Vous êtes sur la page 1sur 165

Lionel Ng, LPBS - Low Voltage Products

Welcome To ABB
Technical Sharing Session
ABB Group
March 10, 2015 | Slide 1

Circuit Breakers
Standards Guidelines IEC 60947-2

Agenda

IEC 60947-2

Circuit Breaker Standard, for industrial application

Definitions for MCCBs and ACBs

Choice criteria based on rated and limit values

ABB Group
March 10, 2015 | Slide 3

Standard for LV apparatus

IEC 60947 Standard for industrial application

International Standard

IEC 60947

European Standard

EN 60947

IEC 60947-1

Part 1: General rules

IEC 60947-2

Part 2: Circuit breakers

IEC 60947-3

Part 3: Switch disconnectors

IEC 60947-4-1

Part 4: Contactors

IEC 60947-5-1

Part 5: Control circuit devices

IEC 60947-6-1

Part 6: Multifunction devices

IEC 60947-7-1

Part 7: Auxiliary materials

ABB Group
March 10, 2015 | Slide 4

IEC Standard definitions

Circuit Breaker - IEC 60947-2

A mechanical switching device capable of breaking, carrying and


making currents under normal circuit conditions and also making,
carrying, for a specified time, and breaking currents under specified
abnormal circuit conditions such as those of short-circuit.

BREAKING

Breaking Capacity

WITHSTAND

Short time withstand

MAKING

Making Capacity

ABB Group
March 10, 2015 | Slide 5

IEC Standard definitions

Switch Disconnector - IEC 60947-3

A mechanical switching device capable of breaking, making and


carrying currents under normal circuit conditions but only making and
carrying, for a specified time, currents under specified abnormal circuit
conditions such as those of short-circuit.

BREAKING

Breaking Capacity

WITHSTAND

Short time withstand

MAKING

Making Capacity

ABB Group
March 10, 2015 | Slide 6

IEC Standard definitions

Moulded case circuit breaker (MCCB): a circuit breaker having a supporting


housing of moulding insulating material, forming an integral part of the circuit
breaker (Tmax-XT).

ABB Group
March 10, 2015 | Slide 7

IEC Standard definitions


Air circuit breaker (ACB): a circuit breaker having a
supporting housing of moulding insulating material and a
metallic frame, forming an integral part of the circuit
breaker (Emax & Emax 2).

ABB Group
March 10, 2015 | Slide 8

Current limiting circuit breaker

Current limiting circuit breaker (IEC 60947-2 def. 2.3)

A circuit breaker with a break-time short enough to prevent the short-circuit


current from reaching its peak value.

A current-limiting circuit
breaker is able to reduce the
stress, both thermal and
dynamic, because it has been
designed to start the opening
operation before the shortcircuit current has reached its
first peak, and to quickly
extinguish the arc between the
contacts.

ABB Group
March 10, 2015 | Slide 9

Current limiting circuit breaker

A = Direction of arc due to the magnetic field


R= Repulsion of moving contacts due to the short circuit current

ABB Group
March 10, 2015 | Slide 10

Current limiting circuit breaker

Energy limitation
Current

Time

ABB Group
March 10, 2015 | Slide 11

Current limiting circuit breaker

Peak limitation curves


Value of the limited peak
of the short circuit current
according to the value of
the symmetrical short
circuit current Irms.

ABB Group
March 10, 2015 | Slide 12

Current limiting circuit breaker

I2t curves

Value of the let-through


energy according to the
value of the symmetrical
short circuit current Irms.

ABB Group
March 10, 2015 | Slide 13

Current limiting circuit breaker

Energy limitation
Protection against short-circuit (IEC 60364)
To protect a cable against short-circuit, the specific let-through energy of
the protective device must be lower or equal to the withstanding energy of
the cable:
Specific let through energy curve LLL

1E3MAs

100MAs

where
I2 t is the specific let-through energy of
the protective device which can be read on
the curves supplied by the manufacturer;
S is the cable cross section [mm2]; in the
case of conductors in parallel it is the
cross section of the single conductor;
k is a factor that depends on the cable
insulating and conducting material.

10MAs

1MAs

0.1MAs

1E-2MAs

0.1kA

ABB Group
March 10, 2015 | Slide 14

1kA

10kA

100kA

Choice criteria

Rated values (Iu, Ue)

Limit values (Icu, Ics, Icw, Icm)

ABB Group
March 10, 2015 | Slide 15

Insulation values (Ui, Uimp)

Rated value Iu

Rated uninterrupted current Iu


the rated uninterrupted current of an equipment is a value of
current, stated by the manufacturer, that the equipment can carry
in uninterrupted duty (at 40 C)

IEC 60947-1 def. 4.3.2.4

ABB Group
March 10, 2015 | Slide 16

Rated value Iu
The rated uninterrupted current Iu is different from the rated
current In, which is the rated current of the thermomagnetic or
electronic trip unit and is lower or equal to Iu.

A new concept
for setting the
current In: the
rating plug

ABB Group
March 10, 2015 | Slide 17

Rated value Iu

Rated uninterrupted current Iu


Some factors may reduce the Iu of a circuit breaker
like temperature, altitude or frequency.
XT1 160

XT4 250

ABB Group
March 10, 2015 | Slide 18

Rated value Ue

Rated operational voltage Ue


the rated operational voltage of an equipment is a value of voltage
which, combined with a rated operational current, determines the
application of the equipment and to which the relevant tests and
the utilization categories are referred.

IEC 60947-1 def. 4.3.1.1

ABB Group
March 10, 2015 | Slide 19

Rated value Ue

Rated operational voltage Ue


Breaking capacity is always referred to the operational voltage; the
breaking capacity decreases when the voltage increases.

ABB Group
March 10, 2015 | Slide 20

Rated value Ue

Some factors may reduce the Ue of a circuit breaker

ABB Group
March 10, 2015 | Slide 21

Choice criteria

Rated values (Iu, Ue)

Limit values (Icu, Ics, Icw, Icm)

ABB Group
March 10, 2015 | Slide 22

Insulation values (Ui, Uimp)

Limit value Icu


Icu = RATED ULTIMATE SHORT
CIRCUIT BREAKING CAPACITY

IEC 60947-2
def. 4.3.5.2.1

Breaking capacity according to a specified test sequence.


Do not include after the short circuit test, the capability of the
circuit breaker to carry its rated current continuously.
- test sequence: O - 3 min - CO
- dielectric withstand at 2 x Ue
- verification of overload release at 2.5 x I1

ABB Group
March 10, 2015 | Slide 23

Limit value Ics


Ics = RATED SERVICE SHORT
CIRCUIT BREAKING CAPACITY

IEC 60947-2
def. 4.3.5.2.2

Breaking capacity according to a specified test sequence.


Include after the short circuit test, the capability of the circuit
breaker to carry its rated current continuously
- test sequence: O - 3 min - CO - 3 min CO
- dielectric withstand at 2 x Ue
- verification of temperature rise at Iu
- verification of overload release at 1.45 x I1
- verification of the electrical life

ABB Group
March 10, 2015 | Slide 24

Limit values Icu and Ics

Relation between Ics and Icu

This relation is always true!!!

Ics Icu
The service breaking capacity Ics can be expressed as
a value of breaking current, in kA;
a percentage of Icu, rounded up
to the lowest whole number,
in accordance with the table (for
example Ics = 25% Icu).
Standard ratios between Ics and Icu

ABB Group
March 10, 2015 | Slide 25

When is Icu required?

Where continuity of service is not a fundamental requirement.

For protection of single terminal load.

For motor protection.

Where maintenance work is easily carried out without much


disruption.

Generally for circuit breaker installed on terminals part of


plant.

When is Ics required?

Where continuity of service is a fundamental requirement.

For installation in power center.

Where is more difficult to make maintenance.

When is difficult to manage spare breakers.

Generally for installation in main distribution board


immediately downstream transformer or generator.

Limit values Icu and Ics


Icu and Ics:

selection criteria

Main circuit breakers or circuit breakers for which


a long out-of-service period can not be accepted
(for example naval installation)
Ics
CB selection
based on
Icu

circuit breakers tor termlnal circuits or


circuit breakers for economic application

ABB Group
March 10, 2015 | Slide 28

Icu or Ics ?

Application of Icu / Ics circuit breakers

When Isc = 100 % of Icu is not necessary ?

When the real short circuit current in the point of


installation is lower than the maximum Ics breaking
capacity.
Breaker A:
Icu =100 kA
with Ics = 100 % of Icu

Breaker B:
Icu = 100 kA
with Ics = 75 % of Icu

Please also consider


that short circuit current
at the end of the line is
still lower

70 kA

50 kA !!!
U

LOAD

When Isc = 100 % of Icu is not necessary ?

Motor Protection according to IEC 60947- 4-1

Duty cycle:
O - 3mins - CO at Iq current (maximum short circuit current)
O - 3mins - CO at r current (critical short circuit current depending from the contactor size)

Where:
O: Tripping of the circuit breaker under short circuit condition.
CO: Closing by the contactor under short circuit condition and tripping of the
circuit breaker.

Icu or Ics ? Conclusion

Consider that not always Ics = 100% of Icu for all the employ
voltage range, i.e. (from 220 V a.c. to 690 V a.c.duty, and 250
V d.c.).

Selection of circuit breaker with breaking capacity Icu or Ics


must be done according to the real technical installation
requirement.

Independently from the duty cycle selected the safety of the


plant is strictly dependent from the maximum circuit breaking
capacity (in most of cases Icu).

Limit value Icw


Icw = RATED SHORT-TIME
WITHSTAND CURRENT

IEC 60947-2
def. 4.3.5.4

Example of use of category B circuit breakers


in electrical plant
The upstream circuit
Trafo 630kVA
breaker can withstand
Ucc%=4%
the fault current up to 1
sec, thus guaranteeing
ACB E1B12
an excellent selectivity
400V
22.7kA
with downstream
MCCB XT4
MCCB XT3
apparatus

ABB Group
March 10, 2015 | Slide 33

Limit value Icw


CATEGORY B
CIRCUIT BREAKER

IEC 60947-2
Table 4

Circuit breakers specifically intended for selectivity in short


circuit conditions in relation to other protection devices in
load-side series, that is with an intentional delay (adjustable)
applicable in short circuit conditions.
These circuit breakers have a specified rated short-time
withstand current Icw.

ABB Group
March 10, 2015 | Slide 34

Limit value Icw


CATEGORY A
CIRCUIT BREAKER

IEC 60947-2
Table 4

Circuit-breakers not specifically intended for selectivity under


short circuit conditions with respect to other protection devices
in series on the load side, that is without intentional short-time
delay provided for selectivity under short-circuit conditions.
These circuit-breakers have not a specified rated short-time
withstand current value Icw.

ABB Group
March 10, 2015 | Slide 35

Limit value Icw


Icw = RATED SHORT-TIME
WITHSTAND CURRENT

IEC 60947-2
Table 3

It is the value of short-time withstand current assigned to the


circuit-breaker by the manufacturer under specified test
conditions. This value is referred to a specified time (usually 1s or 3s).
It must be stated when the circuit-breaker is classified in
category B and its value must be greater than:

The highest value between 12 Iu and 5 kA

for CBs with Iu 2500A

30 kA

for CBs with Iu > 2500A

Circuit breakers without Icw value are classified in category A

ABB Group
March 10, 2015 | Slide 36

Selectivity Categories

Limit value Icm


Icm = RATED SHORT-CIRCUIT
MAKING CAPACITY

IEC 60947-2
def. 4.3.5.1

Making capacity for which the prescribed conditions according


to a specified test sequence include the capability of the circuit
breaker to make the peak current corresponding to that rated
capacity at the appropriate applied voltage.
It is always necessary to verify that:
Icm Ipeak

ABB Group
March 10, 2015 | Slide 38

Limit value Icm


For a.c. the rated short-circuit making
capacity of a circuit-breaker shall be not
less than its rated ultimate short-circuit
breaking capacity, multiplied by the factor
n of the table.

ABB Group
March 10, 2015 | Slide 39

IEC 60947-2
Table 2
Icm n x Icu

Current limiting circuit breaker


Example
Peak
105kA
100kA

T6L800 In800
54kA

16,8kA

XT2L 160 In160

10kA

10kA

ABB Group
March 10, 2015 | Slide 40

50kA

100kA

Irms

Limit value Icm

If the cos of the plant is higher than the standard prescribed


value, it is not necessary to take into account the rated shortcircuit making capacity of the circuit-breakers (Icm).

If the cos of the plant is lower than the standard


prescribed value, usually near to the transformer and/or
generator, it is necessary to verify Icm Ipeak.

ABB Group
March 10, 2015 | Slide 41

Limit value Icm


Sometimes it can happen
Short circuit current of the plant is Icc = 75kA ;
The used circuit breaker has an Icu = 75 kA;
According to the table 2, cosk=0.2 and n=2,2 so Icm = n x Icu = 165 kA.

If the cosk of the plant is equal to 0.16 (lower than the standard
prescribed value) the evaluated Ip = 175 kA.

Since Ip > Icm the CB selected is not correct. I will use a CB with a greater
value of Icu in order to have an Icm value suitable to the peak current of the
plant.

ABB Group
March 10, 2015 | Slide 42

Limit value Icm

ABB Group
March 10, 2015 | Slide 43

Choice criteria

Rated values (Iu, Ue)

Limit values (Icu, Ics, Icw, Icm)

ABB Group
March 10, 2015 | Slide 44

Insulation values (Ui, Uimp)

Limit value Ui
IEC 60947-1
def. 4.3.1.2

Ui = RATED INSULATION
VOLTAGE

The rated insulation voltage of an equipment is the value


of voltage to which dielectric tests and creepage
distances are referred.

It shall be always verified that:

Ue < Ui

ABB Group
March 10, 2015 | Slide 45

Limit value Uimp


Uimp = RATED IMPULSE
WITHSTAND VOLTAGE

IEC 60947-1
def. 4.3.1.3

The peak value of an impulse voltage of prescribed form and


polarity (1,2/50ms) which the equipment is capable of
withstanding without failure under specified conditions of test
and to which the values of the clearances are referred.
It shall be always verified that:
Uimp > transient overvoltage in
the plant

ABB Group
March 10, 2015 | Slide 46

Temperature-rise for terminals and accessible parts


IEC 60947- 2
Table 7

ABB Group
March 10, 2015 | Slide 47

Overload protection

IEC 60947- 2
Table 6

ABB Group
March 10, 2015 | Slide 48

Short circuit protection

IEC 60947- 2
8.3.3.1.2

S
I
ABB Group
March 10, 2015 | Slide 49

Type Tests
IEC 60947- 2
8.3

The tests to verify the characteristics of


circuit breakers are:

type tests carried out on samples:

Type Tests

ABB Group
March 10, 2015 | Slide 51

Routine Tests
IEC 60947- 2
8.4

routine tests carried out on


all circuit breakers and
including the following tests:

ABB Group
March 10, 2015 | Slide 52

Annex F - J
Tests of EMC for circuit breakers with electronic overcurrent protection
Electrostatic discharges
Radiated radio-frequency electromagnetic fields

Immunity

Electrical fast transients/bursts


Surges
Conducted disturbances induced by radio-frequency fields
Harmonics
Voltage fluctuations

Emission

Conducted disturbances
Radiated disturbances

Dry heat test Damp heat test

Climatic tests

Temperature variation cycles at a specified rate of change

CE Marking

According to european directives:


Low Voltage Directive 73/23 EEC
Electromagnetic Compatibility 89/336 EEC

ABB Group
March 10, 2015 | Slide 54

Annex H

Test sequence for circuit-breakers for IT systems


This test is intended to cover the case of a second fault to earth in presence of a first
fault on the opposite side of a circuit breaker when installed in IT systems.

In this test at each pole the applied voltage shall be the phase-to-phase voltage
corresponding to the maximum rated operational voltage of the circuit breaker at which it
is suitable for applications on IT systems.

Circuit Breakers
Standards Guidelines IEC 60898

IEC Standard definitions


Miniature Circuit Breakers MCB
International Standard References
IEC 60898

Applicable to circuit-breakers for protection of wiring installation


in buildings and similar applications, and designed for use by
uninstructed persons, and for not being maintained.
Part 1: Circuit-breakers for a.c. operation
Part 2: Circuit-breakers for a.c. and d.c. operation (additional requirements)

Choice criteria

Rated values (In, Ue)

Limit values (Icn, Ics)

Rated value In
Rated uninterrupted current (In):

the rated uninterrupted current of an equipment is a value


of current, stated by the manufacturer, which the equipment
can carry in uninterrupted duty, at a specified reference
ambient air temperature (30 C).

The rated current doesnt exceed the 125A.

IEC 60898-1 def. 5.2.2

Rated value Ue

Rated operational voltage (Ue):


The rated operational voltage of a circuit-breaker is the
value of voltage, assigned by the manufacturer, to which
its performances (particularly the short-circuit
performance) are referred.
The rated operational voltage doesnt exceed the 440Vac
220Vdc.
IEC 60898-1 def. 5.2.1.1

Choice criteria

Rated values (In, Ue)


Limit

values (Icn
cn, Ics
cs)

Limit value Icn


Icn = RATED SHORT CIRCUIT
CAPACITY

IEC 60898-1
def. 5.2.4

The rated short-circuit capacity is the value of the ultimate


short-circuit breaking capacity for which the prescribed
conditions, according to a specified test sequence, do not
include the capability of the circuit-breaker to carry 0.85 times
its non-tripping current for the conventional time.
test sequence: O - 3 min - CO
- leakage current at 1.1 Ue (< 2 mA)
- dielectric strength test at 900 V
- verification of overload release at 2.8 x In
The rated short circuit capacity doesnt exceed the
25kA in ac and 10kA in dc

Limit value Ics


Ics = RATED SERVICE SHORT
CIRCUIT CAPACITY

IEC 60898-1
def. 3.5.5.2

The service short-circuit capacity of a circuit-breaker is the


value of the breaking capacity for which the prescribed
conditions according to a specified test sequence include the
capability of the circuit-breaker to carry 0.85 times its nontripping current for the conventional time.

Limit value Ics


Service Short Circuit capacity (Ics):
O - 3 min - O - 3 min CO
O - 3 min - CO - 3 min CO
- leakage current at 1.1 Ue (< 2 mA)
- dielectric strength test
- verification of no tripping at 0,85 x In
- test seq. :

(for one or two poles cb)


(for three or four poles cb)

A circuit-breaker with a rated short-circuit capacity (Icn) has a corresponding service shortcircuit capacity (Ics) as from this table:
The circuit breaker with

Icn < 6000A


6000A < Icn < 10000A
Icn > 10000A

Ics is equal to 1xIcn


Ics is equal to 0,75xIcn Minimum value of Ics is 6000A.
Ics is equal to 0,5xIcn Minimum value of Ics is 7500A.

Ics Test

Tripping Curves
Overload characteristics
The main difference between the overload protection curve of the CBs responding to
IEC 60947 or IEC 60898 are referred to the conventional non tripping current.
The prescibed conditions are given in this table:

Tripping Curves
Magnetic characteristics
The CBs according to IEC 60947 usually have the instantaneous threshold at 5 or 10 times
the rated current with a tolerance of + 20%.
The CBs according to IEC 60898-1 (ac applications) have different instantaneous
threshold referred to the type B , C , D as indicated in the table below:

Tripping Curves

Tripping Curves

In some cases, the conditions IB < In < IZ


and I2 < 1.45 IZ do not guarantee complete
protection, e.g. when overcurrents are
present for long periods which are smaller
than I2. They also do not necessarily lead
to an economical solution. It is therefore
assumed that the circuit is designed so
that minor overloads of a long duration will
not occur regularly.

IEC 60364-4-43

Tripping Curves

Comparison IEC 60947-2 vs IEC 60898


IEC 60947-2

IEC 60898-1

People

Instructed

Uninstructed

Maintenance

Possible

Not possible

< 1000 Vac

< 440 Vac

< 1500 Vdc

< 220 Vdc

40 C

30 C

Rated Voltage (Ue)


Ambient
Temperature

No limits
Rated Current

(Iu < 6300 A)


Short circuit
breaking current

No limits for Icu

In = 125 A
Icn = 25 kA (ac)
Icn = 10 kA (dc)

Selection of protective Devices

Generalities about the main electrical parameters


Dont forget

Ue Un
Icu or Ics Ik
Icm Ip

Ue, Icu, Ics, Icm?

Selection of protective Devices

Protection of feeders
against overload

Ib In or I1 Iz
against short-circuit

In
Iz S

I2t k2S2

Ib

Selection of protective Devices


The correct circuit breaker must be selected to satisfy the following
conditions:
It must own short circuit breaking power (lcu or eventually lcs) greater or
equal to the short circuit current lcc
It must use a protection release so that its overload setting current ln (l1)
satisfies the relation lB < ln < lZ
The let through energy (l2t) that flows through the circuit breaker must be
lesser or equal to the maximal one allowed by the cable (KS)

Selection of protective Devices

Selection of protective Devices

As far as the verification required by IEC 60364, according to which the


overload protection must have an intervention current lf that assures the
operation for a value lesser than 1,45 lz (lf < 1,45 lz), we must state that it
is always verified for ABB Circuit breakers, since according to IEC 60947-2
the required value is less than 1,3 ln.

Selection of protective Devices

Selection of protective Devices


Protection of generators
Ingen I1
I3 or I2 2.5-4 x Ingen

Selection of protective Devices

Protection of transformers
InT I1
Upstream CB

I3 or I2 Iinrush

Selection of protective Devices


20kV

Steps
determining the short-circuit
currents
choosing the CB
setting of the MV overcurrent
protection
setting of the LV overcurrent
protection

400V

Selection of protective Devices


20kV

400V

Selection of protective Devices


20kV

400V

Protection of Transformers

As to be able to protect LV/MV transformers LV side, we must mainly


take into account:
Rated current of the protected transformer, LV side, from which
the rated current of the circuit breaker and the setting depend on
(In);
The maximum estimated short circuit current in the installation
point which defines the minimal breaking power of the protection
circuit breaker (Isc).

Protection of Transformers
Switchboards with one transformer

Sn

U20

In
Isc

The rated current of the transformers LV side is defined by the


following expression
Sn x 103
In =
3 x U20
where
Sn = rated power of the transformer [kVA]
U20 = rated secondary voltage (no load) of the transformer [V]
ln = rated current of the transformer, LV side [A]

Protection of Transformers

The full voltage three-phase short circuit current immediately after the LV
side of the transformer can be expressed by the following relation once we
suppose infinite power at the primary:

Isc =

In x 100
Ucc %

where
Ucc %= short circuit voltage of the transformer [%]
ln = rated current, LV side, [A]
lsc = three-phase rated short circuit current, LV side, [A]

Protection of Transformers

The short circuit current is normally lesser than the preceding deduced
value if the circuit breaker is installed at a certain distance by means of
a cable or bar connection, according to the connection impedance.

Protection of Transformers

The following table shows some possible choices within the SACE Emax
ACB range according to the characteristics of the CB to protect.
Attention
Those indications are valid at the conditions that we declare in the table;
different conditions will lead us to repeat calculations and modify the
choices.

Protection of Transformers
Sn

[kVA]

500

630

800

1000

1250

1600

2000

2500

3150

Ucc (1)

6,25

6,25

6,25

6,25

In (2)

[A]

722

909

1154

1443

1804

2309

2887

3608

4547

Isc (2)

[kA]

18

22.7

23.1

28.9

36.1

37

46.2

57.7

72.7

E1B08

E1B12

E1B12

E2B16

E2B20

E3B25

E3B32

E4S40

E6H50

SACE Emax

(1) For values of the percent short circuit voltage Ucc% different from the Ucc% values as per table, the rated three-phase short
circuit current Icn becomes:

Isc = Isc

Ucc %
Ucc %

(2) The calculated values refer to a U20 voltage of 400 V. for different U20 values, do multiply In and Isc the following k times:

U20
k

[V]

220

380

400

415

440

480

500

660

690

1.82

1.05

0.96

0.91

0.83

0.8

0.606

0.580

Protection of Transformers
Switchboards with more than 1 transformer in Parallel

Isc2 + Isc3

I2

I1

Circuit breaker A

I3

Isc1

I5

Isc1 + Isc2 + Isc3

Circuit breaker B

I4

Protection of Transformers

As far as the calculation of the rated current of the transformer is


concerned, the rules beforehand indicated are completely valid.
The minimum breaking capacity of each circuit breaker LV side must be
greater than the highest of the following values: (the example refers to
machine 1 of the figure and it is valid for the three machines in parallel):
lsc 1 (short circuit current of transformer 1) in case of fault
immediately downstream circuit breaker 1;
lsc2 + lsc3 (short circuit currents of transformer 2 and 3) in case of
fault immediately upstream circuit breaker 1;

Protection of Transformers

Circuit breakers l4 and l5 on the load side must have a short circuit
capacity greater than lsc1 + lsc2 + lsc3; naturally every transformer
contribution in the short circuit current calculation is to be lessened by the
connection line transformer - circuit breaker (to be defined case by case).

Low voltage selectivity


with ABB circuit breakers
Selectivity definitions and Standards
ABB Group
March 10, 2015 | Slide 92

Agenda
Low voltage selectivity with ABB circuit breakers

Definitions and Standards

Selectivity techniques
Back-up protection

Introduction
What is selectivity?
Selectivity (or discrimination)

A is the supply side circuit


breaker (or upstream)

is a type of coordination of two or


more protective devices in series.

Selectivity is done between


one circuit breaker on the supply side
and one circuit breaker, or more than
one, on the load side.

B and C are the load side circuit


breakers (or downstream)

Introduction
Protection system philosophy

Reduce the stress and prevent damage

Minimize the area and the duration of


power loss

DAMAGE REDUCTION

Better selectivity

FAULT

CONTINUITY OF SERVICE

Fast fault elimination

Main purposes of coordination


Selectivity purpose
Selective coordination among devices
is fundamental for economical and technical reasons
It is studied in order to:

rapidly identify the area involved in the problem;

bound the effects of a fault by excluding just the affected zone of the
network;

preserve the continuity of service and good power quality to the sound
parts of the network;

provide a quick and precise identification of the fault to the personnel in


charge of maintenance or to management system, in order to restore
the service as rapidly as possible;

achieve a valid compromise between reliability, simplicity and cost


effectiveness.

Standards definition
Selectivity
The definition of selectivity

IEC 60947-1 Standard: Low voltage equipment


Part 1: General rules for low voltage equipment

IEC 60947-1
def. 2.5.23

Trip selectivity (for overcurrent) is a coordination between the


operating characteristics of two or more overcurrent protection
devices, so that, when an overcurrent within established limits
occurs, the device destined to operate within those limits trips
whereas the others do not trip

Overcurrent selectivity
Example
In occurrence of a fault
(an overload or a short circuit)
if selectivity is provided
only the downstream circuit
breaker opens.

Overcurrent selectivity
Example
In occurrence of a fault
(an overload or a short circuit)
if selectivity is not provided
both the upstream and the
downstream circuit breakers
could open

All the system is out of service!

Standards definition
Partial and total selectivity
IEC 60947-2
def. 2.17.2 - 2.17.3

A and B connected in series:

partial selectivity and total selectivity.

Standards definition
Partial selectivity
Partial selectivity is an overcurrent selectivity where, in the
presence of two protection devices against overcurrent in series,
the load side protection device carries out the protection up to a
given level of overcurrent, without making the other device trip.

Is is the ultimate
selectivity
value!

B opens only according to fault current


lower than a certain current value;
values equal or greater than Is
will give the trip of both A and B.
Is = ImA

Standards definition
Total selectivity
Total selectivity is an overcurrent selectivity where, in the
presence of two protection devices against overcurrent in series,
the load side protection device carries out the protection without
making the other device trip.

Only B trips for every current value


lower or equal to the maximum
short-circuit current.
Is = Ik

Standards definition
Partial and total selectivity
Upstream circuit breaker A
T4N 250 PR221DS In = 250 (Icu = 36kA)
Downstream circuit breaker B

S 294 C100 (Icu = 15kA)

Selectivity analysis
Time-current curves

Overload zone
Thermal protection
L protection

Time-current selectivity

Short-circuit zone
Magnetic protection
S, D, I and EF protections

Current, time, energy, zone,


directional, zone directional selectivity

Selectivity analysis
Real currents
Real currents circulating through the circuit breakers

I>

I>

IA = IB
tA

I>

I>

I>

I>

I>

I>

I>

IA = (IB + Iloads) / 2

IA = IB + Iloads
tA
tB

I>

I>

tA

tB

tB

IA=IB

IB IA

IA

IB

Agenda
Low voltage selectivity with ABB circuit breakers

ABB Group, BU Breakers and Switches


March 10, 2015 | Slide 106

Definitions and Standards

Selectivity techniques

Back-up protection

Introduction
Selectivity techniques

Current selectivity

Time selectivity

Energy selectivity

Zone (logical) selectivity

ABB Group, BU Breakers and Switches


March 10, 2015 | Slide 107

Current selectivity
Base concept

Current selectivity: closer to the power supply


the fault point is, higher the fault current is
3kA

In order to guarantee selectivity,


the protections must be set to different
values of current thresholds
1kA

tA

The ultimate selectivity value


is equal to the instantaneous trip threshold
of the upstream protection device

Other methods are needed to have a total


selectivity

tA

A
Ultimate
selectivity
value

tB

ImB

ImA

Current selectivity
Example
Circuit breaker A will be set to a value which does not
trip for faults which occur on the load side of B.
(I3Amin >1kA)
Circuit breaker B will be set to trip for faults which
occur on its load side (I3Bmax < 1kA)
104s

Is

103s

Is = I3Amin

102s
10s

Here the selectivity is a total selectivity,


because it is guaranteed up to the maximum
value of the short-circuit current, 1kA.

1s

B
10-1s
10-2s

0.1kA

1kA

3kA

10kA

Current selectivity
Plus and minus
Plus
Easy to be realized
Economic
Instantaneous

CURRENT SELECTIVITY
Minus
Selectivity is often only partial
Current thresholds rise very quickly

Time selectivity
Base concept

Time selectivity is based on a trip delay of the upstream


circuit breaker, so to let to the downstream protection the
time suitable to trip

Setting strategy:
progressively increase the
trip delays getting closer to
the power supply source

On the supply side


the S function is required

Time selectivity
Example
A will be set with the current threshold I2
adjusted so as not to create trip overlapping
and with a trip time t2 adjusted so that
B always clears the fault before A

B will be set with an instantaneous trip


against short-circuit

I
k
104s

Is

The ultimate selectivity value is:

103s
102s
10s

1s

I2
t2

10-1s
10-2s
0.1kA

1kA

10kA

100kA

Is = IcwA

(if function I = OFF)

Is = I3minA

(if function I = ON)

Time selectivity
Example
Which is the problem of time selectivity?

In the case of fault occurring at the busbars,


circuit breaker A takes a delayed trip time t2

I
k

The network must withstand high values of


let-through energy!

104s
103s
102s
10s

If there are many hierarchical levels, the


progressive delays could be significant!

1s

t2

10-1s
10-2s
0.1kA

1kA

10kA

100kA

Time selectivity
Plus and minus
Plus
Economic solution
Easy to be realized

TIME SELECTIVITY
Minus
Quick rise of setting levels
High values of let-through energy

Energy selectivity
Base concept
Energy selectivity is based on the currentlimiting characteristics of some circuit breakers

104s
103s
A

102s
10s
1s
B

10-1s
10-2s

0.1kA

1kA

The ultimate current


selectivity values
is given by the
manufacturer
(Coordination tables)

10kA

Current-limiting circuit breaker


has an extremely fast trip time,
short enough to prevent the
current from reaching its peak

Energy selectivity
Example

104s
103s

Is = 20kA

Circuit breaker A conditions:

102s
B
10s

I3=OFF

1s

S as for time selectivity

10-1s
10-2s

0.1kA

1kA

10kA

Energy selectivity
Plus and minus
PLUS
High selectivity values
Reduced tripping times
Low stress and network disturbance

ENERGY SELECTIVITY
MINUS
Increasing of circuit breakers size

Zone selectivity
Base concept

Zone selectivity is an evolution of the time


selectivity, obtained by means of a electrical
interlock between devices
locking
signal

The circuit breaker which detects a fault


communicates this to the one on the supply side,
sending a locking signal

Only the downstream circuit breaker opens,


with no need to increase the intentional time
delay

Fault

Zone 3

A Does Not Open


B Does Not Open

Zone 2

Zone 1

Zone selectivity
Example

C Opens

Zone selectivity
Specifications

an external source of 24V

dedicated trip units

PR223EF for Tmax T4, T5 and T6

PR332/P for Tmax T7 and T8

PR122/P and PR123/P for Emax

PR332/P and PR333/P for X1

Is

up to 100kA for Tmax

Is

up to Icw for Emax

Zone 2

a shielded twisted pair cable

Zone 3

Zone 1

Zone selectivity needs:

It is possible to obtain zone selectivity between Tmax and Emax

Zone selectivity
Plus and minus
PLUS
Trip times reduced
Low thermal and dynamic stress
High number of hierarchical levels
Can be made between same size circuit breakers

ZONE SELECTIVITY
MINUS
Cost and complexity of the installation
Additional wiring and components

Agenda
Low voltage selectivity with ABB circuit breakers

ABB Group, BU Breakers and Switches


March 10, 2015 | Slide 122

Definitions and Standards

Selectivity techniques

Back-up protection

Back-up protection
What is back-up protection?
Back-up protection (or cascading)
is a type of coordination of two protective
devices in series which is done in electrical
installations where continuous operation is
not an essential requirement.

Back-up protection
excludes the use
of selectivity!!!

Back-up protection
Standards definition
The definition of back-up is given by the

IEC 60947-1 Standard: Low voltage equipment


Part 1: General rules for low voltage equipment

IEC 60947-1
def. 2.5.24

Back-up is a coordination of two overcurrent protective


devices in series, where the protective device on the supply
side, with or without the assistance of the other protective
device, trips first in order to prevents any excessive stress on
downstream devices.

Back-up protection
Base concept

Back-up is used by those who need


to contain the plant costs

The use of a current-limiting circuit


breaker on the supply side
permits the installation of lower performance
circuit breakers on the load side

Both the continuity of service and the selectivity are sacrificed

Back-up protection
Application example

T4L 250

Ik = 100 kA
Icu (T4L+T1N) = 100kA

T4L 250

T4L 250

T4L 250

Icu = 120kA

T1N 160

T1N 160

T1N 160

Icu = 36kA

Back-up protection tables

Back-up protection
Application example

T4L 250
A

Ik = 100kA

Icu (T4L+T1N) = 100kA

Ik = 100kA
T1N 160

T1N 160

T1N 160

General power supply


is always lost

Back-up protection
Plus and minus

Plus

Economic solution
Quick tripping times

BACK-UP PROTECTION
Minus

No selectivity
Low power quality

Example of Selectivity

~
T5H 630A

70kA

T3N 160A

36kA

Incoming = T5H 630A (70kA


rating) Outgoing = T3N 160A
(36kA rating)
Results: The co-ordination
resulted in a conditional shortcircuit of 65kA for the T3 mccb!

Iz

The discrimination is up to 20kA.

65kA

Example of Selectivity
Discrimination

Example of Selectivity
Back-Up

Example of Selectivity
Meaning of Selectivity Value
T5H

70kA

T5H 70kA
T3N 36kA
T3N

Fault level at Y is 20kA


Y is 20kA

36kA

Example of Selectivity
Meaning of Selectivity Value
T5H

T3N

70kA

T5H
20kA
T3N

36kA

Example of Selectivity
Meaning of Selectivity Value

5kA fault

T5H
ON

T3N
Trip

T5H

70kA

T3N

36kA

5kA

Example of Selectivity
Meaning of Selectivity Value

T5H
5kA fault ON
10kA fault ON

T3N
Trip
Trip

T5H

70kA

T3N

36kA
10kA

Example of Selectivity
Meaning of Selectivity Value

T5H
5kA fault ON
10kA fault ON
20kA fault Trip

T3N
Trip
Trip
Trip

T5H

70kA

T3N

36kA
20kA

Example of Selectivity
Meaning of Selectivity Value

T5H
5kA fault ON
10kA fault ON
20kA fault Trip
36kA fault Trip

T3N
Trip
Trip
Trip
Trip

T5H

70kA

T3N

36kA
36kA

Example of Selectivity
Meaning of Selectivity Value

5kA fault
10kA fault
20kA fault
36kA fault
65kA fault

T5H
ON
ON
Trip
Trip
Trip

T3N
Trip
Trip
Trip
Trip
Trip

T5H

70kA

T3N

36kA
65kA

MV/LV Transformer Substations


Selection of Protective & Control Devices
Motor co-ordination
ABB offers co-ordination tables

MV/LV Transformer Substations


Selection of Protective & Control Devices
Co-ordination between CBs and switch-disconnectors
400V

T2S160

T1D160

Power Factor Correction

ABB Group
March 10, 2015 | Slide 142

Power Factor Correction


Generalities on Power Factor Correction
In alternating current circuits, current is absorbed by a load
which can be represented by two components:

ABB Group
March 10, 2015 | Slide 143

The Active component

In phase with the supply voltage

Directly related to the output

The Reactive component

Quadrature to the voltage

Used to generate the flow necessary for the


conversion of powers through the electric or
magnetic field

In most installations the presence of inductive type


loads, the current lags the active component (IR).

Power Factor Correction


Generalities
Generalities on Power Factor Correction
In order to generate and transmit active power (P) a certain
reactive power (Q) is essential for the conversion of the
electrical energy but is not available to the load.
The power generated and transmitted make up the apparent
power (S).
Power factor (cos ) is defined as the ratio between the
active component (IR) and the total value of current (I).
is the phase angle between the voltage and the current.

ABB Group
March 10, 2015 | Slide 144

Power Factor Correction


Generalities
Generalities on Power Factor Correction

ABB Group
March 10, 2015 | Slide 145

Power Factor Correction


Typical
Power Factors of some electrical equipment
Generalities

ABB Group
March 10, 2015 | Slide 146

Power Factor Correction


Advantages
Generalities of Power Factor Correction

ABB Group
March 10, 2015 | Slide 147

Power Factor Correction


Advantages
Generalities of Power Factor Correction

Better utilization of electrical machines

Better utilization of cables

ABB Group
March 10, 2015 | Slide 148

Generators & transformers are sized according to the


apparent power (S). With the same active power (P),
the smaller the reactive power (Q) delivered, the
apparent power will be smaller.

The reduction in current allows the use of smaller


cables in the installation.

Power Factor Correction


Generalities

Reduction in losses

Reduction in voltage drop

ABB Group
March 10, 2015 | Slide 149

By improving the power factor, power losses is reduced


in all parts of the installation.

The higher the power factor the Voltage drop will be


lower at the same level of Active power.

Power Factor Correction


Generalities

Economical savings

ABB Group
March 10, 2015 | Slide 150

Power supply utilities apply penalties for energy used


with poor factor. An improved power factor will reduce
such penalties from the utilities.

Power Factor Correction


Advantages
Generalities of Power Factor Correction

Improve capacity of transformers and cables

By improving the power factor, you reduce the kVA load on the
transformer and the current carried by the cables

Apparent Power (VA)


e.g 2MVA Transformer
At 100% capacity

Real Power (W)


eg. 500kW Load

ABB Group
March 10, 2015 | Slide 151

Reactive Power (VAR)


e.g Motors (inductive)
100kW at 0.7pf = 102kVAR
Reactive Power (VAR)
eg. 50kVAR Capacitors

Thus additional transformer capacity is available if upgrade or


expansion is required in the future
Or new cables might not be needed if new loads are connected to
an existing switchboard

Power Factor Correction


Different Methods

Distributed power factor correction

ABB Group
March 10, 2015 | Slide 152

It is achieved by connecting a capacitor bank properly


sized according to the load and is connected directly to
the terminals of the load.

Power Factor Correction


Different Methods

Group power factor correction

ABB Group
March 10, 2015 | Slide 153

It is achieved by connecting a capacitor bank properly


sized according to a group of loads and is connected to
the upstream of the loads to be corrected.

Power Factor Correction


Types
of Power
Factor correction
Different
Methods

Centralized power factor correction

ABB Group
March 10, 2015 | Slide 154

It is achieved by installing an automatic power factor


correction bank capacitor bank directly to the main
distribution boards.

Power Factor Correction


Types
of Power
Factor correction
Different
Methods

Combined power factor correction

This solution is derived from a compromise between a


distributed & centralized power factor correction.

ABB Group
March 10, 2015 | Slide 155

Distributed power factor correction is used mainly


for higher loads and a smaller centralized power
factor correction is used for the small loads.

Power Factor Correction


Switching
Protection
Capacitor and
Switching

ABB Group
March 10, 2015 | Slide 156

Electrical switching phenomena

The switching of a capacitor bank causes an electric


transient due to the phenomena of electric charging of
the bank.

The overcurrents at the moment of switching depends


greatly on both the inductance of the upstream network
as well as from the number of connected capacitor
banks.

Power Factor Correction


Switching
Protection
Capacitor and
Switching

ABB Group
March 10, 2015 | Slide 157

Choice of protective device

Power Factor Correction


Capacitor Switching

Resistance

Motor

In

In

In
AC-1

Capacitor

AC-3

AC-6b

Power Factor Correction


Capacitor Switching
Single step capacitor

30 times In

In

Power Factor Correction


Capacitor Switching
Multi steps capacitor bank

> 100 times In

In

Power Factor Correction


Contactor Sizing
Contactor sizing: Thermal current + peak current
Thermal current
Up to 30% for harmonics and voltage fluctuations on main
Up to 15% for tolerances on capacitor power
Contactor have to support Ith

Ith = 1.3 x 1.15 x Inc = 1.5 Inc

Power Factor Correction


Example
Example
kVARh is billed if it is higher than the contracted level.

kVA
kVar

kW

Apparent power (kVA) is significantly higher than the Active power (kW)
The excess current causes losses (kWh) which is billed.

1MVA

The design of the installation has to be over-dimensioned.


The installation requires 850kW at power factor of 0.75.

400V

The transformer will have to be overloaded to 850k / 0.75 = 1.133MVA.

Current taken by the system is


P
I =
= 1636A
3 * U * Cos
Losses in the cables
P = I 2R
Cos = 0.75
850kW Load
ABB Group
March 10, 2015 | Slide 162

I = 1636A

Cos = 0.75
The Transformer, Circuit breaker & Cable has to be increased.

Power Factor Correction


Example
Example
kVA

kVARh is reduced to lower than the contracted level or eliminated.

kVar

kW

Apparent power (kVA) is significantly higher than the Active power (kW)
The charges based on the contracted kVA demand is close to the active
power.

1MVA

The installation requires 850kW at a power factor of 0.9.


400V

The transformer will not be overloaded to 850k / 0.90 = 945 kVA.


Current taken by the system is
P
I =
= 1364A
3 * U * Cos
Losses in the cables
P = I 2R

Cos = 0.90
850kW Load
ABB Group
March 10, 2015 | Slide 163

I = 1364A

Cos = 0.90
There is not need to increase the Transformer, Circuit breaker & Cable.

Power Factor Correction


Technical Application Paper

ABB Group
March 10, 2015 | Slide 164

Vous aimerez peut-être aussi