Vous êtes sur la page 1sur 127

INSTALLATION QUALIFICATION PROTOCOL

For the
NEW PURIFIED WATER SYSTEM
Prepared by

____________________________________

TABLE OF CONTENTS
1.0

PURPOSE AND OBJECTIVE(S) .................................................................................................................................... 4

2.0

BACKGROUND .............................................................................................................................................................. 4

3.0

SCOPE ........................................................................................................................................................................... 4

4.0

REFERENCES ............................................................................................................................................................... 4

5.0

RESPONSABILITIES ...................................................................................................................................................... 5

5.1

Validation Specialist ................................................................................................................................................... 5

5.2

Quality Dept. ............................................................................................................................................................... 5

5.3

Facility Dept. ............................................................................................................................................................... 5

6.0

METHODOLOGY............................................................................................................................................................ 6

6.1

Verification Data Sheet ............................................................................................................................................... 6

6.2

Deviation Report ......................................................................................................................................................... 6

6.3

Signature Log Sheet ................................................................................................................................................... 6

6.4

Test Instruments Calibration ....................................................................................................................................... 6

7.0

EQUIPMENT/PROCESS DESCRIPTION ....................................................................................................................... 7

7.1

Water Softener ........................................................................................................................................................... 7

7.2

Ozone Generator ........................................................................................................................................................ 7

7.3

Reverse Osmosis ....................................................................................................................................................... 7

7.4

Mixed Bed................................................................................................................................................................... 7

7.5

Ozone Destructor ....................................................................................................................................................... 7

7.6

De-gasifier .................................................................................................................................................................. 8

7.7

UV light ....................................................................................................................................................................... 8

7.8

Filter ........................................................................................................................................................................... 8

APPENDIX I: DEVIATION REPORT .......................................................................................................................................... 11


APPENDIX II: SIGNATURE IDENTIFICATION LOG SHEET .................................................................................................... 12
APPENDIX III: TESTING INSTRUMENTS LOG SHEET ........................................................................................................... 13
IQ-01 EQUIPMENT VERIFICATION .......................................................................................................................................... 15
IQ-02 DOCUMENT INVENTORY VERIFICATION .................................................................................................................... 37
IQ-03 DRAWING VERIFICATION .............................................................................................................................................. 56
IQ-04 SYSTEM DESIGN VERIFICATION.................................................................................................................................. 58
IQ-05 PLACEMENT VERIFICATION ......................................................................................................................................... 60
IQ-06 UTILITY VERIFICATION .................................................................................................................................................. 67
IQ-07 INSTRUMENTATION VERIFICATION ............................................................................................................................. 86
IQ-08 MAINTENANCE VERIFICATION ..................................................................................................................................... 88
IQ-09 SAFETY & ERGONOMICS VERIFICATION .................................................................................................................. 107
IQ-10 PROCEDURE VERIFICATION ...................................................................................................................................... 109
IQ CHECKLIST VERIFICATION .............................................................................................................................................. 127

REVISION HISTORY
Revision

Description of change

Date

1.0 PURPOSE AND OBJECTIVE(S)


This protocol (___) intends to provide documented evidence that the new Purified Water System
was installed according to manufacturers specifications and ___ ___ requirements.
This Installation Qualification will provide documented evidence that all key aspects of the Purified
Water System equipments assembly and its auxiliary systems is as intended by manufacturer
design and in accordance to ___s requirements.
At the end of the execution activities, a final report will be developed with a summary of the
executed tests results and the recommendation(s) necessary for the Installation Qualification.
Potential risks involved with the new Purified Water System installation when connected to the
manufacturing processes has already being evaluated by Risk Assessment PLS 0410.
2.0 BACKGROUND
In order to meet the new purified water utility demands at ___ I in ___ ___, ___ ___, a new purified
water system was purchased to replace the existing system. It is expected that this new purified
water system will increase the supply to up to 100 GPM. Additionally, it is intended to produce a
water quality that meets or exceeds current Purified Water USP and EP standards.
3.0 SCOPE
This protocol applies to the new equipment and auxiliary components that constitute the Purified
Water System, installed at ___ in ___ ___, ___ ___
4.0 REFERENCES

FDAs Office of Regulatory Affairs: Guide To Inspections of High Purity Water Systems

5.0 RESPONSABILITIES
5.1 Validation Specialist
Prepare the documents that are applicable to the Validation exercise
Coordinate efforts and resources, along with Facilities Dept., to perform the Validation
exercise
Execute and collect the verification data for the Validation protocol
Verify data against Acceptance Criteria and initiate deviation, as applicable
Investigate, justify, and correct any deviation encountered during Validation execution
Prepare validation Final Report
5.2 Quality Dept.
Evaluate with the originator the extent of the validation required
Review and approve documents for the validation exercise
Review and approve validation activities for compliance and adherence to ___s policies,
practices, and procedures
Check that the collected data meets the acceptance criteria and that all the deviations (if
applicable) are properly resolved
Once executed, review any deviations generated to confirm that investigation and
resolutions are complete
Cooperate with Validation Specialist to investigate, justify, and correct any deviation
encountered during Validation execution
Review and approve Final Report
Maintain original validation documentation, except for drawings and equipment manuals
that will remain in the equipment information files
Store the Validation Package in a designated filing area
5.3 Facility Dept.
Review and approve documents for the validation exercise
Coordinate efforts and resources to perform the validation activities
Supply documentation and tools needed for the protocol execution
Provide training in this protocol to all employees involved (internal and external) during the
execution of this protocol and ensure that all signatures are collected on Signature Log
Sheet
Assist to document, investigate, justify, and correct any deviation encountered during the
IQ protocol execution
Review and approve validation Final Report
Provide technical support for trouble shooting during the execution

6.0 METHODOLOGY
6.1 Verification Data Sheet
All data resulting from test execution will be entered in Verification Data Sheets that will predefine the objective(s) to be attained with the verification, the procedure that will be followed
to reach such objective(s), the reference material to be used, and the criteria to evaluate as
to accept or not the testing results. All data entry will be properly signed and dated by the
executor in the Performed By and Date spaces. In cases where a Field Verification is
requested, a Fail condition will be applied to unverifiable information.
The comments/observations section included in each Data Collection Form will be used to
describe any additional information considered of importance for describing the validated
condition and/or discrepancies and resolution activities produced during the execution. The
comments/observations included must be signed or initialed and dated.
When the test execution is finished, a subject matter expert will sign and date on the
Reviewed by and Date spaces respectively, to state the completeness and correctness of
the data.
6.2 Deviation Report
The following deviations must be documented using the Deviation Report Form attached to
this protocol:
Results invalidated and/or not in compliance with their pre-established Acceptance Criteria
Testing procedure and/or sampling plan not followed or that could not be completed as
planned
These deviations will be handled as per ___ ___ PR
The investigation process due to deviated sampling results will be handled by contract
laboratory, following their own investigation procedures. These incidents will be informed to
who oversees the validation project in ___ ___, ___ PR, which in turn will open a deviation
report to follow the lifecycle of the investigation and to implement any possible changes due
to investigation resolution.
Typographic, text edit and syntax errors will be documented as such in the Comments
section under the corresponding test script, and considered as a minor issue that may not
invalidate a test or become cause for writing a deviation report. These will be explained in the
Final Report.
6.3 Signature Log Sheet
Each individual who signs or initials any page included in this protocol shall be identified
using the Signature Log Sheet by type/printed name, full signature, written initials and
department represented.
6.4 Test Instruments Calibration
All testing equipment used during for the execution shall be currently calibrated with
documented evidence of its up to date calibration status. Copies of the calibration
certificates shall be attached to the protocol and referred to the applicable test script.

7.0 EQUIPMENT/PROCESS DESCRIPTION


Purified Water is water obtained by distillation, ion-exchange treatment, reverse osmosis, and
other suitable processes. It is prepared from water complying with the regulations of U.S.
Environmental Protection Agency (EPA) with respect to drinking water. It contains no added
substances.
The Purified Water system includes the following equipment, along with associated components:

30 um filters (2)

6, 000 and 8, 000 Gal. Tanks

1 um filters (4)

Distribution Pumps (4)

0.2 um filters (4)

Dual Reverse Osmosis unit

Dual Softener unit

Dual Mix Bed unit

Ozone Generator

UV lamps (4)

Ozone Destructor

Degasification unit

Microza filters (18)

7.1 Water Softener


The Water Softener reduces the levels of calcium and other scale creating elements from the
process stream. Water softeners also remove aluminum, copper and other trace metals. The
removal process occurs by ion exchange. The softener vessel is filled with sodium form cation
resin. The calcium, magnesium, barium, strontium, and other ions removed by the resin are
replaced with sodium ions. The cation resin has a fixed capacity for ion removal and must be
regenerated when that capacity has been exhausted.
7.2 Ozone Generator
The Ozone Generator is employed to produce the Ozone used to sanitize the Softened Water
that passes through to the 6,000 Gallon Tank.
7.3 Reverse Osmosis
The Reverse Osmosis unit processes water by means of semi-permeable membranes, which
allow pressurized water to freely pass through the membranes, but almost totally reject
dissolved and suspended substances in the feed water.
7.4 Mixed Bed
The Mixed Bed de-mineralizes water by using the ion exchange process. The influent water
passes through a bed of Cation and Anion resin that are intimately mixed. The mixed bed
configuration functions similarly to a two-bed configuration in regards to the ion exchange
process; however, it is much more efficient and therefore produces water of much greater
purity.
7.5 Ozone Destructor
The Ozone Destructor employs ultraviolet light to reduce the ozone level to a safe preset level
before exiting the skid to the Service Points of Use. Ozone reduction is done by breakage of
the O3 bonds at the ultraviolet spectrum.

As per United States Pharmacopeia (USP) standards

7.6 De-gasifier
De-gasifier membranes are employed to reduce the oxygen level of the water. Membrane
contactors make it possible to transfer gas from an aqueous stream without dispersion. By
virtue of surface tension, the water on one side of the membrane is exposed to the gas side of
the membrane with no liquid transfer, providing a large surface area for gas/liquid contact and
transfer. Dissolved O2 passes from the water surface into the gas side by diffusion and is
swept out by a combined vacuum/air flow.
7.7 UV lights
Ultraviolet lamps produce UV-C (germicidal UV), which is a radiation that when harmful
microbes are exposed to the UV rays, scrambles the DNA structure of the organism,
rendering it sterile and can no longer reproduce.
Almost all of a UV lamps output is concentrated in the 254 nanometers (nm) region in order to
take full advantage of the germicidal properties of this wavelength. The lamp is mounted such
that water passing through a flow chamber is exposed to the UV-C light rays.
7.8 Filters
At the first stage, the raw water enters a 30 m pre-filter to trap any heavy sediment before it
enters the softeners. The 1 m filters will act as a resin trap and removes suspended from the
softeners. The absolute 0.2 micron rated filters significantly enhances the water quality with its
capacity to remove the majority of microorganisms. The Microza ultra filters that are at the end
of the purified water system uses fiber hollow technology that will remove endotoxins and
viruses.
7.9 Distribution Pumps
Two pairs of distribution pumps will provide constant flow of the processed water throughout
the Purified Water System pipelines. Although its functionality will not contribute directly to the
processing of Purified Water, by providing a constant flow will indeed significantly reduce the
chances of microbial growth due to stagnant water.
7.10 Tanks
Two storage tanks will provide storage capacity to the Purified Water System. A 6,000 gallon
tank will store ozone-treated softened water that will supply constant feed to the dual R.O.
unit, while an 8,000 gallon tank will store water post reverse osmosis and de-ozonization
treatment, which will supply constant feed to the main loop.

With this configuration in place, a Purified Water (USP, EP) quality is intended to be achieved through the following processes:
Filtration (by means of 30 um filters, 1 um filters, 0.2 um filters, and R.O. Unit, and Microza filters)
Ion exchange (by means of Softener and Mix Bed)
Sanitation (by means of Ozone Injection and UV light radiation)
Degasification (by means of a de-gasifier unit)

APPENDICES

DEVIATION DESCRIPTION

APPENDIX I: DEVIATION REPORT


Deviation Number: _________________
Test Description/Test Number:
Deviation Area:

I/Q O/Q P/Q

Deviation reported by:_________________________________

Date:

_________________

ENGINEERING INVESTIGATION

Attach additional pages, if necessary


Root Cause:

Manpower

Methods

Equipment

Materials

Environment

CORRECTIVE / PREVENTIVE ACTION

Evaluation performed by:____________________________________

Date:

_________________

Testing required after Corrective action implemented? (YES/NO) ______________


Test results (PASS/FAIL/NA) ________________
Performed by: _______________________________________

Date:

_______________________

Comments:

Reviewed by ______________________________________

Date:

____________________________

APPENDIX II: SIGNATURE IDENTIFICATION LOG SHEET


This sheet is intended to record each individual who takes part of the execution process and is not
included in the front page. The scope of this sheet applies to anyone who signs or initials any page
included in the attached qualification documents. Each person shall be identified by typed or printed
name, full signature, written initials, and department represented.
NAME

SIGNATURE

INITIALS

DEPARTMENT

APPENDIX III: TESTING INSTRUMENTS LOG SHEET


This sheet is intended to record all field test instrument that assists in the execution process.

INSTRUMENT ID

DESCRIPTION

TEST ID

CALIBRATION
DATE/DUE DATE

COPY OF
CERTIFICATE
ATTACHED?
(YES/NO)

PERFORMED
BY/DATE

VERIFICATION DATA SHEETS


INSTALLATION QUALIFICATION

MAIN COMPONENT VERIFICATION

IQ-01

Objective:

Assure that all main and auxiliary components of the Purified Water System are as per
manufacturer/vendor specifications (Manuals, Spec sheets, P & IDs, etc.)

Procedure:
a. Per equipment, collect and document the required information thru physical inspection (tag,
engrave, plate, sticker, etc)
b. Evaluate findings against specifications
References Required:

Note: Vendor/Manufacturer documentation (Manuals, Spec sheets, P & IDs, etc.) does not
count as Actual Result reference

Acceptance Criteria:

Actual results match expected results as per manufacturer written specifications

MAIN COMPONENT VERIFICATION

IQ-01
Filter set 1A & 1B

SPEC

EXPECTED
RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

1A

Tag ID
Cartridge
Manufacturer
Cartridge Part
No.
Housing
Manufacturer
Housing
Part No.
Quantity
Tag ID

1B

Cartridge
Manufacturer
Cartridge Part
No.
Housing
Manufacturer
Housing
Part No.
Quantity
Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAIN COMPONENT VERIFICATION

IQ-01
Filter set 2A & 2B

SPEC

EXPECTED
RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

2A

Tag ID
Cartridge
Manufacturer
Cartridge Part
No.
Housing
Manufacturer
Housing
Part No.
Quantity
Tag ID

2B

Cartridge
Manufacturer
Cartridge Part
No.
Housing
Manufacturer
Housing
Part No.
Quantity
Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAIN COMPONENT VERIFICATION

IQ-01
Filter set 3A & 3B

SPEC

EXPECTED
RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

3A

Tag ID
Cartridge
Manufacturer
Cartridge Part
No.
Housing
Manufacturer
Housing
Part No.
Quantity
Tag ID

3B

Cartridge
Manufacturer
Cartridge Part
No.
Housing
Manufacturer
Housing
Part No.
Quantity
Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAIN COMPONENT VERIFICATION

IQ-01
Filter set 4A & 4B

SPEC

EXPECTED
RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Tag ID

4A

Cartridge
Manufacturer
Cartridge Part
No.
Housing
Manufacturer
Housing
Part No.
Quantity
Tag ID

4B

Cartridge
Manufacturer
Cartridge Part
No.
Housing
Manufacturer
Housing
Part No.
Quantity
Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAIN COMPONENT VERIFICATION

IQ-01
Filter set 5A & 5 B

SPEC

EXPECTED
RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Tag ID

5A

Cartridge
Manufacturer
Cartridge Part
No.
Housing
Manufacturer
Housing
Part No.
Quantity
Tag ID

5B

Cartridge
Manufacturer
Cartridge Part
No.
Housing
Manufacturer
Housing
Part No.
Quantity
Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAIN COMPONENT VERIFICATION

IQ-01
Ozone Generator

SPEC

EXPECTED
RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Tag ID
Manufacturer
Model
Serial No.

Booster pump

Tag ID
Manufacturer
Model

Recirculation pump

Serial No.
Tag ID
Manufacturer
Model
Serial No.
Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAIN COMPONENT VERIFICATION

IQ-01
Ozone Destructor

SPEC

EXPECTED
RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Tag ID
Manufacturer
Model
Serial No.

UV light

Tag ID
Manufacturer
Model
Serial No.
Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAIN COMPONENT VERIFICATION

IQ-01
Dual Softener unit

SPEC

EXPECTED
RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Unit A

Tag ID

Manufacturer
Model
Serial No.

Unit B

Tag ID

Manufacturer
Model

Resin

Control Panel

Serial No.

Manufacturer

Model

Type

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAIN COMPONENT VERIFICATION

IQ-01

Dual Softener unit (Brine Tank)


SPEC

EXPECTED
RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Tag ID

Manufacturer

Model

Serial No.
Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAIN COMPONENT VERIFICATION

IQ-01
6,000 Gal. Tank

SPEC

EXPECTED
RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Tag ID

Manufacturer

Description

Vent Filter

Cartridge
Manufacturer
Cartridge
Part No.
Housing
Manufacturer
Housing
Part No.

Level

Manufacturer

Part No.
Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAIN COMPONENT VERIFICATION

IQ-01
Distribution Pumps (1A, 1B)

SPEC

EXPECTED
RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Tag ID

1A

Manufacturer

Model

Serial No.

Tag ID

2A

Manufacturer

Model

Serial No.
Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAIN COMPONENT VERIFICATION

IQ-01
8,000 Gal. Tank

SPEC

EXPECTED
RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Tag ID

Manufacturer

Description

Vent Filter

Cartridge
Manufacturer
Cartridge
Part No.
Housing
Manufacturer
Housing
Part No.

Level

Manufacturer

Part No.
Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAIN COMPONENT VERIFICATION

IQ-01
Distribution Pumps (2A, 2B)

SPEC

EXPECTED
RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Tag ID

2A

Manufacturer

Model

Serial No.

Tag ID

2B

Manufacturer

Model

Serial No.
Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAIN COMPONENT VERIFICATION

IQ-01
UV lamps (1A, 1B)

SPEC

EXPECTED
RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Tag ID

1A

Manufacturer

Model

Serial No.

Tag ID

1B

Manufacturer

Model

Serial No.
Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

EQUIPMENT VERIFICATION

IQ-01
UV lamps (2A, 2B)

SPEC

EXPECTED
RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Tag ID

2A

Manufacturer

Model

Serial No.

Tag ID

2B

Manufacturer

Model

Serial No.
Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAIN COMPONENT VERIFICATION

IQ-01

Dual Reverse Osmosis (Service unit A)


SPEC

EXPECTED RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Tag ID
Manufacturer
Model
Serial No.

Feed Pump

Tag ID
Manufacturer
Model

Control Panel

Antiscalant Dosing System

Serial No.
Tag ID
Manufacturer
Model
Serial No.
Manufacturer
Model

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAIN COMPONENT VERIFICATION

IQ-01

Dual Reverse Osmosis (Service unit B)


SPEC

EXPECTED RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Tag ID
Manufacturer
Model
Serial No.

Feed Pump

Tag ID
Manufacturer
Model

Control Panel

Antiscalant Dosing System

Serial No.
Tag ID
Manufacturer
Model
Serial No.
Manufacturer
Model

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAIN COMPONENT VERIFICATION

IQ-01

Dual R.O. unit (Cleaning Skid)


SPEC

EXPECTED RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Tag ID
Manufacturer
Model
Serial No.

Cleaning Pump

Tag ID
Manufacturer
Model
Serial No.
Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAIN COMPONENT VERIFICATION

IQ-01
De-gasification unit

SPEC

EXPECTED
RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Tag ID

Manufacturer

Model

Serial No.

Pump

Tag ID
Manufacturer
Model
Serial No.
Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAIN COMPONENT VERIFICATION

IQ-01
Dual Mixed Bed unit

SPEC

EXPECTED
RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Tag ID

Unit A

Manufacturer

Model

Serial No.

Tag ID

Unit B

Manufacturer

Model

Serial No.

Acid &
Caustic

Control Panel

Manufacturer

Model

Type

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAIN COMPONENT VERIFICATION

IQ-01

Microza ultra filtration filters


SPEC

EXPECTED
RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Tag ID

Manufacturer

Part No.

Serial No.
Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

DOCUMENT INVENTORY VERIFICATION

IQ-02

Objective:

Assure that all the basic literature required for the system operation/maintenance of the Purified
Water system is available and properly stored

Procedure:
a. Per equipment, collect all related documentation
b. Document all relevant information according to Document Info column
c. If any of the document type is not applicable, write an Not Apply to the Document Info
column and explain in the Comments/Observations section
References Required:

Manufacturers Documentation - Installation and Operational Manuals, Wiring Diagrams, Spare


Parts List, P & IDs, etc.

Vendors Documentation - Purchase Order, etc.

Acceptance Criteria:

At least the basic literature (see document type) was found for all equipment and was found to
be properly stored

Not applicable document type was properly explained

DOCUMENT INVENTORY VERIFICATION

IQ-02

Filter set 1A & 1B


DOCUMENT
TYPE

DOCUMENT INFO
(DOC #, TITLE, REV., LOCATION)

DOCUMENT STORAGE
(LOCATION)

PERFORMED
BY/DATE

Installation and
Operation
Manual

Purchase Order

Drawings

P & IDs

Other
Documents

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________
If NO, refer to Deviation # __________
Reviewed by:

Date:

DOCUMENT INVENTORY VERIFICATION

IQ-02

Filter set 2A & 2B


DOCUMENT
TYPE

DOCUMENT INFO
(DOC #, TITLE, REV., LOCATION)

DOCUMENT STORAGE
(LOCATION)

PERFORMED
BY/DATE

Installation and
Operation
Manual

Purchase Order

Drawings

P & IDs

Other
Documents

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________
If NO, refer to Deviation # __________
Reviewed by:

Date:

DOCUMENT INVENTORY VERIFICATION

IQ-02

Filter set 3A & 3B


DOCUMENT
TYPE

DOCUMENT INFO
(DOC #, TITLE, REV., LOCATION)

DOCUMENT STORAGE
(LOCATION)

PERFORMED
BY/DATE

Installation and
Operation
Manual

Purchase Order

Drawings

P & IDs

Other
Documents

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________
If NO, refer to Deviation # __________
Reviewed by:

Date:

DOCUMENT INVENTORY VERIFICATION

IQ-02

Filter set 3A & 3B


DOCUMENT
TYPE

DOCUMENT INFO
(DOC #, TITLE, REV., LOCATION)

DOCUMENT STORAGE
(LOCATION)

PERFORMED
BY/DATE

Installation and
Operation
Manual

Purchase Order

Drawings

P & IDs

Other
Documents

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________
If NO, refer to Deviation # __________
Reviewed by:

DOCUMENT INVENTORY VERIFICATION

Date:

IQ-02

Filter set 4A & 4B


DOCUMENT
TYPE

DOCUMENT INFO
(DOC #, TITLE, REV., LOCATION)

DOCUMENT STORAGE
(LOCATION)

PERFORMED
BY/DATE

Installation and
Operation
Manual

Purchase Order

Drawings

P & IDs

Other
Documents

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________
If NO, refer to Deviation # __________
Reviewed by:

DOCUMENT INVENTORY VERIFICATION

Date:

IQ-02

Filter set 5A & 5B


DOCUMENT
TYPE

DOCUMENT INFO
(DOC #, TITLE, REV., LOCATION)

DOCUMENT STORAGE
(LOCATION)

PERFORMED
BY/DATE

Installation and
Operation
Manual

Purchase Order

Drawings

P & IDs

Other
Documents

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________
If NO, refer to Deviation # __________
Reviewed by:

Date:

DOCUMENT INVENTORY VERIFICATION

IQ-02

Dual Softener unit


DOCUMENT
TYPE

DOCUMENT INFO
(DOC #, TITLE, REV., LOCATION)

DOCUMENT STORAGE
(LOCATION)

PERFORMED
BY/DATE

Installation and
Operation
Manual
Purchase Order

Electrical
Drawings
Mechanical
Drawings

P & IDs
PLC Software
Backup &
Report
MSDS

Other
Documents
Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________
If NO, refer to Deviation # __________
Reviewed by:

Date:

DOCUMENT INVENTORY VERIFICATION

IQ-02
6,000 Gal. Tank

DOCUMENT
TYPE

DOCUMENT INFO
(DOC #, TITLE, REV., LOCATION)

DOCUMENT STORAGE
(LOCATION)

PERFORMED
BY/DATE

Installation and
Operation
Manual

Purchase Order

Drawings

P & IDs

Other
Documents

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________
If NO, refer to Deviation # __________
Reviewed by:

Date:

DOCUMENT INVENTORY VERIFICATION

IQ-02

Distribution Pumps (1A, 1B)


DOCUMENT
TYPE

DOCUMENT INFO
(DOC #, TITLE, REV., LOCATION)

DOCUMENT STORAGE
(LOCATION)

PERFORMED
BY/DATE

Installation and
Operation
Manual

Purchase Order

Electrical
Drawings

Mechanical
Drawings

P & IDs

Other
Documents

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________
If NO, refer to Deviation # __________
Reviewed by:

Date:

DOCUMENT INVENTORY VERIFICATION

IQ-02
8,000 Gal. Tank

DOCUMENT
TYPE

DOCUMENT INFO
(DOC #, TITLE, REV., LOCATION)

DOCUMENT STORAGE
(LOCATION)

PERFORMED
BY/DATE

Installation and
Operation
Manual

Purchase Order

Drawings

P & IDs

Other
Documents

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________
If NO, refer to Deviation # __________
Reviewed by:

Date:

DOCUMENT INVENTORY VERIFICATION

IQ-02

Distribution Pumps (2A, 2B)


DOCUMENT
TYPE

DOCUMENT INFO
(DOC #, TITLE, REV., LOCATION)

DOCUMENT STORAGE
(LOCATION)

PERFORMED
BY/DATE

Installation and
Operation
Manual

Purchase Order

Electrical
Drawings

Mechanical
Drawings

P & IDs

Other
Documents

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________
If NO, refer to Deviation # __________
Reviewed by:

Date:

DOCUMENT INVENTORY VERIFICATION

IQ-02

Ozone Generator
DOCUMENT
TYPE

DOCUMENT INFO
(DOC #, TITLE, REV., LOCATION)

DOCUMENT STORAGE
(LOCATION)

PERFORMED
BY/DATE

Installation and
Operation
Manual

Purchase Order

Electrical
Drawings

Mechanical
Drawings

P & IDs

PLC Software
Backup &
Report

Other
Documents
Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________
If NO, refer to Deviation # __________
Reviewed by:

Date:

DOCUMENT INVENTORY VERIFICATION

IQ-02

Ozone Destructor
DOCUMENT
TYPE

DOCUMENT INFO
(DOC #, TITLE, REV., LOCATION)

DOCUMENT STORAGE
(LOCATION)

PERFORMED
BY/DATE

Installation and
Operation
Manual

Purchase Order

Electrical
Drawings

P & IDs

PLC Software
Backup &
Report

Other
Documents

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________
If NO, refer to Deviation # __________
Reviewed by:

Date:

DOCUMENT INVENTORY VERIFICATION

IQ-02

UV lamps (1A, 1B, 2A, 2B)


DOCUMENT
TYPE

DOCUMENT INFO
(DOC #, TITLE, REV., LOCATION)

DOCUMENT STORAGE
(LOCATION)

PERFORMED
BY/DATE

Installation and
Operation
Manual

Purchase Order

Electrical
Drawings

P & IDs

Other
Documents

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________
If NO, refer to Deviation # __________
Reviewed by:

Date:

DOCUMENT INVENTORY VERIFICATION

IQ-02

Dual Reverse Osmosis unit


DOCUMENT
TYPE

DOCUMENT INFO
(DOC #, TITLE, REV., LOCATION)

DOCUMENT STORAGE
(LOCATION)

PERFORMED
BY/DATE

Installation and
Operation
Manual
Purchase Order

Electrical
Drawings
Mechanical
Drawing

P & IDs
PLC Software
Backup &
Report
MSDS

Other
Documents
Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________
If NO, refer to Deviation # __________
Reviewed by:

Date:

DOCUMENT INVENTORY VERIFICATION

IQ-02

Degasification unit
DOCUMENT
TYPE

DOCUMENT INFO
(DOC #, TITLE, REV., LOCATION)

DOCUMENT STORAGE
(LOCATION)

PERFORMED
BY/DATE

Installation and
Operation
Manual

Purchase Order

Electrical
Drawings

Mechanical
Drawings

P & IDs

Other
Documents
Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________
If NO, refer to Deviation # __________
Reviewed by:

Date:

DOCUMENT INVENTORY VERIFICATION

IQ-02

Dual Mixed Bed unit


DOCUMENT
TYPE

DOCUMENT INFO
(DOC #, TITLE, REV., LOCATION)

DOCUMENT STORAGE
(LOCATION)

PERFORMED
BY/DATE

Installation and
Operation
Manual

Purchase Order

Electrical
Drawings

P & IDs

PLC Software
Backup &
Report

Other
Documents

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________
If NO, refer to Deviation # __________
Reviewed by:

Date:

DOCUMENT INVENTORY VERIFICATION

IQ-02

Microza ultra filtration filters


DOCUMENT
TYPE

DOCUMENT INFO
(DOC #, TITLE, REV., LOCATION)

DOCUMENT STORAGE
(LOCATION)

PERFORMED
BY/DATE

Installation and
Operation
Manual

Purchase Order

Electrical
Drawings

P & IDs

Other
Documents

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) ________
If NO, refer to Deviation # __________
Reviewed by:

Date:

DRAWING VERIFICATION

IQ-03

Objective:

Assure concordance between drawings (P & I Ds and Electrical Schematics, etc.) and field
installation of the Purified Water System

Procedure:
a. Collect and document the drawings found thru IQ - 02: Document Inventory Verification
b. Verify against field installation by performing a physical inspection and redline drawings, if
discrepancy occurs
c. Sign, date & submit discrepancies to Facilities Dept. for review
d. Upon review, determine if drawings and/or field installation needs to be updated
e. Attach verified drawings to this protocol
References Required:

Process and Instrument Diagrams (P & I Ds)

Electrical Schematics

Acceptance Criteria:

Drawings match field installation and vice versa

Discrepancies between drawings and field installation were satisfactorily resolved by submitting
changes and updating drawings and/or field installation

DRAWING VERIFICATION

IQ-03
Sheet ______ of ______
Use additional pages as necessary

DRAWING
TYPE & ID

TITLE & REVISION

REDLINED?
(YES/NO)

UPDATE?
(DWG, FLD, NA)

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

SYSTEM DESIGN VERIFICATION

IQ-04

Objective:

Assure that the installation design is in compliance with the specified requirements for systems
capable of producing Purified Water

Procedure:

Verify system installation as per specifications by performing a physical verification and/or


providing documented evidence

Document findings and evaluate against expected results

Note: This verification is best performed during Drawing Verification


References Required:

P & IDs
Material Safety Data Sheets
Chemical Analysis Sheets

Acceptance Criteria:

Actual results match expected results as per Purified Water specifications

SYSTEM DESIGN VERIFICATION


SPEC

EXPECTED RESULT

Feed water

The raw water source supplied to


the system must be from Well or
City Water

Processing

The system contains equipment


capable of performing Deionization
and Reverse Osmosis or
Distillation.

IQ-04
ACTUAL RESULT

PASS/FAIL

Piping will provide constant


circulation of Purified water.

Piping

Contact
material

Piping does not have an unused


portion greater in length than six
diameters of the unused pipe
measured from the axis of the pipe
in use (dead leg).

All material in direct contact shall be


non-reactive to Purified Water.

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

PERFORMED
BY/DATE

PLACEMENT VERIFICATION

IQ-05

Objective:

Assure that the equipments have the appropriate conditions to perform setup and maintenance
and to operate accordingly.

Procedure:

Per equipment, verify field conditions by performing a physical inspection as per expected
results

Document and evaluate findings against expected results

References Required:

Skid Drawings

Acceptance Criteria:

Actual results match expected results as per ___ requirements

PLACEMENT VERIFICATION

IQ-05
SKID #1 - Filter Set 1A, 1B

SPEC

EXPECTED RESULT

Position

The equipment shall


be located along open
type waste drains.

Environment

The equipment is not


placed on direct
sunlight or other
sources of heat.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

PLACEMENT VERIFICATION

IQ-05
SKID #2 - Filter set 2A, 2B

SPEC

EXPECTED RESULT

Position

The equipment shall


be located along open
type waste drains.

Environment

The equipment is not


placed on direct
sunlight or other
sources of heat.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

PLACEMENT VERIFICATION

IQ-05

SKID #3 - Distribution Pumps 1A, 1B; UV lamps 1A, 1B & Filter set 3A, 3B
SPEC

EXPECTED RESULT

Position

The equipment shall


be located along open
type waste drains.

Environment

The equipment is not


placed on direct
sunlight or other
sources of heat.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

PLACEMENT VERIFICATION

IQ-05
SKID #4 - R. O. Piping/Valves

SPEC

EXPECTED RESULT

Position

The equipment shall


be located along open
type waste drains.

Environment

The equipment is not


placed on direct
sunlight or other
sources of heat.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

PLACEMENT VERIFICATION

IQ-05
SKID 5 - Pumps 2A, 2B

SPEC

EXPECTED RESULT

Position

The equipment shall


be located along open
type waste drains.

Environment

The equipment is not


placed on direct
sunlight or other
sources of heat.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

PLACEMENT VERIFICATION

IQ-05
SKID 6 - UV lamps 2A, 2B & Filter 4A, 4B

SPEC

EXPECTED RESULT

Position

The equipment shall


be located along open
type waste drains.

Environment

The equipment is not


placed on direct
sunlight or other
sources of heat.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

PLACEMENT VERIFICATION

IQ-05
SKID 7 - Filter set 5A, 5B

SPEC

EXPECTED RESULT

Position

The equipment shall


be located along open
type waste drains.

Environment

The equipment is not


placed on direct
sunlight or other
sources of heat.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

PLACEMENT VERIFICATION

If NO, refer to Deviation # __________


Date:

IQ-05

Water Softener Skid


SPEC

EXPECTED RESULT

Position

The equipment shall


be located along open
type waste drains.

Environment

The equipment is not


placed on direct
sunlight or other
sources of heat.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

PLACEMENT VERIFICATION

If NO, refer to Deviation # __________


Date:

IQ-05

Ozone Generator Skid


SPEC

EXPECTED RESULT

Position

The equipment shall


be located along open
type waste drains.

Environment

The equipment is not


placed on direct
sunlight or other
sources of heat.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

PLACEMENT VERIFICATION

IQ-05
Ozone Destructor Skid

SPEC

EXPECTED RESULT

Position

The equipment shall


be located along open
type waste drains.

Environment

The equipment is not


placed on direct
sunlight or other
sources of heat.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

PLACEMENT VERIFICATION

If NO, refer to Deviation # __________


Date:

IQ-05

R.O. Skid
SPEC

EXPECTED RESULT

Position

The equipment shall


be located along open
type waste drains.

Environment

The equipment is not


placed on direct
sunlight or other
sources of heat.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

PLACEMENT VERIFICATION

If NO, refer to Deviation # __________


Date:

IQ-05

R.O. Cleaning Skid


SPEC

EXPECTED RESULT

Position

The equipment shall


be located along open
type waste drains.

Environment

The equipment is not


placed on direct
sunlight or other
sources of heat.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

UTILITY VERIFICATION
Objective:

If NO, refer to Deviation # __________


Date:

IQ-06

Assure that the installed utility meets the Purified Water System requirements

Procedure:

Utility Verification

a. Per equipment, perform utility verification as per expected results by using a calibrated test
instrument (when required), and document results
b. Attach copy of instrument calibration certificate and ensure it is up to date
c. Ensure that each utility connection is properly labeled

Electrical Verification

a. Perform verification as per Utility Verification thru a certified electrician


b. Attach copy of Electricians license and ensure it is up to date
Note: All readings will apply a 10% tolerance
References Required:

Test Instruments calibration certificates

Copy of Electricians license

Acceptance Criteria:

Utilities comply with expected results (manufacturer specifications)

All calibrations/certifications are up to date

UTILITY VERIFICATION

IQ-06
Dual Softener unit

ELECTRICAL
SPECS

EXPECTED RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Voltage
Phase
Amperage
Frequency
Panel ID
To be filled by a licensed electrician or electrical engineer with PE license

Does electrical installation comply with NEC standards? (YES/NO) _______________


Electrician signature: ____________________________

OTHER SPECS

EXPECTED RESULT

License Number: ____________________________

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Compressed Air
Chemical
Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

UTILITY VERIFICATION

IQ-06

Transformer

P-OZ2

P-OZ1

OZ-1

Ozone Generator
ELECTRICAL
SPECS
Voltage
Phase
Amperage
Frequency
Panel ID
Voltage
Phase
Amperage
Frequency
Panel ID
Voltage
Phase
Amperage
Frequency
Panel ID
Voltage

EXPECTED
RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Phase
Amperage
Frequency
Panel ID

To be filled by a licensed electrician or electrical engineer with PE license

Does electrical installation comply with NEC standards? (YES/NO) _______________


Electrician signature: ___________________________
OTHER SPECS

EXPECTED
RESULT

Compressed Air

90-110 psig

License Number: ___________________________

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

UTILITY VERIFICATION

IQ-06
Ozone Destructor

ELECTRICAL
SPECS

EXPECTED RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Voltage
Phase
Amperage
Frequency
Panel ID
Bulb installation
To be filled by a licensed electrician or electrical engineer with PE license

Does electrical installation comply with NEC standards? (YES/NO) _______________


Electrician signature: ____________________________

License Number: ____________________________

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

UTILITY VERIFICATION

IQ-06
UV lamps (1A, 1B)

ELECTRICAL
SPECS

EXPECTED RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Voltage
Phase
Amperage
Frequency
Panel ID
Bulb installation
To be filled by a licensed electrician or electrical engineer with PE license

Does electrical installation comply with NEC standards? (YES/NO) _______________


Electrician signature: ____________________________

License Number: ____________________________

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

UTILITY VERIFICATION

IQ-06
UV lamps (2A, 2B)

ELECTRICAL
SPECS

EXPECTED RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Voltage
Phase
Amperage
Frequency
Panel ID
Bulb installation
To be filled by a licensed electrician or electrical engineer with PE license

Does electrical installation comply with NEC standards? (YES/NO) _______________


Electrician signature: ____________________________

License Number: ___________________________

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

UTILITY VERIFICATION

IQ-06
Distribution Pumps (1A, 1B)

ELECTRICAL
SPECS

EXPECTED RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Voltage

Phase

Amperage

Frequency

Panel ID
To be filled by a licensed electrician or electrical engineer with PE license

Does electrical installation comply with NEC standards? (YES/NO) _______________


Electrician signature: ____________________________

License Number: ___________________________

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

UTILITY VERIFICATION

IQ-06
Distribution Pumps (2A, 2B)

ELECTRICAL
SPECS

EXPECTED RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Voltage

Phase

Amperage

Frequency

Panel ID
To be filled by a licensed electrician or electrical engineer with PE license

Does electrical installation comply with NEC standards? (YES/NO) _______________


Electrician signature: ____________________________

License Number: ___________________________

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

UTILITY VERIFICATION

IQ-06
Dual Reverse Osmosis unit

ELECTRICAL
SPECS

EXPECTED
RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Voltage

Voltage

Unit A

Phase

Phase

Amperage

Amperage

Frequency
Panel ID
1

Voltage

Voltage

Unit B

Phase

Phase

Amperage

Amperage

Frequency
Panel ID
To be filled by a licensed electrician or electrical engineer with PE license

Does electrical installation comply with NEC standards? (YES/NO) _______________


Electrician signature: ____________________________
OTHER SPECS

EXPECTED RESULT

Compressed Air

80-110 psig

Comments/Observations:

License Number: _____________________________

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Assembly power to assembly panel (PLC)


2
Plant power to assembly power

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

UTILITY VERIFICATION

IQ-06
Dual Reverse Osmosis unit (Cleaning Skid)

ELECTRICAL
SPECS

EXPECTED RESULT

ACTUAL RESULT

PASS/FAIL

PERFORME
D BY/DATE

Voltage
Phase
Amperage
Frequency
Panel ID
To be filled by a licensed electrician or electrical engineer with PE license

Does electrical installation comply with NEC standards? (YES/NO) _______________


Electrician signature: ____________________________
OTHER SPECS

EXPECTED RESULT

License Number: _________________________

ACTUAL RESULT

PASS/FAIL

PERFORME
D BY/DATE

Chemicals
Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

UTILITY VERIFICATION

IQ-06
Dual Reverse Osmosis unit (pumps)

ELECTRICAL
SPECS

EXPECTED RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

R.O Feed Pump

Voltage
Phase
Amperage
Frequency
Panel ID

R.O. Cleaning
Pump

Voltage
Phase
Amperage
Frequency
Panel ID

ADS Pump

Voltage
Phase
Amperage
Frequency
Panel ID
To be filled by a licensed electrician or electrical engineer with PE license

Does electrical installation comply with NEC standards? (YES/NO) _______________


Electrician signature: ____________________________

License Number: ____________________________

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

UTILITY VERIFICATION

If NO, refer to Deviation # __________


Date:

IQ-06

Degasification unit
ELECTRICAL
SPECS

EXPECTED
RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Degas Panel

Voltage
Phase
Amperage
Frequency
Panel ID

Vacuum Pump

Voltage
Phase
Amperage
Frequency
Panel ID
To be filled by a licensed electrician or electrical engineer with PE license

Does electrical installation comply with NEC standards? (YES/NO) _______________


Electrician signature: ___________________________
OTHER SPECS

EXPECTED
RESULT

License Number: _____________________________

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Compressed Air
Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

UTILITY VERIFICATION

IQ-06
Dual Mixed Bed unit

ELECTRICAL
SPECS

EXPECTED RESULT

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Voltage
Phase
Amperage
Frequency
Panel ID
To be filled by a licensed electrician or electrical engineer with PE license

Does electrical installation comply with NEC standards? (YES/NO) _______________


Electrician signature: ___________________________
OTHER SPECS

EXPECTED RESULT

License Number: ____________________________

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Compressed Air
(control panel)

Clean Compressed
Air
(MB column)

Chemicals
Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

INSTRUMENTATION VERIFICATION

IQ-07

Objective:

Assure that all the instrumentation installed in the Purified Water System that requires
calibration are added to a calibration program

Procedure:
a. Inspect all instruments evaluated with the Calibration Program Addition Form and verify that all
instruments installed at the Purified Water System were included
b. Record instruments (ID & type) that requires calibration according to the Calibration Program
Addition Form
c. Verify if the instrument that requires calibration is currently calibrated and record finding
d. Attach calibration certificate of all calibrated instruments
References Required:
Acceptance Criteria:

Instruments that required calibration were included in site calibration program

Instruments are currently calibrated

INSTRUMENTATION VERIFICATION

IQ-07
Sheet ______ of ______

Use additional pages as necessary

INSTRUMENT ID

INSTRUMENT
TYPE

IT IS CURRENTLY
CALIBRATED?
(YES/NO/NA)

CALIBRATION
DUE DATE

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAINTENANCE VERIFICATION

IQ-08

Objective:

Assure that the Purified Water System is included in a Preventive Maintenance Program and a
spare parts list exists

Procedure:
a. Per equipment, verify and document the required information by collecting documented
evidence (i.e. PM checklist, PM schedule) of the inclusion of the Purified Water System
components into ___s Preventive Maintenance Program
b. Collect the Spare Parts list; verify & document the required information
c. Collect the Lubricants list; verify & document the required information
d. If lubricant specifications is not applicable, write a Not Apply to the Actual Result column and
explain in the Comments/Observations section
References Required:

Evidence of PMP inclusion - PM checklist, PM schedule, PM program printouts, etc.

Spare Parts list

Lubricants list

FOP 4.1 Scheduled Preventive Maintenance

Acceptance Criteria:

All equipment is included in a PM schedule

All equipment has spare part list

Not applicable lubricant requirements were properly explained

MAINTENANCE VERIFICATION

IQ-08
Filter set 1A &1B

SPEC

EXPECTED RESULT

PMP

A PM checklist,
schedule or similar is
available as evidence
of inclusion into the
PM program.

Spare
Parts

Spare parts inventory


is available for the
equipment.

Lubricants

Lubricants inventory is
available for the
equipment.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAINTENANCE VERIFICATION

IQ-08
Filter set 2A & 2B

SPEC

EXPECTED RESULT

PMP

A PM checklist,
schedule or similar is
available as evidence
of inclusion into the
PM program.

Spare
Parts

Spare parts inventory


is available for the
equipment.

Lubricants

Lubricants inventory is
available for the
equipment.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAINTENANCE VERIFICATION

IQ-08
Filter set 3A & 3B

SPEC

EXPECTED RESULT

PMP

A PM checklist,
schedule or similar is
available as evidence
of inclusion into the
PM program.

Spare
Parts

Spare parts inventory


is available for the
equipment.

Lubricants

Lubricants inventory is
available for the
equipment.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAINTENANCE VERIFICATION

IQ-08
Filter set 4A & 4B

SPEC

EXPECTED RESULT

PMP

A PM checklist,
schedule or similar is
available as evidence
of inclusion into the
PM program.

Spare
Parts

Spare parts inventory


is available for the
equipment.

Lubricants

Lubricants inventory is
available for the
equipment.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAINTENANCE VERIFICATION

IQ-08
Filter set 5A & 5B

SPEC

EXPECTED RESULT

PMP

A PM checklist,
schedule or similar is
available as evidence
of inclusion into the
PM program.

Spare
Parts

Spare parts inventory


is available for the
equipment.

Lubricants

Lubricants inventory is
available for the
equipment.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAINTENANCE VERIFICATION

IQ-08
Dual Softener unit

SPEC

EXPECTED RESULT

PMP

A PM checklist,
schedule or similar is
available as evidence
of inclusion into the
PM program.

Spare
Parts

Spare parts inventory


is available for the
equipment.

Lubricants

Lubricants inventory is
available for the
equipment.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAINTENANCE VERIFICATION

IQ-08
Ozone Generator

SPEC

EXPECTED RESULT

PMP

A PM checklist,
schedule or similar is
available as evidence
of inclusion into the
PM program.

Spare
Parts

Spare parts inventory


is available for the
equipment.

Lubricants

Lubricants inventory is
available for the
equipment.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAINTENANCE VERIFICATION

IQ-08
Ozone Destructor

SPEC

EXPECTED RESULT

PMP

A PM checklist,
schedule or similar is
available as evidence
of inclusion into the
PM program.

Spare
Parts

Spare parts inventory


is available for the
equipment.

Lubricants

Lubricants inventory is
available for the
equipment.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAINTENANCE VERIFICATION

IQ-08
6,000 Gal. Tank

SPEC

EXPECTED RESULT

PMP

A PM checklist,
schedule or similar is
available as evidence
of inclusion into the
PM program.

Spare
Parts

Spare parts inventory


is available for the
equipment.

Lubricants

Lubricants inventory is
available for the
equipment.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAINTENANCE VERIFICATION

IQ-08
8,000 Gal. Tank

SPEC

EXPECTED RESULT

PMP

A PM checklist,
schedule or similar is
available as evidence
of inclusion into the
PM program.

Spare
Parts

Spare parts inventory


is available for the
equipment.

Lubricants

Lubricants inventory is
available for the
equipment.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAINTENANCE VERIFICATION

IQ-08
Distribution Pumps (1A, 1B)

SPEC

EXPECTED RESULT

PMP

A PM checklist,
schedule or similar is
available as evidence
of inclusion into the
PM program.

Spare
Parts

Spare parts inventory


is available for the
equipment.

Lubricants

Lubricants inventory is
available for the
equipment.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

MAINTENANCE VERIFICATION

If NO, refer to Deviation # __________


Date:

IQ-08

Distribution Pumps (2A, 2B)


SPEC

EXPECTED RESULT

PMP

A PM checklist,
schedule or similar is
available as evidence
of inclusion into the
PM program.

Spare
Parts

Spare parts inventory


is available for the
equipment.

Lubricants

Lubricants inventory is
available for the
equipment.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

MAINTENANCE VERIFICATION

If NO, refer to Deviation # __________


Date:

IQ-08

UV lamps (1A, 1B)


SPEC

EXPECTED RESULT

PMP

A PM checklist,
schedule or similar is
available as evidence
of inclusion into the
PM program.

Spare
Parts

Spare parts inventory


is available for the
equipment.

Lubricants

Lubricants inventory is
available for the
equipment.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAINTENANCE VERIFICATION

IQ-08
UV lamps (2A, 2B)

SPEC

EXPECTED RESULT

PMP

A PM checklist,
schedule or similar is
available as evidence
of inclusion into the
PM program.

Spare
Parts

Spare parts inventory


is available for the
equipment.

Lubricants

Lubricants inventory is
available for the
equipment.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAINTENANCE VERIFICATION

IQ-08
Dual Reverse Osmosis unit

SPEC

EXPECTED RESULT

PMP

A PM checklist,
schedule or similar is
available as evidence
of inclusion into the
PM program.

Spare
Parts

Spare parts inventory


is available for the
equipment.

Lubricants

Lubricants inventory is
available for the
equipment.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAINTENANCE VERIFICATION

IQ-08
De-gasification unit

SPEC

EXPECTED RESULT

PMP

A PM checklist,
schedule or similar is
available as evidence
of inclusion into the
PM program.

Spare
Parts

Spare parts inventory


is available for the
equipment.

Lubricants

Lubricants inventory is
available for the
equipment.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAINTENANCE VERIFICATION

IQ-08
Dual Mixed Bed unit

SPEC

EXPECTED RESULT

PMP

A PM checklist,
schedule or similar is
available as evidence
of inclusion into the
PM program.

Spare
Parts

Spare parts inventory


is available for the
equipment.

Lubricants

Lubricants inventory is
available for the
equipment.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

MAINTENANCE VERIFICATION

IQ-08
Microza ultra filtration filters

SPEC

EXPECTED RESULT

PMP

A PM checklist,
schedule or similar is
available as evidence
of inclusion into the
PM program.

Spare
Parts

Spare parts inventory


is available for the
equipment.

Lubricants

Lubricants inventory is
available for the
equipment.

ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

SAFETY & ERGONOMICS VERIFICATION

IQ-09

Objective:

Assure that the Purified Water System complies with ___s EHS Safety and Ergonomics
requirements

Procedure:

Collect documented evidence (i.e. EHS checklist) of EHS evaluation of the Purified Water
System

Document evaluation results and compare against expected results

References Required:

Evidence of EHS evaluation - EHS checklist, etc.

Acceptance Criteria:

EHS checklist is approved by EHS representative

SAFETY & ERGONOMICS VERIFICATION


SPEC

EXPECTED
RESULT

IQ-09
ACTUAL RESULT

PASS/FAIL

PERFORMED
BY/DATE

EHS Change
Management
AWO column
checklist was
completed and
approved.
PWS Safety &
Ergonomics
Compliance
EHS found
Purified Water
System to be in
compliance.

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

PROCEDURE VERIFICATION

IQ-10

Objective:

Assure written procedures for the operation and maintenance of the Purified Water System

Procedure:
a. Per equipment, collect and evaluate written procedures (i.e. operating, maintenance, cleaning)
and document findings
b. If any of the specifications is not applicable, write a Not Apply to the Actual Result column and
explain in the Comments/Observations section
c. Evaluate findings against expected results
References Required:

SOPs (at least in DRAFT form)

Acceptance Criteria:

Draft procedures are available for each main component of the Purified Water System.

PROCEDURE VERIFICATION

IQ-10
Filter set 1A & 1B

SOP

EXPECTED
RESULT

Operating
Procedure

A procedure
exists at least in
Draft form.

Maintenance
Procedure

A procedure
exists at least in
Draft form.

ACTUAL RESULT
(DOC. NO., REV. NO., TITLE, STATUS)

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

PROCEDURE VERIFICATION

IQ-10
Filter 2A & 2B

SOP

EXPECTED
RESULT

Operating
Procedure

A procedure
exists at least in
Draft form.

Maintenance
Procedure

A procedure
exists at least in
Draft form.

ACTUAL RESULT
(DOC. NO., REV. NO., TITLE, STATUS)

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

PROCEDURE VERIFICATION

IQ-10
Filter set 3A & 3B

SOP

EXPECTED
RESULT

Operating
Procedure

A procedure
exists at least in
Draft form.

Maintenance
Procedure

A procedure
exists at least in
Draft form.

ACTUAL RESULT
(DOC. NO., REV. NO., TITLE, STATUS)

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

PROCEDURE VERIFICATION

IQ-10
Filter set 4A & 4B

SOP

EXPECTED
RESULT

Operating
Procedure

A procedure
exists at least in
Draft form.

Maintenance
Procedure

A procedure
exists at least in
Draft form.

ACTUAL RESULT
(DOC. NO., REV. NO., TITLE, STATUS)

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

PROCEDURE VERIFICATION

IQ-10
Filter set 5A & 5B

SOP

EXPECTED
RESULT

Operating
Procedure

A procedure
exists at least in
Draft form.

Maintenance
Procedure

A procedure
exists at least in
Draft form.

ACTUAL RESULT
(DOC. NO., REV. NO., TITLE, STATUS)

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

PROCEDURE VERIFICATION

IQ-10
Dual Softener unit

SOP

EXPECTED
RESULT

Operating
Procedure

A procedure
exists at least in
Draft form.

Maintenance
Procedure

A procedure
exists at least in
Draft form.

ACTUAL RESULT
(DOC. NO., REV. NO., TITLE, STATUS)

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

PROCEDURE VERIFICATION

IQ-10
Ozone Generator

SOP

EXPECTED
RESULT

Operating
Procedure

A procedure
exists at least in
Draft form.

Maintenance
Procedure

A procedure
exists at least in
Draft form.

ACTUAL RESULT
(DOC. NO., REV. NO., TITLE, STATUS)

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

PROCEDURE VERIFICATION

IQ-10
Ozone Destructor

SOP

EXPECTED
RESULT

Operating
Procedure

A procedure
exists at least in
Draft form.

Maintenance
Procedure

A procedure
exists at least in
Draft form.

ACTUAL RESULT
(DOC. NO., REV. NO., TITLE, STATUS)

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

PROCEDURE VERIFICATION

IQ-10
Distribution Pumps (1A, 1B)

SOP

EXPECTED
RESULT

Operating
Procedure

A procedure
exists at least in
Draft form.

Maintenance
Procedure

A procedure
exists at least in
Draft form.

ACTUAL RESULT
(DOC. NO., REV. NO., TITLE, STATUS)

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

PROCEDURE VERIFICATION

IQ-10
Distribution Pumps (2A, 2B)

SOP

EXPECTED
RESULT

Operating
Procedure

A procedure
exists at least in
Draft form.

Maintenance
Procedure

A procedure
exists at least in
Draft form.

ACTUAL RESULT
(DOC. NO., REV. NO., TITLE, STATUS)

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

PROCEDURE VERIFICATION

IQ-10
8,000 Gal. Tank

SOP

EXPECTED
RESULT

Operating
Procedure

A procedure
exists at least in
Draft form.

Maintenance
Procedure

A procedure
exists at least in
Draft form.

ACTUAL RESULT
(DOC. NO., REV. NO., TITLE, STATUS)

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

PROCEDURE VERIFICATION

IQ-10
6,000 Gal. Tank

SOP

EXPECTED
RESULT

Operating
Procedure

A procedure
exists at least in
Draft form.

Maintenance
Procedure

A procedure
exists at least in
Draft form.

ACTUAL RESULT
(DOC. NO., REV. NO., TITLE, STATUS)

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

PROCEDURE VERIFICATION

IQ-10
UV lamps (1A, 1B, 2A, 2B)

SOP

EXPECTED
RESULT

Operating
Procedure

A procedure
exists at least in
Draft form.

Maintenance
Procedure

A procedure
exists at least in
Draft form.

ACTUAL RESULT
(DOC. NO., REV. NO., TITLE, STATUS)

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

PROCEDURE VERIFICATION

IQ-10
Dual Reverse Osmosis unit

SOP

EXPECTED
RESULT

Operating
Procedure

A procedure
exists at least in
Draft form.

Maintenance
Procedure

A procedure
exists at least in
Draft form.

ACTUAL RESULT
(DOC. NO., REV. NO., TITLE, STATUS)

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

PROCEDURE VERIFICATION

IQ-10
Degasification unit

SOP

EXPECTED
RESULT

Operating
Procedure

A procedure
exists at least in
Draft form.

Maintenance
Procedure

A procedure
exists at least in
Draft form.

ACTUAL RESULT
(DOC. NO., REV. NO., TITLE, STATUS)

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

PROCEDURE VERIFICATION

If NO, refer to Deviation # __________


Date:

IQ-10

Dual Mixed Bed unit


SOP

EXPECTED
RESULT

Operating
Procedure

A procedure
exists at least in
Draft form.

Maintenance
Procedure

A procedure
exists at least in
Draft form.

ACTUAL RESULT
(DOC. NO., REV. NO., TITLE, STATUS)

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

PROCEDURE VERIFICATION

IQ-10
Microza ultra filtration filters

SOP

EXPECTED
RESULT

Operating
Procedure

A procedure
exists at least in
Draft form.

Maintenance
Procedure

A procedure
exists at least in
Draft form.

ACTUAL RESULT
(DOC. NO., REV. NO., TITLE, STATUS)

PASS/FAIL

PERFORMED
BY/DATE

Comments/Observations:

Conformance to the acceptance criteria was evaluated and the final determination is as follows:
Acceptance Criteria met? (YES/NO) __________
Reviewed by:

If NO, refer to Deviation # __________


Date:

IQ CHECKLIST VERIFICATION
Verify each of the respective IQ tests and document completion and status.

TEST
NUMBER

TEST TITLE

TEST
EXECUTED

(YES/NO)

IQ-01

EQUIPMENT VERIFICATION

IQ-02

DOCUMENT INVENTORY
VERIFICATION

IQ-03

DRAWING VERIFICATION

IQ-04

SYSTEM DESIGN VERIFICATION

IQ-05

PLACEMENT VERIFICATION

IQ-06

UTILITY VERIFICATION

IQ-07

INSTRUMENTATION VERIFICATION

IQ-08

MAINTENANCE VERIFICATION

IQ-09

SAFETY AND ERGONOMICS


VERIFICATION

IQ-10

PROCEDURE VERIFICATION

Performed by:

ACCEPTANCE
CRITERIA
MET?

(YES/NO)

Date:

DEVIATION
NUMBER
(if applies)

DEVIATION
SOLVED

(YES/NO)

Vous aimerez peut-être aussi