Académique Documents
Professionnel Documents
Culture Documents
Not OK
Not OK
Transformers
Not-Applied
Cleaning
the vacuum hose in order to loosen
Applied
dirt that is more firmly attached
to
(Assembled Generators)"Note(2)"
the surface
Compressed air maximum of (30
psi) may be used to remove the
Applied
remaining dust and dirt.
Not-Applied
Not-Applied
Corrective actions
Not-Applied
Recommended action.
1 | Page
Last PM (hours)
Ambient temperature
Check all exposed electrical
connections for tightness.
Electrical Connections -
Generator Inspect
Not OK
OK
Not OK
L1 to
Main stator insulation
resistance
Main rotor insulation
resistance
ground
L2 to ground
wire to ground
Insulation resistance
"Note(6)", "Note(7)","Note(8)","Note(9)"&
Exciter rotor insulation
"Note(10)"
resistance
wire
to ground
L3 to ground
wire to ground
wire to ground
wire to ground
wire to ground
wire to ground
F1to ground
F2 to ground
Recommended action
Not-Applied
2 | Page
"Note(5)"
Recommended action.
1- Switchgear inspection
On de-energized equipment
Procedure
Result
Not OK
Check for foreign objects and loose tools or fallen parts, warped or
distorted insulated bus, and rusty or bent structural framework.
Not OK
Not OK
Inspect the (internal) bus supports for structural integrity and signs
of cracks.
Not OK
Not OK
2- Contact resistance testing of Bus bars
Pole resistance Micro ohms readings
Pole#1
Pole#2
Pole#3
As found (Micro-Ohms)
As left (Micro-Ohms)
As found (Micro-Ohms)
As left (Micro-Ohms)
As found (Micro-Ohms)
As left
(Micro-Ohms)
Phase to ground
Phase (A)
(A) to (B)
Phase to Phase
Phase (B)
(B) to (C)
Phase (C)
(C) to (A)
30
60
DAR
DAR =
Resistance reading at 60 s
Resistance reading at 30 s
3 | Page
Corrective action
1. Clean insulation, insulators, bus hardware, and joint covers with a cleaner that is
suitable for the material and application.
2. All dust and dirt should be vacuumed from the switchgear enclosure and
components. Wiping with a dry, clean cloth buses, insulators, cables, and the
like.
3. The surface of all insulating members should be inspected before any cleaning
or dusting, as well as after cleaning for signs of electrical distress, tracking,
corona, and thermal heating.
4. Clean ventilating openings and filters, Make sure that fans are functioning
properly
5. Lubricate hinges, locks, latches, and so on.
6. Compare equipment nameplate information with latest one-line diagram and
report discrepancies.
7. A torque procedure includes initially tightening the bolts finger tight followed
by the use of a torque wrench to half of the recommended torque value. The
torque sequence should ensure a uniform pressure applied to the mating
connection surfaces. The appropriate symmetrical torque sequence can
ensure full clamping force and contact area.
8. Cleaning of C.B should be carried out using a cloth or brush that is perfectly clean
and dry, without using any solvents, avoiding greased parts except for grease on
electrical contacts. Application of products under pressure or containing solvents
(trichloroethane, trichloroethylene, WD40) is strictly forbidden.
9. Greasing: Grease must not be over applied because the excess, if mixed with
dust, may result in mechanism malfunctions. Generally speaking, under normal
operating conditions, the pole-operating mechanism does not require any
regreasing as it is greased for the life of the product.
Lubrication of the Mechanism
The clusters and disconnecting-contacts must be greased according to
the defined intervals using the greases indicated by manufacture.
The main contacts must not be greased.
Thermography or low resistant measurement is an alternate method to determine the
suitability of a connection. Perform a comparison of measured values.
4 | Page
Thermographic surveys
Reason of survey:
Description of equipment to be tested:
Equipment name
Ampere rating
2Visual inspection
On energized equipment
Procedure
Result
5 | Page
Not OK
With lights out, look for blue or purple corona halos. Orange or red
sputter arcs are created by intermittent sparking.
Not OK
Not OK
3-
Data recording
Procedure
Result
Gen#1
Gen#3
Gen#2
Gen#4
Gen#1
Gen#3
Gen#2
Gen#4
Note(1)
i.
Note(2)
Cleaning may be required at the point of installation.
i.
In this case, a vacuum cleaner should be used to pick up the following items:
dry dirt, dust, and carbon. This will prevent the spreading of these
contaminants.
ii. A small nonconductive tube may need to be connected to the vacuum
cleaner. This will allow the vacuum cleaner to clean the surfaces that are not
exposed. After most of the dust has been removed, a small brush may be
attached to the vacuum hose in order to loosen dirt that is more firmly
attached to the surface.
iii. After the initial cleaning with a vacuum, compressed air may be used to
remove the remaining dust and dirt. Compressed air that is used for cleaning
should be free of moisture and free of oil. Air pressure should be a maximum
of (30 psi) in order to prevent mechanical damage to the insulation.
Note(3)
Thermograph determines the highest point of temperature (hot spots) in the winding. The hotspot is the location in stator windings with the highest temperature. A hot-spot is located
approximately in the center of each stator slot and approximately in the center of each field
winding.
Note(4)
6 | Page
SR5 generators are limited to a 20C (257F) temperature rise over the same conditions SR4
generators.
Note(5)
Use a fine grade of sandpaper to clean the terminals and the cable clamps. Clean the items
until the surfaces are bright or shiny. DO NOT remove material excessively. Excessive removal
of material can cause the clamps to not fit properly.
Note(6)
i.
Note(7)
Note(8)
Recommended Procedure for the Insulation Test
7 | Page
vi. Disconnect the sensing lead wires for the regulator. This may be
accomplished by unplugging the harness connectors.
vii. Disconnect the PT leads of the load share module.
viii.
Use the 30/60 Time Resistance Method:
ix. Evaluate the readings.
Field-Winding Test
Note(9)
6wire exciter rotor is existed in case of 1400 frame (3500 series generator).
Note(10)
Recommended action may be:
If test readings are accepted Cleaning assembled generator.
A high pressure wash is normally an effective way to clean windings. This includes windings that
have been exposed to flooding or windings that have been contaminated by salt. A solution of hot
water and detergent is used for this method of cleaning.
A high pressure wash sprays a high velocity fluid stream of this solution over the generator that is
being cleaned. This detergent washing is followed by multiple sprays of clean water. The clean
water is used in order to remove the detergent or the clean water is used in order to dilute the
detergent.
8 | Page
9 | Page