KNX lighting
control system

LIGHTRAK / SYSTEM GUIDE


INCLUDING BUSCOM

POWERED BY SPECIALISTS

LTK_Bro_Covers v1.indd 1

29/08/2012 12:21

Electrak ... the specialist in power


distribution throughout the workplace
Electrak, part of the Legrand Group in the UK, is a leading manufacturer of power
distribution and lighting control solutions. Its power track, oor boxes and grommets,
desk modules and lighting control ranges are installed in high specication ofces
around the world.

LTK_Bro_002_003 v1.indd 2

29/08/2012 12:14

Legrand is the global specialist in electrical


and digital building infrastructures. Innovation
is the driving force behind its development.
With an increasing investment in research
and development (circa 5% of sales) and more
than 4,000 active patents, the Legrand Group
is focused on maintaining a high rate of new
product launches that present innovative
solutions to the market.

CONTENTS
Buscom trunking
Lightrak system - features
Adapting to changing buildings
Integration with KNX and DALI
Lightrak sensors
System support service
Case studies

4
6
8
10
12
14
15

SUSTAINABLE DEVELOPMENT
From design through to manufacturing,
the Legrand Group selects materials and
processes that respect people and
the environment.
Efcient and environmentally aware product design
Product functions that help to avoid energy waste
Management of manufacturing and logistics sites
Integration of environmental concerns and ISO 14001
procedures at the Groups global sites.*

ORDERING INFORMATION
System components, lighting
control units, sub-cabling
16
Standard switching devices
17
Sub-bus addressable devices
18
Buscom trunking
24 - 37
TECHNICAL INFORMATION
Lightrak
Buscom trunking

19 - 23
38 - 43

* 84% of sites are ISO 14001:2004 accredited including all UK sites.

LEGRAND IN THE UK POWERED BY SPECIALISTS


In the UK Legrand has developed a customer focused
structure which harnesses the power of its market
leading specialist brands to deliver innovative,
integrated solutions for every phase of construction.

LTK_Bro_002_003 v1.indd 3

29/08/2012 12:14

Buscom trunking...
a unique power and data backbone
Buscom is at the heart of Electraks lighting control solutions... distributing both
power and communications within a single busbar trunking system, it provides a
lexible and simple alternative to traditional wiring installations.

THE HEART OF YOUR LIGHTING CONTROL SYSTEM


Installing a matrix of Buscom trunking in the ceiling void creates an accessible power and
communications backbone throughout a building. The backbone can be tapped into at any point to
facilitate instant connection to power and control circuits.
Buscom incorporates a shielded twisted pair communications bus inside each length and tap-off,
and is suitable for use with any lighting control protocol, including: KNX, LonWorks and DALI.

MODULAR. FLEXIBLE. SIMPLE.


Trunking lengths simply push it together, saving time and money on installation. With cable
terminations only required for power and control circuits in the feed unit, Buscom delivers a plug
and play solution that allows for future lighting layout changes to be made quickly and eficiently,
whilst drastically reducing the potential points of failure in comparison with traditional wiring
methods.

04
Power and communications within a single
trunking system
Suitable for use with any lighting control protocol,
including: KNX, LonWorks and DALI
Modular, lexible system which is quick and simple
to install and adapt
Reduced potential points of failure in comparison
with traditional wiring installations

LTK_Bro_004_005 v1.indd 4

29/08/2012 12:15

Buscom adds a new dimension to lighting busbar that extends the unquestionable
plug and play advantages from the power circuit to the control circuit. This unique
system for distributing lighting control signals delivers unrivalled exibility,
regardless of the location of the intelligence...
INTELLIGENCE IN THE PANEL

INTELLIGENCE IN THE BUSBAR

Lighting control modules


located in a central cabinet are
connected to the Buscom system
via communication circuits that
terminate in the feed unit. Control
signals are then distributed
along the trunking run and made
available at any tap-off outlet.

Integrating lighting control


technology into the Buscom feed
unit is particularly effective for
DALI control. Each trunking run
converts to an individual DALI
network into which luminaires can
tap-in at any point.

INTELLIGENCE IN THE LCU

Lighting control units (LCUs)


are mounted onto and plugged
into Buscom trunking, providing
a hub into which multiples of
luminaires and switching devices
are plugged. Buscoms integrated
communication bus provides the
backbone which networks all
control devices together.

05
ENERGY SAVING

As with all Electrak


solutions, Buscom is
a modular system
designed to be quick
and simple to install,
reducing man hours and
energy usage on site.
energy saving

LTK_Bro_004_005 v1.indd 5

29/08/2012 12:15

Lightrak ...

fully addressable lighting control


Designed to work in harmony with
Electraks Buscom trunking, Lightraks
lighting control system offers high end
sophistication with unbeatable
lexibility and speed of installation.

PRESENCE OR
ABSENCE DETECTION
Saves energy and ensures that
lighting is only on when needed

TIMED EVENT CONTROLLER


Programmable touch screen units
optimise energy saving

SCENE SETTING SWITCH


Multiple lighting scenarios are
memorised and retrieved at the
touch of a button

EMERGENCY TEST
MULTI-GANG SWITCHES
Traditional key switch to enable
testing of self-contained emergency
luminaires

1, 2, 4 and 8 gang options connect


via CAT. 5 cable and RJ 45 plugs

06
SNAP ON... PLUG IN
Lightrak lighting control units
(LCUs) simply snap on and plug into
Electraks Buscom trunking and
are easily unplugged, moved and
reprogrammed to accommodate
future lighting layout changes.

LTK_Bro_006_007 v1.indd 6

29/08/2012 12:16

SOPHISTICATED TECHNOLOGY

FULLY ADDRESSABLE

Analogue and DSI dimming


through to full DALI
control in addressable
mode.

A full KNX network can


support in excess of 64,000
KNX devices.
Each output of every
lighting control unit (LCU)
is individually controllable.
Lightrak offers full
building-wide control
for even the largest of
projects.

Networked over a KNX


backbone that can be
integrated onto IP or BMS
systems.

DALI EMERGENCY FEEDBACK

WIDE RANGING CONTROL

Two way DALI


communication facilitates
feedback from DALI
emergency inverters onto
the KNX bus.

A comprehensive range
of control devices is
available: PIR / ultrasonic
sensors - wireless
reconiguration of sensor
parameters - scene setting
- remote control - time
scheduling - traditional
switching and emergency
key switch.

Monitoring and reporting


software can be easily
integrated with KNX.

DAYLIGHT LINKING

ABSENCE DETECTION

Lighting levels are


adjusted in relation to
the natural daylight
contribution.

Optimise energy savings


in cellular ofices and
meeting rooms. The
occupant chooses when
the lights are on; the
system ensures they are
switched off when the
space is vacated.

Sensors initiate dimming,


saving energy and
delivering a constant
luminance at the desk.

07
Fast, easy installation. Snap on / plug in
Fully addressable and PC reconigurable
Analogue, DSI and DALI control
Comprehensive range of energy saving switching,
sensing and scheduling devices available
Seamless connectivity with KNX devices from close to
300 manufacturers
Interface with other building control systems via the
open KNX protocol
Two way communication with DALI, facilitating control
and feedback
Traditional emergency lighting test functions
Comprehensive design and commissioning service

LTK_Bro_006_007 v1.indd 7

29/08/2012 12:17

The ability to adapt with the b

08
At the Category A stage of an ofice it-out the
lighting requirements of the inal tenant are not
known.
With Lightrak, developers are able to install a
cost-effective lighting control solution that is
adequate for the client attraction phase, but can
be upgraded to meet the needs of the incoming
tenant with a minimum level of investment in
time and labour.

LTK_Bro_008_009 v3.indd 8

30/08/2012 16:19

e building throughout its life

09
With a matrix of Buscom trunking installed,
a Lightrak installation provides a future proof
solution where lighting schemes can be
completely reconigured without the need to
run or terminate any additional cables. Lighting
control units are simply unplugged, moved and
reprogrammed; additional devices and control
units can also be added to extend the capability
of any installation.

LTK_Bro_008_009 v3.indd 9

30/08/2012 16:19

Lightrak ...

seamless integration with your


technology of choice
The Lightrak system operates over a KNX backbone. This
enables all control devices connected to the system to
communicate with each other, and facilitates seamless
interoperability with any KNX certied product.

KNX PROTOCOL SYSTEMS


KNX is the worldwide standard for all applications
in home and building control, ranging from lighting
and shutter control to security, HVAC, metering and
energy management. With close to 300 members and
approximately 7000 certied product ranges, the KNX
Association holds partnership agreements with over
30,000 installer companies in over 100 countries.
All products bearing the KNX logo are certied in order
to guarantee system compatibility, interworking and
interoperability and are commissioned via a single,
manufacturer independent design and commissioning tool.

LEFT: KNX was used as the underlying technology at


Terminal 5, Heathrow... possibly the largest lighting
control installation in Europe

10
KNX IS APPROVED AS:

ENERGY SAVING

Lighting accounts
for up to 40% of a
commercial buildings
electricity use.

European Standard (CENELEC EN 50090 and


CEN EN 13321-1)
International Standard (ISO/IEC 14543-3)

(Lighting Industry Federation)

Lighting controls can


provide energy savings
of 30% to 55%.
energy saving

LTK_Bro_010_011 v1.indd 10

For more information about KNX, visit: www.knx.org

29/08/2012 12:18

DALI: DIGITAL LIGHTING CONTROL


DALI (Digital Addressable Lighting Interface) is a protocol
dedicated purely to lighting control, as set out in the
technical standard IEC 62386. Each unit in a DALI network
has its own address, allowing direct communication with
each individual itting.

DALI FEATURE
IMAGE

TECHNICAL FEATURES
The information low with DALI is bi-directional. Rather
than only giving commands about the light level from the
control system to the itting, DALI also enables information
feedback on the condition of the ittings.
The itting can transmit information related to:
whether the light is switched on or off
the preset light level
the ballast condition
Therefore DALI is ideal for use with building automation
systems where remote supervising and service reports are
required.

11
DELIVERING DALI EMERGENCY FEEDBACK
The DALI lighting control unit (LCU) incorporates a
KNX to DALI interface that enables full DALI control in
addressable mode, and also facilitates the feedback from
the DALI network back onto the KNX bus.
Utilising widely available KNX gateways, this DALI
feedback can then be fed into building management
systems (BMS) or other monitoring and reporting software,
allowing emergency lighting test data to be logged and
alarms raised should essential maintenance be required.

For more information about DALI, visit: www.dali-ag.org

LTK_Bro_010_011 v1.indd 11

29/08/2012 12:18

The simple way to instant


energy savings
Combining lighting management sensors with traditional light switches puts users in
complete control. Lights can be manually switched on and off or, if users forget to switch
off lights, the sensors will do so automatically.
EVEN GREATER SAVINGS
Independent research shows that the
added control available through using
absence detection can provide an
additional 10% energy saving over and
above the signicant savings already
offered by presence detection.

IN DARKNESS

Users feel in complete control by turning on


lights using a traditional switch, typically located
by the door

IN BRIGHT LIGHT

The sensor will automatically switch off lights to


save energy when available light is sufcient
(although lights can still be switched on if preferred)*

IN NORMAL
LIGHT

IN WEAK LIGHT

The sensor will automatically switch on lights


when movement is detected and available light
is insufcient*
When leaving the room, lights can be manually
turned off using a switch. If lights are not turned
off, the occupancy sensor will do so automatically

12
ENERGY SAVING

Lighting controls
are eligible for 100%
Enhanced Capital
Allowance under
the Carbon Trust
administered scheme.

energy saving

* Lux levels can be set according to user preferences

LTK_Bro_012_013 v2.indd 12

30/08/2012 09:51

THE RIGHT TECHNOLOGY


FOR EVERY ENVIRONMENT
Legrand lighting management
solutions are available in three
different technologies to provide
effective occupancy detection in
different environments... all of which
can be controlled and commissioned
remotely at the touch of a button.
For small, enclosed spaces
PIR sensors detect occupancy
using the heat difference between
people and the ambient space.
For large spaces and open
areas Ultrasonic sensors
transmit sound waves throughout an
area and measure the speed at which
they come back.
For spaces with low or
infrequent movement from
occupants Dual technology, as the
name suggests, combines both
infra-red and ultrasonic detection.

13
REMOTE CONFIGURATORS FOR INSTANT
PROGRAMMING OF EACH SENSOR
Sensors can be quickly and easily re-congured at the touch of a button,
and without the need to ever remove the sensors from the ceiling... putting
users in complete control and reducing health and safety risks.
Advanced commissioning tool with LCD display
- Precise digital programming
- Instant visibility of individual sensor settings
- PIR / ultrasonic priority preferences for dual technology sensors
Basic commissioning tool
- Pre-programmed settings
Save time. Save money. And, of course, save energy.

LTK_Bro_012_013 v2.indd 13

30/08/2012 09:22

Legrand...
supporting you from initial design
through installation and beyond
DEDICATED DESIGN TEAM
Lighting control units can either be supplied
unprogrammed for third party system integration,
or complete with a full in-house project design and
commissioning service.
Our experienced team provides support at all stages
of a project, from the outline brief through to inal site
commissioning.
Sales engineers work with designers at the early stages
of a project to recommend optimum Buscom layouts
and lighting control options. This service is backed by a
specialist support team who are on hand to work with
clients to complete detailed design schemes and provide
full support through the installation phase.

BESPOKE SOLUTIONS
Every project is unique and sets its own challenges.
Our bespoke product development service enables us to
provide solutions to these challenges, and has delivered
tailor-made lighting control installations in a wide range
of building developments, including: Terminal 5, Heathrow,
London Underground, Canary Wharf and Central Bank
of Kuwait.

14

LTK_Bro_014_015 v1.indd 14

29/08/2012 12:19

TRUSTED THOUGHOUT THE UK AND ACROSS THE WORLD

LIGHTRAK PROJECTS
Royal Bank of Scotland Delhi, India
Fidelity Investments Delhi, India
Cyprus Postal Service Nicosia, Cyprus
2 x ITTL Showrooms Nicosia, Cyprus
Barclays Bank Pane, India
UKPS Liverpool, England
Lloyds TSB Bank Old Broad Street,
London, England
Bridgewater Place, Mixed use
Development Leeds, England
Lloyds TSB Card Contact Centre Petriies, Scotland
Grays School of Art - Robert Gordon
University, Aberdeen, Scotland

Rolls Royce - Glasgow, Scotland


Liverpool School of Tropical Medicine
Ofice and Labs University of Liverpool,
England
Quorum Business Park, Ofice
Development (16 Buildings) - Newcastle
upon Tyne, England
Mann Island, Ofice Development
Liverpool, England
Rotherham Civic Quarters, Local
Government Ofices - Rotherham,
England
First Street Manchester, Manchester City
Council - England

Velocity Buildings, Ofice Development Brooklands, Surrey, England


Broadgate West, Ofice Development
London, England
Abbey Gardens, Ofice Development Reading, England
HSE Dublin, Ireland
KPMG Manchester, England
KPMG Watford, England
Rackspace Data Centre Slough,
England
Translational Research Building
Newcastle University, England
Shadon House Care Facility
Gateshead, England

15

LTK_Bro_014_015 v1.indd 15

29/08/2012 12:20

Lightrak KNX lighting control system


system components, lighting control units (LCUs) and sub-cabling to luminaires

Feed unit

Buscom mounting
power supply unit

See p. 28-29

Luminaire sub
cabling

FFA010

- - -/- - -

FFE115

Timed event
controller

Powered line
coupler

FFA004

FFA008
Lighting control
unit
FFD060

Dimensions and technical information (p. 19-23)


Proprietory lighting control system to work alongside Electraks 25 and 40 A buscom trunking with integral communications bus
Offers high speed installation and unrivaled flexibility for future reconfiguration. PC configurable, covers all lighting control requirements
Based on the KNX open protocol and compatible with 1-10 V, DSI and DALI lighting installations
Designed and manufactured in the UK from robust galvanised steel
Pack

Cat. Nos.

System components

1
1
1
1
1
1
1
1

FFA001
FFA004
FFA006
FFA008
FFA010
FFA012
FFA014
FFA016

Statutory warning plaque


Timed event controller (flush)
Timed event controller (surface)
Powered line coupler
Buscom mounting power supply unit
Line power supply
KNX signal cable 100 m
USB to KNX interface

Lighting control units (LCUs) 9 outputs


(fully addressable)
1
1
1
1
1

FFD054
FFD054B1
FFD054B2
FFD054B3
FFD055

Analogue dimming (1-10 V)


Buscom mounting (standard buscom)
L1 Key B buscom mounting (3 phase buscom)
L2 Key B buscom mounting (3 phase buscom)
L3 Key B buscom mounting (3 phase buscom)
Rewirable surface mounting

1
1
1
1
1

FFD056
FFD056B1
FFD056B2
FFD056B3
FFD057

Digital dimming (DSI)


Buscom mounting (standard buscom)
L1 Key B buscom mounting (3 phase buscom)
L2 Key B buscom mounting (3 phase buscom)
L3 Key B buscom mounting (3 phase buscom)
Rewirable surface mounting

FFD060
FFD060B1
FFD060B2
FFD060B3
FFD061

DALI (digital addressable lighting interface)


Buscom mounting (standard buscom)
L1 Key B buscom mounting (3 phase buscom)
L2 Key B buscom mounting (3 phase buscom)
L3 Key B buscom mounting (3 phase buscom)
Rewirable surface mounting

NEW
1
1
1
1
1

Pack

Cat. Nos.

Sub-cabling to luminaires

FFE080

Plugs only
6 pole rewirable plug (male)

1
1
1
1
1

FFE085
FFE095
FFE115
FFE135
FFE120

FFE125

Pre-wired plugs and leads (5 m LSOH)


With 6 pole male plug to free end 5 core
With 6 pole male plug to free end 6 core
With 6 pole male plug to 6P female plug 6 core
With 6 pole male plug to 4P female plug 4 core
With 6 pole male plug to free end 3 core no
dimming
With 6 pole male plug to free end 4 core no
dimming

16

LTK_Bro_016_017 v4.indd 16

22/08/2012 15:31

Lightrak KNX lighting control system


standard switching devices

Lighting control
unit

- - -/- - -

See p. 16
Multi-gang
switch interface

- - -/- - -

FFB020

4 gang switch
FFB022-4
Presence detector

1 gang switch

1 gang key switch

FFC047

FFB030

FFB032

Dimensions and technical information (p. 19-23)


Standard switching devices connect into the system via simple CAT 5 cabling either straight into a lighting control unit or into a multi-gang switch
interface. The inputs of the control units are addressable and can be commissioned to control any output or group of outputs throughout the entire
KNX network. Future layout changes can be accommodated easily as all control units are plug and play and can be re-commissioned through
KNX ETS software
Pack

Cat. Nos.

Standard presence detector

FFC047

Plug into lighting control unit


Presence detector

Pack

Cat. Nos.

CAT 5 cabling to switching devices

1
1

FFF205
FFF210

5 m CAT 5 lead plug to plug


10 m CAT 5 lead plug to plug

Switches
Switches for 1 gang back box
1
1
1
1

FFB030
FFB032
FFB033
FFB034

Plug into lighting control unit (see p. 16)


1 gang switch
1 gang key switch
1 gang key switch surface (including back box)
2 gang switch
Switches for 2 gang back box

1
1
1

FFB022-2
FFB022-3
FFB022-4

Plug into multi-gang switch interface


(Cat. No. FFB020)
2 gang switch
3 gang switch
4 gang switch
Switches for 2 x 2 gang back box

1
1
1
1

FFB024-5
FFB024-6
FFB024-7
FFB024-8

Plug into multi-gang switch interface


(Cat. No. FFB020)
5 gang switch
6 gang switch
7 gang switch
8 gang switch

Multi-gang switch interface


1

FFB020

Buscom mounted multi-gang switch interface

Back boxes
1
1
1

FFB036
FFB026
FFB028

1 gang
2 gang
2 x 2 gang

17

LTK_Bro_016_017 v4.indd 17

22/08/2012 15:32

Lightrak KNX lighting control system

NEW 2013
able
i
a
Av l

sub-bus addressable devices

FFC020

FFC058
FFC055
FFC052

FFC021

FFC050

FFC023

FFC059

FFC024

Technical information (p. 21)


Addressable sensing and switching devices can be connected in series on a sub-bus
Each sub-bus connects onto the KNX network via a sub-bus to KNX interface unit
The addressable sensors offer a higher level of capability and functionality :
Factory set to presence mode, absence mode activated by commissioning tool
Factory pre-set light level threshold 500 lux for false ceiling, 300 lux for surface mounting / flush mounting detectors
Factory pre-set time delay 15 minutes
Precise adjustment on-site via commissioning tool
Devices can be commissioned to control any output or group of outputs throughout the entire KNX network. Future layout changes can be
accommodated easily as all devices can be re-commissioned through KNX ETS software
Pack

Cat. Nos.

Sub-bus to KNX interface unit

FFC020

Buscom mounting interface unit

Cat. Nos.

Sub-bus sensor for corridors

FFC057

Connects into interface unit (Cat. No. FFC020)


With absence and presence modes
Includes 10 m connection lead
Maximum range 30 m IP 42
PIR sensor 140

Sub-bus sensors ceiling mounting

IR remote control

Connect into interface unit (Cat. No. FFC020)


With absence and presence modes
Includes 5 m connection lead

FFC058

For sub-bus sensors (client use)


On / off dimming controller

Pack

Sub-bus sensors commissioning tool


1

FFC021

Digital hand-held commissioning tool

Other sub-bus devices

PIR sensor

1
1

FFC050
FFC051

Detection field 45 m2 8 m
Optimum distance between detectors : 6 m
PIR ceiling mounting switch sensor 360
Surface mounting box for FFC050
Combined PIR and ultrasonic sensor

1
1

FFC052
FFC053

Light measurement cell

FFC059

Sub-bus switches

Detection field 90 m2 11 m
Optimum distance between detectors : 10 m
PIR and ultrasonic ceiling mounting sensor 360
Surface mounting box for FFC052

Sub-bus sensors wall mounting

FFC030
FFC033

Connect into interface unit (Cat. No. FFC020)


Includes 10 m connection lead
Complete with brushed stainless steel plate, yolk
and magnesium rockers
2 gang 2 way sub-bus switch
4 scenario sub-bus switch

1
1
1

FFC022
FFC023
FFC024

Sub-bus cable 100 m


RJ45 doubler unit to extend sub-bus
Sub-bus to RJ45 connector

Connect into interface unit (Cat. No. FFC020)


With absence and presence modes
Includes 10 m connection lead
PIR sensor
1

FFC054

Maximum range 8 m IP 42
PIR wall mounting sensor 180

Connects into interface unit (Cat. No. FFC020)


Includes 5 m lead
Photocell light level sensor

Sub-bus accessories

Combined PIR and ultrasonic sensor


1

FFC055

Maximum range 11 m IP 42
PIR and ultrasonic wall mounting sensor 180
IP 55 sensor

FFC056

Maximum range 15 m IP 55
PIR wall mounting sensor 270

18

LTK_Bro_018 v4.indd 18

22/08/2012 15:37

Lightrak KNX lighting control system


technical information

n KNX technical specification

n Buscom trunking mounted power supply unit FFA010

Each line coupler can support 64 bus devices (lighting control units,
multi-gang switch interface units, bus interface units etc)
A maximum of 15 line couplers may be linked with a main bus line
together to form an area; therefore an area can support up to 960
devices
The system may be further expanded with the addition of a backbone
bus line which would allow the linking together of 15 main bus lines
via 15 line couplers, therefore any single system could support 14 400
devices
By utilising additional line couplers this total can exceed 64 000 devices
(for additional information, please contact us on +44 (0) 845 600 6266)

Connections
230 V : Electrak integrated tap-off
Bus : Electrak integrated tap-off
Physical specifications
Housing : galvanised steel, natural finish
Dimensions : length 330 mm, width 110 mm, height 60 mm
9 mm bracket clearance from busbar trunking
Weight : approximately 190 kg
Technical specifications
Supply voltage : 230 V
50/60 Hz
Protection (supply) : 13 A BS 1362 fuse fitted in tap-off
Internal protection : 63 A fuse to IEC 127-2
Secondary output voltage : 30 Vdc +/- 2 V
Secondary output current : 640 mA
Tap-off ASTA approved : BS EN 60439-2 : 2000
EMC complies with : EN 50090-2-2 :1997, EN 55022B
Climatic condition class : 3K4 (5C to 40C)
IP rating : 4x
Certification : KNX certified

Within any KNX bus line the following cable lengths are permitted :
Power supply unit to bus device 350 m maximum
Bus device to bus device 700 m maximum
Total bus line length 1 000 m maximum
Minimum distance between 2 power supply units on one line is 200 m(1)

n Powered line coupler FFA008


Connections
230 V : screw connection block
Primary line : screw connection block
Secondary line : screw connection block
Physical specifications
Housing : galvanised steel, natural finish
Dimensions : length 358 mm, width 200 mm, depth 75 mm
Weight : approximately 2750 kg
Technical specifications
Supply voltage : 230V
50/60Hz
Protection (supply) : 13 A BS 1362 fused spur
Internal protection : 63 A fuse to IEC127-2
Primary line load : 15 mW
Secondary line load : 200 mW
Secondary output voltage : 30Vdc +/- 2 V
Secondary output current : 630 mA
EMC complies with : EN 50090-2-2 : 1997, EN 55022B
Climatic condition class : 3K4 (5C to 40C)
IP rating : 4x
Certification : KNX certified

(1) Electrak manufacture a buscom trunking mounted power supply unit for this application,
Cat. No. FFA010 see p. 16

n Line power supply FFA012


Connections
230 V : screw connection block
Bus : screw connection block
Physical specifications
Housing : galvanised steel, natural finish
Dimensions : length 358 mm, width 110 mm, depth 75 mm
Weight : approximately 195 kg
Technical specifications
Supply voltage : 230 V
50/60Hz
Protection (supply) : 13 A BS 362 fused spur
Internal protection : 63 A fuse to IEC 127-2
Secondary output voltage : 30 Vdc +/- 2 V
Secondary output current : 640 mA
EMC complies with : EN 50090-2-2 : 1997, EN 55022B
Climatic condition class : 3K4 (5C to 40C)
IP rating : 4x
Certification : KNX certified

All dimensions (mm) are nominal

19

LTK_Bro_019_023 v4.indd 19

23/08/2012 13:55

Lightrak KNX lighting control system


technical information
n Lighting control unit analogue dimming Cat. Nos.
FFD054/FFD055
Connections
4 RJ45 inputs : CAT 5 providing switching input
9 GST/6 providing 230 V to luminaires
L1 Switched live brown
E Earth green / yellow
N Neutral blue
L2 Maintained live black
2 Dimming common white
3 Dimming red
Physical specifications
Housing : galvanised steel, natural finish
Dimensions : length 358 mm, width 182 mm, depth 35 mm plus 9 mm
bracket clearance from buscom trunking
Weight : approximately 175 kg
Technical specifications
Supply voltage : 230 V
50/60Hz
Maximum load : 10 A BS 1362 fuse fitted in tap-off
Maximum power : 2 300 VA
Bus voltage : 30 Vdc +/- 2 V
Tap-off ASTA approved : BS EN 60439-2 : 2000
EMC complies with : EN 50090-2-2 : 1997
Climatic condition class : 3K4 (5C to 40C)
IP rating : 4x
Certification : KNX certified

n Lighting control unit DSI dimming Cat. Nos. FFD056/


FFD057
Connections
4 RJ45 inputs : CAT 5 providing switching input
9 GST/6 providing 230 V to luminaires
L1 Switched live brown
E Earth green / yellow
N Neutral blue
L2 Maintained live black
2 Dimming common white
3 Dimming red
Physical specifications
Housing : galvanised steel, natural finish
Dimensions : length 358 mm, width 182 mm, depth 35 mm plus 9 mm
bracket clearance from buscom trunking
Weight : approximately 175 kg
Technical specifications
Supply voltage : 230 V
50/60 Hz
Maximum load : 10 A BS 1362 fuse fitted in tap-off
Maximum power : 2 300 VA
Bus voltage : 30 Vdc +/- 2 V
Tap-off ASTA approved : BS EN 60439-2 : 2000
EMC complies with : EN 50090-2-2 : 1997
Climatic condition class : 3K4 (5C to 40C)
IP rating : 4x
Certification : KNX certified

n 4 gang switch Cat. No. FFB022-4


Physical specifications
Housing : steel back box 132 mm x 72 mm minimum 48 mm deep
Dimensions : length 125 mm, width 64 mm, height 41 mm
Weight : approximately 0668 kg
Technical specifications
Supply voltage : 9 Vdc
EMC complies with : EN 50090-2-2 : 1997
Climatic condition class : 3K4 (5C to 40C)
IP rating : 4x
Certification : KNX certified

n 8 gang switch Cat. No. FFB024-8


Physical specifications
Housing : steel back box 136 mm x 136 mm minimum 52 mm deep
Dimensions : length 127 mm, width 122 mm, height 41 mm
Weight : approximately 130 kg
Technical specifications
Supply voltage : 9 Vdc
EMC complies with : EN 50090-2-2 : 1997
Climatic condition class : 3K4 (5C to 40C)
IP rating : 4x
Certification : KNX certified

n Multi-gang switch interface Cat. No. FFB020


Connections
230 V : Electrak integrated tap-off
Bus : Electrak integrated tap-off
Switch : CAT 5 lead (RJ45 to RJ45)
Physical specifications
Housing : galvanised steel, natural finish
Dimensions : length 126 mm, width 102 mm, height 46 mm plus
9 mm mounting bracket
Weight : approximately 066 kg
Technical specifications
Supply voltage : 230 V
50/60 Hz
Protection : 3 A BS 1362 fuse fitted in tap-off
Nominal load : 24 mA
Maximum bus load : 12 mA
Tap-off ASTA approved : BS EN 60439-2 : 2000
EMC complies with : EN 50090-2-2 : 1997
Climatic condition class : 3K4 (5C to 40C)
IP rating : 4x
Certification : KNX certified

n Lighting control unit dimensions


Cat. Nos. FFD054, FFD056, FFD060

n Lighting control unit DALI Cat. Nos. FFD060/FFD061


Connections
4 RJ45 inputs : CAT 5 providing switching input
9 GST/6 providing 230 V to luminaires
L1 Switched live brown
E Earth green / yellow
N Neutral blue
2 DALI
3 DALI
Physical specifications
Housing : galvanised steel, natural finish
Dimensions : length 358 mm, width 182 mm, depth 35 mm plus 9 mm
bracket clearance from buscom trunking
Weight : approximately 175 kg
Technical specifications
Supply voltage : 230 V
50/60 Hz
Maximum load : 10 A
Maximum power : 2 300 VA
KNX bus voltage : 30 Vdc +/- 2 V
Tap-off ASTA approved : BS EN 60439-2 : 2000
EMC complies with : EN 50090-2-2 : 1997
Climatic condition class : 3K4 (5C to 40C)
IP rating : 4x

All dimensions (mm) are nominal

20

LTK_Bro_019_023 v4.indd 20

22/08/2012 16:06

Lightrak KNX lighting control system


sub-bus sensors technical information

n Ceiling mounting
All sub-bus sensors have built-in bracket systems that
enable ceiling mounting. Most sensors are suitable for
standard EU boxes ( 65). This is important for applications
where the ceiling is unavailable for sensor installation. Only
one Cat. No. is required for two ways of mounting

n Sub-bus to KNX interface unit FFC020


Connections
Bus : Electrak integrated tap-off connecting 230 V and KNX bus
Physical specifications
Housing : galvanised steel, natural finish
Dimensions : length 125 mm, width 154 mm, height 72 mm plus 9 mm
mounting bracket
Technical specifications
Supply voltage : 230 V
50/60 Hz
Protection : 3 A BS 1362 fuse fitted in tap-off
Tap-off ASTA approved : BS EN 60439-2 : 2000
EMC complies with : EN 50090-2-2 : 1997
Climatic condition class : 3K4 (5C to 40C)
IP rating : 4x
Certification : KNX certified

n Wall mounting
Wall mounting sensors are supplied with mounting base
Simply ix base to the wall, connect wires to the automatic
wiring block and ix sensor to base

n Settings
Most sensors feature Smart Factory Set technology. Adjustments are
typically not needed after installation
If adjustments need to be made (due to last minute changes in furniture
or ixture placement), sensitivity and time delays should match the
activity levels of the monitored spaces
Hand-held commissioning tool can be used to adjust settings :
This commissioning tool enables a very precise
commissioning of your sensors :
- Time: from 0 seconds to 60 min
- Lux: from 1 lux to 1 275 lux
- Detection mode : presence, presence
walkthrough, absence modes
- PIR and US detection sensibility : low, medium,
high, very high
- Provides access to advanced functions such as
calibration, alarms, choice of mode of detection
(initial detection, maintain detection, retrigger),
daylight function
- Allows downloading, saving and duplication of
sensor parameters
Cat.No FFC021
Presence mode
3'

Walkthrough mode
Absence mode

21

LTK_Bro_019_023 v4.indd 21

23/08/2012 13:56

Lightrak KNX lighting control system


typical layout and system topology
n KNX system topology schematic diagram

Bus line
(max. 64 LCU)

Bus line
(max. 64 LCU)

Example of typical layout

Repeater
power line
coupler
1.5.64

Main line
powered
line coupler

1.5.128
KNX standard
bus cable

1.1 .0

1.2.0

1.3.0

1.4.0

1.5.0

AREA 1 main bus line

1.5.192
(maximum)

1.15.0 (maximum)
KNX standard bus cable interconnecting
main line powered line coupler
AREA 2 main bus line
AREA 3 main bus line
AREA 4 main bus line

Backbone
powered
line coupler
1.0.

AREA 15 main bus line (maximum)


1.0.1

Backbone
power supply unit

1.0.2

1.0.3

1.0.4

1.0.15

Backbone bus line


KNX standard bus cable
interconnecting backbone
powered line coupler

n Example of ceiling layout for Lightrak KNX fully addressable system (see opposite)
Layout key
Electrical distribution board and power cabling
Powered line coupler and KNX cabling
Timed event controller
Buscom feed unit and lengths
1/1

Lighting control unit and reference number


Luminaires and sub-cabling
Standard presence detector and CAT 5 sub cabling
Sub-bus interface unit and sub-bus cabling
PIR bus sensor
Dual technology (PIR and ultrasonic) bus sensor
Bus switch
Bus scenario switch

22

LTK_Bro_019_023 v4.indd 22

23/08/2012 14:39

Cat A lighting layout

1/2

5/2

2/2
4/2

3/2

5/1

4/1
3/1
1/1

2/1

6/2

6/1

The left hand area fitted out to Cat B tenant layout

1/5

2/5

3/3
5/2

1/4
4/2
2/4
3/2
1/3
2/3

5/1

1/2

4/1
2/2

3/1

1/1
2/1

6/1

6/2

23

LTK_Bro_019_023 v4.indd 23

22/08/2012 17:47


pour exemple
XXXXXXxxxxxx
Electrak
buscom
trunking

xxxxxxxx
2P,
3P, dual circuit and 3 phase systems

SYSTEM

IP RATING

RATING

3 m track
05 m spacings

2 m track
05 m spacings

3 m track
10 m spacings

2 m track
10 m spacings

Single sided

BBA3145C

BBA2145C

BBA3141C

BBA2141C

Double sided

BBA3245C

BBA2245C

BBA3241C

BBA2241C

Single sided

CCA3145C

CCA2145C

CCA3141C

CCA2141C

Double sided

CCA3245C

CCA2245C

CCA3241C

CCA2241C

Single sided

BBA3155C

BBA2155C

BBA3151C

BBA2151C

Double sided

BBA3255C

BBA2255C

BBA3251C

BBA2251C

Single sided

CCA3155C

CCA2155C

CCA3151C

CCA2151C

Double sided

CCA3255C

CCA2255C

CCA3251C

CCA2251C

Single sided

BBB3145C

BBB2145C

BBB3141C

BBB2141C

Double sided

BBB3245C

BBB2245C

BBB3241C

BBB2241C

Single sided

CCB3145C

CCB2145C

CCB3141C

CCB2141C

Double sided

CCB3245C

CCB2245C

CCB3241C

CCB2241C

Single sided

BBB3155C

BBB2155C

BBB3151C

BBB2151C

Double sided

BBB3255C

BBB2255C

BBB3251C

BBB2251C

Single sided

CCB3155C

CCB2155C

CCB3151C

CCB2151C

Double sided

CCB3255C

CCB2255C

CCB3251C

CCB2251C

Single sided

BBC3145C

BBC2145C

BBC3141C

BBC2141C

Double sided

BBC3245C

BBC2245C

BBC3241C

BBC2241C

Single sided

CCC3145C

CCC2145C

CCC3141C

CCC2141C

Double sided

CCC3245C

CCC2245C

CCC3241C

CCC2241C

Single sided

BBC3155C

BBC2155C

BBC3151C

BBC2151C

Double sided

BBC3255C

BBC2255C

BBC3251C

BBC2251C

Single sided

CCC3155C

CCC2155C

CCC3151C

CCC2151C

Double sided

CCC3255C

CCC2255C

CCC3251C

CCC2251C

Single sided

BBD3145C

BBD2145C

BBD3141C

BBD2141C

Double sided

BBD3245C

BBD2245C

BBD3241C

BBD2241C

Single sided

CCD3145C

CCD2145C

CCD3141C

CCD2141C

Double sided

CCD3245C

CCD2245C

CCD3241C

CCD2241C

Single sided

BBD3155C

BBD2155C

BBD3151C

BBD2151C

Double sided

BBD3255C

BBD2255C

BBD3251C

BBD2251C

Single sided

CCD3155C

CCD2155C

CCD3151C

CCD2151C

Double sided

CCD3255C

CCD2255C

CCD3251C

CCD2251C

OUTLETS

25 A

IP 4X
40 A

Electrak 30
2P + E system
25 A

IP 54
40 A

25 A

IP 4X
40 A

Electrak 31
3P + E system
25 A

IP 54
40 A

25 A

IP 4X
40 A

Electrak 32
Dual circuit system
25 A

IP 54
40 A

25 A

IP 4X
40 A

Electrak 33
3 phase system
25 A

IP 54
40 A

24

LTK_Bro_024_025 v2.indd 24

22/08/2012 16:16

Centre feed

Suspended feed Suspended feed


unit left hand
unit right hand

Surface feed
unit left hand

Surface feed
unit right hand

Suspended
flexible corner
05 m

Suspended
flexible corner
20 m

Surface flexible
corner 05 m

Surface flexible
corner 20 m

BBA44FC

BBA14LFC

BBA14RFC

BBA34LFC

BBA34RFC

BBA140XC

BBA142XC

BBA340XC

BBA342XC

BBA24LFC

BBA24RFC

BBA240XC

BBA242XC

CCA44FC

CCA14LFC

CCA14RFC

CCA34LFC

CCA34RFC

CCA140XC

CCA142XC

CCA340XC

CCA342XC

CCA24LFC

CCA24RFC

CCA240XC

CCA242XC

BBA15LFC

BBA15RFC

BBA35LFC

BBA35RFC

BBA150XC

BBA152XC

BBA350XC

BBA352XC

BBA25LFC

BBA25RFC

BBA250XC

BBA252XC

CCA15LFC

CCA15RFC

CCA35LFC

CCA35RFC

CCA150XC

CCA152XC

CCA350XC

CCA352XC

CCA25LFC

CCA25RFC

CCA250XC

CCA252XC

BBB44FC

BBB14LFC

BBB14RFC

BBB34LFC

BBB34RFC

BBB140XC

BBB142XC

BBB340XC

BBB342XC

BBB24LFC

BBB24RFC

BBB240XC

BBB242XC

CCB44FC

CCB14LFC

CCB14RFC

CCB34LFC

CCB34RFC

CCB140XC

CCB142XC

CCB340XC

CCB342XC

CCB24LFC

CCB24RFC

CCB240XC

CCB242XC

BBB15LFC

BBB15RFC

BBB35LFC

BBB35RFC

BBB150XC

BBB152XC

BBB350XC

BBB352XC

BBB25LFC

BBB25RFC

BBB250XC

BBB252XC

CCB15LFC

CCB15RFC

CCB35LFC

CCB35RFC

CCB150XC

CCB152XC

CCB350XC

CCB352XC

CCB25LFC

CCB25RFC

CCB250XC

CCB252XC

BBC44FC

BBC14LFC

BBC14RFC

BBC34LFC

BBC34RFC

BBC140XC

BBC142XC

BBC340XC

BBC342XC

BBC24LFC

BBC24RFC

BBC240XC

BBC242XC

CCC44FC

CCC14LFC

CCC14RFC

CCC34LFC

CCC34RFC

CCC140XC

CCC142XC

CCC340XC

CCC342XC

CCC24LFC

CCC24RFC

CCC240XC

CCC242XC

BBC15LFC

BBC15RFC

BBC35LFC

BBC35RFC

BBC150XC

BBC152XC

BBC350XC

BBC352XC

BBC25LFC

BBC25RFC

BBC250XC

BBC252XC

CCC15LFC

CCC15RFC

CCC35LFC

CCC35RFC

CCC150XC

CCC152XC

CCC350XC

CCC352XC

CCC25LFC

CCC25RFC

CCC250XC

CCC252XC

BBD44FC

BBD14LFC

BBD14RFC

BBD34LFC

BBD34RFC

BBD140XC

BBD142XC

BBD340XC

BBD342XC

BBD24LFC

BBD24RFC

BBD240XC

BBD242XC

CCD44FC

CCD14LFC

CCD14RFC

CCD34LFC

CCD34RFC

CCD140XC

CCD142XC

CCD340XC

CCD342XC

CCD24LFC

CCD24RFC

CCD240XC

CCD242XC

BBD15LFC

BBD15RFC

BBD35LFC

BBD35RFC

BBD150XC

BBD152XC

BBD350XC

BBD352XC

BBD25LFC

BBD25RFC

BBD250XC

BBD252XC

CCD15LFC

CCD15RFC

CCD35LFC

CCD35RFC

CCD150XC

CCD152XC

CCD350XC

CCD352XC

CCD25LFC

CCD25RFC

CCD250XC

CCD252XC

25

LTK_Bro_024_025 v2.indd 25

22/08/2012 16:16


pour exemple
XXXXXXxxxxxx
Electrak
buscom
trunking

xxxxxxxx
tap-offs

Rewirable

08 m

2m

3m

5m

DDE408FC

DDE42FC

DDE43FC

DDE45FC

DDF4F

DDE408F

DDE42F

DDE43F

DDE45F

IP RATING

PHASE

With comms

L+ N

Electrak 30

2P + E system

SYSTEM

13 A FUSED TAP-OFFS

IP 4X
No comms
With comms

DDE508FC

DDE52FC

DDE53FC

DDE55FC

DDF5F

DDE508F

DDE52F

DDE53F

DDE55F

DDE408FC

DDE42FC

DDE43FC

DDE45FC

IP 54
No comms
With comms

L1 N

No comms
With comms
No comms
With comms
No comms
With comms

DDE42F

DDE43F

DDE45F

DDE508FC

DDE52FC

DDE53FC

DDE55FC

DDF5F

DDE508F

DDE52F

DDE53F

DDE55F

DDG408FC

DDG42FC

DDG43FC

DDG45FC

L1 N1

DDH4F

DDG408F

DDG42F

DDG43F

DDG45F

DDG508FC

DDG52FC

DDG53FC

DDG55FC

DDH5F

DDG508F

DDG52F

DDG53F

DDG55F

DDE408FC

DDE42FC

DDE43FC

DDE45FC

IP 54
With comms

IP 4X
No comms
With comms

DDF4F

DDE408F

DDE42F

DDE43F

DDE45F

DDE508FC

DDE52FC

DDE53FC

DDE55FC

DDF5F

DDE508F

DDE52F

DDE53F

DDE55F

DDJ408FC

DDJ42FC

DDJ43FC

DDJ45FC

IP 54
No comms
With comms

L2 N2

Electrak 32

DDE408F

IP 4X

No comms

Dual circuit system

DDF4F

IP 54

L1 L2 N

Electrak 31

3P + E system

IP 4X

IP 4X
No comms
With comms

DDK4F

DDJ408F

DDJ42F

DDJ43F

DDJ45F

DDJ508FC

DDJ52FC

DDJ53FC

DDJ55FC

DDK5F

DDJ508F

DDJ52F

DDJ53F

DDJ55F

IP 54
No comms
With comms

L1 N

IP 4X

No comms
With comms

IP 54

No comms

L2 N

With comms

IP 4X

With comms
No comms
With comms

DDM408L1FC

DDM42L1FC

DDM43L1FC

DDM45L1FC

DDM408L1F

DDM42L1F

DDM43L1F

DDM45L1F

DDM508L1FC

DDM52L1FC

DDM53L1FC

DDM55L1FC

DDN5L1F

DDM508L1F

DDM52L1F

DDM53L1F

DDM55L1F

DDM408L2FC

DDM42L2FC

DDM43L2FC

DDM45L2FC

DDN4L2F

DDM408L2F

DDM42L2F

DDM43L2F

DDM45L2F

DDM508L2FC

DDM52L2FC

DDM53L2FC

DDM55L2FC

DDN5L2F

DDM508L2F

DDM52L2F

DDM53L2F

DDM55L2F

DDM408L3FC

DDM42L3FC

DDM43L3FC

DDM45L3FC

DDN4L3F

DDM408L3F

DDM42L3F

DDM43L3F

DDM45L3F

DDM508L3FC

DDM52L3FC

DDM53L3FC

DDM55L3FC

DDN5L3F

DDM508L3F

DDM52L3F

DDM53L3F

DDM55L3F

DDP4SF

L3 N

IP 4X
No comms
With comms

IP 54
No comms

L+L+L+N

Phase
selectable

Electrak 33

IP 54
3 phase system

No comms

DDN4L1F

With comms

IP 4X
No comms
With comms

IP 54
DDP5SF

With comms

No comms

No comms

With comms

No comms

IP 4X
IP 54

26

LTK_Bro_026_027 v2.indd 26

22/08/2012 16:17

16 A UNFUSED TAP-OFFS
Rewirable

08 m

2m

3m

5m

DDE408C

DDE42C

DDE43C

DDE45C

DDF4

DDE408

DDE42

DDE43

DDE45

DDE508C

DDE52C

DDE53C

DDE55C

DDF5

DDE508

DDE52

DDE53

DDE55

DDE408C

DDE42C

DDE43C

DDE45C

DDF4

DDE408

DDE42

DDE43

DDE45

DDE508C

DDE52C

DDE53C

DDE55C

DDF5

DDE508

DDE52

DDE53

DDE55

DDG408C

DDG42C

DDG43C

DDG45C

DDH4

DDG408

DDG42

DDG43

DDG45

DDG508C

DDG52C

DDG53C

DDG55C

DDH5

DDG508

DDG52

DDG53

DDG55

DDE408C

DDE42C

DDE43C

DDE45C

DDF4

DDE408

DDE42

DDE43

DDE45

DDE508C

DDE52C

DDE53C

DDE55C

DDF5

DDE508

DDE52

DDE53

DDE55

DDJ408C

DDJ42C

DDJ43C

DDJ45C

DDK4

DDJ408

DDJ42

DDJ43

DDJ45

DDJ508C

DDJ52C

DDJ53C

DDJ55C

DDK5

DDJ508

DDJ52

DDJ53

DDJ55

DDM408L1C

DDM42L1C

DDM43L1C

DDM45L1C

DDN4L1

DDM408L1

DDM42L1

DDM43L1

DDM45L1

DDM508L1C

DDM52L1C

DDM53L1C

DDM55L1C

DDN5L1

DDM508L1

DDM52L1

DDM53L1

DDM55L1

DDM408L2C

DDM42L2C

DDM43L2C

DDM45L2C

DDN4L2

DDM408L2

DDM42L2

DDM43L2

DDM45L2

DDM508L2C

DDM52L2C

DDM53L2C

DDM55L2C

DDN5L2

DDM508L2

DDM52L2

DDM53L2

DDM55L2

DDM408L3C

DDM42L3C

DDM43L3C

DDM45L3C

DDN4L3

DDM408L3

DDM42L3

DDM43L3

DDM45L3

DDM508L3C

DDM52L3C

DDM53L3C

DDM55L3C

DDN5L3

DDM508L3

DDM52L3

DDM53L3

DDM55L3

DDP4S

DDP5S

DDR408

DDR42

DDR43

DDR45

DDR508

DDR52

DDR53

DDR55

27

LTK_Bro_026_027 v2.indd 27

22/08/2012 16:17

Electrak 30 2P + E buscom trunking


power and communication distribution

CCA3145C

CCA2145C

CCA14RFC

CCA142XC

CCA14LFC
Selection chart (p. 24-27)
Dimensions and technical information (p. 38-43)
Integral communication bus suitable for KNX, Lonworks, DALI protocols, etc. 25 A and 40 A systems
Outlets on one or two sides. IP 4X or IP 54 ingress protection
Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
Pack

Cat. Nos.

Electrak 30
2 P + E + comms single sided system

Pack

Cat. Nos.

2P + E buscom trunking system with integral


communications bus circuit available in IP 4X
and IP 54 versions
Socket outlets are colour coded white and are
located on just one side of the bar
2P + E trunking lengths
Trunking lengths push fit into each other, and
feed units or flexible lengths. Trunking lengths
can be surface mounted or suspended using the
various bracket options
1
1
1
1
1
1
1
1

25 A
BBA3145C
BBA2145C
BBA3141C
BBA2141C
40 A
CCA3145C
CCA2145C
CCA3141C
CCA2141C

Length
(m)

Tap-off
outlets

Weight
(kg)(1)

3
2
3
2

6
4
3
2

447
327
442
324

3
2
3
2

6
4
3
2

457
336
452
331

Flexible lengths for single sided system


Flexible lengths can be used to change
direction, change level or overcome
obstructions
Suspended right to left

1
1
1
1

BBA140XC
BBA142XC
CCA140XC
CCA142XC

Length
(m)

Rating
(A)

Weight
(kg)(1)

05
2
05
2

25
25
40
40

291
321
294
333

Surface mounted right to left


1
1
1
1

BBA340XC
BBA342XC
CCA340XC
CCA342XC

Length
(m)

Rating
(A)

Weight
(kg)(1)

05
2
05
2

25
25
40
40

299
305
302
341

L
N
PE

Feed units for single sided system


Feed units come with 2 x 25 mm and
2 x 16 mm cable entry holes and single screw
cable terminals for power and data
Left feed units are supplied with right end stop
Right feed units are supplied with left end stop
Centre feed units are supplied with right and left
end stops
Suspended
Weight
(kg)(1)

1
1
1
1

BBA14LFC
BBA14RFC
CCA14LFC
CCA14RFC

25 A left
25 A right
40 A left
40 A right

122
149
127
149

Surface mounted
Weight
(kg)(1)

1
1
1
1

BBA34LFC
BBA34RFC
CCA34LFC
CCA34RFC

25 A left
25 A right
40 A left
40 A right

131
154
131
154

Centre feed
Weight
(kg)(1)

1
1

BBA44FC
CCA44FC

25 A
40 A

18
18

(1) Weights shown are for IP 4X rated buscom. For all other
weights, contact us on +44 (0) 845 600 6266

Key : How to select the correct components


All examples on this page show IP 4X buscom trunking
IP rating is dictated by the red letters
4 = IP 4X. For IP 54 version, replace 4 with 5

28

LTK_Bro_028_029 v3.indd 28

23/08/2012 13:58

Electrak 30 2P + E buscom trunking


power and communication distribution

CCA3245C

CCA2245C

DDE45
DDE45C
DDF4F
Selection chart (p. 24-27)
Dimensions and technical information (p. 38-43)
Integral communication bus suitable for KNX, Lonworks, DALI protocols, etc. 25 A and 40 A systems
Outlets on one or two sides. IP 4X or IP 54 ingress protection
Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
Pack

Cat. Nos.

Electrak 30
2 P + E + comms double sided system

Pack

Cat. Nos.

2P + E buscom trunking system with integral


communications bus circuit available in IP 4X
and IP 54 versions
Socket outlets are colour coded white and are
located on both sides of the bar
The comms circuit is only available on one side
of the bar as shown in the diagram below
2P + E trunking lengths
Trunking lengths push fit into each other, and
feed units or flexible lengths. Double sided
trunking must be fixed using suspended fixing
brackets
1
1
1
1
1
1
1
1

25 A
BBA3245C
BBA2245C
BBA3241C
BBA2241C
40 A
CCA3245C
CCA2245C
CCA3241C
CCA2241C

Length
(m)

Tap-off
outlets

Weight
(kg)(1)

3
2
3
2

11
7
6
4

485
352
470
347

3
2
3
2

11
7
6
4

PE
N
L

Pre-wired tap-off units to pick-up L1+N, colour


coded white
Length
(m)

1
1
1
1

DDE408C
DDE42C
DDE43C
DDE45C

505
365
496
361

08
2
3
5

Fixed
polarity

Weight
(kg)(1)

L+N

02
04
05
07

13 A fused tap-off units


Pre-wired tap-off units to pick-up L1+N, supplied
with BS 1362 fuse, colour coded white

C
L
N
PE

Tap-off units with and without comms


Power only tap-offs can plug into any tap-off outlet
Tap-offs with comms can only be plugged into the
comms side of the bar
16 A unfused tap-off units

1
1
1
1

DDE408FC
DDE42FC
DDE43FC
DDE45FC

Length
(m)

Fixed
polarity

Weight
(kg)(1)

08
2
3
5

L+N

02
04
05
07

Tap-off units without comms rewirable


16 A unfused tap-off unit

Feed units for double sided system


Double sided feed units come with 2 x 25 mm
cable entry holes for each side of the bar, plus a
further 2 x 16 mm . holes for the comms side of
the bar
Single screw cable terminals are provided for
power and data. Supplied with end stops

Rewirable tap-off unit to pick-up L1+N, colour


coded white, can plug into any tap-off outlet
1

DDF4

25 A left
25 A right
40 A left
40 A right

129
151
139
161

Flexible lengths for double sided system


Flexible lengths can be used to change
direction, change level or overcome obstructions
Suspended right to left
1
1
1
1

BBA240XC
BBA242XC
CCA240XC
CCA242XC

Length
(m)

Rating
(A)

Weight
(kg)(1)

05
2
05
2

25
25
40
40

314
367
325
391

L+N

014

Rewirable tap-off unit to pick-up L1+N, supplied


with BS 1362 fuse, colour coded white, can plug
into any tap-off outlet

Weight(kg)(1)

BBA24LFC
BBA24RFC
CCA24LFC
CCA24RFC

Weight
(kg)(1)

13 A fused tap-off unit

Suspended
1
1
1
1

Fixed
polarity

DDF4F

Fixed
polarity

Weight
(kg)(1)

L+N

014

(1) Weights shown are for IP 4X rated buscom. For all other
weights, contact us on +44 (0) 845 600 6266

Key : How to select the correct components


All examples on this page show IP 4X buscom trunking
IP rating and tap-off type is dictated by the red letters
4 = IP 4X. For IP 54 version, replace 4 with 5
C = Tap-off with communications circuit
For power only, remove the C

29

LTK_Bro_028_029 v3.indd 29

22/08/2012 16:18

Electrak 31 3P + E buscom trunking


power and communication distribution

CCB3145C

CCB2145C

CCB14RFC

CCB142XC

CCB14LFC
Selection chart (p. 24-27)
Dimensions and technical information (p. 38-43)
Integral communication bus suitable for KNX, Lonworks, DALI, protocols etc. 25 A and 40 A systems
Outlets on one or two sides. IP 4X or IP 54 ingress protection
Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
Pack

Cat. Nos.

Electrak 31
3P + E single sided system

Pack

Cat. Nos.

Flexible lengths can be used to change


direction, change level or overcome
obstructions

3P + E buscom trunking system with integral


communications bus circuit available in IP 4X
and IP 54 versions
Socket outlets are colour coded white and are
located on just one side of the bar
3P + E trunking lengths
Trunking lengths push fit into each other, and
feed units or flexible lengths. Trunking lengths
can be surface mounted or suspended using the
various bracket options
1
1
1
1
1
1
1
1

25 A
BBB3145C
BBB2145C
BBB3141C
BBB2141C
40 A
CCB3145C
CCB2145C
CCB3141C
CCB2141C

Length
(m)

Tap-off
outlets

Weight
(kg)(1)

3
2
3
2

6
4
3
2

462
337
458
334

3
2
3
2

6
4
3
2

477
347
473
344

C
L2
L1
N
PE

Flexible lengths for single sided system

Suspended right to left


1
1
1
1

BBB140XC
BBB142XC
CCB140XC
CCB142XC

Length
(m)

Rating
(A)

Weight
(kg)(1)

05
2
05
2

25
25
40
40

304
340
308
356

Surface mounted right to left


1
1
1
1

BBB340XC
BBB342XC
CCB340XC
CCB342XC

Length
(m)

Rating
(A)

Weight
(kg)(1)

05
2
05
2

25
25
40
40

299
332
300
348

Feed units for single sided system


Feed units come with 2 x 25 mm and
2 x 16 mm cable entry holes and single screw
cable terminals for power and data
Left feed units are supplied with right end stop
Right feed units are supplied with left end stop
Centre feed units are supplied with right and left
end stops
Suspended
Weight
(kg)(1)

1
1
1
1

BBB14LFC
BBB14RFC
CCB14LFC
CCB14RFC

25 A left
25 A right
40 A left
40 A right

125
148
133
155

Surface mounted
Weight
(kg)(1)

1
1
1
1

BBB34LFC
BBB34RFC
CCB34LFC
CCB34RFC

25 A left
25 A right
40 A left
40 A right

129
152
137
159

Centre feed
Weight
(kg)(1)

1
1

BBB44FC
CCB44FC

25 A
40 A

18
18

(1) Weights shown are for IP 4X rated buscom. For all other
weights, contact us on +44 (0) 845 600 6266

Key : How to select the correct components


All examples on this page show IP 4X buscom trunking
IP rating is dictated by the red letters
4 = IP 4X. For IP 54 version, replace 4 with 5

30

LTK_Bro_030_031 v3.indd 30

23/08/2012 14:05

Electrak 31 3P + E buscom trunking


power and communication distribution

CCB3245C

CCB2245C

DDE45
DDE45C
DDH4F
Selection chart (p. 24-27)
Dimensions and technical information (p. 38-43)
Integral communication bus suitable for KNX, Lonworks, DALI protocols,
etc. 25 A and 40 A systems
Outlets on one or two sides. IP 4X or IP 54 ingress protection
Fast installation (trunking push fits together in seconds). High quality
materials. Suspended or surface mounted
Pack

Cat. Nos.

Trunking lengths push fit into each other, and feed


units or flexible lengths. Double sided trunking
must be fixed using suspended fixing brackets

1
1
1
1

Length
(m)

Tap-off
outlets

Weight
(kg)(1)

3
2
3
2

11
7
6
4

515
372
506
368

3
2
3
2

11
7
6
4

545
392
536
388

Length
(m)

1
1
1
1
1
1
1
1

DDE408C
DDE42C
DDE43C
DDE45C
DDG408C
DDG42C
DDG43C
DDG45C

PE
N
L1
L2

C
L2
L1
N
PE

Suspended
Weight (kg)(1)

25 A left
25 A right
40 A left
40 A right

Length
(m)

1
1
1
1
1
1
1
1

DDE408FC
DDE42FC
DDE43FC
DDE45FC
DDG408FC
DDG42FC
DDG43FC
DDG45FC

08
2
3
5
08
2
3
5

Fixed
polarity

L+N

L1 + L2 + N

Weight
(kg)(1)

02
04
05
07
02
04
05
07

Tap-off units without comms rewirable

1
1

DDF4
DDH4

Fixed
polarity

Weight
(kg)(1)

L+N
L1 L2 N1

014
014

13 A fused tap-off unit


Rewirable tap-off units supplied with BS 1362
fuse, colour coded white, can plug into any
tap-off outlet

Flexible lengths can be used to change


direction, change level or overcome obstructions
Suspended right to left
BBB240XC
BBB242XC
CCB240XC
CCB242XC

L1 + L2 + N

02
04
05
07
02
04
05
07

16 A unfused tap-off unit


Rewirable tap-off units colour coded white, can
plug into any tap-off outlet

135
158
149
172

Flexible lengths for double sided system

1
1
1
1

L+N

Weight
(kg)(1)

Pre-wired tap-off units to pick-up L1, L2+N,


supplied with BS 1362 fuse, colour coded white

Feed units for double sided system

BBB24LFC
BBB24RFC
CCB24LFC
CCB24RFC

08
2
3
5
08
2
3
5

Fixed
polarity

13 A fused tap-off units

Double sided feed units come with 2 x 25 mm


cable entry holes for each side of the bar, plus
a further 2 x 16 mm . holes for the comms side
of the bar. Single screw cable terminals are
provided for power and data

1
1
1
1

Tap-off units with and without comms


Power only tap-offs can plug into any tap-off outlet
Tap-offs with comms can only be plugged into the
comms side of the bar
16 A unfused tap-off units
Pre-wired tap-off units to pick up L1, L2+N,
colour coded white

3P + E trunking lengths

25 A
BBB3245C
BBB2245C
BBB3241C
BBB2241C
40 A
CCB3245C
CCB2245C
CCB3241C
CCB2241C

Cat. Nos.

Electrak 31
3P + E double sided system
3P + E buscom trunking system with integral
communications bus circuit available in IP 4X
and IP 54 versions
Socket outlets are colour coded white and are
located on both sides of the bar
The comms circuit is only available on one side
of the bar as shown in the diagram below

1
1
1
1

Pack

Length
(m)

Rating
(A)

Weight
(kg)(1)

05
2
05
2

25
25
40
40

345
403
353
435

1
1

DDF4F
DDH4F

Fixed
polarity

Weight
(kg)(1)

L+N
L1 L2 N1

014
014

(1) Weights shown are for IP 4X rated buscom. For all other
weights, contact us on +44 (0) 845 600 6266

Key : How to select the correct components


All examples on this page show IP 4X buscom trunking
IP rating and tap-off type is dictated by the red letters
4 = IP 4X. For IP 54 version, replace 4 with 5
C = Tap-off with communications circuit. For power only, remove the C

31

LTK_Bro_030_031 v3.indd 31

22/08/2012 16:20

Electrak 32 4P + E (dual circuit) buscom trunking


power and communication distribution

CCC3145C

CCC2145C

CCC14RFC

CCC142XC

CCC14LFC
Selection chart (p. 24-27)
Dimensions and technical information (p. 38-43)
Integral communication bus suitable for KNX, Lonworks, DALI protocols, etc. 25 A and 40 A systems
Outlets on one or two sides. IP 4X or IP 54 ingress protection
Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
Pack

Cat. Nos.

Electrak 32
4P + E (dual circuit) single sided system

Pack

Cat. Nos.

Flexible lengths can be used to change


direction, change level or overcome
obstructions

Dual circuit buscom trunking system with integral


communications bus circuit available in IP 4X
and IP 54 versions
Socket outlets are colour coded white and are
located on just one side of the bar
4 P + E trunking lengths
Trunking lengths push fit into each other, and
feed units or flexible lengths. Trunking lengths
can be surface mounted or suspended using the
various bracket options
1
1
1
1
1
1
1
1

25 A
BBC3145C
BBC2145C
BBC3141C
BBC2141C
40 A
CCC3145C
CCC2145C
CCC3141C
CCC2141C

Length
(m)

Tap-off
outlets

Weight
(kg)(1)

3
2
3
2

6
4
3
2

477
347
473
344

3
2
3
2

6
4
3
2

497
361
493
358

C
L2
N2
L1
N1
PE

Flexible lengths for single sided system

Suspended right to left


1
1
1
1

BBC140XC
BBC142XC
CCC140XC
CCC142XC

Length
(m)

Rating
(A)

Weight
(kg)(1)

05
2
05
2

25
25
40
40

317
359
322
379

Surface mounted right to left


1
1
1
1

BBC340XC
BBC342XC
CCC340XC
CCC342XC

Length
(m)

Rating
(A)

Weight
(kg)(1)

05
2
05
2

25
25
40
40

309
351
314
371

Feed units for single sided system


Feed units come with 2 x 25 mm and
2 x 16 mm cable entry holes and single screw
cable terminals for power and data
Left feed units are supplied with right end stop
Right feed units are supplied with left end stop
Centre feed units are supplied with right and left
end stops
Suspended
Weight
(kg)(1)

1
1
1
1

BBC14LFC
BBC14RFC
CCC14LFC
CCC14RFC

25 A left
129
25 A right
152
40 A left
138
40 A right
161
Surface mounted
Weight
(kg)(1)

1
1
1
1

BBC34LFC
BBC34RFC
CCC34LFC
CCC34RFC

25 A left
25 A right
40 A left
40 A right
Centre feed

133
156
142
165
Weight
(kg)(1)

1
1

BBC44FC
CCC44FC

25 A
40 A

18
18

(1) Weights shown are for IP 4X rated buscom. For all other
weights, contact us on +44 (0) 845 600 6266

Key : How to select the correct components


All examples on this page show IP 4X buscom trunking
IP rating is dictated by the red letters
4 = IP 4X. For IP 54 version, replace 4 with 5

32

LTK_Bro_032_033 v3.indd 32

23/08/2012 14:06

Electrak 32 4P + E (dual circuit) buscom trunking


power and communication distribution

CCC3245C

CCC2245C

DDJ45
DDJ45C
DDK4F
Selection chart (p. 24-27)
Dimensions and technical information (p. 38-43)
Integral communication bus suitable for KNX, Lonworks, DALI protocols,
etc. 25 A and 40 A systems
Outlets on one or two sides. IP 4X or IP 54 ingress protection
Fast installation (trunking push fits together in seconds). High quality
materials. Suspended or surface mounted
Pack

Cat. Nos.

4 P + E trunking lengths
Trunking lengths push fit into each other, and
feed units or flexible lengths. Double sided
trunking must be fixed using suspended fixing
brackets

1
1
1
1

25 A
BBC3245C
BBC2245C
BBC3241C
BBC2241C
40 A
CCC3245C
CCC2245C
CCC3241C
CCC2241C

Length
(m)

Tap-off
outlets

Weight
(kg)(1)

3
2
3
2

11
7
6
4

546
392
537
388

3
2
3
2

11
7
6
4

586
470
577
415

BBC24LFC
BBC24RFC
CCC24LFC
CCC24RFC

PE
N1
L1
N2
L2

C
L2
N2
L1
N1
PE

DDE408C
DDE42C
DDE43C
DDE45C
DDJ408C
DDJ42C
DDJ43C
DDJ45C

08
2
3
5
08
2
3
5

Fixed
polarity

L1 + N1

L2 + N2

Weight
(kg)(1)

02
04
05
06
02
04
05
06

13 A fused tap-off units


Pre-wired tap-off units to pick up L1+N1 or L2+N2,
supplied with BS 1362 fuse, colour coded white
1
1
1
1
1
1
1
1

DDE408FC
DDE42FC
DDE43FC
DDE45FC
DDJ408FC
DDJ42FC
DDJ43FC
DDJ45FC

08
2
3
5
08
2
3
5

Fixed
polarity

L1 + N1

L2 + N2

Weight
(kg)(1)

02
04
05
06
02
04
05
06

Feed units for double sided system

Tap-off units without comms rewirable


16 A unfused tap-off units
Rewirable tap-off units to pick up required
circuit, colour coded white, can plug into any
tap-off outlet

25 A left
25 A right
40 A left
40 A right

1
1

DDF4
DDK4

Fixed
polarity

Weight
(kg)(1)

L1 + N1
L2 + N2

014
014

13 A fused tap-off units


Rewirable tap-off units to pick up required
circuit, supplied with BS 1362 fuse, colour coded
white, can plug into any tap-off outlet

142
164
160
183

Flexible lengths can be used to change


direction, change level or overcome obstructions
Suspended right to left
BBC240XC
BBC242XC
CCC240XC
CCC242XC

Length
(m)

1
1
1
1
1
1
1
1

Double sided feed units come with 2 x 25 mm


cable entry holes for each side of the bar, plus
a further 2 x 16 mm . holes for the comms side
of the bar. Single screw cable terminals are
provided for power and data
Supplied with end stops
Suspended

Flexible lengths for double sided system

1
1
1
1

Tap-off units with and without comms


Power only tap-offs can plug into any tap-off outlet
Tap-offs with comms can only be plugged into the
comms side of the bar
16 A unfused tap-off units
Pre-wired tap-off units to pick up L1+N1 or
L2+N2, colour coded white

Length
(m)

Weight
(kg)(1)

1
1
1
1

Cat. Nos.

Electrak 32
4P + E (dual circuit) double sided system
Dual circuit buscom trunking system with integral
communications bus circuit available in IP 4X
and IP 54 versions
Socket outlets are colour coded white and are
located on both sides of the bar
The comms circuit is only available on one side
of the bar as shown in the diagram below

1
1
1
1

Pack

Length
(m)

Rating
(A)

Weight
(kg)(1)

05
2
05
2

25
25
40
40

342
452
391
532

1
1

DDF4F
DDK4F

Fixed
polarity

Weight
(kg)(1)

L1 + N1
L2 + N2

014
014

(1) Weights shown are for IP 4X rated buscom. For all other
weights, contact us on +44 (0) 845 600 6266

Key : How to select the correct components


All examples on this page show IP 4X buscom trunking
IP rating and tap-off type is dictated by the red letters
4 = IP 4X. For IP 54 version, replace 4 with 5
C = Tap-off with communications circuit. For power only, remove the C

33

LTK_Bro_032_033 v3.indd 33

22/08/2012 16:21

Electrak 33 4P + E (3 phase) buscom trunking


power and communication distribution

CCD3145C

CCD2145C

CCD14RFC

CCD142XC

CCD14LFC
Selection chart (p. 24-27)
Dimensions and technical information (p. 38-43)
Integral communication bus suitable for KNX, Lonworks, DALI protocols, etc. 25 A and 40 A systems
Outlets on one or two sides. IP 4X or IP 54 ingress protection
Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
Pack

Cat. Nos.

Electrak 33
4P + E (3 phase) single sided system

Pack

Cat. Nos.

3 phase buscom trunking system with integral


communications bus circuit available in IP 4X
and IP 54 versions
Socket outlets are colour coded grey and are
located on just one side of the bar
4 P + E trunking lengths
Trunking lengths push fit into each other, and
feed units or flexible lengths. Trunking lengths
can be surface mounted or suspended using the
various bracket options
1
1
1
1
1
1
1
1

25 A
BBD3145C
BBD2145C
BBD3141C
BBD2141C
40 A
CCD3145C
CCD2145C
CCD3141C
CCD2141C

Length
(m)

Tap-off
outlets

Weight
(kg)(1)

3
2
3
2

6
4
3
2

477
347
475
344

3
2
3
2

6
4
3
2

497
361
493
358

C
L3
L2
L1
N1
PE

Flexible lengths for single sided system


Flexible lengths can be used to change
direction, change level or overcome
obstructions
Suspended right to left

1
1
1
1

BBD140XC
BBD142XC
CCD140XC
CCD142XC

Length
(m)

Rating
(A)

Weight
(kg)(1)

05
2
05
2

25
25
40
40

317
359
322
379

Surface mounted right to left


1
1
1
1

BBD340XC
BBD342XC
CCD340XC
CCD342XC

Length
(m)

Rating
(A)

Weight
(kg)(1)

05
2
05
2

25
25
40
40

309
351
314
371

Feed units for single sided system


Feed units come with 2 x 25 mm and
2 x 16 mm cable entry holes and single screw
cable terminals for power and data
Left feed units are supplied with right end stop
Right feed units are supplied with left end stop
Centre feed units are supplied with right and left
end stops
Suspended
Weight
(kg)(1)

1
1
1
1

BBD14LFC
BBD14RFC
CCD14LFC
CCD14RFC

25 A left
129
25 A right
152
40 A left
138
40 A right
161
Surface mounted
Weight
(kg)(1)

1
1
1
1

BBD34LFC
BBD34RFC
CCD34LFC
CCD34RFC

25 A left
25 A right
40 A left
40 A right
Centre feed

133
156
142
165
Weight
(kg)(1)

1
1

BBD44FC
CCD44FC

25 A
40 A

180
180

(1) Weights shown are for IP 4X rated buscom. For all other
weights, contact us on +44 (0) 845 600 6266

Key : How to select the correct components


All examples on this page show IP 4X buscom trunking
IP rating is dictated by the red letters
4 = IP 4X. For IP 54 version, replace 4 with 5

34

LTK_Bro_034_036 v2.indd 34

23/08/2012 14:07

Electrak 33 4P + E (3 phase) buscom trunking


power and communication distribution

CCD3245C

CCD2245C

DDM408L1C

DDM408L1

Selection chart (p. 24-27)


Dimensions and technical information (p. 38-43)
Integral communication bus suitable for KNX, Lonworks, DALI protocols, etc. 25 A and 40 A systems
Outlets on one or two sides. IP 4X or IP 54 ingress protection
Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
Pack

Cat. Nos.

Electrak 33
4P + E (3 phase) double sided system

Pack

Cat. Nos.

3 phase buscom trunking system with integral


communications bus circuit available in IP 4X
and IP 54 versions
Socket outlets are colour coded grey and are
located on both sides of the bar
The comms circuit is only available on one side
of the bar as shown in the diagram below

Pre-wired tap-off units to pick up required circuit,


colour coded grey
Length
(m)

4 P + E trunking lengths
Trunking lengths push fit into each other, and
feed units or flexible lengths. Double sided
trunking must be fixed using suspended fixing
brackets
1
1
1
1
1
1
1
1

25 A
BBD3245C
BBD2245C
BBD3241C
BBD2241C
40 A
CCD3245C
CCD2245C
CCD3241C
CCD2241C

Length
(m)

Tap-off
outlets

Weight
(kg)(1)

3
2
3
2

11
7
6
4

546
392
537
388

3
2
3
2

11
7
6
4

586
470
577
415

PE
N
L1
L2
L3

C
L3
L2
L1
N
PE

1
1
1
1
1
1
1
1
1
1
1
1

DDM408L1C
DDM42L1C
DDM43L1C
DDM45L1C
DDM408L2C
DDM42L2C
DDM43L2C
DDM45L2C
DDM408L3C
DDM42L3C
DDM43L3C
DDM45L3C

Double sided feed units come with 2 x 25 mm


cable entry holes for each side of the bar, plus
a further 2 x 16 mm . holes for the comms side
of the bar. Single screw cable terminals are
provided for power and data
Suspended
BBD24LFC
BBD24RFC
CCD24LFC
CCD24RFC

25 A left
25 A right
40 A left
40 A right

142
164
160
183

Flexible lengths for double sided system


Flexible lengths can be used to change
direction, change level or overcome obstructions

Fixed
polarity

L1 + N

L2 + N

L3 + N

Weight
(kg)(1)

02
04
05
06
02
04
05
06
02
04
05
06

Pre-wired tap-off units to pick up required circuit,


supplied with BS 1362 fuse, colour coded grey,
can plug into any
Electrak 33 tap-off outlet
Length
(m)

1
1
1
1
1
1
1
1

Weight
(kg)(1)

08
2
3
5
08
2
3
5
08
2
3
5

13 A fused tap-off units

Feed units for double sided system

1
1
1
1

Tap-off units
Power only tap-offs can plug into any tap-off outlet
of the 3 phase bar
Tap-offs with comms can only be plugged into the
comms side of the 3 phase bar
16 A unfused tap-off units

1
1
1
1

DDM408L1FC
DDM42L1FC
DDM43L1FC
DDM45L1FC
DDM408L2FC
DDM42L2FC
DDM43L2FC
DDM45L2FC
DDM408L3FC
DDM42L3FC
DDM43L3FC
DDM45L3FC

08
2
3
5
08
2
3
5
08
2
3
5

Fixed
polarity

L1 + N

L2 + N

L3 + N

Weight
(kg)(1)

02
04
05
06
02
04
05
06
02
04
05
06

(1) Weights shown are for IP 4X rated buscom. For all other
weights, contact us on +44 (0) 845 600 6266

Suspended right to left


1
1
1
1

BBD240XC
BBD242XC
CCD240XC
CCD242XC

Length
(m)

Rating
(A)

Weight
(kg)(1)

05
2
05
2

25
25
40
40

342
452
391
532

Key : How to select the correct components


All examples on this page show IP 4X buscom trunking
IP rating and tap-off type is dictated by the red letters
4 = IP 4X. For IP 54 version, replace 4 with 5
C = Tap-off with communications circuit. For power only, remove the C

35

LTK_Bro_034_036 v2.indd 35

22/08/2012 16:22

Electrak 33 4P + E (3 phase) buscom trunking


power and communication distribution

DDN4L1F

DDR43

Selection chart (p. 24-27)


Dimensions and technical information (p. 38-43)
Integral communication bus suitable for KNX, Lonworks, DALI protocols, etc. 25 A and 40 A systems
Outlets on one or two sides. IP 4X or IP 54 ingress protection
Fast installation (trunking push fits together in seconds). High quality materials. Suspended or surface mounted
Pack

Cat. Nos.

Tap-off units without comms rewirable

Pack

Cat. Nos.

16 A unfused tap-off units


Rewirable tap-off units to pick up required
circuit, colour coded grey, can plug into any
Electrak 33 tap-off outlet
1
1
1

DDN4L1
DDN4L2
DDN4L3

Fixed
polarity

Weight
(kg)(1)

L1 + N
L2 + N
L3 + N

014
014
014

13 A fused tap-off units


Rewirable tap-off units to pick up required
circuit, supplied with BS 1362 fuse, colour coded
grey, can plug into any
Electrak 33 tap-off outlet
1
1
1

DDN4L1F
DDN4L2F
DDN4L3F

Fixed
polarity

Weight
(kg)(1)

L1 + N
L2 + N
L3 + N

014
014
014

Tap-off units without comms


4P + E pre-wired
(LSOH 5 x 15 mm2 cable)
16 A unfused tap-off units
Pre-wired tap-off units to pick up required circuit,
colour coded grey, can plug into any
Electrak 33 tap-off outlet

1
1
1
1

DDR408
DDR42
DDR43
DDR45

Length
(m)

Fixed
polarity

08
2
3
5

L+L+L+N
L+L+L+N
L+L+L+N
L+L+L+N

Weight
(kg)(1)

020
036
050
063

Phase selectable tap-off units without


comms 2P + E terminals rewirable
16 A unfused tap-off unit
Rewirable tap-off units, phase selectable, colour
coded grey, can plug into any
Electrak 33 tap-off outlet
1

DDP4S

Fixed
polarity

Weight
(kg)(1)

L+N

014

13 A fused tap-off unit


Rewirable tap-off units, phase selectable,
supplied with BS 1362 fuse, colour coded grey,
can plug into any Electrak 33 tap-off outlet
1

DDP4SF

Fixed
polarity

Weight
(kg)(1)

L+N

014

(1) Weights shown are for IP 4X rated buscom. For all other
weights, contact us on +44 (0) 845 600 6266

Key : How to select the correct components


All examples on this page show IP 4X buscom trunking
IP rating is dictated by the red letters
4 = IP 4X. For IP 54 version, replace 4 with 5

36

LTK_Bro_034_036 v2.indd 36

23/08/2012 14:08

Electrak buscom trunking


fixings and ancillary items

EEC348

EEA304

EEC356

EEB340

EEB344

EEA312

EEA308

EEA328

EEA332

EEA324

EEC352

EEC360

EEC364

Dimensions and technical information (p. 41)


Brackets are manufactured from robust galvanised steel, ensuring that the entire installation can be expected to stand up to all normal site conditions
Pack

Cat. Nos.

Fixings

EEA304

Ancillary items

Pack

Cat. Nos.

Trunking 57 mm edge surface mounting fixing


bracket

EEC356

2 m empty length for adjusting the length at the


end of a run (to be cut)

EEA308

Trunking suspended fixing bracket

EEC360

IP 54 outlet cover (spare or replacement)

EEA312

Trunking suspended fixing bracket c/w cable


duct stirrup. Used when running cable duct on
top of buscom trunking

EEC364

Joint sleeve is used if load is hung off trunking


joint or near when joint is centre of a fixing span

EEC366

Left hand end stop spare

EEA324

Luminaire suspension fixing bracket

EEC368

Right hand end stop spare

EEA328

Luminaire 45 mm edge suspension fixing


bracket (clip on)

EEA332

Luminaire 57 mm edge suspension fixing


bracket (clip on)

EEB340

Open hook luminaire suspended bracket

EEB344

Closed ring on luminaire

EEC348

Cable duct 3 m long x 50 mm(w) x 13 mm(h)

EEC357

Joint bracket cable duct

EEC352

Cable duct fixing bracket

37

LTK_Bro_037 v2.indd 37

22/08/2012 16:24

Electrak buscom trunking


technical information
n Standards

Electrical test data

ASTA approved to BS EN 60439-2 and IEC 439-2


Manufactured within an approved ISO 9001 : 2008 facility
Assessed Quality Assurance Certificate No. 10679
Electrak fully complies with the requirements of BS 7671 : 2008
(IEE Wiring Regulations)

n Buscom trunking options


L
N
PE

L2
L1
N
PE

L2
N2
L1
N1
PE

L3
L2
L1
N
PE

25 A

40 A

UOM

Derating factor for Electrak 32 single sided

08

Derating factor for Electrak 32 double sided


08
07

Derating factor for Electrak 33 double sided

08

Rated operational voltage (Ue)


230/400 230/400 V
Rated insulation voltage (Ui)
500
500
V
Frequency (f)
50/60
50/60
Hz
Rated impulse withstand voltage
40
40
KV
39
27
m/m
Busbar resistance (R20)
42
30
m/m
Resistance (R1)
48
34
m/m
Impedance (Z1)
25
16
m/m
Reactance (X1)
Protective conductor
15
15
m/m

Communication bus

Electrak buscom trunking can be used with Electraks cost effective


lighting control system, Lightrak KNX, or any other systems using
control protocols such as KNX, Lonworks, DALI, etc.
Electraks overhead trunking couples high quality engineering with
rigidity of design, and provides power for a variety of applications
including lighting, heating and ventilation. The robust easy fix modular
system permits loads to be suspended directly from the trunking using
Electraks various fixing brackets
Push fit connection keeps installation costs to a minimum

Volt drops

25 A

40 A

UOM

Live and neutral : busbars


(R1+R2) Feed unit
Tap-off 08 m
Tap-off 20 m
Flexible length assembly 05 m
Flexible length assembly 2 m

90
30
220
520
50
200

60
24
220
520
35
140

mV/A/m
mV/A
mV/A
mV/A
mV/A
mV/A

Earth fault loop

25 A

40 A

UOM

Impedance : busbar
Earth housing
Feed unit
Tap-off 08m
Tap-off 20m
Flexible length assembly 05 m
Flexible length assembly 2 m
Rated conditional short-circuit current (Icc)
Rated short time withstand current (Icw) at 1 sec
Rated peak short-circuit current (Ipk)
Ambient temperature

45
15
24
230
530
25
100
160
065
0975
350

30
15
24
230
530
175
70
160
10
15
350

m/m
m/m
m
m
m
mV/A
mV/A
KA
KA
KA
C

Mechanical data

25 A

40 A

UOM

Track lengths simply push fit together

n Feed units
25 A rated - max. conductor size 6 mm2
40 A rated - max. conductor size 16 mm2
Double sided trunking feed units have power
cable terminals on both sides.
IP 4X galvanised steel
IP 54 ABS

Number of conductors
Busbar conductor cross sectional area
Cable terminal capacity
Cable terminal capacity bus
Tap-off cable 16 A
Tap-off cable 13 A fused
Tap-off entry
Feed unit entry holes power
Feed unit entry holes bus
IP rating (optional)

2-10
2-10
40
60
60
160
15
15
15
15
15
15
160
160
250
250
160
160
4 X (54) 4 X (54)

mm2
mm2
mm2
mm2
mm2
mm
mm
mm

Direct protection by enclosure. Indirect protection by protective circuit

2 pole + earth + comms

Comms bus
Max. conductor size 15 mm2
Red +
Black -

38

LTK_Bro_038_043 v3.indd 38

22/08/2012 16:27

Electrak buscom trunking


technical data

Communication control circuit


Type
Construction
Insulation - conductor
Sheath

Bus cable (LSOH)


Sheathed 05 mm2 copper twisted pair
Flame retardant low emission HCL
LSOH material

Rated insulation voltage (Ui)


(between power circuit and bus)

500 V

Max. bus operating voltage


50 V
Max. bus operating current
065 A
Max. conductor resistance (@20C)
732 /km
Max. mutual capacitance
100 nf/km
Material specifications
Buscom trunking housing
Galvanised steel
Busbars
High conductivity copper
Busbar insulator
Flame retardant LSOH to BS 7211
Trunking connector / tap-off entry box / cable connector
Flame retardant polycarbonate
Tap-off housing
Flame retardant polycarbonate
Trunking connector blades / tap-off blades
Copper
Feed unit IP 4X
Galvanised steel
Feed unit IP 54
ABS
Flexible length conduit
Flame retardant LSOH nylon
Feed unit terminals / earth block
Brass
Brackets
Galvanised steel
13 A tap-off, fuse
To BS 1362, ASTA approved
Durability
Electrak power and communications distribution systems are well designed and extremely robust. They can be expected to stand up to all normal
site conditions Electrak has been short circuit strength tested by ASTA
Earth fault loop impedance
BS 7671 : 2008 IEE Wiring Regulations require accurate determination of the total earth loop impedance, which must be sufficiently low to allow
the protective device to operate within the specified time, which for socket outlets is 04 seconds
The values relevant to Electrak for calculating the earth fault loop impedance are shown in the electrical test data table, see opposite
Buscom trunking rating in ambient temperatures
Average ambient air temperature
Rating factor (K1)

25C

30C

35C

40C

45C

50C

11

105

095

090

085

For ambient temperatures other than 35C apply the multiplier factor K1 to the rated current
Buscom trunking mechanical loading
For point loads and evenly distributed loads the maximum weight that can be supported is given below
Maximum loading for suspended buscom trunking
Fixing distance (m)

15

25

35

Max. point load (deflection = 1/500 x span) (Kg)

20

17

13

12

Max. distributed load (deflection = 1/500 x span) (Kg)

33

28

22

20

15

12

Max. point load (deflection = 1/350 x span) (Kg)

33

24

18

16

10

Max. distributed load (deflection = 1/350 x span) (Kg)

55

40

30

26

16

15

Maximum loading for surface mounted buscom trunking


Fixing distance in metres (m)

15

25

35

Max. point load (deflection = 1/500 x span) (Kg)

10

45

35

Max. distributed load (deflection = 1/500 x span) (Kg)

16

10

75

Max. point load (deflection = 1/350 x span) (Kg)

13

10

Max. distributed load (deflection = 1/350 x span) (Kg)

20

16

11

10

Notes
1. Where trunking joints occur in the middle of the suspension span, and weight is to be suspended from that point, it is recommened to use a
strenghting bracket EEC364 over the joint to stop deflection
2. If the load requirements exceed the above figures, please contact us on +44 (0) 845 600 6266
For design information and technical specification, please contact us on +44 (0) 845 600 6266
Suspension rods and fixings should be of suitable size to carry the weight of both the track and suspended load

39

LTK_Bro_038_043 v3.indd 39

22/08/2012 16:27

Electrak buscom trunking


dimensions

n Fixing dimensions
Buscom trunking 3 m
05 m outlet spacings
220

1955

3 000

500

1955

500

500

500

1 000

500

1 000

3045

8045

05 m outlet spacings

Buscom trunking 2 m

Buscom trunking
End view

05 m outlet spacings

2 000
45

1955

220

500

500

500

3045
32

57

1955

1 000

8045

Suspended feed unit

05 m outlet spacings

Feed unit left

Single sided
system

Feed unit right

Double sided
system

2 x 16

2 x 16

148

57

209

308

220

517

2 x 25

209

104

End view both have 2 x 16 mm holes


extra in comms feed

429

Surface feed unit end view

End stop left

End stop right

4 x 25
52

148

52
10

220

320

2 x 25

2 x 16

Centre feed front view

57

2 x 25
220

218

2 x 16
300

308

828

All dimensions (mm) are nominal

40

LTK_Bro_038_043 v3.indd 40

22/08/2012 16:28

Cat. No. EEA304 Surface trunking fixing bracket


with trunking clipped in
107
75

Cat. No. EEA324 Luminaire


suspended fixing bracket

30

92

75

82
7

997

945

60

15

8.5
22
57

12
85
38

Cat. No. EEA308 Suspended trunking


fixing bracket
82
85

Cat. No. EEA328 Luminaire 45 mm


edge suspension fixing bracket

12
70

38

21

21

13

108

125

130

85

30

60

35

Cat. No. EEA332 Luminaire 57 mm


edge suspension fixing bracket

21

82
38

535

Cat. No. EEA312 Suspended trunking


fixing bracket cable duct stirrup
12

85

85
39

6
30

78

141

163

85

Fused tap-off

Cat. No. EEC352 Cable duct fixing


bracket
12

Fuse holder

Tap-off
fuse removal

77

13

35

50

95

59

Pre-wired tap-offs 33 mm deep

68

Cat. No. EEB344


Closed ring hook

Cat. No. EEB340


Open hook
M5

70

70

M5

All dimensions (mm) are nominal

96

Rewirable and phase selection


tap-offs 35 mm deep

68

136

41

LTK_Bro_038_043 v3.indd 41

22/08/2012 16:28

Electrak buscom trunking


installation
n Design and installation
Electraks buscom trunking system comprises continuous lengths of galvanised steel trunking available in 2 m and 3 m lengths with integral
connectors and regular tap-off outlets on one or both sides
Each trunking run commences with a feed unit for electrical and comms bus cable termination. The connection between the trunking, the feed
unit and subsequent trunking lengths is push fit and requires no tools to terminate the connection or ensure good earthing. Each complete track
run is finished with an end stop. Flexible lengths can be used to overcome obstructions or used as corners where required
The trunking system is available with IP 4X or IP 54 ingress protection, fully factory tested and ASTA approved to BS EN 60439-2 : 2008
End stop
Push fit connection

1
2

To install - push fit parts together


To take apart - use a screwdriver to depress the locking catch

1
2

Left feed unit

Buscom trunking
lengths

2
1

Push in
to release

Considerations before installation


Calculate the distance between fixing brackets - the maximum fixing distance should not exceed 4 m. If loads are to be hung,
please consult loading charts on page 39. The maximum buscom trunking weight is 2 kg/m
When fixing brackets to drop rods or surfaces, see mounting details below
Suspended trunking fixing brackets

Cable duct clips


into bracket
EEA312
When using cable
duct along trunking

EEA308

EEC352
Cable duct bracket

EEB344
Surface mounted trunking fixing brackets

2
1
EEA304 57 mm Edge surface fixing bracket
Considerations before installation
Ensure surface is level. Screw fix through both fixing holes of
surface fixing brackets to surface with No. 8 fixing screws
Hook trunking into place and push fit to close

42

LTK_Bro_038_043 v3.indd 42

22/08/2012 16:28

Luminaire mounting fixing brackets :


suspended trunking

EEA324 Luminaire fixing brackets

EEA328 45 mm Edge luminaire fixing brackets (maximum load 5 kg)

Luminaire mounting fixing brackets :


surface trunking

EEA304

EEA304

EEA332
EEA332

EEB340

EEB344

EEA332 57 mm Edge luminaire fixing bracket (maximum load 5 kg)


See maximum loading charts p. 39
All dimensions (mm) are nominal

43

LTK_Bro_038_043 v3.indd 43

22/08/2012 16:29

Contact details
Quotations and Technical Support:
The Power Distribution Division of
Legrand Electric Ltd.
Great King Street North,
Birmingham, B19 2LF
Tel: +44 (0) 845 600 6266
Fax: +44 (0) 845 600 6760
E-mail: powersales.uk@legrand.co.uk
Customer Services:
The Power Distribution Division of
Legrand Electric Ltd.
No. 1 Industrial Estate
Medomsley Road, Consett,
County Durham, DH8 6SR
Tel: +44 (0) 845 600 6266
Fax: +44 (0) 845 600 6366
E-mail: powersales.uk@legrand.co.uk
Accounts:
Legrand Electric Ltd.
Great King Street North,
Birmingham, B19 2LF
Tel: +44 (0) 870 608 9000
Fax: +44 (0) 870 608 9004

Head office (UK and Ireland):


Legrand Electric Limited
Great King Street North, Birmingham, B19 2LF
Tel: 0870 608 9000 Fax: 0870 608 9004
Website: www.legrand.co.uk

This document is printed on sustainably sourced paper. Please recycle.