1SDC007101G0202
MV/LV transformer
substations: theory and
examples of short-circuit
calculation
and switch-disconnectors.......................... 21
2 Calculation of short-circuit
currents
2.1 Data necessary for the calculation ........... 11
2.2 Calculation of the short-circuit current...... 12
2.3 Calculation of motor contribution ............. 15
2.4 Calculation of the peak current value ...... 15
L
L
L2
L2
L3
L3
N
LOAD
The utility prescribes and defines the criteria and methods for connection of normal customers (intended as
those who are not other power producers or special
users with disturbing loads characterised, for example,
by harmonics or flicker) in its official documentation.
These prescriptions specifically apply to connections
to the MV grid with rated voltage of 15kV and 20kV
whereas, for other MV voltage values, they can be applied for similarity.
As an example, below we give the prescriptions provided
by an Italian distribution utility regarding the power of
the transformer which can be used. The power values
allowed are as follows:
- power not higher than 1600kVA for 15kV networks
- power not higher than 2000kVA for 20kV networks.
The powers indicated refer to a transformer wit vk%=6%.
The limit relative to the installable power is also established and, in order not to cause unwanted trips of the
overcurrent protection of the MV line during the putting
into service operations of their own plants, the customers cannot install more than three transformers, each
Method 1
Substation with a single transformer
IMV
IMV
MV line
MV line
SMV
ILV
L
Diagram 1
ILV
L2
L
L2
Diagram 1a