K-LINE INSULATORS LIMITED

50 Passmore Avenue, Toronto, Ontario M1V 4T1


Tel: (416) 292-2008 - Fax: (416) 292-2094
E-Mail insulators@k-line.net
Web Page: www.k-line.net

Dear Sir/Madam,
I'm pleased to introduce you to our complete line of polymer insulated products. The attached
K-LINE INSULATORS catalogue includes the products we are currently offering to the utility
industry.
Other products are under development and will be available shortly. As these products come on
the market, we will issue you the pertinent information. In the meantime, if you require an
insulator configuration not shown in the catalogue, give us a call.
If you would like to receive updates to our catalogue, please mail us at insulators@k-line.net to
be included in our database.
We look forward to fulfilling your polymer insulator needs. Should you have any questions or
need further information, feel free to call me at (416) 292-2008.
Sincerely,
K-LINE INSULATORS LIMITED

A.J. (Tony) Carreira, P.Eng.


President

K-LINE INSULATORS LIMITED


50 Passmore Avenue, Toronto, Ontario, Canada, M1V 4T1
Tel; (416) 292-2008 Fax: (416) 292-2094
E-Mail; insulators@k-line.net Web Page: www.k-line.net

K-LINE INSULATORS PROFILE

K-LINE INSULATORS is a quality silicone insulator manufacturer.


The company was established in 1983 with its head office located in Toronto, Ontario,
Canada. K-LINE INSULATORS products are distributed world-wide through a
consolidated network of representatives.
Product lines manufactured by K-LINE INSULATORS include transmission and
distribution suspension, line post and station post insulators, featuring our patented
Universal Line Post design. Other products include riser support insulators, dead-end
extension insulators, polymer-coated guy strains, and specialty insulators for in-line
switches, air-break switches, interphase spacers, railways and live line tools. These
insulators are designed to the various standards (i.e. CSA, CEA, ANSI, IEEE, IEC, etc.).
K-LINE INSULATORS introduced a patented Universal Polymeric Line Post End Fitting
design. The end fitting is referred to as the "K" clamp. Finally, there is one line post
insulator that can be installed in either a horizontal or vertical configuration, with the
clamp integrated into the insulator design. Some of the immediate benefits of the "K"
clamp are that it is made of corrosion resistant aluminum casting, has the capability to
accommodate a full range of conductor sizes, contains only a single captive live-line
operable bolt, and no loose parts. Purchasers of the "K" clamp have been able to take
advantage of labour cost savings in stringing, sagging, and conductor clamping, along
with other savings related to shipping, stocking, and maintenance. The "K" clamp has
performed excellently in the field since 1992.
K-LINE INSULATORS has excellent engineering resources and test facilities for product
development. K-LINE INSULATORS uses its own proprietary technologies, designs and
rubber formulations, in the manufacture of all its insulator products.
K-LINE INSULATORS' highly developed proprietary silicone rubber formulation is
characterized by its superior contamination performance. All insulators are injection
molded, one piece, and exhibit self-cleaning characteristics. The rubber is bonded to the
fibreglass core strength member. These products have a long and proven performance
record in severely contaminated environments.
Continued on next page >

K-LINE INSULATORS LIMITED


50 Passmore Avenue, Toronto, Ontario, Canada, M1V 4T1
Tel; (416) 292-2008 Fax: (416) 292-2094
E-Mail; insulators@k-line.net Web Page: www.k-line.net

K-LINE INSULATORS PROFILE (Continued)

K-LINE INSULATORS manufactures all of its products and is registered to the rigid
Quality Assurance Standards of the ISO9001 program. The company is audited on a
continuous basis by its customers and an internationally recognized quality management
auditing firm.
K-LINE INSULATORS is known for its readiness to listen to its customers' needs for
customized polymeric insulator designs that meet their special requirements. We offer
appropriate support in the proper selection of insulators to suit the application, with
training and documentation on special installation requirements. K-LINE INSULATORS
is committed to a continuous improvement policy in quality, service, delivery, and cost
reduction. Much pride comes from the innovation of new products and the continuous
improvements of present products to ensure that the insulators are the most cost effective
and have a long term system performance.
K-LINE INSULATORS approach to innovative insulator solutions is well demonstrated
and respected by its customers.
K-LINE INSULATORS people are totally dedicated to continuous quality and
performance improvement. They are dedicated to developing the best materials and
designs that lead to optimum product solutions. These characteristics amongst others,
have contributed to the success of the various strategic alliances K-LINE INSULATORS
has forged with some of its customers.
K-LINE INSULATORS is sensitive and committed to the needs of its customers and is
always prepared to give them the service they expect and deserve.

K-Line Insulators
Catalogue Number Designation of Distribution Class Insulators
Catalogue Number
Insulator
Type

Suspension/
Deadend

KL

Company
ID

Voltage Class

Material

Insulator
Type

X
End Fittings *

K-Line

15
28
35
46
69

Shed Design

A - Alternating
sheds
No A Other shed
design

Structure End
Fitting

C- Clevis
S Socket
T Tongue
Y Y-clevis
E Oval eye

S - Silicone
rubber

Line End
Fitting

T - Tongue
H - Thimble
B Ball
E Oval eye
Y Y-clevis

N/A

Line Post

N/A

N/A

K - K-clamp
V - Vertical
H - Horizontal
T - Tie-Top C
Neck
TF - Tie-Top F
Neck
E Drop Eye

Special
Variations
A - LA insulator
F Iron Fittings
IEC 16mm ball
M - Medium SML
70 kN
N - Non-standard
R - 90 aligned
end fittings
120 120 kN
A Lock washer
Al Alum base
D - Tinned alum
line fitting
G - Gain base
M20 - 20 mm
tapped
M22 - 22 mm
tapped
M24 - 24 mm
tapped
N - Non-standard

Station Post

CP - Cap &
Pin
P - Post

T1 - Tapped one end


T2 - Tapped both ends
No Ts - Thru holes both ends

Railway

N/A

RW Railway

C- Clevis
S Socket
T Tongue
B Ball

Riser

A - Alternating
sheds
No A Other shed
design

RSI Riser
support
insulator

Interphase
Spacer

Guy

N/A

M12 - 12 mm
tapped
M16 - 16 mm
tapped
M20 - 20 mm
tapped

C- Clevis
S Socket
T Tongue
B Ball

U - Clamp

D - Tin plated
aluminum line
fitting
X 5/8 tapped
base

See Distribution and Transmission Interphase Spacers Page

Insulated
length in
inches

N/A

N/A

N/A

C- Clevis
H - Thimble
T Tongue
R Roller
B - Threaded

T - Tongue
H - Thimble
C- Clevis
R Roller
B - Threaded

R - 90 deg turn on
end fittings
S - Silicone

Note:
* Different fittings will be designated by the addition of a number to the letter.
December 7, 2002

K-Line Insulators
Catalogue Number Designation of Transmission Class Insulators
Catalogue Number

KL

Insulator
Voltage
Type
Company
Class
ID

Suspension/
Deadend

Shed
Design

Material

Insulator
Type

H High
leakage

N/A
N/A

Line Post
K-Line

Station Post

69
115
138
161
230

End Fittings
Line End
Fitting
B - Ball
T - Tongue
Y Y Clevis
E - Eye
E -Eye
V -Vertical
H -Horizontal

Structure
End Fitting
S Socket
C- Clevis
T - Tongue
Y Y Clevis
E - Eye
G Gain base
B - Curved
BF Flat 7
BF8 Flat 8

AAlternati
ng
sheds

SSilicone
rubber

No. of
Sheds

Corona
Ring

Other
Additions

M Med ring
N No ring

#
N/A

P - Post

T1 - Tapped one end


T2 - Tapped both ends
No Ts - Thru holes both
ends

A - IEC
B IEC20
R 90 Deg
S SS pin

M12 - 12 mm
tapped
M16 - 16 mm
tapped
M20 - 20 mm
tapped
N - Nonstandard
December 6, 2002

K-Line Insulators
Distribution and Transmission Interphase Spacers

Insulator

Interphase
Spacer

Number of
Characters

Total

Catalogue Number
KL

Company
ID
K-Line

Insulator

Rod

Insulator

Rod

Insulator
rubber

Rod length
if
applicable

Insulator
rubber if
applicable

3-4

0-1

0-2

0-1

0-4

0-1

Rod length
P if
if
hinged
applicable

0-2

0-2

Fitting

Fittings

Special

U
U
D Tin
Universal Universal Coupler
Clamp
Clamp
length
KK
KK
M
clamp
clamp
Medium
T Tongue T Tongue
ring
C Clevis C Clevis N No
ring
L Large
ring
AAdapter
1-2

1-2

0-3

7-22

Examples:
Insulator and rod - KL46SNX25U1U1D & KLH19X30TT
Two insulators and rod(s) - KL46SNX46SNX12U1U1D & KLH13X35XH13X30PTT
Two insulators - KL28ASX15ASU1U1D6 & KLH25XH28PCC
July 3, 2002

K-LINE INSULATORS LIMITED

Catalogue D-DS

TORONTO, ONTARIO, CANADA

DISTRIBUTION SILICONE INSULATORS


Deadend / Suspension
15 kV to 69 kV

Distribution Silicone Insulators


Deadend / Suspension
In general Overhead Distribution Lines tend to experience a large number of outages and interruptions due to
insulation failures. These failures may be from surface contamination or wetting on line insulators that result in
flashovers or pole fires.
Silicone deadend/suspension insulators offer the ultimate solution in improved performance. Because of its
hydrophobicity, this material inherently resists water filming thereby limiting leakage currents. Insulators with
reduced leakage currents, even when contaminated, require less frequent washing. The savings in such
maintenance costs are added benefits of using silicone insulators.
KLine silicone polymer distribution deadend/suspension insulators are manufactured and tested to world-class
polymer insulator standards; CEA LWIWG-01, ANSI C29.13, and IEC 1109. K-Line Insulators Limited is
registered to ISO 9001 Quality Systems.

PERFORMANCE BENEFITS
The performance benefits of K-Line Insulators distribution deadend/suspension insulators are listed below.

Improves Reliability (by minimizing interruptions and outages due to vandalism, pole fires, and flashovers in
all types of environments)
Eliminates or Reduces Maintenance (such as washing and trouble calls) and is compatible with existing plant
Improves Power Quality (less RI and TVI)
Energy Efficiency (lower losses due to lower leakage currents)
Safety (light weight for handling and installation)
Service Life (consistent performance over its service life)
Life Cycle Cost (savings over porcelain insulators)

APPLICATION
Distribution deadend/suspension insulators are used on overhead lines operating at or below 69 kV. These
insulators are used to support line conductors in suspension or deadend modes such as line terminations, angles,
and tangents. These insulators can be used with bare or covered conductors.

CORE MATERIAL
The core rod of the distribution deadend/suspension insulator is made of a high quality fiberglass that has been
specially formulated for electrical and mechanical applications.

HOUSING AND SHEDS


The housing and sheds of the insulator are one piece, injected molded silicone rubber that is chemically bonded to
the core rod. This ensures that the interface between the rubber and rod is impenetrable against moisture ingress.

DISTRIBUTION DEADEND/SUSPENSION INSULATOR

TECHNICAL DATA
SPECIFICATIONS

UNIT

Voltage Class
CEA & ANSI Class
Section Length L
Dry Arcing Distance
Leakage Distance
Low-Frequency
Dry
Flashover
Wet
Impulse Critical Flashover
(Pos.)
Radio Influence Voltage Test
(RIV) at 1 MHz
Max.
Specified Mechanical Load
(SML)
Torsional Load
Approx. Weight
Standard Packaging

kV
mm (in)
mm (in)
mm (in)
kV
kV

KL15ASCTM
15
DS15
322 (12.7)
193 (7.6)
384 (15.1)
100
70

KL28ASCTM
28
DS28
433 (17.0)
290 (11.4)
590 (23.2)
135
105

CATALOGUE NUMBER**
KL35SCTM
KL46SCT
35
46
DS35
DS46
486 (19.1)
574 (22.6)
348 (13.7)
419 (16.5)
750 (29.5)
988 (38.9)
153
180
144
150

KL46SCTA
46
646 (25.4)
490 (19.3)
1059 (41.7)
200
155

KL69HC1T116
69
DS69
733 (28.9)
627 (24.7)
1798 (70.8)
260
205

kV

145

225

264

300

355

425

kV
V

15
Below 1

20
Below 1

30
Below 3

30
Below 3

30
Below 5

44
Below 2

kN (lb)

70 (15,700)

70 (15,700)

70 (15,700)

90 (20,200)

90 (20,200)

90 (20,200)

Nm (ftlb)
kg (lb)
-

83 (62)
0.7 (1.5)
15

83 (62)
0.8 (1.8)
15

83 (62)
1.1 (2.5)
12

83 (62)
1.4 (3.0)
12

83 (62)
1.6 (3.5)
12

83 (62)
2.2 (4.8)
3

** The catalogue numbers in the above table are for CT clevis-tongue fittings. For other combinations of end
fittings or mechanical strengths, see End Fittings Section.

END FITTINGS
There are five standard end fittings that are available on the deadend/suspension insulators: clevis, tongue,
thimble eye, socket, and ball (See Below). The clevis, tongue, and thimble eye fittings are made from high
strength, corrosion resistant extruded aluminum. While the socket and ball fittings are hot-dip galvanized iron.
The end fittings are crimped on to the core rod to provide the mechanical performance. A watertight seal
between the rubber and end fittings eliminates possible moisture ingress. This special silicone rubber to metal
fittings sealing process provides total exclusion of moisture.
The end fittings of the distribution class deadend/suspension are rated for a specified mechanical strength,
SML of 70 kN (15,700 lb) or 90 kN (20,200 lb).
The clevis and tongue end fittings are the two most common fittings used with additional adaptors and
clamps. The thimble eye end fitting is a unique design that integrates the insulator tongue end fitting and a
preformed conductor grip adapter to attach to the line conductor. This thimble eye essentially eliminates one
item in the assembly and from inventory.
For other special end fittings please contact K-Line Insulators.
Clevis - C

Tongue - T

Thimble Eye H

SML 90 kN

Socket S

Ball B

SML 90 kN

SML 90 kN

K-LINE INSULATORS LIMITED


50 Passmore Avenue, Toronto, Ontario, Canada M1V 4T1
Tel.: (416) 292-2008 Fax: (416) 292-2094 E-Mail: insulators@k-line.net Web Page: www.k-line.net
March 2003

K-LINE INSULATORS LIMITED

Catalogue D-LP

TORONTO, ONTARIO, CANADA

DISTRIBUTION SILICONE INSULATORS


Line Post
15 kV to 69 kV

Distribution Silicone Insulators


Line Post
Insulator contamination is a common problem on overhead lines. The fundamental element for interruptions with
contaminated insulators is moisture. Wet atmospheric conditions result in water filming on surfaces and causing
leakage currents to develop. On wood structures, leakage currents can cause pole top fires. On steel structures,
leakage currents can develop into faults.
Silicone offers the ultimate solution in line post insulators. Because of its hydrophobicity, this material inherently
resists water filming thereby limiting leakage currents. Silicone insulators reduce leakage currents, even when
contaminated and require less frequent washing. The savings in such maintenance costs are added benefits of using
silicone insulators.
KLine silicone polymer distribution line post insulators are manufactured and tested to world-class polymer
insulator standards, CEA LWIWG-02. K-Line Insulators Limited is registered to ISO 9001 Quality Systems.

PERFORMANCE BENEFITS
The performance benefits of K-Line Insulators distribution line post insulators are listed below.

Improves Reliability (by minimizing interruptions and outages due to vandalism, pole fires, and
flashovers in all types of environments)
Eliminates or Reduces Maintenance (such as washing and trouble calls) and is compatible with existing
plant
Improves Power Quality (less RI and TVI)
Energy Efficiency (lower losses due to lower leakage currents)
Safety (light weight for handling and installation)
Service Life (consistent performance over its service life)
Life Cycle Cost (savings over porcelain insulators)

APPLICATION
Distribution line post insulators are used on overhead distribution lines operating at and below 69 kV. These
insulators are commonly installed on metal or wooden structures to horizontally or vertically support the line
conductor. Also, these insulators are used to support high voltage conductor jumpers or leads.

ROD
The core rod of the insulator is made of a high quality fiberglass that has been specially formulated for electrical
and mechanical applications.

HOUSING AND SHEDS


The housing and sheds of the insulator are one piece, injection molded silicone rubber that chemically bonds to
the core rod. This ensures that the interface between the rubber and rod is impenetrable against moisture ingress.

LINE POST INSULATORS

K-Clamp**

H-Horizontal

V-Vertical

T-TieTop (C-neck)
TF-TieTop (F-neck)

TECHNICAL DATA
SPECIFICATION

UNIT

Voltage Class
CEA Class
Section Length (L)***
Dry Arcing Distance
Leakage Distance
Critical Impulse Flashover (Positive)
Dry
Low-Frequency Flashover
Wet
Test
Radio Influence Voltage (RIV)
at 1000 kHz
Max

kV
mm (in)
mm (in)
mm (in)
kV

Specified Tensile Load (STL)


Specified Cantilever Load (SCL)
Max. Design Cantilever Load (MDCL)
Number of Sheds
Approx. Weight
Standard Packaging

kV
kV
V
kN (lb)
kN (lb)
kN (lb)
kg (lb)
-

KL15S
15
LP15
297 (11.7)
138 (5.4)
275 (10.8)
129
75
40
10
2.5
22 (5000)
12.5 (2800)
6 (1350)
2
3.4 (7.4)
3

CATALOGUE NUMBER*
KL28S
KL35S
KL46S
28
348 (13.7)
184 (7.2)
420 (16.5)
156
92
62
15
2.5
22 (5000)
12.5 (2800)
6 (1350)
3
3.7 (8.0)
3

35
LP28M
424 (16.7)
264 (10.4)
657 (25.9)
193
118
83
22
2.5
22 (5000)
12.5 (2800)
6 (1350)
5
4.3 (9.4)
3

46
LP46
501 (19.7)
339 (13.3)
860 (33.9)
240
146
111
30
2.5
22 (5000)
12.5 (2800)
6 (1350)
6
4.7 (10.3)
3

KL69S
69
LP46M
640 (25.2)
478 (18.8)
1121 (44.1)
309
203
160
30
2.5
22 (5000)
12.5 (2800)
6 (1350)
10
9.1 (20.0)
2

Ordering Information
To catalogue number, add suffix H for horizontal, V for vertical, T for C-neck Tie-top, TF for the F-neck Tie-top, or K for
K-clamp. The standard base thread is -10 UNC. Different base threads are available upon request.

** K-clamp conductor diameter range is 7.6 mm (0.30) to 34.0 mm (1.34).


*** Section lengths are for K-clamp insulators. For others refer to Section Length Adjustment Table under End Fittings.

K-LINE INSULATORS LIMITED


50 Passmore Avenue, Toronto, Ontario, Canada M1V 4T1
Tel.: (416) 292-2008 Fax: (416) 292-2094 E-Mail: insulators@k-line.net Web Page: www.k-line.net
March 2003

END FITTINGS
LINE END FITTING
The line end fitting of line post insulators are available in four different configurations: horizontal or vertical
clamp-top, tie-top, or K-clamp.
All line end fittings on line post insulators are made of corrosion resistant aluminum alloy castings.

SECTION LENGTH ADJUSTMENT


Line End Fitting

Line End Fitting Designation

Section Length

K-Clamp
Horizontal
Vertical
Tie-Top (F-neck)
Tie-Top (C-neck)

K
H
V
TF
T

See Technical Data sheet


L - 9 mm (0.4)
L - 23 mm (0.9)
L - 33 mm (1.3)
L - 53 mm (2.1)

Clamp-Top
The conventional horizontal and vertical trunnion accommodates a standard line post insulator, bolted conductor
clamp. On the horizontal design the line end fitting has an additional eye for the attachment of other devices
during installation or maintenance activities.

Tie-Top
The tie-top is designed for tying a conductor to the neck of the insulator. It is available in two standard neck
sizes: C or F-neck.

K-Clamp
K-Line Insulators Limited has introduced a new concept in the polymer line post live end fitting design. This end
fitting is referred to as the K clamp. The uniqueness of this end fitting is a result of the many advantages it has
over the traditional horizontal, vertical and tie-top configurations.
Some advantages of the K clamp include:
1) Excellent corrosion resistant aluminum casting
2) A long, smooth contoured conductor clamping zone
3) The clamp accommodates a full range of conductor sizes
4) A single captive live-line operable bolt
5) All parts are captive
6) Lower overall length permits standard cover up hoods to effectively cover all insulator sheds
7) The design can be installed in either a horizontal or vertical configuration
8) Inventory reduction is accomplished because one insulator is used for both configurations and a
separate clamp is not required
9) The price of the new insulator is cost comparative with the purchase of a standard trunnion post
insulator and a separate clamp
10) Substantial labour cost savings in stringing, sagging and conductor clamping
11) Other savings related to shipping, stocking and maintenance

BASE END FITTING


The standard base for line post insulators is a round flat iron base with a threaded hole that accommodates a
standard insulator stud or bolt. For other special bases contact K-Line Insulators Limited.
Hot-dip galvanizing to CSA G164 and ASTM A153 specifications provides corrosion protection of the base end
fitting.

New Silicone Line Post Insulator


For 69 kV Overhead Lines
K-Line Insulators has introduced a new silicone line post insulator that is applicable for 69 kV overhead lines. This
insulator is designed for installations with high electrical requirements. This insulator features the highly reliable
proprietary K-Line silicone rubber that is one piece, injection molded and chemically bonded to a high quality
epoxy fiberglass rod.
This insulator will greatly improve the electrical performance of the System, especially in contaminated
environments. Insulator contamination is a common problem on overhead lines. The fundamental element for
interruptions with contaminated insulators is moisture. Wet atmospheric conditions result in water filming on
surfaces and causing leakage currents to develop. On wood structures, leakage currents can cause pole top fires
and eventual failures. On steel structures, leakage currents can develop into faults. K-Lines proprietary silicone
material offers the ultimate solution in post insulator applications. Because of its hydrophobicity, this material
inherently resists water filming thereby limiting leakage currents. These silicone insulators reduce leakage
currents, even when contaminated and require less frequent if any washing. The savings in maintenance costs
are added benefits of using K-Line silicone insulators.
The 69 kV line post insulator has been designed to meet the requirements of CEA LWIWG-02, ANSI C29.18, and
IEC 61952. The 69 kV line post insulator is available in four different configurations: horizontal, vertical, tie-top, or
K-clamp. The K-clamp design offers the best and most cost effective solution in most cases.

69 kV K-Clamp Line Post


The K-clamp insulator has an integral clamp for attaching the
conductor directly to the line post insulator without the use of
a separate conductor clamp. The K-clamp insulator can be
mounted either in the vertical or horizontal position and offers
several advantages over the conventional line post insulators.
The K-clamp has a smooth clamping zone that accommodates
a conductor diameter range of 0.30 inch (7.6 mm) to 1.34 inch
(34 mm). The single galvanized steel clamp bolt that secures
the keeper can be operated with hot line tools from either side
of the clamp. It also extends beyond the clamp body to allow
for the attachment of stringing devices.
The K-clamp insulator can provide substantial labour cost
savings in stringing, sagging and conductor clamping. There
are other savings that can be achieved in shipping, stocking
and maintenance.

Configuration & Hardware Accessories


The 69 kV line post is available in three other configurations: vertical, horizontal, or tie-top (ANSI F-Neck). Also,
the horizontal line post can be supplied with a gain base (See below). For the clamp-top trunnions conductor
clamps are also available.

Vertical

Tie-Top

Horizontal with Gain Base

Technical Data
SPECIFICATION

UNIT

CATALOGUE
NUMBER*

SPECIFICATION

UNIT

KL69S
Voltage Class

kV

CEA Class
ANSI Class
Dry Arcing Distance
Leakage Distance
Critical Impulse Flashover (Positive)
Low-Frequency Flashover

Dry
Wet

kV

45

Max

Specified Tensile Load (STL)

kN (lb)

22 (5000)

Specified Cantilever Load (SCL)

kN (lb)

11 (2475)

551 (21.7)

Max. Design Cantilever Load (MDCL)

kN (lb)

5.5 (1240)

1511 (59.5)

Approx. Weight

kg (lb)

8.0 (17.5)

LP69M

51-16 & 51-26

kV
kV

KL69S
Test

69

mm
(in)
mm
(in)

CATALOGUE
NUMBER*

360

Radio Influence Voltage (RIV)


at 1 MHz

Standard Packaging

235
190**

* Ordering Information
To Line Post Catalogue Number, add suffix KP1 for K-clamp, HP1 for horizontal, VP1 for vertical, or TFP1 for tie-top. The standard base thread is -9 UNC.
Different base threads are available upon request.
** The value shown is as per CEA and the ANSI value is 165 kV.

K-LINE INSULATORS LIMITED


50 Passmore Avenue, Toronto, Ontario, Canada M1V 4T1
Tel.: (416) 292-2008 Fax: (416) 292-2094 E-Mail: insulators@k-line.net Web Page: www.k-line.net

July 2005

K-LINE INSULATORS LIMITED

Catalogue D-SP

TORONTO, ONTARIO, CANADA

DISTRIBUTION SILICONE INSULATORS


Station Post
15 kV to 46 kV

Distribution Silicone Insulators


Station Post
One of the most critical assets of an electrical Distribution System is the station. Not only is this asset the heart of
the supply to large electrical loads but it also serves many customers from industrial to residential. Therefore,
outages or interruptions due to insulation failures are costly and impact negatively on customer service. With KLine silicone station post insulators these are greatly minimized through improved performance to reliability and
savings in the life cycle cost.
Silicones hydrophobic property allows K-Line station post insulators to electrically outperform porcelain
insulators. The lightweight feature of polymer insulators makes them easy to handle and install. The size and
fittings of polymer station post insulators ensure that they are compatible with existing station post hardware and
arrangements. Experience with silicone polymer insulators has proven their superiority over porcelain insulators.
KLine silicone polymer distribution station post insulators are manufactured and tested to world-class polymer
insulator standards, CSA and ANSI. K-Lines Quality System is registered to ISO 9001 Quality Systems.

PERFORMANCE BENEFITS
The performance benefits of K-Line Insulators distribution station post insulators are listed below.

Improved Reliability (interruptions and outages due to vandalism, and flashovers in all types of
environments are a thing of the past)

Eliminates or Reduces Maintenance (such as washing and trouble calls) and are compatible with existing
porcelain insulators
Improves Power Quality (lower RI and TVI)
Energy Efficiency (reduced losses due to lower leakage currents)
Safety (light weight for handling and installation, eliminates catastrophic mechanical failures)
Service Life (consistent performance over its service life)
Life Cycle Cost (savings over porcelain insulators)

APPLICATION
Distribution station post insulators are used in open-type stations operating at and below 46 kV. These insulators
support the bus, leads, or other apparatus within the station.

ROD
The core rod of the distribution station post insulator is made of a high quality fiberglass that has been specially
formulated for electrical and mechanical applications.

HOUSING AND SHEDS


The housing and sheds of the insulator are one piece, injected molded silicone rubber that chemically bonds to the
core rod. This ensures that the interface between the rubber and rod is impenetrable against moisture ingress.

DISTRIBUTION STATION POST INSULATOR

TECHNICAL DATA
SPECIFICATION
Voltage Class
ANSI Technical Reference (TR)

UNIT
kV

KL15SCP

KL25SC

15

25

CATALOGUE NUMBER*
KL25SP
KL25SPN
28

28

KL35SP

KL46SPT2

35

46

No.

4 & 205

208

10

210

214

Section Length (L)

mm (in)

254 (10)

305 (12)

355 (14)

381 (15)

559 (22)

Dry Arcing Distance

mm (in)

145 (5.7)

190 (7.5)

260 (10.2)

270 (10.6)

Leakage Distance

mm (in)

275 (10.8)

420 (16.5)

635 (25)

660 (26.0)

kV

125

155

165

185

457 (18)
345
(13.6)
864
(34.0)
225

kV

130

160

175

195

240

310

kV

40

55

65

75

100

140

kV

10

15

22

22

30

30

2.5

2.5

2.5

2.5

2.5

2.5

45
(10000)
12.5
(2800)

45
(10000)
12.5
(2800)

45
(10000)
12.5
(2800)

45
(10000)
12.5
(2800)

45
(10000)
12.5
(2800)

45
(10000)

kN (lb)

6 (1350)

6 (1350)

6 (1350)

6 (1350)

6 (1350)

6 (1350)

No.

10

kg (lb)

3.4 (7.4)

3.7 (8.0)

4.2 (9.2)

4.3 (9.4)

6.0 (13.4)

9.1 (20.0)

Impulse Withstand
Critical Positive Impulse
Flashover
Low-Frequency Wet Withstand
Radio Influence
Test
Voltage (RIV) at
Max
1000 kHz
Specified Tensile Load (STL)
Specified Cantilever Load
(SCL)
Max Design Cantilever Load
(MDCL)
Number of Sheds
Approx. Weight

kN (lb)
kN (lb)

483 (19.0)
1121 (44.1)
275

12.5 (2800)

* Ordering Information:
1. Above catalogue numbers apply to insulators with through holes on both ends. (Except for KL46SPT2).
2. Add T1 to catalogue numbers for insulators with one end tapped & the other with through holes.
3. Add T2 to catalogue number for insulators with both ends tapped.

END BASES
The standard base fittings are flat round iron bases that are available with bolt circle mounting holes with
either through or tapped holes. These bases are compatible with the porcelain station post insulator
standard.
The end bases are radially swaged on to the core rod to provide the mechanical performance and reduce
the stress concentration. Our proprietary design ensures a watertight seal between the rubber and end
fitting. This special silicone rubber to metal fittings sealing process prevents moisture ingress to the core
fiberglass rod. For other special base requirements, please contact K-Line Insulators Limited.
Corrosion protection of the end bases is provided by hot-dip galvanizing to CSA G164 and ASTM A153
specifications.

K-LINE INSULATORS LIMITED


50 Passmore Avenue, Toronto, Ontario, Canada M1V 4T1
Tel.: (416) 292-2008 Fax: (416) 292-2094 E-Mail: insulators@k-line.net Web Page: www.k-line.net

March 2003

K-LINE INSULATORS LIMITED

Catalogue T-DS

TORONTO, ONTARIO, CANADA

TRANSMISSION SILICONE INSULATORS


Deadend / Suspension
69 kV to 230 kV

Transmission Silicone Insulators


Deadend / Suspension
One of the most important items on any transmission overhead line is the insulator. This item is the backbone of
the transmission system in minimizing interruptions and outages, and providing for a safe plant. Therefore, it is
essential to have high quality and dependable insulators on the system. With KLine silicone polymer
transmission insulators these objectives can be easily achieved with a substantial savings in the life cycle cost.
Experience with silicone polymer insulators has proven their superiority over porcelain insulators. Today more
Electric Utilities are shifting to silicone polymer insulators to improve overall performance on transmission
overhead lines.
KLine silicone polymer transmission suspension/deadend insulators are manufactured and tested to world-class
polymer insulator standards, CSA C411.4, ANSI C29.11 and IEC 1109. K-Line Insulators Limited is registered to
ISO 9001 Quality Systems.

PERFORMANCE BENEFITS
The performance benefits of K-Line Insulators transmission suspension/deadend insulators are listed below.

Improved Reliability (interruptions and outages due to vandalism, pole fires, and flashovers in all types of
environments are a thing of the past)
Eliminates or Reduces Maintenance (such as washing and trouble calls) and is compatible with existing plant
Improves Power Quality (less RI and TVI)
Energy Efficiency (reduced losses due to lower leakage currents)
Safety (light weight for handling and installation)
Service Life (consistent performance over its service life)
Life Cycle Cost (savings over porcelain insulators)

APPLICATION
Transmission suspension/deadend insulators are used on transmission lines operating at and above 66kV. These
insulators are installed on metal or wooden structures on cross arms to hold the conductor longitudinally (dead-end) or
vertically (suspension). The connections to the structures or arms and line vary depending on the Utilities preference.

ROD
The core rod of the transmission suspension/deadend insulator is made of a high quality fiberglass that has been
specially formulated for electrical and mechanical applications.

HOUSING AND SHEDS


The housing and sheds of the insulator are one piece, injected-molded silicone rubber that chemically bonds to the
core rod. This ensures that the interface between the rubber and rod is impenetrable against moisture ingress.

DEADEND / SUSPENSION INSULATOR

TECHNICAL DATA

TECHNICAL DATA

Catalogue
Number

Voltage
Class
kV

KL69HBS13

Section
Length (Note 1)
L
mm

(in)

Dry Arcing
Distance
mm

(in)

Leakage
Distance
mm

Positive
Critical
Impulse
Flashover

(in)

Low
Frequency
Flashover

Weight
(Note 2)

kV

Dry
kV

Wet
kV

kg

(lb)

660 (26.0)

523 (20.6)

1466 (57.7)

355

215

170

2.9 (6.3)

764 (30.1)

627 (24.7)

1798 (70.8)

425

260

205

3.3 (7.2)

KL69HBS19

867 (34.1)

732 (28.8)

2131 (83.9)

485

300

235

3.6 (8.0)

KL115HBS22

970 (38.2)

818 (32.2)

2461 (96.9)

540

335

265

4.2 (9.2)

1074 (42.3)

917 (36.1)

2794 (110.0)

600

375

300

4.5 (10.0)

KL115HBS28

1179 (46.4)

1021 (40.2)

3127 (123.1)

660

415

335

5.0 (10.9)

KL138HBS31

1281 (50.4)

1128 (44.4)

3460 (136.2)

725

455

370

5.4 (11.8)

1384 (54.5)

1229 (48.4)

3792 (149.3)

785

495

400

5.8 (12.7)

KL138HBS37

1488 (58.6)

1331 (52.4)

4125 (162.4)

845

530

430

6.1 (13.1)

KL161HBS40

1590 (62.6)

1410 (55.5)

4458 (175.5)

895

560

460

7.5 (16.4)

1694 (66.7)

1514 (59.6)

4790 (188.6)

960

605

495

7.9 (17.3)

KL161HBS46

1798 (70.8)

1618 (63.7)

5123 (201.7)

1025

650

530

8.3 (18.2)

KL230HBS49

1903 (74.9)

1722 (67.8)

5456 (214.8)

1090

695

570

8.6 (19.0)

KL69HBS16

KL115HBS25

KL138HBS34

KL161HBS43

KL230HBS52
KL230HBS55

69

115

138

161

230

2004 (78.9)

1824 (71.8)

5789 (227.9)

1155

740

605

9.0 (19.9)

2108 (83.0)

1928 (75.9)

6121 (241.0)

1220

785

640

9.5

(20.8)

Notes:
1.

Section lengths are based on ball and socket hardware. For lengths of insulators with alternate end fittings combination see
Section Lengths.

2.

Weight includes standard rings where applicable. See section on Corona Rings.

SECTION LENGTHS
The section lengths (L) published on the Technical Data sheet are for the ball and socket end fittings. For alternate
combinations of end fittings, use the following table to establish section lengths.

SECTION LENGTH ADJUSTMENT


End Fitting
ANSI Ball / Socket
ANSI Ball / Y-clevis
ANSI Ball / oval Eye
oval Eye / oval Eye
Clevis / Tongue

End Fitting
Designation
BS
BY
BE
EE
CT

Section Length
L (see Technical Data sheet)
L + 36 mm (1.4)
L + 41 mm (1.6)
L + 84 mm (3.3)
L + 21 mm (0.8)

CORONA RINGS
High voltage lines above 88 kV phase-to-phase can generate unnecessary noise (RI and TVI) and corona due to
the high electrical stress concentration. To minimize these effects gradient or corona rings are installed on the end
fitting of the insulator. Guidelines used in the application of these rings are noted below.
Insulators that are used on system voltages above 88 kV and below 150 kV are supplied with a built-in gradient
ring. Insulators that are used on system voltages from 150 kV and above are supplied with a separate corona ring
for assembly in the field before installation. The ring is designed for installation in only one orientation and
location to avoid miss application. These rings are made from aluminum that make them light weight and
corrosion resistant.

Gradient (Built-in) Ring


88 kV to below 150 kV

Corona Ring
150 kV to 230 kV

END FITTINGS
The end fittings on the transmission insulator are made of high strength, cast (forged) steel. The insulators have a
specified mechanical load (SML) rating of 120 kN (27,000 lbs.). Also, all insulators are proof tested to 60 kN
(13,500 lbs.) in tension.
The end fittings are radialy swaged on to the core rod to provide the mechanical performance and reduce the
stress concentration. Our proprietary design insures a watertight seal between the rubber and end fitting. This
special silicone rubber to metal fittings sealing process prevents moisture ingress to the core fiberglass rod.
Hot-dip galvanizing to CSA G164 and ASTM A153 Standard provides corrosion protection of the end fittings.
The cotter key is made from stainless steel.
The standard end fittings that are available are listed and detailed in the below. For other special end fittings
contact K-Line Insulator Limited.

END FITTING COMBINATIONS

ORDERING INFORMATION
For ordering the catalogue number of the specific insulator is formulated as shown below.

Cat. No. KL 115 H BS 28


Company ID

No. of Sheds (See Tech Data)

Voltage Class (See Tech Data)

End Fitting Designation (See


End Fittings)
High Leakage

K-LINE INSULATORS LIMITED


50 Passmore Avenue, Toronto, Ontario, Canada M1V 4T1
Tel.: (416) 292-2008 Fax: (416) 292-2094 E-Mail: insulators@k-line.net Web Page: www.k-line.net

March 2003

K-LINE INSULATORS LIMITED

Catalogue T-LP

TORONTO, ONTARIO, CANADA

Transmission Silicone Insulators


Line Post
69 kV to 161 kV

Transmission Silicone Insulators


Line Post
Today transmission lines are required to be more aesthetically pleasing and are routed through narrow right-ofways or along roadways. Also, at the lower transmission voltages (e.g., 115 kV and 69 kV) these lines are routed
through urban areas and along roadways similar to distribution circuits to supply substations and larger customers.
In some situations these lines share the same route and poles with distribution circuits. With K-Line silicone line
post transmission insulators an aesthetic compact line design can be easily achieved with a substantial savings in
the life cycle cost.
KLine silicone polymer transmission line post insulators are manufactured and tested to world-class polymer
insulator standards, CSA and ANSI. K-Lines Quality System is registered to ISO 9001 Quality Systems.

PERFORMANCE BENEFITS
The performance benefits of K-Line Insulators transmission line post insulators are listed below.

Improved Reliability (interruptions and outages due to vandalism, pole fires, and flashovers in all types of
environments are a thing of the past)
Eliminate or Reduce Maintenance (such as washing and less trouble calls) and is compatible with existing
plant
Improves Power Quality (lower RI and TVI)
Energy Efficiency (reduced losses due to lower leakage currents)
Safety (light weight for handling and installation)
Service Life (consistent performance over its service life)
Life Cycle Cost (savings over porcelain insulators)

APPLICATION
Transmission line post insulators are used on overhead transmission lines operating at and above 66 kV. These
insulators are commonly installed either vertically or horizontally on metal or wooden structures to support the
conductor. Also, these insulators are used to support high voltage conductor jumpers or leads.

ROD
The core rod of the transmission line post insulator is made of a high quality fiberglass that has been specially
formulated for electrical and mechanical applications.

HOUSING AND SHEDS


The housing and sheds of the insulator are one piece, injected molded silicone rubber that is chemically bonded to
the core rod. This ensures that the interface between the rubber and rod is impenetrable against moisture ingress.

TECHNICAL DATA
Catalog
Number

Voltage
Class
kV

KL69ASH13
KL69ASH16

69

KL69ASH19
KL115ASH22

Section
Length
(See Note)
L
mm

(in)

Dry Arcing
Distance
mm

(in)

Leakage
Distance
mm

(in)

Positive
Critical
Impulse
Flashover

kV

Low

Frequency
Flashover

Dry
kV

Wet
kV

Ultimate
Cantilever Load

kN

(lbs)

775 (30.5)

617

(24.3)

1544 (60.8)

380

250

225

29.4 (6600)

899 (35.4)

742

(29.2)

1890 (74.4)

450

295

260

26.1 (5870)

1022 (40.3)

866

(34.1)

2238 (88.1)

520

340

295

22.9 (5140)

1147 (45.2)

991

(39.0)

2583 (101.7)

595

385

330

19.6 (4410)

1271 (50.0)

1115 (43.9)

2931 (115.4)

665

430

365

16.5 (3700)

1395 (54.9)

1237 (48.7)

3277 (129.0)

735

475

410

14.9 (3340)

1519 (59.8)

1361 (53.6)

3622 (142.6)

805

520

450

13.3 (2980)

1643 (64.7)

1486 (58.5)

3970 (156.3)

880

560

475

11.7 (2630)

1767 (69.9)

1610 (63.4)

4318 (170.0)

955

600

495

10.1 (2275)

115
KL115ASH25
KL138ASH28

138

KL138ASH31
KL161ASH34
161
KL161ASH37

Note: Section length based on a horizontal trunnion and without any support base. For alternate bases and
line fittings (as well as overall lengths and weights of these) refer to the section on fittings and weights.

END BASES
The standard base fittings are flat round iron bases that are available with bolt circle mounting holes with
either through or tapped holes. These bases are compatible with the porcelain station post insulator
standard.
The end bases are radially swaged on to the core rod to provide the mechanical performance and reduce
the stress concentration. Our proprietary design insures a watertight seal between the rubber and end
fitting. This special silicone rubber to metal fittings sealing process prevents moisture ingress to the core
fiberglass rod. For other special base requirements, please contact K-Line Insulators Limited.
Corrosion protection of the end bases is provided by hot-dip galvanizing to CSA G164 or ASTM A153
specifications.

K-LINE INSULATORS LIMITED


50 Passmore Avenue, Toronto, Ontario, Canada M1V 4T1
Tel.: (416) 292-2008 Fax: (416) 292-2094 E-Mail: insulators@k-line.net Web Page: www.k-line.net

March 2003

K-LINE INSULATORS LIMITED

Catalogue T-SP

TORONTO, ONTARIO, CANADA

Transmission Silicone Insulators


Station Post
69 kV to 161 kV

Transmission Silicone Insulators


Station Post
One of the most critical assets of an electrical Transmission System is the station. Not only is this asset the heart
of the supply to large electrical loads but it also serves many customers from industrial to residential. Therefore,
outages or interruptions due to insulation failures are costly and impact negatively on customer service. With KLine silicone station insulators these are greatly minimized through improved performance to reliability and
savings in the life cycle cost.
Silicones hydrophobic property allows K-Line station insulators to electrically outperform porcelain insulators.
The lightweight feature of polymer insulators makes it easy to handle and install. The size and fittings of polymer
station insulators ensure that they are compatible with existing station post hardware and arrangements.
Experience with silicone polymer insulators has proven their superiority over porcelain insulators.
KLine silicone polymer transmission station post insulators are manufactured and tested to world-class polymer
insulator standards, CSA and ANSI. K-Lines Quality System is registered to ISO 9001 Quality Systems.

PERFORMANCE BENEFITS
The performance benefits of K-Line Insulators transmission station post insulators are listed below.

Improved Reliability (interruptions and outages due to vandalism, and flashovers in all types of
environments are a thing of the past)

Eliminate or Reduce Maintenance (such as washing and trouble calls) and is compatible with existing
porcelain insulators
Improves Power Quality (lower RI and TVI)
Energy Efficiency (reduced losses due to lower leakage currents)
Safety (light weight for handling and installation, eliminates catastrophic mechanical failures)
Service Life (consistent performance over its service life)
Life Cycle Cost (savings over porcelain insulators)

APPLICATION
Transmission station post insulators are used in open-type stations operating at and above 66 kV. These insulators
support the bus, leads, or other apparatus within the station.

ROD
The core rod of the transmission station post insulator is made of a high quality fiberglass that has been specially
formulated for electrical and mechanical applications.

HOUSING AND SHEDS


The housing and sheds of the insulator are one piece, injected molded silicone rubber that chemically bonds to the
core rod. This ensures that the interface between the rubber and rod is impenetrable against moisture ingress.

TRANSMISSION STATION POST INSULATOR

TECHNICAL DATA
Catalogue
Voltage Section
Number
(See Notes 1, Class Length, L
2, & 3)
kV
mm (in)
KL69ASP13
KL69ASP16

69

KL69ASP19
KL115ASP22
KL115ASP25
KL138ASP28
KL138ASP31
KL161ASP34
KL161ASP37

115

138

161

Dry
Arcing
Distance

Leakage
Distance

mm

mm

(in)

(in)

Positive
Impulse
Withstand
kV

Low
Frequency
Flashover
Dry
Wet

Specified
Cantilever
Load
SCL

Specified
Tensile
Load
STL

kV

kN

kN

kV

(lbs)

(lbs)

Equivalent
Height to
ANSI
Technical
Reference
Number

762 (30.0)

605 (23.8)

1534 (60.4)

355

245

195

29.9 (6725)

111 (25,000)

TR216/278

895 (35.2)

742 (29.2)

1890 (74.4)

430

295

240

26.2 (5885)

111 (25,000)

1019 (40.1) 866 (34.1)

2238 (88.1)

520

340

280

22.9 (5140)

111 (25,000)

1143 (45.0) 990 (39.0)

2583 (101.7)

565

385

320

19.7 (4440)

111 (25,000)

TR286/287

1267 (49.9) 1115 (43.9) 2931 (115.4)

635

430

360

16.5 (3705)

111 (25,000)

1372 (54.0) 1220 (48.0) 3256 (128.2)

690

470

400

15.1 (3405)

111 (25,000)

TR288/289

1515 (59.6) 1361 (53.6) 3622 (142.6)

765

520

450

13.3 (2995)

111 (25,000)

1639 (64.5) 1476 (58.1) 3970 (156.3)

830

555

480

11.7 (2640)

111 (25,000)

1763 (69.4) 1600 (63.0) 4315 (169.9)

900

595

510

10.2 (2290)

111 (25,000)

Ordering Information:
1. Above catalogue numbers apply to insulators with through holes on both ends.
2. Add T1 to catalogue numbers for insulators with one end tapped & the other with through holes.
3. Add T2 to catalogue number for insulators with both ends tapped.

End Bases
The standard base fittings are flat round iron bases that are available with bolt circle mounting holes with
either through or tapped holes. These bases are compatible with the porcelain station post insulator
standard.
The end bases are radialy swaged on to the core rod to provide the mechanical performance and reduce
the stress concentration. Our proprietary design insures a watertight seal between the rubber and end
fitting. This special silicone rubber to metal fittings sealing process prevents moisture ingress to the core
fiberglass rod. For other special base requirements, please contact K-Line Insulators Limited.
Corrosion protection of the end bases is provided by hot-dip galvanizing to CSA G164 and ASTM A153
specifications.

K-LINE INSULATORS LIMITED

Catalogue GI

TORONTO, ONTARIO, CANADA

Silicone Guy Strain Insulators

Silicone Guy Strain Insulators


Safety codes mandate the electrical strength of guy insulators to have a dry flashover voltage at least twice the
voltage to ground of the highest voltage supply circuit with which the guy could come in contact, and a wet
flashover equal to the highest voltage between any two conductors. When using porcelain, two or more insulators
are usually needed to comply with these requirements.
Fibreglass guy strain insulators so located that there is a possibility of contact with the supply conductors are
prone to electrical tracking and failure. Paint coatings are easily removed in handling, and by weathering, and do
not adequately protect the rod. Unprotected fiberglass core exposed to the elements can fail as a result of brittle
fracture.
K-Line guy strain insulators are protected from the environment including the effects of voltage, ultra-violet rays
and acid rain by a fully bonded, electrically track-free, and impenetrable silicone rubber sheath. The electrical
and mechanical requirements of the safety codes are easily met by K-Line Insulators. K-Line Insulators Limited
is registered to ISO 9001 Quality Systems. Each assembled insulator is proof tested, and permanently marked to
show the date of test.

GUY STRAIN INSULATORS

TECHNICAL DATA
SPECIFICATIONS

KL11

KL24

KL36

KL54

KL78

GI30

GI60

GI90

GI140

GI200

mm (in)

280 (11)

610 (24)

910 (36)

1370 (54)

1980 (78)

Dry

kV

115

235

335

485

680

Wet

kV

60

145

235

370

550

kN (lb)

100 (22,480)

100 (22,480)

100 (22,480)

100 (22,480)

100 (22,480)

CEA Class
Insulated Length A * *
Low-Frequency Flashover
Specified Mechanical Load
(SML)
Routine Test Load (RTL)

CATALOGUE NUMBER *

UNIT

kN (lb)

50 (11,240)

50 (11,240)

50 (11,240)

50 (11,240)

50 (11,240)

Torsional Load

Nm (ftlb)

56 (42)

56 (42)

56 (42)

56 (42)

56 (42)

Approx. Weight

kg (lb)

0.6 (1.3)

0.7 (1.5)

0.9 (2.0)

1.5 (3.3)

2.0 (4.4)

24

15

15

15

15

Standard Packaging

Ordering Information:
*
To catalogue number, add suffix CTS for clevis-tongue, CCS for clevis-clevis, RRS for roller-roller, or HHS for thimble eye-thimble eye, (other
custom fittings can be accommodated).
** Other lengths are available on request.

K-LINE INSULATOR LIMITED


50 Passmore Avenue, Toronto, Ontario, Canada M1V 4T1
Tel.: (416) 292-2008 Fax: (416) 292-2094 E-Mail: insulators@k-line.net Web Page: www.k-line.net
March 2003

K-LINE INSULATORS LIMITED

Catalogue D-EI

TORONTO, ONTARIO, CANADA

DISTRIBUTION SILICONE INSULATORS


Extension
15 kV to 46 kV

Distribution Silicone Insulators


Extension
K-Line dead-end extension insulators are manufactured by coupling either silicone sleeved rod to polymer deadend insulators. Extension insulators are made using the same manufacturing methods and quality assurance
program as the dead-end and guy insulators. Each dead-end extension insulator is mechanically proof tested to
44kN, (10,000 lbs).
For installations in normal operating environments, K-Line insulators are recommended. For extremely
contaminated, salt laden or chemical environments, K-Line SILICONE insulators are the ultimate solution.
The Technical Data table (See Next Section) shows the standard lengths available. Custom lengths are available
on request.

APPLICATION
Extension insulators are used when more length is needed than the standard insulator can supply.

ROD
The core rod of the extension insulator is made of a high quality fiberglass that has been specially formulated for
electrical and mechanical applications.

HOUSING AND SHEDS


The housing and sheds of the dead-end insulator are one piece, injected-molded silicone rubber that chemically bonds
to the core rod. This ensures that the interface between the rubber and rod is impenetrable against moisture ingress.

FITTINGS
The extension insulator comes standard with aluminum clevis and tongue end fittings, and a coupler.

DISTRIBUTION EXTENSION INSULATOR

TECHNICAL DATA
CATALOG
NUMBER

VOLTAGE
RATING (kV)
(See Notes 1 & 2)

DIMENSIONS
mm

WEIGHT
kg (lbs.)

749 (29.5)

279 (11.0)

1.2 (2.6)

1080 (42.5)

610 (24.0)

1.4 (3.1)

KL15ASX36S

1384 (54.5)

914 (36.0)

1.6 (3.5)

KL28ASX11

864 (34.0)

279 (11.0)

1.4 (3.1)

1196 (47.1)

610 (24.0)

1.6 (3.6)

1499 (59.0)

914 (36.0)

1.9 (4.1)

KL15ASX11S
KL15ASX24S

KL28ASX24

15

28

KL28ASX36
KL35SX11
KL35SX24

35

KL35SX36
KL46SX11
KL46SX24

46

KL46SX36

889 (35.0)

279 (11.0)

2.2 (4.9)

1219 (48.0)

610 (24.0)

2.5 (5.4)

1524 (60.0)

914 (36.0)

2.6 (5.8)

1003 (39.5)

279 (11.0)

1.7 (3.8)

1334 (52.5)

610 (24.0)

2.0 (4.3)

1638 (64.5)

914 (36.0)

2.1 (4.6)

Notes:
1) For the complete specifications of the insulator, refer to Distribution Insulators Deadend/Suspension, Catalogue D-DS.
2) The silicone covered rod in series with the insulator will add to the total insulation level.

CL DATAK-LINE INSULATORS LIMITED


K-LINE ISULATORS LIMITED
50 Passmore Avenue, Toronto, Ontario, Canada M1V 4T1
Tel.: (416) 292-2008 Fax: (416) 292-2094 E-Mail: insulators@k-line.net Web Page: www.k-line.net

March 2003

K-LINE INSULATORS LIMITED

Catalogue TD-IPS

TORONTO, ONTARIO, CANADA

TRANSMISSION & DISTRIBUTION


SILICONE INSULATORS
Interphase Spacer
15 kV to 230 kV

Transmission & Distribution Silicone


Interphase Spacer Insulators
With the environmental exposure to ice and/or wind Overhead Transmission and Distribution Lines that
are bare open-wire design are quite susceptible to conductor motion that may result in outages or
interruptions on the electrical system due to conductor contact, flashovers, or any plant damage.
Interphase spacers were developed to minimize the probability of these occurrences by insuring that
conductors remain apart during their movement.
K Line interphase spacers consist of silicone rubber insulation over a fiberglass rod. They are very
light and flexible. They are connected on the conductor with clamps with or without armour rods. The
interphase spacers meet the requirements of CEA LWIWG-01, IEEE 1024, ANSI C29.11 and CSA
C411.4. K-Line Insulators Limited is registered to ISO 9001 Quality Systems.

PERFORMANCE BENEFITS
The performance benefits of K-Line Insulators interphase spacer insulators are listed below.

Improves Reliability (by minimizes interruptions and outages due to vandalism and flashovers in all types of
environments)
Eliminates or Reduces Maintenance (such as washing and trouble calls) and is compatible with existing plant
Improves Power Quality (less RI and TVI)
Energy Efficiency (lower losses due to lower leakage currents)
Safety (light weight for handling and installation)
Service Life (consistent performance over its service life)
Life Cycle Cost (savings over porcelain insulators)

APPLICATION
One or two interphase spacers are installed in each span. One spacer is installed if there are two vertically
positioned conductors and it is installed at one-third of the span. Two spacers are installed if there are three
vertically positioned conductors. The first spacer is installed between the mid and lower conductors one-third of
the span from one end. The second spacer is installed between the mid and upper conductor one-quarter of the
span from the other end.

CORE MATERIAL
The core rod of the interphase spacer insulator is made of a high quality fiberglass that has been specially
formulated for electrical and mechanical applications.

HOUSING AND SHEDS


The housing and sheds of the insulator are one piece, injected molded silicone rubber that is chemically bonded to
the core rod. This ensures that the interface between the rubber and rod is impenetrable against moisture ingress

K-LINE INSULATORS LIMITED


50 Passmore Avenue, Toronto, Ontario, Canada M1V 4T1
Tel.: (416) 292-2008 Fax: (416) 292-2094 E-Mail: insulators@k-line.net Web Page: www.k-line.net

K-LINE INSULATORS LIMITED


50 Passmore Avenue, Toronto, Ontario, Canada M1V 4T1
Tel.: (416) 292-2008 Fax: (416) 292-2094 E-Mail: insulators@k-line.net Web Page: www.k-line.net
March 2003

DISTRIBUTION RISER SUPPORT INSULATOR

TECHNICAL DATA
SPECIFICATIONS

UNIT

Voltage Class
Section Length L
Dry Arcing Distance
Leakage Distance

kV
mm (in)
mm (in)
mm (in)

Low-Frequency Flashover

Dry
Wet

Critical Impulse Flashover (Pos.)


Radio Influence Voltage (RIV)
at 1 MHz

Test
Max.

Specified Cantilever Load (SCL)


Max. Design Cantilever Load (MDCL)
Approx. Weight
Standard Packaging

kV
kV
kV
kV
V
kN (lb)
kN (lb)
kg (lb)
-

CATALOGUE NUMBER**
KL15ARSIU
15
389 (15.3)
195 (7.6)
385 (15.1)
100
70
145
15
Below 1
1.6 (362)
0.8 (181)
0.7 (1.5)
15

KL28ARSIU

KL35SRSIU

KL46SRSIU

KL69HRSIU16

28
(19.7)
(11.4)
(23.2)
135
105
225
20
Below 1
1.1 (250)
0.6 (125)
0.9 (1.9)
15

35
569 (22.4)
348 (13.7)
750 (29.5)
153
144
264
30
Below 3
0.9 (211)
0.5 (106)
2.1 (4.7)
12

46
619 (24.4)
419 (16.5)
988 (38.9)
180
150
300
30
Below 5
0.8 (190)
0.4 (95)
2.2 (4.8)
12

69
779 (30.7)
627 (24.7)
1798 (70.8)
260
205
425
44
Below 10
0.6 (144)
0.3 (72)
2.3 (5.1)
3

500
290
590

** Options: For 5/8 tapped hole add X, for M16 add M16, or for M20 add M20 and for tin-plated clamp add D to the catalogue number.

K-LINE INSULATORS LIMITED


50 Passmore Avenue, Toronto, Ontario, Canada M1V 4T1
Tel.: (416) 292-2008 Fax: (416) 292-2094 E-Mail: insulators@k-line.net Web Page: www.k-line.net
March 2003

Distribution Silicone Insulators


Riser Support
On distribution overhead lines there are numerous tap-offs from the main line to provide connections to
equipment (e.g., transformers, switches, fuses, underground cables, etc.) or lines (e.g., services, junctions, etc.).
Normally leads are used to connect the equipment or line to the main line. These leads can be long and difficult or
hazardous to operate. The use of riser support insulators can provide a safe and economical support for these
leads.
KLine silicone riser support insulators are manufactured and tested to world-class polymer insulator standards,
CSA, CEA, ANSI and IEC. K-Line Insulators Limited is registered to ISO 9001 Quality Systems.

APPLICATION
Distribution riser support insulators are used on distribution lines operating at or below 69 kV. These insulators are
installed on metal, concrete or wooden structures and on cross arms to hold and insulate the conductor leads.

ROD
The core rod of the distribution riser support insulator is made of a high quality fiberglass that has been specially
formulated for electrical and mechanical applications.

HOUSING AND SHEDS


The housing and sheds of the insulator are one piece, injected-molded silicone rubber that chemically bonds to the
core rod. This ensures that the interface between the rubber and rod is impenetrable against moisture ingress.

FITTINGS
The riser insulator comes standard with a clamp to hold the conductor and a threaded hole for mounting.

Conductor Clamp
The clamp is an aluminum clamp that can accommodate copper or aluminum conductors # 6 AWG (0.20) to 556.5
kcmil (0.95).

Threaded Base
The base is typically threaded for -11, -10, M16x2, or M20x2.5 galvanized bolt.
For other special clamp features or base threads please contact K-Line Insulators Limited.

K-LINE INSULATORS LIMITED

Catalogue MB-PT

TORONTO, ONTARIO, CANADA

Single Circuit
Pole Top Framing Assembly

Single Circuit
Pole Top Framing Assembly
The ultimate in labour saving and convenience is provided by K-Line's single circuit pole-top framing
assembly (35 kV shown). The assembly comes complete in kit form with mounting bracket, polymer line post
insulators, trunnion clamps and insulator mounting studs. Install with two bolts and the structure is ready to
sag.
The hot dip galvanized steel bracket comes with predrilled holes for mounting of riser support insulators and a
grounding lug. The insulators are of silicone, the ultimate in polymer line post insulators for maintenance-free
operation.
.