Vous êtes sur la page 1sur 19

Project Name: Carmen De Bolivar

Project Location: Bolivar, Colombia


Dealer: Florida Aquastore Latin America
4722 NW Boca Raton Blvd.; Suite C-102
Boca Raton, Florida, 33431-6358
Phone: (561) 994-2400 Fax: (561) 994-2444
Project Number:

1407970

Submittal Release.No.:

Aquastore Glass Fused to Steel Bolted Storage Tank


25' diameter (nom.) x 25' high (nom.) Model 2525
Steel Floor Foundation
Shell interior coating:
Vitrium fused glass with Edgecoat process

Shell exterior coating:


Fused glass
Shell Exterior Color:

Cobalt Blue

Roof Exterior Color:

White

Date: September 15, 2014


EQuote # 1407970 rev. 2
Construction Method: Jack

19 pages.
This document consists of ______
Submitted by:

Date:

9/24/14

Date:

Expires:

Date:

Tank Project Drawing Index


Document Number

Document Title

1407970-001

Tank Drawing

1407970-010

Tank Calculations & Design Formulas

1407970-011

Tank General Notes

1407970-012

Tank Fastener Schedule

1407970-013

Tank Schematic

1407970-014

Tank Parts List

Foundation Project Index


1407970-002

SF Foundation Drawing

1407970-003

Anchor Bolt Placement

1407970-023

Foundation Parts List

1407970-024

Foundation Fastener Schedule

1407970-025

Manufacturers Warranty

DOCUMENT NUMBER: 1407970-010

TITLE: TANK CALCULATIONS

PAGE: 1

REL.: 1
DATE: September 15, 2014
BY:

JS

SUMMARY OF TANK DESIGN INPUT DATA


STRUCTURE MODEL

25 25

FOUNDATION TYPE

Steel Floor

SPECIFIC GRAVITY

1.000

H/V PRESSURE RATIO

1.000

FREEBOARD

15.000 in

ROOF TYPE

Knuckle

ROOF WEIGHT

5.000 psf

24.410 kg/m2

SC ROOF HEIGHT

2.500 in

63.500 mm

DC ROOF PROJ AREA

73.290 sq ft

6.809 sq m

DC ROOF CENTROID

21.000 in

533.400 mm

TOTAL ROOF HEIGHT

59.910 in

1521.714 mm

ROOF SNOW LOAD

15.000 psf

0.718 kPa

WIND DESIGN

ASCE 7-05*(12.35 psf)*

EXPOSURE FACTOR

IMPORTANCE FACTOR

1.000

WIND SPEED

100.000 mph

WIND STIFFENER ANALYSIS

ASCE 7-05*(12.35 psf)*

SEISMIC DESIGN

AWWA D103 97 (EFFECTIVE MASS)

SEISMIC ZONE

USE FACTOR, I

1.250

SITE AMPLIFICATION FACTOR

1.500

ALLOWABLES USED

AWWA D103-97

Add Anchors even if not required?

YES

FLOOR O.D

25.250 ft

AQUA2 VERSION

3.1.0.1

381.000 mm

45.000 m/s

7696.200 mm

SUMMARY OF INTERNALLY ASSIGNED PARAMETERS


BOLT DIAMETER

0.500 in

12.700 mm

HOLE DIAMETER

0.562 in

14.288 mm

TOP COURSE EDGE DIST

1.000 in

25.400 mm

STEEL FLOOR IN FNDN

0.094 in

2.388 mm

DIST T/FTG TO B/FLR

0.000 in

0.000 mm

TOTAL FNDN THICKNESS

0.094 in

2.388 mm

SHEET DENSITY

590.000 pcf

9451 kg/m3

STEEL ELASTIC MODULUS

30000000 psi

206843 MPa

STEEL FLOOR DENSITY

590 pcf

9451 kg/m3

NET SHEET WIDTH

105.462 in

2679.000 mm

NET STANDARD SHEET HT.

54.990 in

1397.000 mm

STARTER PANEL HEIGHT

18.683 in

474.548 mm

INVENTORY USED

wssf(1311)

DOCUMENT NUMBER: 1407970-010

TITLE: TANK CALCULATIONS

PAGE: 2

25 25 AQUASTORE STRUCTURE DESIGN SUMMARY (9 FULL LENGTH SHEETS PER RING/COURSE)

COURSE
NUMBER

THICK
In.

THICK mm

GEOM
CODE

MAT
CODE

LIMITING
FACTOR(S)

0.099

2.515

1201

0.099

2.515

1201

0.099

2.515

1201

0.132

3.353

1201

[41]

0.164

4.166

1201

[41]

FND

0.197

5.004

6321

WIND STIFFENERS REQUIRED:


NONE

ANCHORS REQUIRED:

(3)1 1/4 inch ANCHORS REQUIRED


PER SHEET.

STRUCTURE DIAMETER

25.18 ft

7674.01 mm

HEIGHT OF STRUCTURE TO EAVE

=

24.5 ft

74 mm

SLOSHING WAVE HEIGHT

2.33 ft

710.78 mm

VOLUME OF STRUCTURE TO EAVE

12208 cu ft

346 m3

VOLUME OF CONTENTS

11586 cu ft

328 m3

VOLUME OF CONTENTS

86668 gal

328076 L

VOLUME OF STEEL FLOOR FND.

4 cu ft

0 m3

WEIGHT OF EMPTY CYLINDER ABOVE FLOOR

11737 lb

5324 kg

WEIGHT OF ROOF

2489 lb

1129 kg

SNOW (LIVE) LOAD

7468 lb

3387 kg

WEIGHT OF CONTENTS

722959 lb

327928 kg

STEEL FLOOR WEIGHT

2314 lb

1050 kg

TOTAL WEIGHT ON FOOTING

746967 lb

338818 kg

WIND SHEAR AT TOP OF FOOTING

8595 lb

38231 N

WIND MOMENT AT TOP OF FOOTING

119115 ft-lb

162 kN-m

SEISMIC SHEAR AT TOP OF FOOTING

249535 lb

1109986 N

SEISMIC MOMENT AT TOP OF FOOTING

2628214 ft-lb

3564 kN-m

DOCUMENT NUMBER: 1407970-010

TITLE: TANK CALCULATIONS

PAGE: 3

---- STRESS-PSI ----

HOOP STRESS ANALYSIS


Course
Number

Depth
(ft)

Press
(PSI)

Net
Tensile

Allowable
Tensile

Hole
Bearing

Allowable
Bearing

Bolt
Shear

Allowable
Shear

3.4

1.5

3077

25400

4777

67500

1204

29454

8.0

3.5

7205

25400

11186

67500

2820

29454

12.6

5.5

11333

25400

17594

67500

4435

29454

17.2

7.4

11595

25400

18002

67500

6051

29454

21.7

9.4

11825

25400

18358

67500

7667

29454

FND

23.3

10.1

9478

25400

13717

67500

6881

29454

---- STRESS-PSI ----

AXIAL STRESS ANALYSIS


Course
Number

Axial
Compressive

Allowable
Compressive

Hole
Bearing

Allowable
Bearing

Bolt
Shear

Allowable
Shear

125

1282

1253

67500

316

29454

144

1282

1441

67500

363

29454

162

1282

1630

67500

411

29454

140

1697

1411

67500

474

29454

132

2093

1324

67500

553

29454

FND

116

2495

583

67500

292

29454

DOCUMENT NUMBER: 1407970-010

TITLE: TANK CALCULATIONS

PAGE: 4

---- STRESS-PSI ----

WIND STRESS ANALYSIS


Course
Number

Axial
Comp

Wind
Bending

Total
Comp

Allowable
Comp

Hole
Bearing

Allowable
Bearing

Bolt
Shear

Allowable
Shear

45

16

62

1709

64

41

105

1709

619

90000

156

39272

1051

90000

265

83

76

159

39272

1709

1595

90000

402

39272

81

92

84

108

173

2262

1734

90000

583

39272

192

2790

1932

90000

807

FND

76

101

39272

177

3326

890

90000

446

39272

---- STRESS-PSI ----

SEISMIC STRESS ANALYSIS


Course
Number

Axial
Comp

Seismic
Bending

Total
Comp

Allowable
Comp

Hole
Bearing

Allowable
Bearing

Bolt
Shear

Allowable
Shear

45

59

104

1709

1049

90000

265

39272

64

410

474

1709

4762

90000

1201

39272

83

1126

1209

1709

12145

90000

3062

39272

81

1665

1746

2262

17540

90000

5896

39272

84

2291

2374

2790

23849

90000

9960

39272

FND

76

2230

2306

3326

11581

90000

5810

39272

DOCUMENT NUMBER: 1407970-010

TITLE: TANK CALCULATIONS

PAGE: 5

SEISMIC STRESS ANALYSIS CONTINUED


---- STRESS-PSI ----

Course
Number

Hydro-Dynamic
Hoop

Total
Hoop

Allowable
Tensile

1622

4698

33867

2526

9730

33867

3060

14393

33867

2472

14068

33867

1989

13814

33867

FND

1655

11133

33867

DOCUMENT NUMBER: 1407970-011

REL:1

TITLE: TANK GENERAL NOTES

PAGE: 1

TANK DESIGN SPECIFICATIONS


This tank is designed in accordance with AWWA Standard D103-97 allowable stresses.
See page 1 of Document 1407970-010 for Summary of Tank Design Input Data.

COATINGS SPECIFICATIONS
Coatings used on components of this tank are in compliance with the appropriate sections of AWWA
Standard D103.

STRUCTURE BOLT SPECIFICATIONS


Structure bolts are carbon steel, zinc mechanically deposited per the latest revision of ASTM B695,
class 50,type 1;with 1/2"-13 UNC-2A thread, and conform to AWWA D103,Section 2.2.1, as noted below.
A. 1 inch long and 1-1/4 inch long bolts conform to the mechanical properties of SAEJ429, Grade 5
- equivalent to the mechanical properties of ASTM A325.
B. 1-1/2 inch long and longer bolts conform to the mechanical properties of SAEJ429, Grade 8
- equivalent to the mechanical properties of ASTM A490.
Unless noted, all tank structure connections are bearing type connections, snug-tight condition, per
ANSI/AISC 360-05. Tank manufacturer does not require special inspection per IBC, Section 1704.

APPURTENANCE AND PIPING ORIENTATION


Orientation of all appurtenances and piping connections shall be established in the field.

THROUGH-THE-SHEET PENETRATIONS
All openings through the tank side wall greater than 4 inches (102mm) in diameter shall be reinforced in
accordance with AWWA D103, Section 3.11. All openings through sheets having less than 24 inches (610
mm) between horizontal bolt lines, or having less than 24 inches (610 mm) of available sheet space from
the floor surface up to the first horizontal bolt line shall not exceed a diameter of 4 inches (102 mm).
These openings of 4 inches (102 mm) and less shall be reinforced in accordance with AWWA D103,
Section 3.11.

$77$&+(0(17S TO THE TANK SHELL


3HU$::$'DOODWWDFKPHQWVPDGHWRWKHWDQNVKDOOEHGHVLJQHGVRWKDWQRVLJQLILFDQWORDGLVLPSDUWHGRQWKH
WDQNZDOO$WWDFKHPHQWVLQFOXGHWKRVHIRUSLSLQJQR]]OHVPL[HUVEUDFNHWVVXSSRUWVHWF8QOHVVQRWHGRWKHUZLVHLQ
WKLVGRFXPHQWWKLVWDQNLVQRWGHVLJQHGWRVXSSRUWDQ\ORDGVIURPDWWDFKPHQWV

LADDER AND ROOF SPECIFICATIONS


The ladder and roof walkway systems are manufactured in compliance with AWWA Standard D103
Section 5.4. and meet minimum OSHA requirements. In addition, the tank ladder side rails are fabricated
from 6061-T6 aluminum while the ladder rungs are fabricated from 6061-T4 aluminum.

ROOF MANWAY OPENING


Field cut roof manway opening from roof panel and/or roof knuckle using the outside edges of the
prepunched notches and holes as the opening outline. (Do not use a cutting torch to perform this
operation.) Apply sealer to the appropriate roof surfaces and field cut edges.

DOCUMENT NUMBER: 1407970-011

REL:1

TITLE: TANK GENERAL NOTES

PAGE: 2

CATHODIC PROTECTION SPECIFICATIONS


This tank is equipped with a cathodic protection system conforming to NACE SP0196-2011. This system
is designed to protect the items described below.
Entire submerged portion of tank sidewall and floor area including appurtenances supplied by the tank
manufacturer. Submerged uncoated metal objects not supplied by the tank manufacturer totaling: 0 sq. ft.
Submerged coated metal objects not supplied by the tank manufacturer totaling: 0 sq. ft.
This system is suitable for use in liquid having a resistivity of 3000 - 5000 ohm-centimeters.
Field verification of liquid resistivity is required after the tank is placed into service.
The performance of the cathodic protection system may be adversely affected if the system is operated
outside the resistivity range above.
The presence of submerged uncoated metallic items, for which cathodic protection has not been provided
by the tank supplier, may also adversely affect the performance of the cathodic protection system.
Electrical isolation and/or the determination of the cathodic protection requirements for such submerged
items shall be the responsibility of the owner or the owner's designated agent.
Tank warranty issues may also be affected.
For further information, refer to the instructions provided with the cathodic protection system.

10

DOCUMENT NUMBER: 1407970-012

REL:1

TITLE: TANK FASTENER SCHEDULE

PAGE: 1

Structure bolt quantities at (H)orizontal and (V)ertical seams


Thru the sheet fasteners

BOLT LENGTHS:

1"
25.40

GRAVITY VENT
CAP

1 1/4"

1 1/2"

1 3/4"

31.75

38.10

44.45

Truss Fasteners

2"
50.80

2 1/4"

2 1/2"

57.15

63.50

1 1/4"
31.75

2 1/4"

3"

3 1/2"

57.17

76.20

C.S.

C.S.

C.S.

88.90
C.S.

24
54

PANEL/KNUCKLE

1184

MANWAY

4
16

SEAM Wide H 1

157

SEAM

V 1

32

459

SEAM Wide H 2

176

22

SEAM

V 2

459

SEAM Wide H 3

180

18

SEAM

V 3

459

SEAM Wide H 4

178

20

SEAM

V 4

459

SEAM Wide H 5

198

SEAM

V 5

459

SEAM Fnd. H 6

178

20

ACCESS DOOR

30

REINF. PLT.

90

3789

947

110

30

Total:

11

DOCUMENT NUMBER: 1407970-013

REL:1

TITLE: TANK SCHEMATIC

PAGE: 1

Note: All brackets located at top of specified ring.


Ring are identified from top of tank to foundation
Ring #

Sheet
Thick.

Bracket Type

Bracket
Quantity

Vertical Bolt
Line

Shell Sheet Part


No.

RING # : 1

0.099'' (2.5mm)

Y-BRKT

2V

256050-0100

RING # : 2

0.099'' (2.5mm)

Y-BRKT

2V

256050-0100

RING # : 3

0.099'' (2.5mm)

NONE

2V

256050-0100

RING # : 4

0.132'' (3.4mm)

Y-BRKT

2V

256050-1200

RING # : 5

0.164'' (4.2mm)

Y-BRKT

2V

256050-0500

FND. :

0.197'' (5.0mm)

Y-BRKT

3V

See fnd. parts list

12

DOCUMENT NUMBER: 1407970-014


Item
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58

Quantity

REL:1

TITLE: TANK PARTS LIST

Part No.

Description

1
1
1
26
1
26
1

1407970-001
1407970-002
266146J2300
251462J2200
266112J2206
253911J2200
266111J2206

TANK ASSEMBLY
FOUNDATION ASSEMBLY
ROOF CAP
ROOF PANEL, WHITE
ROOF PANEL W/MANWAY C-OUT, WHITE
ROOF KNUCKLE, WHITE
ROOF KNUCKLE W/MANWAY C-OUT, WHITE

54
1
1
1
1
4
14
1
1
1
1

263156-001
255469-000
257993-000
264391-000
263883-000
267692-000
265777-203
268476-000
264082-000
258447-002
264769-000

PLASTIC ENCAPSULATED NUT


GRAVITY VENTILATOR
ROOF GUARDRAIL ASSEMBLY
MANWAY PLATFORM ASSEMBLY
ROOF MANWAY ASSEMBLY
EDGE TRIM
SEALER 98, CARTONS (BLACK)
FALL PROTECTION BRACKET
SHORT LADDER ASSEMBLY
LADDER W/CAGE KIT
LADDER DOOR ASSEMBLY

1
2

277650-000
266214-1300

GASKET, 24"
REINFORCING PLATE, .197"

3789
947
110
30

262000-001
262000-002
262000-003
262000-004

STRUCTURE BOLT, 1"


STRUCTURE BOLT, 1 1/4"
STRUCTURE BOLT, 1 1/2"
STRUCTURE BOLT, 1 3/4"

4822
4822

252275-000
262416-001

WASHER, 1/2"
HEX. NUT, 1/2" HDZ

PAGE: 1

13

DOCUMENT NUMBER: 1407970-014


Item
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118

Quantity

REL:1

TITLE: TANK PARTS LIST

PAGE: 2

Part No.

Description

4822
5
1

081816-000
264913-000
276534-000

PROTECTIVE COVER
BUSS BAR
AQUASTORE CP LIT. PACK

266680-100

CATHODIC PROT. SYSTEM - MAG.

3
2
1
1
3
3

262778-000
257249-000
266182-000
271220-000
262166-000
260581-000

DANGER DECAL
INFORMATION SIGN
NAMEPLATE
OPERATORS MANUAL
IMPORTANT DECAL
TANK MOD. WARNING DECAL

260910-000

Y BRACKET ASSY. SET (SHORT)

1
1

260813-0102
266216-0502

AQUASTORE TRADENAME SHEET


24" ROUND ACCESS DOOR SHEET

280516-025

24" ACCESS DOOR, NORMAL DUTY, STANDARD (GALV)

26

256050-0100

SHELL SHEET 0.099" HSLA

9
8

256050-1200
256050-0500

SHELL SHEET 0.132" HSLA


SHELL SHEET 0.164" HSLA

14

15

16

DOCUMENT NUMBER: 1407970-023


Item
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49

Quantity

REL:1

TITLE: FND. PARTS LIST

Part No.

Description

1
9
1

1407970-002
261718-1300
263748K0100

S.F. FOUNDATION ASSY.


0.197" FND. SHT. HSLA
25.0 FT. DIA. FLOOR ASSEMBLY

261067-002

TAPERED SPACER

27
27

265621-010
261424-000

ANCHOR BOLT ASSY., 1 1/4"


ANCHOR BOLT CHAIR

27

261725-010

WASHER, PLATE, 1 1/4"

265777-203

SEALER 98, CARTONS(BLACK)

693
45

081816-000
263156-001

PROTECTIVE COVER [OUTSIDE]


ENCAPSULATED NUT, PLASTIC

549
144

262000-002
262000-003

STRUCTURE BOLT 1 1/4"


STRUCTURE BOLT 1 1/2"

693
780

262416-001
252275-000

HEX NUT, 1/2" HDZ


WASHER, 1/2"

266346K0100

CENTER COVER PLATE

PAGE: 1

17

DOCUMENT NUMBER: 1407970-024

BOLT LENGTHS:

1"

REL:1

TITLE: FND. FASTENER SCHEDULE

1 1/4"

1 1/2"

1 3/4"

2"

25.40

31.75

38.10

44.45

50.80

ANCH. CHAIR

144

72

VERTICAL

117

HORIZONTAL

288

72

PAGE: 1

ANCHOR
RODS

18

19

345 Harvestore Drive


DeKalb, Illinois 60115-9607 U.S.A.
815-756-1551 Phone, 815-756-7821 Fax

LIMITED WARRANTY

MANUFACTURERS

IN NO EVENT SHALL CST STORAGE BE LIABLE (WHETHER


FOR BREACH OF WARRANTY OR CONTRACT, FOR STRICT
LIABILITY OR NEGLIGENCE, OR OTHERWISE) FOR ANY
SPECIAL, INCIDENTAL, PUNITIVE OR CONSEQUENTIAL
DAMAGES, INCLUDING, BUT NOT LIMITED TO, DAMAGES
FOR LOSS OF CONTENTS OR LOSS OF PROFITS, OR FOR
THE CONDITION OR QUALITY OF LIQUID STORED IN THE
TANK, OR FOR ANY INABILITY OF OWNER TO PROVIDE
PRODUCT OR SERVICE TO ANY CUSTOMER OF OWNER.

In the event of any failure of any Aquastore brand liquid storage


tank to perform as warranted in the Limited Warranty, the sole and
exclusive obligation of CST Storage shall be, at its sole option,
either to repair the tank or repair or replace (FOB factory) any part
of the tank which is defective.

Limitation of Remedies

d. The CST Storage Limited Warranty shall become void and


terminate if the tank is not used, operated and maintained in
accordance with the requirements stated in the CST Storage
Operating Manual(s) supplied with the tank, or if the tank is
damaged or subject to any abuse, misuse or vandalism.

c. The CST Storage Limited Warranty shall become void and


terminate if any alterations are made to the tank without the prior
written approval of CST Storage.

b. The CST Storage Limited Warranty


does not cover damage caused by
shipping, handling or tank erection, or
damage caused by operating or maintenance
activities. CST Storage makes no warranty about and
shall not be responsible for any defects in erection or installation of
a tank.

a. The CST Storage Limited Warranty


shall remain in effect only as long as
the tank is used for the storage of
municipal potable water or
municipal sewage waste water.
T h e C S T St o r a g e L i m i t e d
Warranties shall become void and
terminate should the tank be used
for storage of any other liquid.

The CST Storage Limited Warranty is subject to


the following limitations and conditions:

Limitations and Conditions

CST Storage warrants that an Aquastore brand liquid storage


tank will be free from defects in workmanship and materials, under
normal and proper use, maintenance and operation, during the
period expiring on the earlier of (i) five years after liquid is first
introduced into the tank or (ii) 62 months after shipment from the
factory, if the tank is purchased with an Aquastore brand cathodic
protection system.

Five-Year Warranty

Aquastore is the registered trademark of CST Storage


Copyright 2011 CST Storage Printed in U.S.A.
CST P/N 267233-000 Rel. 3 ECN 11005

This Limited Warranty and related limitations and disclaimers


cannot be modified or amended by a CST Storage Authorized
Dealer, and can be modified or amended only by written document
signed by an authorized CST Storage employee.

The CST Storage Authorized Dealers are independent contractors


and are not agents or employees of CST Storage. No statement
by any CST Storage Authorized Dealer or any CST Storage
employee shall constitute an understanding, agreement,
representation or warranty by CST Storage. CST Storage makes
no warranty with respect to goods manufactured by others, even if
sold by a CST Storage Authorized Dealer.

EXCEPT FOR THE LIMITED WARRANTY SET FORTH ABOVE,


T H E R E A R E N O U N D E R S TA N D I N G S , A G R E E M E N T S ,
REPRESENTATIONS OR WARRANTIES, EITHER EXPRESS OR
IMPLIED, RESPECTING THE AQUASTORE BRAND LIQUID
STORAGE TANK CST STORAGE EXPRESSLY DISCLAIMS THE
IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS
FOR A PARTICULAR PURPOSE.

Disclaimers

Any Warranty claim shall be made to CST Storage in writing. Once


a claim has been made, CST Storage shall have the right to
perform on-site inspections of the tank. If CST Storage chooses to
do repair work (which, for purposes of this paragraph, shall include
repairing or replacing defective parts) on the tank, CST Storage
shall be granted permission to perform such work with
its own service personnel or personnel of
others, and under nonunion conditions
unless CST Storage otherwise agrees.
Any repairs made to a tank before
CST Storage is notified of a claim
shall be at the Owner's expense.
Preparation for inspection or
repair of a tank (such as
removing the contents and
obstructive equipment in the tank)
shall be the sole responsibility and
expense of Owner. Preparation of
the tank for use after repair shall be
the sole responsibility and expense of
the Owner.

Any action against CST Storage for breach of warranty or contract ,


or for strict liability, negligence or otherwise relating to a tank, must
be commenced within one year after such cause of action accrues.

Vous aimerez peut-être aussi