NETWORK ANALYZER
NETWORK ANALYZER
S.A. DE CONSTRUCCIONES INDUSTRIALES
NETWORK ANALYZERS
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
PRODUCTS RANGE
LED DISPLAY
DIN RAIL MOUNTING
TCEM
CT-05
NA-03
AR-05
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
MAR 144, MDA 144
PRODUCTS RANGE
NETWORK ANALYZERS
DIRECT CURRENT
ANALIZADORES
DE RED CORRIENTE
ALTERNA
LCD DISPLAY
DIN RAIL MOUNTING
AR3DC
LED DISPLAY
PANEL (144 x 144) MOUNTING
TMCC
TMCQ
SACIgest
IN
NA-04
AR-04
OUT
Analyzers
NETWORK ANALYZERS
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
CONT
CONTENTS
PRODUCTS RANGE..................................................................................................................................................................................................................................................................... NA.03
NA.06
NA.08
NA.10
CT-05
NA-05
AR-05
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
NETWORK ANALYZER - ANG96 STANDARD VERSION
The ANG96 is a digital device, able to measure all the variables associated with
an electrical line. It accepts the three currents and three voltage signal in a fourwire conguration. It is also possible to use it in a three-wire conguration, using
two or three current transformers.
GENERAL FEATURES
DIN SIZE 96 x 96
LCD 128 x 64 DISPLAY WITH BACKLIGHT
4 CUADRANT MEASUREMENT
NEUTRAL CURRENT MEASUREMENT
HARMONIC DISTORTION (THD on V and I)
MAXIMUM DEMAND (A, kW, kVA and kvar)
MAXIMUM AND MINIMUM VALUES
TRUE RMS VOLTAGE AND CURRENT
SERIAL PORT RS485
2 HOUR COUNTERS
ELECTRICAL PARAMETER
SYMBOL
L1
L2
L3
Voltage (Line-to-neutral)
Voltage (Line-to-Line)
Current
Neutral current
Active power (P)
Reactive power (Q)
Apparent power (S)
Power factor (Cos )
Maximum demand (I)
Maximum demand (P)
Maximum demand (Q)
Maximum demand (S)
Frequency
THD Current
THD Voltage
Import active energy (EP+)
Hour counter active positive (T+)
Export active energy (EP-)
Hour counter active negative (T-)
Import inductive react energy (Eq+)
Import capaitive react energy (Eq-)
V
V
A
A
kW
kvar
kVA
PF
A
kW
kvar
kVA
Hz
A
V
kWh
h-m-s
kWh
h-m-s
kvarh
kvarh
TOTAL
HOUR COUNTERS
2 hour counters:
- Active power + (consumed)
- Active power - (generated)
- Limit:
- Resolution:
NA-06
AR-04
50.000 hours
1 second
Analyzers
NETWORK ANALYZERS
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
TECHNICAL SPECIFICATIONS
OUTPUT
INPUT
Rated voltage (Un)
0-520 V AC.
Relays
250 V AC.,3A
Burden
Pulse weight
60 ms
1 and 5 A
Serial port
RS485
Burden
Protocol
MODBUS RTU
Operating range
10 - 120% In
Frequency
Programmable
Baud rate
45 - 65 Hz
Overload
1200-19200 bps
Standard 9600 bps
2 In permanent, 20 In 1 s
Connection
1,2 Vn permanent, 2 Vn 10 s
2 wires
UNIVERSAL Aux. V.
Burden
< 4 VA
2 Vn x 10 s.
1,2 Vn permanent.
20 In x 1 s.
2 In permanent.
GENERAL
LCD DISPLAY
GENERAL FEATURES
Case material
ABS,UL94 V0
Dimensions
DIN 96 x 96 mm
Terminals
Pluggable
2,5 mm
Weight
0,4 Kg
Protection
Proteccin:
Opcional:
Optional protection
Seguridad elctrica:
Electrical safety
IP 20 Terminals
IP 20 Terminales
IP 54 Front
IP 54 Frontal
IP 65 con
tapa
frontal
IP 65 Front
cover
(EN 61010) Clase 2
(EN
61010)
Class
2
Categora III
Category III
ACCURACY
Parameter
Operating
range
Accuracy
Voltage
Current
Active power
Reactive power
Apparent power
Power factor
Frequency
Active energy
Reactive energy
20-120%
1-120%
1-120%
1-120%
1-120%
0,5%
45-65Hz
5-120%
5-120%
0,3%(read.+full sca.)
0,3%(read.+full scal.)
0,3%(read.+full sca.)
0,3%(read.+n sca.)
0,4%(read.+n sca.)
1%(Full scale)
0,2%(Full scale)
0,5% reading
1% reading
CONTACT OUTPUTS
Contact outputs can be set as max. or min. alarm contacts
associated to any measured parameter or as active energy
and reactive enrgy pulses. They can also be set as contacts
managed from the central unit.
CONNECTIONS
Max. 3 x 300 (520) V
X /5 A, X /1A
Universal Aux. V
45 - 65 Hz
CT-05
NA-07
AR-05
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
NETWORK ANALYZER - ANG96 ETHERNET VERSION
The ANG96 is a digital device, able to measure all the variables associated with
an electrical line. It accepts the three currents and three voltage signal in a fourwire conguration. It is also possible to use it in a three-wire conguration, using
two or three current transformers.
NE
GENERAL FEATURES
DIN SIZE 96 x 96
LCD 128 x 64 DISPLAY WITH BACKLIGHT
4 CUADRANT MEASUREMENT
NEUTRAL CURRENT MEASUREMENT
HARMONIC DISTORTION (THD on V and I)
MAXIMUM DEMAND (A, kW, kVA and kvar)
MAXIMUM AND MINIMUM VALUES
TRUE RMS VOLTAGE AND CURRENT
SERIAL PORT RS485
2 HOUR COUNTERS
ETHERNET TCP/IP PORT
ELECTRICAL PARAMETER
SYMBOL
L1
L2
L3
Voltage (Line-to-neutral)
Voltage (Line-to-Line)
Current
Neutral current
Active power (P)
Reactive power (Q)
Apparent power (S)
Power factor (Cos )
Maximum demand (I)
Maximum demand (P)
Maximum demand (Q)
Maximum demand (S)
Frequency
THD Current
THD Voltage
Import active energy (EP+)
Hour counter active positive (T+)
Export active energy (EP-)
Hour counter active negative (T-)
Import inductive react energy (Eq+)
Import capaitive react energy (Eq-)
V
V
A
A
kW
kvar
kVA
PF
A
kW
kvar
kVA
Hz
A
V
kWh
h-m-s
kWh
h-m-s
kvarh
kvarh
TOTAL
HOUR COUNTERS
2 hour counters:
- Active power + (consumed)
- Active power - (generated)
- Limit:
- Resolution:
NA-08
AR-04
50.000 hours
1 second
Analyzers
NETWORK ANALYZERS
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
TECHNICAL SPECIFICATIONS
OUTPUT
INPUT
Rated voltage (Un)
0-520 V AC.
Relays
250 V AC.,3A
Burden
Pulse weight
60 ms
1 and 5 A
Serial port
RS485
Burden
Protocol
MODBUS RTU
Operating range
10 - 120% In
Frequency
Programmable
Baud rate
45 - 65 Hz
Overload
1200-19200 bps
Standard 9600 bps
2 In permanent, 20 In 1 s
1,2 Vn permanent, 2 Vn 10 s
Connection
2 wires
Ethernet port
TCP/IP
UNIVERSAL Aux. V.
Burden
< 4 VA
2 Vn x 10 s.
1,2 Vn permanent.
20 In x 1 s.
2 In permanent.
GENERAL
LCD DISPLAY
GENERAL FEATURES
Case material
ABS,UL94 V0
Dimensions
DIN 96 x 96 mm
Terminals
Pluggable
2,5 mm
Weight
0,4 Kg
Protection
Proteccin:
Opcional:
Optional protection
Seguridad elctrica:
Electrical safety
IP 20 Terminals
IP 20 Terminales
IP 54 Front
IP 54 Frontal
IP 65 con
tapa
frontal
IP 65 Front
cover
(EN 61010) Clase 2
(EN
61010)
Class
2
Categora III
Category III
CONTACT OUTPUTS
Contact outputs can be set as max. or min. alarm contacts
associated to any measured parameter or as active energy
and reactive enrgy pulses. They can also be set as contacts
managed from the central unit.
CONNECTIONS
ACCURACY
Parameter
Operating
range
Accuracy
Voltage
Current
Active power
Reactive power
Apparent power
Power factor
Frequency
Active energy
Reactive energy
20-120%
1-120%
1-120%
1-120%
1-120%
0,5%
45-65Hz
5-120%
5-120%
0,3%(read.+full sca.)
0,3%(read.+full scal.)
0,3%(read.+full sca.)
0,3%(read.+n sca.)
0,4%(read.+n sca.)
1%(Full scale)
0,2%(Full scale)
0,5% reading
1% reading
CT-05
NA-09
AR-05
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
NETWORK ANALYZER - ANG96 GENERATOR VERSION
The ANG96 is a digital device, able to measure all the variables associated with
an electrical line. It accepts the three currents and three voltage signal in a fourwire conguration. It is also possible to use it in a three-wire conguration, using
two or three current transformers.
NE
GENERAL FEATURES
Energy counters*
Contadores
de energa *
Hour counters
**
Contadores
de tiempo
**
DIN SIZE 96 x 96
LCD 128 x 64 DISPLAY WITH BACKLIGHT
4 CUADRANT MEASUREMENT
NEUTRAL CURRENT MEASUREMENT
HARMONIC DISTORTION (THD on V and I)
MAXIMUM DEMAND (A, kW, kVA and kvar)
MAXIMUM AND MINIMUM VALUES
TRUE RMS VOLTAGE AND CURRENT
SERIAL PORT RS485
4 HOUR COUNTERS
ELECTRICAL PARAMETER
SYMBOL
L1
L2
L3
Voltage (Line-to-neutral)
Voltage (Line-to-Line)
Current
Neutral current
Active power (P)
Reactive power (Q)
Apparent power (S)
Power factor (Cos )
Maximum demand (I)
Maximum demand (P)
Maximum demand (Q)
Maximum demand (S)
Frequency
THD Current
THD Voltage
Import active energy (EP+),(DP+)*
Hour counter active positive (T+)**
Export active energy (EP-),(DP-)*
Hour counter active negative (T-)**
Import induct. react. energy (Eq+),(Dq+)*
Import capacit. react. energy (Eq-),(Dq-)*
V
V
A
A
kW
kvar
kVA
PF
A
kW
kvar
kVA
Hz
A
V
kWh
h-m-s
kWh
h-m-s
kvarh
kvah
TOTAL
HOUR COUNTERS
4 Hour counters:
- Active power +(consumed) Normal Mode
- Active power - (generated) Normal Mode
- Active power +(consumed) Generator Mode
- Active power - (generated) Generator Mode
- Limit:
- Resolution:
NA-10
AR-04
50.000 hours
1 second
Analyzers
NETWORK ANALYZERS
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
TECHNICAL SPECIFICATIONS
OUTPUT
INPUT
Rated voltage (Un)
0-520 V AC.
Relays
Burden
Pulse weight
60 ms
1 and 5 A
Serial port
RS485
Burden
Protocol
MODBUS RTU
Operating range
10 - 120% In
Frequency
Programmable
Baud rate
45 - 65 Hz
Connection
1,2 Vn permanent, 2 Vn 10 s
Generator Voltage
2 wires
230 V AC.
AUXILIARY VOLTAGE
UNIVERSAL Aux. V.
Burden
< 4 VA
OVERLOAD
2 Vn x 10 s.
1,2 Vn permanent.
20 In x 1 s.
2 In permanent.
LCD DISPLAY
GENERAL
GENERAL FEATURES
Case material
ABS,UL94 V0
Dimensions
DIN 96 x 96 mm
Terminals
Pluggable
2,5 mm
Weight
0,4 Kg
Protection
Proteccin:
Opcional:
Optional protection
Seguridad elctrica:
Electrical safety
1200-19200 bps
Standard 9600 bps
2 In permanent, 20 In 1 s
Overload
250 V AC.,3A
IP 20 Terminals
IP 20 Terminales
IP 54 Front
IP 54 Frontal
IP 65 con
tapa
frontal
IP 65 Front
cover
(EN 61010) Clase 2
(EN
61010)
Class
2
Categora III
Category III
CONTACT OUTPUTS
Contact outputs can be set as max. or min. alarm contacts
associated to any measured parameter or as active energy
and reactive enrgy pulses. They can also be set as contacts
managed from the central unit.
CONNECTIONS
ACCURACY
Parameter
Operating
range
Accuracy
Voltage
Current
Active power
Reactive power
Apparent power
Power factor
Frequency
Active energy
Reactive energy
20-120%
1-120%
1-120%
1-120%
1-120%
0,5%
45-65Hz
5-120%
5-120%
0,3%(read.+full sca.)
0,3%(read.+full scal.)
0,3%(read.+full sca.)
0,3%(read.+n sca.)
0,4%(read.+n sca.)
1%(Full scale)
0,2%(Full scale)
0,5% reading
1% reading
CT-05
NA-11
AR-05
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
NETWORK ANALYZER - LAB96
Instrument with microprocessor, programmable, with three LED display
indicating measurements and built-in keypad.
GENERAL FEATURES
DIN 96 X 96 INSTRUMENT
MEASUREMENT IN 4 QUADRANTS
THREE-PHASE 3 or 4 WIRE
NEUTRAL CURRENT
HARMONIC DISTORTION (THD V and I)
HARMONIC MEASURING (up to 15) (optional)
MAXIMUM DEMAND A, kW, kVA
MAX. and MIN. VALUES
TRUE RMS.
RS 485 SERIEAL PORT
1 CONTACT OUTPUT
ELECTRICAL PARAMETER
SYMBOL
L1
L2
L3
Voltage (Line-to-neutral)
Voltage (Line-to-Line)
Current and neutral current
Active power (P)
Inductive reactive power (QL)
Capacitive reactive power (QC)
Apparent power (S)
Power factor (Cos )
Maximum demand ( I )
Maximum demand (P)
Maximum demand (S)
Frequency
THD Current
THD Voltage
Import active energy (EP+)
Import capacitive react. energy (EQC+)
Import inductive react. energy (EQL+)
Import apparent energy (ES+)
Export active energy (EP-)
Export capacitive react. energy (EQC-)
Export inductive react. energy (EQL-)
Export apparent energy (ES-)
V
V
A
kW
kvar
kvar
kVA
PF
A
kW
kVA
Hz
A
V
kWh
kvarh
kvarh
kVAh
kWh
kvarh
kvarh
kVAh
TOTAL
15th
15th
MODEL
LAB96
MODEL
LAB96
- LAB96-B
- LAB96-BA
Basic model.
Basic model.
Current insulated.
Basic model.
Current insulated.
RS 485 Serial port.
1 Relay.
- LAB96-CH
LAB96-C
Harmonic measuring.
(up to 15)
LAB96-C
Universal auxiliary power supplied.
- LAB96-C
NA-12
AR-04
- LAB96-U
Analyzers
GENERAL
GENERAL FEATURES
SETTING
-
Case material
UL94 V0
Dimensions
Terminals
Pluggable
2,5 mm
Weight
0,4 kg
IP 51 Frontal
Protection
IP 31 terminals
Type:
Connection:
Protocol:
Baud rate:
RS 485.
2 wire.
MODBUS RTU.
Programmable.
300 - 19200 Bauds.
Standard 9600 Bauds.
Category III
ACCESSORIES
- x/5 A or x/1 A transformers.
- RS232/RS485 converters.
- RS 485 ampliers.
OPTIONAL
- Management software SACIgest.
- Reading software (without additional cost).
OVERLOAD
-
Electrical safety
DISPLAY
2 Vn x 10 s.
1,2 Vn permanent.
20 In x 1 s.
2 In permanent.
TECHNICAL SPECIFICATIONS
ACCURACY
INPUT
3-Phase, 3 or 4 wire,balanced or unbalanced
Rated Voltage (Un)
Burden
< 0,7 VA
5A
Burden
< 0,75 VA
Operating range
0 - 110 % In
Frequency
45-65 Hz
Parameter
Operating
range
Accuracy
Voltage
Current
Active power
Reactive power
Apparent power
Power factor
Frequency
Active energy
Reactive energy
10-100%
10-100%
10-100%
10-100%
10-100%
0,5 - 1
45-65Hz
10-100%
10-100%
0,5 2 digits
0,5 2 digits
1% 2 digits
1% 2 digits
1% 2 digits
6
0,2% 2 digits
1% 2 digits
1% 2 digits
Type
24 V D.C. 50 mA
*Contact output can be set as max. or min. alarm contacts
associated to a measured parameter, or as active energy and
reactive energy pulses.
AUXILIARY VOLTAGE
CONNECTIONS
3 x 230 (400) V Aux. V.
3x/5 A
+
Aux. V. AC.
20 21
50-60Hz
L1
Aux. V. A.C.
230 V
Burden
5 VA
Operating range
85-110 % Un
Universal Aux. V.
Burden
5 VA
Frequency
50-60 Hz
RS485
12 13 L+ L- GND
L
L2
L3
l
2
8 11
k
3
k
6
k
9
CT-05
NA-13
AR-05
NETWORK ANALYZERS
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
NETWORK ANALYZER - LABM
Instrument with microprocessor, programmable, LCD display indicating three
measurements, and built-in keypad.
GENERAL FEATURES
ELECTRICAL PARAMETER
SYMBOL
L1
L2
L3
TOTAL
Voltage (Line-to-neutral)
Voltage (Line-to-Line)
Current and neutral current
Active power (P)
Inductive reactive power (QL)
Capacitive reactive power (QC)
Apparent power (S)
Power factor (Cos )
Maximum demand ( I )
Maximum demand (P)
Maximum demand (S)
Frequency
THD Current
THD Voltage
Import active energy (EP+)
Import capacitive react. energy (EQC+)
Import inductive react. energy (EQL+)
Import apparent energy (ES+)
Export active energy (EP-)
Export capacitive react. energy (EQC-)
Export inductive react. energy (EQL-)
Export apparent energy (ES-)
V
V
A
kW
kvar
kvar
kVA
PF
A
kW
kVA
Hz
A
V
kWh
kvarh
kvarh
kVAh
kWh
kvarh
kvarh
kVAh
15th
15th
MODEL
LABM
MODEL
LABM
- LABM-B
- LABM-BA
Basic model.
Basic model.
Current insulated.
Basic model.
Current insulated.
RS 485 Serial port.
1 Relay.
- LABM-CH
LABM-C
Harmonic measuring.
(up to 15)
LABM-C
Universal auxiliary power supplied.
- LABM-C
NA-14
AR-04
- LABM-U
Analyzers
GENERAL
GENERAL FEATURES
Case material
UL94 V0
Dimensions
3 modules, 52,5 x 85 mm
Terminals
Pluggable
2,5 mm
Weight
0,21 Kg
SETTING
-
IP 41 Frontal
Protection
IP 20 Terminals
Type:
Connection:
Protocol:
Baud rate:
RS485.
2 wire.
MODBUS RTU.
Programmable.
300 - 19200 Bauds.
Standard 9600 Bauds.
OVERLOAD
-
2 Vn x 10 s.
1,2 Vn permanent.
20 In x 1 s.
2 In permanent.
Electrical safety
Category III
ACCESSORIES
- x/5 A or x/1 A transformers.
- RS232/RS485 converters.
- RS 485 ampliers.
OPTIONAL
- Management software SACIgest.
- Reading software (without additional cost).
DISPLAY
- Maximum and minimum values of: V1, V2, V3, V 12, V23,
V31, I1, I2, I3, P, Q, S, Cos and Hz.
TECHNICAL SPECIFICATIONS
ACCURACY
INPUT
Three-phase, 3 or 4 wire, balanced or unbalanced
Rated Voltage (Un)
Parameter
Operating
range
Accuracy
Voltage
Current
Active power
Reactive power
Apparent power
Power factor
Frequency
Active energy
Reactive energy
20-120%
1-120%
1-120%
1-120%
1-120%
0,5%
45-65Hz
5-120%
5-120%
0,3%(read.+full sca.)
0,3%(read.+full sca.)
0,3%(read.+full sca.)
0,3%(read.+full sca.)
0,4%(read.+full sca.)
1%(F.S)
0,2%(F.S)
0,5% reading
1% reading
Burden
0,7 VA
Burden
0,9 VA
Operating range
0- 110 % In
Frequency
50-60 Hz
CONEXIONES
Type
24 V DC. 50 mA
CONNECTIONS
10 11 12 13 14 15
Aux. V
GND L- L+
10 11 12 13 14 15
1 2 3 4 5 6 7 89
AUXILIARY VOLTAGE
1 2 3 4 5 6 7 89
Aux. V. A.C.
230 V
Burden
5 VA
Operating range
85-110 % Un
Universal Aux. V.
Burden
5 VA
Frequency
50-60 Hz
RS 485
L1
L2
L3
N
L k
K
3 x 230 (400) V
3x/5 A
Aux. V AC.
50-60Hz
l
L k
CT-05
NA-15
AR-05
NETWORK ANALYZERS
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
NETWORK ANALYZER - AR3AC
Programmable instrument with microprocessor and LCD display indicator for
measurements.
GENERAL FEATURES
MODEL
ELECTRICAL PARAMETER
SYMBOL
TOTAL
Voltage (Line-to-neutral)
Current
Active power (P)
Reactive power (Q)
Apparent power (S)
Power factor (Cos )
Frequency
Import active energy (EP+)
Export active energy (EP-)
Inductive reactive energy (EQ+)
Capacitive reactive energy (EQ-)
V
A
kW
kvar
kVA
PF
Hz
kWh
kWh
kvarh
kvarh
AR3AC
SETTING
-
SERIAL PORT
- Type:
- Protocol:
- Baud rate:
- Max. N of instruments per line:
RS 485.
MODBUS RTU.
Optional.
Standard 9600 Bauds.
32.
LCD DISPLAY
The equipment is set through the serial port.
- 1 LCD display (4 digits + sign).
- Height of digits: 8 mm.
- Up to 11 measuring parameters.
NA-16
AR-04
Analyzers
TECHNICAL SPECIFICATIONS
GENERAL
INPUT
GENERAL FEATURES
230 V AC.
Mounting
Burden
1 mA
Case material
ABS,UL94 V0
Operating range
20-120 % Un.
Dimensions
DIN rail
1 or 5 A
Terminals
With screws
Direct connection
30 A AC.
16 mm
x/5 A
Weight
0,15 Kg
Operating range
1-120 % In
Temperature range
-10...60 C
IP 54 Frontal
Protection
IP 20 Terminals
CONTACTS OUTPUT *
Number of outputs
Electrical safety
Category III
Optocoupler
Type
48 V DC 10 mA
OVERLOAD
-
2 Vn x 10 s.
1,2 Vn permanent.
20 In x 1 s.
2 In permanent.
ACCURACY
AUXILIARY VOLTAGE
Aux. V. AC.
Self supplied
ACCESSORIES
- x/5 A or x/1 A transformers.
- RS232/RS485 converters.
- RS 485 ampliers.
OPTIONAL
- Reading software (without additional cost).
- Management software SACIgest.
CONNECTIONS
Parameter
Operating
range
Accuracy
Voltage
Current
Active power
Reactive power
Apparent power
Power factor
Frequency
Active energy
Reactive energy
80-120%
1-120%
1-120%
1-120%
1-120%
0,5%
45-65Hz
5-120%
5-120%
0,5%(read.+full sca.)
0,5%(read.+full sca.)
0,5%(read.+full sca.)
0,5%(read.+full sca.)
0,5%(read.+full sca.)
1%(F.S)
0,2%(F.S)
1% reading
2% reading
< 30 A
P1/K
P2/L
L
RS 485
s1/k
COM L- L+
s2/l
1
30 31 32
10
11
CT-05
NA-17
AR-05
NETWORK ANALYZERS
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
NETWORK ANALYZER
- LCAM
ANALIZADOR
DE RED - LCAM
Programmable
instrument
with microprocessor
, LCD
display indicating three
Instrumento con
microprocesador,
programable,
display
measurements,
and built-in
keypad.
LCD con indicacin
de tres
medidas, y teclado integrado.
GENERAL FEATURES
ELECTRICAL PARAMETER
SYMBOL
L1
L2
L3
Voltage (Line-to-neutral)
Voltage (Line-to-Line)
Current
Active power (P)
Reactive power (Q)
Apparent power (S)
Power factor (Cos )
Frequency
Import active energy (EP+)
Export active energy (EP-)
Import inductive reactive energy (EQL+)
Import capacitive reactive energy (EQC+)
V
V
A
kW
kvar
kVA
PF
Hz
kWh
kWh
kvarh
kVAh
(*)
(*)
(*)
TOTAL
MODEL
- LCAM-BA
MODELO
- LCAM-C
LCAM
Basic model.
Current insulated.
Basic model.
Current insulated.
RS 485 Serial port.
2 Relays.
- Type:
- Protocol:
- Baud rate:
RS 485.
MODBUS RTU.
Programmable.
300 - 19200 Bauds.
- Max. N of instruments per line:
32.
- Max. length of system per line (without amplier):
1250 m.
SETTING
LCD DISPLAY
-
NA-18
AR-04
Analyzers
TECHNICAL SPECIFICATIONS
GENERAL
INPUT
GENERAL FEATURES
Mounting
Burden
1 mA per phase
Case material
ABS,UL94 V0
Operating range
20-120 % Un.
Dimensions
1 or 5 A
Terminals
With screws
Burden
16 mm
Operating range
1 - 120 % In
Weight
0,15 Kg
Frequency
50 or 60 Hz
Temperature range
-10...60 C
IP 54 Frontal
Protection
OVERLOAD
-
DIN rail
IP 20 Terminals
2 Vn x 10 s.
1,2 Vn permanent.
20 In x 1 s.
2 In permanent.
Electrical safety
Category III
ACCESORIES
CONTACTS OUTPUT *
Number of outputs
2
Relay N.O.
Type
250 V, 3 A
* Contact output can be set as max. or min. alarm contacts
associated to any measured parameter, or as energy pulses.
They can also be set as contacts managed from the central unit.
OPTIONAL
- Reading software (without additional cost).
- Management software SACIgest.
AUXILIARY VOLTAGE
Aux. V. A.C.
63,5/110 V or 230/400 V
Operating range
80-120% Un
Aux. V. C.C
18 - 72 V
Burden
3 VA
CONNECTIONS
3 x 230 (400) V
3x/5 A
Aux. V. AC.
50-60Hz
Aux. V.
Aux. V.
Relays
RS485
RL 1 R L0
L+ L- COM
- Maximum and minimum values of: V12, V23, V31, I1, I2,
I3, P, Q, S, Cos and Hz.
23 24 25
26
27 28
ACCURACY
L1
Parameter
Operating
range
Accuracy
L2
Voltage
Current
Active power
Reactive power
Apparent power
Power factor
Frequency
Active energy
Reactive energy
20-120%
1-120%
1-120%
1-120%
1-120%
0,5%
45-65Hz
5-120%
5-120%
0,3%(read.+full sca.)
0,3%(read.+full sca.)
0,3%(read.+full sca.)
0,3%(read.+full sca.)
0,5%(read.+full sca.)
0,6%(F.S)
0,2%(F.S)
1% reading
2% reading
L3
N
k
2
8 11
l
3
k
4
l
6
l
7
CT-05
NA-19
AR-05
NETWORK ANALYZERS
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
NETWORK ANALYZER - LDA 144
Programmable instrument with microprocessor , LCD display indicating three
measurements, and built-in keypad.
GENERAL FEATURES
ELECTRICAL PARAMETER
SYMBOL
L1
L2
L3
Voltage (Line-to-neutral)
Voltage (Line-to-Line)
Current
Neutral current
Active power (P)
Reactive power (Q)
Apparent power (S)
Power factor (Cos )
Maximum demand (I)
Maximum demand (P)
Maximum demand (Q)
Maximum demand (S)
Frequency
THD Current
THD Voltage
Import active energy (EP+)
Export active energy (EP-)
Import reactive energy (EQ+)
Export reactive energy (EQ-)
V
V
A
A
kW
kvar
kVA
PF
A
kW
kvar
kVA
Hz
A
V
kWh
kWh
kvarh
kvarh
MODEL
LDA 144
SETTING
- LDA 144-BA
Basic model.
Current insulated.
Current insulated.
RS 485 Serial port.
2 Relays.
- LDA 144-C
NA-20
AR-04
TOTAL
RS485.
MODBUS RTU.
Programmable.
Standard 9600 Bauds.
Analyzers
GENERAL
TECHNICAL SPECIFICATIONS
INPUT
3-Phase, 4wire, unbalanced
Rated Voltage (Un)
Burden
1 mA per phase
Operating range
20-120 % Un.
1 or 5 A
Burden
Operating range
1- 120 % In
Frequency
50-60 Hz
GENERAL FEATURES
Iluminacin de Display
posterior.
Material
envolvente
ABS, UL94 V0.
Display lighting
Back (optional)
Dimensiones
DIN 96 x 96 x 49 mm.
Case material
Metal+ABS, UL94
V0
Conexiones
Enchufables.
Dimensions
Mx. seccin
del hilo
Peso Connection
Proteccin
Max. wire section
Opcional
Weight
Seguridad elctrica (EN 61010)
Protection
Electrical safety
OVERLOAD
(Frontal).
IP0,85
65 con
kg tapa frontal.
Clase 2.
IP 54 Frontal
Categora III.
IP 20 Terminals
Category III
2 Vn x 10 s.
1,2 Vn permanent.
20 In x 1 s.
2 In permanent.
ACCESSORIES
2
Relay N.O.
Type
250 V, 3 A
* Contact output can be set as max. or min. alarm contacts
associated to any measured parameter, or as active energy and
reactive energy pulses. They can also be set as contacts
managed from the central unit.
AUXILIARY VOLTAGE
Aux. V. A.C.
63,5/110 V or 230/400 V.
Burden
3 VA
Operating range
80-120 % Un
Aux. V. D.C.
18-72 V
Burden
3W
Universal Aux. V.
85/264 V A.C.;90/300 V DC
Burden
5 VA
OPTIONAL
- Reading software (without additional cost).
- Management software SACIgest.
DISPLAY
-
CONNECTIONS
ACCURACY
Parameter
Operating
range
Accuracy
Voltage
Current
Active power
Reactive power
Apparent power
Power factor
Frequency
Active energy
Reactive energy
20-120%
1-120%
1-120%
1-120%
1-120%
0,5%
45-65Hz
5-120%
5-120%
0,3%(read.+full sca.)
0,3%(read.+full sca.)
0,3%(read.+full sca.)
0,3%(read.+full sca.)
0,5%(read.+full sca.)
0,6% reading
0,2%(rated freq.)
1% reading
2% reading
3 x 230 (400) V
3x/5 A
Aux. V. AC
50-60 Hz
CT-05
NA-21
AR-05
NETWORK ANALYZERS
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
NETWORK ANALYZER - LDA 144 with memory
Programmable instrument with microprocessor , LCD display indicating three
measurements, and built-in keypad.
GENERAL FEATURES
ELECTRICAL PARAMETER
SYMBOL
L1
L2
L3
Voltage (Line-to-neutral)
Voltage (Line-to-Line)
Current
Neutral current
Active power (P)
Reactive power (Q)
Apparent power (S)
Power factor (Cos )
Maximum demand (I)
Maximum demand (P)
Maximum demand (Q)
Maximum demand (S)
Frequency
THD Current
THD Voltage
Import active energy (EP+)
Export active energy (EP-)
Import reactive energy (EQ+)
Export reactive energy (EQ-)
V
V
A
A
kW
kvar
kVA
PF
A
KW
kvar
kVA
Hz
A
V
kWh
kWh
kvarh
kvarh
TOTAL
ROTATING MEMORY
The equipment is equipped with a rotating memory to store the following values:
1 - FIXED
2 - PROGRAMMABLE
Up to 4 alarms can be set and saved. These can be dened as maximum or minimum , as % of the rated value and
measurement variable. Alarm data is recorded with satrt time, length and variable affected.
NA-22
AR-04
Analyzers
MODEL
LDA 144
SETTING
- LDA 144-M
Current insulated.
RS 485 Serial port.
2 Relays
SERIAL PORT
- Type:
- Protocol:
- Baud rate:
TECHNICAL SPECIFICATIONS
INPUT
RS485.
MODBUS RTU.
Programable.
Standard 9600 Bauds.
9600 Bauds.
GENERAL
Burden
1 mA per phase
Display lighting
Back (optional)
Operating range
20-120 % Un.
Case material
Metal+ABS, UL94 V0
1 or 5 A
Dimensions
Burden
Connection
Pluggable
Operating range
1- 120 % In
Frequency
50-60 Hz
Weight
2,5 mm
0,85 kg
Protection
IP 20 Terminals
Electrical safety
Relay N.O.
250 V, 3 A
IP 54 Frontal
ACCESSORIES
OVERLOAD
OPTIONAL
2 Vn x 10 s.
1,2 Vn permanent.
20 In x 1 s.
2 In permanent.
DISPLAY
AUXILIARY VOLTAGE
Aux. V. A.C.
63,5/110 V or 230/400 V.
Burden
3 VA
Operating range
80-120 % Un
Aux. V. D.C
18-72 V
Burden
3W
Universal Aux. V.
85/2654 V AC.;90/300 V DC
Burden
5 VA
CT-05
NA-23
AR-05
NETWORK ANALYZERS
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
CONNECTIONS
ACCURACY
Parameter
Voltage
Current
Active power
Reactive power
Apparent power
Power factor
Frequency
Active energy
Reactive energy
Operating
range
Accuracy
20-120%
1-120%
1-120%
1-120%
1-120%
0,5%
45-65Hz
5-120%
5-120%
0,3%(read.+full sca.)
0,3%(read.+full sca.)
0,3%(read.+full sca.)
0,3%(read.+full sca.)
0,5%(lect.+n esc.)
0,6% reading
0,2%(rated freq.)
1% reading
2% reading
L1
L2
3 x 230 (400) V
3x/5 A
Aux. V. AC.
50-60Hz
L3
Rels
R L0 R L1
l
7
14 15 16
L2
L3
L1
N
V. Aux.
V.
RS 232
RS232
8 10 11 12 13 Aux.
RD
TD
GND
RD
RS 485
5
9
TD
NA-24
AR-04
GND
LL+
COM
Analyzers
SACI
NETWORK ANALYZERS
ANALIZADORES
NETWORK ANALYZERS
DE RED
NETWORK ANALYZER - SNG96
Programmable instrument with microprocessor and LCD display indicator for
measurements and built-in keypad.
GENERAL FEATURES
ELECTRICAL PARAMETER
SYMBOL
L1
L2
L3
Voltage (Line-to-neutral)
Voltage (Line-to-Line)
Current
Maximum demand (I)
Import active energy (EP+)
Export active energy (EP-)
V
V
A
A
kWh
kWh
MODEL
SNG96
GENERAL
GENERAL FEATURES
TECHNICAL SPECIFICATIONS
INPUT
ENTRADA
400 V
Burden
1 mA per phase
Operating range
50-600 V
5A
Burden
Operating range
0- 120 % In
Frequency
45-65 Hz
AUXILIARY VOLTAGE
Case material
ABS,UL94 V0
Dimensions
DIN 96 x 96 mm
Terminals
Pluggable
2,5 mm
Weight
0,4 Kg
Protection
IP 20 Terminals
Optional protection
IP 54 Frontal
IP 65 with frontal cover
Electrical safety
ACCESSORIES
AUXILIARY VOLTAGE
.
TOTAL
Aux. V. AC.
Self supplied
Burden
< 4 VA
SETTING
- Primary current.
- Integration time of maximum demand.
- x/5 A transformers.
DISPLAY
- LCD display built-in keypad (5 Keys)
- Selectable pages with up () and down ().
- Back lighting.
OVERLOAD
-
2 Vn x 10 s.
1,2 Vn permanent.
20 In x 1 s.
2 In permanent.
CT-05
NA-25
AR-05
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
CONNECTIONS
ACCURACY
Parameter
Operating
range
Accuracy
Voltage
Current
Active energy
Reactive energy
20-120%
1-120%
5-120%
5-120%
0,3%(read.+full sca.)
0,3%(read.+full sca.)
0,5% reading
1% reading
NA-26
AR-04
50-600 V
x/5 A
45-65 Hz
Analyzers
SACI
NETWORK ANALYZERS
ANALIZADORES
NETWORK ANALYZERS
DE RED
NETWORK ANALYZER - MAR96
Instrument with microprocessor, programmable, with three LED display
indicating measurements and built-in keypad.
GENERAL FEATURES
DIN 96 x 96 INSTRUMENT
MEASUREMENT IN 4 QUADRANTS
THREE- PHASE, 4 WIRE
MAX. and MIN. VALUES
TRUE RMS
RS232/RS 485 SERIAL PORTS
2 CONTACTS OUTPUT
4 DIGITAL INPUTS
ELECTRICAL PARAMETER
SYMBOL
L1
L2
L3
Voltage (Line-to-neutral)
Voltage (Line-to-Line)
Current
Active power (P)
Reactive power (Q)
Apparent power (S)
Power factor (Cos )
Frequency
Import active energy (EP+)
Export active energy (EP-)
Inductive reactive energy (Eq+)
Capacitive reactive energy (Eq-)
V
V
A
kW
kvar
kVA
PF
Hz
kWh
kWh
kvarh
kvarh
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
TOTAL
(*)
MODEL
MAR96
SERIAL PORT
- MAR96
- MAR96-I
- MAR96-II
- MAR96-3
Single-phase.
Three-phase, 3 wire, balanced.
Three-phase, 3 wire, unbalanced.
Three-phase, 4 wire, unbalanced.
Current insulated.
2 Relays.
SETTING
-
Type:
Protocol:
Connection:
Baud rate:
RS 485.
MODBUS RTU.
2 or 4 wire.
Programmable.
300 - 19200 Bauds.
Standard 9600 Bauds.
- Max. N of instruments per line:
32.
- Max length of system per line (without amplier): 1250 m.
(On request RS 232 serial port).
LED DISPLAY
-
CT-05
NA-27
AR-05
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
GENERAL
4 DIGITAL INPUTS
Digital inputs can be used to:
GENERAL FEATURES
TECHNICAL SPECIFICATIONS
INPUT
Rated Voltage (Un)
Burden
1 mA per phase
Operating range
20-120 % Un
1 or 5 A
Burden
Operating range
1- 120 % In
Frequency
50 - 60 Hz
Case material
ABS,UL94 V0
Dimensions
DIN 96 x 96 mm
Terminals
Pluggable
2,5 mm
Weight
0,6 Kg
Protection
IP 20 Terminals
IP 54 Frontal
Optional protection
Electrical safety
Category III
ACCESSORIES
- x/5 A or x/1 A transformers.
- RS232/RS485 converters.
- RS 485 ampliers.
CONTACTS OUTPUT *
OPTIONAL
Number of outputs
Type
OVERLOAD
-
2 Vn x 10 s.
1,2 Vn permanent.
20 In x 1 s.
2 In permanent.
AUXILIARY VOLTAGE
Aux. V. A.C.
Burden
6 VA
Operating range
80-120 % Un
CONNECTIONS
3 x 230 (400) V
3x/5 A
Aux. V. AC.
50-60 Hz
Relays
NA-28
AR-04
Digital inputs
ACCURACY
Parameter
Operating
range
Accuracy
Voltage
Current
Active power
Reactive power
Apparent power
Power factor
Frequency
Active energy
Reactive energy
20-120%
1-120%
1-120%
1-120%
1-120%
0,5
45-65 Hz
5-120%
5-120%
0,2%(read.+full sca.)
0,2%(read.+full sca.)
0,2%(read.+full sca.)
0,2%(read.+full sca.)
0,4%(read.+full sca.)
0,4% reading
0,2%(rated freq.)
1% reading
2% reading
Analyzers
SACI
NETWORK ANALYZERS
ANALIZADORES
NETWORK ANALYZERS
DE RED
NETWORK ANALYZER - MAR144
Instrument with microprocessor, programmable, with three LED display
indicating measurements and built-in keypad.
GENERAL FEATURES
ELECTRICAL PARAMETER
SYMBOL
L1
L2
L3
TOTAL
Voltage (Line-to-neutral)
Voltage (Line-to-Line)
Current
Active power (P)
Reactive power (Q)
Apparent power (S)
Power factor (Cos )
Frequency
Consumed active energy (EP+)
Generated active energy (EP-)
Inductive reactive energy (Eq+)
Capacitive reactive energy (Eq-)
V
V
A
kW
kvar
kVA
PF
Hz
kW-h
kW-h
kvar-h
kvar-h
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
(*)
MODEL
MAR144
- MAR144-BA
Basic model.
Current insulated.
Single-phase
Three-phase, 3 wire, balanced.
Three-phase, 3 wire, unbalanced.
Three-phase, 4 wire, unbalanced.
Current insulated.
2 Relays
Barden insulated (optional)
- MAR144
- MAR144-I
- MAR144-II
- MAR144-3
Type:
Protocol:
Connection:
Baud rate:
RS 485.
MODBUS RTU.
2 or 4 wire.
Programmable.
300 - 19200 Bauds.
Standard 9600 Bauds.
- Max. N of instruments per line:
32.
- Max length of system per line (without amplier):
1250 m.
(On request RS 232 serial port).
SETTING
LED DISPLAY
CT-05
NA-29
AR-05
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
4 DIGITAL INPUTS (Optional)
Digital inputs can be used to:
AUXILIARY VOLTAGE
Aux. V. AC.
63,5/110 V or 230/400 V
Burden
6 VA
Operating range
80-120 % Un
Aux. V. DC.
18-72 V
Burden
3W
UNIVERSAL Aux. V.
Burden
4 VA
1.
4-20 mA.
programmable.
GENERAL
GENERAL FEATURES
TECHNICAL SPECIFICATIONS
INPUT
Case material
Metal+ABS,UL94V0
Dimensions
Terminals
Pluggable
2,5 mm
Weight
0,75 Kg
Protection
IP 20 Terminals
Burden
1 mA per phase
Optional protection
Operating range
20-120 % Un
1 or 5 A
Burden
Operating range
1- 120 % In
Frequency
50 - 60 Hz
IP 54 Frontal
(EN 61010) Class 2
Electrical safety
Category III
ACCESSORIES
- x/5 A or x/1 A transformers.
- RS232/RS485 converters.
- RS 485 ampliers.
CONTACTS OUTPUT *
OPTIONAL
Number of outputs
Type
OVERLOAD
-
2 Vn x 10 s.
1,2 Vn permanent.
20 In x 1 s.
2 In permanent.
CONNECTIONS
ACCURACY
3 x 230 (400) V
3x/5 A
Aux. V AC.
50-60 Hz
Relays
Aux. V.
NA-30
AR-04
Parameter
Operating
range
Accuracy
Voltage
Current
Active power
Reactive power
Apparent power
Power factor
Frequency
Active energy
Reactive energy
20-120%
1-120%
1-120%
1-120%
1-120%
0,5
45-65 Hz
5-120%
5-120%
0,2%(read.+full sca.)
0,2%(read.+full sca.)
0,2%(read.+full sca.)
0,2%(read.+full sca.)
0,4%(read.+full sca.)
0,4% reading
0,2%(rated freq.)
1% reading
2% reading
Analyzers
SACI
NETWORK ANALYZERS
ANALIZADORES
NETWORK ANALYZERS
DE RED
NETWORK ANALYZER - MDA96
Instrument with microprocessor, programmable, with three LED display
indicating measurements and built-in keypad.
GENERAL FEATURES
DIN 96 x 96 INSTRUMENT
MEASUREMENT IN 4 QUADRANTS
THREE-PHASE, 4 WIRE
NEUTRAL CURRENT
HARMONIC DISTORTION (THD V and I)
MAXIMUM DEMAND, A, kW, kVA, kvar
MAX and MIN VALUES
TRUE RMS
RS232/RS 485 SERIAL PORT
2 CONTACTS OUTPUT
ELECTRICAL PARAMETER
SYMBOL
L1
L2
L3
Voltage (Line-to-neutral)
Voltage (Line-to-Line)
Current
Neutral current
Active power (P)
Reactive power (Q)
Apparent power (S)
Power factor (Cos )
Maximum demand (I)
Maximum demand (P)
Maximum demand (Q)
Maximum demand (S)
Frequency
THD Current
THD Voltage
Consumed active energy (EP+)
Generated active energy (EP-)
Inductive reactive energy (Eq+)
Capacitive reactive energy (Eq-)
V
V
A
A
kW
kvar
kVA
PF
A
kW
kvar
kVA
Hz
A
V
kWh
kWh
kvarh
kvarh
MODEL
MDA96
SERIAL PORT
- MDA96-BA
Basic model.
Current insulated.
Current insulated.
RS 485 Serial port.
2 Relays.
- MDA96-C
SETTING
-
TOTAL
Type:
Protocol:
Connection:
Baud rate:
RS 485.
MODBUS RTU.
2 or 4 wire.
Programmable.
300 - 19200 Bauds.
Standard 9600 Bauds.
- Max. N of instruments per line:
32.
- Max length of system per line (without amplier): 1250 m.
(On request RS 232 serial port).
CT-05
NA-31
AR-05
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
DISPLAY LED
LED DISPLAY
-
GENERAL FEATURES
Case material
Metal+ABS,UL94 V0
Dimensions
DIN 96 x 96 mm
Terminals
Pluggable
2,5 mm
Weight
0,6 Kg
Protection
IP 20 Terminals
IP 54 Frontal
Optional protection
IP 65 frontal cover
(EN 61010) Class 2
Electrical safety
TECHNICAL SPECIFICATIONS
Category III
INPUT
Rated Voltage (Un)
Burden
1 mA per phase
Operating range
20-120 % Un
1 or 5 A
Burden
Operating range
1- 120 % In
Frequency
50 - 60 Hz
OPTIONAL
- Reading software (without additional cost).
- Management software SACIgest.
CONTACTS OUTPUT *
ACCURACY
Number of outputs
Type
OVERLOAD
-
ACCESSORIES
2 Vn x 10 s.
1,2 Vn permanent.
20 In x 1 s.
2 In permanent.
AUXILIARY VOLTAGE
Aux. V. AC
63,5/110 V or 230/400 V
Burden
3 VA
Operating range
70-120 % Un
Aux. V. DC
18-72 V
Parameter
Operating
range
Accuracy
Voltage
Current
Active power
Reactive power
Apparent power
Power factor
Frequency
Active energy
Reactive energy
20-120%
1-120%
1-120%
1-120%
1-120%
0,5
45-65 Hz
5-120%
5-120%
0,3%(read.+full sca.)
0,3%(read.+full sca.)
0,3%(read.+full sca.)
0,3%(read.+full sca.)
0,5%(read.+full sca.)
0,6% reading
0,2%(rated freq.)
1% reading
2% reading
CONNECTIONS
Burden
3W
Universal Aux. V.
Burden
4 VA
3 x 230 (400) V
3x/5 A
Aux.V. A.C.
50-60 Hz
Relays
Aux. V.
NA-32
AR-04
Analyzers
SACI
NETWORK ANALYZERS
ANALIZADORES
NETWORK ANALYZERS
DE RED
NETWORK ANALYZER - MDA144
Instrument with microprocessor, programmable, with three LED display
indicating measurements and built-in keypad.
GENERAL FEATURES
ELECTRICAL PARAMETER
SYMBOL
L1
L2
L3
Voltage (Line-to-neutral)
Voltage (Line-to-Line)
Current
Neutral current
Active power (P)
Reactive power (Q)
Apparent power (S)
Power factor (Cos )
Maximum demand (I)
Maximum demand (P)
Maximum demand (Q)
Maximum demand (S)
Frequency
THD Current
THD Voltage
Consumed active energy (EP+)
Generated active energy (EP-)
Inductive reactive energy (Eq+)
Capacitive reactive energy (Eq-)
V
V
A
A
kW
kvar
kVA
PF
A
kW
kvar
kVA
Hz
A
V
kWh
kWh
kvarh
kvarh
MODEL
MDA144
SERIAL PORT
Current insulated.
RS 485 Serial port.
2 Relays.
Burden insulated (optional)
SETTING
Instrument identify code.
Primary voltage.
Primary current.
Contact operating mode.
Alarms.
Integration time.
TOTAL
Type:
Protocol:
Connection:
Baud rate:
RS 485.
MODBUS RTU.
2 or 4 wire.
Programmable.
300 - 19200 Bauds.
Standard 9600 Bauds.
- Max. N of instruments per line:
32.
- Max length of system per line (without amplier): 1250 m.
(On request, RS 232 serial port)
- Optional:
(1) Frontal connection of the back connector. (Copy of serial port)
(2) Independent serial port RS232C.
.
CT-05
NA-33
AR-05
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
4 DIGITAL INPUTS
Digital inputs can be used to:
AUXILIARY VOLTAGE
DIGITAL OUTPUTS
10 independent programmable relays, for assigning variables
and alarm setting.
ANALOGUE OUTPUT *
63,5/110 V or 230/400 V
Aux. V. AC.
Burden
4 VA
Operating range
80-120 % Un
Aux. V. DC.
18-72 V
Burden
5W
UNIVERSAL Aux. V.
Burden
4 VA
GENERAL
Number of outputs:
Type:
Moperating range:
(*) Voltage isolation needed.
1.
4-20 mA.
programmable.
GENERAL FEATURES
TECHNICAL SPECIFICATIONS
INPUT
Rated Voltage (Un)
Burden
1 mA per phase
Operating range
20-120 % Un
1 or 5 A
Burden
Operating range
1- 120 % In
Frequency
50 - 60 Hz
Case material
Metal+ABS,UL94 V0
Dimensions
Terminals
Pluggable
2,5 mm
Weight
0,75 Kg
Protection
IP 20 Terminals
Optional protection
IP 54
(EN 61010) Class 2
Electrical safety
Category III
LED DISPLAY
-
CONTACTS OUTPUT *
Number of outputs
Type
ACCESSORIES
- x/5 A or x/1 A transformers.
- RS232/RS485 converters.
- RS 485 ampliers.
OPTIONAL
OVERLOAD
ACCURACY
2 Vn x 10 s.
1,2 Vn permanent.
20 In x 1 s.
2 In permanent.
CONNECTIONS
3 x 230 (400) V
3x/5 A
Aux. V. AC
50-60 Hz
Relays
Aux. V.
NA-34
AR-04
Parameter
Operating
range
Accuracy
Voltage
Current
Active power
Reactive power
Apparent power
Power factor
Frequency
Active energy
Reactive energy
20-120%
1-120%
1-120%
1-120%
1-120%
0,5
45-65 Hz
5-120%
5-120%
0,2%(read.+full sca.)
0,2%(read.+full sca.)
0,2%(read.+full sca.)
0,2%(read.+full sca.)
0,4%(read.+full sca.)
0,4% reading
0,2%(rated freq.)
1% reading
2% reading
Analyzers
SACI
NETWORK ANALYZERS
ANALIZADORES
NETWORK ANALYZERS
DE RED
NETWORK ANALYZER - TCEM
Instrument with microprocessor, programmable, in DIN rail and LED display.
GENERAL FEATURES
ELECTRICAL PARAMETER
SYMBOL
L1
L2
L3
TOTAL
Voltage (Line-to-neutral)
Voltage (Line-to-Line)
Current
Active power (P)
Reactive power (Q)
Apparent power (S)
Power factor (Cos )
Frequency
Consumed active energy (EP+)
Generated active energy (EP-)
Inductive reactive energy (Eq+)
Capacitive reactive energy (Eq-)
V
V
A
kW
kvar
kVA
PF
Hz
kWh
kWh
kvarh
kvarh
TCEM
CONTACT OUTPUT
TCEM
TCEM-1
TCEM-2
TCEM-3
Single-phase.
Three-phase, 3 wire, balanced.
Three-phase, 3 wire, unbalanced.
Three-phase, 4 wire, unbalanced.
4 DIGITAL INPUTS
Digital inputs can be used to:
SETTING
-
SERIAL PORT
-
Type:
RS485.
Protocol:
MODBUS RTU.
Connection:
2 or 4 wire.
Baud rate:
9600 Bauds.
Max. N of instruments per line:
32.
Max length of system per line (without amplier):
1250 m.
(On request, RS 232 serial port)
CT-05
NA-35
AR-05
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
GENERAL
LED DISPLAY
- LED Display ( 4 Digits + Sign).
- Built-in keypad
- 12 consecutive displayed parameters by pressing the rotate
button.
GENERAL FEATURES
Modules
TECHNICAL SPECIFICATIONS
INPUT
Rated Voltage (Un)
Burden
1 mA per phase
Operating range
20-120 % Un
1 or 5 A
Burden
Operating range
1- 120 % In
Frequency
50 - 60 Hz
DIN rail
Case material
ABS,UL94 V0
Dimensions
9 modules 155 x 90 mm
Terminals
Pluggable
2,5 mm
Weight
0,65 Kg
Protection
IP 40
(EN 61010) Class 2
Electrical safety
Category III
ACCESSORIES
- x/5 A or x/1 A transformers.
- RS232/RS485 converters.
- RS 485 ampliers.
CONTACTS OUTPUT *
OPTIONAL
Number of outputs
Optocoupler
N.O. 5 - 48 V DC
Pulse length
100 ms
OVERLOAD
* Contact output can be set as pulse for active energy. It can also
be set as contacts managed from the central unit.
AUXILIARY VOLTAGE
Aux. V. AC.
Burden
6 VA
Operating range
80-120 % Un
2 Vn x 10 s.
1,2 Vn permanent.
20 In x 1 s.
2 In permanent.
CONNECTIONS
CONNECTIONS
3 x 230 (400) V
3x/5 A
Aux. V. A.C.
50 - 60 Hz
ACCURACY
Parameter
Voltage
Current
Active power
Reactive power
Apparent power
Power factor
Frequency
Active energy
Reactive energy
Operating
range
Accuracy
L1
20-120%
1-120%
1-120%
1-120%
1-120%
0,5
45-65 Hz
5-120%
5-120%
0,2%(read.+full sca.)
0,2%(read.+full sca.)
0,2%(read.+full sca.)
0,2%(read.+full sca.)
0,4%(read.+full sca.)
0,4% reading
0,2%(rated freq.)
1% reading
2% reading
L2
L3
N
k
1 2
RS485
L-
GND
L+
25 26 27
NA-36
AR-04
l
7
k
8
Aux. V.
10 11
20 21
Digital inputs
Pulses
12 13 14 15 16
17 18
COM A B
Analyzers
SACI
NETWORK ANALYZERS
ANALIZADORES
NETWORK ANALYZERS
DE RED
D.C. NETWORK ANALYZER - AR3DC
Instrument with microprocessor,programmable , LCD display, designed for
measuring variables in a network of low voltage DC.
GENERAL FEATURES
MODEL
ELECTRICAL PARAMETER
SYMBOL
TOTAL
Voltage
Current
Active power (P)
Consumed active energy (EP+)
Generated active energy (EP-)
Ampere Hour (+)
Ampere Hour (-)
Shunt rated current
V
A
kW
kWh
kWh
Ah+
AhIp
AR3DC
LCD DISPLAY
- LCD display (4 digits + Sign).
- Height of digits: 8 mm.
- Up to 8 measuring parameters.
SETTING
-
SERIAL PORT
-
Type:
Protocol:
Connection:
Baud rate:
Max N of instruments per line:
RS 485.
MODBUS RTU.
2 wire.
Standar 9600 Bauds.
32.
CT-05
NA-37
AR-05
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
GENERAL
TECHNICAL SPECIFICATIONS
INPUT
Rated Voltage (Un)
GENERAL FEATURES
Burden
Case material
ABS,UL94 V0
Operating range
80-120 % Un
Dimensions
3 modules 52 x 90 mm
Mounting
DIN rail
Terminals
With screws
16 mm
Weight
0,15 Kg
Operating range
1- 120 % In
Temperature range
0 - 40 C
Protection
IP 20 terminals
Optional protection
IP 54 frontal
Direct connection
Electrical safety
Category III
Number of outputs
Optocoupler
ACCESSORIES
* Contact output can be set as max. or min. alarm contacts
associated to any measured parameter, or as energy. They can
also be set as contacts managed from the central unit.
AUXILIARY VOLTAGE
Aux. V. D.C.
Self supplied
CONNECTIONS
OPTIONAL
- Reading software (without additional cost).
- Management software SACIgest.
- Connection negative to ground.
OVERLOAD
- 2 Vn x 10 s.
- 1,2 Vn permanent.
- 20 In x 1 s.
ACCURACY
NA-38
AR-04
Parameter
Operating
range
Accuracy
Voltage
Current
Active power
Active energy
Reactive energy
Ampere hour (+)
Ampere hour (-)
80-120%
1-120%
1-120%
1-120%
1-120%
1-120%
1-120%
0,5%(read.+full sca.)
0,5%(read.+full sca.)
0,5%(read.+full sca.)
1%(read.+full sca.)
1%(read.+full sca.)
1%(read.+full sca.)
1%(read.+full sca.)
Analyzers
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
NETWORK ANALYZERS
GENERAL FEATURES
MODEL
ELECTRICAL PARAMETER
SYMBOL
TOTAL
Voltage
Current
kW
kWh
kWh
Ah+
Ah-
Ip
TMCC
ANALOGUE OUTPUT
- Number of outputs:
- Type:
- Accepted measurement:
SETTING
-
1.
4-20 mA.
parameters.
LED DISPLAY
Type:
Protocol:
Connection:
Baud rate:
RS 485.
MODBUS RTU.
2 wire.
Optional.
Standard 9600 Bauds.
32.
CT-05
NA-39
AR-05
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
GENERAL
TECHNICAL SPECIFICATIONS
INPUT
Rated voltage (Un)
GENERAL FEATURES
Case material
ABS,UL94 V0
Burden
Dimensions
Operating range
20-120 % Un
Depth
88 mm
In / 60mV DC
Terminals
Pluggable
Operating range
1- 120 % In
16 mm
Type
Weight
0,72 Kg
Temperature range
0 - 40 C
Protection
IP 20 terminals
Optional protection
IP 54 frontal
(EN 61010) Class 2
Electrical safety
* Contact output can be set as max. or min. alarm contacts
associated to any measured parameter, or as energy. They can
also be set as contacts managed from the central unit.
Aux. V. DC
24 or 48 V (*)
Aux. V. AC
Universal Aux. V.
Burden
2,8 VA
Operating range
85-110 % Un
Frequency
50 or 60 Hz
OPTIONAL
2 Vn x 10 s.
1,2 Vn permanent.
20 In x 1 s.
2 In permanent.
ACCURACY
V-
V+ I+
5 6
Relays
R1 R0
I-
910
Aux. V
Aux. V
14 15 16
11
Aux. V. AC
13
Relays
R1 R0
Parameter
Operating
range
Accuracy
Voltage
Current
Active power
Active energy
Reactive energy
Ampere hour (+)
Amperio hour (-)
20-120%
1-120%
1-120%
1-120%
1-120%
1-120%
1-120%
0,5%(read.+full sca.)
0,5%(read.+full sca.)
0,5%(read.+full sca.)
1%(read.+full sca.)
1%(read.+full sca.)
1%(read.+full sca.)
1%(read.+full sca.)
14 15 16
Aux V. DC
RS 485
RS 232
NA-40
AR-04
OVERLOAD
CONNECTIONS
1 1 12 13
ACCESSORIES
- Shunts x/60mV.
- RS232/RS485 converters.
- RS 485 ampliers.
AUXILIARY VOLTAGE
Aux. V
Category III
RD
TD
GND
5
9
4
LL+
COM
Analyzers
NETWORK ANALYZERS
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
NETWORK QUALITY ANALYZER - TMCQ
Instrument with microprocessor, programmable, four-line LCD display and
integrated keyboard. It detects and records defects voltage supply network,
such as overvoltage or undervoltage, Dips and microcuts that exceeds
programmed limits.
GENERAL FEATURES
MODEL
TMCQ
- TMCQ II
- TMCQ 3
Three-phase, 3 wire
Three-phase, 4 wire
OPERATING MODE
The equipment measures the true effective value of the voltage
(RMS) of a three-phase system, taking 128 samples per period.
The measured values are compared with the predened upper
and lower values ( both programmable). If the values measured
are within the preset limits, they are not considered and therefore
not recorded. On the other hand, if the predened limits are
exceeded, the detection process begins, the event is classied
and measured, the detection process begins, the event is
classied and measured and once nished, data is saved in a
memory powered by a rechargeable battery.
SETTING
-
N.
Type.
Phase.
Date.
Time.
Length.
Maximum or minimum value.
Average value.
SERIAL PORT
-
Type:
RS485 (optional RS232).
Connections:
2 or 4 wire.
Protocol:
MODBUS RTU.
Standard baud rate:
9600 Bauds.
Insulation by optocoupler between output and
measurement inputs.
LCD DISPLAY
- 4 lines, 20 characters.
- Built-in keypad (5 keys)
- Allows recorded data to be displayed.
CT-05
NA-41
AR-05
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
ROTATING MEMORY
GENERAL
TECHNICAL SPECIFICATIONS
INPUT
GENERAL FEATURES
Case material
ABS,UL94 V0
Dimensions
Depth
88 mm
Terminals
Pluggable
2,5 mm
Weight
0,72 Kg
Temperature range
0 - 40 C
Burden
100,110,230 or 400 V DC
1mA per phase
Protection
IP 20 terminals
Operating range
0-150 % Un
Optional protection
IP 54 frontal
Electrical safety
Category III
AUXILIARY VOLTAGE
Self supplied in any of the three phases.
4 wire version
Self supplied between phases.
3 wire version
Burden
< 3 VA
Frequency
50 or 60 Hz
ACCESSORIES
- RS232/RS485 converters.
- RS 485 ampliers.
OPTIONAL
- Reading software (without additional cost).
- Management software SACIgest.
OVERLOAD
-
2 Vn x 10 s.
1,2 Vn permanent.
20 In x 1 s.
2 In permanent.
CONNECTIONS
CONNECTIONS
L1
L2
L3
N
L1
L2
L3
L1 L2 L3 N
L1 L2 L3
TMCQ-3
TMCQ-II
NA-42
AR-04
RD
TD
GND
RS 485
RS 232
RS 485
RS 232
5
9
4
LL+
COM
RD
TD
GND
5
9
4
LL+
COM
Analyzers
SACI
NETWORK ANALYZERS
ANALIZADORES
NETWORK ANALYZERS
DE RED
RS232/RS485 CONVERTER - IFR
IFR equipment converts the RS 232 standard levels to the corresponding levels
in the RS485 standard.
IFR converters allow a PC with RS232 to be connected to an RS485 bus.
RS232 drivers activations can be with RTS or automatically if this option has
been selected with internal bridges.
For the automatic option, data from the RS232 line activates the drivers.
When data transfer nishes, the IFR converters return to receive mode.
GENERAL FEATURES
MODEL
IFR
- IFR1
AUXILIARY VOLTAGE
2 WIRE.
1 serial port RS232.
1 Serial port RS485.
- IFRA3
- IFRA
2 or 4 wire.
Optically insulated.
1 serial port RS232.
1 Serial port RS485.
- IFR4
2 or 4 wire.
Optically insulated.
1 serial port RS232.
4 serial port RS485.
Aux. V. AC.
110 or 220 V.
Aux. V. DC.
12, 24 or 48 V
Burden
IFR1
3 VA
IFRA, IFR4
6 VA
IFRA
3W
GENERAL
GENERAL FEATURES
Case material
ABS,UL94 V0
Dimensions
TECHNICAL SPECIFICATIONS
IFR1
INPUT
Number of outputs
Type
(3 Modules), 52 x 90 mm.
IFRA3
(3 Modules), 52 x 90 mm.
IFRA
IFR4
Terminals
Pluggable
2,5 mm
Weight
Number of outputs
IFR1, IFRA, IFRA3
IFR4
Type
RS 485
Baud rate
300-76800 Bauds
IFR1-IFRA3
0,30 kg
IFRA
0,45 kg
IFR4
0,65kg
Mounting
DIN rail
OVERLOAD
-
2 Vn x 10 s.
1,2 Vn permanent.
20 In x 1 s.
2 In permanent.
CT-05
NA-43
AR-05
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
CONNECTIONS
RS-485 / RS-232
RS-485
RS-232
1 2 3 4 5 6 7 8 9
2 3
4 5
RTS
-
RTS
+
1 2
5 6 7 8 9
AUTO
GND
GND
RTS RD TD
RD
V.aux.
RS-232
TD
DSR
LA+
V.aux.
LA-
RTS
L+
IFR1
RS-485
RS-232
1
2 3
RD
TD
CTS
RS-485
RS-232
10 11 12 13 14 15 16 17 18
2 3
GND
4 5
RD
Aux. V
RTS DSR
TD
6 7
CTS
10 11 12 13 14 15 16 17 18
8 9
GND
LA+ LA-
L+ L-
RD
TD
RS-485
IFRA - (4 wire)
RS-232
1
RS-485
RS-485
10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 27 26
Aux. V
DTR
RTS
Aux. V
RTS DSR
L+ L-
RS-485
IFRA - (2 wire)
L-
RS-485
IFRA3 - (4 wire)
L- L+
GND
L+ L-
L+ L-
L+ L-
L+ L-
RS-485
RS-485
RS-485
RS-485
IFR4 - (2 wire)
RS-232
1
RD
TD
DTR
RTS
RS-485
RS-485
10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 27 26
LA3LA3+
LA2LA2+
LA1LA1+
LA4LA4+
Aux. V
GND
L+ L-
L+ L-
L+ L-
L+ L-
RS-485
RS-485
RS-485
RS-485
IFR4 - (4 wire)
NA-44
AR-04
Analyzers
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
NETWORK ANALYZERS
GENERAL FEATURES
MODEL
RT485
GENERAL
2 or 4 wire.
TECHNICAL SPECIFICATIONS
GENERAL FEATURES
300-76800 Baudios.
INPUT
Case material
ABS,UL94 V0
IFRA
Number of outputs
Terminals
Type
RS 485
0,45 kg
Mounting
DIN rail
LED indication
OUTPUT
Number of outputs
Rx4
Type
RS 485
Rx2
Baud rate
300-19200 Bauds
TX
Sent data
OVERLOAD
AUXILIARY VOLTAGE
A.C.
D.C.
2 Vn x 10 s.
1,2 Vn permanent.
20 In x 1 s.
2 In permanent.
CONNECTIONS
RS-485 (Imput)
RS-485 (Output)
12345
10 11 12 13 14
17 18
RA+ (LA+)
LA+
RS-485 (Input)
12 13 14
17 18
RB-(LA-)
LA-
RS-485 (Output)
34
Aux. V.
Aux. V
L+
COM
L-
Connection to 4 wire
L+
COM
COM
L-
T/RB-(L-)
T/RA+ (L+)
Connection to 2 wire
COM
T/RB-(L-)
T/RA+ (L+)
CT-05
NA-45
AR-05
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
ETHERNET CONVERTER - etherGATE
The etherGATE is a communications gateway used to convert the physical Ethernet
environment to serial RS-485 or RS-232 communications or vice versa in the
routing mode.
NE
GENERAL FEATURES
TECHNICAL SPECIFICATIONS
POWER CIRCUIT
Single-phase (A1 A2)
NETWORK INTERFACE
Type
Frequency
4763 Hz
Connector
RJ 45
Maximum consumption
4,67,5 V.A
Network protocols
Working temperature
-10 ..+ 60 C
SERIAL INTERFACE
MECHANICAL FEATURES
Case material
UL94 - V0 Plastic
IP 20.
Type
Transmission speed
Protection degree
Dimensions (mm)
Data bits
7, 8
Weight (g)
120 g
Parity
2.000 m
Stop bit
1 or 2
CONNECTIONS
Figure 1. Standard connection of serial equipment
NA-46
AR-04
Analyzers
SACI
NETWORK ANALYZERS
ANALIZADORES
NETWORK ANALYZERS
DE RED
CONNECTIONS
CT-05
NA-47
AR-05
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
MANAGEMENT SOFTWARE - SACIGEST
The SACIgest program is a system allowing the SACI terminals
installed on the net to be easily managed as graphs. The
electrical installation is grouped by sections, each of which
is displayed differently, in the way they are inserted in their
corresponding terminals.
A variable for each terminal can be monitored on the screen
and placed in an appropriate position on the graph.
The system includes the easy creation of virtual terminals
based on actual terminals by simply applying a denition
formula.
Given the possible inclusion of direct current analyzer
terminals, alternating current sections and direct current
sections can be created.
Terminal models handling the system are as follows:
MAR, TMC
MDA
LCA_, LDA_, LAB, ANG
TCEM,
CP2000, CP3000, CP4000
TMCQ
M1D, M2D, TCID, TCI, TCIV (*)
TMC-C TMCC-H
TTI
VIRTUAL
(*) Via TTI.
Pentium III
128 Mb
SVGA
Colour, 15 800 x 600
XP, Win , Vista, Win 8, 32 bits,
It must also have a serial port for the RS-232 - RS485 converter
connection (IFRxx Model). It can be phisically or through a
converter USB-RS232.
NA-48
AR-04
Analyzers
MANAGEMENT
- SACIGEST
SOFTWARE
DESOFTWARE
GESTIN - SACIGEST
Versions
Versiones
Sub-versions
There are also the following installation options for all of the
above mentioned versions:
- Normal: This is the normal installation with no limit on terminals.
CT-05
NA-49
AR-05
NETWORK ANALYZERS
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
MANAGEMENT SOFTWARE - SACIGEST
SOFTWARE - LCDA
SOFTWARE - REMREADER
SOFTWARE - MODEMCFG
This software allows to choose the optimal way to properly
operate with the network.
SOFTWARE - LCDAM
LCDAM software is designed to manage the more common
versions of LCA, LCAM, LCC, LCCM, LDA96, LDA144
and LDA144 with memory. This version can manage
different equipment on the system with the option to set
the communication speed and program it via modem. It
allows to manage any equipment connected to the rst four
communication ports on the PC.
Given that two identical modems do not exist and that not all
modems accept the same commands, this software has been
created to extract the existing conguration in Windows and to
recongure it. It is easy to assume that the modem has to be
installed previously using Windows to allow this conguration
software to receive its information.
NA-50
AR-04
Analyzers
NETWORK ANALYZERS
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
APPLICATION - APP FOR iPHONE - SACIGEST
W
NE
New APP for iPhone, SACIgest v1.0 with which making accuracte readings of SACI equipments of the
installation, is possible from anywhere in the world.
The new APP has 3 main screens
Network setup:
This menu is to congurate, the public IP address, the TCP port location Software SACIgest. and a
geographical place where facility is located.(Last one just to clarify)
Conguration:
In this menu, it will be necessary, SACI devices used in the installation and their MODBUS ID
identication.
Once accepted, the equipment must be identied within the application and you can visualize the
corresponding readings.
Download:
If the device is congured correctly, in this third screen will appear the corresponding readings in real
time.
It accepts as many devices as devices in the installation.
- SACIgest program is a system that allows management of SACI terminals installed on a network in a
simple and graphic way
The electrical installation is grouped by sections, each one with a different visualization, in which the
corresponding terminals are inserted.
Models of terminals managed by the system are:
Network analyzers:
ANG96
LCC, LCCM
LCA, LCAM, LDA, LDA144
LAB96, LABM
MAR96, MAR144
MDA96, MDA144
TCEM,TMCC, TMCQ
Measuring transducers
CP 2000, CP 3000, CP 4000...
CT-05
NA-51
AR-05
SACI
ANALIZADORES
NETWORK ANALYZERS
DE RED
ACCESSORIES - IP65 PROTECTION COVER
Protective cover IP 65 for panel mounting devices.
NE
GENERAL FEATURES
EASY ASSEMBLY.
PROTECCTION AGAINST BUMPS, SCRATCHES OR ANY
OTHER EXERNAL EXPOSURE, RAIN, LIQUIDS...
FULLY ADJUSTABLE.
AVAILABLE IN 2 STANDAD SIZES.
Model
Dimension
Ordering code
3V
96x96 mm
YVARSV193
4V
72x72 mm
YVARSV194
MOUNTING.
1- Insert the rubber into the device through the back area.
Then introduce the device into the panel hole intended, and help
yourself to him to bring the rubber at the front area of the device.
2- Fit the plastic cover from the front. The pressure between the
rubber, the device and the panel will make sure it is securely
attached
3- Hold the device to the panel with the corresponding xing
system.
1
- The device will be fully adjusted and protected. The material
composed it makes it completely waterproof against dust,
liquids ... avoiding the risk that may occur against rain or another
external exposures.
NA-52
AR-04
Analyzers