ORTHOFLUOR FP
SF6 circuit breaker
from 7.2 to 36 kV
Indoor applications
Modular design
IEC, VDE and BS standards
Technical
Specifications
AREVA T&D
Endurance
The very high endurance originates
in the minimum wear of the gas
and of the contacts which are little
stressed because of the low energy
of the arc; this is due to:
- the intrinsic qualities of the gas,
- the limited arcing time,
- smaller arc length,
- the instability of the arc roots
thanks to the use of hollow
tungsten alloy arcing contacts,
- full separation of arcing contacts
and current carrying contacts.
Safety
The FP circuit breakers operate
under low pressure.
The internal pressure rise, due to
gas compression and heating upon
switching remains low.
A safety membrane vents any
excessive pressure that might
arise, however improbable.
At the atmospheric pressure, the
circuit- breaker maintains sufficient
dielectric characteristics and
ensures safe load switching.
The rapid gas recombination
and the injection of fresh gas
into the inter-electrode space
ensures perfect breaking at TRV
values amply higher than those
recommended by the applicable
IEC standard.
Easy installation
The design of the separate pole
circuit-breaker and the various
possible arrangements make for
fast and easy adaptation to many
configurations of open units or of
prefabricated cubicles.
Fast reclosing
Maintenance
Capacitive switching
The SF6 technique, particularly well
suited to capacitor-bank switching
and protection, precludes any
overvoltage upon breaking which
would jeopardize the durabilityu of
the bank.
Equipment designation
- overcurrent withstand,
24
25
FP 1716 B
A
B
C
D
E
F
G
H
J
Pole spacings
mm
0
Circuit breaker type 1
FP
1
210
250
300
7
2
1
1
2
7
350
400
Description of a pole
Insulating rod
Filling valve
Absorption catalyst
Safety bursting membrane
Base frame
FP 3616 D pole
Breaking operation
Autopneumatic (puffer)
1
2
3
7
8
3
9
5
6
"CLOSED POSITION"
Current flows between terminals
1 and 6 of the equipment via main
fixed contact 2 and 5, sliding
contacts 3 and 5 and rod 4.
DURING OPENING
"OPEN POSITION"
1
7
8
9
3
2
3
4
5
6
2
4
"CLOSED POSITION"
PRESSURE BUILD-UP
ARC BLASTING
Performance data
Main characteristics
Dilectric tests
Rated
voltage
kVV
impulse
kVc
50 Hz
kV rms
Breaking
capacity
kA rms
7.2
60
20
16
20
25
31.5
40
50
16
20
25
31.5
40
50
12.5
16
20
25
31.5
40
12.5
16
20
25
31.5
40
12.5
16
20
25
31.5
12
75
17.5
95
24
125
36
170
28
36
50
70
400
630
800
1250
1600
210
250
300
350
400
2000
2500
3150
4000
Other characteristics
Overcurrent rating
The kA making current of all the
circuit breakers in the FP range
is equal to 2.5 times the breaking
current KA r.m.s. (for other values
please consult us).
The short-time withstand current is
equal to the breaking current held
for 1 or 3 seconds (please consult
us).
Capacitor switching
- In single capacitor-bank :
for voltages < 24 kV : 1000 A
36 kV : 800 A
- Back-to-back banks : please
consult us.
Life span
Electrical
The very great durability is due
to the minimal deterioration of
the gas and wear of the contacts
which are but little affected by the
low arc energy in turn due to :
- the intrinsic qualities of the gas,
- the short arcing time,
- the short length of the arc,
- the instability of the arc roots
arising from the use of hollow
arcing contacts of a tungsten
alloy.
The endurance of the
ORTHOFLUOR type FP breakers
is inversely proportional to the
square of the current interrupted.
The adjacent curves show
the permissable number of
interruptions for a moderate
level of wear as a function of the
current interrupted.
Mechanical :
By the very principle of operation,
the movements of the mechanical
parts are damped naturally by
the compression of the gas and
the level of operational energy is
moderate. The self-centring of the
tolerances make the equipment
insensitive to any misalignment
attributable to wear.
Operating cycles
The FP type circuit breakers allow
for the following cycles :
A. : O - 3 min CO - 3 min CO
B. : CO - 15 s - CO
C. : O - 0,3 s - CO - 3 min - CO
(For this fast cycle, please consult
us).
Operating time
Irrespective of the auxiliary supply
voltage and of the breaking current
values, the average operating
times, expressed in ms, are :
Undervoltage trip
coil (ms)
Ouverture.........................
50
110
Arc maximum...................
20
20
Temps total
de coupure.......................
70
130
Gas tightness :
This is ensured by a dynamic joint
at the point of entry of the shaft.
The gas tightness is adequate
for equipments sealed for life
maximum rate of leakage :
10-6 cm3 x bar/sec.
Number of breaks
8
6
4
8
6
4
2
102
80
60
40
20
10
8
6
4
2
3. FP 0740 - FP 1240
0,2
0,4
10
20
40 60
kA
Number of breaks
8
6
4
2
8
6
4
2
6. FP 0750
102
80
60
40
20
10
8
6
4
2
0,2
0,4
10
20
40 60
kA
Overall dimensions
Front arrangement
References
Dimensions in mm
210
< 31.5 kA
1250 A
350
400
25 kA
24 kV
31.5 kA
31.5 kA
> 24 kV 40 kA
740
840
840
940
1040
680
700
740
740
740
840
840
840
940
940
940
1040
1250 A
841
841
931
1013
> 1250 A
894
894
1060
894
1013
1060
894
1013
1060
984
984
1013
1013
> 2500 A
1060
476
476
595
476
595
595
476
595
595
476
566
595
595
1250 A
470
470
470
563
> 1250 A
520
563
600
520
563
600
520
563
600
520
520
563
563
> 2500 A
600
300
31.5 kA > 40 kA
31.5 kA > 40 kA
31.5 kA > 40 kA
< 31.5 kA
< 31.5 kA
40 kA 50 kA
40 kA 50 kA
40 kA 50 kA
680
> 1250 A
250
B
C
Front arrangement
Longitudinal arrangement
Longitudinal arrangement
Reference
Dimensions in mm
210
C
D
< 31.5 kA
250
300
350
31.5 kA > 40 kA
31.5 kA > 40 kA
< 31.5 kA > 40 kA
< 31.5 kA
31.5 kA
40 kA 50 kA
40 kA 50 kA
40 kA 50 kA
1250 A 1040
1040
1220
25 kA
24 kV
> 24 kV
1370
1370
400
31.5 kA
31.5 kA
40 kA
-
1040
1120
1050
1120
1220
1220
1370
1370
1454
> 2500 A
1040
1220
1220
1370
1354
1370
1470
1250 A
841
841
985
894
> 1250 A
894
894
894
985
1032
985
1032
931
970
1032
> 2500 A
1032
894
985
894
985
1032
1250 A
476
476
476
476
476
567
> 1250 A
476
567
567
567
> 2500 A
567
567
567
567
376
376
376
376
376
376
376
376
376
376
376
376
376
The dimensions given in the table above are applicable to our standard range. For other requirements, please
consult us.
Weight : Up to 1250 A : 115 kg to 175 kg. / Above 1250 A : 215 kg to 235 kg.
Description
of the operating mechanism
The FP range of circuit breakers
is equipped with an operating
mechanism using the energy stored
in a spring. This mechanism can be
of two types :
- BLR, manually charged
- BLRM, electrically charged.
The sturdiness and reliability of this
operating mechanism have been
demonstrated for 30 years.
The loaded closing spring is held
by a latch-in. The manually or
electrically controlled release of this
latch-in causes :
- the closing spring to fully expand,
- the breaker to close,
- the tripping spring to be charged.
The cuircuit breaker, controlled
by the tripping spring, is held in
the closed position, ready to open
instantaneously, by a further latchin.
It is then possible to charge the
closing spring again while the
breaker is in the closed position,
which authorizes a fast reclosing
cycle.
The BLRM mechanisms are the
motorized version of the BLR
operating mecanism and they
ensure automatic charging of the
closing spring.
They are especially recommended
for circuit breakers intended to
ensure a cycle of fast reclosing
operation generally followed by a
cycle of slow closing operation.
Depending on the torque required,
these control mechanisms are fitted
with different types of springs.
Operating mechanism
Rollers
Direct current
Alternating
current
210 W
230 W
80 W
80 W
30 W
30 W
30 W
ADDITIONAL
AMT
71
SHUNT TRIP
COIL
75
29
25
WITH CLOSING
TRIPPING THROUGH
NO VOLT
COIL TYPE MIA
K1
ANTI-PUMPING
77
SA
AP
AP
MOTOR
CIRCUIT
FUSES
Fm
IN
IN
AP
MC
M
MIA
Th
SA
MOTOR
SA
BE
BD
SB
AP
K1
Rcp
MCA 2
MCA 3
MCA 1
MCA 2
MCA 3
MCA 1
SA
ANTI-PUMPING
35
AP
AP
BDS
LOCKING
MICRO
SWITCH
RP
BD
CLOSING
SA
IN
Option
BLR
BLRM
72
39
30
26
24
94
89
86
15
16
18
14
X
X
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
NOT TO
BE
CUMULATED
WITH
OPTION 4
Captions :
X : Basic equipment
O : Option
- : Not an option
10
76
04
IN CASE OF 2 THRESHOLDS
PRESSURE SWITCH
OPTION 86 1st THRESHOLD
ALARM OR TRIPPING
OPTION 89 2nd THRESHOLD
TRIPPING
OPTION 16
TO USE IN ADDITION
TO OPTION 15
36
38
02
32
O
X
O
O
NOT TO BE
CUMULATED
WITH OPTION 22
22
01
21
NOT TO BE
CUMULATED
WITH OPTION 38
130
680
130
200
75
10
390
122,5
168
20
200
376
Weight : BLR 56 kg - BLRM 60 kg.
NG
RO
CH
ANTI-PUMPING
MOTOR
MOTOR
CIRCUIT
FUSES
MOTOR
CIRCUIT
BREAKER
SPRING
POSITION
INDICATION
35
AP
AP
33
Fm1
SA
FAULT
INDICATION
MICRO
SWITCH
31
V/J
31
Q1
IN
AP
MC3
IN
Fm2
36
O
NOT TO BE
CUMULATED
WITH OPTION 38
01
X
13
11
15
13
11
15
13
12
14
12
16
14
10
12
16
14
SA
IN
22
11
11
SC
08
29
Q1
34
21
SB
IN
32
32
31
92
O
O
O
O
X
X
O
O
NOT TO BE
CUMULATED
WITH
OPTION 31
Attention :
The 19 circuits wired to a terminal
are a maximum for circuit breakers
supplied loose.
130
225
11
Striker
Relay
TC
>
>>
Internal synopsis
Description
12
Total flexibility
The settings for tripping time delays
and thresholds are completely
independent.
The wide range of settings for time
delays ensures the selectivity of the
circuit-breakers is extremely precise
when phase faults and homopolar
faults occur.
16 settings from 1.25 to 20 seconds
for phase faults,
8 settings from 0.2 to 0.9 second for
earth faults.
A simplified option provides phase
fault detection with two current
transformers.
td(s)
T0
20
I0 = 0,05+
INT
To =10
0
0
0
0
0
0
0
+0,01
+0,02
+0,04
+0,08
+0,16
+0,32
+0,64
0
0
0
+0,1
+0,2
+0,4
To
1,25
1
t(s) = 0,2+
I>>
I>
I0
+0,02
+0,04
+0,08
+0,16
+0,32
+0,64
0
0
0
0
+1,25
+2,5
+5
+10
0
0
0
+1
+2
+2
I>>
I0
I>
1,2
Simple to use
All the threshold and time delay
settings are clearly indicated on the
front panel.
+1,25 =
+3 =
To
I >>
I>
I>>
TRIP
10
Tripping curve
Designed for users
I>
INT
TEST
0.1
0.01
+0,1 =
I>Is
t(s)
0
0
0
0
0
0
0
Technical features
Relay and current transformers characteristics
Solid state relay
Current setting range
Tripping indicator
Current transformer
Two values
INT
Thermal withstand capacity (Continuous)
(3 s)
100 or 630 A
2 x INT
25 kA
Overcurrent protection
Setting range
I>
Low trip threshold
Is
Inverse time delay
To
Short circuit current setting
I>>
Short circuit tripping delay
ANSI: 50 - 51
From 0.1 to 1.36 INT by step 0.02
1.2 x I>
From 1.25 s to 20 s by step 1.25 s
From 3 to 8 x I> by step 1
30 ms
ANSI: 51N
From 0.05 to 1.32 INT by step 0.01
From 0.2 s to 0.9 s by step 0.1 s
Capability
Relay curves
Electromagnetic compatibility
Climatic environmental testing
Vibration tests
IEC 255-3
IEC 1000-4
IEC 68-2
10 000 C.B operations
13
12
Withstand voltages
Lightning
impulse (kVP)
75
50/60 Hz 1 mn
kV rms
28
24
125
50
36*
170
70
Breaking
capacity
kA
630 A
800 A
16
RXFP 1216B
RXFP 1216C
25
RXFP 1225B
RXFP 1225C
29
RXFP 1229B
RXFP 1229C
16
RXFP 2416B
RXFP 2416C
25
RXFP 2425B
RXFP 2425C
16
RXFP 3616B
RXFP 3616C
25
RXFP 3625B
RXFP 3625C
* Only with low voltage current transformers : see technical specification : T001-STS-11/99 (consult us).
14
Striker
Operations counter
Closing coil
Anti-pumping relay
Frontal arrangement
599
170
740
190
120
120
250
250
376
34
16
104
188
376
746
263
841
170
219
40
20
20
75
80
34
353
60
600
706
320
Weight
Longitudinal arrangement
190
210
300
250
250
428
376
120
120
293
38
34
104
34
134
476
278
263
841
706
170
188
26
52
100
100
790
15
www.areva-td.com
Products - L4PS - Orthofluor FP - V1 - 71148 - EN - - AREVA - 01-2006. AREVA, the AREVA logo and any alternative version there of are trademarks and service marks of AREVA. The other names mentioned, registered or not, are
the property of their respective companies. Printed in France. Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this
brochure should only be regarded as a guide and is intented for information purposes only. Its contents do not constitute an offer for sale or advise on the application of any product referred to in it. We cannot be held responsable for any
reliance on any decisions taken on its contents without specific advise.