Vous êtes sur la page 1sur 11

CALCULATION SUMMARY

Project Name : Job Name

Project Location:

Drawing No. :

City:

Design Areas
Design Area
Name

Tercer piso

Calc. Mode
(Model)

Demand (HW)

Occupancy

Area of
Total Water Pressure @
Application
Source

Min.
Density

Min.
Pressure

Min.
Flow

Calculated
Heads

Hose
Streams

Margin To
Source

(ft)

(gpm)

(psi)

(gpm/ft)

(psi)

(gpm)

(gpm)

(psi)

2000

330,5

165,2

0,1

12,8

40

100

36,6

File: C:\Users\Hidraulico\Desktop\Planos\HTMC 3P.dwg


Date 26/09/2014

Copyright 2002-2012 Tyco Fire Protection Products

Page 1

HYDRAULIC CALCULATIONS
for
Job Information
Project Name : Job Name
Contract No. :

City:

Project Location:

Date: 26/09/2014

Contractor Information
Name of Contractor:
Address:

City:

Phone Number:

E-mail:

Name of Designer:
Authority Having Jurisdiction:

Design
Remote Area Name

Tercer piso

Remote Area Location

HTMC

Occupancy Classification
Density (gpm/ft)

0,1

Area of Application (ft)

2000

Coverage per Sprinkler (ft)

400

Number of Calculated Sprinklers

In-Rack Demand (gpm)

Special Heads
Hose Streams (gpm)

100

Total Water Required (incl. Hose Streams) (gpm)

330,5

Required Pressure at Source (psi)

124,1

Type of System

Wet

Volume - Entire System (gal)

127,3 gal

Water Supply Information


Date

26/09/2014

Location

HTMC

Source

W1

Notes

File: C:\Users\Hidraulico\Desktop\Planos\HTMC 3P.dwg


Date 26/09/2014

Copyright 2002-2012 Tyco Fire Protection Products

Page 2

Job : Job Name

Node Labels:
Pipe Labels:

Off
Off

Diagram for Design Area : Tercer piso


(Optimized Hydraulic Simplified)

File: C:\Users\Hidraulico\Desktop\Planos\HTMC 3P.dwg


Date 26/09/2014

Copyright 2002-2012 Tyco Fire Protection Products

Page 3

Job : Job Name

Hydraulic Analysis for : Tercer piso


Calculation Info
Calculation Mode
Hydraulic Model
Fluid Name
Fluid Weight, (lb/ft)
Fluid Dynamic Viscosity, (lbs/ft)

Demand
Hazen-Williams
Water @ 60F (15.6C)
N/A for Hazen-Williams calculation.
N/A for Hazen-Williams calculation.

Water Supply Parameters


Flow (gpm)
0
500

Supply 1 : W1

Pressure (psi)
170
150

Hoses
Inside Hose Flow / Standpipe Demand (gpm)
Outside Hose Flow (gpm)
Additional Outside Hose Flow (gpm)

100

Other (custom defined) Hose Flow (gpm)


Total Hose Flow (gpm)

100

Sprinklers
Ovehead Sprinkler Flow (gpm)

230,5

InRack Sprinkler Flow (gpm)

Other (custom defined) Sprinkler Flow (gpm)

Total Sprinkler Flow (gpm)

230,5

Required Margin of Safety (psi)

W1 - Pressure (psi)

124,1

W1 - Flow (gpm)

230,5

Demand w/o System Pump(s)

N/A

Other

File: C:\Users\Hidraulico\Desktop\Planos\HTMC 3P.dwg


Date 26/09/2014

Copyright 2002-2012 Tyco Fire Protection Products

Page 4

Job : Job Name

Hydraulic Analysis for : Tercer piso

File: C:\Users\Hidraulico\Desktop\Planos\HTMC 3P.dwg


Date 26/09/2014

Copyright 2002-2012 Tyco Fire Protection Products

Page 5

Job : Job Name

Hydraulic Analysis for : Tercer piso


Graph Labels
Label

Values

Description

S1

Supply point #1 - Static

S2

Supply point #2 - Residual

D1

Elevation Pressure

D2
D3

Flow (gpm)

Pressure (psi)

170

500

150

4,3

System Demand

230,5

124,1

System Demand + Add.Out.Hose

330,5

124,1

Curve Intersections & Safety Margins


Intersection

Curve Name
Supply

Safety Margin

Pressure (psi)

Flow (gpm)

Pressure (psi)

@ Flow (gpm)

163,6

269

36,6

330,5

Open Heads
Head Ref.

Head Type

Required
Coverage

Calculated

K-Factor
Density

Flow

Pressure

Density

Flow

Pressure

(ft)

(gpm/psi)

(gpm/ft)

(gpm)

(psi)

(gpm/ft)

(gpm)

(psi)

S52

Overhead
Sprinkler

400

11,2

0,1

40

12,8

0,1

40

12,8

S53

Overhead
Sprinkler

400

11,2

0,1

40

12,8

0,13

52,1

21,6

S54

Overhead
Sprinkler

400

11,2

0,1

40

12,8

0,106

42,6

14,5

S55

Overhead
Sprinkler

400

11,2

0,1

40

12,8

0,113

45,2

16,3

S56

Overhead
Sprinkler

400

11,2

0,1

40

12,8

0,127

50,7

20,5

File: C:\Users\Hidraulico\Desktop\Planos\HTMC 3P.dwg


Date 26/09/2014

Copyright 2002-2012 Tyco Fire Protection Products

Page 6

Job : Job Name

Hydraulic Calculations / Fluid Delivery Time Analysis

Node Data
Node#
Elev

Type
Hgroup

K-Fact.
Discharge
Coverage Tot. Pres.
Req. Pres.
Open/Closed Overdischarge Density Elev. Pres. Req. Discharge
gpm
gpm

gpm/psi

ft

ft
gpm/ft

psi
psi

psi
gpm

S52
50

Overhead Sprinkler 11,2


HEAD
Open

40
0

400
0,1

12,8
-4,3

12,8
40

S53
50

Overhead Sprinkler 11,2


HEAD
Open

52,1
12,1

400
0,13

21,6
-4,3

12,8
40

S54
50

Overhead Sprinkler 11,2


HEAD
Open

42,6
2,6

400
0,106

14,5
-4,3

12,8
40

S55
50

Overhead Sprinkler 11,2


HEAD
Open

45,2
5,2

400
0,113

16,3
-4,3

12,8
40

S56
50

Overhead Sprinkler 11,2


HEAD
Open

50,7
10,7

400
0,127

20,5
-4,3

12,8
40

003
50

Node
NODE

19,3
-4,3

009
49

Node
NODE

33,3
-3,9

074
49

Node
NODE

119,8
-3,9

267
49

Node
NODE

31,8
-3,9

272
50

Node
NODE

23,2
-4,3

273
50

Node
NODE

16,1
-4,3

274
50

Node
NODE

14,7
-4,3

W1
40

Supply
SUPPLY

-230,5

124,1
0

File: C:\Users\Hidraulico\Desktop\Planos\HTMC 3P.dwg


Date 26/09/2014

Copyright 2002-2012 Tyco Fire Protection Products

Page 7

Job name: Job Name

Sheet number:___________________

PIPE INFORMATION
Node 1
Node 2

Elev 1
Elev 2

(ft)

K-Factor 1 Flow added(q)* Nominal ID


Fittings
K-Factor 2 Total flow (Q) Actual ID
quantity x (name) = length

(gpm/psi)

(gpm)

11,2

(in)

S52
274

50
50

274
273

50
50

0
40

273
272

50
50

272
267

1 1x(us.90)=2
1,049

C Factor total (Pt)


Pf per ft elev (Pe)
frict (Pf)

(ft)

(psi)

120
0,4681

12,8
0
1,9

1.25 1x(us.Tee-Br)=6
1,38

5,69
6
11,69

120
0,1231

14,7
0
1,4

42,6
82,6

1.25 1x(us.Tee-Br)=6
1,38

9,1
6
15,1

120
0,4714

16,1
0
7,1

50
49

52,1
134,6

1.25 1x(us.Tee-Br)=6
1,38

1
6
7

120
1,1656

23,2
0,4
8,2

267
009

49
49

0
134,6

2.5
2,469

21,02
0
21,02

120
0,0686

31,8
0
1,4

009
074

49
49

95,9
230,5

2.5 2x(us.90)=12
2,469 1x(us.Tee-Br)=12

441,94
24
465,94

120
0,1857

33,3
0
86,5

074
W1

49
40

0
230,5

4 1x(us.90)=10
4,026

13,39
10
23,39

120
0,0172

119,8
3,9
0,4

S54
273

50
50

11,2

42,6
42,6

6,1
6
12,1

120
0,1383

14,5
0
1,7

S55
003

50
50

11,2

45,2
45,2

3,11
2
5,11

120
0,5868

16,3
0
3

003
S56

50
50

7,85
0
7,85

120
0,1543

19,3
0
1,2

S56
009

50
49

7,87
12
19,87

120
0,6217

20,5
0,4
12,4

S53
272

50
50

2,23
6
8,23

120
0,2005

21,6
0
1,7

1.25 1x(us.Tee-Br)=6
1,38
1 1x(us.90)=2
1,049

0
45,2

1.25
1,38

11,2

50,7
95,9

1.25 2x(us.Tee-Br)=12
1,38

11,2

52,1
52,1

1.25 1x(us.Tee-Br)=6
1,38

11,2

NOTES

(psi)

2,13
2
4,13

40
40

(ft)

L
F
T

Discharge shown for flowing nodes only

2006 National Fire Protection Association

Page 8

Job : Job Name

Hydraulic Calculations

PIPE INFORMATION
Node 1
Node 2

Elev 1
Elev 2

(ft)

K-Factor 1 Flow added (q) Nominal ID


Fittings
K-Factor 2 Total flow (Q) Actual ID
quantity x (name) = length

(gpm/psi)

(gpm)

(in)

L
F
T

(ft)

C Factor total (Pt)


Pf per ft elev (Pe)
frict (Pf)

(ft)

(psi)

NOTES

(psi)

Path No: 1
11,2

S52
274

50
50

40
40

274
273

50
50

0
40

273
272

50
50

272
267

1 1x(us.90)=2
1,049

2,13
2
4,13

120
0,4681

12,8
0
1,9

1.25 1x(us.Tee-Br)=6
1,38

5,69
6
11,69

120
0,1231

14,7
0
1,4

42,6
82,6

1.25 1x(us.Tee-Br)=6
1,38

9,1
6
15,1

120
0,4714

16,1
0
7,1

50
49

52,1
134,6

1.25 1x(us.Tee-Br)=6
1,38

1
6
7

120
1,1656

23,2
0,4
8,2

267
009

49
49

0
134,6

2.5
2,469

21,02
0
21,02

120
0,0686

31,8
0
1,4

009
074

49
49

95,9
230,5

2.5 2x(us.90)=12
2,469 1x(us.Tee-Br)=12

441,94
24
465,94

120
0,1857

33,3
0
86,5

074
W1

49
40

0
230,5

4 1x(us.90)=10
4,026

13,39
10
23,39

120
0,0172

119,8
3,9
0,4

W1

124,1

Path No: 2
S54
273

50
50

11,2

42,6
42,6

1.25 1x(us.Tee-Br)=6
1,38

6,1
6
12,1

120
0,1383

273

14,5
0
1,7
16,1

Path No: 3
S55
003

50
50

003
S56

50
50

S56
009

50
49

11,2

11,2
11,2

45,2
45,2

1 1x(us.90)=2
1,049

0
45,2

1.25
1,38

50,7
95,9

1.25 2x(us.Tee-Br)=12
1,38

3,11
2
5,11

120
0,5868

16,3
0
3

7,85
0
7,85

120
0,1543

19,3
0
1,2

7,87
12
19,87

120
0,6217

20,5
0,4
12,4

009

33,3

Path No: 4
S53
272

50
50

11,2

52,1
52,1

1.25 1x(us.Tee-Br)=6
1,38

272

2,23
6
8,23

120
0,2005

21,6
0
1,7
23,2

File: C:\Users\Hidraulico\Desktop\Planos\HTMC 3P.dwg


Date 26/09/2014

Copyright 2002-2012 Tyco Fire Protection Products

Page 9

Job : Job Name

Hydraulic Calculations

PIPE INFORMATION
Node 1
Node 2

Elev 1
Elev 2

(ft)

K-Factor 1 Flow added (q) Nominal ID


Fittings
K-Factor 2 Total flow (Q) Actual ID
quantity x (name) = length

(gpm/psi)

(gpm)

(in)

(ft)

L
F
T
(ft)

C Factor total (Pt)


Pf per ft elev (Pe)
frict (Pf)
(psi)

Pressures are balanced to a high degree of accuracy. Values may vary by 0.1 psi due to display rounding.

Maximum Velocity of 28,88 ft/s occurs in the following pipe(s):

NOTES

(psi)

(267-272)

File: C:\Users\Hidraulico\Desktop\Planos\HTMC 3P.dwg


Date 26/09/2014

Copyright 2002-2012 Tyco Fire Protection Products

Page 10

Job : Job Name

Device Graphs

File: C:\Users\Hidraulico\Desktop\Planos\HTMC 3P.dwg


Date 26/09/2014

Copyright 2002-2012 Tyco Fire Protection Products

Page 11

Vous aimerez peut-être aussi