the footing is selected so that the gross soil pressure does not exceed
the allowable soil pressure. The flexural reinforcement and the shear strength of the footing
are then calculated by using the net soil pressure. Thus, the area of the footing is selected to
be
344

Reinforced Concrete II

Dr. Nasr Abboushi

where and refer to the unfactored service dead and live loads.
Once the area of the footing is known, the rest of the design of the footing is based on soil
stresses due to the factored loads.

345

Reinforced Concrete II

Dr. Nasr Abboushi

11.4 DESIGN CONSIDERATIONS.


Footings must be designed to carry the column loads and transmit them to the soil safely.
The design procedure must take the following strength requirements into consideration:
1. The area of the footing based on the allowable bearing soil capacity.
2. One-way shear.
3. Two-way shear, or punching shear.
4. Bending moment and steel reinforcement required.
5. Bearing capacity of columns at their base and dowel requirements
6. Development length of bars
7. Differential settlement
In this course we will consider the first 4 points only.
11.4.1 Size of footings.
The area of the footings can be determined from the actual external loads (unfactored
forces and moments) such that the allowable soil pressure is not exceeded. In general, for
vertical loads

where the total service load is the unfactored design load.


The area of footing can be determined from the net soil pressure by

Once the area is determined, a factored soil pressure is obtained by dividing the factored
load,
, by the area of the footing. This is required to design the footing
by the strength design method.

The allowable soil pressure,


conditions.

, is obtained from soil test and is based on service load

11.4.2 One-way shear (Beam shear).


For footings with bending action in one direction, the critical section is located at a distance
from the face of the column. The diagonal tension at section m-m in the figure of one way
shear can be checked as was done before in beams. The allowable shear in this case is equal
to

where
width of section m-m. The factored shear force at section m-m can be
calculated as follows:
346

Reinforced Concrete II

Dr. Nasr Abboushi

(
If no shear reinforcement is to be used, then

)
can be determined, assuming

11.4.3 Two-way shear (Punching shear).


Two-way shear is a measure of the diagonal tension caused by the effect of the column load
on the footing. Inclined cracks may occur in the footing at a distance
from the face of
the column on all sides. The footing will fail as the column tries to punch out part of the
footing.
The ACI Code, Section 11.11.2 allows a shear strength, , in footings without shear
reinforcement for two-way shear action, the smallest of
(

where

Ratio of long side to short side of the rectangular column.


347

Reinforced Concrete II

Dr. Nasr Abboushi

For shapes other than rectangular, is taken to be the ratio of the longest dimension of the
effective loaded area in the long direction to the largest width in the short direction
(perpendicular to the long direction).
perimeter of the critical section taken at
from the loaded area.
effective depth of footing.
for normal-weight concrete.
is assumed to be:

for interior columns,

for edge columns, and

for corner columns.


Based on the preceding three values of , the effective depth, , required for two-way
shear is the largest obtained from the following formulas assuming
):

11.4.4 Flexural strength and footing reinforcement.


The critical sections for moment occur at the face of the
column (section n-n). The bending moment in each
direction of the footing must be checked and the
appropriate reinforcement must be provided. In square
footings and square columns, the bending moments in
both directions are equal. To determine the
reinforcement required, the depth of the footing in each
direction may be used. Because the bars in one direction
rest on top of the bars in the other direction, the
effective depth, , varies with the diameter of the bars
used.
According to ACI, 7.7, minimum clear cover in cast-inplace concrete against and permanently exposed to
earth (such as footings) should not be less than
.
The ACI Code, Section 10.5, indicates that for structural
slabs of uniform thickness, the minimum area and
348

Reinforced Concrete II

Dr. Nasr Abboushi

maximum spacing of steel bars in the direction of bending shall be as required for shrinkage
and temperature reinforcement (see section 8.4, 8.5 page 195).
The reinforcement in one-way footings
and two-way footings must be
distributed across the entire width of
the footing. In the case of two-way
rectangular footings, the ACI Code,
Section 15.4.4, specifies that in the long
direction, a portion of the total
reinforcement
distributed
uniformly along the width of the
footing. In the short direction, a certain
ratio of the total reinforcement in this
direction must be placed uniformly
within a bandwidth equal to the length
of the short side of the footing
according to

The bandwidth must be centered on the centerline of the column. The remaining
reinforcement in the short direction must be uniformly distributed outside the bandwidth.
This remaining reinforcement percentage shall not be less than that required for shrinkage
and temperature.
When structural steel columns or masonry walls are used, then the critical sections for
moments in footings are taken at halfway between the middle and the edge of masonry
walls and halfway between the face of the column and the edge of the steel base place (ACI
Code, Section 15.4.2).

349

Reinforced Concrete II

Dr. Nasr Abboushi

11.4.5 Transfer of Load from Column to Footing


The column applies a concentrated load on the footing. This load is transmitted by bearing
stresses in the concrete and by stresses in the dowels or column bars that cross the joint.
The design of such a joint is considered in ACI Code Section 15.8. The area of the dowels can
be less than that of the bars in the column above, provided that the area of the dowels is at
least
times the column area (ACI Code Section 15.8.2.1) and is adequate to transmit
the necessary forces. Such a joint is shown below.

Generally, the column bars stop at the bottom of the column, and dowels are used to
transfer forces across the columnfooting joint. Dowels are used because it is awkward to
embed the column steel in the footing, due to its unsupported height above the footing and
the difficulty in locating it accurately. The above figure a shows an
column
with
and
bars. The column is supported on a footing made of
concrete. There are
Grade-420 dowels in the connection. The dowels
extend into the footing a distance equal to the compression development length of a
bottom bar in
concrete (
) and into the column a distance equal to the
greater of
1. the compression lap-splice length for a
bar in
concrete (
), and
2. the compression development length of a
bar in
concrete (
).
350

Reinforced Concrete II

Dr. Nasr Abboushi

This joint could fail by reaching various limit states, including


1. crushing of the concrete at the bottom of the column, where the column bars are no
longer effective,
2. crushing in the footing below the column,
3. bond failure of the dowels in the footing, and
4. failure in the column of the lap splice between the dowels and the column bars.

11.4.6 Bearing Strength.


The total capacity of the column for pure axial load is
, of which
is carried
by the steel and the rest by the concrete, as shown in the previous figure b. At the joint, the
area of the dowels is less than that of the column bars, and the force transmitted by the
dowels is
, where
is the area of the dowels and is that for tied columns. As a
result, the load carried by the concrete has increased. In the above figure, the dowels are
hooked so that they can be supported on and tied
to the mat of footing reinforcement when the
footing concrete is placed. The hooks cannot be
used to develop compressive force in the bars
(ACI Code Section 12.5.5).
The maximum bearing load on the concrete is
defined in ACI Code Section 10.14 as
. If the load combinations from ACI
Code Section 9.2 are used, ACI Code Section
9.3.2.4 gives
for bearing and
is the
area of the contact surface.
When the supporting surface is wider on all sides
than the loaded area, the maximum bearing load
may be taken as

Where

not more than , where

is the

area of the lower base of a right pyramid or cone


formed by extending lines out from the sides of
the bearing area at a slope of 2 horizontal to 1
vertical to the point where the first such line
intersects an edge. This is illustrated in next
figure. The first intersection with an edge occurs
at point B, resulting in the area
shown
crosshatched.
351

Reinforced Concrete II

Dr. Nasr Abboushi

If dowels are needed, the required area of dowels

Two distinct cases must be considered:


(1) joints that do not transmit computed moments to the footing and
(2) joints that do.
These will be discussed separately.

No Moment Transferred to Footing


If no moments are transmitted, or if the eccentricity falls within the kern of the column,
there will be compression over the full section. The total force transferred by bearing is
then calculated as
times the smaller of the bearing stresses allowed on the
column or the footing, where
is total area of the column and
is the area of the bars
or dowels crossing the joint. Any additional load must be transferred by dowels.

Moments Are Transferred to Footing


If moments are transmitted to the footing, bearing stresses will exist over part, but not all,
of the column cross section. The number of dowels required can be obtained by considering
the area of the joint as an eccentrically loaded column with a maximum concrete stress
equal to the smaller of the bearing stresses allowed on the column or the footing. Sufficient
reinforcement must cross the interface to provide the necessary axial load and moment
capacity. Generally, this requires that all the column reinforcement or similar-sized dowel
bars must cross the interface. This steel must be spliced in accordance with the
requirements for column splices.

Practical Aspects
Three other aspects warrant discussion prior to the examples. The minimum cover to the
reinforcement in footings cast against the soil is
(ACI Code Section 7.7.1). This
allows for small irregularities in the surface of the excavation and for potential
contamination of the bottom layer of concrete with soil. Sometimes, the bottom of the
excavation for the footing is covered with a lean concrete seal coat, to prevent the bottom
from becoming uneven after rainstorms and to give a level surface for placing
reinforcement.
The minimum depth of the footing above the bottom reinforcement is
for footings
on soil and
for footings on piles (ACI Code Section 15.7). ACI Code Section 10.6.4,
covering the distribution of flexural reinforcement in beams and one-way slabs, does not
apply to footings.
352

Reinforced Concrete II

11.5

Dr. Nasr Abboushi

SPREAD (ISOLATED) FOOTINGS.

Spread footings are square or rectangular pads that spread a column load over an area of
soil large enough to support the column load. The soil pressure causes the footing to deflect
upward, causing tension in two directions at the bottom. As a result, reinforcement is placed
in two directions at the bottom.

Example (isolated concentrically loaded square column):


Determine the base area and overall thickness for a square spread footing with the following
design conditions:
Service dead load
Service live load
Service surcharge
Permissible (allowable) soil pressure
Soil density
,
.
Solution:
Calculating the weight of footing,
soil, and the surcharge floor load:

weight

of

footing

(assume

weight of soil:

Total surcharge load on foundation:


Net soil pressure,

353

Reinforced Concrete II

Dr. Nasr Abboushi

Required sizes of footing:

Take
Depth of footing and shear design:

One-way shear (Beam shear)


at distance from the face of support:
(

Let

Assume cover 75 mm, and steel bars of


Generally, the thickness of aspread footing is governed by two-way shear. The shear will be
checked on the critical perimeter at
from the face of the column and, if necessary, the
thickness will be increased or decreased. Because there is reinforcement in both directions,
the average will be used:
354

Reinforced Concrete II

Dr. Nasr Abboushi

Two-way shear (Punching shear)


Let
(

)
(

(
)

Take

Try

Design for flexure in long direction:


Take steel bars of

.
355

)
(

Reinforced Concrete II

Take

Dr. Nasr Abboushi

with

Using bars of
instead of
So no need to check for
.

Step

as assumed before makes the effective depth

is the smallest of:

1.
2.

356

larger.

Reinforced Concrete II

Dr. Nasr Abboushi

Design for flexure in short direction:

Take steel bars of

Take

with

Using bars of
instead of
So no need to check for
.

as assumed before makes the effective depth

357

larger.

Reinforced Concrete II

Dr. Nasr Abboushi

0.55 m

Check for the development length as will be discussed later (see chapter 12.)
Design the columnfooting joint.
The column-footing joint is shown here. The factored load at the base of the column is
358

Reinforced Concrete II

Dr. Nasr Abboushi

The maximum bearing load on the bottom of the column (ACI


Code Section 10.14.1) is
where
is the area
of the contact surface between the column and the footing
and
is for the column. When the contact supporting
surface on the footing is wider on all sides than the loaded
area, the maximum bearing load on the top of the footing
may be taken as

where

is the area of the lower base of a right

pyramid or cone as defined earlier. ACI Code Section 9.3.2.4 defines


bearing.

equal to 0.65 for

The allowable bearing on the base of the column is


Note:

here for column.

The allowable bearing on the footing is


By inspection,

for the footing exceeds 2; hence, the


2.8 m

maximum bearing load on the footing is

Note:

here for footing.


2.8 m

Thus, the maximum load that can be transferred by bearing is


NOT needed.
The minimum area of dowels

, and dowels are

Note: If dowels are needed, the required area of dowels


Where
has been used. This is the
value from ACI Code Sections 9.3.2.2(b) for
compression-controlled tied columns and 9.3.2.4 for bearing.
Use
or use the same reinforcement as in the column if larger.
The dowels must extend into the footing a distance equal to the compression-development
length (
and
concrete). The bars will be extended down to the level of the
main footing steel and hooked
. The hooks will be tied to the main steel to hold the
dowels in place. The dowels must extend into the column a distance equal to the greater of
a compression splice for the dowels or the compression development length of the column
bars. Dowel each corner bar.
359

Reinforced Concrete II

11.6

Dr. Nasr Abboushi

STRIP (WALL) FOOTINGS.

A wall footing cantilevers out on both sides of the wall as shown. The soil pressure causes
the cantilevers to bend upward, and as a result, reinforcement is required at the bottom of
the footing. The critical sections for design for flexure and anchorage are at the face of the
wall (section AA). One-way shear is critical at a section a distance from the face of the
wall (section BB).
The presence of the wall prevents two-way shear.

Example (strip or wall footings):


A
thick concrete wall carries a service (unfactored) dead load of
and a
service live load of
. From the geotechnical report, the allowable soil pressure,
, is
for shallow foundations. Design a wall footing to be based
below
the final ground surface, using
normal-weight concrete and
.
The density of the soil is
.
Solution:
Estimate the size of the footing and the factored net pressure. Consider a 1- strip of
footing and wall. Allowable soil pressure is
. Because the thickness of the
footing is not known at this stage, it is necessary to guess a thickness for a first trial.
Try a
-thick footing.
Therefore,
and we have:

Take

Depth of footing and shear design:

360

Reinforced Concrete II

Dr. Nasr Abboushi

One-way shear (Beam shear)


Shear usually governs the thickness of footings. Only one-way shear is significant in a wall
footing. at distance from the face of column:
(

Let

(
Assume cover

, and steel bars of

Design for flexure:


Take steel bars of

Or Take

with

Using bars of
instead of
So no need to check for
.
Step
is the smallest of:

as assumed before makes the effective depth

1.
361

larger.

Reinforced Concrete II

Dr. Nasr Abboushi

2.
Select the minimum (temperature) reinforcement. By ACI Code Section 7.12.2.1 we
require the following reinforcement along the length of the footing.
The maximum spacing is
or
reinforcement, placed as shown.

. Provide 9

362

) for shrinkage

Reinforced Concrete II

11.7

Dr. Nasr Abboushi

FOOTINGS UNDER ECCENTRIC COLUMN LOADS.

When a column transmits axial loads only, the footing can be designed such that the load
acts at the centroid of the footing, producing uniform pressure under the footing. However,
in some cases, the column transmits an axial load and a bending moment, as in the case of
the footings of fixed-end frames. The pressure q that develops on the soil will not be uniform
and can be evaluated from the following equation:

where
vertical load, positive in compression,
area of the contact surface between the soil and the footing,
moment of inertia of this area,
moment about the centroidal axis
of the footing area
distance from the centroidal axis to
the point where the stresses are being
calculated.
The moment, , can be expressed as
, where is the eccentricity of the
load relative to the centroidal axis of the
area . The maximum eccentricity for
which the previous equation applies is
that which first causes
at some
point. Larger eccentricities will cause a
portion of the footing to lift off the soil,
because the soil footing interface
cannot resist tension. For a rectangular
footing, this occurs when the
eccentricity exceeds

This is referred to as the kern distance.


Loads applied within the kern, the
shaded area will cause compression
over the entire area of the footing, and
the previous equation can be used to
compute .
Various pressure distributions for
rectangular footings are shown in the
figure below. If the load is applied
concentrically, the soil pressure
is
363

Reinforced Concrete II

Dr. Nasr Abboushi

. If the load acts through the kern point,


at one side and
at the
other. If the load falls outside the kern point, the resultant upward load is equal and
opposite to the resultant downward load, as shown in next figure (d). Generally, such a
pressure distribution would not be acceptable, because it makes inefficient use of the
footing concrete, tends to overload the soil, and may cause the structure to tilt.

364

Reinforced Concrete II

Dr. Nasr Abboushi

The different design conditions are summarized as follows:


1. When
, the soil pressure is trapezoidal (figure b, page 364).

2. When

, the soil pressure is triangular (figure c, page 364).

3. When

, the soil pressure is triangular (figure d, page 364).


(

Example:
Determine the dimensions of an isolated footing subjected to the loads:
Permissible net (allowable) soil pressure
Column dimensions
Solution (1) rectangular footing with uniform pressure:

Use
Solution (2) rectangular footing with nonuniform pressure:
Use

No tension zone.

365

Reinforced Concrete II

Dr. Nasr Abboushi

. Take

Solution (3) Square footing with nonuniform pressure:


Assume

Design the footing for shear and flexure as usual.

Example:
Determine the dimension

of an isolated footing subjected to the loads:

Permissible net (allowable) soil pressure


Column dimensions

Solution:

There is a tension zone.

Take
(

366

Reinforced Concrete II

Dr. Nasr Abboushi

Example (Design a Rectangular Footing for a Column Subjected to Axial Load and Bending):
The rectangular footing has a width of
and it will be supporting a
column
that is carrying the following loads.

Service surcharge
Permissible (allowable) soil pressure
Soil density
( soil depth

The length and depth of the footing are to be determined.


Design the footing assuming
and
Solution:
1. Factored loads.

2. Estimate footing length and depth. Estimate the overall thickness, , of the footing to
be between 1.5 and 2.0 times the size of the column, so select
.
The net permissible bearing pressure is:
Assume the soil pressure distribution at the base of the footing is trapezoidal (no tension
zone). Assuming a footing width, , and a footing length, , an expression for the maximum
bearing pressure under the footing is:

Setting
length, .

we can use the following expression to solve for the required footing

or

Using the positive solution, select a footing length of

3. Calculate factored soil pressures. (Note: In the prior step the acting loads were used
with the allowable soil bearing pressure to select the size of the footing. Now, the
factored loads will be used to determine the soil pressures that will subsequently be
used to determine the factored moment and shear used for the design of the
footing.)

367

Reinforced Concrete II

Dr. Nasr Abboushi

4. Check for one-way shear. The critical section for checking one-way shear strength is
shown. To simplify this check, it is conservative to assume that the maximum
factored soil pressure of
acts on the entire shaded region. Thus, the
factored shear force to be resisted at the critical section is (Take steel bars of
):

at distance

from the face of support:


368

Reinforced Concrete II

Dr. Nasr Abboushi

Let

Thus, the footing is OK for one-way shear.

5. Check footing thickness for two-way shear. The critical shear perimeter is located
away from each column face, as shown. Assume the average effective depth for
the footing is (Take steel bars of
):
Thus, each side of the critical shear perimeter has a length of
factored
shear
stress
inside
the
(

. Using the average


critical
perimeter

) the net factored shear to be transferred across

the critical perimeter is:

369

Reinforced Concrete II

Dr. Nasr Abboushi

)
(

(
)

(
)

)
(

Take

Thus, the footing depth satisfies the strength requirement for the net shear force.
6. Design for flexure in long direction. Take steel bars of

370

Reinforced Concrete II

Take

Dr. Nasr Abboushi

with

Using bars of
instead of
So no need to check for
.

Step

as assumed before makes the effective depth

larger.

is the smallest of:

1.
2.
The design procedure for flexural reinforcement in the transverse direction would be Similar.
For the arrangement of the bars in the transverse direction (ACI Code Section 15.4.4.2).

371

Reinforced Concrete II

11.8

Dr. Nasr Abboushi

COMBINED FOOTINGS.

Combined footings are used when it is necessary to support two columns on one footing.
When an exterior column is so close to a property line that a spread footing cannot be used,
a combined footing is often used to support the edge column and an interior column.
The shape of the footing is chosen such that the centroid of the area in contact with soil
coincides with the resultant of the column loads supported by the footing.
Sometimes, a combined footing will be designed as two isolated pads joined by a strap or
stiff beam. Here, the exterior footing acts as a wall footing, cantilevering out on the two
sides of the strap. The interior footing can be designed as a two-way footing. The strap is
designed as a beam and may require shear reinforcement in it.

372

Reinforced Concrete II

Dr. Nasr Abboushi

The soil pressure is assumed to act on longitudinal beam strips, ABC. These transmit the
load to hypothetical cross beams, AD and BE, which transmit the upward soil reactions to
the columns. For the column placement shown, the longitudinal beam strips would deflect
as shown, requiring the reinforcement shown.

For the transverse direction its


assumed that the column load is
spread over a width under the
column equal to the column
width plus
on each side,
whenever that is available. In
other words, the column load
acts on a beam under the column
within the footing, which has a
maximum width of (
) and a
length equal to the short side of
the footing.
373

Reinforced Concrete II

Dr. Nasr Abboushi

Example (combined footing):


A combined footing supports a
column carrying a service dead load of
and a service live load of
, plus a
column
carrying service loads of
dead load and
live load. The
distance between the columns is
, center to center. The allowable net soil bearing
pressure is
.
Design the footing, assuming that
(normal-weight concrete) and
.
Solution:

Footing dimensions.

374

Reinforced Concrete II

Dr. Nasr Abboushi

Depth of footing and shear design:

375

Reinforced Concrete II

Dr. Nasr Abboushi

One-way shear (Beam shear)


at distance from the face of support:
Assume
and steel bars of

At column 1

At column 2

The thickness

is adequate enough.

Two-way shear (Punching shear)

At column 1,

(
(

)
)

)
(

(
)

The thickness

is adequate enough.

376

(
)

)
(

Reinforced Concrete II

Dr. Nasr Abboushi

At column 2,

Check for two options of punching action


(
(

)
)

)
(

(
)

(
)

)
(

The thickness

is adequate enough.

Now, we can design the footing for flexure. By calculating the negative and positive
moments or by analyzing the combined footing using BeamD software we plot the moment
diagram. The moment diagram is plotted for the full 3.3 m width of the footing.
Design the flexural reinforcement in the longitudinal direction.

Design for Negative moment (midspan)

Take steel bars of

377

Reinforced Concrete II

Dr. Nasr Abboushi

Provide
Take

with

Using bars of
instead of
So no need to check for
.

Step

as assumed before makes the effective depth

larger.

is the smallest of:

1.
2.

Design for Positive moment (under columns)


column 2 and

The
Take

at the face of

at the face of column 1.


is control here.

with

Design the flexural reinforcement in the transverse direction (transverse beams).


Transverse strips under each column will be assumed to transmit the load from the
longitudinal beam strips into the column. The width of the beam strips will be assumed to
extend
on each side of the column. The actual width is unimportant, because the
moments to be transferred are independent of the width of the transverse beams.
The factored load on column 1 is
.
This is balanced by an upward net force of

The maximum moment in this transverse beam at the face of column 1 is


(

378

Reinforced Concrete II

Dr. Nasr Abboushi

The Band width under column 1 is

Take the Band width

Take

with

The factored load on column 2 is


This is balanced by an upward net force of

The maximum moment in this transverse beam is


(

The Band width under column 1 is


Take the Band width

Take

with

379

Reinforced Concrete II

Dr. Nasr Abboushi

Select the minimum (temperature) reinforcement. By ACI Code Section 7.12.2.1 we


require the following reinforcement along the length of the footing.
The maximum spacing is
Provide 7
(
shown.

11.9

or
) or

.
for shrinkage reinforcement, placed as

CONTINUOUS FOOTINGS.

Example
A continuous footing supports three
columns carrying a service dead load and a
service live load as shown. The length of the footing is
. The allowable net soil bearing
pressure is
.
Design the footing, assuming that
and
.

380

Reinforced Concrete II

Dr. Nasr Abboushi

Solution:
1. Footing width.

The eccentricity of the resultant force is

Note

No tension or zero pressure.

2. Calculate factored soil pressures.

381

Reinforced Concrete II

Dr. Nasr Abboushi

3. Depth of footing and shear design:


Assume
and steel bars of
The beam load:



One-way shear (Beam shear)

At column 1,
at distance from the face of support:

At column 2,
at distance from the Left face of support:

(
at distance

from the Right face of support:

Or from the right:


(

At column 3,

:
382

Reinforced Concrete II

at distance

Dr. Nasr Abboushi

from the face of support:

The thickness

is adequate enough.

Two-way shear (Punching shear)

At column 1,

)
(

(
)

The thickness
Take
(

is NOT adequate enough.


,
)

383

(
)

)
(

Reinforced Concrete II

Dr. Nasr Abboushi

The thickness

is adequate enough.

At column 2,

)
(

(
)

The thickness

is adequate enough.

At column 3,

)
384

)
(

Reinforced Concrete II

Dr. Nasr Abboushi

)
(

(
)

The thickness

is adequate enough.

Now, we can design the footing for flexure. By calculating the negative and positive
moments or by analyzing the combined footing using BeamD software we plot the moment
diagram. The moment diagram is plotted for the full
width of the footing.
1

1
A

A
0.3 0.3
0.45

1.7
2.

0.3

1.7
2.

load group no. 1


Total loads

A
0.3 0.3
0.45

Units:kN,meter

-2127.7
-2070.5 -2070.5

-1816.3 -1816.3

0.45

2.

-1562.1 -1562.1
-1504.9
2.

-482.3

0.45

-387.7

0.14

0.51
0.46

95.2

4
A

0.13
-25.4
154.3 68.3

-15.9
213.5
506.4

527.2
816.2

385

Reinforced Concrete II

Dr. Nasr Abboushi

11.10 MAT FOUNDATIONS.


When the bearing capacity of the soil is low, isolated footings are replaced by a raft
foundation. In such a case, a solid reinforced concrete rigid slab is constructed under the
entire building as shown below. Structurally, raft foundations resting directly on soil act as a
flat slab or a flat plate, upside down, i.e., loaded upward by the bearing pressure and
downward by the concentrated column reactions. The raft foundation develops the
maximum available bearing area under the building. If the bearing capacity of the soil is so
low that even this large bearing capacity is insufficient, deep foundations such as piles must
be used. Apart from developing large bearing areas, another advantage of raft foundations is
that their continuity and rigidity that helps in reducing differential settlement of individual
columns relative to each other, which might be caused by local variations in the quality of
subsoil, or other causes.
The design of raft foundations may be carried out by one of two methods:
T conv ntional igid m t od and;
T finit l m nt m t od utilizing comput p og ams.
The conventional method is easy to apply and the computations can be carried out using
hand calculations. However, the application of the conventional method is limited to rafts
with relatively regular arrangement of columns.
In contrast, the finite element method can be used for the analysis of raft regardless of the
column arrangements, loading conditions, and existence of cores and shear walls.
Commercially available computer programs can be used. The user should, however, have
sufficient background and experience.

Conventional rigid method:


The raft foundation shown below has dimensions
. Columns' service loads are
indicated as , , , ... etc. The application of the conventional method can be
summarized as follows:
386

Reinforced Concrete II

Dr. Nasr Abboushi

Where
area of the raft
moment of inertia of the raft about

axis

moment of inertia of the raft about

axis

moment of the applied loads about the


axis,
moment of the applied loads about the
axis,
Where and , are the eccentricities of the resultant from the center of gravity of the raft.

387

Reinforced Concrete II

Dr. Nasr Abboushi

The coordinates of the eccentricities are given by:

Where

are the

coordinates of

Where

are the

coordinates of

To draw the shear and moment diagrams we can divide the raft into several strips in the
direction (B1, B2, B3) and in the
direction (B4, B5, B6, B7). The soil pressure at the
center-line of the strip is assumed constant along the width of the strip.

Design each strip for shear and flexure as in the continuous footing design.

Example
Design the mat foundation, assuming that
and
net soil bearing pressure is
. Columns dimensions are
388

. The allowable
.

Reinforced Concrete II

Dr. Nasr Abboushi

Solution:

Y
B

0.9 m
445 KN
267 KN
(712) KN
(961) KN

801 KN
534 KN
(1335) KN
(1816) KN

845 KN
534 KN
(1379) KN
(1868) KN

489 KN
311 KN
(800) KN
(1084) KN

9m

E
801 KN
534 KN
(1335) KN
(1816) KN

1601 KN
890 KN
(2491) KN
(3345) KN

1779 KN
1112 KN
(2891) KN
(3914) KN

890 KN
534 KN
(1424) KN
(1922) KN

9m

K
K
1957 KN
1334 KN
(3291) KN
(4483) KN

I
845 KN
578 KN
(1423) KN
(1939) KN

1779 KN
1068 KN
(2847) KN
(3844) KN

534 KN
311 KN
(845) KN
(1138) KN

801 KN
534 KN
(1335) KN
(1816) KN

L
890 KN
534 KN
(1424) KN
(1922) KN

9m
801 KN
534 KN
(1335) KN
(1816) KN

534 KN
311 KN
(845) KN
(1138) KN
X

0.9 m
N

M
7.3 m

O
7.3 m

0.6 m

P
7.3 m
0.6 m

389

Reinforced Concrete II

Dr. Nasr Abboushi

390

Reinforced Concrete II

Dr. Nasr Abboushi

The maximum soil pressure


pressure
.

ill b at point P and is l ss t

allo abl soil

Design the strip - B F J N

961

1816

1868

1084

5729

1816

3345

3914

1922

10997

1939

3844

4483

1922

12188

1138

1816

1816

1138

5908
34822

Check

391

Reinforced Concrete II

Dr. Nasr Abboushi

The mat foundation will be divided into several strips in both directions. The stress
distribution will be defined for each strip as was done for the previous strip.
Each strip will be treated as continuous footing with flexure along the strip only. Analysis and
design of the strip will be analoge to the analysis an design of continuous footing.

392

Reinforced Concrete II

CHAPTER 12
12.1

Dr. Nasr Abboushi

DEVELOPMENT, ANCHORAGE, AND SPLICING OF REINFORCEMENT.


INTRODUCTION

In a reinforced concrete beam, the flexural compressive


forces are resisted by concrete, while the flexural tensile
forces are provided by reinforcement, as shown in the
figure (a) right. For this process to exist, there must be a
force transfer, or bond, between the two materials. The
forces acting on the bar are shown in the figure (b). For the
bar to be in equilibrium, bond stresses must exist. If these
disappear, the bar will pull out of the concrete and the
tensile force, , will drop to zero, causing the beam to fail.
Bond stresses must be present whenever the stress or
force in a reinforcing bar changes from point to point
along the length of the bar. This is illustrated by
the free-body diagram in the figures. If
is
greater than
bond stresses, , must act on
the surface of the bar to maintain equilibrium.
Summing forces parallel to the bar, one finds
that the average bond stress,
, is
(

And taking (

12.2

(
)

)
gives

FLEXURAL BOND

In a beam, the force in the steel at a crack can


be expressed as

where is the internal lever arm and


moment acting at the section.

is the

393

Reinforced Concrete II

Dr. Nasr Abboushi

If we consider a length of beam between two cracks, as shown in the above figures, the
moments acting at the two cracks are
and
. If the beam is reinforced with one bar of
diameter , the forces on the bar are as shown. Summing horizontal forces gives
(

If there is more than one bar, the bar perimeter is replaced with the sum of the perimeters
, giving

The last two equations give the average bond stress between two cracks in a beam. The
actual bond stresses vary from point to point between the cracks.

12.3

MECHANISM OF BOND TRANSFER

A smooth bar embedded in concrete develops bond by adhesion between the concrete and
the bar and by a small amount of friction. Both of these effects are quickly lost when the bar
is loaded in tension, particularly because the diameter of the bar decreases slightly, due to
Poissons ratio. For this reason, smooth bars are generally not used as reinforcement. In
cases where smooth bars must be embedded in concrete (anchor bolts, stirrups made of
small diameter bars, etc.), mechanical anchorage in the form of hooks, nuts, and washers on
the embedded end (or similar devices) are used.
Although adhesion and friction are present when a deformed bar is loaded for the first time,
these bond-transfer mechanisms are quickly lost, leaving the bond to be transferred by
bearing on the deformations of the bar as shown in figure (a). Equal and opposite bearing
stresses act on the concrete, as shown in figure (b). The forces on the concrete have both a
longitudinal and a radial component (figures c and d). The latter causes circumferential
tensile stresses in the concrete around the bar. Eventually, the concrete will split parallel to
the bar, and the resulting crack will propagate out to the surface of the beam. The splitting
394

Reinforced Concrete II

Dr. Nasr Abboushi

cracks follow the reinforcing bars along the bottom or side surfaces of the beam,
as shown in figure below. Once these cracks develop, the bond transfer drops rapidly unless
reinforcement is provided to restrain the opening of the splitting crack.

395

Reinforced Concrete II

Dr. Nasr Abboushi

The load at which splitting failure develops is a function of:


1. the minimum distance from the bar to the surface of the concrete or to the next bar
the smaller this distance, the smaller is the splitting load;
2. the tensile strength of the concrete; and
3. the average bond stress as this increases, the wedging forces increase, leading to a
splitting failure.
Typical splitting failure surfaces are shown in the above figure. The splitting cracks tend to
develop along the shortest distance between a bar and the surface or between two bars.
The circles touch the edges of the beam where the distances are shortest.
If the cover and bar spacings are large compared to the bar diameter, a pull-out failure can
occur, where the bar and the annulus of concrete between successive deformations pull out
along a cylindrical failure surface joining the tips of the deformations.

12.4

DEVELOPMENT LENGTH

Because the actual bond stress varies along the length of a bar anchored in a zone of
tension, the ACI Code uses the concept of development length rather than bond stress. The
development length, , is the shortest length of bar in which the bar stress can increase
from zero to the yield strength, . If the distance from a point where the bar stress equals
to the end of the bar is less than the development length, the bar will pull out of the
concrete. The development lengths are different in tension and compression, because a bar
loaded in tension is subject to in-and-out bond stresses and hence requires a considerably
longer development length. Also, for a bar in compression, bearing stresses at the end of the
bar will transfer part of the compression force into the concrete.
The development length can be expressed in terms of the ultimate value of the average
bond stress by setting
in equation for
equal to :

Here,

is the value of

at bond failure in a beam test.

1. Tension-Development Lengths
Analysis of Bond Splitting Load
Although the code equations for bond strength were derived from statistical analyses of test
results, the following analysis illustrates the factors affecting the splitting load.
Consider a cylindrical concrete prism of diameter
, containing a bar of diameter as
shown in figure (a) below. The radial components of the forces on the concrete, shown
below in figures b and c, cause a pressure on a portion of the cross section of the prism, as
shown in (b). This is equilibrated by tensile stresses in the concrete on either side of the bar.
In figure (c), the distribution of these stresses has arbitrarily been assumed to be triangular.
The circular prism in the figure below represents the zones of highest radial tensile stresses,
396

Reinforced Concrete II

Dr. Nasr Abboushi

shown by the larger circles in the previous figure. Splitting is assumed to occur when the
maximum stress in the concrete is equal to the tensile strength of the concrete,
. For
equilibrium in the vertical direction in a prism of length equal to
(

where is the ratio of the average tensile stress to the maximum tensile stress and equals
for the triangular stress distribution shown in figure c below. Rearranging gives
(

If the forces shown in the figures b and c on page (395) are assumed to act at
average bond stress,

, at the onset of splitting is equal to . Taking

gives

The length of bar required to raise the stress in the bar from zero to
development length,

Substituting equation for

, the

is called the

gives

Arbitrarily taking
(for the reasons to be given in the derivation of Equations for
Development Lengths later in the chapter) and rearranging yields

Basic Tension-Development Equation.


The ACI Code simplified the design expressions, in two stages as will be explained later. First,
a basic expression was developed for the development length, given in ACI Code Section
12.2.3 as

(
397

( )

Reinforced Concrete II

where the confinement term (

Dr. Nasr Abboushi

) is limited to 2.5 or smaller, to prevent pull-out bond

failures, and the length is not taken less than


. Also,
is the development length,
.
is the bar diameter,
.
is a bar-location factor given in ACI Code Section 12.2.4.
is an epoxy-coating factor given in ACI Code Section 12.2.4.
is a bar-size factor given in ACI Code Section 12.2.4.
is the lightweight concrete factor defined in ACI Code Section 12.2.4(d).
is the smaller of:
(a) the smallest distance measured from the surface of the concrete to the center of a
bar being developed, and
(b) one-half of the center-to-center spacing of the bars or wires being developed.
is a transverse reinforcement factor given in ACI Code Section 12.2.3.
Values for these factors will be presented later.
The second stage in the derivation of the basic expression for was to substitute common
values of and
into the basic expression for (equation ( )) as described next.
Simplified Tension-Development-Length Equation.
The basic equation for
was simplified by substituting lower limit values of and
for
common design cases, to get widely applicable equations that did not explicitly include these
factors. For deformed bars or deformed wire, ACI Code Section 12.2.2 defines the
development length, as given in the following Table.
The Cases 1 and 2 described in the top row of the Table are illustrated in the next figures
(a and b). Thecode minimumstirrups and ties mentioned in case 1 correspond to the
minimum amounts and maximum spacings specified in ACI Code Sections 11.4.5, 11.4.6.3,
and 7.10.5 (
, and ties spaces and bars arrangement).
and Smaller Bars
and Deformed Wires
Case 1: Clear spacing of bars being developed
or spliced not less than , and stirrups or ties
throughout
not less than the code
minimum

or

( )

Case 2: Clear spacing of bars being developed


or spliced not less than
and clear cover
not less than

Other cases
(
- The length

and Larger Bars

computed using these equations shall not be taken less than


398

(
.

Reinforced Concrete II

Dr. Nasr Abboushi

Bar-Spacing Factor,
The factor is the smaller of two quantities:
1. In the first definition, is the smallest distance from the surface of the concrete to the
center of the bar being developed. (See figure (a) on page 397).
ACI Code Section 7.7.1(c) gives the minimum cover to principal reinforcement as
.
For a beam stem not exposed to weather, with
bars enclosed in
stirrups or ties,
will be
(

2. In the second definition, is equal to one-half of the center-to-center spacing of the


bars.
ACI Code Section 7.6.1 gives the minimum clear spacing of parallel bars in a layer as , but
not less than
. For
bars, the diameter is
, giving the center-to-center
spacing of the bars as

and

The smaller of the two values discussed here is


. The minimum
stirrups or ties given in ACI Code Sections 7.10.5, 11.4.5, and 11.4.6.3 correspond to
between
and
, depending on a wide range of factors. Thus, for this case,
(
)
. Substituting this and the appropriate bar size factor, , into equation
( ) gives equations ( ) and ( ) in the above table.
For Case 2 in the table, consider a slab with clear cover to the outer layer of bars of
and a
clear spacing between the bars of
. It is assumed that splitting in the cover will be
restrained by bars perpendicular to the bars being developed. As a result, is governed by
the bar spacing. If the clear spacing is
, the center-to-center spacing is
. Thus,
. Substituting this into Eq. ( ) and taking

gives Eqs. ( ) or (

) in

the previous Table.


For the situation where the minimum clear cover to the bar being developed is
and
the minimum clear spacing is
is the smaller of
and . Substituting
and
into Eq. ( ), assuming that
gives Eqs. (
) and (
), which apply to
cases other than 1 and 2, as shown in the Table.
Typically,
is about
for
to
bottom bars and about
for
and
larger bottom bars.
399

Reinforced Concrete II

Dr. Nasr Abboushi

Factors in Equations ( ) through (


)
The Greek-letter factors in Equations ( ) through (
) are defined in ACI Section 12.2.4 as
follows:
bar location factor
Horizontal reinforcement so placed that more than
of fresh
concrete is cast in the member below the development length or
splice............................................................................................................ 1.3
Other reinforcement................................................................................. 1.0
coating factor
Epoxy-coated bars or wires with cover less than
or clear spacing less
than
....................................................................................................... 1.5
All other epoxy-coated bars or wires........................................................... 1.2
Uncoated and galvanized reinforcement .................................................... 1.0
) need not be taken greater than 1.7.
The product of (
bar-size factor
and smaller bars and deformed wires .............................................. 0.8
and larger bars.................................................................................... 1.0
Comparison of equation ( ) with a large collection of bond and splice tests showed that a
shorter development length was possible for smaller bars.
lightweight-aggregate-concrete factor
When any lightweight-aggregate concrete is used ................................... 0.75
However, when the splitting tensile strength
is specified,
shall be
permitted to be taken as
but not more than.......................... 1.0
When normal-weight concrete is used ........................................................1.0
transverse reinforcement index

where
total cross-sectional area of all transverse
reinforcement within the spacing , which
crosses the potential plane of splitting along
the reinforcement being developed within
the development length,
.(illustrated in
right figure).
maximum center-to-center spacing of transverse reinforcement within ,
number of bars or wires being developed or spliced along the plane of splitting.
ACI Code Section 12.2.3 allows
to be taken equal to zero to simplify the calculations,
even if there is transverse reinforcement.
400

Reinforced Concrete II

Dr. Nasr Abboushi

IMPORTANT. The basic rule governing the development and anchorage of bars is as follows:
The calculated tension or compression in reinforcement at each section of reinforced
concrete members shall be developed on each side of that section by embedment length,
hook, headed deformed bar, or mechanical anchorages, or a combination thereof. (ACI Code
Section 12.1)
Example:
A 400-mm-wide cantilever beam frames into the edge of a 400-mm-thick wall similar to
figure below. To reach
, the three
bars at the top of the beam are stressed to their
yield strength at point at the face of the wall. Compute the minimum embedment of the
bars into the wall and the development length in the beam. The concrete is sand/lowdensity concrete with a strength of
. The yield strength of the flexural reinforcement
is
. Construction joints are located at the bottom and top of the beam, as shown.
The beam has closed
stirrups with
at a spacing of
throughout
its length. (The stirrups are not shown.) The cover is 40 mm to the stirrups. The three
bars are inside
vertical steel in each face of the wall.
@
O.C.

450 mm

A
387.5mm

Construction joint

Construction joint
Wall

1.5 m

400 mm

Solution:
Anchorage of a traight bar (in a wall).
We shall do this problem twice, first using ACI Code Section 12.2.2 (Table page 398) and
then using ACI Code Section 12.2.3, Eq. ( ).
1. Find the spacing and confinement case for bars anchored in wall. The clear side
). The clear spacing of
cover to the
bars in the wall is (
the bars is

Because the clear spacing between the bars is not less than
bars exceeds , this is Case 2, and for
bars, Eq. (
2. Compute the development length. From Eq. ( ),
401

and the clear cover to the


) applies

Reinforced Concrete II

Dr. Nasr Abboushi

where
because there will be more than 300 mm of fresh concrete under the bar when
the concrete in the beam covers the bars (
).
because the bars are not epoxy coated.
because the concrete has low-density aggregates

The bars must extend 2184 mm into the wall to develop the full yield strength.
Extend the bars 2.2 m into the wall.
3. Compute the development length for

bars in the beam using Eq. ( ).

Where
and are the same as in step 2. For a
bar,
. is the smaller of:
(a) the distance from the center of the bar to the nearest concrete surface; measuring
from the side face to the center of the bar is
(b) half the center-to-center spacing of the bars;

, and
(

Thus,
.
The transverse reinforcement index is:

where
is the spacing of transverse reinforcement along the development length,
which is equal to
in this example (vertical
steel bars in each
face of the wall).
The number of bars being anchored.
is the area of transverse reinforcement crossing the
potential splitting plane within the spacing (one vertical
bar @ 300
mm in each face of the wall). Thus,

Then,

Thus, this term is set equal to 2.5 in Eq. ( ) to get

402

Reinforced Concrete II

Dr. Nasr Abboushi

Thus,
and the bars must extend 1310 mm into the wall. Extend the bars 1.35
m into the wall.
In this case, there is a large difference between the
computed from equation ( ) and
the
computed from equation ( ). This is because equation ( ) was derived by using
(

) equal to 1.5. In this case it is actually equal to 2.5.

Development of a bar in a cantilever.


The cantilever extends 1.5 m from the face of the wall. The bars shown are stressed to their
yield strength at the face of the wall. Is there adequate development length for
bars in
the span? If not, what is the largest-size bar that can be used?
The point of maximum bar force occurs at the face of the wall (point A). The bar must be
developed on each side of this point. To accomplish this, the bar must extend a minimum of
into the support (previous solution) and a minimum into the span.
1. Find the spacing and confinement case. From the previous example, the clear
spacing between the
bars in the beam is
. for the 175-mm stirrup
spacing, the minimum area of stirrups, by section 11.4.6.3, is

The stirrups provided are


double-leg stirrups, for which
.
The spacing does not exeed
.
Since the clear spacing between the bars is at least
and the stirrups exceed the minimum
amount required, this is case 1, and for
bars, equation ( ) applies.
2. Compute the development length. From the previous example, the development
length for a
top bar is
.
Since the bar extend
into the beam from the face of the wall, there
is insufficient length to develop a
bar. We must use smaller bars, with shorter , or
hook the
bars at . Try
with (
compared with
for
). For the new bar arrangement, we must start over.
1. Find the spacing and confinement case for bars anchored in the beam. The clear side
). The clear spacing
cover to the
bars in the beam is (
of the bars is

Since the stirrups exceed the ACI Code minimum and the clear spacing between the bars is
not less than
and the clear cover to the
bars exceeds , this is Case 1, and for
bars, Eq. ( ) applies
403

Reinforced Concrete II

Dr. Nasr Abboushi

2. Compute the development length. From Eq. ( ),

The bars must extend 1258 mm into the beam. Since


be developed whithout hooks at the free end. Use

bars can

bars.

ACI Section 12.2.5 allows the development length to be reduced by multiplying


by the
)
ration (
) (
. We will not take advantage of
this, because the reduced anchorage length will not allow the bars to be used for their full
capacity in the event of a change in use of structure.

Compression-Development Lengths
Compression-development lengths are considerably shorter than tension-development
lengths, because some force is transferred to the concrete by the bearing at the end of the
bar and because there are no cracks in such an anchorage region (and hence no in-and-out
bond). The basic compression-development length is (ACI Code Section 12.3)

where the constant


has units of
. The development length in compression
may be reduced by multiplying
by the applicable modification factors given in ACI Code:
Section 12.3.3 for excess reinforcement. (
)
)
Reinforcement enclosed within spiral reinforcement....(
The resulting development length shall not be less than
.
Example:
Determine the required development length of column steel reinforcements which are
embedded in a footing a s shown below in the figure.
Take
,
.
Solution:

The available development length:

404

Reinforced Concrete II

12.5

Dr. Nasr Abboushi

HOOKED ANCHORAGES

Behavior of Hooked Anchorages.


Hooks are used to provide additional anchorage when there is insufficient straight length
available to develop a bar. Unless otherwise specified, the so-called standard hooks
described in ACI Code Section 7.1 are used. Details of
and
standard hooks and
standard stirrup and tie hooks are given in the next figure. It is important to note that a
standard hook on a large bar takes up a lot of room, and the actual size of the hook is
frequently quite critical in detailing a structure.

OR

(a) Standard hooksACI Code Sections 7.1 and 7.2.1

405

Reinforced Concrete II

Dr. Nasr Abboushi

(b) Stirrup and tie hooksACI Code Section 7.1.3


A
hook loaded in tension develops forces in the manner shown in the figure below. The
stress in the bar is resisted by the bond on the surface of the bar and by the bearing on the
concrete inside the hook. The hook
moves inward, leaving a gap between
it and the concrete outside the bend.
Because the compressive force inside
the bend is not collinear with the
applied tensile force, the bar tends to
straighten out, producing compressive
stresses on the outside of the tail.
Failure of a hook almost always
involves crushing of the concrete inside
the hook. If the hook is close to a side
face, the crushing will extend to the
surface of the

concrete, removing the

side cover. Occasionally, the concrete


outside the tail will crack, allowing the
tail to straighten.
Design of Hooked Anchorages.
The design process described in ACI Code Section 12.5.1 does not distinguish between
and
hooks or between top and bottom bar hooks. The development length of a hook,
(illustrated in the figure (a), page 405), is computed using the following equation, which
may be reduced by appropriate multipliers given in ACI Code Section 12.5.3, except as
limited in ACI Code Section 12.5.4. The final development length shall not be less than
or
, whichever is greater. Accordingly,
406

Reinforced Concrete II

Dr. Nasr Abboushi

(
)

where
for epoxy-coated bars or wires and 1.0 for galvonized and uncoated
reinforcement, and is the lightweight-aggregate factor given in ACI Code Section 12.2.4(d).
Multipliers from ACI Section 12.5.3
The factors from ACI Code Section 12.5.3 account for the confinement of the hook by
concrete cover and stirrups. Confinement by stirrups reduces the chance that the concrete
between the hook and the concrete surface will spall off, leading to a premature hook
failure.
For clarity, ACI Code Section 12.5.3(a) has been divided here into two sentences. The factors
are as follows:
12.5.3(a1) for
hooks on
and smaller bars with side cover (normal to the plane of
the hook) not less than 65 mm ..........................................................................
12.5.3(a2) for
hooks on
and smaller bars with side cover (normal to the plane of
the hook) not less than 65 mm and cover on the bar extension (tail) beyond the
hook not less than 50 mm .................................................................................
The multipliers in ACI Code Section 12.5.3(b) and (c) reflect the confinement of the concrete
outside the bend.
12.5.3(b) for
hooks on
and smaller bars that are either
enclosed within ties or stirrups perpendicular to the bar being developed, spaced
not greater than
along the development length,
, of the hook, as shown in
Fig. (a) below, or
enclosed within ties or stirrups parallel to the bar being developed, spaced not
greater than
along the length of the tail extension of the hook plus bend, as
shown in Fig. (b)........................................................................................
, except
as given in ACI Code Section 12.5.4.
12.5.3(c) for
hooks on
or smaller bars enclosed within ties or stirrups
perpendicular to the bar being developed, spaced not greater than
along the
development length,
, of the hook.
except
as given in ACI Code Section 12.5.4.
12.5.3(d) where anchorage or development for is not specifically required, reinforcement
in excess of that required by analysis . (

) (

).

ACI Code Section 12.5.4 states that for bars being developed by a standard hook at
discontinuous ends of members with both side cover and top (or bottom) cover over a hook
of less than 65 mm the hooked bar shall be (must be) enclosed within ties or stirrups
perpendicular to the bar being developed, spaced not greater than
along the
development length of the hook,
. In this case, the factors of ACI Code Section 12.5.3(b)
and (c) shall not apply. ACI Code Section 12.5.4 applies at such points as the ends of simply
supported beams (particularly if these are deep beams), at the free ends of cantilevers, and
at the ends of members that terminate in a joint with less than 65 mm of both side cover
407

Reinforced Concrete II

Dr. Nasr Abboushi

and top (or bottom) cover over the hooked bar. Hooked bars at discontinuous ends of slabs
are assumed to have confinement from the slab on each side of the hook; hence, ACI Code
Section 12.5.4 is not applied.

Concrete cover per 12.5.4.


408

Reinforced Concrete II

Dr. Nasr Abboushi

Table for Hook Lengths,

from equation

from ACI Code Sections 12.5.3 and 12.5.4, but Not Less than

Location
1. Anywhere,
12.5.3(a)

Type

Hooked
Bar
size

Side
Cover,
mm

2. Anywhere,
12.5.3(a)
3. Anywhere,
12.5.3(b)

Any

4. Anywhere,
12.5.3(b)

Any

5. Anywhere,
12.5.3(c)

6. At the ends
of members,
12.5.4

Any

Times Factors
or

Top or
Bottom
Cover,
mm

Tail
Cover

Stirrups or ties

Any

Any

Not required

Factor

Any

Not required

Any

Any

Enclosed in stirrups or
ties perpendicular to
hooked bar, spaced
along

Except
as in
line 6

Any

Enclosed in stirrups or
ties parallel to hooked
bar spaced
along

Except
as in
line 6

Any

Enclosed in stirrups or
ties perpendicular to
hooked bar, spaced
along

Except
as in
line 6

Any

Any

or

Any

Enclosed in stirrups or
ties perpendicular to
hooked bar, spaced

is the diameter of the bar being developed by the hook


The first stirrup or tie should enclose the hook within
If two or more factors apply,

of the outside of the bend.

is multiplied by the product of the factors

Line 6 (ACI Code Section 12.5.4) applies at the discontinuous ends of members

The previous Figures (page 408) shows the meaning of the words ties or stirrups parallel
to or perpendicular to the bar being developed in ACI Code Sections 12.5.3(b) and (c), and
12.5.4. In ACI Code Sections 12.5.3 and 12.5.4, is the diameter of the hooked bar, and the
first tie or stirrup shall enclose the bent portion of the hook, within
of the outside of the
bend.
If a hook satisfies more than one of the cases in ACI Code Section 12.5.3,
from Equation
is multiplied by each of the applicable factors. Thus, if a
hook satisfies both the covers
from ACI Code Section 12.5.3(a) and the stirrups from 12.5.3(b),
is the length from the
409

Reinforced Concrete II

Dr. Nasr Abboushi

first part of Equation for


multiplied by
from 12.5.3(a) and 0.8 from 12.5.3(b), making
the total reduction
Finally, the length of the hook, shall not be less than
or
,
whichever is greater, after all the reduction factors have been applied.
Hooks may not be used to develop bars in compression, because bearing on the outside of
the hook is not efficient.
Example (Hooked Bar Anchorage into a Column)
The exterior end of a 400-mm-wide-by-600-mm-deep continuous beam frames into
a 600 mm-square column, as shown below. The column has four
longitudinal bars. The
negative-moment reinforcement at the exterior end of the beam consists of four
bars.
The concrete is
normal-weight concrete. The longitudinal steel strength is
. Design the anchorage of the four
bars into the column. It should be clear
(from the previous examples) that a straight
bar cannot be developed in a 600-mmdeep column. Thus, assume a hooked bar anchorage is required.

410

Reinforced Concrete II

Dr. Nasr Abboushi

Solution:
Compute the development length for hooked beam bars. The basic development length for a
hooked bar is

Therefore,

Assume that the four


bars will extend into the column inside the vertical column bars,
as shown in the above figure. ACI Code Section 11.10.2 requires minimum ties in the joint
area. The required spacing of
closed ties by ACI Code Section 11.10.2 (Except for
connections not part of a primary seismic load-resisting system that are restrained on four
sides by beams or slabs of approximately equal depth, connections shall have lateral
reinforcement not less than that required by Eq. (11-13) within the column for a depth not
less than that of the deepest connection of framing elements to the columns. See also 7.9.) is
computed as:

The second expression governs, so

The side cover to hooked bars is determined as:


(

This exceeds 65 mm and is therefore O.K. The top cover to the lead-in length in the joint
exceeds 65 mm because the joint is in the column.
The cover on the bar extension beyond the hook (the tail of the hook) is

12.5.3.2(a): The side cover exceeds 65 mm, and the cover on the bar extension is equal to
50 mm; therefore, the 0.7 reduction factor could be used. Note, if we used
ties in the
joint, the cover on the bar extension after the hook would be less than 50 mm, and thus, the
multiplier = 1.0.
ACI Code Section 12.5.4 does not apply because the side cover and top cover both exceed
65 mm. Therefore, only the minimum ties required by ACI Section 11.10.2 are required:
ties at 300 mm. These are spaced farther apart than
therefore,
ACI Code Section 12.5.3(b) does not apply, and so the multiplier is 1.0. Thus,

Take
The hook-development length available is
411

Reinforced Concrete II

Dr. Nasr Abboushi

Because 600 mm exceeds 350 mm, the hook development length is O.K.
Check the vertical height of a standard hook on a
bar. From Fig. a (page 410), the
vertical height of a
standard hook is
. This will
fit into the joint.
Therefore, anchor the four
bars into the joint, as shown in the previous figure.
12.6

BAR CUTOFFS AND DEVELOPMENT OF BARS IN FLEXURAL MEMBERS

Why Bars Are Cut Off


In reinforced concrete, reinforcement is provided near the tensile face of beams to provide
the tension component of the internal resisting couple. A continuous beam and its moment
diagram are shown below. At midspan, the moments are positive, and reinforcement is
required near the bottom face of the member. The opposite is true at the supports. For
economy, some of the bars can be terminated or cut off where they are no longer needed.

The location of the cut-off points is discussed in this section.


Four major factors affect the location of bar cutoffs:
1. Bars can be cut off where they are no longer needed to resist tensile forces or where
the remaining bars are adequate to do so. The location of points where bars are no
longer needed is a function of the flexural tensions resulting from the bending
moments and the effects of shear on these tensile forces.
2. There must be sufficient extension of each bar, on each side of every section, to
develop the force in that bar at that section. This is the basic rule governing the
development of reinforcement, presented in Section 8-6 (ACI Code Section 12.1).
3. Tension bars, cut off in a region of moderately high shear force cause a major stress
concentration, which can lead to major inclined cracks at the bar cutoff.
4. Certain constructional requirements are specified in the code as good practice.
412

Reinforced Concrete II

Dr. Nasr Abboushi

Generally speaking, bar cut offs should be kept to a minimum to simplify design and
construction, particularly in zones where the bars are stressed in tension.
In the following sections, the location of theoretical cut-off points for flexure, referred to as
flexural cut-off points, is discussed. This is followed by a discussion of how these flexural
cut-off locations must be modified to account for shear, development, and constructional
requirements to get the actual cut-off points used in construction.
Location of Flexural Cut-Off Points
The calculation of the flexural cut-off points will be illustrated with the simply supported
beam shown next. At midspan, this beam has
reinforcing bars, shown in section
(figure c). At points and
two of these bars are cut off, leaving
bars in the end
portions of the beam, as shown in figure b.
The beam is loaded with a uniform factored load of
including its selfweight, which
gives the diagram of ultimate moments,
, shown in figure d. This is referred to as the
required-moment diagram, because, at each section, the beam must have a reduced
nominal strength,
at least equal to
. The maximum required moment at midspan is

Assuming
concrete, Grade-420 reinforcement and a tension-controlled section
so
, the moment capacity,
, of the section with
bars is
,
which is adequate at midspan. At points away from midspan, the required
is less than
, as shown by the moment diagram in figure d. Thus, less reinforcement
(less

) is required at points away from midspan. This is accomplished by cutting off some

of the bars where they are no longer needed. In the example illustrated in the figure below,
it has been arbitrarily decided that
bars will be cut off where they are no longer
needed. The remaining
bars give a reduced nominal strength
. Thus, the two bars theoretically can be cut off when
because the remaining three bars will be strong enough to resist
. From an equation for
the required-moment diagram (figure d), we find at
from each support.
Consequently, the two bars that are to be cut off are no longer needed for flexure in the
outer
of each end of the beam and theoretically can be cut off at those points, as
shown in figure e.
Figure f is a plot of the reduced nominal moment strength,
, at each point in the beam
and is referred to as a moment-strength diagram. At midspan (point E in figure e), the beam
has five bars and hence has a capacity of
. To the left of point , the beam
contains three bars, giving it a capacity of
. The distance
represents the
development length, , for the two bars cut off at . At the ends of the bars at point ,
these two bars are undeveloped and thus cannot resist stresses. As a result, they do not add
to the moment capacity at . On the other hand, the bars are fully developed at , and in
the region from to they could be stressed to if required. In this region, the moment
capacity is
.
413

Reinforced Concrete II

Dr. Nasr Abboushi

414

Reinforced Concrete II

Dr. Nasr Abboushi

The three bars that extend into the supports are cut off at points and . At and ,
these bars are undeveloped, and as a result, the moment capacity is
at and .
At points
and
the bars are fully developed, and the moment capacity
In figure g, the moment-capacity diagram from figure f and the required moment diagram
from figure d are superimposed. Because the moment capacity is greater than or equal to
the required moment at all points, the beam has adequate capacity for flexure, neglecting
the effects of shear.
The ACI Code does not explicitly treat the effect of shear on the tensile force. Instead, ACI
Code Section 12.10.3 arbitrarily requires that longitudinal tension bars be extended a
minimum distance equal to the greater of
or
past the
theoretical cut-off point for flexure.

Development of Bars at Points of Maximum Bar Force. For reinforcement and concrete to
act together, each bar must have adequate embedment on both sides of each section to
develop the force in the bar at that section. In beams, this is critical at
1. Points of maximum positive and negative moment, which are points of maximum bar
stress.
2. Points where reinforcing bars adjacent to the bar under consideration are cut off or
bent (ACI Code Section 12.10.2).
Thus, bars must extend at least a development length, , each way from such points or be
anchored with hooks or mechanical anchorages.
ACI Code 12.10 requires special precautions, specifying that no flexural bar shall be
terminated in a tension zone unless one of the following conditions is satisfied:
1. The shear is not over two-thirds of the design strength
.
(

2. Stirrups in excess of those normally required are provided over a distance along each
terminated bar from the point of cutoff equal to
provide an area
, where
at the section.

. These "binder" stirrups shall

. In addition, the stirrup spacing shall not exceed


is the ratio of the area of bars cut off to the total area of bars

3. The continuing bars, if


or smaller, provide twice the area required for flexure at
that point, and the shear does not exceed three-quarters of the design strength
(

415

Reinforced Concrete II

Dr. Nasr Abboushi

416

Reinforced Concrete II

Dr. Nasr Abboushi

417

Reinforced Concrete II

12.7

Dr. Nasr Abboushi

DEVELOPMENT OF POSITIVE MOMENT REINFORCEMENT.

The concept of requiring the development of reinforcement on both sides of a section where
the bars are to be fully stressed may also be applied to the continuation of positive moment
tension reinforcement beyond either the centerline of a simple support or a point of
inflection.
Simple Supports
Referring to the next figure, consider the point A on the factored moment
curve near a
simple support, where the factored moment
equals the moment capacity
of the
bars continuing into the support. The distance from point A to the end of the bars must be at
least equal to the required development length
as computed from ACI-12.2. This
requirement given in ACI-12.11.3 is that the available embedment length must equal or
exceed , or
( )
Where

nominal flexural strength of all reinforcement at the section assumed to be


(

stressed at

factored shear at the support, and


the straight embedment length beyond the centerline of support to the end of
the bars [When the bars are hooked, the equation ( ) is considered automatically satisfied.]
In the next figure, the area of the shaded portion of the shear diagram equals the change in
moment between the center of support and point A; thus the ordinate on the factored
moment diagram at A is
Thus, the distance
equal to

between the point A and the centerline of support is approximately


( )

Comparing Eq. ( ) and Eq. ( ), it is seen that Eq. ( ) is identical to


or

The factor
accounts for the fact that bars extending into a simple support have less
tendency to cause splitting when confined by a compressive reaction. When the beam is
supported in such a way that there are no bearing stresses above the support, the factor
becomes

(as eq. (

)) [The ACI Code allows a

such cases [see Eq. ( )].


418

increase in the value of

or

in

Reinforced Concrete II

Dr. Nasr Abboushi

Inflection Points
Since an inflection point is a point of zero moment located away from a support (refer to the
next figures), bars in that region are not confined by a compressive reaction; therefore the
factor is interpreted as not to apply. In this case, the embedment length that must
exceed the required development length ; (ACI-12.11.3) may be stated as
[
where
and
of inflection.

refer to the nominal flexural strength and the factored shear at the point

419

Reinforced Concrete II

Dr. Nasr Abboushi

The limitation of the usable


to
or the
has been
applied because, according to the ACI Commentary-R12.11.3, there is no experimental
evidence to show that long anchorage length will be fully effective in developing a bar in a
short length between the point of inflection and a point of maximum stress.
Additional development of reinforcement at the face of support is required by ACI-12.11.2
when the flexural member is part of the primary lateral load resisting system.
Equations ( ) and ( ) are written in terms of
rather than
because the
development length equations were derived on the basis of developing
in the bars, not
. These Equations are not applied in negative-moment regions, because the shape of the
moment diagram is concave downward such that the only critical point for anchorage is the
point of maximum bar stress.
The consequence of these special requirements at the point of zero moment is that, in some
cases, smaller bar sizes must be used to obtain smaller , even though requirements for
development past the point of maximum stress are met.
ACI Code 12.11.1 requires that at least one-third the positive moment reinforcement in
simple members and one-fourth the positive moment reinforcement in continuous members
shall extend along the same face of member into the support. In beams, such reinforcement
shall extend into the support at least
.
420

Reinforced Concrete II

Dr. Nasr Abboushi

Example
Check the Code requirement of development length at support of the beam shown.
Take
.
Solution:

421

Reinforced Concrete II

Dr. Nasr Abboushi

Using equation (

) from the table on page 398 (Case 1 with minimum stirrups).

The available length satisfies the Code requirement.

12.8

DEVELOPMENT OF NEGATIVE MOMENT REINFORCEMENT.

According to ACI Code 12.12, at least one-third of the total reinforcement provided for
negative moment at the support must be extended beyond the extreme position of the
point of inflection a distance not less than one-sixteenth the clear span (
), or , or
, whichever is greatest.
Requirements for bar cutoff or bend point locations are summarized in the next figure. If
negative bars are to be cut off, they must extend a full development length beyond the
face of the support. In addition, they must extend a distance
or
beyond the
theoretical point of cutoff defined by the moment diagram. The remaining negative bars
(at least one-third of the total negative area) must extend at least beyond the theoretical
point of cutoff of bars and in addition must extend ,
, or
(whichever is
greatest) past the point of inflection of the negative-moment diagram.
If the positive bars are to be cut off, they must project
past the point of theoretical
maximum moment, as well as or
beyond the cutoff point from the positive-moment
diagram. The remaining positive bars must extend past the theoretical point of cutoff of
bars and must extend at least
into the face of the support.
422

Reinforced Concrete II

Dr. Nasr Abboushi

When bars are cut off in a tension zone, there is a tendency toward the formation of
premature flexural and diagonal tension cracks in the vicinity of the cut end. This may result
in a reduction of shear capacity and a loss in overall ductility of the beam.
As an alternative to cutting off the steel, tension bars may be anchored by bending them
across the web and making them continuous with the reinforcement on the opposite face.
Although this leads to some complication in detailing and placing the steel, thus adding to
construction cost, some engineers prefer the arrangement because added insurance is
423

Reinforced Concrete II

Dr. Nasr Abboushi

provided against the spread of diagonal tension cracks. In some cases, particularly for
relatively deep beams in which a large percentage of the total bottom steel is to be bent, it
may be impossible to locate the bend-up point for bottom bars far enough from the support
for the same bars to meet the requirements for top steel. The theoretical points of bend
should be checked carefully for both bottom and top steel.
It may be evident from review of the previous sections that the determination of cutoff or
bend points in flexural members is complicated and can be extremely time-consuming in
design. It is important to keep the matter in perspective and to recognize that the overall
cost of construction will be increased very little if some bars are slightly longer than
absolutely necessary, according to calculation, or as dictated by ACI Code provisions. In
addition, simplicity in construction is a desired goal, and can, in itself, produce compensating
cost savings. Accordingly, many engineers in practice continue all positive reinforcement into
the face of the supports the required 150 mm and extend all negative reinforcement the
required distance past the points of inflection, rather than using staggered cutoff points.
Example
Locate the flexural cut-off for the beam shown below.
Take
.

Solution:

(
(

)
424

Reinforced Concrete II

Dr. Nasr Abboushi

For

:
(

The length of

from symmetrical center of beam

Take
The total length of

is

.
425

Reinforced Concrete II

For

Dr. Nasr Abboushi

The total length of

is

12.9 REINFORCEMENT
REQUIREMENTS.

CONTINUITY

AND

STRUCTURAL

INTEGRITY

The primary purpose for both the continuity and structural-integrity reinforcement
requirements is to tie the structural elements together and prevent localized damage from
spreading progressively to other parts of the structure. However, because of the limited
amount of calculations required to select and detail this reinforcement, structures satisfying
these requirements cannot be said to have been designed to resist progressive collapse.
Continuity Reinforcement
Requirements for continuity reinforcement in continuous beams are given in ACI Code
Sections 12.11.1 and 12.11.2 for positive-moment (bottom) reinforcement and in ACI Code
Sections 12.12.1 through 12.12.3 for negative-moment (top) reinforcement.
These requirements are summarized in next figures for positive-moment reinforcement and
for negative-moment reinforcement respectively.

426

Reinforced Concrete II

Dr. Nasr Abboushi

ACI Code Section 12.11.1 requires that at least one-third of the positive-moment
reinforcement used at midspan for simply supported members and at least one-fourth of the
positive-moment reinforcement used at midspan for continuous members shall be
continued at least 150 mm into the supporting member (Fig. a). Further, if the beam under
consideration is part of the primary lateral load-resisting system, ACI Code Section 12.11.2
requires that the bottom reinforcement must be continuous through interior supports and
fully anchored at exterior supports (Fig. b).
ACI Code Section 12.12.1 requires that negative-moment reinforcement must be continuous
through interior supports and fully anchored at exterior supports (next figure).
ACI Code Section 12.12.2 requires that all of the negative-moment reinforcement must
extend the development length, , into the span before being cut off. Finally, ACI Code
Section 12.12.3 requires that at least one-third of the negative-moment reinforcement
provided at the face of the support shall be extended beyond the point of inflection a
distance greater than or equal to the largest of ,
, and
. Theoretically, no top
steel should be required beyond the point of inflection, where the beam moment changes
from negative to positive. The minimum extension given by the ACI Code accounts for
427

Reinforced Concrete II

Dr. Nasr Abboushi

possible shifts in the theoretical point of inflection due to changes in the loading and for the
effect of shear on longitudinal steel requirements.

Structural-Integrity Reinforcement
Requirements for structural-integrity reinforcement in continuous floor members first
appeared in the 1989 edition of the ACI Code. These requirements, which are given in ACI
Code Section 7.13, were clarified and strengthened in the 2002 and 2008 editions of the ACI
Code. The structural-integrity requirements are supplemental to the continuity
requirements discussed previously and were added to better tie the structural members
together in a floor system and to provide some resistance to progressive collapse. Because
the ACI Code Committee was concerned that a significant number of structural engineers
using Chapter 12 were not aware of the structural-integrity requirements, ACI Code Section
12.1.3 was added in 2008 to specifically direct the designers attention to the need to satisfy
ACI Code Section 7.13 when detailing reinforcement in continuous beams. Structuralintegrity requirements for reinforced concrete (nonprestressed) continuous slabs are given
in ACI Code Chapter 13, for precast construction in Code Chapter 16, and for prestressed
two-way slab systems in Code Chapter 18. Those requirements will not be discussed here.
The structural-integrity requirements in ACI Code Section 7.13 can be divided into
requirements for joists, perimeter beams, and interior beams framing into columns. For joist
construction, as defined in ACI Code Sections 8.13.1 through 8.13.3, ACI Code Section
7.13.2.1 requires that at least one bottom bar shall be continuous over all spans and through
428

Reinforced Concrete II

Dr. Nasr Abboushi

interior supports and shall be anchored to develop


at the face of exterior supports.
Continuity of the bar shall be achieved with either a Class B tension lap splice or a
mechanical or welded splice satisfying ACI Code Section 12.14.3. Class B lap splices are
defined in ACI Code Section 12.15.1 as having a length of
(but not less than
).
The value for the development length, , is to be determined in accordance with ACI Code
Section 12.2, which has been given previously ( see pages 397 and 398 ). When determining
, the
minimum does not apply, and the reduction for excessive reinforcement
cannot be applied.
ACI Code Section 7.13.2.2 states that perimeter beams must have continuous top and
bottom reinforcement that either passes through or is anchored in the column core, which is
defined as the region of the concrete bounded by the column longitudinal reinforcement.

The continuous top reinforcement shall consist of at least one-sixth of the negative-moment
(top) reinforcement required at the face of the support, but shall not be less than two bars.
The continuous bottom
reinforcement
shall
consist of at least onefourth of the positivemoment
(bottom)
reinforcement required at
midspan, but not less than
two
bars.
At
noncontinuous supports
(corners), all of these bars
must be anchored to
develop
at the face of
the support. Also, all of
the
continuous
longitudinal bars must be
enclosed
by
closed
transverse reinforcement
429

Reinforced Concrete II

Dr. Nasr Abboushi

(ACI Code Section 7.13.2.3), as specified for torsional transverse reinforcement in ACI Code
Sections 11.5.4.1 and 11.5.4.2, and placed over the full clear span at a spacing not exceeding
. As before, reinforcement continuity can be achieved through either the use of Class B
tension lap splices or a mechanical or welded splice.

For interior beams framing between columns, ACI Code Section 7.13.2.5 defines two ways to
satisfy the structural-integrity requirements for continuous longitudinal reinforcement. If
closed transverse reinforcement is not present, then structural integrity must be achieved by
continuous bottom reinforcement similar to that required for perimeter beams (see next
Figure a). As before, this reinforcement must pass through or be fully anchored in the
column core, and reinforcement continuity can be achieved through either a Class B tension
lap splice or a mechanical or welded splice. For interior beams that are not part of the
primary system for resisting lateral loads, the bottom reinforcement does not need to be
continuous through interior supports or fully anchored at exterior supports, and structural
integrity can be achieved by a combination of bottom and top steel that is enclosed by
closed transverse reinforcement (Fig. b). The top steel must satisfy the requirements of ACI
Code Section 12.12 and must be continuous through the column core of interior supports or
fully anchored in the column core of exterior supports. The bottom steel must satisfy the
requirements given in ACI Code Section 12.11.1. The closed transverse reinforcement (not
shown in Fig. b) must satisfy ACI Code Sections 11.5.4.1 and 11.5.4.2 and must be provided
over the full clear span at a spacing not exceeding
. How continuity and structuralintegrity requirements affect the selection of cut-off points and longitudinal reinforcement
detailing are given in the examples.
430

Reinforced Concrete II

Dr. Nasr Abboushi

Example
The beam shown below is constructed of normal-weight concrete,
, and Grade420 reinforcement,
. It supports a factored dead load of
and a
factored live load of
. The cross sections at the points of maximum positive and
negative moment, as given in figures below, are shown next.
431

Reinforced Concrete II

Dr. Nasr Abboushi

Solution:
1. Locate flexural cut offs for positive-moment reinforcement. The positive moment in
span AB is governed by the loading case in
Fig. a below .From a free-body analysis of a
part of span AB (Fig. d), the equation for
at a distance from A is

At midspan, the beam has two


plus two
bars. The two
bars will be cut off. The
capacity of the remaining bars is calculated as
follows:

Therefore, flexural cut-off points occur where


.
Setting
the equation for
can be rearranged to

432

Reinforced Concrete II

Dr. Nasr Abboushi

Thus
or
from A. These flexural cut-off points are shown in figure c for
bending moment diagram and figure a for location of positive moment cut-off points. They
will be referred to as theoretical flexural cut-off points E and F. In a similar fashion, by
setting
the flexural cut-off point G is found to be
from A or
from B.
2. Compute the development lengths for the bottom bars.

Because the bar spacing exceeds for both the


and
bars, and because the beam
has minimum stirrups, the bars satisfy Case 1 in the Table on page 398.

Thus, for the

bars,

and for the

bars

.
3. Locate actual cut-off points for positive-moment reinforcement. The actual cut-off
points are determined from the theoretical flexural cut-off points using rules stated
earlier. Because the location of cut offs G and D are affected by the locations of cut
offs E and F, the latter are established first, starting with F. Because the beam is
simply supported it is not included in the ACI Code listing of members that are
susceptible to actions requiring structural integrity.
a) Cutoff F. Two
bars are cut off. They must satisfy rules for anchorage, extension
of bars into the supports and effect of shear on moment diagrams.
Extension of bars into the supports. At least one-third of the positive-moment
reinforcement, but not less than two bars, must extend at least
into the
supports. We shall extend two
bars into each of the supports A and B.
Effect of shear. Extend the bars by the larger of
or
. Therefore, the first trial position of the actual cutoff is
at
from the center of the support at A, say,
. (see point
F in next Fig. b).
Anchorage. Bars must extend at least past the points of maximum bar stress. For
the bars cut off at F, the maximum bar stress occurs near midspan, at
from
A. The distance from the point of maximum bar stress to the actual bar cutoff is
.
for the
bars is
. The distance available is
more than therefore OK. Cut off two
bars at
from A (shown as point
F in Fig. b).
433

Reinforced Concrete II

Dr. Nasr Abboushi

b) Cutoff G. Two
bars are cut off; we must consider the same three items as
covered in step (a), plus we must check the anchorage at a point of inflection using
Eq. ( ) on page 419.
Extension of bars into simple supports. In step (a), we stated the need to extend two
bars
into support B. Thus, G is at
.
Effects of shear. Because the cut off is at the support, we do not need to extend the
bars further.
Anchorage. Bars must extend at least past actual cut offs of adjacent bars. for
bottom bar
. Distance from F to G
. Bar does not extend , therefore extend the bars to
say,
.
Anchorage at point of inflection. Must satisfy Eq. ( ) on page 419 at point of
inflection (point where the moment is zero). Therefore, at G,
. The
point of inflection is
from the support (see figure c). At this point
is
(Fig. b) and the moment strength
for the bars in the beam at the point
of inflection (two
bars) is

) or
larger of (
extension of the bar past the point of inflection (
and

OK, because this length exceeds


from B (shown as point G in Fig. b).

. Cut off two

but not more than the actual


). Therefore,

bars (

c) Cutoff E. Two
bars are cut off; we must check for the effect of shear and
development length (anchorage).
Effects of shear, positive moment. Extend the bars
past the flexural
cutoff point. Therefore, the actual cutoff E is at
from A.
Anchorage, positive moment. The distance from the point of maximum moment to
the actual cutoff exceeds
therefore OK. Cut off two
bars at
from A (point E in Fig. b; note that this is changed later).
d) Cutoff D. Two
bars are cut off; we must consider extension into a support,
extension beyond the cut-off point and development of bars at a simple support
using Eq. ( ) on page 418.
Extension into simple support. This was done in step (a).
Bars must extend from the actual cutoff E, where
(
bars).
The maximum possible length available is
. Because
this is less than , we must either extend the end of the beam, hook the ends of the
434

Reinforced Concrete II

Dr. Nasr Abboushi

bars, use smaller bars, or eliminate the cutoff E. We shall do the latter. Therefore,
extend all four bars 150 mm past support A.
Development of bars at simple support. We must satisfy Eq. ( ) on page 418 at the
support.
(

Because this exceeds , development at the simple support is satisfied. The actual cut-off
points are illustrated in figure below.

4. Locate flexural cutoffs for negative-moment reinforcement. The negative moment is


governed by the loading case in the next figure a. The equations for the negative
bending moments are as follows:
Between A and B, with measured from A
435

Reinforced Concrete II

and between C and B, with

Dr. Nasr Abboushi

measured from C,

Over the support at B, the reinforcement is two


bars plus two
bars are no longer required when the moment is less than
(strength of the beam with two
bars).
So, between A and B,
from A.
Therefore, the theoretical flexural cut-off point for two
from A. Finally, between B and C,
from C
Therefore, the theoretical flexural cut-off point for
two
top bars in span BC is at
from C.
The flexural cut-off points for the negativemoment steel are shown in the figure a below and
are lettered H, J, K, and L.
5. Compute development lengths for the top
bars. Because there is more than
of concrete below the top bars,
. Thus, for the
bars,
, and for the
bars,
.
6. Locate the actual cut-off points for the
negative-moment reinforcement.
Again, the inner cutoffs will be considered first,
because their location affects the design of the
outer cutoffs. The choice of actual cut-off points is
illustrated in Fig. b below.
a) Cutoff J. Two
bars are cut off;
Effects of shear. Extend bars by
past the theoretical flexural
cut off. Cut off at
from A and
from B, say,
.

436

bars. The two

top bars in span AB is at

Reinforced Concrete II

Dr. Nasr Abboushi

Anchorage of negative-moment steel. The bars must extend


from the point of
maximum bar stress. For the two
top bars, the maximum bar stress is at B. The
actual bar extension is
. This exceeds
therefore OK.
Cut off two
bars at
from B (point J in Fig. b).
b) Cutoff H. Two
bars cut off.
Anchorage. Bar must extend
past J, where
therefore OK. Extend two
from the end of the beam (point H in Fig. b).

. Length available
bars to

c) Cutoff K. Two
bars are cut off. The theoretical flexural cut off is at
from C
(
from B).
Effect of shear. Extend bars
. The end of the bars is at
from B, say,
.
Anchorage. Extend past B. for a
top bar
. The extension of
is thus not enough. Try extending the
top bars
past B to point K.
Therefore, cut off two
bars at
from B (point K in Fig. b). Note that this is
changed in the next step.

437

Reinforced Concrete II

Dr. Nasr Abboushi

d) Cutoff L. Two
bars are cut off.
Anchorage. The bars must extend
past K. For a
top bar
. The available extension is
which is less than
therefore, not OK. Two solutions are available: either extend all the bars to the end
of the beam, or change the bars to six
bars in two layers. We shall do the
former.
The final actual cut-off points are shown in the next figure.
7. Check whether extra stirrups are required at cutoffs. ACI Code Section 12.10.5
prohibits bar cutoffs in a tension zone, unless
12.10.5.1:

at actual cutoff

) at that point, or

12.10.5.2: Extra stirrups are provided at actual cut-off point, or


12.10.5.3: The continuing flexural reinforcement at the flexural cutoff has twice the required
(
).
and
Because we have determined the theoretical cut-off points on the basis of the continuing
reinforcement having 1.0 times the required
it is unlikely that we could use ACI Code
Section 12.10.5.3, even though the actual bar cut-off points were extended beyond the
theoretical cut-off points. Further, because we only need to satisfy one of the three sections
noted, we will concentrate on satisfying ACI Code Section 12.10.5.1.
As indicated from the beam section in Fig. b on page 432, the initial shear design was to use
double-leg stirrups throughout the length of the beam. We can determine the value
for
(
)

(
From this,

. So, if

at the actual cut-off point exceeds

need to modify the design for the stirrups to increase

, and thus,

, we will

a) Cutoff F. This cutoff is at


from B, which is in a flexural tension zone for the
bottom reinforcement. From Fig. b (page 432), for load Case 1, the shear at F is:
where the sign simply indicates the direction of the shear force. This value for
so we must either decrease the spacing for the
to a larger (

) stirrup. We will try

stirrups at a

and then,
438

spacing:

exceeds

stirrups or change

Reinforced Concrete II

Dr. Nasr Abboushi

This value exceeds so the modified stirrup design is OK. This tighter spacing should start at
the cut-off point and extend at least a distance toward the maximum positive-moment
region. For simplicity, use a
stirrup spacing from the center of support B for 1.65
in. toward midspan of span AB (see next Figure).
b) Cutoff J. The cutoff is located at
from B. The flexural tension that occurs in
these bars is due to load Case 2 (Figure on page 437). By inspection,
at J is
considerably less than

. Therefore, no extra stirrups are required

at this cut off.


The final reinforcement details are shown in next figure. For nonstandard beams such as this
one, a detail of this sort should be shown in the contract drawings.
The calculations just carried out are tedious, and if the underlying concepts are not
understood, the detailing provisions are difficult to apply. Several things can be done to
simplify these calculations. One is to extend all of the bars past their respective points of
inflection so that no bars are cut off in zones of flexural tension. This reduces the number of
cutoffs required and eliminates the need for extra stirrups, on one hand, while requiring
more flexural reinforcement, on the other. A second method is to work out the flexural cutoff points graphically.

Example
Design the simply supported beam shown below. The dead load is
including the weight of the beam. The live load consist of a concentrated load of
midspan.
Take
.
Use
@
for vertical stirrups. Assume
for self-weight.
439

not
at

Reinforced Concrete II

Dr. Nasr Abboushi

Solution:
(
)
(
)
Take
At midspan

.
.
(

(
(

For

)
440

Reinforced Concrete II

Dr. Nasr Abboushi

For

(a)

, and

(b) half the center-to-center spacing of the bars; one bar only (no spacing)
Thus,

For

:
(a)

, and

(b) half the center-to-center spacing of the bars;


(
Thus,
.

NOTE: according to ACI 12.2.3 It shall be permitted to use


even if transverse reinforcement is present.
441

as a design simplification

Reinforced Concrete II

Dr. Nasr Abboushi

For

The length of

from symmetrical center of beam

Take
The total length of
For

is

The total length of

is

442

Reinforced Concrete II

Dr. Nasr Abboushi

Example
Design the beam shown below. The total factored load is
Take
.
Stirrups
@


Solution:

Point of inflection (when

443

Reinforced Concrete II

Dr. Nasr Abboushi

For (

(
(

For

(
(

)
)

Development length:

For

:
(c)

, and

(d) half the center-to-center spacing of the bars; one bar


only (no spacing)
Thus,
.

Splitting plane

(
444

Reinforced Concrete II

Dr. Nasr Abboushi

For

For

:
(c)

, and

(d) half the center-to-center spacing of the bars;


(
)
Thus,
.

Splitting plane

For

(outer or corner bars):


(a)

, and

(b) half the center-to-center spacing of the bars;


(

Splitting plane

Thus,

445

Reinforced Concrete II

Dr. Nasr Abboushi

The final length of bars will be calculated and checked as discussed in the example
(page 431). These bars are illustrated in the above figure.
446

Reinforced Concrete II

Dr. Nasr Abboushi

12.10 SPLICES OF REINFORCEMENT.


Frequently, reinforcement in beams and columns must be spliced. There are four types of
splices: lapped splices, mechanical splices, welded splices, and end-bearing splices. All four
types of splices are permitted, as limited in ACI Code Sections 12.14, 12.15, and 12.16.
Tension Lap Splices
In a lapped splice, the force in one bar is transferred to the concrete, which transfers it to
the adjacent bar. The force-transfer mechanism shown in Fig. a is clearly visible from the
crack pattern sketched in Fig. b. The transfer of forces out of the bar into the concrete
causes radially outward pressures on the concrete, as shown in Fig. c; these pressures, in
turn, cause splitting cracks along the bars similar to those shown in Fig. a (page 395). Once
such cracks occur, the splice fails as shown in the next photo. The splitting cracks generally
initiate at the ends of the splice, where the splitting pressures tend to be larger than at the
middle.

As shown in Fig. b, large transverse cracks occur at the discontinuities at the ends of the
spliced bars. Transverse reinforcement in the splice region delays the opening of the splitting
cracks and hence improves the splice capacity.
ACI Code Section 12.15 distinguishes between two types of tension lap splices, depending on
the fraction of the bars spliced in a given length and on the reinforcement stress at the
splice. Table R12.15.2 of the ACI Commentary is reproduced below. The splice lengths for
each class of splice are as follows:
Class A splice:
Class B splice:

447

Reinforced Concrete II

Dr. Nasr Abboushi

Because the stress level in the bar is accounted for in Table above, the reduction in the
development length for excess reinforcement allowed in ACI Code Section 12.2.5 is not
applied in computing for this purpose.
The center-to-center distance between two bars in a lap splice cannot be greater than onefifth of the splice length, with a maximum of
. (ACI Code Section 12.14.2.3). Bars
larger than
cannot be lap spliced, except for compression lap splices at footing-to448

Reinforced Concrete II

Dr. Nasr Abboushi

column joints (ACI Code Section 15.8.2.3). Lap splices should always be enclosed within
stirrups, ties, or spirals, to delay or prevent the complete loss of capacity indicated in the
previous photo. As indicated in ACI Code Sections 12.2.2 and 12.2.3, the presence of
transverse steel may lead to shorter and hence shorter splices. ACI Code Section 21.5.2.3
requires that tension lap splices of flexural reinforcement in beams resisting seismic loads be
enclosed by hoops or spirals.
For lap splices of slab and wall reinforcement, effective clear spacing of bars being spliced at
the same location is taken as the clear spacing between the spliced bars (R12.15.1). This
clear spacing criterion is illustrated in (a). Spacing for noncontact lap splices (spacing
between lapped bars not greater than (
) lap length nor
) should be considered
the same as for contact lap splices. For lap splices of column and beam bars, effective clear
spacing between bars being spliced will depend on the orientation of the lapped bars; see
Fig. (b) and (c), respectively.

The designer must specify the class of tension lap splice to be used. The class of splice
depends on the magnitude of tensile stress in the reinforcement and the percentage of total
reinforcement to be lap spliced within any given splice length as shown in Table above. If the
area of tensile reinforcement provided at the splice location is more than twice that required
for strength (low tensile stress) and
or less of the total steel area is lap spliced within the
required splice length, a Class A splice may be used. Both splice conditions must be satisfied,
otherwise, a Class B splice must be used. In other words, if the area of reinforcement
449

Reinforced Concrete II

Dr. Nasr Abboushi

provided at the splice location is less than twice that required for strength (high tensile
stress) and/or more than 1/2 of the total area is to be spliced within the lap length, a Class B
splice must be used.

Compression Lap Splices


Reinforcing bars in compression are spliced mainly in columns, where bars are most often
terminated just above each floor or every other floor. This is done partly for construction
convenience, to avoid handling and supporting very long column bars, but it is also done to
permit column steel area to be reduced in steps, as loads become lighter at higher floors.
Compression bars may be spliced by lapping, by direct end bearing, or by welding or
mechanical devices that provide positive connection. The minimum length of lap for
compression splices is set according to ACI Code 12.16:
For bars with
(

For bars with

but not less than


. For
less than
, the required lap is increased by onethird. When bars of different size are lap-spliced in compression, the splice length is to be
the larger of the development length of the larger bar and the splice length of the smaller
bar. In exception to the usual restriction on lap splices for large-diameter bars,
and
bars may be lap-spliced to
and smaller bars.
End-Bearing Splices
Direct end bearing of the bars has been found by test and experience to be an effective
means for transmitting compression. In such a case, the bars must be held in proper
alignment by a suitable device.
Section 12.16.4 specifies the requirements for end-bearing compression splices. End-bearing
splices are only permitted in members containing closed ties, closed stirrups or spirals
(12.16.4.3). Section R12.16.4.1 cautions the engineer in the use of end-bearing splices for
bars inclined from the vertical. End-bearing splices for compression bars have been used
almost exclusively in columns and the intent is to limit use to essentially vertical bars
because of the field difficulty of getting adequate end bearing on horizontal bars or bars
significantly inclined from the vertical. Mechanical or welded splices are also permitted for
compression splices and must meet the requirements of 12.14.3.2 or 12.14.3.4, respectively.
Column Splices
Lap splices, butt-welded splices, mechanical connections, or end-bearing splices may be used
in columns, with certain restrictions. Reinforcing bars in columns may be subjected to
compression or tension, or, for different load combinations, both tension and compression.
Accordingly, column splices must conform in some cases to the requirements for
compression splices only or tension splices only or to requirements for both. ACI Code 12.17
450

Reinforced Concrete II

Dr. Nasr Abboushi

requires that a minimum tension capacity be provided in each face of all columns, even
where analysis indicates compression only. Ordinary compressive lap splices provide
sufficient tensile resistance, but end-bearing splices may require additional bars for tension,
unless the splices are staggered.
Type of lap splice to be used will depend on the bar stress at the splice location, compression
or tension, and magnitude if tension, due to all factored load combinations considered in the
design of the column. Type of lap splice to be used will be governed by the load combination
producing the greatest amount of tension in the bars being spliced. The design requirements
for lap splices in column bars can be illustrated by a typical column load-moment strength
interaction as shown.
Bar stress at various locations along the strength interaction curve define segments of the
strength curve where the different types of lap splices may be used. For factored load
combinations along the strength curve, bar stress can be readily calculated to determine
type of lap splice required. However, a design dilemma exists for load combinations that do
not fall exactly on the strength curve (below the strength curve) as there is no simple exact
method to calculate bar stress for this condition.

A seemingly rational approach is to consider factored load combinations below the strength
curve as producing bar stress of the same type, compression or tension, and of the same
approximate magnitude as that produced along the segment of the strength curve
intersected by radial lines (lines of equal eccentricity) through the load combination point.
451

Reinforced Concrete II

Dr. Nasr Abboushi

This assumption becomes more exact as the factored load combinations being investigated
fall nearer to the actual strength interaction curve of the column. Using this approach, zones
of bar stress can be established as shown in the previous figure.
For factored load combinations in Zone 1, all column bars are considered to be in
compression. For load combinations in Zone 2 of the figure, bar stress on the tension face of
the column is considered to vary from zero to
in tension. For load combinations in
Zone 3, bar stress on the tension face is considered to be greater than
in tension. Type
of lap splice to be used will then depend on which zone, or zones, all factored load
combinations considered in the design of the column are located. The designer need only
locate the factored load combinations on the load-moment strength diagram for the column
and bars selected in the design to determine type of lap splice required. Use of load-moment
design charts in this manner will greatly facilitate the design of column bar splices. For
example, if factored gravity load combination governed design of the column, say Point A in
the figure above, where all bars are in compression, but a load combination including wind,
say Point B, produces some tension in the bars, the lap splice must be designed for a Zone 2
condition (bar stress is tensile but does not exceed
in tension).
The design requirements for lap splices in columns are summarized in the Table below. Note
that the compression lap splice permitted when all bars are in compression (see 12.17.2.1)
considers a compression lap length adequate as a minimum tensile strength requirement.

For lap splices, where the bar stress due to factored loads is compression, column lap splices
must conform to the requirements presented in the previous section for compression
splices. Where the stress is tension and does not exceed
, lap splices must be Class B if
more than one-half the bars are spliced at any section, or Class A if one-half or fewer are
spliced and alternate lap splices are staggered by . If the stress is tension and exceeds
then lap splices must be Class B, according to ACI Code.
If lateral ties are used throughout the splice length having an area of at least
in
both directions, where
is the spacing of ties and
is the overall thickness of the
member, the required splice length may be multiplied by
but must not be less than

452

Reinforced Concrete II

by

Dr. Nasr Abboushi

. If spiral reinforcement confines the splice, the length required may be multiplied
but again must not be less than
.

End-bearing splices, as described above, may be used for column bars stressed in
compression, if the splices are staggered or additional bars are provided at splice locations.
The continuing bars in each face must have a tensile strength of not less than
times
the area of reinforcement in that face.
As mentioned in before, column splices are commonly made just above a floor. However, for
frames subjected to lateral loads, a better location is within the center half of the column
height, where the moments due to lateral loads are much lower than at floor level. Such
placement is mandatory for columns in "special moment frames" designed for seismic loads.

Splices of welded deformed wire reinforcement in tension


For tension lap splices of deformed wire reinforcement, the code requires a minimum lap
length of
, but not less than
Lap length is measured
between the ends of each
reinforcement
sheet.
The
development length
is the
value calculated by the provisions
in 12.7. The code also requires
that the overlap measured
between the outermost cross
wires be at least
. The
next Figure shows the lap length requirements.
If there are no cross wires within the splice length, the provisions in 12.15 for deformed wire
must be used to determine the length of the lap.
453

Reinforced Concrete II

Dr. Nasr Abboushi

Splices of welded plain wire


reinforcement in tension
The minimum length of lap for
tension lap splices of plain wire
reinforcement is dependent upon
the ratio of the area of
reinforcement provided to that
required by analysis. Lap length is
measured between the outermost
cross wires of each reinforcement
sheet. The required lap lengths are
shown in Figure below.

Example
Compute the minimum lap length of the reinforcement at the retaining wall joints shown
below.
Take
.
Solution:
Clear cover

(a)

, and

(b) half the center-to-center spacing


of the bars;
Thus,

Class B lap splice

Take

454

Reinforced Concrete II

Dr. Nasr Abboushi

Example
An axially loaded reinforced concrete column of
dimension with six bars of
is intended to lapped at a floor level. Determine the lap length of the reinforcement.
Take
Ties

.
@

Solution:

RC Slab

In the 300 mm direction:

In the 450 mm direction:

Take

455

Reinforced Concrete II

Dr. Nasr Abboushi

Example
Design the tension lap splices for the grade beam shown below.

Take
.
Dimensions of the Beam section
bars top and bottom (continuous).
Stirrups
@
(entire span)
Bending moments

IMPORTANT: Preferably, splices should be located away from zones of high tension. For a typical
grade beam, top bars should be spliced under the columns, and bottom bars about midway between
columns. Even though in this example the splice at A is not a preferred location, the moment at A is
relatively small. Assume for illustration that the splices must be located as shown.

Solution:
Assuming all bars are spliced at the same location.

(c)

, and

(d) half the center-to-center spacing of the bars; (


Thus,
.

456

Reinforced Concrete II

Dr. Nasr Abboushi

Lap Splice of Bottom Reinforcement at Section B

Class B lap splice required


Note: Even if lap splices were staggered (
with (

), a Class B splice must be used

Class B Splice
It is better practice to stagger alternate lap splices. As a result, the clear spacing between
spliced bars will be increased with a potential reduction of development length.
Clear spacing
Center-to-center spacing of bars being developed
Distance from center of bar to concrete surface
Thus,
457

Reinforced Concrete II

Dr. Nasr Abboushi

Class B Splice
Use 1.1 m lap splice @ B and stagger alternate lap splices.
Lap Splice of Top Reinforcement at Section A
As size of top and bottom reinforcement is the same, computed development and splice
lengths for top bars will be equal to that of the bottom bars increased by the 1.3 multiplier
for top bars.
In addition, because positive and negative factored moments are different, the ratio of
provided to required reinforcement may affect the type of splice as demonstrated below.
@

If alternate lap splices are staggered at least a lap length (As spliced = 50%):
Class A splice may be used
If all bars are lap spliced at the same location (within required n lap length):
Class B splice must be used
Assuming splices are staggered, the top bar multiplier will be 1.3.
Class A splice
Use 1.1 m lap splice @ A also, and stagger alternate lap splices.

458

Reinforced Concrete II

Dr. Nasr Abboushi

Example
Design the lap splice for the tied column detail shown.
Continuing bars from column above (
Offset bars from column below (
)
Take
.
Dimensions of the column section
.
bars (above and below floor level)
Ties
@

Lap splice to be designed for the following factored load


combinations:
1.
2.
3.

Solution:
1. Determine type of lap splice required.
Type of lap splice to be used depends on the bar stress at
the splice location due to all factored load combinations
considered in the design of the column. For design
purposes, type of lap splice will be based on which zone, or
459

Reinforced Concrete II

Dr. Nasr Abboushi

zones, of bar stress all factored load combinations are located on the column load-moment
strength diagram. The load-moment strength diagram (column design chart) for the
column with
bars is shown above, with the three factored load
combinations considered in the design of the column located on the interaction strength
diagram.
Note that load combination (2) governed the design of the column (selection of
bars).
For load combination (1), all bars are in compression (Zone 1), and a compression lap splice
could be used. For load combination (2), bar stress is not greater than
(Zone 2), so a
Class B tension lap splice is required; or, a Class A splice may be used if alternate lap splices
are staggered. For load combination (3), bar stress is greater than
(Zone 3), and a Class
B splice must be used.

Lap splice required for the


bars must be based on the load combination producing
the greatest amount of tension in the bars; for this example, load combination (3) governs
the type of lap splice to be used.
Class B splice required
460

Reinforced Concrete II

Dr. Nasr Abboushi

2. Determine lap splice length


.
a) distance from center of bar being developed
to the nearest concrete surface
, and
b) half the center-to-center spacing of the bars.
Clear spacing between bars being developed is large
and will not govern.
Thus,
.

Class B splice
Use
lap splice for the

bars at the floor level indicated.

461

Vous aimerez peut-être aussi