Académique Documents
Professionnel Documents
Culture Documents
2-1
Introduction
The principle of transformer action is based on the work of
34
FIGURE 2-1 Transformer construction: (a) core type: (b) shell type.
Transformer core material is made of nonaging, cold-rolled, highpern ability silicon steel laminations, and each lamination is insulated
with a varnish < oxide coating io reduce eddy currents. The coils are
wound with insulated alun num conductor or insulated copper conductor,
35
36
37
2-3
Figure 2-3 (a) Transformer with battery primary circuit to aid in the explanation
of transformer action (b) transformer with sinusoidal source and no load
secondary.
38
where:
N1 = turns in coil 1
N2 = turns in coil 2
In accordance with Lenz's law, the voltage generated in each coil will be
induced in a direction to oppose the action that caused it. Thus, the
induced emf in coil 1 must be opposite in direction to the battery voltage,
as shown in Figure 2-3(a). This opposing voltage, shown as e, in Figure
2-3(a), is called a counter-emf (.cemf).
In the case of coil 2, the induced cmf and associated current must
be in a direction that will develop a counterclockwise (CCW) mmf to
oppose the build-up of flux in its window. Thus, with the direction of
mmf known, the direction of induced emf and associated current may be
determined by applying the right-hand rule to coil 2. Note: The induced
emfs and secondary current in Figure 2-3(a) are transients. When mutual
reaches steady state, d/dt = 0, the induced emfs = 0, and i2 = 0.
39
(2-1)
Es = 4.44Ns max
(2-2)
Np
Ns
action and to supply the hysteresis and eddy-current losses in the iron.5
This no-load current, called the exciting current, varies between 1 and 2
percent of rated current in large power transformers, and may be as high
as 6 percent of rated current in very small distribution transformers.
41
Where
I0 = exciting current
Ife = core loss component
Im = magnetizing component
XM = fictitious magnetizing reactance that accounts for the
magnetizing current
Rfe = fictitious resistance that ccounts for the core loss
Vr = voltage applied to primary
No-Load Ampere-Turns and Its Components
Multiplying Eq. (2-4) by the primary turns expresses the no-load
mmf in terms of its quadrature components:
where:
M = mutual flux produced by the magnetizing component of exciting
current
IM = magnetizing current
core = reluctance of transformer core
42
where:
VT = applied voltage
Ip = primary current
Ep = voltage induced in the primary
Rp = resistance of primary winding
Voltage Ep is the cemf in the primary coil caused by the sinusoidal
variation of flux in its window.
43
current, adds its mmf to the magnetizing component, causing the flux to
increase. Thus,
FIGURE 2-5 Relative directions of secondary current and secondary mmf for
one cycle when load switch is closed.
transient increase in cemf, causing the primary current to drop back to its
initial no-load value.
Although described as a step-by-step process, the actual behavior,
when loading or unloading are essentially simultaneous, and takes place
in a fraction of a second. Note: This entire discussion assumed constant
permeability and no leakage flux.
45
The relationship between coil flux leakage and mutual flux for the
respective primary and secondary coils shown in Figure 2-6, are
p = m + lp
s = M - ls
where:
p = net flux in window of primary coil
s = net flux in window of secondary coil
M = mutual flux
lp = leakage flux associated with the primary coil
pS = leakage flux associated with the secondary coil
Equations (2-12) and (2-13) illustrate how the leakage flux in both
windings serve to reduce the output voltage of the secondary; the mutual
flux is less than the available primary flux because of primary leakage,
and the net flux in the secondary is the mutual flux less the secondary
leakage. Less flux in the secondary coil results in a lower secondary
voltage than if no leakage were present.
The voltage drop caused by leakage flux is proportional to the load
current. The greater the load current, the greater the magnitudes of both
the primary and secondary ampere-turns, and hence the greater the
respective leakage fluxes in both primary and secondary windings.
Although leakage flux has an adverse effect on the transformer output
voltage, it proves an asset under severe short-circuit conditions; the large
voltage drop caused by the intense leakage flux limits the current to a
lower value than would otherwise occur if no leakage were "present, and
thus helps to avoid damage to the transformer.
46
47
where:
a = turns ratio
VHS/VLS = nameplate voltage ratio
EHS/ELS = ratio of induced voltages
Voltages E'p and E'S are induced by the same flux, and thus must
hive the phase angle. Hence,
The apparent power input to the ideal transformer must equal the
apparent output. Expressed as phasor power (see Appendix A- 5),.
48
Therefore
49
'when multiplied by the current in them, will result in voltage drops equal
to these brought about by the respective leakage fluxes.
Figure 2-8(a) represents a real transformer with all its associated
core losses and flux leakages. The induced emfs in the primary and
secondary coils, due to the net flux through their respective windows, are
where:
Ep = net voltage induced in primary
E'p = voltage induced in primary due to mutual flux
Elp = voltage induced in primary due to primary leakage
ES = net voltage induced in secondary
E'S = voltage induced in secondary due to mutual flux
ElS = voltage induced in secondary due to secondary leakage
50
FIGURE 2-8 (a) Real transformer; (b) equivalent circuit of real transformer
using an ideal Transformer and external components.
(2-24)
(2-25)
Ip = Ife + IM + Ip.load
(2-26)
where
Applying Kirchhoff's law to the secondary in Figure 2-8(a),
Es = ISRS + Vload
51
(2-27)
(2-28)
Induced voltages Ep, and E'p are due to the mutual flux, and
induced voltages Efp and E,s are due to their respective leakage fluxes!
Using Eqs. (2-25), (2-26). and (2-28) as a guide, the real
transformer in Figure 2-8(a) may be redrawn as an equivalent circuit
using an ideal transformer whose windings are in series with external
components that account for the losses, the voltage drops, and the
exciting current of the real transformer. This is shown in Figure 2-8(b).
The leakage flux, shown in the equivalent "leakage coils" in Figure 28(b), may be expressed in terms of the respective coil currents, and the
reluctances of the respective leakage paths of the real transformer. Thus,
52
(2-41)
(2-42)
Figure 2-11 Equivalent circuits in terms of high-side and low-side values for stepdown operation.
54
The exciting current branch, shown with broken lines in Figure 21]a may be omitted when making calculations involving operations at or
near related load; for such loadings, the load component of primary
current is so much greater than the exciting current that the exciting
current may be neglected. Howe when making calculations for loadings
less than 25 percent rated load, the i load components must he considered
if significant errors in current calculate are to be avoided.
Z load . I .S
1
Z load . HS
a2
55
It should be noted that the lower voltage rating and higher current
rating of the low side (compared to the high side) requires the low side to
have less turns of larger cross-sectional area conductor. Hence, the
equivalent impedance of the transformer referred to the low side will
always be less than the equivalent impedance referred to the high side.
The circuit models shown in Figure 2-1 l(a) and Figure 2-I2(a) are
used to determine the input impedance of the combined transformer and
load. The circuit models shown in Figuie 2-1 l(b) and Figure 2-12(b) are
used to determine the no-load voltage and the voltage regulation.
(2-44)
where:
E = voltmeter reading at the output terminals when no load is connected
to the transformer
56
(2-45)
where:
ILS = rated low-side current at specified power factor
VLS = rated low-side voltage (output V, breaker closed)
ELS = no-load low-side voltage (output V, breaker open)
Zeq.LS = equivalent impedance of transformer referred to low side
where:
ZPU = per-unit impedance
RPU = per-unit resistance
Xpu = per-unit reactance
58
Note: Vrated and Irated are also called base current respectively per-unit
impedance of a transformer is often expressed in terms of a base
impedance obtained from the transformer rating.
Note: Irated , Vrated , Req , Xeq, and Zeq must be all high-side values or all low
values. The per-unit impedance (and percent impedance) has the same
whether calculated using all high-side values or all low-side values. This
is i advantage when making calculations involving systems that have
more than transformer, each at a different voltage level.
The per-unit system has its greatest application in the solution of
netv problems involving several voltage levels, and is used extensively in
power! tem analysis [3].
59
60
Figure 2-14 Phasor diagrams: (a) lagging power-factor load; (b) leading powerfactor load.
Substituting appropriate equations from equation set (2-46) into Eq. (256).
61
Where:
Thus.
62
(2-65)
Where I and Req are both high-side values or are both low-side values.
Depending on its apparent power rating, the efficiency of distribution
transformers and power transformers varies from 96 to over 99 percent;
the larger transformers have the higher efficiencies.
Calculating Efficiency from Per-Unit Values
Quick-and-easy calculations of efficiency may be accomplished if
the transformer parameters and the core loss are given in per-unit values
or percent values. appropriate equation is derived by first expressing Pout
in Eq. (2-65) in terms of apparent power. Thus,
63
where:
Fp = per-unit power factor
S = apparent power of connected load (VA)
l = load current
Dividing both numerator and denominator in Eq. (2-66) by the
rated power of the transformer,
where:
= per-unit efficiency
Srated = Vra,edIrated = rated apparent power, also called base app
power
Defining.
64
The components in Eq. (2-7!) and Eq. (2-72) may be expressed all
in per-unit or all in percent. However, the calculated efficiency wil! be in
per-unit.
65
FIGURE 2-15 Open-circuit test: (a) connection diagram; (b) equivalent circuit.
made on the low side, the open-circuit parameters referred to the low side
may be obtained by substituting into the following equations:10
66
Short-Circuit Test
The purpose of the short-circuit test is to determine the equivalent
resistance,; equivalent leakage reactance, and-equivalent impedance of
the transformer windings. The connections and instrumentation required
for the test are shown Figure 2-16(a). The high side of the transformer
under test is connected to the
FIGURE 2-16 Short-circuit test: (a) connection diagram; (b) equivalent circuit.
supply line through an adjustable-voltage autotransformer, and the lowvoltage side is jumped by connecting a short piece of large crosssectional area copper across its terminals; in effect, the secondary is
shorted. The jumper represents a load impedance of almost zero ohms.
That is, Zload 0 . Thus, by jumping the secondary, the test provides
data that include the effects of primary and secondary resistance, and
67
VSC
2
PSC I SC
R eq . HS
Z eq . HS
Z eq . HS
2
2
R eq
. HS X eq . HS
The short-circuit test may be made using either winding. For reasons of lo
current input and meter sizing, however, the high-voltage winding is
preferredj the measurements are made on the low side, the resultant
values determined frj the test would be the equivalent resistance,
equivalent reactance, and equiva impedance referred to the low side.
68
69