QAS 14-15-20-24 Kd
QAS 14-15-20-24 Kd
Instruction Manual for AC Generators
Printed matter N
9829 3096 41
01/2011
-4-
Congratulations on the purchase of your AC generator. It is a solid, safe and reliable machine, built according to the
latest technology. Follow the instructions in this booklet and we guarantee you years of troublefree operation. Please
read the following instructions carefully before starting to use your machine.
While every effort has been made to ensure that the information in this manual is correct, Atlas Copco does not assume
responsibility for possible errors. Atlas Copco reserves the right to make changes without prior notice.
Contents
Safety precautions for portable
generators ......................................................6
Leading particulars .....................................13
Maintenance ................................................42
Maintenance schedule ...........................42
Engine maintenance...............................44
(*) Measuring the alternator
insulation resistance...............................44
Engine oil specifications ........................44
Engine oil level check .............................45
Engine oil and oil filter change..............45
Engine coolant specifications ................46
Coolant check..........................................47
Storage ....................................................48
Preparing for operation after storage ...48
Installation...............................................36
Connecting the generator ......................37
Before starting ........................................38
Operating Qc1002 ...............................39
Operating Qc2002 ...............................40
-5-
Disposal ........................................................71
Introduction
The policy of Atlas Copco is to provide the users of their
equipment with safe, reliable and efficient products.
Factors taken into account are among others:
-
-6-
-7-
-8-
-9-
- 10 -
- 11 -
- 12 -
Leading particulars
General description
The QAS 14 and QAS 20 are AC generators, built for continuous running at sites where no electricity is available or as stand-by in cases of interruption of the mains. The
generator operates at 50/60 Hz, 230/240 V in line-to-neutral mode and 400/480 V in line-to-line mode. The QAS 14 and QAS 20 generators are driven by a fluid-cooled
diesel engine, manufactured by KUBOTA. An overview of the main parts is given in the diagram below.
ESB
FCW
1
2
3
4
5
6
7
ESB
FCF
FCW
FCF
2
7
- 13 -
Lifting beam
Side doors
Engine exhaust
Data Plate
Door, access to control and indicator panel
Output terminal board
Earthing rod (not available in combination with an ITrelay)
Emergency stop button
Filler cap fuel
Filler cap coolant
BS
DFO
AF
FCW
F
VI
FCO
G1
FF
DPF
DH
OLD
OF
DFW
- 14 -
A
AF
BS
C
DFO
DFW
DH
DPF
E
F
FCF
FCO
FCW
FF
G1
OF
OLD
VI
Alternator
Air filter
Battery switch
Coupling
Drain flexible engine oil
Drain flexible coolant
Drain and access hole (in the frame)
Drain plug fuel
Engine
Fan
Filler cap fuel
Filler cap engine oil
Filler cap coolant
Fuel filter
Battery
Oil filter
Engine oil level dipstick
Vacuum indicator
Bodywork
The alternator, the engine, the cooling system, etc. are
enclosed in a sound-insulated bodywork that can be
opened by means of side doors (and service plates).
The recess in the roof has a lifting rod in the middle.
diesel
Markings
- 15 -
Position 1
Closed
Position 2
H0
Qc1002 Module
H0
P4
400
500
P3
80
300
40
200
20
100
0
S20
S20
Qc 1002
145
A1
F10
F10
0
10
Qc 145
Q1
N13
Reset
On
Fault
Test
X1
L1
L2
L3
X25
PE
X25
- 16 -
Power
Qc 1002
145
Remote
Power
DOWN: Is used to scroll through the
display information and to adjust
parameter value downwards.
Alarm
Remote
Alarm
- 17 -
Parameter list
Alarm list
LOG list
Battery Voltage
Fuel level
the
the
Qc1002
LOG List
v1.00.0
Battery 13.2 V
00168.1h
Parameter display
Parameter
This view shows a number of Parameter settings and
gives access to them.
An overview is given in Parameter list on page 19.
Alarm List
0 Alarm(s)
Service 1
Service 2
59h
59h
- 18 -
Fuel
75%
00168.1h
This view shows the Fuel level and the running hours.
400V
50Hz
00168.1h
This view shows the voltage, frequency and running
hours.
Parameter list
The Parameter Menu's are pre-programmed!
PREHEAT
COOLDOWN
- 19 -
Language selection
Icons is the default factory set language, but 6
other languages can be selected: English, French,
German, Italian, Spanish and Cyrillic (Russian).
All information in the Parameter List display is
always in English.
Generator Underfrequency: failclass, enable,
delay, setpoint
Generator Overfrequency: failclass, enable, delay,
setpoint
Generator Undervoltage: failclass, enable, delay,
setpoint
Generator Overvoltage: failclass, enable, delay,
setpoint
It's possible to scroll between configuration menu's
by using the pushbuttons UP and DOWN.
Pushing the ENTER button activates the
configuration menu which is shown at the display.
This is the described menu flow for changing the unit type:
Qc1002
Qc 1002
145
145
Parameter
Running time
Unit type
Unit type
- 20 -
GENERATOR
UNDERVOLTAGE
LOW OIL
PRESSURE
GENERATOR
OVERFREQUENCY
GENERATOR
UNDERFREQUENCY
GENERATOR
OVERVOLTAGE
HIGH COOLANT
TEMPERATURE
SERVICE TIMER
1
CHARGING
ALTERNATOR
SERVICE TIMER
2
- 21 -
ENGINE ALARM
LOG list
Installation wirings:
Events are:
shutdowns
Qc1002
Water
Time:
START FAILURE
Fail classes
All the activated alarms of the Qc1002 have their
own pre-defined fail class.
All alarms are enabled according to one of these three
statuses:
disabled alarm, no supervision of alarm (OFF).
STOP FAILURE
00001h
1
2
3
4
Controller type
Event number
Event
Running hours
- 22 -
S20
A1
S20
F10
F10
Q1
N13
Reset
Qc2002 Module
On
Fault
Test
X1
L1
L2
L3
X25
PE
X25
- 23 -
Power
G
.
GENERATOR
CONTACTOR: Is used to
open or close the Generator
contactor, if the Qc2002
is in Manual Operation
Qc2002
Automatic
145
Start
Alarm
Stop
G
Generator
Contactor
Mains
Contactor
Power
Automatic
Start/Stop
Generator
contactor
- 24 -
Mains
contactor
Alarm
the
the
Parameter list
Alarm list
LOG list
Battery Voltage
Fuel level
kWh counter
Generator currents
Parameter display
Parameter
This view shows a number of Parameter settings and
gives access to them.
An overview is given in Parameter list on page 28.
G L1-L2
G L2-L3
G L3-L1
400V
400V
400V
Qc2002
1.00.1
This view shows the controller type and the ASW
version number.
- 25 -
Alarm List
0 Alarm(s)
This view shows the number of active alarms and
gives access to them.
An overview is given in Alarm Display (pop-up
window) on page 32.
LOG List
Battery 13.2 V
00168.1h
Service 1
Service 2
59h
59h
Fuel
75%
0.00
50Hz
50Hz
00168.1h
This view shows the Fuel level and the running hours.
G L1-L2
G f L1
P
400V
50Hz
80kW
4860kWh
PF
G f L1
M f L1
- 26 -
P
Q
S
80kW
0kVAr
80kVA
M L1-L2
M L2-L3
M L3-L1
400V
400V
400V
100A
100A
100A
G I1
G I2
G I3
G L1-N
G L2-N
G L3-N
230V
230V
230V
M L1-N
M L2-N
M L3-N
230V
230V
230V
START OFF/
EXTENDED
STOP TIMER
- 27 -
Parameter list
Island operation
Genset mode
Horn Delay
Genset Mode
Island
Island
0.0s
20.0s
990.0s
AMF
This menu is used to set the delay, how long the
general alarm relay stays energized (if present). If set
to 0.0s, the general alarm relay will stay energized
continuously.
- 28 -
Unit menu
Running Time
Cur.
168
20000
St 2 Reset
No
Yes
St 1 Reset
No
No
Unit
C/bar
C/bar
MF high freq
F/psi
No
MF high frequency
Language
English
Icons is the default factory set language, but 6 other
languages can be selected: English, French, German,
Italian, Spanish and Cyrillic (Russian). All
information in the Parameter List display is always in
English.
Yes
- 29 -
100%
110
120%
MF low freq
80%
90
100%
M frequency delay
MF high voltage
M freq delay
10s
30
9900s
2.0
MF high volt
100%
110
120%
MF low volt
MF freq delay
1.0s
M voltage delay
990.0s
80%
90
100%
- 30 -
M volt delay
10s
30
9900s
MF volt delay
1.0s
2.0
990.0s
> Volt
Enable
enable
enable
disable
warning
FC
warning
0
SP
450
< Volt
shutdown
< Volt
999
Enable
enable
enable
< Volt
99
warning
disable
99
< Volt
SP
450
999
Overfrequency enable
FC
warning
Delay
Undervoltage setpoint
Undervoltage failclass
Overvoltage delay
0
> Volt
Undervoltage enable
Overvoltage failclass
> Volt
Undervoltage delay
Overvoltage setpoint
Overvoltage enable
shutdown
> Freq
Enable
enable
enable
disable
Overfrequency failclass
> Freq
warning
- 31 -
warning
FC
shutdown
> Freq
SP
38
< Freq
70
SP
38
Underfrequency enable
< Freq
Enable
disable
warning
warning
Underfrequency failclass
< Freq
70
enable
enable
99
Underfrequency setpoint
Overfrequency setpoint
Underfrequency delay
Overfrequency delay
FC
shutdown
- 32 -
GENERATOR
OVERVOLTAGE
ENGINE ALARM
GENERATOR
UNDERVOLTAGE
EMERGENCY
STOP
GENERATOR
OVERFREQUENCY
START FAILURE
GENERATOR
UNDERFREQUENCY
STOP FAILURE
SERVICE TIMER
1
HZ/V FAILURE
SERVICE TIMER
2
OIL LEVEL
LOW OIL
PRESSURE
HIGH COOLANT
TEMPERATURE
CHARGING
ALTERNATOR
LOW FUEL
LEVEL
- 33 -
OIL
TEMPERATURE
LOG list
Fail classes
Events are:
shutdowns
service timer 1/2 reset
Together with each event, the real time of the event
will be stored.
1
Qc2002
EVENT LOG #04
Water
Time:
27/6
14:27
1
2
3
4
Controller type
Event number
Event
Date and hour of the event
- 34 -
H0
P4
400
500
P3
80
300
40
200
20
100
0
S2
S20
Qc 1002
145
F10
S13
Reset
Q1
N13
N13
On
Fault
Test
Q1
X1
X1
L1
L2
L3
PE
- 35 -
Operating instructions
- 36 -
Installation
Place the generator on a horizontal, even and solid
floor.
The generator should be kept with the doors
closed, in order to avoid the ingress of water and
dust. Dust ingress reduces the lifetime of filters
and may reduce your generator's performance.
Check that the engine exhaust is not directed
towards people. If the generator is operated
indoors, install an exhaust pipe of sufficient
diameter to duct the engine exhaust towards the
outside. Check for sufficient ventilation so that the
cooling air is not recirculated. If necessary,
consult Atlas Copco.
Leave enough space for operation, inspection and
maintenance (at least 1 meter at each side).
Check that the inner earthing system is in
compliance with the local legislation.
Use coolant for the engine cooling system. Refer
to the Engine instruction book for the proper
coolant mixture.
- 37 -
3 I L R cos + X sin
e = -----------------------------------------------------------------------------1000
e = Voltage drop (V)
I = Rated current (A)
L = Length of conductors (m)
R = Resistance (/km to VDE 0102)
X = Reactance (/km to VDE 0102)
Protection
Before starting
Drain any coolant and sediment from the fuel prefilter. Check the fuel level and top up if necessary.
It is recommended to fill the tank after the days
operation to prevent coolantdamp in a nearly
empty tank from condensing.
- 38 -
Operating Qc1002
Starting Qc1002
To start up the unit locally, proceed
as follows:
Switch on the battery switch, if applicable.
Switch off circuit breaker Q1. This is not
necessary when a plant contactor is installed
between Q1 and the load.
Put the starter switch S20 in position I (ON). The
unit starts a preheating cycle which takes 12
seconds.
After the preheating period, the unit will start. The
starting attempt will take maximum 12 seconds.
Switch on circuit breaker Q1.
- 39 -
Stopping Qc1002
To stop the unit locally, proceed as
follows:
Switch off the load.
Switch off circuit breaker Q1.
Let the engine run for about 5 minutes.
Stop the engine by putting the starter switch S20
in position O.
Lock the side doors and the door of the indicators
and control panel to avoid unauthorized access.
Operating Qc2002
Starting Qc2002
or
- 40 -
Stopping Qc2002
- 41 -
Maintenance
Maintenance schedule
Before carrying out any maintenance activity, check that the start switch is in position O and that no electrical power is present on the terminals.
Maintenance schedule
Daily
2912 6382 05
1625 0010 72
Service pak
For the most important subassemblies, Atlas Copco has developed service kits that combine all wear parts. These service kits offer you the benefits of genuine parts,
save on administration costs and are offered at reduced price, compared to the loose components. Refer to the parts list for more information on the contents of the
service kits.
Check for air, fuel, coolant and oil leakage
- 42 -
Test thermostats
- 43 -
Notes:
Engine maintenance
- 44 -
Engine
between -15C (5F)
and 40C (104F)
between -25C (-13F)
and 40C (104F)
Type of lubricant
PAROIL E
PAROIL Extra
Specifications PAROIL
PAROIL from Atlas Copco is the ONLY oil tested
and approved for use in all engines built into Atlas
Copco compressors and generators.
Extensive laboratory and field endurance tests on
Atlas Copco equipment have proven PAROIL to
match all lubrication demands in varied conditions. It
meets stringent quality control specifications to
ensure your equipment will run smoothly and
reliably.
The quality lubricant additives in PAROIL allow for
extended oil change intervals without any loss in
performance or longevity.
PAROIL provides wear protection under extreme
conditions. Powerful oxidation resistance, high
chemical stability and rust- inhibiting additives help
reduce corrosion, even within engines left idle for
extended periods.
PAROIL contains high quality anti-oxidants to
control deposits, sludge and contaminants that tend to
build up under very high temperatures.
PAROIL's detergent additives keep sludge forming
particles in a fine suspension instead of allowing them
to clog your filter and accumulate in the valve/rocker
cover area.
PAROIL releases excess heat efficiently, whilst
maintaining excellent bore-polish protection to limit
oil consumption.
PAROIL has an excellent Total Base Number (TBN)
retention and more alkalinity to control acid
formation.
PAROIL prevents Soot build-up.
Liter
US
gal
Imp
gal
cu.ft
Order
number
can
1.3
1.1
0.175
1630 0135 00
can
20
5.3
4.4
0.7
1630 0136 00
US
gal
Imp
gal
cu.ft
Order
number
can
1.3
1.1
0.175
1615 5953 00
can
20
5.3
4.4
0.7
1615 5954 00
barrel
209
55.2
46
7.35
1615 5955 00
- 45 -
Specifications PARCOOL EG
- 46 -
Liter
US
gal
Imp
gal
cu.ft
Order
number
can
1.3
1.1
0.175
1604 5308 00
can
20
5.3
4.4
0.7
1604 5307 01
barrel
210
55.2
46
7.35
1604 5306 00
Coolant check
Monitoring coolant condition
In order to guarantee the lifetime and quality of the
product, thus to optimise engine protection, regular
coolant-condition-analysis is advisable.
Visual check
pH measurement
Check the pH value of the coolant using a pHmeasuring device.
The pH-meter can be ordered from Atlas Copco
with part number 2913 0029 00.
Typical value for EG = 8.6.
If the pH-level is below 7 or above 9.5, the coolant
should be replaced.
Topping up of coolant
Verify if the engine cooling system is in a good
condition (no leaks, clean,...).
Check the condition of the coolant.
If the condition of the coolant is outside the limits,
the complete coolant should be replaced (see
section Replacing the coolant).
Always top-up with PARCOOL EG.
Topping up the coolant with water only, changes
the concentration of additives and is therefore not
allowed.
Flush
Flush twice with clean water. Used coolant must
be disposed or recycled in accordance with laws
and local regulations.
From the Atlas Copco Instruction book, determine
the amount of PARCOOL EG required and pour
into the radiator top tank.
It should be clearly understood that the risk for
contamination is reduced in case of proper
cleaning.
In case a certain content of other coolant remains
in the system, the coolant with the lowest
properties influences the quality of the mixed
coolant.
Fill
To assure proper operation and the release of
trapped air, run the engine until normal engine
operation temperature is reached. Turn off the
engine and allow to cool.
Recheck coolant level and add if necessary.
- 47 -
- 48 -
Checking voltmeter P4
Put a voltmeter in parallel with voltmeter P4 on
the control panel.
Check that the read-out of both voltmeters is the
same.
Stop the generator and disconnect one terminal.
Check that the internal resistance of the voltmeter
is high.
Checking ammeter P3
Measure during the load, by means of a clamp-on
probe, the outgoing current in the third phase (L3).
Compare the measured current with the current
indicated on ammeter P3. Both readings should be
the same.
- 49 -
Alternator troubleshooting
Symptom
Possible cause
Blown fuse.
Replace fuse.
No residual voltage.
Reset voltage.
Intervention of protection.
Winding failure.
Check windings.
Corrective action
Reset voltage.
Failed regulator.
Substitute regulator.
Intervention by protection.
Current too high, power factor lower than 0.8; speed lower than 10%
of rated speed.
Failed regulator.
Substitute regulator.
Failed regulator.
Substitute regulator.
- 50 -
Defective gauge.
Misfire
Fault in atomisers.
Fault in cold start system.
- 51 -
Defective gauge.
Engine overload.
Vibration
Crankcase pressure
Restriction in breather pipe.
Vacuum pipe leaks or fault in exhauster.
Bad compression
Fan damaged.
- 52 -
Circuit diagrams
Battery switch
Power circuit
Unit
Circuit
QAS 14-15-20-24 Kd
QAS 14-15-20-24 Kd - 1 phase
9822 0992 65
9822 0992 66
Engine circuit
Unit
Circuit
QAS 14-15-20-24 Kd
9822 0992 77
Controller circuit
Unit
Circuit
- 53 -
9822 0992 78
9822 0992 79
Battery switch
The battery switch is situated inside the soundinsulated bodywork. It allows to open or to close the
electrical connection between the battery and the
engine circuits.
DEIF
xxxxxxxx
-power in control
To make sure that the engine can start and accept load
immediately, an external coolant heater (1000 W,
240 V) is provided which keeps the engine
temperature between 38C and 49C.
xxxx
xxxx
xxxxxxxxxxx
xxxxxxxxxxxxxxxx
xxxxxxxxxxxxxxx
xxxxxxxxxxxxxx
voltage
Setting:
Lower output
rotation
= Counterclockwise
- 54 -
P4
400
500
H0
P3
80
300
40
200
20
100
0
P4
500
S20
80
40
200
20
Qc 1002
P3
100
X5
400
300
X5
S20
Qc 1002
145
145
F10
N13
Q4
X3
Q3
N13
16A-30mA
Reset
Q5
On
Q1
Q3
Reset
Fault
On
Fault
Test
Test
Q5
X3
Q5
X2
X1
L1
Q5
16A-30mA
L2
L3
X1
PE
- 55 -
L1
L2
L3
PE
On
Fault
Test
Q1
Q1
N13
Reset
Box
Q1
N13
Reset
IT-relay
X1
X1
On
Fault
Test
L1
L2
PE
Q1
X1
X1
L1
L2
L3
PE
- 56 -
S2
H0
P4
400
500
P3
80
300
40
200
20
100
0
S20
Qc 1002
145
F10
Q1
N14
Q1
N14
X1
X1
L1
L2
L3
PE
- 57 -
View outside
Position 1
Wheel chocks
EFT
EFR
Position 2
View inside
EFR
EFT
EFT
EFR
- 58 -
Wheel chocks
- 59 -
Technical specifications
Technical specifications for QAS 14 15 units
Readings on gauges
Gauge
Reading
Unit
Ammeter L3 (P3)
Voltmeter (P4)
A
V
Settings of switches
Switch
Function
Activates at
Shut down
Shut down
0.5 bar
103C
QAS14
QAS15
50 Hz
60 Hz
50 Hz
1500 rpm
PRP
100 kPa
30%
25C
60 Hz
1800 rpm
PRP
100 kPa
30%
25C
Reference conditions 1)
Rated frequency
Rated speed (optional)
Generator service duty
Absolute air inlet pressure
Relative air humidity
Air inlet temperature
Limitations 2)
50C
4000 m
85%
-18C
-25C
50C
4000 m
85%
-18C
-25C
Performance data 2) 3) 5)
11 kW
10.5 kW
13 kW
13 kW
- 60 -
Mode of operation
Site
Operation
Start-up and control mode
- 61 -
0.8 cos
1.0 cos
13.7 kVA
10.5 kVA
400 V
NA
230 V
19.8 A
NA
45.7 A
G2
11 kW
100%
< 5%
isochronous
0.9 kg/h
2.0 kg/h
2.6 kg/h
3.0 kg/h
0.279 kg/kWh
33 h
N/A
13 g/h
89 dB(A)
0.8 cos
1.0 cos
16.3 kVA
13 kVA
480 V
220 V
240 V
19.6 A
42.8 A
54.2A
G2
13 kW
100%
< 5%
isochronous
1.3 kg/h
2.2 kg/h
2.9 kg/h
3.7 kg/h
0.298 kg/kWh
26,7 h
N/A
18.5 g/h
91 dB(A)
115 l
N/A
11 kW
100%
115 l
N/A
13 kW
100%
PRP
land use
single
manual/automatic
PRP
land use
single
manual/automatic
Start-up time
Mobility/Config. acc. to ISO 8528-1:1993
(optional)
Mounting
Climatic exposure
Degree of protection
Status of neutral (TT or NT)
Status of neutral (IT) (optional)
Alternator 4)
Standard
Make
Model
Rated output, class H temp. rise
rating type acc. ISO 8528-3
Degree of protection
Insulation stator class
Insulation rotor class
Number of wires
Engine 4)
Standard
Type KUBOTA
Rated net output
rating type acc. ISO 3046-7
production tolerance
Coolant
Combustion system
Aspiration
Number of cylinders
Swept volume
Speed governing
Capacity of oil sump
Capacity of cooling system
Electrical system
- 62 -
unspecified
transportable/D
mobile/E
fully resilient
open air
IP 54
earthed
insulated
unspecified
transportable/D
mobile/E
fully resilient
open air
IP 54
earthed
-
IEC34-1
ISO 8528-3
LEROY SOMER
LSA40.S3
15 kVA
BR
IP 23
H
H
12
IEC34-1
ISO 8528-3
LEROY SOMER
LSA40.S3
19 kVA
BR
IP 23
H
H
12
ISO 3046
ISO 8528-2
D1703M-BG
12.8 kW
ICXN
5%
coolant
direct injection
natural aspirated
3
1.7 l
electronic
8l
9l
12 Vdc
ISO 3046
ISO 8528-2
D1703M-BG
15.1 kW
ICXN
5%
coolant
direct injection
natural aspirated
3
1.7 l
electronic
8l
9l
12 Vdc
Emission compliance
Power circuit
EU STAGE II
Circuit-breaker, 3-ph.
Number of poles
Thermal release It (thermal release is higher at 25C)
Magnetic release Im
4
20 A
3..5xIn
4
20 A
3..5xIn
NA
NA
NA
4
50 A
3..5xIn
2
50 A
3..5xIn
2
63A
3..5xIn
0.030-30 A
10-100 kOhm
0.030-30 A
-
Dimensions (LxWxH)
Weight net mass
Weight wet mass
- 63 -
Notes
1)
2)
3)
4)
5)
Derating
Height
(m)
0
500
1000
1500
2000
2500
3000
3500
0
100
100
95
85
80
75
70
65
5
100
100
90
85
80
75
70
65
10
100
100
90
85
80
75
65
60
15
100
95
90
85
75
70
65
60
- 64 -
20
100
95
90
80
75
70
65
60
Temperature
(C)
25
100
95
85
80
75
70
65
60
30
100
90
85
80
75
65
60
60
35
95
90
85
75
70
65
60
55
40
95
85
80
75
70
65
66
55
45
90
85
80
75
70
65
60
55
50
90
85
75
70
65
60
55
50
Reading
Unit
Ammeter L3 (P3)
Voltmeter (P4)
A
V
Settings of switches
Switch
Function
Activates at
shut down
shut down
0.5 bar
105C
Reference conditions 1)
Rated frequency
Rated speed (optional)
Generator service duty
Absolute air inlet pressure
Relative air humidity
Air inlet temperature
Limitations 2)
Performance data 2) 3) 5)
- 65 -
QAS20
QAS24
50 Hz
60 Hz
50 Hz
1500 rpm
PRP
100 kPa
30%
25C
60 Hz
1800 rpm
PRP
100 kPa
30%
25C
50C
4000 m
85%
-18C
-25C
50C
4000 m
85%
-18C
-25C
16.0 kW
14.0 kW
0.8 cos
1.0 cos
19.4 kW
16.0 kW
0.8 cos
1.0 cos
Mode of operation
Site
Operation
Start-up and control mode
Start-up time
Mobility/ Config. acc. to ISO 8528-1:1993
(optional)
- 66 -
20.0 kVA
14 kVA
400 V
NA
230 V
28.9 A
NA
60.9 A
G2
16.0 kW
100%
< 5%
isochronous
1.0 kg/h
2.7 kg/h
3.3 kg/h
4.2 kg/h
0.260 kg/kWh
23.5 h
N/A
21 g/h
90 dB(A)
24.2 kVA
16 kVA
480 V
220 V
240 V
29.1 A
60.4 A
66.7 A
G2
19.4 kW
100%
< 5%
isochronous
1.3 kg/h
3.2 kg/h
4.1 kg/h
4.6 kg/h
0.254 kg/kWh
21.5 h
N/A
23 g/h
94 dB(A)
115 l
N/A
16.0 kW
100%
115 l
N/A
19.4 kW
100%
PRP
land use
single
manual/automatic
unspecified
transportable/D
mobile/E
PRP
land use
single
manual/automatic
unspecified
transportable/D
mobile/E
Mounting
Climatic exposure
Degree of protection (cubicle)
Status of neutral (TT or TN)
Status of neutral (IT) (optional)
Alternator 4)
Standard
Make
Model
Rated output, class H temp. rise
rating type acc. ISO 8528-3
Degree of protection
Insulation stator class
Insulation rotor class
Number of wires
Engine 4)
Standard
Type KUBOTA
Rated net output
rating type acc. ISO 3046-7
production tolerance
Coolant
Combustion system
Aspiration
Number of cylinders
Swept volume
Speed governing
Capacity of oil sump
Capacity of cooling system
Electrical system
Emission compliance
- 67 -
fully resilient
open air
IP 54
earthed
insulated
fully resilient
open air
IP 54
earthed
-
IEC34-1
ISO 8528-3
LEROY SOMER
LSA 40.M5
20 kVA
BR
IP 23
H
H
12
IEC34-1
ISO 8528-3
LEROY SOMER
ISO 3046
ISO 8528-2
V2403M-BG
18.8 kW
ICXN
5%
coolant
direct injection
natural aspirated
4
2.4 l
electronic
9l
9l
12 Vdc
EU STAGE II
ISO 3046
ISO 8528-2
V2403M-BG
22.1 kW
ICXN
5%
coolant
direct injection
natural aspirated
4
2.4 l
electronic
9l
9l
12 Vdc
LSA 40.M5
25 kVA
BR
IP 23
H
H
12
Power circuit
Circuit-breaker, 3-ph.
Number of poles
Thermal release It (thermal release is higher at 25C)
Magnetic release Im
4
32 A
3..5xIn
4
32 A
3..5xIn
NA
NA
NA
4
63 A
3..5xIn
2
63A
3..5xIn
2
63A
3..5xIn
0.030-30 A
10-100 kOhm
0.030-30 A
-
Dimensions (LxWxH)
Weight net mass
Weight wet mass
- 68 -
Notes
1)
2)
3)
4)
5)
Derating
Height
(m)
0
500
1000
1500
2000
2500
3000
3500
0
100
100
95
85
80
75
70
65
5
100
100
90
85
80
75
70
65
10
100
100
90
85
80
75
65
60
15
100
95
90
85
75
70
65
60
- 69 -
20
100
95
90
80
75
70
65
60
Temperature
(C)
25
100
95
85
80
75
70
65
60
30
100
90
85
80
75
65
60
60
35
95
90
85
75
70
65
60
55
40
95
85
80
75
70
65
60
55
45
90
85
80
75
70
65
60
55
50
90
85
75
70
65
60
55
50
Dataplate
1
1 bar
14.504 psi
1g
0.035 oz
1 kg
2.205 lb
-YA3---
1 km/h
0.621 mile/h
1 kW
1l
0.264 US gal
1l
1l
0.035 cu.ft
1m
3.281 ft
11
1 mm
0.039 in
1 m/min
35.315 cfm
12
13
1 mbar
0.401 in wc
1N
0.225 lbf
1 Nm
0.738 lbf.ft
tF
32 + (1.8 x tC)
tC
(tF - 32)/1.8
4
5
6
A
B
C
7
8
9
10
14
15
16
- 70 -
A
B
C
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Disposal
General
When developing products and services, Atlas Copco
tries to understand, address, and minimize the
negative environmental effects that the products and
services may have, when being manufactured,
distributed, and used, as well as at their disposal.
Recycling and disposal policy are part of the
development of all Atlas Copco products. Atlas
Copco company standards determine strict
requirements.
Disposal of materials
- 71 -
- 72 -
Circuit diagrams
- 73 -
T2
T3
T11
T8
T12 T5
T8
T2
240V-60Hz
T1
T2
T3
141
V1
T9
T2
PE
T1
U1
bx0
T5
400V/480V
N1
0V
T11
T8
T7
T10
T11
W1
bx0
T3
V1
110
T1
T4
T6
6-
U1
29
a0
5+
T7
T10 T11
T8
T6 T12
T3
T9
6-
b0
PE
ESee Note 2
N1
a2
T1
T4
5+
b0
W1
28
E+
R12
G3
G3
N12
Canopy
Cubicle
142
c8
to Circ.Diagr ENGINE
Ampere-meter
143
c8
c8
T3
140
to Circ.Diagr ENGINE
Ampere-meter
F2
F3
N
a0
a0
ELR-Relay
IT-Relay
b54
a6
N14
R
PE
N1
a0
a6
N13
S2b
a2
a3
(0)
a2
a3
a3
a6
a3
(0)
13
Q1
a3
y54 y54
c2
S13
PE
g54
a3
U>
c1
12
a3
a6
12 5
to Circ.Diagr CONTROLLER
a2
a6
a0
F1-F3
G3
N12
N13
N14
Q1
Q4
Q5
R5
R12
S2b
118
13
a2
T13
31 34
12
102
118
13
118
13
12
a6
A2
a0
a6
118
a3
A1
A2
5
A1
T1
T2
In
R<
a0
to Circ.Diagr ENGINE
V-meter & Control Module
U1
F1
V1
y54
x6
125
N1
W1
x0
W1
x0
N1
x0
V1
U1
c8
126
T2
127
T1
(0)
124
Dual Frequency
D E
- 74 -
S12
S13
T1-T3
T13
U1
X1
Fuses 4 A
Alternator
Automatic voltage regulator
Earth leakage relay (O)
IT-relay (O)
Circuit breaker (O)
Circuit breaker 16 A (O)
Circuit breaker 16 A/30 mA (O)
Coolant heater (O)
Voltage adjustment 1 k (O)
Emergency stop
(S2a: see Controller circuit)
50/60 Hz switch (O)
E.L.R. Disable switch (O)
Current transformers
Torus earth leakage (O)
Battery charger (O)
Terminal board
U1 a6
B-
a2
H
I
J
K
L
B+
x0
QAS
14-20
30-40
PE
L3
x0
x0
b6 (0)
L2
b0
L1
(0)
441
Cubicle
Canopy
441
b6
441
b0
R5
442
442
X3
X4
X5
X9
(O)
Coolant Heater
PE
Battery charger
D E
x6
y54
X1
b6
442
X2 X3 X4 X5
- 32A 16A 16A-1ph
63A 32A 16A 16A-1ph
Q2 Q3 Q4 Q5
- (Q1) 16A 16A/30mA
(Q1) 32A 16A 16A/30mA
Notes
b0
L1
240V-60Hz
T1
60/5A
60/5A
100/5A
150/5A
Q1
40A
63A
100A
125A
Wire Size x
10mm2
16mm2
35mm2
50mm2
Wire Size y
10mm2
16mm2
16mm2
25mm2
L3
PE
x0
x0
x0
y54
1
x6
L1
L2
L3
PE
T13 y54
X1
PE
PE-EDF
e0
e0
e0
e6
e54
g6
g54
e0
L3 N
32A
PE
L3
PE
L3
L2
N
c54
c6
c0
Q5
c0
5L3
4L3
4L2
4L1
c0
e0
L3 N
L2 L1
c54
16A
30mA
3L3
3L2
3L1
e0
X2
63A
c6
16A
PE
2N
2L3
2L2
g0
c0
c0
X3
c0
L3 N
X4
c6
X5
N
16A
L2 L1
16A
L2 L1
(0)
- 75 -
Legend
Wire size :
Colour code :
2
0 = black
a = 1 mm 2
1 = brown
b = 1.5mm2
2 = red
c = 2.5mm2
3 = orange
d = 4 mm 2
4 = yellow
e = 6 mm 2
5 = green
f = 10 mm2
6 = blue
g = 16 mm2
7 = purple
h = 25 mm2
8 = grey
i = 35 mm 2
9 = white
j = 50 mm2
54 = green/yel.
k = 70 mm2
l = 95 mm2
lx = 95 mm 2EPR-CSP (BS6195-4C)
bx = 1.5 mm NSGAFOeU
Q4
32A
g0
c0
c0
(0)
5N
Q3
g0
L1
PE
L3
L1
L2
See Note 3
H
I
J
K
L
(0)
to T13.Tx
PE
QAS
14
20
30
40
L2
PE
Wire Size y
2.5mm2
6mm2
10mm2
16mm2
Wire Size x
2.5mm2
6mm2
10mm2
16mm2
L3
Q1
20A
32A
50A
63A
L2
T1
30/5A
30/5A
60/5A
60/5A
L1
400V/480V
QAS
14
20
30
40
2L1
to Circ.Diagr CONTROLLER
13
12
F1-F2
G3
N12
N13
N14
Q1
Q3
Q5
R5
R12
S2b
5+
T7
E-
6-
T10
T11
29
See Note 2
a0
T1
T4
T5
T8
T12
110
T8
T11
T8
230V
50Hz
T3
T1
T3
to Circ.Diagr ENGINE
Ampere-meter
143
U1
0V
T2
T6
PE
a2
R12
G3
E+
W1
28
N12
Canopy
Cubicle
c8
see Note 4
T1
140
to Circ.Diagr ENGINE
Ampere-meter
y54
x0
x0
F1
U1
W1
c8
F2
a0
IT-Relay
a0
b54
a6
PE
a3
a2
a3
102
118
13
118
13
a2
A2
a3
a6
a2
T13
31 34
a3
(0)
13
118
a6
T1
T2
In
A1
12
a3
N13
S2b
R<
A1 A2
118
13
12
N14
Q1
a3
y54 y54
c2
S13
PE
f54
a3
12
a3
a6
U>
c1
12 5
to Circ.Diagr CONTROLLER
a2
a6
- 76 -
a0
a0
see Note 5
N1
(0)
125
(0)
126
Dual Frequency
to Circ.Diagr ENGINE
V-meter & Control Module
S12
S13
T1
T13
U1
X1
X2
X3
X5
(O)
Fuses 4 A
Alternator
Automatic voltage regulator
Earth leakage relay (O)
IT-relay (O)
Circuit breaker
Circuit breaker 32 A (O)
Circuit breaker 16 A/30 mA (O)
Coolant heater (O)
Voltage adjustment 1 k (O)
Emergency stop
(S2a: see Controller circuit)
50/60 Hz switch (O)
E.L.R. Disable switch (O)
Current transformer
Torus earth leakage (O)
Battery charger (O)
Terminal board
Outlet socket 63 A (O)
Outlet socket 32 A (O)
Outlet socket 16 A (O)
Optional equipment
E
N
PE
L
x0
x6
63A
e6
4L
c0
X5
L
32A
PE
c6
L
16A
y54
X1
(0)
L1
L2
PE
1ph
Legend
Wire size :
L
e0
X3
X2
N
T1
60/5A
60/5A
T1
60/5A
60/5A
PE
4N
3L
b0
QAS
14
20
QAS
230V/240V 14
1ph - ZZ
20
PE
16A
30mA
32A
g54
g54
3N
g6
c54
c6
c0
Q5
PE
L
L
g0
230V-50Hz
1ph - ZZ
e54
e6
b6 (0)
b6
PE
b0
(0)
e0
Q3
441
441
b6
g0
441
b0
Cubicle
Canopy
442
x0
x0
R5
g6
x0
442
Battery charger
x6
B+
PE
g54
x54
Coolant Heater
a2
442
to Circ.Diagr CONTROLLER
U1 a6
B-
L1 L2 L3 N
13
12
PE
Notes
Colour code :
2
0 = black
a = 1 mm 2
1 = brown
b = 1.5mm2
2 = red
c = 2.5mm2
3 = orange
d = 4 mm 2
4 = yellow
e = 6 mm 2
5 = green
f = 10 mm2
6 = blue
g = 16 mm2
7 = purple
h = 25 mm2
8 = grey
i = 35 mm 2
9 = white
j = 50 mm2
54 = green/yel.
k = 70 mm2
l = 95 mm2
lx = 95 mm 2EPR-CSP (BS6195-4C)
bx = 1.5 mm NSGAFOeU
- 77 -
S8
S10
Y1
b3
a2
GND
GND
Speed sensor B+
a3
d2
c2
K1
16
M1
K0
d2
K0
+
M
G2
E1
B7
B+
+
IG
GND
B11
M6
M
K1
Legend
Wire size :
a6
Colour code :
2
= 1 mm 2
= 1.5mm2
= 2.5mm2
= 4 mm 2
= 6 mm 2
= 10 mm2
= 16 mm
h = 25 mm2
i = 35 mm 2
j = 50 mm2
k = 70 mm 2
lx = 95 mm 2ERP-CSP (BS6195-4C)
bx = 1.5 mm NSGAFOeU
0
1
2
3
4
5
= black
= brown
= red
= orange
= yellow
= green
a6
6 = blue
7 = purple
8 = grey
9 = white
54 = green/yel.
- 78 -
b6 b6
a6
a6
12
12
12
12
12
12
a6
12
(O)
12
a
b
c
d
e
f
g
Main B+
S9
1 19
50
Solenoid (-)
b3
20
49
Solenoid (+)
17
18
47
Direct B+
Oil switch
Speed switch
Charge signal
34
a3
a3
13
a3
a3
15
28
a3
A4
C2
X10 A4 X10 C2
a3
12
27
a3
S1
a3
16
26
G1
15
a2
32
48
a3
1
N11
17
26
a3 a3 a3
46
a2
a3
c2
A5
X10 A5
C5
X10 C5
C4
X10 C4
c2
C1 B1 B2
X10 C1 B1 B2
11
C3
X10 C3
A3
X10 A3
17
A1
X10 A1
a6
B7
B11
E1
G1
G2
K0
K1
M1
M6
S1
N11
S8
S9
S10
X10
Y1
(O)
- 79 -
143
c2
14
15
38
14
125
NO
NO
Com
Com
NO
NO
NO
Generator Contactor
Preheat Relay
Generator Voltage L1
Start/Stop
Remote Start
Input
Input
Input
a2 a3 a3
18
19
9 12 13 14 15 16 17 18
7
a3 a3
a2
a2
a3
13
a6
a6
a3
- 80 -
12
a2
C3
X10 C3
11
c2
A3
X10 A3
a3 a3 a3
C1 B1 B2
X10 C1 B1 B2
a6
C4
X10 C4
c2
A1
X10 A1
to Circ.Diagr POWER
X9.13
17
a2
K5
3
12
c2
19 18
12
10A
a6 a3
S20
F10
17
Input
GND
CAN-H
Input
Input
GND
17
a2
*only on QAS30/40
17
a0
13
a6
CAN-L
P4
V
11
128
a0
6
10
4
129
3 1 2
12
140
c8
11 12 8
Generator Voltage L2
Qc1002
143
0 Vdc (Batt-)
A
P3
c8
S4
A
P2
142
to Circ.Diagr POWER
Current Transfo T1-T3
126 127
126
12
140
141
P1
c8
126
125
a0
23 24 25 32 33 34 35 36
Com
126
125
*only on QAS14/20
a0 a0
5
7
9
a3 a3 a0 a3 a3 a3
19 21
P4
c8
a0
a0 a0
a0
a0
17
Circ.Diagr POWER
Curr.Transfo T3
a6 a2
c8
126
125
126
125
a0
B
C
D
A1 26 27
a0
124 125
S20
X10
X25
(O)
a0 a0
a0
S2a
P3
c8
S4
S12b
Circ.Diagr POWER
Fuses F1-F2
F10
H0
K5
P1-P3
P4
S2a
Circ.Diagr POWER
Fuses F1-F3
A1
X25
442
441
12
60Hz
Generator Contactor
Output: 12Vdc, max.8Adc1
b6 b0
X25
5 6
Fx Fx
6A 6A
(*) N L1
(*)= Connect L2 to X25.5
with 230Vd-systems
MAINS SUPPLY (1P+N)
Customer's Installation
(see Instruction Manual)
26
50Hz
Sx=Remote
Start/Stop-switch
12
a6
38
to A1.17
PE
S12b
to Circ.Diagr POWER
X9.441 & X9.442
a3 a3
a0 a6
X25
X25
1 2
3 4
Sx
X25
PE
18
19
B
C
D
to A1.18
a3
C4
X10 C4
(0)
12
Dual Frequency
e2 e2
a6
C4
X10 C4
to Circ.Diagr POWER
X9.5
Legend
Wire size :
15
12
a3
K5
12
a3
H0
a6
a6
a6
A5
X10 A5
a3
C5
X10 C5
12
15
E
a3
a
b
c
d
e
f
g
12
(0)
60Hz
a3
to Circ.Diagr POWER
X9.12
a6
A4
C2
X10 A4 X10 C2
- 81 -
Colour code :
2
= 1 mm 2
= 1.5mm2
= 2.5mm2
= 4 mm 2
= 6 mm 2
= 10 mm2
= 16 mm
h = 25 mm2
i = 35 mm 2
j = 50 mm2
k = 70 mm 2
lx = 95 mm 2ERP-CSP (BS6195-4C)
bx = 1.5 mm NSGAFOeU
0
1
2
3
4
5
= black
= brown
= red
= orange
= yellow
= green
6 = blue
7 = purple
8 = grey
9 = white
54 = green/yel.
c8
3 Phase
c8
c8
a0 a0 a0 a6
c8
a6
(0)
a2
A B
1
2
3
GND
Input
5
6
7
8
9
CD
E F G
- 82 -
W/L-Input D+
Input
Spare Output
NO
H I J K
L MN
NO
Com
NO
s2
s1
s2
s1
s2
s1
37 38 39 41 43 45 46 47 49 50 51 52
Com
Com
NC
Com
NO
c8
c8
c8
c8
53 54 55 56 57 58
Qc2002
12 13 14 15 16 17 18 23 24 25 32 33 34 35 36
PE
PE
Fx
2 3 4 5
Fx Fx Fx Fx
6A
6A 250mA 250mA 250mA
N
L1 L1 L2 L3
X25
a6 b6 b0 a0 a0 a0 a0 a0 a0 a6
6
7
8
12
18
to A1.18
to A1.38
to Circ.Diagr POWER
X9.441 & X9.442
124
447
446
445
444
443
442
442
441
441
124
towards
X25.8
141
12
a6
140
a6
142
c8
140
140
442
446
125
447
443
441
444
445
125
126
124
127
17
12
124
125
140
141
143
c8
Preheat Relay
NO
Mains Contactor
Generator Contactor
Mains Voltage L1
Mains Voltage L2
Mains Voltage L3
Generator Voltage L1
Generator Voltage L2
Generator Voltage L3
a0 a6 a0 a0 a0 a0 a6 a0 a0 a0 a0 a0
NO
Remote Start
Common for Relay Outputs
Input
Com
Input
Input
Input
Input
a6
125
a6 a2
Input
(0)
0 Vdc (Batt-)
c8
12/24 Vdc (Batt+)
A1 26 27
Input
124
a0
a6
CAN-H
a0
127
124
141
a0
GND
a0
126
125
to Circ.Diagr POWER
Fuse F1
a0
CAN-L
125
c8
126
c8
127
140
c8
124
c8
140
143
c8
142
Single Phase
141
c8
to Circ.Diagr POWER
Fuses F1-F3
to Circ.Diagr POWER
Current Transfo T1
c8
17
140
to Circ.Diagr POWER
Current Transfo T1-T3
a3 a6
X25
9 10
Sx
Sx=Remote
Start/Stop-switch
S20
a2
10A
a2 a3 a3
a3 a3 a3
14
15
L MN
14
18
H I J K
17
F10
13
a6 a3
c2
17
E F G
11
CD
12
A B
a3 a3 a3
X25
a2
K5
12
14
a6
a3
to Circ.Diagr POWER
X9.12
12
S2a
a6
12
13
c2
a2
to A1.17
19
a6
a6
C4
X10 C4
a3
C4
X10 C4
a3
A5
X10 A5
0 = black
1 = brown
2 = red
3 = orange
4 = yellow
5 = green
6 = blue
7 = purple
8 = grey
9 = white
54 = green/yel.
to A1.16
a6
a6
a6
C2
X10 C2
K5
12
a = 1 mm 2
b = 1.5mm2
c = 2.5mm2
d = 4 mm 2
e = 6 mm 2
f = 10 mm2
g = 16 mm
2
h = 25 mm2
i = 35 mm 2
j = 50 mm2
k = 70 mm 2
lx = 95 mm 2ERP-CSP (BS6195-4C)
bx = 1.5 mm NSGAFOeU
a6
12
Colour code :
2
a3 a3
A4 C5
X10 A4 C5
to Circ.Diagr POWER
X9.5
(0)
to A1.17
12
12
Dual Frequency
Legend
Wire size :
12
26
a3 a3 a3
C1 B1 B2
X10 C1 B1 B2
15
12
a2
C3
X10 C3
a3
17
c2
A3
X10 A3
11
c2
A1
X10 A1
50Hz
60Hz
S12b
to Circ.Diagr POWER
X9.13
K5
a6
e2 e2
C4
X10 C4
(0)
Single Phase
(0)
A1
F10
K5
S2a
S12b
S20
X10
X25
(O)
- 83 -
- 84 -
www.atlascopco.com