Vous êtes sur la page 1sur 4

TECHNICAL SCHEDULES A & B FOR

SWITCHGEAR PIUs IN ACCORDANCE WITH EST 240-64685228


Type Tests per IED product family

Schedule A: Purchasers specific requirements


Schedule B: Guarantees and technical particulars of equipment offered

4.1

General

4.1.4
4.1.4

Type testing laboratory


SANS/ILAC accreditation of laboratory

4.2

Type Tests (per IED product family)


Test

4.2.1

Standard

Ports*

Compliance criteria

Manufacturer product family/series name

Product Safety

1(a)

Dielectric withstand

IEC 60255-5

2kV r.m.s. 50Hz for 1 minute between all terminals to case earth, 1kV across
contacts.

1(b)

Insulation resistance

IEC 60255-5

Insulation resistance greater than 20M when measured at 500Vd.c.

1(c)

Electrical impulse (1.2/50s)

IEC 60255-5

5kV 1.2/50s waveform, 0.5J

Enclosure protection

SANS 60529

ENC

Protected against ingress of dust particles, dripping water.


2

Protected against access to hazardous parts with the back of a hand.

4.2.2

Environmental specifications

Cold

IEC 60068-2-1

16 hours at -25oC (LCD screen operative)

Dry Heat

IEC 60068-2-2

16 hours tolerance at +55oC/+70oC (control room / outdoor application)

Cyclic Temperature and Humidity

IEC 60068-2-30

25oC and 95% relative humidity/ 55oC and 95% relative humidity, 12 + 12 hour
cycle

Response: 1g, 10 - 150Hz, 1 sweep, energised. Contacts should not close for
longer than 2ms.

Endurance: 1g 10 150Hz, 20 sweeps, un-energised. Contacts should not close


for longer than 2ms.

Response: 5g, 11ms, 3 pulses in each direction, energised

Withstand: 15g, 11ms, 3 pulses in each direction, un-energised

Vibration

Shock

IEC 60255-21-1

IEC 60255-21-2

Bump

IEC 60255-21-2

10g, 16ms, 1000 pulses un-energised.

Seismic

IEC 60255-21-3

Test method A (single axis sine sweep test) 1 35Hz, 1 sweep.

TECHNICAL SCHEDULES A & B FOR


SWITCHGEAR PIUs IN ACCORDANCE WITH EST 240-64685228
Type Tests per IED product family (concluded)

4.2.3

Immunity Specifications

Note: Refer to IEC 60255-26 for an overview of electromagnetic compatibility requirements.

1(a) (c)
1(d)

4.2.3

Voltage dips, interruption, gradial


start-up/shut-down

IEC 60255-11

PS

50ms interruption has no effect on operation


No maloperation for 5s interruption.
No maloperation for decaying DC over 60s, rising over 60s.

AC ripple

IEC60255-11

PS

Device shall function correctly with 12% 100Hz ac signal superimposed on the
d.c. supply.

SANS 61000-4-8

ENC

Immunity Specifications (Continued)

Power frequency magnetic field

1MHz oscillatory waves

Electrostatic Discharge

Radiated Radio Frequency field

Fast Transient

Surge

Induced Radio Frequency field

Power Frequency immunity

4.2.4

Emission Specifications

IEC60255-22-1 or SANS
61000-4-18

PS, IO

100A/m continuous, 1000A/m 1-3s, 50Hz


2.5kV CM, 1kV DM, 2s total test duration, 6 10 bursts at 400Hz repetition.

COM

1kV CM, 0kV DM, 2s total test duration, 6 10 bursts at 400Hz repetition.

IEC 60255-22-2 or SANS


61000-4-2

ENC

6kV Contact Discharge, 8kV Air Discharge

IEC 60255-22-3 or
SANS 61000-4-3

ENC

10V/m unmod r.m.s., 80% AM (1kHz), 80MHz 1GHz, 1.4 2.7 GHz

IEC 60255-22-4

PS, IO, E
COM

IEC 60255-22-5 or
SANS 61000-4-5
IEC 60255-22-6 or
SANS 61000-4-6
IEC 60255-22-7

PS, IO
COM
PS, IO

2kV, 5kHz
1kV, 5kHz
1,2/50s (8/20s) voltage (current) surge:
0,5; 1; 2 kV line to earth, 0,5; 1 kV line to line
0,5; 1 kV line to earth
2kV

PS, COM, IO, E 10Vrms, 150kHz 80MHz


IO

AC voltages applied to D.C. inputs: 150V r.m.s. DM, 300V r.m.s. CM

Note: Refer to IEC 60255-26 for an overview of electromagnetic compatibility requirements.

Conducted emission

IEC 60255-25

PS

Radiated emission

IEC 60255-25

ENC

0,15 0,5 MHz: 79dB(V) quasi peak, 66dB(V) ave.


0,5 30 MHz: 73dB(V) quasi peak, 60dB(V) ave.
30 230 MHz: 40dB(V) quasi peak at 10m
230 1000 MHz: 47dB(V) quasi peak at 10m

* Immunity and Emission tests are applicable to specific ports of the Equipment Under Test:COM: (Rear) communication ports; E: Earth terminal; ENC: Device enclosure; IO: Inputs/Outputs; PS: Power Supply
CM = Common Mode, DM = Differential Mode.

Schedule A
Specify
Specify

Specify
Comply
Comply
Comply
IP41
(front panel)
IP1X (rear)
-25oC Test Ad
+55oC / +70oC
Test Bd
+55oC Test Db
Class 2 Response
Class 1 Endurance
Class 1 Response
Class 1 Withstand
Class 1
Class 1

Schedule B

ply

Comply
Comply

Class 5

Class 3

Class 3
Class 3
Class B
Class 3
Class 3
Class A

Vous aimerez peut-être aussi