High and Extra High Voltage Cable System

66 - 500 kV XLPE Cable

S.C.C Group

Company Profile
Demirer Kablo is among the worlds leading manufacturers in the the high and extra high voltage energy
cables industry. Manufacturing telecommunication
cables, signalling cables and cable accessories
besides energy cables up to 500 kV and providing
laying, jointing, terminating, testing, supervision and
commissioning services, Demirer Kablo is a global
turnkey project contractor.
Satisfying the growing demand of energy, in todays
world, is one of the main prerequisities for industrial
growth and thus rise in living standards. Demirer
Kablo, with the cable systems it manufactured,
creates value in the energy transmission area and
contributes to satisfaction of this demand.
Demirer Kablo is committed to being the pioneering
company of the world in its sector. Continuing its
operations in this direction, Demirer Kablo puts
human and environment to the first place along with
customer satisfaction and carries out its research and
development activities in order to manufacture
energy cables providing more efficient, more reliable
and more clean energy transmission. In every region
we operate in the world, we take pride in contributing
to local societies. Being aware of our responsibility
towards human and environment, we always give
priority to occupational health and safety and
environmental consciousness, we preserve our high
ethical values, we abide by applicable laws, rules and
regulations and we respect local and national
culltures.
We are aware that our success depends on the confidence of our customers in us and our ability to continously satisfy their changing and challenging needs.
Alongside the products and services we provide with
the highest quality and most competitive prices;
always listening to them and providing them fast,
creative and innovative solutions whenever they are in
need, we are committed to satisfying our customers,
exceeding their expectations.

01

HV & EHV Cable Systems

In every region we operate in the world, we take pride in


contributing to local societies. Being aware of our
responsibility towards human and environment, we
always give priority to occupational health and safety and
environmental consciousness, we preserve our high
ethical values, we abide by applicable laws, rules and
regulations and we respect local and national culltures.
Demirer Kablo, working with most competent professionals, considers its highly skilled workforce as one of its
most important values, and with continous training,
ensures their adaptation to improving technology and
changing conditions. Our diversity, responsibility, open
communication, trust and kindness oriented culture
guides all of our 277 employees and hundreds of business partners who are all experts in their field.
State of the art manufacturing facility of Demirer Kablo,
having an outdoor area of 200.000 m2 and closed area of
40.000 m2, is founded in 1982. It consists of a cable
factory and an accessories factory, manufacturing cables
and accessories up to 500 kV. Three high technology
CDCC lines and a test laboratory are in operation in the
cable factory.
Demirer Kablos annual production capacity can reach
40.000 tonnes of cables depending on the type of product. As of 01.01.2013, Demirer Kablo manufactured and
delivered more than 7.400 kilometres of HV/EHV cables.
Cable systems of Demirer Kablo are certified through
type and prequalification Tests by KEMA, CESI, Georgia
Power and similar international institutions.
In addition to the 400kV cable systems supplied for the
local market, Demirer Kablo has completed High Voltage
and Extra High Voltage projects in over 60 countries,
from India to United States and from Saudi Arabia to
Iceland with complete customer satisfaction.
Relying on our flexibility in the face of change, our farseeing strategy and the excellence of our products and
services, we look to the future in complete confidence.
We believe that our inspiration and excitement on creating value and ambition to serve our customers better at
every occasion, will ensure our sustainable development.

HV & EHV Cable Systems

02

Brief History
1982
1983
1985
1987

Foundation of Demirer Kablo in Bozuyuk


Start of production with 35kV medium voltage cable
Acquisition of Demirer Kablos majority shares by Saudi Cable Company (SCC)
Acquisition of Kavel Kablo by SCC

1990
1990
1993
1994
1994
1995
1996
1997
2002
2003
2003

First high voltage cable production (69 kV)


Start of fiberoptic cables production by Kavel Kablo
Start of 154 kV high voltage cables production
Raise of SCC share in Demirer Kablo to 100%
Installation of 2nd CDCC line
Start of 220 kV extra high voltage cables production
Acquisition of ISO 9001 certificate
Relocation of Kavel Kablo factory near to Demirer Kablo factory in Bozuyuk
Reach of total produced HV cable length to 3000 km
Start of 380 kV high voltage cables development
Acquisition of ISO 14001 Environmental Management System Certificate
Merger of Demirer Kablo and Kavel Kablo under Demirer Kablo
(Kavel remains as the brand name for telecommunication cables)

2005
2006
2007
2008
2009
2009
2009
2011

03

Acquisition of OHSAS 18001 Certificate


First 380 kV turnkey project award by TEA in Turkey
Installation of 3rd CDCC line
Completion and energization of first 380 kV project
Completion of 380 kV long term prequalification test with success
Reach of total produced HV/EHV cable length to 7000 km
Finalization of sixth 380 kV turnkey project

HV & EHV Cable Systems

Content
1.00 Design & Construction of XLPE Cable

05

1.10 Manufacturing Process

08

1.20 CCV Production Line

09

1.30 Cable Construction & Continuous Current Ratings 10


1.40 XLPE Cable and Cable System Standards

12

1.50 Formulas

14

1.60 High and Extra High Voltage Cables

18

1.70 Quality Control

68

1.80 Cable Accessories

71

1.90 Cable System Configurations

73

HV & EHV Cable Systems

04

1.00

Design & Construction of XLPE Cable


Conductor
Conductor Screen
Insulation
Insulation Screen
Metallic Shield
Outer Sheath

Classification

Components

Material
Conductor
Shape
Insulation
Metallic Shield

Outer Sheath

Copper
Aluminium
Compacted Circular
Milliken

XLPE
Copper wire screen incorporated with copolymer coated AI or Cu tapes
Lead alloy sheath supported with copper wire screen
Lead alloy sheath
PVC
PE
Halogen free, fire retardant

Rated Voltage

Conductor size

60 - 550 (kV)

185 - 3,000 mm2

Typical conductor constructions:


Circular stranded compacted conductors up to 1,600 mm2
Milliken conductors up to 3,000 mm2 with 5 or 6 segments
Round solid aluminium conductors and Milliken copper conductors with
enameled wires are available.

05

HV & EHV Cable Systems

Conductor:
The cable consists of stranded compacted copper or
aluminum conductor. Milliken conductors are used
above 1,000 mm2 to reduce skin effect. The individual
segments are insulated from each other. Semi
conductive tape may be applied over conductor.
Longitudinal watertight design is provided
depending on environmental conditions.

Conductor screen, Insulation,


Insulation screen :
All three layers are simultaneously applied by a triple
extrusion process, using supersmooth, super clean
HV/EHV grade raw materials with immediate curing
on the CDCC (Completely Dry Curing and Cooling)
line. High quality handling system is used.
Average insulation thicknesses are defined in the
tables; lower thicknesses for insulation may be
offered.

Lead alloy sheath supported with copper wire


screen:
Radial watertightness is provided by extruded lead
sheath.
The copper wire screen is placed under lead sheath.
Screen area is in longitudinally watertight design by
water swellable tapes. Short circuit current is shared
proportionally by the copper wire screen and lead
sheath. Lead sheath provides excellent corrosion
resistance.
Lead alloy sheath:
Radial watertightness is provided by extruded lead
sheath. Longitudinal watertightness is achieved by
using water swellable tapes applied under lead sheath.
Lead sheath carries the short circuit current. Lead
sheath provides excellent corrosion resistance.
All above types of metallic sheaths can be designed to
carry extra high short circuit currents.

Metallic shields:
Copper wire screen incorporated with copolymer
coated Al or Cu tapes:
Copolymer coated metallic tapes are applied over the
copper wire screen to provide radial watertightness.
Metallic tape is bonded to the polyethylene outer
sheath to provide excellent mechanical properties.
Screen area is made longitudinally watertight by
means of water swellable tapes. Geometrical cross
section area of copper screen is choosen to suit the
short circuit requirements in each individual application. Subject types have low weight design.

Optical fibre:
Above metallic shields can be optionally equipped with
optical fibers in tubes for temperature monitoring.

Outer sheath:
HDPE sheath is used in most cases which guarantees
excellent mechanical and electrical strength. PE
sheaths are halogen free. Flame retardant paint can be
applied on site to limit the fire spread in building and
tunnel applications. PVC sheaths are used with different formulas optimized for the purposes. PVC sheaths
are also used when higher fire performance is required.
Halogen free and fire retardant sheaths are used when
higher fire performance is required in building and
tunnel applications. In order to facilitate the testing of
the outer sheath, a conductive layer is applied over it.

HV & EHV Cable Systems

06

XLPE Insulated with Cu Wire + Lead Sheath


Conductor
Conductor Screen
XLPE Insulation
Insulation Screen
Semiconducting Tape
Copper Wire Screen
Lead Sheath
PE or PVC Outer Sheath

XLPE Insulated with Cu Wire + AI Tape


Conductor
Conductor Screen
XLPE Insulation
1A
Semi Conducting Tape
Copper Wire Screen
Copper Tape
Aluminum Laminated Tape
PE or PVC Outer Sheath

3C

2B

XLPE Insulated with Lead Sheath

1A

07

HV & EHV Cable Systems


3C

Conductor
Conductor Screen
2B
XLPE Insulation
Insulation Screen
Semi Conducting Tape
Lead Sheath
Tape
PE or PVC Outer Sheath

1.10

Manufacturing Process
AL

CU

Drawing

Stranding
Stranding

Yarn

Compacted
Segment

Compacted
Round

Assemble

SC Tape
Segment
Assembl.

WB Tape

Taping

SC Layer

Insulation
Insulation

SC Layer

Degassing

Degassing & Taping


SC Tape

CU Wire Screen

Taping

WB Tape

Metallic
Screen

Lead Sheath

Outer
Sheath

HFFR

3C
PE

PVC

Sheating & Packing

Testing

Packing

Wooden Lagging

HV & EHV Cable Systems

08

CCV Production Line

Extrusion
Compounds coming from
clean room are extruded
by triple extrusion
Curing Zone
Compounds are
cured by heating
under pressurized
Nitrogen gas.

09

HV & EHV Cable Systems

Cooling Zone
Cured core is cooled down by circulating
Nitrogen gas.

1.30

Cable Construction & Continuous Current Ratings

Laying Conditions
a
b

Current carrying capacities are based on following conditions:


In air: 30 oC ambient temperature, load factor: 1.0
(Cables are assumed to be protected from direct solar radiation)
In soil: 25 oC ambient temperature,
thermal resistivity of the soil: 1 K.m/W, load factor: 1.0
Depth of laying: 1500 mm.
Arrangement of single core cables:
Trefoil formation: 3 cables laid in touching triangular bundles
Flat formation: 3 cables laid side by side,
"axial distance;" in soil: 3D , in air: 4D
D = Outer diameter of the cable

Earthing of metal sheaths or screens; cross bonding or single point bonding

Correction Factors For Various Laying Conditions


Correction Factors For Various Ambient Air Temperature
Air Temperatures (oC)

20 C

25 C

30 C

35 C

40 C

45 C

50 C

Rating Factor

1,09

1,05

0,95

0,9

0,85

0,8

Correction Factors For Various Ground Temperature


Ground Temperatures (oC)

15 C

20 C

25 C

30 C

35 C

40 C

45 C

Rating Factor

1,08

1,04

0,96

0,92

0,87

0,82

Correction Factors For Various Soil Thermal Resistivities


Soil Thermal Resistivity (km/W)

0,7

1,2

1,5

2,5

Rating Factor

1,13

0,93

0,85

0,74

0,67

0,62

1500

1750

2000

2500

0,98

0,96

Correction Factors For Various Depths of Laying


Depth of Laying (mm)

750

1000

1250

Rating Factor

1,1

1,06

1,03

HV & EHV Cable Systems

0,93

10

Technical Data
a) I thN, Max. short-circuit current on the conductor during 1 s, kA
Initial Temperature: 90oC , Final Temperature: 250oC
Cross Section ( mm2 )

Aluminium Conductor

Copper Conductor

240

22,6

34,3

300

28,2

42,9

400

37,6

57,2

500

47,0

71,5

630

59,2

90,1

800

75,2

114,4

1000

94,0

143,0

1200

112,8

171,6

1400

131,6

200,2

1600

150,4

228,8

2000

188,0

286,0

2500

235,0

357,5

282,0

429,0

0,094

0,143

3000
2

per mm

Short circuit current for various tripping times (Tk -sec), Ith

I th =

I thN
Tk

where,
I thN = short-circuit current for 1 second (as per above table)

11

HV & EHV Cable Systems

1.40

XLPE CABLE AND CABLE SYSTEM STANDARDS

DKs XLPE cable systems are designed to meet requirements of international and / or national standards.
Commonly used standards for HV/EHV cables are as follows:
IEC
(International Electrotechnical Commission)
IEC 60228
Conductors of insulated cables
IEC 60287
Electric cables Calculation of the current rating
IEC 60332
Tests on electric cables under fire conditions
IEC 60502
Power cables with extruded insulation and their
accessories
IEC 60840
Power cables with extruded insulation and their
accessories for rated voltage above 30 kV (Um=36 kV) up
to 150 kV (Um=170 kV). Test methods and requirements
IEC 60853
Calculation of the cyclic and emergency current rating of
cables
IEC 61443
Short circuit temperature limits of electric cables with
rated Voltages above 30 kV (Um = 36 kV)
IEC 60949
Calculation of thermally permissible short-circuit currents,
taking into account non-adiabatic heating effects
IEC 62067
Power cables with extruded insulation and their
accessories for rated voltage above 150 kV
(Um=170 kV) up to 500 kV (Um=550 kV)
Test methods and requirements

CENELEC
(European Commitee for Electrotechnical
Standardization)
HD 632
Power cables with extruded insulation and their
accessories for rated voltage above 36 kV
(Um=42 kV) up to 150 kV (Um=170 kV)
ICEA
(Insulated Cable Engineers Association,Inc.)
S-108-720
Standard for extruded insulated power cables
rated above 46 kV through 345 kV
AEIC
(Association of Edison Illuminating Companies)
CS 9
Specification for extruded insulation power cables
and their accessories rated above 46 kV through
345 kV AC
ISO
(International Organization for Standardization)
Our systems comply with the requirements of
ISO 9001
and
ISO 14001
OHSAS
(Occupation Health and Safety Assessments
Series)
Our systems comply with the requirements of
OHSAS 18001

HV & EHV Cable Systems

12

13

HV & EHV Cable Systems

1.50

Formulas

Load Current (I)


I =

For single phase ac systems

I =

For three-phase systems

P
( A)
U .Cos
P
( A)
3U .Cos

P=

load to be transmitted in kW

U=

operating voltage (phase to phase voltage) in kV

Cos

power factor of load

DC resistance at operating temperature, oC (R)

R = R20 (1+ 20 .) / km

where,
o
R20 = dc resistance of conductor at 20 C /km
20 = temperature coefficient of the resistance at
o
20 C, 1/deg C
for copper : 20 = 0.00393 1/deg C
for aluminium : 20 = 0.00403 1/deg C
= temperature difference (-20)

Operating capacitance

C =

5.56 r

D
ln
d

x10

-2

F / km

where,
r = dielectric constant of insulation
D
= diameter over insulation, mm
d
= diameter of conductor including semiconductive layer, if any, mm

Capacitive reactance, Xc

Xc =

10

/ km

Capacitance current
-3

Ic = Uo..C.10

A / km

where,

=
Uo =
C
=

angular frequency, 1/s


voltage between conductor and earth, kV
operating capacitance, F/km

HV & EHV Cable Systems

14

Formulas
Earth leakage current

Ie = 3Uo..C.10-3 A / km
Inductance per conductor
in trefoil formation,

L = 0 .2 (

1
a
+ ln
) mH / km
r
4

in flat formation,
mean inductance:

3
L m = 0 .2 (

1
+ ln
4

2a
r

where,
a
=
r
=

) mH / km

Inductive reactance, XL

X L = L.10-3 / km
(L in mH / km)
Three-phase active power, P

P =

3 . U . I . Cos

kW

Three-phase apparent power, S

S =

15

3 . U .I

kVA

HV & EHV Cable Systems

axial spacing of conductors, mm


raidus of conductor, mm

Formulas
Voltage drop
Three-phase current
U

3 . I . L .( R w . Cos

+ X L . Sin

). 10-3

Percentage voltage drop:


u

U
U

x 100 %

where,
U
=
I
=
Rw =
XL =
L
=

operating voltage, kV
load current, A
effective resistance, /km
inductive reactance, /km
length of cable, m
phase angle of load

where,
I
=
Rw =

load current, A
effective resistance, /km

Loses due to current ( I2 R Losses ), V


Under uniform load:
V=3.I2.Rw.10-3 kW / km

Dielectric losses, Vd
Vd

3 Uo2 . . C . tan . 10-3

kW / km

where,
Uo =

=
C
=
tan =

voltage between conductor and earth, kV


angular frequency, 1/s (2f)
operating capacitance, F/km
loss factor

Electric-field stress, E
Electric-field stress at radius x(mm), E x
Ex

Uo
x ln

kV / mm

R
r

R
r

Maximum electric-field stress


E max =

Uo

=
=

voltage between conductor and screen


or metallic sheath, kV
radius over insulation, mm
radius of conductor including
semi-conductive layers, if any, mm

kV / mm

R
r ln
r

Dynamic force between two conductors;


Fs

where,
Uo =

2 . 10-7 . Is2
a

kN / m

where,
a
=
IS
=

Phase axis distance (mm)


K . 2 . Ith

where in,
=
Impulse short-circuit current [kA]
IS
K
=
surge factor (usually defined as 1.8)
Ith
=
Short-circuit current [kA]

HV & EHV Cable Systems

16

17

HV & EHV Cable Systems

1.60

High and Extra High Voltage Cables


Voltage Level

Cable Type

38/66 (72,5) kV

XLPE INSULATED WITH Cu WIRE + AI TAPE

38/66 (72,5) kV

XLPE INSULATED WITH Cu WIRE + LEAD SHEATH

38/66 (72,5) kV

XLPE INSULATED WITH LEAD SHEATH

64/110 (123) kV

XLPE INSULATED WITH Cu WIRE + AI TAPE

64/110 (123) kV

XLPE INSULATED WITH Cu WIRE + LEAD SHEATH

64/110 (123) kV

XLPE INSULATED WITH LEAD SHEATH

76/132 (145) kV

XLPE INSULATED WITH Cu WIRE + AI TAPE

76/132 (145) kV

XLPE INSULATED WITH Cu WIRE + LEAD SHEATH

76/132 (145) kV

XLPE INSULATED WITH LEAD SHEATH

87/150 (170) kV

XLPE INSULATED WITH Cu WIRE + AI TAPE

87/150 (170) kV

XLPE INSULATED WITH Cu WIRE + LEAD SHEATH

87/150 (170) kV

XLPE INSULATED WITH LEAD SHEATH

127/220 (245) kV

XLPE INSULATED WITH Cu WIRE + AI TAPE

127/220 (245) kV

XLPE INSULATED WITH Cu WIRE + LEAD SHEATH

127/220 (245) kV

XLPE INSULATED WITH LEAD SHEATH

190/330 (362) kV

XLPE INSULATED WITH Cu WIRE + AI TAPE

190/330 (362) kV

XLPE INSULATED WITH Cu WIRE + LEAD SHEATH

190/330 (362) kV

XLPE INSULATED WITH LEAD SHEATH

220/380 (420) kV

XLPE INSULATED WITH Cu WIRE + AI TAPE

220/380 (420) kV

XLPE INSULATED WITH Cu WIRE + LEAD SHEATH

220/380 (420) kV

XLPE INSULATED WITH LEAD SHEATH

290/500 (550) kV

XLPE INSULATED WITH Cu WIRE + AI TAPE

290/500 (550) kV

XLPE INSULATED WITH Cu WIRE + LEAD SHEATH

290/500 (550) kV

XLPE INSULATED WITH LEAD SHEATH

HV & EHV Cable Systems

18

38/66 (72,5) kV

2B

XLPE Insulated with Cu Wire + AI Tape


Continuous Current Rating for Single Circuit (A)

COPPER CONDUCTOR
Cross-Sectional Area ( mm2 )

240

300

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

545

617

706

805

920

1039

1157

1333

1488

1642

1799

Pipe

522

591

678

776

890

1009

1129

1304

1463

1622

1787

Trefoil

576

658

762

877

1012

1049

1292

1542

1741

1942

2149

Flat (S=3D)

715

820

955

1108

1292

1483

1688

1974

2251

2536

2836

Cross-Sectional Area ( mm2 )

240

300

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

424

481

554

635

728

830

937

1054

1210

1352

1494

Pipe

406

462

532

612

704

806

913

1031

1189

1335

1482

Trefoil

449

515

601

697

807

931

1060

1226

1432

1619

1815

Flat (S=3D)

557

642

752

878

1023

1189

1364

1558

1834

2085

2353

In Air

HDPE pipe diameter = 2D

ALUMINIUM CONDUCTOR

In Air

HDPE pipe diameter = 2D

19

HV & EHV Cable Systems

Cross-Sectional
Area (mm2)

240

300

400

500

630

800

1000

Circular

Circular

Circular

Circular

Circular

Circular

Circular

18

20,4

23,45

26,4

30,25

34

39

43,5

49,5

56

63,5

Thickness of Conductor Screen (mm)

1,4

1,4

1,5

1,6

1,6

Thickness of Insulation (mm)

11

11

11

10

10

10

10

10

10

10

10

Cu-Screen Cross-Sectional Area (mm )

35

50

50

50

50

50

50

70

70

70

95

Thickness of Outer Sheath (mm)

2,6

2,6

2,7

2,8

2,9

3,1

3,3

3,5

3,9

4,1

Outer Diameter of Cable (mm)

57

59

62

63

67

71

77

83

90

97

106

Weight of Cable (kg/m)

CONDUCTOR
(Cu)

Shape
Diameter (mm)

Thickness of Insulation Screen (mm)


2

1200
Milliken

1600
Milliken

2000
Milliken

2500
Milliken

4,3

5,1

8,5

10,3

12,6

14,7

18,5

22,7

28,6

Max. DC Cu Conductor Resistance


at 20C (ohm/km)

0,0754

0,0601

0,047

0,0366

0,0283

0,0221

0,0176

0,0151

0,0113

0,009

0,0072

Capacitance (F/km)

0,174

0,189

0,207

0,242

0,267

0,291

0,329

0,363

0,403

0,447

0,497

Inductance (mH/km)

0,414

0,397

0,381

0,360

0,446

0,334

0,323

0,315

0,305

0,297

0,290

240

300

400

500

630

800

1000

1200

1600

2000

2500

Circular

Circular

Circular

Circular

Circular

Circular

Circular

18,5

21,1

24,25

27,4

30,6

34,8

39

43,5

50,2

56,5

63,5

0,125

0,1

0,0778

0,0605

0,0469

0,0367

0,0291

0,0247

0,0186

0,0149

0,0127

2,9

3,3

3,8

4,1

4,6

5,4

6,3

7,4

10,6

12,9

Cross-Sectional
Area (mm2)
CONDUCTOR
(Al)

Shape
Diameter (mm)

Max. DC Al Conductor Resistance


at 20C (ohm/km)
Weight of Cable (kg/m)

Milliken

Milliken

HV & EHV Cable Systems

Milliken

Milliken

20

38/66 (72,5) kV
XLPE Insulated with Cu Wire + Lead Sheath

1A

Continuous Current Rating for Single Circuit (A)

COPPER CONDUCTOR
Cross-Sectional Area ( mm2 )

240

300

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

551

624

714

814

932

1050

1170

1349

1504

1663

1820

Pipe

523

595

683

781

898

1016

1138

1316

1474

1640

1807

Trefoil

576

661

766

882

1020

1158

1305

1561

1765

1976

2185

Flat (S=3D)

730

841

981

1138

1332

1530

1744

2039

2329

2639

2941

Cross-Sectional Area ( mm2 )

240

300

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

428

487

560

643

737

840

947

1066

1225

1370

1513

Pipe

407

464

536

617

709

812

920

1040

1201

1349

1499

Trefoil

449

518

604

702

815

940

1072

1242

1454

1650

1848

Flat (S=3D)

569

659

773

902

1055

1227

1409

1610

1896

2169

2440

In Air

HDPE pipe diameter = 2D

ALUMINIUM CONDUCTOR

In Air

HDPE pipe diameter = 2D

21

HV & EHV Cable Systems

Cross-Sectional
Area (mm2)

240

300

400

500

630

800

1000

Circular

Circular

Circular

Circular

Circular

Circular

Circular

18

20,4

23,45

26,4

30,25

34

39

43,5

49,5

56

63,5

Thickness of Conductor Screen (mm)

1,4

1,4

1,5

1,6

1,6

Thickness of Insulation (mm)

11

11

11

10

10

10

10

10

10

10

10

Thickness of Insulation Screen (mm)

Cu-Screen Cross-Sectional Area (mm2)

35

50

50

50

50

50

50

70

70

70

95

Thickness of Lead Sheath (mm)

1,7

2,2

2,2

2,4

2,4

2,6

2,7

Thickness of Outer Sheath (mm)

2,7

2,8

2,9

2,9

3,1

3,3

3,4

3,6

4,3

Outer Diameter of Cable (mm)

60

63

66

67

71

76

82

88

94

102

111

Weight of Cable (kg/m)

7,6

9,2

10,3

11,3

13,1

15,7

18,4

21,5

25,9

31,4

38,4

Max. DC Cu Conductor Resistance


at 20C (ohm/km)

0,0754

0,0601

0,047

0,0366

0,0283

0,0221

0,0176

0,0151

0,0113

0,009

0,0072

Capacitance (F/km)

0,174

0,189

0,207

0,242

0,267

0,291

0,329

0,363

0,403

0,447

0,497

Inductance (mH/km)

0,423

0,409

0,392

0,371

0,356

0,344

0,333

0,325

0,314

0,306

0,299

240

300

400

500

630

800

1000

1200

1600

2000

2500

Circular

Circular

Circular

Circular

Circular

Circular

Circular

18,5

21,1

24,25

27,4

30,6

34,8

39

43,5

50,2

56,5

63,5

0,125

0,1

0,0778

0,0605

0,0469

0,0367

0,0291

0,0247

0,0186

0,0149

0,0127

6,2

7,4

8,1

8,5

9,2

10,8

12,1

14,3

16,8

19,2

22,7

CONDUCTOR
(Cu)

Shape
Diameter (mm)

Cross-Sectional
Area (mm2)
CONDUCTOR
(Al)

Shape
Diameter (mm)

Max. DC Al Conductor Resistance


at 20C (ohm/km)
Weight of Cable (kg/m)

1200
Milliken

Milliken

1600
Milliken

Milliken

HV & EHV Cable Systems

2000
Milliken

Milliken

2500
Milliken

Milliken

22

38/66 (72,5) kV
XLPE Insulated with Lead Sheath

3c

Continuous Current Rating for Single Circuit (A)

COPPER CONDUCTOR
Cross-Sectional Area ( mm2 )

240

300

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

549

620

710

810

925

1044

1164

1347

1502

1660

1819

Pipe

519

588

675

774

888

1006

1129

1310

1433

1634

1803

Trefoil

568

648

752

867

1002

1139

1282

1550

1754

1963

2178

Flat (S=3D)

725

830

969

1126

1316

1515

1727

2043

2335

2641

2973

Cross-Sectional Area ( mm2 )

240

300

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

427

482

556

639

733

835

942

1065

1225

1367

1508

Pipe

403

459

530

611

702

805

913

1035

1199

1344

1492

Trefoil

442

508

594

691

801

926

1055

1235

1450

1641

1834

Flat (S=3D)

563

650

763

893

1042

1215

1396

1614

1907

2171

2431

In Air

HDPE pipe diameter = 2D

ALUMINIUM CONDUCTOR

In Air

HDPE pipe diameter = 2D

23

HV & EHV Cable Systems

Cross-Sectional
Area (mm2)

240

300

400

500

630

800

1000

Circular

Circular

Circular

Circular

Circular

Circular

Circular

18

20,4

23,45

26,4

30,25

34

39

43,5

49,5

56

63,5

Thickness of Conductor Screen (mm)

1,4

1,4

1,5

1,6

1,6

Thickness of Insulation (mm)

11

11

11

10

10

10

10

10

10

10

10

Thickness of Insulation Screen (mm)

Thickness of Lead Sheath (mm)

2,1

2,1

2,2

2,2

2,3

2,4

2,6

2,7

2,8

3,2

3,4

Thickness of Outer Sheath (mm)

2,6

2,7

2,8

2,8

3,1

3,2

3,4

3,6

4,2

Outer Diameter of Cable (mm)

56

59

62

63

68

72

78

84

91

100

108

Weight of Cable (kg/m)

7,6

8,5

9,8

10,9

12,9

15,3

18,5

21,3

26,1

32,2

39,4

Max. DC Cu Conductor Resistance


at 20C (ohm/km)

0,0754

0,0601

0,047

0,0366

0,0283

0,0221

0,0176

0,0151

0,0113

0,009

0,0072

Capacitance (F/km)

0,174

0,189

0,207

0,242

0,267

0,291

0,329

0,363

0,403

0,447

0,497

Inductance (mH/km)

0,416

0,396

0,38

0,359

0,346

0,335

0,325

0,317

0,307

0,301

0,294

240

300

400

500

630

800

1000

1200

1600

2000

2500

Circular

Circular

Circular

Circular

Circular

Circular

Circular

18,5

21,1

24,25

27,4

30,6

34,8

39

43,5

50,2

56,5

63,5

0,125

0,1

0,0778

0,0605

0,0469

0,0367

0,0291

0,0247

0,0186

0,0149

0,0127

6,2

6,7

7,6

9,3

10,4

12,2

14

16,5

20

23,7

CONDUCTOR
(Cu)

Shape
Diameter (mm)

Cross-Sectional
Area (mm2)
CONDUCTOR
(Al)

Shape
Diameter (mm)

Max. DC Al Conductor Resistance


at 20C (ohm/km)
Weight of Cable (kg/m)

1200
Milliken

Milliken

1600
Milliken

Milliken

HV & EHV Cable Systems

2000
Milliken

Milliken

2500
Milliken

Milliken

24

64/110 (123) kV

2B

XLPE Insulated with Cu Wire + AI Tape


Continuous Current Rating for Single Circuit (A)

COPPER CONDUCTOR
Cross-Sectional Area ( mm2 )

240

300

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

545

617

706

805

920

1039

1157

1333

1488

1642

1799

Pipe

522

591

678

776

890

1009

1129

1304

1463

1622

1787

Trefoil

576

658

762

877

1012

1149

1292

1542

1741

1942

2149

Flat (S=3D)

715

820

955

1108

1292

1483

1688

1974

2251

2536

2836

Cross-Sectional Area ( mm2 )

240

300

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

424

481

554

635

728

830

937

1054

1210

1352

1494

Pipe

406

462

532

612

704

806

913

1031

1189

1335

1482

Trefoil

449

515

601

697

807

931

1060

1226

1432

1619

1815

Flat (S=3D)

557

642

752

878

1023

1189

1364

1558

1834

2085

2353

In Air

HDPE pipe diameter = 2D

ALUMINIUM CONDUCTOR

In Air

HDPE pipe diameter = 2D

25

HV & EHV Cable Systems

Cross-Sectional
Area (mm2)

240

300

400

500

630

800

1000

Circular

Circular

Circular

Circular

Circular

Circular

Circular

18

20,4

23,45

26,4

30,25

34

39

43,5

49,5

56

63,5

Thickness of Conductor Screen (mm)

1,4

1,4

1,5

1,6

1,6

Thickness of Insulation (mm)

15

15

15

14

14

14

14

14

14

14

14

Thickness of Insulation Screen (mm)

Cross-Sectional Area (mm2)

95

95

95

95

95

95

95

95

95

95

95

Thickness of Outer Sheath (mm)

2,8

2,9

3,1

3,2

3,4

3,5

3,6

3,8

4,2

4,5

Outer Diameter of Cable (mm)

65

67

71

72

76

80

86

92

98

106

114

Weight of Cable (kg/m)

5,6

6,3

7,2

8,2

9,7

11,6

14

16

19,9

24,2

30

Max. DC Cu Conductor Resistance


at 20C (ohm/km)

0,0754

0,0601

0,047

0,0366

0,0283

0,0221

0,0176

0,0151

0,0113

0,009

0,0072

Capacitance (F/km)

0,141

0,152

0,165

0,188

0,206

0,224

0,251

0,275

0,304

0,336

0,372

Inductance (mH/km)

0,442

0,424

0,407

0,392

0,376

0,363

0,349

0,34

0,328

0,318

0,309

240

300

400

500

630

800

1000

1200

1600

2000

2500

Circular

Circular

Circular

Circular

Circular

Circular

Circular

18,5

21,1

24,25

27,4

30,6

34,8

39

43,5

50,2

56,5

63,5

0,125

0,1

0,0778

0,0605

0,0469

0,0367

0,0291

0,0247

0,0186

0,0149

0,0127

4,1

4,5

5,3

5,9

6,7

7,4

8,7

10,4

12

14,3

CONDUCTOR
(Cu)

Shape
Diameter (mm)

Cross-Sectional
Area (mm2)
CONDUCTOR
(Al)

Shape
Diameter (mm)

Max. DC Al Conductor Resistance


at 20C (ohm/km)
Weight of Cable (kg/m)

1200
Milliken

Milliken

1600
Milliken

Milliken

HV & EHV Cable Systems

2000
Milliken

Milliken

2500
Milliken

Milliken

26

64/110 (123) kV
XLPE Insulated with Cu Wire + Lead Sheath

1A

Continuous Current Rating for Single Circuit (A)

COPPER CONDUCTOR
Cross-Sectional Area ( mm2 )

240

300

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

547

620

710

810

925

1046

1164

1342

1497

1653

1812

Pipe

525

596

685

783

898

1018

1139

1317

1495

1638

1806

Trefoil

584

668

774

891

1028

1170

1315

1566

1767

1976

2186

Flat (S=3D)

721

829

966

1120

1305

1499

1706

1994

2274

2563

2865

Cross-Sectional Area ( mm2 )

240

300

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

427

484

557

639

732

836

942

1061

1218

1361

1505

Pipe

410

466

538

618

711

815

921

1041

1200

1347

1498

Trefoil

456

523

610

708

820

947

1077

1244

1454

1645

1843

Flat (S=3D)

563

649

761

888

1033

1203

1378

1574

1851

2106

2376

In Air

HDPE pipe diameter = 2D

ALUMINIUM CONDUCTOR

In Air

HDPE pipe diameter = 2D

27

HV & EHV Cable Systems

Cross-Sectional
Area (mm2)

240

300

400

500

630

800

1000

Circular

Circular

Circular

Circular

Circular

Circular

Circular

18

20,4

23,45

26,4

30,25

34

39

43,5

49,5

56

63,5

Thickness of Conductor Screen (mm)

1,4

1,4

1,5

1,6

1,6

Thickness of Insulation (mm)

15

15

15

14

14

14

14

14

14

14

14

Thickness of Insulation Screen (mm)

Cu-Screen Cross-Sectional Area (mm2)

95

95

95

95

95

95

95

95

95

95

95

Thickness of Lead Sheath (mm)

2,2

2,2

2,2

2,4

2,4

2,5

2,6

2,8

2,9

Thickness of Outer Sheath (mm)

3,2

3,2

3,3

3,5

3,6

3,7

3,9

4,3

4,6

Outer Diameter of Cable (mm)

69

71

75

76

80

85

91

96

103

111

120

CONDUCTOR
(Cu)

Shape
Diameter (mm)

Weight of Cable (kg/m)

1200
Milliken

1600
Milliken

2000
Milliken

2500
Milliken

10,1

10,9

12,5

13,6

15,5

18,2

21,1

23,8

28,7

34

41,3

Max. DC Cu Conductor Resistance


at 20C (ohm/km)

0,0754

0,0601

0,047

0,0366

0,0283

0,0221

0,0176

0,0151

0,0113

0,009

0,0072

Capacitance (F/km)

0,141

0,152

0,165

0,188

0,206

0,224

0,251

0,275

0,304

0,336

0,372

Inductance (mH/km)

0,457

0,435

0,418

0,397

0,38

0,368

0,354

0,345

0,333

0,323

0,313

240

300

400

500

630

800

1000

1200

1600

2000

2500

Circular

Circular

Circular

Circular

Circular

Circular

Circular

18,5

21,1

24,25

27,4

30,6

34,8

39

43,5

50,2

56

63,5

0,125

0,1

0,0778

0,0605

0,0469

0,0367

0,0291

0,0247

0,0186

0,0149

0,0127

8,6

9,2

10,4

10,8

14,7

16,6

19,2

21,8

25,6

Cross-Sectional
Area (mm2)
CONDUCTOR
(Al)

Shape
Diameter (mm)

Max. DC Al Conductor Resistance


at 20C (ohm/km)
Weight of Cable (kg/m)

11,6

13,4

Milliken

Milliken

HV & EHV Cable Systems

Milliken

Milliken

28

64/110 (123) kV
XLPE Insulated with Lead Sheath

3c

Continuous Current Rating for Single Circuit (A)

COPPER CONDUCTOR
Cross-Sectional Area ( mm2 )

240

300

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

545

617

707

806

921

1041

1159

1342

1495

1654

1815

Pipe

522

592

680

778

892

1011

1133

1314

1471

1367

1807

Trefoil

576

659

764

880

1015

1155

1300

1560

1761

1971

2189

Flat (S=3D)

715

822

958

1111

1295

1490

1695

2001

2282

2579

2903

Cross-Sectional Area ( mm2 )

240

300

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

424

481

554

636

729

832

938

1060

1219

1362

1501

Pipe

406

462

533

614

705

808

916

1038

1200

1347

1491

Trefoil

450

516

602

700

810

936

1066

1240

1452

1643

1833

Flat (S=3D)

558

643

754

881

1026

1194

1370

1580

1863

2120

2372

In Air

HDPE pipe diameter = 2D

ALUMINIUM CONDUCTOR

In Air

HDPE pipe diameter = 2D

29

HV & EHV Cable Systems

Cross-Sectional
Area (mm2)

240

300

400

500

630

800

1000

Circular

Circular

Circular

Circular

Circular

Circular

Circular

18

20,4

23,45

26,4

30,25

34

39

43,5

49,5

56

63,5

Thickness of Conductor Screen (mm)

1,4

1,4

1,5

1,6

1,6

Thickness of Insulation (mm)

15

15

15

14

14

14

14

14

14

14

14

Thickness of Insulation Screen (mm)

Thickness of Lead Sheath (mm)

2,3

2,4

2,5

2,5

2,6

2,7

2,8

3,1

3,4

3,5

Thickness of Outer Sheath (mm)

2,9

3,1

3,1

3,3

3,4

3,5

3,7

3,9

4,3

4,5

Outer Diameter of Cable (mm)

65

68

72

73

77

82

87

93

100

109

117

Weight of Cable (kg/m)

9,4

10,5

12

13

15,1

17,7

20,8

23,7

28,9

35

42,5

Max. DC Cu Conductor Resistance


at 20C (ohm/km)

0,0754

0,0601

0,047

0,0366

0,0283

0,0221

0,0176

0,0151

0,0113

0,009

0,0072

Capacitance (F/km)

0,141

0,152

0,165

0,188

0,206

0,224

0,251

0,275

0,304

0,336

0,372

Inductance (mH/km)

0,446

0,426

0,408

0,387

0,372

0,361

0,347

0,338

0,327

0,318

0,31

240

300

400

500

630

800

1000

1200

1600

2000

2500

Circular

Circular

Circular

Circular

Circular

Circular

Circular

18,5

21,1

24,25

27,4

30,6

34,8

39

43,5

50,2

56,5

63,5

0,125

0,1

0,0778

0,0605

0,0469

0,0367

0,0291

0,0247

0,0186

0,0149

0,0127

8,8

9,8

10,2

11,3

12,8

14,5

16,4

19,5

22,9

26,8

CONDUCTOR
(Cu)

Shape
Diameter (mm)

Cross-Sectional
Area (mm2)
CONDUCTOR
(Al)

Shape
Diameter (mm)

Max. DC Al Conductor Resistance


at 20C (ohm/km)
Weight of Cable (kg/m)

1200
Milliken

2,9

Milliken

1600
Milliken

Milliken

HV & EHV Cable Systems

2000
Milliken

Milliken

2500
Milliken

Milliken

30

76/132 (145) kV

2B

XLPE Insulated with Cu Wire + AI Tape


Continuous Current Rating for Single Circuit (A)

COPPER CONDUCTOR
Cross-Sectional Area ( mm2 )

240

300

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

543

615

704

803

917

1035

1154

1331

1483

1639

1795

Pipe

522

592

679

776

890

1007

1128

1304

1460

1621

1785

Trefoil

578

662

763

879

1014

1152

1294

1542

1741

1942

2148

Flat (S=3D)

708

814

951

1102

1284

1474

1677

1961

2236

2518

2815

Cross-Sectional Area ( mm2 )

240

300

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

423

479

552

633

726

828

934

1052

1207

1349

1491

Pipe

407

462

532

612

704

806

912

1030

1188

1333

1481

Trefoil

452

518

602

699

809

933

1061

1225

1431

1618

1813

Flat (S=3D)

553

637

748

873

1016

1182

1355

1548

1820

2070

2335

In Air

HDPE pipe diameter = 2D

ALUMINIUM CONDUCTOR

In Air

HDPE pipe diameter = 2D

31

HV & EHV Cable Systems

Cross-Sectional
Area (mm2)

240

300

400

500

630

800

1000

Circular

Circular

Circular

Circular

Circular

Circular

Circular

18

20,4

23,45

26,4

30,25

34

39

43,5

49,5

56

63,5

Thickness of Conductor Screen (mm)

1,2

1,2

1,2

1,2

1,2

1,2

1,4

1,4

1,5

1,6

1,6

Thickness of Insulation (mm)

17

17

16

16

16

16

16

16

16

16

16

Thickness of Insulation Screen (mm)

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

Cu-Screen Cross-Sectional Area (mm2)

95

95

95

95

95

95

95

95

95

95

95

Thickness of Outer Sheath (mm)

3,1

3,1

3,2

3,3

3,4

3,6

3,7

3,9

1,3

4,6

Outer Diameter of Cable (mm)

70

73

74

77

81

85

91

96

103

111

120

Weight of Cable (kg/m)

6,1

6,8

7,6

8,8

10,3

12,2

14,6

16,8

20,5

24,9

30,8

Max. DC Cu Conductor Resistance


at 20C (ohm/km)

0,0754

0,0601

0,047

0,0366

0,0283

0,0221

0,0176

0,0151

0,0113

0,009

0,0072

Capacitance (F/km)

0,132

0,141

0,16

0,172

0,188

0,204

0,226

0,248

0,273

0,301

0,334

Inductance (mH/km)

0,458

0,44

0,415

0,4

0,383

0,369

0,355

0,345

0,333

0,323

0,313

240

300

400

500

630

800

1000

1200

1600

2000

2500

Circular

Circular

Circular

Circular

Circular

Circular

Circular

18,5

21,1

24,25

27,4

30,6

34,8

39

43,5

50,2

56,5

63,5

0,125

0,1

0,0778

0,0605

0,0469

0,0367

0,0291

0,0247

0,0186

0,0149

0,0127

4,7

5,3

5,9

6,4

7,3

9,3

11

12,7

15,1

CONDUCTOR
(Cu)

Shape
Diameter (mm)

Cross-Sectional
Area (mm2)
CONDUCTOR
(Al)

Shape
Diameter (mm)

Max. DC Al Conductor Resistance


at 20C (ohm/km)
Weight of Cable (kg/m)

1200
Milliken

Milliken

1600
Milliken

Milliken

HV & EHV Cable Systems

2000
Milliken

Milliken

2500
Milliken

Milliken

32

76/132 (145) kV
XLPE Insulated with Cu Wire + Lead Sheath
1A

Continuous Current Rating for Single Circuit (A)

COPPER CONDUCTOR
Cross-Sectional Area ( mm2 )

240

300

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

545

618

708

808

924

1043

1163

1339

1494

1650

1807

Pipe

526

598

685

783

899

1018

1140

1315

1475

1636

1802

Trefoil

587

671

775

892

1031

1171

1317

1566

1769

1974

2185

Flat (S=3D)

816

825

961

1113

1298

1490

1696

1981

2258

2543

2843

Cross-Sectional Area ( mm2 )

240

300

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

425

482

556

637

731

834

941

1058

1215

1358

1501

Pipe

411

467

538

618

711

814

922

1039

1200

1346

1495

Trefoil

459

526

611

709

822

947

1078

1244

1453

1642

1841

Flat (S=3D)

559

644

756

882

1027

1194

1370

1564

1838

2090

2358

In Air

HDPE pipe diameter = 2D

ALUMINIUM CONDUCTOR

In Air

HDPE pipe diameter = 2D

33

HV & EHV Cable Systems

Cross-Sectional
Area (mm2)

240

300

400

500

630

800

1000

Circular

Circular

Circular

Circular

Circular

Circular

Circular

18

20,4

23,45

26,4

30,25

34

39

43,5

49,5

56

63,5

Thickness of Conductor Screen (mm)

1,2

1,2

1,2

1,2

1,2

1,2

1,4

1,4

1,5

1,6

1,6

Thickness of Insulation (mm)

17

17

16

16

16

16

16

16

16

16

16

Thickness of Insulation Screen (mm)

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

Cu-Screen Cross-Sectional Area (mm2)

95

95

95

95

95

95

95

95

95

95

95

Thickness of Lead Sheath (mm)

2,2

2,2

2,2

2,2

2,4

2,4

2,5

2,6

2,7

2,8

Thickness of Outer Sheath (mm)

3,1

3,2

3,2

3,3

3,5

3,6

3,7

3,9

4,1

4,5

4,8

Outer Diameter of Cable (mm)

74

77

78

81

86

90

96

101

108

116

125

11,3

12,3

13,1

14,5

17

19,2

22,3

25,4

30,1

35,6

43,1

Max. DC Cu Conductor Resistance


at 20C (ohm/km)

0,0754

0,0601

0,047

0,0366

0,0283

0,0221

0,0176

0,0151

0,0113

0,009

0,0072

Capacitance (F/km)

0,132

0,141

0,16

0,172

0,188

0,204

0,226

0,248

0,273

0,301

0,334

Inductance (mH/km)

0,468

0,45

0,425

0,41

0,394

0,38

0,365

0,355

0,342

0,332

0,322

240

300

400

500

630

800

1000

1200

1600

2000

2500

Circular

Circular

Circular

Circular

Circular

Circular

Circular

18,5

21,1

24,25

27,4

30,6

34,8

39

43,5

50,2

56,5

63,5

0,125

0,1

0,0778

0,0605

0,0469

0,0367

0,0291

0,0247

0,0186

0,0149

0,0127

10

10,6

10,9

11,7

13,1

14,4

15,8

17,9

20,7

23,3

27,4

CONDUCTOR
(Cu)

Shape
Diameter (mm)

Weight of Cable (kg/m)

Cross-Sectional
Area (mm2)
CONDUCTOR
(Al)

Shape
Diameter (mm)

Max. DC Al Conductor Resistance


at 20C (ohm/km)
Weight of Cable (kg/m)

1200
Milliken

Milliken

1600
Milliken

Milliken

HV & EHV Cable Systems

2000
Milliken

Milliken

2500
Milliken

Milliken

34

76/132 (145) kV
XLPE Insulated with Lead Sheath

3c

Continuous Current Rating for Single Circuit (A)

COPPER CONDUCTOR
Cross-Sectional Area ( mm2 )

240

300

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

543

616

705

804

919

1037

1156

1338

1493

1650

1812

Pipe

523

594

680

778

892

1010

1131

1312

1471

1634

1805

Trefoil

580

663

882

1018

1158

1302

1559

1762

1970

2189

Flat (S=3D)

711

816

953

1105

1288

1480

1685

1988

2268

2560

2881

Cross-Sectional Area ( mm2 )

240

300

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

423

480

552

634

728

830

936

1057

1216

1358

1498

Pipe

407

463

533

614

706

808

914

1037

1199

1345

1490

Trefoil

452

519

603

701

812

937

1067

1240

1452

1641

1831

Flat (S=3D)

554

639

750

876

1020

1187

1362

1570

1852

2105

2353

765

In Air

HDPE pipe diameter = 2D

ALUMINIUM CONDUCTOR

In Air

HDPE pipe diameter = 2D

35

HV & EHV Cable Systems

Cross-Sectional
Area (mm2)

240

300

400

500

630

800

1000

Circular

Circular

Circular

Circular

Circular

Circular

Circular

18

20,4

23,45

26,4

30,25

34

39

43,5

49,5

56

63,5

Thickness of Conductor Screen (mm)

1,2

1,2

1,2

1,2

1,2

1,2

1,4

1,4

1,5

1,6

1,6

Thickness of Insulation (mm)

17

17

16

16

16

16

16

16

16

16

16

Thickness of Insulation Screen (mm)

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

Thickness of Lead Sheath (mm)

2,4

2,5

2,5

2,6

2,7

2,8

2,9

3,2

3,5

3,8

Thickness of Outer Sheath (mm)

3,1

3,2

3,2

3,3

3,4

3,5

3,7

3,8

4,4

4,7

Outer Diameter of Cable (mm)

71

74

75

78

82

86

92

98

105

113

123

10,5

11,7

12,5

14,5

16,4

19

22,5

25,3

30,4

36,7

44,8

Max. DC Cu Conductor Resistance


at 20C (ohm/km)

0,0754

0,0601

0,047

0,0366

0,0283

0,0221

0,0176

0,0151

0,0113

0,009

0,0072

Capacitance (F/km)

0,132

0,141

0,16

0,172

0,188

0,204

0,226

0,248

0,273

0,301

0,334

Inductance (mH/km)

0,459

0,441

0,416

0,402

0,385

0,372

0,358

0,348

0,336

0,327

0,318

240

300

400

500

630

800

1000

1200

1600

2000

2500

Circular

Circular

Circular

Circular

Circular

Circular

Circular

18,5

21,1

24,25

27,4

30,6

34,8

39

43,5

50,2

56,5

63,5

0,125

0,1

0,0778

0,0605

0,0469

0,0367

0,0291

0,0247

0,0186

0,0149

0,0127

9,1

10

10,4

11,4

12,6

14,2

15,7

17,8

21

24,4

29,1

CONDUCTOR
(Cu)

Shape
Diameter (mm)

Weight of Cable (kg/m)

Cross-Sectional
Area (mm2)
CONDUCTOR
(Al)

Shape
Diameter (mm)

Max. DC Al Conductor Resistance


at 20C (ohm/km)
Weight of Cable (kg/m)

1200
Milliken

Milliken

1600
Milliken

Milliken

HV & EHV Cable Systems

2000
Milliken

Milliken

2500
Milliken

Milliken

36

87/150 (170) kV

2B

XLPE Insulated with Cu Wire + AI Tape


Continuous Current Rating for Single Circuit (A)

COPPER CONDUCTOR
Cross-Sectional Area ( mm2 )

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

702

802

916

1035

1151

1327

1480

1635

1791

Pipe

681

778

892

1009

1128

1304

1460

1621

1784

Trefoil

768

882

1018

1156

1299

1543

1742

1943

2148

Flat (S=3D)

942

1095

1274

1462

1663

1942

2214

2492

2784

Cross-Sectional Area ( mm2 )

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

550

632

725

827

932

1049

1205

1346

1487

Pipe

535

614

705

807

912

1030

1189

1333

1480

Trefoil

605

701

811

935

1063

1226

1431

1617

1811

Flat (S=3D)

741

867

1009

1172

1345

1534

1803

2048

2310

In Air

HDPE pipe diameter = 2D

ALUMINIUM CONDUCTOR

In Air

HDPE pipe diameter = 2D

37

HV & EHV Cable Systems

Cross-Sectional
Area (mm2)

400

500

630

800

1000

Shape

Circular

Circular

Circular

Circular

Circular

Diameter (mm)

23,45

26,4

30,25

34

39

43,5

49,5

56

63,5

Thickness of Conductor Screen (mm)

1,2

1,2

1,2

1,2

1,4

1,4

1,5

1,6

1,6

Thickness of Insulation (mm)

18

18

18

18

18

18

18

18

18

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

Cu-Screen Cross-Sectional Area (mm )

95

95

95

95

95

95

95

95

95

Thickness of Outer Sheath (mm)

3,3

3,3

3,4

3,6

3,7

3,7

4,4

4,7

Outer Diameter of Cable (mm)

78

81

85

90

95

101

107

114

124

Weight of Cable (kg/m)

9,2

10,8

12,7

15,1

17,4

21,2

25,6

31,6

Max. DC Cu Conductor Resistance


at 20C (ohm/km)

0,047

0,0366

0,0283

0,0221

0,0176

0,0151

0,0113

0,009

0,0072

Capacitance (F/km)

0,148

0,159

0,173

0,187

0,207

0,226

0,249

0,274

0,304

Inductance (mH/km)

0,429

0,411

0,393

0,38

0,365

0,354

0,341

0,33

0,32

400

500

630

800

1000

1200

1600

2000

2500

Shape

Circular

Circular

Circular

Circular

Circular

Diameter (mm)

24,25

27,4

30,6

34,8

39

43,5

50,2

56,5

63,5

0,0778

0,0605

0,0469

0,0367

0,0291

0,0247

0,0186

0,0149

0,0127

5,8

6,3

6,9

7,8

8,6

9,9

11,6

13,4

15,9

CONDUCTOR
(Cu)

Thickness of Insulation Screen (mm)


2

Cross-Sectional
Area (mm2)
CONDUCTOR
(Al)

Max. DC Al Conductor Resistance


at 20C (ohm/km)
Weight of Cable (kg/m)

1200
Milliken

Milliken

1600
Milliken

Milliken

HV & EHV Cable Systems

2000
Milliken

Milliken

2500
Milliken

Milliken

38

87/150 (170) kV
XLPE Insulated with Cu Wire +Lead Sheath

1A

Continuous Current Rating for Single Circuit (A)

COPPER CONDUCTOR
Cross-Sectional Area ( mm2 )

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

706

807

922

1040

1159

1336

1491

1647

1804

Pipe

687

785

900

1018

1139

1316

1476

1637

1803

Trefoil

779

896

1033

1174

1320

1565

1769

1975

2185

Flat (S=3D)

951

1105

1286

1476

1679

1960

2235

2516

2812

Cross-Sectional Area ( mm2 )

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

554

636

729

832

938

1056

1213

1356

1498

Pipe

539

619

711

814

921

1040

1201

1347

1495

Trefoil

614

711

823

948

1079

1243

1452

1641

1839

Flat (S=3D)

748

876

1018

1183

1356

1548

1818

2067

2332

In Air

HDPE pipe diameter = 2D

ALUMINIUM CONDUCTOR

In Air

HDPE pipe diameter = 2D

39

HV & EHV Cable Systems

Cross-Sectional
Area (mm2)

400

500

630

800

1000

Shape

Circular

Circular

Circular

Circular

Circular

Diameter (mm)

23,45

26,4

30,25

34

39

43,5

49,5

56

63,5

Thickness of Conductor Screen (mm)

1,2

1,2

1,2

1,2

1,4

1,4

1,5

1,6

1,6

Thickness of Insulation (mm)

18

18

18

18

18

18

18

18

18

Thickness of Insulation Screen (mm)

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

Cu-Screen Cross-Sectional Area (mm2)

95

95

95

95

95

95

95

95

95

Thickness of Lead Sheath (mm)

2,2

2,4

2,4

2,4

2,5

2,6

2,8

2,9

3,2

Thickness of Outer Sheath (mm)

3,4

3,5

3,6

3,7

3,9

4,2

4,6

4,9

Outer Diameter of Cable (mm)

82

86

90

94

100

106

113

120

130

Weight of Cable (kg/m)

13,9

15,9

17,8

20,1

23,3

26,4

31,5

37,1

45,1

Max. DC Cu Conductor Resistance


at 20C (ohm/km)

0,047

0,0366

0,0283

0,0221

0,0176

0,0151

0,0113

0,009

0,0072

Capacitance (F/km)

0,148

0,159

0,173

0,187

0,207

0,226

0,249

0,274

0,304

Inductance (mH/km)

0,436

0,421

0,404

0,389

0,374

0,363

0,352

0,34

0,33

400

500

630

800

1000

1200

1600

2000

2500

Shape

Circular

Circular

Circular

Circular

Circular

Diameter (mm)

24,25

27,4

30,6

34,8

39

43,5

50,2

56,5

63,5

0,0778

0,0605

0,0469

0,0367

0,0291

0,0247

0,0186

0,0149

0,0127

11,7

13,1

14

15,6

16,8

18,9

22,1

24,8

29,4

CONDUCTOR
(Cu)

Cross-Sectional
Area (mm2)
CONDUCTOR
(Al)

Max. DC Al Conductor Resistance


at 20C (ohm/km)
Weight of Cable (kg/m)

1200
Milliken

Milliken

1600
Milliken

Milliken

HV & EHV Cable Systems

2000
Milliken

Milliken

2500
Milliken

Milliken

40

87/150 (170) kV
XLPE Insulated with Lead Sheath

3c

Continuous Current Rating for Single Circuit (A)

COPPER CONDUCTOR
Cross-Sectional Area ( mm2 )

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

703

802

918

1036

1155

1331

1486

1641

1798

Pipe

682

779

894

1012

1133

1309

1467

1629

1794

Trefoil

771

886

1023

1162

1307

1553

1755

1962

2171

Flat (S=3D)

945

1098

1279

1468

1671

1952

2225

2508

2803

Cross-Sectional Area ( mm2 )

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

551

633

726

828

934

1056

1208

1351

1495

Pipe

535

615

706

808

916

1034

1194

1340

1491

Trefoil

607

703

814

940

1069

1234

1441

1631

1829

Flat (S=3D)

743

870

1012

1177

1349

1541

1810

2061

2326

In Air

HDPE pipe diameter = 2D

ALUMINIUM CONDUCTOR

In Air

HDPE pipe diameter = 2D

41

HV & EHV Cable Systems

Cross-Sectional
Area (mm2)

400

500

630

800

1000

Shape

Circular

Circular

Circular

Circular

Circular

Diameter (mm)

23,45

26,4

30,25

34

39

43,5

49,5

56

63,5

Thickness of Conductor Screen (mm)

1,2

1,2

1,2

1,2

1,4

1,4

1,5

1,6

1,6

Thickness of Insulation (mm)

18

18

18

18

18

18

18

18

18

Thickness of Insulation Screen (mm)

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

Thickness of Lead Sheath (mm)

2,6

2,7

2,8

2,9

3,2

3,3

3,7

3,9

Thickness of Outer Sheath (mm)

3,3

3,4

3,6

3,7

3,8

4,2

4,6

4,9

Outer Diameter of Cable (mm)

79

83

87

91

97

103

110

118

128

Weight of Cable (kg/m)

13,6

15,4

17,6

20,2

23,5

27

31,9

38,7

46,5

Max. DC Cu Conductor Resistance


at 20C (ohm/km)

0,047

0,0366

0,0283

0,0221

0,0176

0,0151

0,0113

0,009

0,0072

Capacitance (F/km)

0,148

0,159

0,173

0,187

0,207

0,226

0,249

0,274

0,304

Inductance (mH/km)

0,428

0,413

0,396

0,382

0,368

0,358

0,345

0,336

0,326

400

500

630

800

1000

1200

1600

2000

2500

Shape

Circular

Circular

Circular

Circular

Circular

Diameter (mm)

24,25

27,4

30,6

34,8

39

43,5

50,2

56,5

63,5

0,0778

0,0605

0,0469

0,0367

0,0291

0,0247

0,0186

0,0149

0,0127

11,4

12,6

13,8

15,4

16,9

19,5

22,5

26,4

30,8

CONDUCTOR
(Cu)

Cross-Sectional
Area (mm2)
CONDUCTOR
(Al)

Max. DC Al Conductor Resistance


at 20C (ohm/km)
Weight of Cable (kg/m)

1200
Milliken

Milliken

1600
Milliken

Milliken

HV & EHV Cable Systems

2000
Milliken

Milliken

2500
Milliken

Milliken

42

127/220 (245) kV

2B

XLPE Insulated with Cu Wire + Al Tape


Continuous Current Rating for Single Circuit (A)

COPPER CONDUCTOR
Cross-Sectional Area ( mm2 )

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

696

795

909

1026

1143

1316

1469

1622

1776

Pipe

680

778

890

1006

1126

1299

1455

1614

1776

Trefoil

771

886

1020

1159

1302

1540

1738

1938

2142

Flat (S=3D)

923

1072

1254

1437

1633

1905

2169

2434

2723

Cross-Sectional Area ( mm2 )

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

545

627

720

820

925

1040

1195

1335

1475

Pipe

534

614

704

805

910

1026

1184

1328

1473

Trefoil

607

703

812

936

1064

1222

1426

1610

1801

Flat (S=3D)

726

849

993

1152

1319

1504

1764

2004

2258

In Air

HDPE pipe diameter = 2D

ALUMINIUM CONDUCTOR

In Air

HDPE pipe diameter = 2D

43

HV & EHV Cable Systems

Cross-Sectional
Area (mm2)

400

500

630

800

1000

Shape

Circular

Circular

Circular

Circular

Circular

Diameter (mm)

23,45

26,4

30,25

34

39

43,5

49,5

56

63,5

Thickness of Conductor Screen (mm)

3,3

1,8

1,2

1,2

1,4

1,4

1,5

1,6

1,6

Thickness of Insulation (mm)

23

22

21

21

20

20

20

20

20

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

Cu-Screen Cross-Sectional Area (mm )

150

150

150

150

150

150

150

150

150

Thickness of Outer Sheath (mm)

3,6

3,6

3,7

3,8

3,8

4,2

4,6

4,9

Outer Diameter of Cable (mm)

93

91

92

96

99

105

112

119

128

Weight of Cable (kg/m)

10,3

10,9

12,1

14

16,1

18,3

22,4

26,8

32,8

Max. DC Cu Conductor Resistance


at 20C (ohm/km)

0,047

0,0366

0,0283

0,0221

0,0176

0,0151

0,0113

0,009

0,0072

Capacitance (F/km)

0,139

0,143

0,156

0,168

0,191

0,209

0,229

0,252

0,277

Inductance (mH/km)

0,462

0,434

0,408

0,394

0,375

0,365

0,352

0,339

0,33

400

500

630

800

1000

1200

1600

2000

2500

Shape

Circular

Circular

Circular

Circular

Circular

Diameter (mm)

24,25

27,4

30,6

34,8

39

43,5

50,2

56,5

63,5

0,0778

0,0605

0,0469

0,0367

0,0291

0,0247

0,0186

0,0149

0,0127

8,2

9,1

9,9

11,1

12,8

14,7

17

CONDUCTOR
(Cu)

Thickness of Insulation Screen (mm)


2

Cross-Sectional
Area (mm2)
CONDUCTOR
(Al)

Max. DC Al Conductor Resistance


at 20C (ohm/km)
Weight of Cable (kg/m)

8,1

1200
Milliken

Milliken

1600
Milliken

Milliken

HV & EHV Cable Systems

2000
Milliken

Milliken

2500
Milliken

Milliken

44

127/220 (245) kV
XLPE Insulated with Cu Wire +Lead Sheath

1A

Continuous Current Rating for Single Circuit (A)

COPPER CONDUCTOR
Cross-Sectional Area ( mm2 )

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

700

799

915

1032

1151

1325

1478

1633

1788

Pipe

696

784

898

1016

1136

1312

1468

1630

1793

Trefoil

780

897

1034

1175

1322

1561

1762

1967

2174

Flat (S=3D)

930

1081

1264

1450

1647

1921

2187

2461

2746

Cross-Sectional Area ( mm2 )

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

549

630

723

826

931

1047

1203

1344

1485

Pipe

538

619

710

812

919

1036

1195

1341

1487

Trefoil

614

712

822

948

1078

1238

1444

1632

1826

Flat (S=3D)

732

856

1001

1162

1330

1517

1779

2022

2277

In Air

HDPE pipe diameter = 2D

ALUMINIUM CONDUCTOR

In Air

HDPE pipe diameter = 2D

45

HV & EHV Cable Systems

Cross-Sectional
Area (mm2)

400

500

630

800

1000

Shape

Circular

Circular

Circular

Circular

Circular

Diameter (mm)

23,45

26,4

30,25

34

39

43,5

49,5

56

62

Thickness of Conductor Screen (mm)

3,3

1,8

1,2

1,2

1,4

1,4

1,5

1,6

1,6

Thickness of Insulation (mm)

23

22

21

21

20

20

20

20

20

Thickness of Insulation Screen (mm)

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

Cu-Screen Cross-Sectional Area (mm2)

150

150

150

150

150

150

150

150

150

Thickness of Lead Sheath (mm)

2,5

2,5

2,5

2,6

2,7

2,8

2,9

3,2

3,2

Thickness of Outer Sheath (mm)

3,8

3,8

3,8

4,2

4,4

4,8

5,1

Outer Diameter of Cable (mm)

98

96

97

101

104

110

117

125

134

Weight of Cable (kg/m)

18,3

18,7

19,9

22,6

25

28,1

33,5

39,1

46,8

Max. DC Cu Conductor Resistance


at 20C (ohm/km)

0,047

0,0366

0,0283

0,0221

0,0176

0,0151

0,0113

0,009

0,0072

Capacitance (F/km)

0,139

0,143

0,156

0,166

0,191

0,209

0,229

0,252

0,277

Inductance (mH/km)

0,472

0,444

0,418

0,403

0,383

0,372

0,359

0,347

0,337

400

500

630

800

1000

1200

1600

2000

2500

Shape

Circular

Circular

Circular

Circular

Circular

Diameter (mm)

24,25

27,4

30,6

34,8

39

43,5

50,2

56

63,5

0,0778

0,0605

0,0469

0,0367

0,0291

0,0247

0,0186

0,0149

0,0127

16,2

16

16,2

17,8

18,8

20,8

24,1

26,9

31,1

CONDUCTOR
(Cu)

Cross-Sectional
Area (mm2)
CONDUCTOR
(Al)

Max. DC Al Conductor Resistance


at 20C (ohm/km)
Weight of Cable (kg/m)

1200
Milliken

Milliken

1600
Milliken

Milliken

HV & EHV Cable Systems

2000
Milliken

Milliken

2500
Milliken

Milliken

46

127/220 (245) kV
XLPE Insulated with Lead Sheath

3c

Continuous Current Rating for Single Circuit (A)

COPPER CONDUCTOR
Cross-Sectional Area ( mm2 )

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

697

797

911

1028

1147

1325

1479

1634

1792

Pipe

682

780

893

1010

1131

1310

1467

1628

1795

Trefoil

775

890

1026

1166

1311

1559

1760

1967

2182

Flat (S=3D)

926

1076

1259

1444

1641

1931

2198

2474

2781

Cross-Sectional Area ( mm2 )

400

500

630

800

1000

1200

1600

2000

2500

Direct-buried

546

628

720

822

927

1047

1204

1345

1482

Pipe

535

615

706

808

914

1035

1195

1340

1483

Trefoil

609

706

816

941

1071

1238

1447

1634

1819

Flat (S=3D)

729

852

996

1157

1326

1525

1794

2035

2273

In Air

HDPE pipe diameter = 2D

ALUMINIUM CONDUCTOR

In Air

HDPE pipe diameter = 2D

47

HV & EHV Cable Systems

Cross-Sectional
Area (mm2)

400

500

630

800

1000

Shape

Circular

Circular

Circular

Circular

Circular

Diameter (mm)

23,45

26,4

30,25

34

39

43,5

49,5

56

63,5

Thickness of Conductor Screen (mm)

3,3

1,8

1,2

1,2

1,4

1,4

1,5

1,6

1,6

Thickness of Insulation (mm)

23

22

21

21

20

20

20

20

20

Thickness of Insulation Screen (mm)

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

1,2

Thickness of Lead Sheath (mm)

3,1

3,2

3,3

3,4

3,8

Thickness of Outer Sheath (mm)

3,7

3,7

3,8

3,9

4,1

4,3

4,7

Outer Diameter of Cable (mm)

95

93

94

98

102

107

114

123

131

Weight of Cable (kg/m)

18

18,4

19,6

22,3

25,2

28,2

33,4

40,3

48,2

Max. DC Cu Conductor Resistance


at 20C (ohm/km)

0,047

0,0366

0,0283

0,0221

0,0176

0,0151

0,0113

0,009

0,0072

Capacitance (F/km)

0,139

0,143

0,156

0,168

0,191

0,209

0,229

0,252

0,277

Inductance (mH/km)

0,465

0,440

0,413

0,397

0,377

0,365

0,353

0,343

0,333

400

500

630

800

1000

1200

1600

2000

2500

Shape

Circular

Circular

Circular

Circular

Circular

Diameter (mm)

24,25

27,4

30,6

34,8

39

43,5

50,2

56,5

63,5

0,0778

0,0605

0,0469

0,0367

0,0291

0,0247

0,0186

0,0149

0,0127

15,9

15,6

15,8

17,5

18,8

21

24

CONDUCTOR
(Cu)

Cross-Sectional
Area (mm2)
CONDUCTOR
(Al)

Max. DC Al Conductor Resistance


at 20C (ohm/km)
Weight of Cable (kg/m)

1200
Milliken

Milliken

1600
Milliken

Milliken

HV & EHV Cable Systems

2000
Milliken

Milliken

28,1

2500
Milliken

Milliken

32,5

48

190/330 (362) kV
2B

XLPE Insulated with Cu Wire + Al Tape


Continuous Current Rating for Single Circuit (A)

COPPER CONDUCTOR
Cross-Sectional Area ( mm2 )

800

1000

1200

1600

2000

2500

Direct-buried

1013

1128

1298

1447

1596

1746

Pipe

1000

1117

1287

1441

1593

1751

Trefoil

1157

1298

1529

1724

1921

2122

Flat (S=3D)

1402

1596

1859

2113

2384

2659

Cross-Sectional Area ( mm2 )

800

1000

1200

1600

2000

2500

Direct-buried

809

913

1025

1177

1313

1450

Pipe

800

903

1017

1172

1310

1453

932

1058

1212

1412

1593

1782

1123

1289

1468

1719

1959

2205

In Air

HDPE pipe diameter = 2D

ALUMINIUM CONDUCTOR

Trefoil
In Air
Flat (S=3D)
HDPE pipe diameter = 2D

49

HV & EHV Cable Systems

Cross-Sectional
Area (mm2)

800

1000

Circular

Circular

34

39

43,5

49,5

56

63,5

Thickness of Conductor Screen (mm)

1,2

1,4

1,4

1,5

1,6

1,6

Thickness of Insulation (mm)

28

27

27

27

26

26

1,2

1,2

1,2

1,2

1,2

1,2

Cu-Screen Cross-Sectional Area (mm )

185

185

185

185

185

185

Thickness of Outer Sheath (mm)

4,3

4,3

4,5

4,7

5,3

Outer Diameter of Cable (mm)

111

114

120

127

132

141

Weight of Cable (kg/m)

16,6

18,8

21,3

25,2

29,4

35,6

Max. DC Cu Conductor Resistance


at 20C (ohm/km)

0,0221

0,0176

0,0151

0,0113

0,009

0,0072

Capacitance (F/km)

0,138

0,155

0,168

0,183

0,206

0,227

Inductance (mH/km)

0,425

0,402

0,039

0,375

0,358

0,346

800

1000

1200

1600

2000

2500

Circular

Circular

34,8

39

43,5

50,2

56,5

63,5

0,0367

0,0291

0,0247

0,0186

0,0149

0,0127

11,7

12,3

13,8

15,7

17,2

19,9

CONDUCTOR
(Cu)

Shape
Diameter (mm)

Thickness of Insulation Screen (mm)


2

Cross-Sectional
Area (mm2)
CONDUCTOR
(Al)

Shape
Diameter (mm)

Max. DC Al Conductor Resistance


at 20C (ohm/km)
Weight of Cable (kg/m)

1200
Milliken

Milliken

1600
Milliken

Milliken

2000
Milliken

Milliken

HV & EHV Cable Systems

2500
Milliken

Milliken

50

190/330 (362) kV
XLPE Insulated with Cu Wire +Lead Sheath
Continuous Current Rating for Single Circuit (A)

COPPER CONDUCTOR
Cross-Sectional Area ( mm2 )

800

1000

1200

1600

2000

2500

Direct-buried

1018

1135

1306

1457

1607

1758

Pipe

1008

1127

1299

1454

1608

1767

Trefoil

1171

1316

1548

1747

1947

2151

Flat (S=3D)

1412

1608

1876

2130

2403

2679

Cross-Sectional Area ( mm2 )

800

1000

1200

1600

2000

2500

Direct-buried

814

918

1032

1185

1322

1459

Pipe

806

911

1026

1183

1323

1466

943

1071

1227

1429

1614

1804

1131

1299

1479

1732

1974

2221

In Air

HDPE pipe diameter = 2D

ALUMINIUM CONDUCTOR

Trefoil
In Air
Flat (S=3D)
HDPE pipe diameter = 2D

51

HV & EHV Cable Systems

1A

Cross-Sectional
Area (mm2)

800

1000

Circular

Circular

34

39

43,5

49,5

56

63,5

Thickness of Conductor Screen (mm)

1,2

1,4

1,4

1,5

1,6

1,6

Thickness of Insulation (mm)

28

27

27

27

26

26

Thickness of Insulation Screen (mm)

1,2

1,2

1,2

1,2

1,2

1,2

Cu-Screen Cross-Sectional Area (mm2)

185

185

185

185

185

185

Thickness of Lead Sheath (mm)

2,8

2,9

3,2

3,2

3,2

Thickness of Outer Sheath (mm)

4,5

4,5

4,7

4,9

5,2

5,5

Outer Diameter of Cable (mm)

116

120

126

133

141

147

Weight of Cable (kg/m)

27,3

30,2

33,6

39,3

44,6

51

Max. DC Cu Conductor Resistance


at 20C (ohm/km)

0,0221

0,0176

0,0151

0,0113

0,009

0,0072

Capacitance (F/km)

0,138

0,155

0,168

0,183

0,206

0,227

Inductance (mH/km)

0,432

0,411

0,399

0,373

0,367

0,355

800

1000

1200

1600

2000

2500

Circular

Circular

34,8

39

43,5

50,2

56

63,5

0,0367

0,0291

0,0247

0,0186

0,0149

0,0127

22,9

23,7

26,1

29,8

31,7

35,3

CONDUCTOR
(Cu)

Shape
Diameter (mm)

Cross-Sectional
Area (mm2)
CONDUCTOR
(Al)

Shape
Diameter (mm)

Max. DC Al Conductor Resistance


at 20C (ohm/km)
Weight of Cable (kg/m)

1200
Milliken

Milliken

1600
Milliken

Milliken

HV & EHV Cable Systems

2000
Milliken

Milliken

2500
Milliken

Milliken

52

190/330 (362) kV
XLPE Insulated with Lead Sheath

3c

Continuous Current Rating for Single Circuit (A)

COPPER CONDUCTOR
Cross-Sectional Area ( mm2 )

800

1000

1200

1600

2000

2500

Direct-buried

1016

1131

1302

1452

1605

1755

Pipe

1005

1121

1292

1448

1606

1764

Trefoil

1165

1308

1540

1738

1943

2145

Flat (S=3D)

1408

1603

1868

2125

2407

2676

Cross-Sectional Area ( mm2 )

800

1000

1200

1600

2000

2500

Direct-buried

810

915

1029

1181

1322

1460

Pipe

801

906

1020

1178

1321

1467

933

1066

1221

1423

1611

1806

1121

1295

1475

1728

1978

2230

In Air

HDPE pipe diameter = 2D

ALUMINIUM CONDUCTOR

Trefoil
In Air
Flat (S=3D)
HDPE pipe diameter = 2D

53

HV & EHV Cable Systems

Cross-Sectional
Area (mm2)

800

1000

Circular

Circular

34

39

43,5

49,5

56

63,5

Thickness of Conductor Screen (mm)

1,2

1,4

1,4

1,5

1,6

1,6

Thickness of Insulation (mm)

28

27

27

27

26

26

Thickness of Insulation Screen (mm)

1,2

1,2

1,2

1,2

1,2

1,2

3,5

3,6

3,7

3,9

4,1

4,4

4,4

4,5

4,6

4,8

5,2

5,5

114

118

123

130

136

146

27,6

30,6

34,1

39,8

45,6

54,4

Max. DC Cu Conductor Resistance


at 20C (ohm/km)

0,0221

0,0176

0,0151

0,0113

0,009

0,0072

Capacitance (F/km)

0,138

0,155

0,168

0,183

0,206

0,227

Inductance (mH/km)

0,427

0,407

0,394

0,38

0,364

0,353

800

1000

1200

1600

2000

2500

Circular

Circular

34,8

39

43,5

50,2

56,5

63,5

0,0367

0,0291

0,0247

0,0186

0,0149

0,0127

22,8

24,1

26,6

30,4

33,4

38,7

CONDUCTOR
(Cu)

Shape
Diameter (mm)

Thickness of Lead Sheath (mm)


Thickness of Outer Sheath (mm)

Outer Diameter of Cable (mm)


Weight of Cable (kg/m)

Cross-Sectional
Area (mm2)
CONDUCTOR
(Al)

Shape
Diameter (mm)

Max. DC Al Conductor Resistance


at 20C (ohm/km)
Weight of Cable (kg/m)

1200
Milliken

Milliken

1600
Milliken

Milliken

2000
Milliken

Milliken

HV & EHV Cable Systems

2500
Milliken

Milliken

54

220/380 (420) kV

2B

XLPE Insulated with Cu Wire +Al Tape


Continuous Current Rating for Single Circuit (A)

COPPER CONDUCTOR
Cross-Sectional Area ( mm2 )

800

1000

1200

1600

2000

2500

3000

Direct-buried

1006

1120

1287

1434

1583

1730

2004

Pipe

996

1110

1277

1428

1582

1737

2021

Trefoil

1153

1293

1521

1715

1911

2111

2457

Flat (S=3D)

1387

1586

1853

2105

2367

2640

3116

Cross-Sectional Area ( mm2 )

800

1000

1200

1600

2000

2500

3000

Direct-buried

806

906

1017

1166

1302

1436

1640

Pipe

795

897

1008

1161

1301

1440

1652

928

1054

1214

1405

1585

1772

2038

1111

1281

1463

1712

1945

2189

2542

In Air

HDPE pipe diameter = 2D

ALUMINIUM CONDUCTOR

Trefoil
In Air
Flat (S=3D)
HDPE pipe diameter = 2D

55

HV & EHV Cable Systems

Cross-Sectional
Area (mm2)

800

1000

Circular

Circular

34

39

43,5

49,5

56

63,5

71

Thickness of Conductor Screen (mm)

1,8

1,4

1,4

1,5

1,6

1,6

1,6

Thickness of Insulation (mm)

30

28

27

27

27

27

27

1,2

1,2

1,2

1,2

1,2

1,2

1,2

Cu-Screen Cross-Sectional Area (mm )

185

185

185

185

185

185

185

Thickness of Outer Sheath (mm)

4,4

4,4

4,5

4,7

5,1

5,3

5,6

Outer Diameter of Cable (mm)

116

117

120

127

134

143

152

Weight of Cable (kg/m)

17,6

19,2

21,3

25,4

29,9

36

42,7

Max. DC Cu Conductor Resistance


at 20C (ohm/km)

0,0221

0,0176

0,0151

0,0113

0,009

0,0072

0,006

Capacitance (F/km)

0,135

0,151

0,168

0,182

0,2

0,22

0,241

Inductance (mH/km)

0,433

0,405

0,39

0,375

0,362

0,349

0,336

800

1000

1200

1600

2000

2500

3000

Circular

Circular

34,8

39

43,5

50,2

56,5

63,5

71

0,0367

0,0291

0,0247

0,0186

0,0149

0,0127

0,0099

12,7

12,7

13,8

15,9

17,7

20,3

23,4

CONDUCTOR
(Cu)

Shape
Diameter (mm)

Thickness of Insulation Screen (mm)


2

Cross-Sectional
Area (mm2)
CONDUCTOR
(Al)

Shape
Diameter (mm)

Max. DC Al Conductor Resistance


at 20C (ohm/km)
Weight of Cable (kg/m)

1200
Milliken

Milliken

1600
Milliken

Milliken

2000

2500

Milliken

Milliken

Milliken

Milliken

HV & EHV Cable Systems

3000
Milliken

Milliken

56

220/380 (420) kV
XLPE Insulated with Cu Wire +Lead Sheath

1A

Continuous Current Rating for Single Circuit (A)

COPPER CONDUCTOR
Cross-Sectional Area ( mm2 )

800

1000

1200

1600

2000

2500

3000

Direct-buried

1011

1126

1295

1444

1592

1801

2017

Pipe

1003

1199

1289

1441

1595

1812

2039

Trefoil

1166

1310

1539

1737

1936

2205

2490

Flat (S=3D)

1396

1597

1867

2121

2388

2743

3138

Cross-Sectional Area ( mm2 )

800

1000

1200

1600

2000

2500

3000

Direct-buried

808

911

1023

1174

1310

1446

1651

Pipe

802

904

1018

1172

1311

1453

1668

938

1066

1220

1422

1604

1793

2062

1118

1290

1474

1725

1963

2204

2558

In Air

HDPE pipe diameter = 2D

ALUMINIUM CONDUCTOR

Trefoil
In Air
Flat (S=3D)
HDPE pipe diameter = 2D

57

HV & EHV Cable Systems

Cross-Sectional
Area (mm2)

800

1000

Circular

Circular

34

39

43,5

49,5

56

63,5

71

Thickness of Conductor Screen (mm)

1,8

1,4

1,4

1,5

1,6

1,6

1,6

Thickness of Insulation (mm)

30

28

27

27

27

27

27

Thickness of Insulation Screen (mm)

1,2

1,2

1,2

1,2

1,2

1,2

1,2

Cu-Screen Cross-Sectional Area (mm2)

185

185

185

185

185

185

185

Thickness of Lead Sheath (mm)

2,9

2,9

3,2

3,2

3,2

3,2

Thickness of Outer Sheath (mm)

4,6

4,6

4,7

4,9

5,3

5,5

5,8

Outer Diameter of Cable (mm)

122

122

126

133

141

149

158

Weight of Cable (kg/m)

29,1

30,8

33,6

39,3

44,6

51,7

60

Max. DC Cu Conductor Resistance


at 20C (ohm/km)

0,0221

0,0176

0,0151

0,0113

0,009

0,0072

0,006

Capacitance (F/km)

0,135

0,151

0,168

0,182

0,2

0,22

0,241

Inductance (mH/km)

0,442

0,415

0,399

0,384

0,37

0,351

0,344

800

1000

1200

1600

2000

2500

3000

Circular

Circular

34,8

39

43,5

50,2

56,5

63,5

71

0,0367

0,0291

0,0247

0,0186

0,0149

0,0127

0,0099

24,7

24,2

26,1

29,9

32,4

36

40,7

CONDUCTOR
(Cu)

Shape
Diameter (mm)

Cross-Sectional
Area (mm2)
CONDUCTOR
(Al)

Shape
Diameter (mm)

Max. DC Al Conductor Resistance


at 20C (ohm/km)
Weight of Cable (kg/m)

1200
Milliken

Milliken

1600
Milliken

Milliken

2000
Milliken

Milliken

2500
Milliken

Milliken

HV & EHV Cable Systems

3000
Milliken

Milliken

58

220/380 (420) kV
XLPE Insulated with Lead Sheath

3c

Continuous Current Rating for Single Circuit (A)

COPPER CONDUCTOR
Cross-Sectional Area ( mm2 )

800

1000

1200

1600

2000

2500

3000

Direct-buried

1009

1124

1292

1440

1589

1798

2015

Pipe

1000

1115

1283

1437

1590

1808

2036

Trefoil

1161

1303

1532

1729

1929

2200

2487

Flat (S=3D)

1392

1593

1862

2116

2382

2738

3138

Cross-Sectional Area ( mm2 )

800

1000

1200

1600

2000

2500

3000

Direct-buried

805

909

1021

1170

1307

1444

1649

Pipe

799

901

1013

1167

1308

1451

1666

934

1061

1214

1415

1599

1789

2060

1115

1287

1471

1721

1957

2203

2560

In Air

HDPE pipe diameter = 2D

ALUMINIUM CONDUCTOR

Trefoil
In Air
Flat (S=3D)
HDPE pipe diameter = 2D

59

HV & EHV Cable Systems

Cross-Sectional
Area (mm2)

800

1000

Circular

Circular

34

39

43,5

49,5

56

63,5

71

Thickness of Conductor Screen (mm)

1,8

1,4

1,4

1,5

1,6

1,6

1,6

Thickness of Insulation (mm)

30

28

27

27

27

27

27

Thickness of Insulation Screen (mm)

1,2

1,2

1,2

1,2

1,2

1,2

1,2

Thickness of Lead Sheath (mm)

3,7

3,7

3,7

3,9

4,2

4,4

4,7

Thickness of Outer Sheath (mm)

4,6

4,6

4,6

4,9

5,2

5,5

5,8

Outer Diameter of Cable (mm)

120

120

123

131

138

148

158

Weight of Cable (kg/m)

29,9

31,6

34,1

39,9

46,7

55,1

65,3

Max. DC Cu Conductor Resistance


at 20C (ohm/km)

0,0221

0,0176

0,0151

0,0113

0,009

0,0072

0,006

Capacitance (F/km)

0,135

0,151

0,168

0,182

0,2

0,22

0,241

Inductance (mH/km)

0,438

0,411

0,394

0,38

0,364

0,355

0,343

800

1000

1200

1600

2000

2500

3000

Circular

Circular

34,8

39

43,5

50,2

56,5

63,5

71

0,0367

0,0291

0,0247

0,0186

0,0149

0,0127

0,0099

22,8

25,1

26,6

30,6

34,5

39,4

40,7

CONDUCTOR
(Cu)

Shape
Diameter (mm)

Cross-Sectional
Area (mm2)
CONDUCTOR
(Al)

Shape
Diameter (mm)

Max. DC Al Conductor Resistance


at 20C (ohm/km)
Weight of Cable (kg/m)

1200
Milliken

Milliken

1600
Milliken

Milliken

2000
Milliken

Milliken

2500
Milliken

Milliken

HV & EHV Cable Systems

3000
Milliken

Milliken

60

290/500 (550) kV
XLPE Insulated with Cu Wire + Al Tape

2B

Continuous Current Rating for Single Circuit (A)

COPPER CONDUCTOR
Cross-Sectional Area ( mm2 )

800

1000

1200

1600

2000

2500

3000

Direct-buried

983

1095

1255

1354

1537

1754

1933

Pipe

979

1093

1253

1355

1543

1772

1956

Trefoil

1139

1280

1498

1637

1877

2168

2394

Flat (S=3D)

1348

1531

1788

1982

2289

2664

2989

Cross-Sectional Area ( mm2 )

800

1000

1200

1600

2000

2500

3000

Direct-buried

785

885

991

1118

1269

1399

1597

Pipe

782

883

990

1118

1274

1409

1614

915

1041

1186

1359

1560

1741

2004

1079

1236

1412

1635

1897

2122

2470

In Air

HDPE pipe diameter = 2D

ALUMINIUM CONDUCTOR

Trefoil
In Air
Flat (S=3D)
HDPE pipe diameter = 2D

61

HV & EHV Cable Systems

Cross-Sectional
Area (mm2)

800

1000

Circular

Circular

34

39

43,5

49,5

56

63,5

71

Thickness of Conductor Screen (mm)

2,4

2,7

1,6

1,6

1,6

Thickness of Insulation (mm)

33

33

31

30

30

30

30

1,2

1,2

1,2

1,2

1,2

1,2

1,2

Cu-Screen Cross-Sectional Area (mm )

185

185

185

185

185

185

185

Thickness of Outer Sheath (mm)

4,7

4,8

4,8

4,9

5,3

5,6

5,8

Outer Diameter of Cable (mm)

130

134

136

139

147

155

162

Weight of Cable (kg/m)

19,3

21,7

23,5

27

31,7

37,6

43,8

Max. DC Cu Conductor Resistance


at 20C (ohm/km)

0,0221

0,0176

0,0151

0,0113

0,009

0,0072

0,006

Capacitance (F/km)

0,132

0,14

0,158

0,172

0,187

0,204

0,219

Inductance (mH/km)

0,456

0,434

0,415

0,394

0,379

0,365

0,354

800

1000

1200

1600

2000

2500

3000

Circular

Circular

34,8

39

43,5

50,2

56,5

63,5

71

0,0367

0,0291

0,0247

0,0186

0,0149

0,0127

0,0099

14,5

15,4

16,2

17,6

19,3

21,9

24,5

CONDUCTOR
(Cu)

Shape
Diameter (mm)

Thickness of Insulation Screen (mm)


2

Cross-Sectional
Area (mm2)
CONDUCTOR
(Al)

Shape
Diameter (mm)

Max. DC Al Conductor Resistance


at 20C (ohm/km)
Weight of Cable (kg/m)

1200
Milliken

Milliken

1600
Milliken

Milliken

2000
Milliken

Milliken

HV & EHV Cable Systems

2500
Milliken

Milliken

3000
Milliken

Milliken

62

290/500 (550) kV
XLPE Insulated with Cu Wire +Lead Sheath
1A

Continuous Current Rating for Single Circuit (A)

COPPER CONDUCTOR
Cross-Sectional Area ( mm2 )

800

1000

1200

1600

2000

2500

3000

Direct-buried

989

1102

999

1363

1547

1757

1945

Pipe

987

1102

998

1367

1557

1775

1973

Trefoil

1151

1294

1198

1655

1898

2172

2422

Flat (S=3D)

1356

1540

1421

1991

2303

2666

3006

Cross-Sectional Area ( mm2 )

800

1000

1200

1600

2000

2500

3000

Direct-buried

789

891

1263

1126

1277

1408

1607

Pipe

787

891

1264

1129

1284

1421

1628

925

1051

1513

1374

1577

1759

2025

1085

1244

1800

1646

1904

2134

2485

In Air

HDPE pipe diameter = 2D

ALUMINIUM CONDUCTOR

Trefoil
In Air
Flat (S=3D)
HDPE pipe diameter = 2D

63

HV & EHV Cable Systems

Cross-Sectional
Area (mm2)

800

1000

Circular

Circular

34

39

43,5

49,5

56

63,5

71

Thickness of Conductor Screen (mm)

2,4

2,7

1,6

1,6

1,6

Thickness of Insulation (mm)

33

33

31

30

30

30

30

1,2

1,2

1,2

1,2

1,2

1,2

1,2

Cu-Screen Cross-Sectional Area (mm )

185

185

185

185

185

185

185

Thickness of Lead Sheath (mm)

3,2

3,2

3,2

3,2

3,2

3,2

3,2

Thickness of Outer Sheath (mm)

4,9

5,1

5,5

5,8

Outer Diameter of Cable (mm)

137

141

142

145

153

161

168

Weight of Cable (kg/m)

33,6

36,4

38,4

42,3

47,7

54,6

61,5

Max. DC Cu Conductor Resistance


at 20C (ohm/km)

0,0221

0,0176

0,0151

0,0113

0,009

0,0072

0,006

Capacitance (F/km)

0,132

0,14

0,158

0,172

0,187

0,204

0,219

Inductance (mH/km)

0,465

0,443

0,424

0,402

0,388

0,373

0,361

800

1000

1200

1600

2000

2500

3000

Circular

Circular

34,8

39

43,5

50,2

56,5

63,5

71

0,0367

0,0291

0,0247

0,0186

0,0149

0,0127

0,0099

28,8

30,1

31,2

32,9

35,3

38,9

42,2

CONDUCTOR
(Cu)

Shape
Diameter (mm)

Thickness of Insulation Screen (mm)


2

Cross-Sectional
Area (mm2)
CONDUCTOR
(Al)

Shape
Diameter (mm)

Max. DC Al Conductor Resistance


at 20C (ohm/km)
Weight of Cable (kg/m)

1200
Milliken

Milliken

1600
Milliken

Milliken

2000
Milliken

Milliken

HV & EHV Cable Systems

2500
Milliken

Milliken

3000
Milliken

Milliken

64

290/500 (550) kV
XLPE Insulated with Lead Sheath

3c

Continuous Current Rating for Single Circuit (A)

COPPER CONDUCTOR
Cross-Sectional Area ( mm2 )

800

1000

1200

1600

2000

2500

3000

Direct-buried

986

1099

1260

1359

1545

1755

1944

Pipe

984

1099

1260

1362

1554

1772

1972

Trefoil

1146

1289

1507

1648

1893

2168

2419

Flat (S=3D)

1353

1536

1795

1986

2299

2664

3004

Cross-Sectional Area ( mm2 )

800

1000

1200

1600

2000

2500

3000

Direct-buried

787

889

995

1123

1276

1406

1606

Pipe

785

888

995

1125

1283

1419

1628

920

1047

1193

1368

1573

1756

2023

1082

1241

1417

1641

1901

2133

2483

In Air

HDPE pipe diameter = 2D

ALUMINIUM CONDUCTOR

Trefoil
In Air
Flat (S=3D)
HDPE pipe diameter = 2D

65

HV & EHV Cable Systems

Cross-Sectional
Area (mm2)

800

1000

Circular

Circular

34

39

43,5

49,5

56

63,5

71

Thickness of Conductor Screen (mm)

2,4

2,7

1,6

1,6

1,6

Thickness of Insulation (mm)

33

33

31

30

30

30

30

Thickness of Insulation Screen (mm)

1,2

1,2

1,2

1,2

1,2

1,2

1,2

Cross-Sectional Area (mm2)

3,7

3,8

3,8

3,9

4,3

4,5

4,7

Thickness of Outer Sheath (mm)

4,8

4,9

4,9

5,1

5,5

5,7

Outer Diameter of Cable (mm)

134

138

140

143

151

160

168

Weight of Cable (kg/m)

CONDUCTOR
(Cu)

Shape
Diameter (mm)

1200
Milliken

1600
Milliken

2000
Milliken

2500
Milliken

3000
Milliken

33,5

36,8

38,9

43,3

50,9

59

67,4

Max. DC Cu Conductor Resistance


at 20C (ohm/km)

0,0221

0,0176

0,0151

0,0113

0,009

0,0072

0,006

Capacitance (F/km)

0,132

0,14

0,158

0,172

0,187

0,204

0,219

Inductance (mH/km)

0,461

0,44

0,42

0,399

0,386

0,371

0,360

800

1000

1200

1600

2000

2500

3000

Circular

Circular

34,8

39

43,5

50,2

56,5

63,5

71

0,0367

0,0291

0,0247

0,0186

0,0149

0,0127

0,0099

28,8

30,5

31,6

34

38,4

43,3

48,1

Cross-Sectional
Area (mm2)
CONDUCTOR
(Al)

Shape
Diameter (mm)

Max. DC Al Conductor Resistance


at 20C (ohm/km)
Weight of Cable (kg/m)

Milliken

Milliken

Milliken

HV & EHV Cable Systems

Milliken

Milliken

66

67

HV & EHV Cable Systems

1.70

Quality Control

High and Extra High Voltage Cable production requires


highest possible precision at manufacturing stage, similar
capable Quality Control experience and equipments in
order to achieve best quality.
Being aware of this fact Demirer Kablo gives utmost
importance to Quality Control, therefore continuously
making remarkable investments to state of the art testing
equipments as well as following up of new technologies
and keeping Q.C. personnel highly trained.
High quality raw material is the prerequisite for high quality
finish product therefore Demirer kablo uses only reputable
suppliers.
Some of our Quality Control Equipments and their
purpose are listed below in three Categories:

1.Quality Control Equipments:


a CSS2 Cleanliness Scanning System which detects
a.
any particulars prior to extrusion (x-head), warns, and
keeps image of the particular.
b Sikora X-Ray 8000 Wall thickness measuring device
a.
scans hot wall thicknesses and eccentricity of three layer
and warns if tolerance exceeded.

c.
c IPEC Ultrasense Ultrasound Flaw Detection
detects any bubble or protrusion penetration, measures
cold wall thicknesses of three layers, warns if tolerances
exceeded and keep log for future checking.
d Sikora X-Y Diameter Gauge measures cold diameter
a.
from both axis.

HV & EHV Cable Systems

68

Quality Control
2. High Voltage Test Equipment
a

69

1.050 kV 22.500 kVA AC Test System capable of


I. Long term High Voltage Tests
II. System Type Tests
III. AC Step Voltage Tests
Impulse Test System
2.400 kV 120 kJ Lightning Impulse 1.540, + 1.050 Switching Impulse
I. Lightning & Switching Impulse Voltage Tests
500 kV 20.000 kVA AC Resonant Test System
Partial Discharge Dedector
I. High Voltage Tests
II. Partial Discharge Tests
350 kV 4.000 kVA AC Resonant Test System
Partial Discharge Dedector
I. High Voltage Tests
II. Partial Discharge Tests

HV & EHV Cable Systems

Impulse Test System


1.400 kV 42 kJ Lightning Impulse
I. Lightning Impulse Voltage Tests

150 kV 125 kVA AC Dielectric Test Set


I. Long Term Voltage Tests
II. Type Tests

525 kV 3 kW DC Test System


I. DC Voltage Tests
II. Site Tests

Schering Bridge
I. Tan Measurement
II. Capacitance Measurement

Cable Heating Test System


I. Heating Cycle Voltage Test
II. Water Penetration Tests

Quality Control
3. Non-Electrical Test Equipment
a

Moisture Content (two spaces) Measuring Device


I. Insulation and SC materials moisture content measurement

Fourier Transform Infrared Spectrometer (FTIR)


I. Spectral Analysis of Insulation and Sheath materials

Thermogravimetric Analyzer (TGA)


I. Insulation and sheath materials
By product concentration
OIT
Carbon Black Measurements

Thermal Analysis Equipment & DSC


I. Insulation, sheath and various materials
Thermal Analysis
Melting Point Measurements

Digital Microohm-meter
I. DC Resistance Measurement

Optical Thickness Measuring Systems


I. Thickness Measurement

Flame Spread Test Cell


I. Flame Spread Test

Smoke Density Test Room


I. Smoke Density Test

Universal Test System


I. Tensile strength and elongation measurements

HV & EHV Cable Systems

70

1.80

Cable Accessories

Straight and Insulated Joints.


Porcelain and Composite type of Outdoor Terminations.
GIS and Transformer Terminations(oil-type and dry-type)
Link Boxes for Direct Earthing and Cross-Bonding Connections.
DTS (Distributed Temperature Sensing) Systems with integrated
optical fibre in metallic tube or with seperated FO cable fixed
over power cables.

71

HV & EHV Cable Systems

Site Services
Underground power cable lines are installed commonly inside modernized cities due toexistence of
highway crossings, bridges and many sophisticated
buildings. Underground power cable installation
enables non-disturbance of existing structures. XLPE
power cable technology provides a long-term reliable
system which does not require maintenance.
DEMRER KABLO well trained technical team is
capable of organizing, carrying out and performing
the tests of all kinds of HV XLPE cable projects
between 60 kV and 400 kV allaround the world.

Our Services
1) Supply and installation of XLPE underground
2) Supply and installation of power cable accessories
3) System design of power cable & FO cable systems
4) Project management.
5) Power cable installation civil works
6) Installation of power cable accessories, supervision, testing & commissioning
7) Fault location & cable repair
8) Training of customer personnel

HV & EHV Cable Systems

72

1.90

Cable System Configurations

Both-End Bonding
Cable Terminations

Cable Terminations

This system is mostly designed for short


length of circuits. A current continuously flows
on the metallic screen because both ends are
earthed.
It will automatically reduce the current carrying
capacity in the conductor of cable while it
provides no touching voltage at both ends.
This is a common method for the short lengths
of open switchyards and transformer circuits.

Direct
Earthing

Direct
Earthing
Conductor

Metallic Screen

E(V)
Induced
Voltage

Direct Earthing

Single-Point Bonding

Cable Terminations

Direct Earthing

Cable Terminations

Direct Earthing

This system is designed to prevent circulation


currents on the metallic screen of the cable.
This increases current carrying capacity of the
cable directly. Induced voltage over metallic
screen on the cable is proportionalto the cable
length and the current passing through the
conductor. Single-Point Bonding Method can
only be used for limited route lengths. Maximum length is limited by the screen voltage
induced at the open end (SVL side).

SVLs

Direct
Earthing
Conductor
Induced
Voltage

E(V)

Direct Earthing

73

HV & EHV Cable Systems

L(m)
(Distance)

Metallic Screen

Parallel Earthing
Conductor

L(m)
(Distance)

Cross Bonding
Cable Terminations

Cable Terminations

Cross-Bonding Method is commonly used for


long lengths of circuits to balance the
Impedances of the phases for flat formation
and to minimize the induced voltages occured
on the metallic screens of the cables at the
same time.
Transposition equalizes the impedances while
the cross-bonding connections made in the
link boxes minimize the induced voltages.
A current flowsthrough the metallic sheath
connections, but no significant current flows
through the screens.

Direct Earthing

SVL

Direct
Earthing
Conductor

Minor Section Minor Section Minor Section

Metallic
Screen

Direct
Earthing

Minor Section

Induced
Voltage

E(V)

Cross-bonding
points

Direct Earthing
point

/3

/3

Direct Earthing
point

/3

HV & EHV Cable Systems

(Distance)

L(m)

74

Designed and Printed by UANADAM


www.ucanadam.com

Head Office

: Barbaros Bulvar 59 Preveze Han


34353 Beikta - stanbul / TURKEY
Tel
: +90 (212) 261 51 63 Pbx
Telefax : +90 (212) 258 16 56
e-mail : export@masscable.com

www.masscable.com

Factory : Yaft Mevkii


Bozyk / TURKEY
Tel
: +90 (228) 314 28 00 Pbx
Telefax : +90 (228) 314 28 08
e-mail : factory@masscable.com

Vous aimerez peut-être aussi