EA0379R1
Description
Features
The Flowrite 599 Series SKD6xU Electronic Valve Actuators require a 24 Vac supply
and receive a 0 to 10 Vdc or a 4 to 20 mA control signal to proportionally control a valve.
These actuators are designed to work with Flowrite 599 Series valves with a 3/4-inch
(20 mm) stroke.
Manual override
Maintenance-free
Application
These electronic actuators are designed to be used with Flowrite 599 Series valves and
Siemens Industry standard valves with a 3/4-inch (20 mm) stroke in liquid service and
steam service applications.
Product Number
Warning/Caution Notations
WARNING:
CAUTION:
Technical Instructions
Document Number 155-180P25
June 11, 2013
Specifications
Power supply
Operating voltage
Frequency
Power consumption
Control signals
Function
Agency Certification
24 Vac -20%/+30%
50/60 Hz
17 VA/12W
0 to 10 Vdc or 4 to 20 mA
(DIP switch selectable)
0 to 10 Vdc 100K ohms
4 to 20 mA; 240 ohm
<1%
1%
0 to 1000 ohms
0 to 1.6V
0 to 9.8 Vdc + 2%
>10K ohm
4 to 19.6 mA + 2%
< 500 ohms
Nominal stroke
Run time with control operation (full stroke)
Pushing stroke, 0 to 100%
Pulling and Spring return stroke, 100 to 0%
Nominal Force
NC and 3-way upper
NO and 3-way by-pass
UL approval
UL873
cUL
30 seconds
15 seconds
Stroke
0%
100%
Force
225 lbs (1000 N)
258 lbs (1150 N)
Ambient conditions
Housing
NEMA Rating
Miscellaneous
Dimensions
Conduit opening
Weight
SKD60U
SKD62U
See Figure 17
1/2-inch NPSM
Page 2
Accessories
Technical Instructions
Document Number 155-180P25
June 11, 2013
EA0170R1
Switching capacity
24 Vac
4A resistive
2A inductive
Lowest recommended
current
10 mA
599-00417 Packing heating element.
EA0393R1
Operating Voltage
24 Vac
Heating Output 20 W
599-10071 Weather Shield.
EA0853R1
Service Kits
4-668-5748-8
4-104 5634-8
4-268 5504-8
538-996
WARNING:
This product contains a spring under high compression. Do not attempt to
disassemble the actuator.
Page 3
Technical Instructions
Document Number 155-180P25
June 11, 2013
;;
Legend
1
Pressure cylinder
Piston
Oscillating pump
Return spring
Bypass valve
Position indicator
EA0389R1
SKD Details
Operation
Figure 6.
Figure 5.
3/4 in.
(20mm)
EA0387R1
Page 4
Technical Instructions
Document Number 155-180P25
June 11, 2013
Mounting and
Installation
EA0921R1
Start-up
NOTE: The valve body assembly determines the complete assembly action.
Stroke Calibration
To determine the stroke positions 0% and 100% in the valve, calibration is required
when the valve/actuator are commissioned for the first time.
The actuator must be mechanically connected to a valve and must have a 24 Vac power
supply. The calibration procedure can be repeated as often as necessary.
EA1065R1
CAUTION:
Before starting calibration, be sure the manual adjuster
is set to Automatic to register the actual values.
Actuator then runs to the 100 stroke position (2), green LED
flashes.
Figure 9.
Stroke
0%
EA1066R1
2
1
3
y
100 %
Figure 10.
Technical Instructions
Document Number 155-180P25
June 11, 2013
Stroke Calibration,
Continued
LED
Display
ON
Green
Normal Operation
Flashing
ON
Red
Flashing
OFF
Override Control
Action
Automatic operation
Wait for calibration to be completed
(LED stops flashing)
- Check mounting
- Restart stroke calibration (by
short-circuiting calibration slot)
- Replace electronics
Check the valve
-Check mains
-Replace electronics
Internal Error
Inner valve jammed
No power supply
Faulty electronics
No Function
G
G0
M
U
Hmin
Stroke
100 %
G0
Y
0%
50
900
R[ ]
U
EA1064R1
Vmax
100 %
G0
Stroke
Hmax
Stroke
100 %
Vmax
0%
0%
Page 6
Technical Instructions
Document Number 155-180P25
June 11, 2013
Start-up, Continued
Calib.
Connection
Terminals
G0 G Y M U Z
Status
AC 24V
50/60Hz
G
0 ... 10V
G0
4 ... 20mA Chm
OK
Green
Calib.
Error
Stroke Calibration
Red
Calib.
Status
LED Status
Indication
Valve
Jam
EA1068R1
DIP Switches
Functions See Below
1
2
Figure 11. SKD Electronic Features.
Selection of
Control Signal
Selection of
Flow Characteristic
ON
4 to 20 mA
Modified*
OFF
Factory Setting
0 to 10 Vdc
Default
DIP Switches
(Left to right)
*Changing the default setting will modify an equal percentage valve to a linear flow characteristic.
When set to default, the flow characteristic is determined by the valve body.
Three-Way Valve
Page 7
Technical Instructions
Document Number 155-180P25
June 11, 2013
Manual Operation
>3x360
<< AUTO >>
0
EA1080R1
Figure 12. The Manual Setting Knob in Manual and Automatic Position.
- Turn the manual setting knob clockwise for manual operation.
- A red indicator becomes visible as you begin to crank. Each complete revolution
(360) is equal to 3/32-inch (2.5 mm) stroke.
- If a signal is sent to the actuator while it is in manual operation, the actuator will
move but the control will not be accurate.
- The valve cannot be commanded to its 0% position while in manual operation.
Automatic operation
For automatic operation the manual override knob must be in the fully closed position.
Turn the manual override knob counterclockwise until the red indicator disappears.
Wiring
Do not use autotransformers. Use earth ground isolating step-down Class 2 power
supplies.
Determine supply transformer rating by summing total VA of all actuators used.
The maximum rating for Class 2 step-down transformer is 100 VA.
Page 8
Technical Instructions
Document Number 155-180P25
June 11, 2013
Wiring Diagrams
G (SP)
B1
B
B1
G0
N1
Y1 M
EA1074R1
AC 24 V
F1
Y1
G0
G0 (SN)
B1
F1
N1
Y1
Sensor
Temperature Limiter
Controller
Actuator
G
G0
Y
M
U
Z
Table 2.
Receiving Impedance
Actuator input signal Low (<500 Ohm) High (>10K Ohm)
0 to 20 mA
4 to 20 mA
EA0185R1
G (SP)
24V~
20W
C1
4
Troubleshooting
0 to 10 Vdc
2 to 10 Vdc
EA0184R1
0 to 10 Vdc
4 to 20 mA
GO (SN)
Check that the wires are connected correctly and attached securely.
Check for adequate power supply.
Check that the actuator is set for automatic operation. See the Start-Up section.
Page 9
Technical Instructions
Document Number 155-180P25
June 11, 2013
Dimensions
11-1/4
(285)
8-13/16
(224)
4-13/16
(122)
4-13/16
(122)
2-9/16
(65)
4-1/2
(114)
1-15/16
(49)
9-3/8
(232)
12-7/8
(327)
EA0854R1
3/4
(19)
5
(126)
Page 10
Technical Instructions
Document Number 155-180P25
June 11, 2013
NOTE:
The top
knockout
position should
be used when
installing the
Weather Shield.
Dimensions,
Continued
4-3/4
(120)
2-1/2
(64)
4-1/8
(105)
5
(127)
KNOCKOUT
FOR STANDARD
1/2" CONDUIT
CONNECTOR
5-5/8
(143)
11-13/16
(300)
EA0385R1
4-7/8
(123)
2-5/8
(66)
1-3/4
(44)
2-9/16
(65)
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as
design improvements are introduced. Flowrite is a trademark of Siemens Industry, Inc. Other product or company names mentioned herein may be
the trademarks of their respective owners. 2013 Siemens Industry, Inc.
Page 11