Académique Documents
Professionnel Documents
Culture Documents
a.c. currents.
To measure larger currents with electromechanical meters, it is necessary to
insert a
shunt resistance into the circuit and measure the voltage drop across it. Apart
from the
obvious disturbance of the measured system, one particular difficulty that results
from
this technique is the large power dissipation in the shunt. In the case of a.c.
current
measurement, care must also be taken to match the resistance and reactance of
the
shunt to that of the measuring instrument so that frequency and waveform
distortion
in the measured signal are avoided.
Current transformersprovide an alternative method of measuring high-magnitude
currents that avoids the difficulty of designing a suitable shunt. Different versions
of
these exist for transforming both d.c. and a.c. currents. A d.c. current
transformer
is shown in Figure 7.15. The central d.c. conductor in the instrument is threaded
through two magnetic cores that carry two high impedance windings connected
in
series opposition. It can be shown (Baldwin, 1973) that the current flowing in the
windings when excited with an a.c. voltage is proportional to the d.c. current in
the
central conductor. This output current is commonly rectified and then measured
by a
moving-coil instrument.
An a.c. current transformer typically has a primary winding consisting of only
a few copper turns wound on a rectangular or ring-shaped core. The secondary
winding on the other hand would normally have several hundred turns according
to
the current step-down ratio required. The output of the secondary winding is
measured